abb manual st7 eng

16
Operating Manual 1YMS603002-en Outdoor modular transformer substation type ST7 with 35/6 kV oil or dry type transformers, and complete switchgear 35 and 6(10) kV type SPY

Upload: puiu-tiganasu

Post on 25-Nov-2015

177 views

Category:

Documents


5 download

DESCRIPTION

catalog

TRANSCRIPT

  • Operating Manual 1YMS603002-en

    Outdoor modular transformer substation type ST7with 35/6 kV oil or dry type transformers,and complete switchgear 35 and 6(10) kV type SPY

  • 2 ABB

    Table of contents

    1. Introduction1.1 Substation applications1.2 Operation conditions31.3 Conforms to standards

    2. Substation technical documentation2.1 Single-line diagram2.2 Substation components2.3 Spare parts

    3. Technical specifications and main equipment3.1. Complete 35 kV switchgear block

    4. Substation secondary circuits

    5. Substation design

    6. Advantages of the substation

    7. Installation of control cables between blocks

    8. Substation protection from atmospheric surges

    9. Transport9.1 Railway transportation9.2. Road transportation9.3. Transportation on the substation own skids9.4 Fixing substation blocks on transport platforms

    10. Substation assembly and setting up10.1 Preparation of the site10.2.Substation assembly10.3 Visual inspection of the devices and apparatus10.4 Mechanical tests10.5 Earthing resistance measurement10.6 Electrical measurements

    11. Commissioning

    12. Operation

    13. Periodical inspections, overhauls and maintenance

    NOTE!The following documents should be included with this manual:

    COMPLETE SWITCHGEAR TYPE SPYfor 12 kV rated voltage and up to 3150 A rated current, with vacuum circuit-breakers type VD4Technical description and operation instructions

    COMPLETE SWITCHGEAR TYPE SPYfor 35 kV rated voltage and up to 3150 A rated current, with vacuum circuit-breakers type VD4Technical description and operation instructions

  • 3ABB

    1. Introduction

    1.1 Substation applications(Fig. 1 and 2)

    The ST7 transformer substation with oil or dry type trans-formers for rated power from 2,500 kVA to 16,000, is de-signed to supply 3-phase, 6(10) kV, 50 Hz high voltagepower to the power consuming objects.The substation power supply is 35 kV (two overhead 35 kVlines), and the power distribution (converted by powertransformer) is 6(10) kV.The type ST7 substation is designed in particular to supplypower to oil, gas and other installations (group pumpplants, drilling and mining).This manual contains general technical specifications of thesubstation, operation conditions, list of components, con-cise design description, list of instruments and equipment,packaging and transport information, and practical recom-mendations regarding installation, setting up, adjustment,service and maintenance.To understand this documentation you should refer to oper-ating documentations of the substation components.When operating the substation, apart from this document,you should follow your national regulations: Work safetyin power systems, and Power system installation regula-tions.

    1.2 Operation conditionsNormal substation operation is guaranteed when observingthe following climate conditions:- Ambient temperature between 55C and +40C.- Relative humidity at +20C below 90%- Max. substation installation altitude below 1000 m- Max. thickness of icing 20 mm at the wind speed of up to

    38 m/sec.

    1.3 Conformity to standardsThe transformer substation type ST7 conforms to interna-tional IEC standardsand the requirements of GOST 1516.3 standard regardinglightning impulse test voltage and power frequency voltagefor 35 kV and 6(10) kV.

    2. Technical documentation of the substation

    2.1 Single-line diagramThe substation type ST7- 35/6 kV single-line diagram withoil or dry type transformers is shown in the complete set ofthe substation diagrams.

    2.2 Substation componentsThe substation consists of the following functional modules: 35 kV switchgear block (Fig. 3) Two oil or dry type transformer blocks 35/6 kV,

    2,500 kVA, 4,000 kVA, 6,300 kVA, 10,000 or 16,000 kVA,with manual or automatic voltage regulation on the 35 kV ide

    6(10) kV switchgear block (Fig. 4), with vacuum circuit-breaker type VD4 in withdrawable version, consisting oftwo 6 kV sections, arranged in two-row design, in two or

    three block segments (depending on the substationsingle-line diagram). Segments are transported separatelyand joined together on site.

    Components for connection of blocks with detailedinstallation instructions.

    2.3 Spare partsThe delivery includes a full spare parts kit, work safety ac-cessories, and mounting equipment as agreed duringcontract preparation.

