a study on the operational stability of a refrigeration system having a variable speed compressor
TRANSCRIPT
![Page 1: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/1.jpg)
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 4
www. i ifi i r .org
ava i lab le at www.sc iencedi rec t .com
journa l homepage : www. e lsev ier . com/ loca te / i j re f r ig
A study on the operational stability of a refrigeration systemhaving a variable speed compressor
Yiming Chen, Shiming Deng*, Xiangguo Xu, Mingyin Chan
Department of Building Services Engineering, The Hong Kong Polytechnic University, Kowloon, Hong Kong SAR, China
a r t i c l e i n f o
Article history:
Received 7 January 2008
Received in revised form
14 April 2008
Accepted 21 April 2008
Published online 10 May 2008
Keywords:
Refrigeration system
Compression system
Compressor
Variable speed
Experiment
Superheating
* Corresponding author. Tel.: þ852 2766 5859E-mail address: [email protected] (S.
0140-7007/$ – see front matter ª 2008 Elsevidoi:10.1016/j.ijrefrig.2008.04.012
a b s t r a c t
The increased use of variable speed compressors (VSC) in refrigeration systems can poten-
tially lead to the unstable operation when compressor speed is varied from time to time for
capacity control. The causes of unstable operation may be classified into two groups, one
relating to control algorithms and the other to the inherent characteristics of systems. This
paper reports on a study on the operational stability of a VSC refrigeration system due to its
inherent characteristics. Based on experimental results, a new modified minimal stable su-
perheat (MSS) line having a maximum MSS value and a minimal MSS value has been pro-
posed. Using the modified MSS line, and supported by a series of purposely designed
experiments, a detailed analysis on the operational stability of a VSC refrigeration system
due to its inherent characteristics when its compressor speed is changed for capacity con-
trol has been carried out and presented.
ª 2008 Elsevier Ltd and IIR. All rights reserved.
Etude sur la stabilite lors du fonctionnement d’un systemedote d’un compresseur a vitesse variable
Mots cles : Systeme frigorifique ; Systeme a compression ; Compresseur ; Vitesse variable ; Experimentation ; Surchauffe
1. Introduction
In vapour compression refrigeration systems, there exists an
expansion valve – evaporator control loop which regulates
the refrigerant flow into the evaporator. The instability of
such a control loop and the fluctuations of certain other oper-
ational parameters such as the degree of refrigerant superheat
(DS), normally known as hunting, have been noted in several
previous studies for thermostatic expansion valve (TEV)
; fax: þ852 2765 7198.Deng).er Ltd and IIR. All rights
controlled evaporator refrigeration systems (Wedekind, 1971;
Wedekind and Stoecker, 1966; Wedekind and Stoecker, 1968;
Ibrahim, 2001; Mithraratne and Wijeysundera, 2002; Mithrar-
atne et al., 2000).
Two groups of possible causes have been suggested in
explaining the cause of hunting. The first concentrated on
the influence of the control characteristics of an expansion
valve on system stability (Dhar and Soedel, 1979; Brobesen,
1982; Higuchi and Hayano, 1982). Another, however, tried to
reserved.
![Page 2: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/2.jpg)
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 4 1369
explain the cause of hunting based on the inherent cha-
racteristics of an evaporator. Random fluctuations in the re-
frigerant mixture–vapour transition point due to the nature
of two-phase evaporating flow were described (Wedekind,
1971; Wedekind and Stoecker, 1966; Wedekind and Stoecker,
1968). The concept of minimal stable superheat (MSS), which
was defined as a critical minimal DS at which a refrigeration
system could exhibit unstable operation, was first proposed
by Huelle (1967). Huelle observed that hunting often occurred
when a low DS was set in a refrigeration system even when its
TEV was replaced by a manually operated expansion valve.
Huelle (1972) later introduced conceptually a so-called mini-
mal stable superheat signal line as shown in Fig. 1. The MSS
signal line suggested by Huelle was a monotone conic curve
starting from the original point. In addition, Huelle considered
that the MSS in a refrigeration system was influenced by the
inherent characteristics of its evaporator itself. Chen et al.
(2002) experimentally confirmed the existence of such a MSS
line, without further verifying whether the MSS line was actu-
ally a monotone conic curve as suggested by Huelle (1972).
