a method for accurate transmission line impedance

11
A method for accurate transmission line impedance parameter estimation Article Accepted Version Ritzmann, D., Wright, P. S., Holderbaum, W. and Potter, B. (2016) A method for accurate transmission line impedance parameter estimation. IEEE Transactions on Instrumentation and Measurement, 65 (10). pp. 2204-2213. ISSN 0018-9456 doi: https://doi.org/10.1109/TIM.2016.2556920 Available at https://centaur.reading.ac.uk/66551/ It is advisable to refer to the publisher’s version if you intend to cite from the work. See Guidance on citing . Published version at: http://ieeexplore.ieee.org/document/7465793/ To link to this article DOI: http://dx.doi.org/10.1109/TIM.2016.2556920 Publisher: IEEE All outputs in CentAUR are protected by Intellectual Property Rights law, including copyright law. Copyright and IPR is retained by the creators or other copyright holders. Terms and conditions for use of this material are defined in the End User Agreement . www.reading.ac.uk/centaur CentAUR Central Archive at the University of Reading

Upload: others

Post on 22-Feb-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A method for accurate transmission line impedance

A method for accurate transmission line impedance parameter estimation Article

Accepted Version

Ritzmann, D., Wright, P. S., Holderbaum, W. and Potter, B. (2016) A method for accurate transmission line impedance parameter estimation. IEEE Transactions on Instrumentation and Measurement, 65 (10). pp. 2204-2213. ISSN 0018-9456 doi: https://doi.org/10.1109/TIM.2016.2556920 Available at https://centaur.reading.ac.uk/66551/

It is advisable to refer to the publisher’s version if you intend to cite from the work. See Guidance on citing .Published version at: http:// ieeexplore.ieee.org/document/7465793/ To link to this article DOI: http://dx.doi.org/10.1109/TIM.2016.2556920

Publisher: IEEE

All outputs in CentAUR are protected by Intellectual Property Rights law, including copyright law. Copyright and IPR is retained by the creators or other copyright holders. Terms and conditions for use of this material are defined in the End User Agreement .

www.reading.ac.uk/centaur

CentAUR

Central Archive at the University of Reading

Page 2: A method for accurate transmission line impedance

Reading’s research outputs online

Page 3: A method for accurate transmission line impedance

1

A Method for Accurate Transmission LineImpedance Parameter Estimation

Deborah Ritzmann, Student Member, IEEE, Paul S. Wright, William Holderbaum, Member, IEEE,and Ben Potter, Member, IEEE

Abstract—Real-time estimation of power transmission lineimpedance parameters has become possible with the availabilityof synchronized phasor measurements of voltage and current.If sufficiently accurate, the estimated parameter values are apowerful tool for improving the performance of a range of powersystem monitoring, protection and control applications, includingfault location and dynamic thermal line rating. The accuracy ofthe parameter estimates can be reduced by unknown errors inthe synchronized phasors that are introduced in the measurementprocess. In this paper, a method is proposed with the aim ofobtaining accurate estimates of potentially variable impedanceparameters, in the presence of systematic errors in voltage andcurrent measurements. The method is based on optimization toidentify correction constants for the phasors. A case study ofa simulated transmission line is presented to demonstrate theeffectiveness of the new method, which is better in comparisonwith a previously proposed method. The results as well as limitsand potential extensions of the new method are discussed.

Index Terms—Accuracy, admittance measurement, impedancemeasurement, optimization methods, parameter estimation, pha-sor measurement unit, transmission line measurements

I. INTRODUCTION

CONTINUOUS electricity supply has become one ofthe backbones of many economies worldwide. For this

reason, reliable and efficient operation of power networks is acrucial challenge that needs to keep pace with their increas-ingly complex nature. Reliability and efficiency are ensuredthrough careful monitoring, protection and control of powersystems, which requires a range of electrical measurements asinputs. One of these inputs are the impedance parameters oftransmission lines; for example in current differential protec-tion [1] and fault location [2].

Traditionally, parameters were calculated off-line usinghandbook formulae based on tower geometry and conductorproperties [3], [4] or through fault record analysis [5]. Thesemethods are not able to track short-term changes in impedanceparameters, which may occur due to Joule heating and ambienttemperature variations. Nowadays it is possible to calculatethe impedance parameters of transmission lines on-line andin real-time from synchronized phasor (synchrophasor) mea-surements of voltage and current at both line ends. The

This work was supported by the Climate Knowledge and Innovation Com-munity (Climate-KIC) of the European Institute of Innovation and Technology(EIT).