    3.Technical specifications and main equipment

    3.1. Complete 35 kV switchgear block(Fig 3) consists of two separately transported segments,joined together on site of substation destination.

    3.1.1 General specifications:Rated voltage ...............................................................35 kVRated frequency ...........................................................50 HzRated current of busbars .............................................630 Rated short time current, 1s...........................................16 kRated peak withstand current.......................................40 k

    35 kV circuit-breaker type: vacuum circuit-breaker typeVD4 with spring/motor drive

    3.1.2 Main parts of the 35 kV switchgear:- 35 kV switchgear (item 1.1) with 35 kV / 1250 A vacuum

    circuit-breakers type VD4;- 3-pole switch-disconnectors type -2-35/10001

    (item 1.2) with manual drive type -5-21 or type-00-21 (item 1.6) equipped with mechanicaland electromagnetic interlocks and latching contacts forindication system.

    - GXD51 (item 1.3) surge arresters for 40.5 kV operatingvoltage, and 10 kA nominal discharge current;

    - Surge arrester operation counters type GLKA (item 1.4)(one piece per each phase);

    - 35000:v3/100:v3/100:3V voltage transformers, built intothe busbars of the bus coupler and bus riser panel,separately for each section of the complete measuringmodule.

    3.1.3 Primary block circuitsFor the primary circuits, each section of the 35 kV blockconsists of the following panels: 35 kV incoming line feeder with equipment located on

    the block roof (substationary outdoor version) The panelis equipped with the following (see Fig. 3):- 3-pole switch-disconnector type -2-35/10001

    (35 kV/100 A) (item 1.2), equipped with two earthcontacts,

    - manual drive type -05-21 (item 1.5) for theswitch-disconnector, with built-in latching contacts forindication of position and earthing switch, and withmechanical and electrical interlocks;

    - surge arresters type GXD 51 (item 1.3) with operation

  • 4 ABB

    counters type GLKA (item 1.4), one piece per eachphase;Surge arresters type GXD 51, to provide properoperation of the surge arrester operation counters, areisolated from the framework of the block with supportinsulators for a voltage of 1 kV.Connection of the 35 kV line to the substation isperformed through the power supply terminals (item1.6), fixed to the 35 kV support insulators (item 1.7).

    35 kV bus coupler panel with circuit-breaker type VD4in indoor, withdrawable version. The panel is equippedwith the following:- 35 kV (35 kV, 1250 A, 25 kA) withdrawable vacuum

    circuit-breaker type VD4- 300/5/5 A current transformers (other rated currents

    are available)- voltage transformers type VEN-36-14 with built-in

    fuses type 17CAV, 36 kV, 2 A. 35 kV bus riser panel

    The panel is equipped with the following:- 35 kV withdrawable busbar disconnector- voltage transformers type VEN-36-14 with built-in

    fuses type 17CAV, 36 kV, 2 A. 35/6 kV power transformer panel with vacuum circuit-

    breaker (indoor version, withdrawable).The panel is equipped with the following:- 35 kV (35 kV, 1250 , 25 kA) withdrawable vacuum

    circuit-breaker type VD4- xxx./5/5 A current transformers, one per each phase.

    (Primary current of the current transformers dependson the power of the power transformer)

    Auxiliary transformer panelThe panel is equipped with the following:- 35/0.231 kV, 100 kVA dry type transformer- 36 kV disconnector with 36 kV fuses

    Detailed information on the use of the 35 kV panelscan be found in the technical description the SPY-35switchgear operating instructions.

    3.2 Power transformer blockThe substation uses a 35/6 kV power transformer oil or drytype, with the power of 2,500 kVA, 4,000 kVA, 6,300 kVA ,10,000 kVA or 16,000kVA with the following features:- manual voltage adjustment on the 35 kV side, after

    disconnection of 35 kV and 6 kV power, or- onload automatic voltage adjustment

    3.3 6(10) kV switchgear block (Fig. 4)The 6(10) kV switchgear block consists of two or three seg-ments (depending on the single-line electrical diagram ofthe substation), separately transported and joined on site.

    3.3.1 General specifications:- rated voltage.........................................................6(10) kV- operating voltage................................................7.2(12) kV- rated current of busbars.................................up to 3150 A- rated short time current, 1s......................................20 kA- rated peak withstand current....................................50 k- number of overhead and cable outgoing lines.........12 pcs.- vacuum circuit-breaker type.......................................VD4

    3.3.2 The complete switchgear type SPY consists of the following 6(10) kV panels:

    - two incoming panels- two voltage transformer panels- from six to nine outgoing panels for overhead or cable

    lines in section one- from six to nine outgoing panels for overhead or cable

    lines in section two- two busbar coupler circuit-breaker panels (with circuit-

    breaker and disconnector in each section adequately)- two capacitor battery panels- two capacitor batteries from 600 up to 1200 kVArDetailed information on the use of the 35 kV panels can befound in the technical description the SPY-6 switchgearoperating instructions.