When the concept of MSS line was introduced by Huelle
(1972) based on his experiments, variable speed compressors
had not been used. Hence, his MSS line was proposed based
on a single speed compressor working with a narrow capacity
modulating range. However, variable speed compressors are
increasingly used nowadays because of their higher operating
efficiency and wider capacity modulating ranges. Electronic
expansion valves (EEV), on the other hand, have found more
and more applications in refrigeration systems due to their
quick response and the increased use of variable speed com-
pressor (Lars, 1999). There have also been a number of
reported studies on the hunting observed in EEV-controlled
refrigeration systems (Outtagarts et al., 1997; Li et al., 2004;
Aprea and Mastrubllo, 2002; Chen, 2005). Therefore, it became
necessary to revisit the MSS line concept in the context of vari-
able speed compressor refrigeration systems which have
larger capacity modulating ranges.
This paper reports on a study on the operational stability
for a VSC refrigeration system due to its inherent characteris-
tics. Firstly, an experimental direct expansion (DX) air condi-
tioning (A/C) plant, where all related experimental work was
carried out, is briefly described. Secondly, the experimental
work on qualitatively determining the relationship between
MSS and the load imposed on a refrigeration system is
QM
Q
M
MSS line
Unstable region
Stable region
θθM
Degree of superheat (°C)
Ref
rige
rati
on lo
ad (
kW)
Fig. 1 – The MSS line as proposed by Huelle (1972).
presented, and a modified MSS line proposed. This is followed
by reporting a detailed analysis on the operational stability of
a VSC–EEV DX A/C system due to changes in compressor
speed, using the modified MSS line and supported by a series
of purposely designed experiments.
2. Description of the experimentalDX A/C plant
All the experimental work involved was carried out in the
experimental DX A/C plant whose schematic diagram is shown
in Fig. 2. The major components in the plant included a variable
speed rotor compressor, a high-efficiency tube-louver-finned
DX evaporator and an air-cooled tube-plate-finned condenser.
The nominal output cooling capacity from the DX air condi-
tioning plant was 9.9 kW (w2.8 RT), but its actual output cool-
ing capacity can, however, be modulated from 15% to 110% of
the nominal capacity through varying compressor speed.
The plant included a simulated air conditioned space,
where load generating units (LGUs), having an adjustable
heating capacity of up to 33.6 kW, were placed for simulating
space cooling load.
The experimental DX A/C plant has been fully instru-
mented. All measurements were computerized, so that all
the measured data can be recorded for subsequent analysis.
3. Experimentation on qualitativelydetermining the MSS line
3.1. Experimental conditions
Using the experimental DX A/C plant, a series of steady-state
experiments were carried out to measure the MSS at different
cooling loads, or equivalently the output cooling capacity of
the DX A/C plant. Since the TEV and the EEV were installed
in parallel, experiments were carried out in either a TEV- or
an EEV-controlled DX A/C system.
Considering the inherent operational characteristics of
a refrigeration system, at steady-state operation, a prescribed
range of fluctuation of �0.5 �C in DS was set. This range was
used to assess whether hunting of DS occurred.
The procedures ofexperimentation were as follows. For both
the TEV- and EEV-controlled systems, a fixed compressor speed
corresponding to a fixed cooling load and a relatively high value
of DS were firstly set. After the system reached a steady-state
operation, the setting of DS was gradually lowered with an in-
terval of w0.1 �C, with the actually operating DS being moni-
tored. When the actually operating DS could no longer be
controlled within the �0.5 �C of its setting, i.e., the prescribed
fluctuation range, the last DS setting was then taken as the min-
imal stable superheat under that fixed system cooling load.
The corresponding load imposed on the experimental DX
A/C system, at which the MSS was determined, was evaluated
by
Q ¼ maðhai � haoÞ (1)
where ma was the mass flow rate of air passing through the DX
evaporator, at w0.513 kg/s; hai the enthalpy of air at the
![Page 3: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/3.jpg)
Variable-speed compressor
Refrigerant side
Air side
LGUs
Air-conditioned space
Variable-speed supply fan
EEV
(7.8m×3.4m×2.9m)
DX evaporator cooling coil
Air-cooled condenser
Variable-speed condenser fan
Stop valve
TEV
Stop valve
Fig. 2 – The schematic diagram of the experimental DX A/C plant.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 41370
evaporator inlet, kJ/kg; hao the enthalpy of air at the evapora-
tor outlet, kJ/kg. With the measured air dry bulb and wet bulb
temperature at the evaporator outlet, and known air temper-
atures at the inlet, i.e., 25.0 �C dry bulb and 19.5 �C wet bulb
(indoor air temperature settings), both hai and hao can be
determined.