D. Ritzmann, W. Holderbaum and B. Potter are with the Schoolof Systems Engineering, University of Reading, Reading, RG6 6UR,UK (e-mail: [email protected]; [email protected];[email protected]).

P. S. Wright is with the National Physical Laboratory, Teddington, TW110LW, UK (e-mail: [email protected]).

synchrophasors are usually reported by Phasor MeasurementUnits (PMUs) that are installed in substations [6].

Synchrophasor-based transmission line impedance determi-nation has been investigated by many researchers since the1990s. Early studies demonstrated the feasibility of the conceptand advantages over traditional methods [7]–[9]. The deter-mined parameter values are only useful if they satisfy accuracyrequirements, which depend on the specific applications. Forfault location [2] and dynamic thermal line rating [10], itis desirable to detect thermally induced variation of the lineresistance, which ranges from 1% to 20% [11].

Parameter accuracy may be expressed in terms of minimumand maximum limits that are derived from the accuracy of thesynchrophasor measurements [1]. The accuracy of the reportedsynchrophasors is influenced by the entire measurement chain.

PMUs themselves often exceed the requirements of 1%Total Vector Error and 1 µs time-tagging to UTC, given inIEEE Standard C37.118.1-2011 [12]; for instance, PMUswith accuracies of ±0.03% in phasor magnitude and ±0.01

in phase angle (±0.6 µs at 50Hz) have been manufactured[13]. Hence, if only the accuracy of PMUs is considered,uncertainties in impedance parameter estimates of less than2% are possible [1].

It is important to recognize that additional systematic errorsof up to 1% in the magnitude and 1 in the phase angle of thesynchrophasors may be introduced by the remaining measure-ment chain, as is recognized in IEEE Standard C37.242-2013[14]. The remaining measurement chain includes instrumenttransformers, cables, burdens and external time synchroniza-tion equipment such as GPS antennae and connection cables.

Ideally, these errors should be characterized and correctedbefore the impedance parameter estimation process. For ex-ample, in addition to the nominal transformer ratios, trans-former correction factors should be applied, and time-taggingadjusted for delays in the synchronization signal. However,the actual correction factors may differ from their values atthe time of characterization due to ageing or modificationof the instrumentation channel. Consequently, the measuredsynchrophasors can be subject to unknown errors, which canhave an adverse impact on parameter estimation accuracy.

A number of approaches have been proposed to reducethe impact of random errors in synchrophasor measurementson impedance parameter determination: unbiased linear leastsquares estimation [15], [16], non-linear least squares algo-rithms [17]–[19], total least squares estimation [20] as wellas optimization procedures [7], [21]. On the other hand, theimpact and reduction of systematic errors in the synchrophasor

Page 4: A method for accurate transmission line impedance

2

R L

C2

C2

G2

G2

Y2

Y2

Z

Vs Vr

Is Ir

Fig. 1. Nominal pi circuit diagram for a medium length transmission line.It shows the lumped impedance and admittance components as well as thesending and receiving end voltages and currents.

measurements with regards to impedance parameter estimationhas received less attention.

One solution is to estimate individual correction factorsfor both magnitude and phase angle of voltage and currentalong with the parameters in an optimization procedure [21].However, this approach makes use of a wide range of mea-surements and assumes time-invariant impedance parameters.Hence, there is a need to develop effective methods for thereduction of the impact of systematic errors in synchrophasormeasurements on real-time impedance parameter estimation.

In a previous paper by the authors, a potential solutionfor this problem has been proposed [22]. It consists of amethod that assumes linear variation of the impedance pa-rameters over short periods of time. Correction constants forthe synchrophasors are identified by minimising the residualsof a least squares fit of the calculated parameters to a linearmodel. The method was shown to effectively reduce theimpact of systematic errors in voltage measurements of a shorttransmission line, neglecting shunt admittance. But for longerlines shunt admittance is significant as it causes the current tovary along the line, and thus needs to be taken into accountin parameter calculations. Furthermore, systematic errors canalso occur in synchrophasor measurements of current. The aimof this paper is to propose an extension of the method suchthat it can effectively reduce the impact of systematic errors inall synchrophasor measurements for the general transmissionline modelled by the lumped pi circuit, which has both seriesimpedance and shunt admittance.

The rest of the paper is structured as follows: in the nextsection, models for the transmission line and systematic errorsare defined and the proposed method is presented. Thereafter, acase study of a simulated line is considered and a comparisonwith an existing linear least squares-based method is made.The fourth section is a discussion of the case study results, aswell as strengths and limits of the proposed method. The finalsection concludes the paper.