    3.3.3 Basic equipment of the 6(10) kV primary circuitspanel consist of the following:

    - three-pole vacuum breakers type VD4, 12 kV, 630 or1250 A in withdrawable version

    - current transformers type IMZ10, 12 kV- truck with voltage transformers in epoxy insulation type

    UMZ12-1, 6000:3/100:3/100:3V, 100 V, with fuses- outdoor surge arresters type GXD10 for 8 kV operating

    voltage and 10 kA discharge current- indoor surge arresters type GXR8 for 6.4 kV operating

    voltage, 10 kA discharge current (in 6(10) kV outgoinglines)

    - power fuses type WBP-6 for protection of voltagetransformers.

    Each 6(10) kV panel is equipped with secondary circuitcabinet for control measurements, indication andtelemechanics.

    4.Substation secondary circuitsThe substation secondary circuits are made according tothe substation electrical diagrams. Detailed description ofall functions of secondary circuit diagrams is included in thefollowing documents:1. OUTDOOR TRANSFORMER SUBSTATION type ST7

    with 35/6 kV oil type transformers for the power of.kVA, with 35 kV and 6(10) kV vacuum circuit-breakers,and with a complete switchgear type SPY.Electrical diagrams of primary and secondary circuits.Telemechanics.

    2. The technical documentation for the substationmicroprocessor device providing measurement, automatics,remote control and switchgear protection. Operatorsmanual.

    5.Substation design

    5.1 The equipment and construction elements of eachsubstation block are placed on separate skids and fixedusing bolts.The skids are designed to be moved using a caterpillartractor or lifted by a crane, and placed on a transport platform.

  • 5ABB

    5.2 Connections of the substation primary circuits aremade with copper bars. Earthing connections are madewith Zinc plated flat bars or copper bars.

    5.3 Connections of the substation secondary circuitsand connections between individual blocks are made usinginsulated copper wires or multi-conductor cables.Bars for connection of individual blocks, multi-conductorcables for power, control and indication connections be-tween blocks are supplied with the substation.

    5.4 The 35 kV switchgear block consists of two, and the6(10) kV block of two or three segments, designed likeprefabricated kiosks, joined together on site. Each kiosk ofthe prefabricated block of the 35 kV and 6(10) kVswitchgear is equipped with double, water-proof roof, andexternal walls with thermoinsulation. Both gable walls,joined together during assembly of the block, are closed fortransport with removable boards, protecting the kiosks in-ternal equipment from atmospheric influences.Kiosks joints are sealed during assembly of the substation.The necessary external design elements of the block aredelivered as complete set along with the substation equipment.Every block of the 35 kV and 6(10) kV switchgears pro-vides a service corridor with two entrances.

    5.5 High voltage panels of the 35 kV block withvacuum circuit-breaker and section disconnector are deliv-ered in withdrawable version.All HV panels of the 6(10) kV switchgear block, except thecapacitor battery cabinet, are delivered in withdrawable version.Panels with withdrawable parts are fitted with mechanicaland electrical interlocks designed to prevent:- withdrawing of the truck with HV circuit-breakers into the

    service or testing position with closed circuit-breaker;- closing the circuit-breaker before locking the truck in

    service or testing position;- closing the earthing switch before moving the truck out to

    the testing position;- moving the truck into the service position with earthing

    switch on;

    5.6 All metal parts of the substation are earthed to themetal skid framework. Each skid provides two earthingbolts for connection of the external earthing circuit.

    5.7 The substation steel structure is made of Al/Znplated steel sheet and painted.

    5.8 Busbars and HV bar connections are painted withthe following color paints:- yellow phase A,- green phase B,- red phase C,- black earth and earthing bolt heads.

    5.9 The substation also provides:- service corridor lighting,- lighting of individual LV compartments of panels,- substation external lighting.

    5.10 Enclosure of the kioskThe enclosure of each 35 kV and 6 kV kiosk consists ofthe following elements:- bottom,- side walls,- roof.