The same were repeated at other experimental compressor
speeds or cooling loads. For the EEV-controlled system, the
cooling load covered a range between 5.3 and 9.9 kW. For the
TEV-controlled system, the cooling load was between 5.3
and 9.7 kW.
Since the objective of the study was to investigate the
cause of the unstable operation of a VSC refrigeration system
due to its inherent characteristics, the simplest control algo-
rithm necessary for enabling system’s operation was adopted,
as using more advanced control algorithms such as multi-
input–multi-output (MIMO) may well complicate the cause
of unstable operation. Therefore, in order to eliminate the
possible impact of different control algorithms or parameter
settings on operational stability, during all experiments,
expansion valves were P- (for TEV) or PID (for EEV) feedback
controlled, and compressor speed was manually altered.
Furthermore, for the EEV used, a set of constant P-I-D values,
520, 186 and 11, respectively, was adopted. This set of P-I-D
parameters was proved to have caused stable operation of
the experimental refrigeration system under a wide range of
cooling loads when the degree of refrigerant superheat was
set at 6 �C. On the other hand, while it was understood that
the experimental results reported in this paper were obtained
under this setting, and the numerical values obtained under
other P-I-D settings may be different, the general principle
and its related analysis shall remain valid.
3.2. Results and discussions
Fig. 3 shows the measured relationship between MSS and
cooling load in the TEV-controlled system. As seen, the mea-
sured MSS increased generally with the increase of cooling
load. However, when the cooling load was lower than
w5.8 kW, the MSS remained steady at w3.2 �C. When the cool-
ing load increased to greater than w8.4 kW, the MSS did not
further increase, but stayed at w6.5 �C. Similar phenomena
were also observed in the EEV-controlled system, as shown
in Fig. 4.When the cooling load was lower than w6.8 kW, the
MSS stayed steady at w4.2 �C, and when the cooling load
was higher than w9.2 kW, the MSS stayed steady at w6.1 �C.
An examination of both Fig. 3 and Fig. 4 suggested that for
the two different systems, the shapes of curve representing
the relationship between MSS and cooling load looked similar.
Both were a piecewise function rather than a monotone func-
tion as suggested by Huelle. Hence, the shape of a modified
MSS line has been suggested as a piecewise curve shown in
Fig. 5, having a minimum MSS value, qmin and a maximum
MSS value, qmax. Between qmin and qmax, the curve is of conical
shape.
The existence of both qmin and qmax in a refrigeration sys-
tem is significant with respect to both its operational stability
and energy efficiency. The existence of qmin requires that the
DS should not be set at below qmin even when the system is
operated with a very small load, or unstable operation may
occur. On the other hand, the existence of qmax implies that
there is no need to have a large DS setting when the system
is operated with a larger load, resulting in a poor operational
efficiency. Ideally, DS should be set along a MSS line, for
both operational stability and efficiency.
![Page 4: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/4.jpg)
QM
Q
M
MSS line
θ
Unstable region
Stable region
θMSS θmax.θmin.
Degree of superheat (°C)
Coo
ling
load
/Out
put
cool
ing
capa
city
(kW
)
Fig. 5 – A modified MSS line for a refrigeration system.
Coo
ling
load
/Out
put
cool
ing
capa
city
(kW
)
Minimal stable superheat (°C)
4
5
6
7
8
9
10
3 3.5 4 4.5 5 5.5 6 6.5 7
Fig. 3 – Minimal stable superheat at different cooling loads
(TEV-controlled system).
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 4 1371
4. Analysis on the operational stability ofa VSC–EEV DX A/C system due to thechanges in compressor speed
Varying compressor speed has been widely recognized as the
most energy efficient way for capacity control in a refrigera-
tion system. Various control strategies (Chen, 2005; Li and
Deng, 2007a,b) have been developed for capacity control
through varying compressor speed. In response to system
load changes, compressor speed may be continuously altered
from time to time to adjust output cooling capacity to match
the changes in cooling load. As observed previously (Chen,
2005), changing compressor speed can well lead to the unsta-
ble operation of a VSC–EEV DX A/C system. It is also noted that
in practical operation, while compressor speed may be either
increased or reduced, the setting of DS of the system would
normally remain unaltered.