II. METHODS

A. Transmission Line Model

The nominal pi circuit, as shown in Fig. 1, is the stan-dard model for the electrical parameters of a medium lengthtransmission line (80 km to 240 km) [3]. For medium lengthlines, the effects of shunt admittance cannot be ignored, but

lumped components are still a good approximation for theactual, distributed parameters [3].

The circuit consists of a series impedance component Z,as well as shunt admittance Y , which is split into two equalcomponents at either end of the line, as shown in Fig. 1.The series impedance Z has resistance R and inductanceL, while the shunt admittance Y consists of conductance Gand capacitance C. Conductance G is normally considerednegligible and omitted from the model; however, it is usefulfor the consideration and correction of systematic errors aswill be shown in Section II-C. The measured currents andvoltages at either end of the line are modelled by V

s

, Is

, Vr

, Ir

,which are assumed to be phasors at the nominal power systemfrequency f ; subscript s refers to sending and subscript r toreceiving end. By Kirchhoff’s Voltage and Current Laws, thecircuit equations are

Vs

= (Is

Y

2Vs

)Z + Vr

(1)

Is

= (Vs

+ Vr

)Y

2+ I

r

, (2)

where Vs

, Is

, Vr

, Ir

, Z, Y 2 C, Z = R + jX , X = 2fL,Y = G+ jB, B = 2fC and R,X,G,B,L,C, f 2 R>0. Xis the inductive reactance and B is the capacitive susceptance.

Substitution of (2) into (1) leads to the following formulaefor impedance Z and admittance Y :

Z =V 2s

V 2r

Vs

Ir

+ Vr

Is

(3)

Y = 2Is

Ir

Vs

+ Vr

. (4)

If a single set of synchronized measurements Vs

, Is

, Vr

, Ir

isavailable from a PMU or equivalent device, values of Z andY can be calculated; parameters R, X , G and B are obtainedfrom the real and imaginary parts of Z and Y, respectively.

B. Systematic Errors in the Synchrophasor Measurements

In this paper, systematic errors in the form of a proportionalerror in the phasor magnitude and additive offset in the phaseangle are considered. Let V

s

be a synchrophasor measurementof the sending end voltage V

s

with systematic errors as

inmagnitude and

s

in phase angle. Vs

and Vs

are related by

Vs

= Vs

(1 + as

) exp(js

), (5)

where Vs

2 C, as

,s

2 R. This structure is chosen in line withtransformer correction factors, which are the general model forexpressing errors caused by instrument transformers [23]. Thesystematic errors are assumed to be constant, since in real-time applications, the utilized voltage and current measure-ments span only a limited part of the instrument ranges andinstrumentation channels are designed for long-term stability.

On the basis of accuracy classes of instrument transformersand previous characterization of instrumentation channels, theerrors are assumed to be less than 1% in magnitude and lessthan 0.01 rad in phase angle [14]. Thus it is assumed that|a

s

|, |s

| < 0.01 and the following small angle approximationis made:

exp(js

) 1 + js

. (6)

Page 5: A method for accurate transmission line impedance

3

Substituting (6) into (5) gives

Vs

= Vs

(1 + as

)(1 + js

) = Vs

(1 + as

+ js

+ jas

s

). (7)

The lower order term jas

s

will be omitted. Hence,

Vs

= Vs

(1 + as

+ js

). (8)

Define the overall error Vs

2 C in the synchrophasormeasurement V

s

as

Vs

= Vs

Vs

= (as

+ js

)Vs

. (9)

Similarly, Is

, Vr

, Ir

2 C are defined as synchrophasor mea-surements that have systematic errors a

r

,r

, bs

, s

, br

, r

suchthat V

r

= Vr

(1+ar

+jr

), Is

= Is

(1+bs

+js

), Ir

= Ir

(1+br

+ jr

), and Is

, Vr

, Ir

2 C are overall errors defined asV

r

= (ar

+ jr

)Vr

, Is

= (bs

+ js

)Is

, Ir

= (br

+ jr

)Ir

.Suppose the values of a

s

,s

, ar

,r

, bs

, s

, br

, r

are un-known. Then the impedance and admittance estimates fromsynchrophasors with systematic errors are given by

Z =Vs

2 Vr

2

Vs

Ir

+ Vr

Is

(10)