    5.10.1 Kiosk bottomThe kiosk bottom is made as a carrying frame filled withthermoinsulation material, and allowing to join the block skids.The carrying framework has welded terminals marked with earthsign for connection of the substation external earthing circuit.All the 35 kV panels, 6(10) kV panels, auxiliary transform-ers, 110 V= and 220 V/50 Hz equipment cabinet, are joinedto this frame, according to the single-line diagram.The kiosk bottom is fitted with special towing hooksmounted into the skids, used to lift the block for transportand to set it in the destination position.Blocks are lifted using a special traverse with ropes, sup-plied with the substation blocks.

    5.10.2 Side wallsEach side wall consists of a carrying frame and steel inter-nal and external cover sheets, with thermoinsulation mate-rial between them.Doors with protective roofs are mounted in the side walls,allowing to enter the substation service corridor and accessthe internal equipment for service and maintenance. Thecorridor entry doors are equipped with door-locks. Thedoors provide eyelets and padlocks for sealing the substa-tion. Other doors to the service corridor are also equippedwith PANIC type door locks to provide safety of the sub-station personnel, and allow to open the door from inside.The side doors that provide access to the MV transformercompartment, panel bars with circuit-breaker and 35 kVcoupler busbar or MV transformer, are locked with specialpull-locks and triangular head bolts, engaged using specialkeys.

    5.10.3 Roof of the kioskThe roof consists of a carrying frame and steel internal andexternal cover sheets, with thermoinsulation material be-tween them.The roof protects the block interior from atmospheric influences.Supporting structures and 35 kV input panel primary circuitequipment are mounted to the 35 kV block roof. The com-plete 35 kV bushing insulators are mounted to the blockroof, after removal of the transport cover. Use new sealswith this operation.Support structures and 6(10) kV surge arresters aremounted to the 6(10) kV block roof.The complete 6(10) kV bushing insulators with metal cov-ers are mounted on the roof of 6(10)kV kiosk, after removalof the transport cover. Use seals with this operation.

    6.Advantages of the substation

    Dimensions and transport weight of the completely assem-bled 35 kV and 6(10) kV blocks allows to deliver them byrail, truck or by ship.

  • 6 ABB

    All individual substation blocks are designed for movingthem on their own skids.The distance between skids along the substation axis is1880 mm, and skid width is 400 mm.On the site of destination the substation can be mounted on:- special platform or concrete foundation, at the proper

    level to provide protection from flood or snowdrifts(see Fig. 5 and 6),

    - directly on flattened and dried land.The block unit pressure on the ground is below 5 N/cm2.The substation type ST7 is designed for operation withoutnecessary presence of the substation operating personnel.The installed (inside the blocks) automatic temperature andhumidity control systems guarantees normal operating con-ditions (Ambient temperature between 55C and +40C)for the primary and secondary circuit indoor equipment.

    The substation is designed to co-operate with remote con-trol and service systems (telemechanics) in the followingscope:- performing On/Off cycles of the 35 kV and 6(10) kV

    circuit-breakers,- applying interlocks to the individual automatic systems- indication of warning and emergency conditions at the

    substation- indication of 35 kV and 6(10) kV circuit-breaker operating

    positions- indication of improper heating operation- measurement of electrical values- fire indication system.The secondary AC and DC current devices are suppliedfrom auxiliary power transformer, and do not require anyadditional supply from secondary circuits.All protection, automatics, control, measurement and indi-cation systems are performed using different types of inte-grated microprocessor devices built into the LV panel cabi-net, depending on the electrical diagrams. Detailed descrip-tions of all the substation secondary circuits are includedwith the substation electrical diagrams.The substation provides earthing for any part of the primarycircuits with power off, using substationary earths. Simulta-neously, the substation performs earthing interlock of theparts of primary circuits with power on.Switching operations using the 35 kV switch-disconnectorincoming panel are performed outside of the block, withmanual drive fixed to the side wall of the block.Switching operation using the 35 kV and 6(10) kV couplercircuit-breaker are performed from the service corridor orby means of telemechanic systems (see substation electri-cal diagrams).The cabinets and 110 V= and 220 V, 50 Hz secondary de-vices are accessed and serviced from the substation serv-ice corridor.Insulation of secondary circuits air or solid/air.Overhead power line panels are equipped with support in-sulators and bushing insulators.Indoor outgoing panels are equipped with epoxy supportinsulators and bushing insulators.High arc protection sensitivity, internal arc detection andisolation system, and immediate pressure reduction system

    make the 35 kV and 6(10) kV blocks of the ST7 substationsafe for personnel and resistant to internal arc faults.Complete factory assembling of primary and secondarycircuits reduces time of site assembly, which is limited tothe mounting of the 35 kV blocks, support structures and35 kV incoming panel equipment, dismantled before han-dling for transport. The assembly on site also requires con-nection of 35 kV and 6(10) kV block secondary circuits,connection of telemechanics concentrator (not included inthe delivery), connection of the substation to the 35 kVoverhead lines, insertion and connection of 35/6 kV powertransformer primary and secondary circuits (supplied by theclient).Design solutions, construction materials and anti-corrosioncoatings guarantee many years of reliable operation of thesubstation, even in harsh natural environments.