This section presents a detailed analysis on the operational
stability of a VSC–EEV DX A/C system due to the changes in
compressor speed for capacity control, using the modified
MSS line and supported by a series of purposely designed
experiments carried out in the experimental VSC–EEV DX A/
C plant. These experiments were designed with reference to
MSS experimental results shown in Fig. 4, having a qmax of
w6.1 �C and a qmin of w4.2 �C, respectively.
As mentioned earlier, compressor speed may be either
increased or reduced. Because there existed fundamental dif-
ferences with regard to the operational stability for the two
4
5
6
7
8
9
10
11
3.8 4.2 4.6 5 5.4 5.8 6.2 6.6
Minimal stable superheat (°C)
Coo
ling
load
/Out
put
cool
ing
capa
city
(kW
)
Fig. 4 – Minimal stable superheat at different cooling loads/
output cooling capacities (EEV-controlled system).
speed changing modes, i.e., an increasing mode and a decreas-
ing mode, the analysis was also separated into two parts,
corresponding to the two speed changing modes.
4.1. Operational stability analysisat speed increasing mode
Using the modified MSS line shown in Fig. 5, the operational
stability analysis for the experimental VSC–EEV DX A/C
system at speed increasing mode is illustrated in Fig. 6.
Depending on the value of DS setting, a steady-state operating
point of the experimental system may be on the either side of
qmax, such as points m and n in Fig. 6.
In Fig. 6 n represents that the VSC–EEV DX A/C system
operates steadily at a cooling load Qn, with its DS setting, qn,
greater than qmax. If compressor speed is increased, the oper-
ating point will move from n to n0, which represents that the
system operates at a larger cooling load of Qn0 but with the
same DS setting, qn. As seen from Fig. 6, both n and n0 are sit-
uated in the stable region. Hence the increase in compressor
speed for capacity control (from Qn to Qn0) would not lead to
the hunting of DS when the system finally operates steadily
at point n0. However, immediately after the increase of com-
pressor speed, more refrigerant is sucked into compressor
from the evaporator while the EEV would need time to
respond allowing more refrigerant flowing into the
Q
m
MSS line
θ
Unstable region
θm
Degree of superheat (°C)
Coo
ling
load
/Out
put
cool
ing
capa
city
(kW
)
m
Stable region
n
θn
nQm´
(Qn´)
Qm
(Qn)
θmin. θmax
Expected locusof DS change
Fig. 6 – Analysis of the operational stability of a VSC–EEV
DX A/C system at speed increasing mode.
![Page 5: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/5.jpg)
20304050607080
02468
101214
0 300 600 900 1200 1500 1800 2100
Time (s)
of
max
.co
mpr
esso
r sp
eed
Deg
ree
ofsu
perh
eat
(°C
)
DS setting = 8.0°C
Fig. 7 – The measured DS at speed increasing mode (DS
setting [ 8.0 8C).
30
40
50
60
70
80
00 600 9001 200 1500 1800 2100
Time (s)
of
max
.co
mpr
esso
r sp
eed
Deg
ree
ofsu
perh
eat
(°C
)
02468
101214
0 300 600 900 1200 1500 1800 2100
Time (s)
DS setting = 4.8°C
DS setting = 7.0°C
Fig. 9 – The measured DS at speed increasing mode (with
varied DS setting from 4.8 to 7.0 8C).
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 41372
evaporator. Therefore, these exists a short period when there
is less than required refrigerant in the DX evaporator, causing
a sudden increase in DS. Then the operating DS will gradually
return to its setting. The expected locus of DS should not be
simply a straight line connecting the two points, but like those
shown in Fig. 6. The expected locus of DS change will not cross
the MSS line; hence no hunting of DS is expected.
Fig. 7 shows the results of a related experiment to support
the above analysis. The DS setting was 8.0 �C, which was
greater than the reference qmax of w6.1 �C. At about t¼ 300 s
when the compressor speed was step increased from 40% to
70% of its maximum speed, the measured DS also significantly
increased to 14 �C, within a very short period, and then grad-
ually reduced to restore its setting. No fluctuation of the mea-
sured DS may be observed.
On the other hand, in Fig. 6, m represents that the DX A/C
system operates steadily with its DS setting, qm, lower than
qmax. If the compressor speed is increased, the operating point
will move from m to m0. Unlike the n–n0 point case, while point
m is situated in the stable region, point m0 is in the unstable
region. Hence, when the system is eventually operated at
point m0, fluctuation of DS cannot be avoided. In fact, fluctua-
tion of DS may occur as soon as the expected locus of DS
change crosses the MSS line. Fig. 8 shows the results of
a related experiment to support the above analysis. The DS
20304050607080
00 6009 00 1200 1500 1800
Time(s)
% o
f m
ax.
com
pres
sor
spee
dD
egre
e of
supe
rhea
t (°
C)
0
2
4
6
8
10
0 300 600 900 1200 1500 1800 2100
Time (s)
DS setting = 4.8°C
Fig. 8 – The measured DS at speed increasing mode (DS
setting [ 4.8 8C).
setting was 4.8 �C, which was between the reference qmax of
w6.1 �C and the reference qmin of w4.2 �C. From Fig. 8, it can
be seen that the measured DS firstly increased to over 10 �C
following a step increase in compressor speed from 40% to
70% of its maximum speed. After the EEV allowed more refrig-
erant flow, the measured DS then gradually reduced to
approach to its setting, with, however, noticeable fluctuation
of DS occurring from approximately t¼ 1100 s onwards, to
the end of experiment.
For a VSC–EEV refrigeration system having a DS setting
smaller than qmax, in order to avoid the possible fluctuations
of DS due to speed increase, it is possible to simultaneously
increase its DS setting to greater than qmax. Fig. 9 shows the
results of a specially designed experiment to verify this infer-
ence. The original DS setting was 4.8 �C. At t¼ 300 s, when the
compressor speed was step increased from 40% to 70% of its
maximum speed, the DS setting was also increased to 7.0 �C
(>qmax of w6.1 �C). Therefore, the fluctuations of DS in Fig. 8
can no longer be observed in Fig. 9, in the late part of the
experimental period.
4.2. Operational stability at speed decreasing mode
Also using the MSS line shown in Fig. 5, the analysis of opera-
tional stability for the experimental VSC–EEV DX A/C system
Qp
´Qo
Q
o
MSS line
θ
Unstable region
θo
Degree of superheat (°C)
Coo
ling
load
/Out
put
cool
ing
capa
city
(kW
)
o´
Stable region
p
θp
p´
Qp
Qo
θmin. θmax.
Expected locusof DS change
Fig. 10 – Analysis of the operational stability of a VSC–EEV
DX A/C system at speed decreasing mode.
![Page 6: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/6.jpg)
of m
ax.
com
pres
sor
spee
d D
egre
e of
supe
rhea
t (°
C)
40
50
60
70
80
90
300 600 9001 200 1500 18002 100
Time (s)
0
2
4
6
8
0 300 600 900 1200 1500 1800 2100 2400
Time (s)
DS setting = 7.0°C
Fig. 11 – The measured DS at speed decreasing mode
(DS setting [ 7.0 8C).
40
50
60
70
80
00 600 900 1200 1500 18002 100
Time (s)
0
2
4
6
8
10
0 300 600 900 1200 1500 1800 2100
Time (s)
of
max
.co
mpr
esso
r sp
eed
Deg
ree
ofsu
perh
eat
(°C
)
DS setting = 7.0°C
Fig. 13 – The measured DS at speed decreasing mode with
a small magnitude of speed change.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 4 1373
at speed decreasing mode is shown in Fig. 10. Similarly DS set-
ting may be on either side of qmax, as represented by point o
and p. For both cases, unlike speed increasing mode, both
starting points and ending points are situated in the stable
region. Hence, no fluctuation of DS would be expected when
the system is eventually operated steadily at either point o0
and p0. Nevertheless, it is possible that during the transit
from o to o0 or from p to p0, fluctuations of the measured DS
can actually occur as the expected locus of DS change may
well cross the MSS line, depending on the magnitude of the
step decrease in compressor speed.