    7. Installation of control cables between blocksInstall the designed cables and optical cables for connec-tion of block secondary circuits in a special, sealed cableduct, supplied with the substation blocks.Fix the duct to the block base. Duct length (number of seg-ments) can be determined on site; it depends on the dis-tance between blocks.

    8.Protection of the substation fromatmospheric lightining discharge

    Protection from atmospheric lightining discharges comingover the 35 kV overhead lines is provided by GXD51 surgearresters, installed in three phases from the side of 35 kVsubstation income see Fig. ST7-05/03-01. The GXD51surge arresters are installed on the substation block roof,and are equipped with operation counter mounted outsidethe side wall of the 35 kV block.GXD51 surge arresters and cables from the arresters to theoperation counters are isolated from the block structureusing 1 kV support insulators.Protection of the substation and the near power lines fromthe lightning discharges should be made according to thelocal regulations.

    9.TransportDimensions and weights of individual 35 kV and 6 kVblocks allow them to be transported using railway, truck andwater transport means.The 35 kV and 6 kV blocks are also designed to be movedon their own skids.Skid distance is 1880 mm, skid width is 400 mm.The block unit pressure on the ground is below 5 N/cm2.Loading of the blocks onto the transport platforms is per-formed with a crane of the proper capacity, using a specialtraverse with ropes, supplied with the substation blocks2) Disassembled devices should be placed inside the serv-ice corridor or in additional wooden boxes. Detailed de-scription of all packaging can be found in PACKAGING TRANSPORTATION Instructions, found on each piece of adelivery.

  • 7ABB

    9.1 Railway transportationUse a crane with proper capacity to load the substationonto the rail cars. Lifting of blocks is allowed only using aspecial traverse with ropes, supplied with the substationblocks, and only using special hooks in the block base,marked according to standards.

    9.2. Road transportationTransportation of the substation on the road can be per-formed using special transport platforms.Lifting of blocks is allowed only using a special traversewith ropes, supplied with the substation blocks, and onlyusing special hooks in the block base, marked according tostandards.

    9.3. Transportation on the substation own skidsThe substation blocks are designed to be moved on theirown skids at short distances, on ground roads, with thespeed of up to 20 km/h.

    9.4 Fixing substation blocks on transport platformsTo prevent longitudinal movement of the block on the trans-port platform place wedges on both ends of the skids, andsecure the wedges with an additional supporting beam.Lateral movement of the block on the platform is preventedby beams fixed along each skid.Wedges and beams should be made of wood, and fixedwith proper nails to the platform floor.

    10. Substation assembly and setting up

    10.1 Preparation of the siteEach time, before installing the substation in a new place,prepare the site in the following way:- level and dry the area or built a special platform, or drive

    proper piles into the ground- install protective and operating earthing circuits- set the supporting structure of 35 kV and 6 kV overhead

    lines- build an external fence around the substation site (fence

    elements are not supplied).

    10.2.Substation assemblyAssemble the substation in the following order:- set substation blocks as indicated in the Fig ST7-05/03-02- mount the 35 kV incoming panel in the space provided,

    according to the Fig. ST7-05/03-01 and Fig. 3- assemble the 6 kV switchgear block- assemble the 35/6 kV power transformer block- mount external protection elements of secondary circuit

    block interconnections- connect secondary circuits between blocks according to

    the electrical diagrams- make settings of the secondary microprocessor device

    for protection, control, measurement and automatics- connect the substation to the telemechanics system- insert the 36 kV, 3.15 A fuses that protect the MV auxiliary

    transformer and the fuses that protect the 35 kV and 6 kVvoltage transformers

    - connect the substation blocks to the external earthing circuit

    10.3 Visual inspection of the devices and apparatusWhen the assembly is finished, perform the following:- make sure the assembly was properly made- tighten bolts for equipment mounting and supporting structure- carefully clean all substation components to restore

    proper insulation- repair all damages of the anti-corrosion coatings caused

    by transport- perform inspection of the earthing equipment- remove all foreign items from the substation blocks- check for presence of 36 kV fuses in voltage transformer

    protection

    10.4 Mechanical testsPerform the following:- set the 35 kV and 6 kV circuit-breaker type VD4 and its

    drive according to the Instructions of installation andoperation of circuit-breaker type VD4