Figs. 11 and 12 show the results of two related supporting
experiments, where the settings of DS were 7.0 �C (>the refer-
ence qmax of w6.1 �C) and 5.5 �C (<the reference qmax of
w6.1 �C), respectively. The compressor speed reductions
were from 80% to 50% and from 60% to 40% of its maximum
speed, respectively. In Fig. 11, it can be seen that immediately
after the speed decrease at t¼ 300 s, there was a significant
drop in DS to below 2.0 �C. This was because there was more
refrigerant than needed inside the evaporator and it took
time for the EEV to reduce refrigerant flow. This means that
the expected locus of DS change could well cross the MSS
line during transit, so that the measured DS fluctuated. At
about t¼ 620 s, fluctuations of the measured DS could no lon-
ger be observed, suggesting that the operating point returned
3040506070
300 600 900 1200 1500 1800 2100
Time (s)
0123456
0 300 600 900 1200 1500 1800 2100
Time (s)
of
max
.co
mpr
esso
r sp
eed
Deg
ree
ofsu
perh
eat
(°C
)
DS setting = 5.5°C
Fig. 12 – The measured DS at speed decreasing mode
(DS setting [ 5.5 8C).
to the stable region. Afterwards, the measured DS gradually
returned to its setting at 7.0 �C. Similar observations may
also be obtained from Fig. 12.
For these two experiments, as the magnitudes of speed
decrease are relatively significant, it is then possible for the
actual operating point to cross the MSS line and move into
the unstable region during transit. Therefore, it intuitively fol-
lows that limiting the magnitude of each step decrease in
compressor speed may help avoid the possible occurrence of
DS fluctuation. However, although this may help achieve a bet-
ter operational stability, the sensitivity of capacity control
may be lowered when a compressor speed decrease of a larger
magnitude is called for.
Fig. 13 shows the results of a follow-up experiment, from
that shown in Fig. 11. The operational conditions including
the DS for both experiments were the same, except the magni-
tude of speed reduction, i.e., 10% (60–50%), compared to 30%
(80–50%). It can be seen from Fig. 13 that when the step change
in compressor speed took place at t¼ 300 s, the measured DS
also dropped, but afterwards gradually increased to approach
to its setting. During the transit, no oscillations of measured
DS may be observed. This implied that the actual operating
point did not cross the MSS line and stayed in the stable region.
5. Conclusions
This paper reports on a study on the operational stability due
to systems’ inherent characteristics in a VSC refrigeration
system. The following conclusions may be drawn:
� The so-called minimal stable superheat (MSS), as proposed
by Huelle (1972), does exist in both a TEV- and an EEV-
controlled refrigeration system.
� A modified MSS line would possess a piecewise function
shape instead of a monotone function shape, having a min-
imum MSS value and a maximum MSS value, as shown in
Fig. 5.
� The modified MSS line can be used to analyze and explain
the operational stability of a VSC–EEV DX A/C system due
to the changes in compressor speed for capacity control.
In a VSC–EEV DX A/C system, if its DS setting is lower
![Page 7: A study on the operational stability of a refrigeration system having a variable speed compressor](https://reader036.vdocuments.mx/reader036/viewer/2022080309/57501de91a28ab877e8dfb1d/html5/thumbnails/7.jpg)
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 1 3 6 8 – 1 3 7 41374
than qmax, increasing compressor speed may lead to the
hunting of DS if the final operating point is in the unstable
region. On the contrary, if the DS setting is already greater
than qmax, no hunting of DS would occur.
� Also in a VSC–EEV DX A/C system, decreasing compressor
speed may cause hunting of the operating DS during transit,
but no hunting of DS is expected after the system reaches
a steady-state operation under the new compressor speed.
� It is beneficial to operational stability to have speed reduc-
tions of smaller varying magnitudes, although this may
reduce the sensitivity of a capacity controller.
The modified MSS line and its related analysis as well as
the related experimental results reported provide detailed
insights to the operational stability of a VSC refrigeration sys-
tem due to its inherent characteristics. The other group of the
cause of unstable operation, which is related to control algo-
rithms or setting adopted by various controllers installed in
the system, was not addressed in the current study. Further-
more, it is noted that the current trend in developing
advanced control strategies for EEV–VSC systems is increas-
ingly based on MIMO (He et al., 1998; Skogestad and
Postletheaite, 1996; Qi and Deng, 2008). Nevertheless, the
results reported in this paper are as a matter of fact part of sys-
tem’s inherent characteristics and can therefore be used in
assisting the further design of controllers, such as those
MIMO based, for a VSC refrigeration system.
Acknowledgements
The authors thank The Hong Kong Polytechnic University for fi-
nancially supporting the work reported (Project No.: A – PG 40).
r e f e r e n c e s
Aprea, C., Mastrubllo, R., 2002. Experimental evaluation ofelectronic and thermostatic expansion valves performanceusing R22 and R407C. Applied Thermal Engineering 22,205–218.