    - test the operation of the 35 kV switch-disconnectors ofincoming panels, paying special attention to the properoperation of the operating drive and earthing switch,according to the instructions

    - test operation of the 35 kV switch-disconnectors andtheir drive that protects the MV transformer, payingspecial attention to proper operation of the operatingblades, according to the apparatus instructions

    - test the 35 kV and 6 kV circuit-breakers for proper operation- test all interlocks for proper operation

    10.5 Earthing resistance measurementUse technical method of earthing resistance measurement.The value of the resistance should meet the requirementsgiven in local regulations.

    10.6 Electrical measurementsPerform the following:- test the electrical strength of main circuit insulation or its

    fragments. The value of the resistance should meet therequirements given in national regulations.

    - test the electrical strength of the secondary circuit insulationor its fragments. The value of the resistance should meetthe requirements given in national regulations.

    - perform inspection of all secondary circuit connections inall blocks and substations.

    11. CommissioningWhen all works, measurements and tests are successfullyperformed, connect the 35 kV overhead lines.Perform the commissioning of the substation in accordancewith all your country regulations and procedures.

    12. OperationOperation and maintenance of the substation should beperformed by properly trained personnel, in accordancewith the contents of this manual, and especially with na-tional regulations regarding HV equipment operation.

  • 8 ABB

    13. Periodical inspections, overhaulsand maintenance

    General inspection of the substation and installed equip-ment should be performed during every visit of the operat-ing personnel, and also:- after automatic switch off caused by a fault current- in case of detection of short circuit of one phase to

    the ground- after severe storms and lightning in the substation

    neighborhood.When planning a general overhaul perform the followingsteps:- create a plan of the overhaul- obtain all the necessary instruments, spare parts

    and materials- instruct the overhaul team.During the overhaul:- perform the overhaul according to the plan- clean the insulators and insulation materials- check bolt joints- check interlock mechanisms- check HV apparatus and their connections- check secondary circuit equipment and connections.

    NOTEInspections and overhauls should be performed at intervalsindicated by the manufacturers of the equipment installed inthe substation, unless the national regulation requireshorter periods for specific apparatus.

  • 9A

    BB

    1 35 kV block2 35/6 kV power transformer block3 35/6 kV power transformer block4 6 kV block5 Busbar bridge 35 kV to the power transformer6 Busbar bridge 35 kV to the power transformer7 Busbar bridge 6 kV to the 35/6 kV power transformer 4000 kV8 6 kV incoming busbar bridge9 6 kV overhead line entry10 Busbar bridge 35 kV to the 35/6 kV power transformer11 6 kV cable connection compartment

    Fig. 1 General view of the transformer substation type ST7:A) with oil and air transformers and with cable outgoing linesB) with dry transformers and cable outgoing lines

  • 10A

    BB

    1 35 kV block No.12 35 kV block No.23 Transformer block No.14 Transformer block No.25 6 kV block No.16 6 kV block No.2

    Fig. 2. General view of the transformer substation type ST7: top view

  • 11A

    BB

    1.1 35 kV switchgear panel1.2 35 kV switch disconnector1.3 35 kV surge arrester1.4 Surge arrester operation counter1.5 Switch disconnector drive1.6 Line terminal1.7 Support insulator

    Fig.3 35 kV block of the substation type ST7

  • 12A

    BB

    4.1 Outgoing overhead line panel4.2 Outgoing cable line panel4.3 Service corridor4.4 6 kV incoming busbar bridge4.5 support structure for 6 kV overhead line.

    Fig.4 6(10) kV block of the substation type ST7

  • 13A

    BB

    1 35 kV block no. 12 35 kV block no.23 Transformer block4 6 kV block5 Supports pillars

    Fig.5 ST7 substation block arrangement plan with oil transformers

  • 14A

    BB

    1 35 kV block no. 12 35 kV block no. 23 Transformer block4 6 kV block5 Supports pillars

    Fig. 6 ST7 substation block arrangement plan with dry transformers

  • 15ABB

  • ABB Sp. z o.o.Branch Warsawul. Zegaska 1,04-713 WarsawPoland

    1YM

    S60

    3002

    -en

    Pub

    licat

    ion

    09.2

    004