Brobesen, P.M.T., 1982. Control with a thermostatic expansionvalve. International Journal of Refrigeration 5 (4), 209–212.
Chen, W., Chen, Z.J., Zhu, R.Q., Wu, Y.Z., 2002. Experimentalinvestigation of a minimum stable superheat control systemof an evaporator. International Journal of Refrigeration 25,1137–1142.
Chen W., 2005. Modeling and control of a direct expansion (DX)variable-air-volume (VAV) air conditioning (A/C) system, Ph.D.Thesis, The Hong Kong Polytechnic University.
Dhar M., Soedel W., 1979 Transient analysis of vapor compressionrefrigeration system: part I, mathematical model and part II,computer simulation. In: Proceedings of 15th InternationalCongress of Refrigeration Meeting, 1979, Venice, Italy, pp.1035–1067.
He, X.D., Liu, S., Asada, H.H., Itoh, H., 1998. Multivariable controlof vapor compression systems. HVAC&R Research 4 (3),205–230.
Higuchi, K., Hayano, M., 1982. Dynamic characteristics ofthermostatic expansion valves. International Journal ofRefrigeration 5 (4), 216–220.
Huelle, Z.R., 1967. Heat load influences upon evaporatorparameters. In: Proceedings of XII International Congress ofRefrigeration Meeting vol. 3 (32), 1967, Madrid, pp. 985–999.
Huelle, Z.R., October 1972. The Mss-line – a new approach to thehunting problem. ASHRAE Journal, 43–46.
Ibrahim, G.A., 2001. Effect of sudden changes in evaporatorexternal parameters on a refrigeration system with anevaporator controlled by thermostatic expansion valve.International Journal of Refrigeration 24, 566–576.
Lars B.K., 1999. Novel electronic high reliability valve principle forcontrol of direct expansion. In: Proceedings of 20thInternational Congress of Refrigeration, 1999, Sydney, IIR/IIF,p. 445.
Li, Z., Deng, S.M., 2007. A DDC-based capacity controller ofa direct expansion (DX) air conditioning (A/C) unit forsimultaneous indoor air temperature and humidity control –Part I: Control algorithms and preliminary controllability tests.International Journal of Refrigeration 30 (1), 113–123.
Li, Z., Deng, S.M., 2007. A DDC-based capacity controller ofa direct expansion (DX) air conditioning (A/C) unit forsimultaneous indoor air temperature and humidity control –Part II: Further development of the controller to improvecontrol sensitivity. International Journal of Refrigeration 30(1), 124–133.
Li, X.Q., Chen, J.P., Chen, Z.J., et al., 2004. A new method forcontrolling refrigerant flow in automobile air conditioning.Applied Thermal Engineering 24, 1073–1085.
Mithraratne, P., Wijeysundera, N.E., 2002. An experimental andnumerical study of hunting in thermostatic-expansion–valve-controlled evaporators. International Journal ofRefrigeration 25, 992–998.
Mithraratne, P., Wijeysundera, N.E., Bong, T.Y., 2000. Dynamicsimulation of a thermostatically controlled counter-flowevaporator. International Journal of Refrigeration 23, 174–189.
Outtagarts, A., Harberschill, P., Lallemand, M., 1997. Thetransient response of an evaporator fed through anelectronic expansion valve. The Journal of Energy Research21, 793–807.
Qi, Q., Deng, S.M., 2008. Multivariable control-oriented modelingof a direct expansion (DX) air conditioning (A/C) system.International Journal of Refrigeration, doi:10.1016/j.ijrefrig.2007.10.009.
Skogestad, S., Postletheaite, I., 1996. Multivariable FeedbackControl Analysis and Design. John Wiley & Sons Ltd.
Wedekind G.L., Stoecker W.F., 27–29 June 1966 Transient responseof the mixture–vapor transition point in horizontalevaporating flow. In: ASHRAE 73rd Annual Meeting, 27–29 June1966, Toronto Canada, pp. IV.2.1–IV.2.15.
Wedekind, G.L., Stoecker, W.F., February 1968. Theoretical modelfor predicting the transient response of the mixture–vapourtransition points in horizontal evaporating flow. Transactionsof ASME, Journal of Heat Transfer, 165–174.
Wedekind, G.L., 1971. An experimental investigation into theoscillatory motion of mixture–vapor transition point inhorizontal evaporating flow. Journal of Heat Transfer 93,47–54.