Y = 2Is

Ir

Vs

+ Vr

, (11)

where Vs

, Is

, Vr

, Ir

have been substituted into (3) and (4).Z and Y deviate from Z and Y , respectively, and thus theestimated parameters are in error. This loss of accuracy can bereduced by estimating values of a

s

,s

, ar

,r

, bs

, s

, br

, r

tocorrect the phasor measurements. The following observationsare used to simplify the problem:

• Since Z is proportional to (V 2s

V 2r

), it is more sensitiveto a

s

,s

, ar

,r

than to bs

, s

, br

, r

and the error in Zcaused by a

s

,s

is approximately equal and opposite tothe error caused by a

r

,r

(see Appendix C).• Since Y is proportional to (I

s

Ir

), it is more sensitiveto b

s

, s

, br

, r

than to as

,s

, ar

,r

and the error in Ycaused by b

s

, s

is approximately equal and opposite tothe error caused by b

r

, r

(see Appendix C).Therefore it is assumed that error constants a

s

, ar

,s

,r

canbe combined into ’net’ errors a, in V

r

, where a = ar

as

, = r

s

, |a|, || < 0.02. Similarly bs

, s

, br

, r

arecombined into errors b, in I

r

, where b = br

bs

, = r

s

, |b|, || < 0.02.In the next section a method for estimating values of a,, b

and is presented.

C. Proposed Method for Identification of Correction Con-stants

To reduce the deviations in estimated parameters Z and Ydue to systematic errors that were described in the previoussubsection, synchrophasor measurements should be correctedbefore parameters estimates are calculated. A method has beendesigned to identify such correction constants and is presentedin the following paragraphs.

The method assumes no knowledge of the true values ofimpedance and admittance parameters. Instead, it is assumed

that the behaviour of the resistance and reactance is ap-proximately linear over short periods relative to the thermaltime constant of overhead line conductors (5min to 20minaccording to IEEE Standard 738-2012 [24]) because of slowvariation in the rate of change of resistance and reactance.Conductance and susceptance are assumed to be constant.Therefore the calculated parameters are fitted to linear modelswith respect to time. Let the models for R,X,G,B befR

, fX

, fG

, fB

: R+ ! R, respectively, where

fR

(ti

) = qR

ti

+ rR

(12)

fX

(ti

) = qX

ti

+ rX

(13)

fG

(ti

) = rG

(14)

fB

(ti

) = rB

(15)

and qR

, rR

, qX

, rX

, rG

, rB

2 R are constants, which areestimated in a least squares sense from a set of N 2 Nparameter values R

i

, Xi

, Gi

, Bi

2 R, calculated at timeinstants t

i

, i = 1, . . . , N , with ti

= it and t 2 R theconstant time interval between synchrophasor measurements.The time interval t

N

t1 is a moving window that is chosen tobe less than the thermal time constant of the line. The details ofthe estimation of q

R

, rR

, qX

, rX

, rG

, rB

are given in AppendixA.

Suppose that Ri

, Xi

, Gi

, Bi

are calculated from syn-chrophasor measurements with systematic errors, then thegoodness of fit of f

R

, fX

, fG

, fB

is reduced. To measure thegoodness of fit, the sum of the squared residual is calculatedas

SR

=

NX

i=1

(Ri

fR

(ti

))2, (16)

where SR

2 R+. Equivalent expressions are assumed forSX

, SB

, SG

2 R+, in terms of Xi

, fX

, Gi

, fG

, Bi

, fB

, re-spectively. By minimizing S

R

, SX

, SG

and SB

, correctionconstants can be found that maximize the goodness of fitof f

R

, fX

, fG

and fB

, and thus result in impedance andadmittance parameter estimates that are more consistent withthe expected physical behaviour of the line over time.SR

and SX

are sensitive to errors in Vs

and Vr

and can beminimized by finding optimal values of correction constantsa, for V

r

. Hence, optimization problem 1 is formulated:

minimizea,

gZ

(a,) = SR

+ SX

subject to |a| < 0.02, || < 0.02,(17)

with initial values: a = 0, = 0. The objective functiongZ

: R2 ! R+ is evaluated using correction constants a,to recalculate the impedance parameters as follows:

Zi

= Ri

+ jXi

= Zi

+@Z

@Vr

Vr=Vri

Vri , (18)

where Vri = (a + j)V

ri , and Zi

is calculated using (10)from synchrophasor measurements V

si , Isi , Vri , Iri taken attime t

i

. The first order Taylor approximation of Z is takenbecause V

ri is small and in this way Zi

remains linear ina,. The partial derivative @Z

@Vris given in Appendix B. Once

Ri

and Xi

have been recalculated using (18), new values for

Page 6: A method for accurate transmission line impedance

4

qR

, rR

, qX

, rX

, rG

, rB

are estimated and SR

as well as SX

are updated to give a new value of gZ

.Similarly, S

G

and SB

are sensitive to errors in Is

and Ir

.Optimization problem 2 is defined to identify optimal valuesof correction constants b, 2 R for I

r

that minimize SG

andSB

:minimize

b,

gY

(b, ) = µ(SG

+ SB

)

subject to |b| < 0.02, || < 0.02,(19)

with initial values: b = 0, = 0. Since G and B are ofthe order of 106 and 104, respectively, S

G

and SB

canbecome very small and factor µ is introduced to avoid badscaling. The objective function g

Y

: R2 ! R+ is evaluatedusing correction constants b, to recalculate the admittanceparameters as follows:

Yi

= Gi

+ jBi

= Yi

+@Y

@Ir

Ir= ˜

Iri

Iri , (20)

where Iri = (b+j)I

ri , and Yi

is calculated using (11) fromsynchrophasor measurements V

si , Isi , Vri , Iri taken at time ti

.The first order Taylor approximation of Y is taken because I

r

is small and Yi

remains linear in b, . The partial derivative@Y

@Iris given in Appendix B.

Both (17) and (19) are nonlinear constrained optimizationproblems, for which minima can be obtained with a range ofalgorithms. In this instance the interior-point method was cho-sen [25]. g

Z

and gY

are convex and thus the local minima areglobal in the feasible regions.The reason is that Z

i

and Yi

arelinear in the respective correction constants and estimation ofqR

, rR

, qX

, rX

, rG

, rB

(see Appendix A) as well as evaluationof g

Z

and gY

preserve convexity.Fig. 2 shows a flow chart that summarizes the processes

of identifying correction constants and estimating values ofthe line parameters. The final parameter estimates at a giventime t

N

are obtained by fitting functions fR

, fX

, fB

to theparameter values calculated from corrected measurements andevaluating f

R

(tN

), fX

(tN

), fB

(tN

). The aim of this step isto give parameter estimates with reduced random variation,which occurs in the individually calculated parameter values.

In the next section, the effectiveness of the proposed methodis demonstrated in a case study.

III. CASE STUDY

In this section, the specifications of the transmission linesimulation are given, and results of the application of theproposed method as well as an existing linear least squares-based method are presented.

A. Transmission Line Simulation

A single phase of the 400 kV, 102 km long transmissionline located between substations Grendon and Staythorpe,East Midlands, England [26], was simulated in Matlab. Thenominal parameter values are R0 = 2.96, X0 = 32.4and B0 = 3.69 104 S. The resistance was assumed tovary sinusoidally within ±4% of the nominal value, whichcorresponds to a change in line temperature of approximately±10 C over the period of the simulation.

Fig. 2. This flow chart illustrates how values for correction constants andimpedance parameters are estimated by the proposed method.

Time ti (h)

0 1 2 3 4 5 6 7

rms

Volt

age

Mag

nit

ude

(kV

)

140

160

180

200

220

240

| Vs|

| Vr|

Fig. 3. This graph shows the magnitude of the sending and receiving endvoltages over the period of the simulation.

The network at either end of the line was modelled by anequivalent voltage source; Fig. 3 shows the root-mean-square(rms) magnitude of the sending and receiving end voltages.A variable load profile ranging from 15% to 100% of ratedcurrent was assumed to occur over a seven hour period; rmsvalues of current magnitude are shown in Fig. 4. Synchronizedmeasurements of steady-state current and voltage phasors ateach line end were taken at time intervals of t = 2min forblocks of 10 s.

Page 7: A method for accurate transmission line impedance

5

Time ti (h)

0 1 2 3 4 5 6 7

rms

Cu

rren

t M

agn

itu

de

(kA

)

0

1

2

3

4

| Is|

| Ir|

Fig. 4. This graph shows the magnitude of the sending and receiving endcurrents over the period of the simulation. Their difference is very smallcompared to the absolute magnitudes.

In order to reflect the measurement uncertainty that wouldbe present in practice, the measurements were contaminatedwith Gaussian noise of mean zero and standard deviationsof 0.03% and 0.04% in magnitudes of voltage and current,respectively, and 0.3mrad in all phase angles.

Systematic errors in both sending and receiving end voltagesand currents as modelled in Section II-B were applied to allsynchrophasor measurements. The mean of the synchrophasorswas taken over each 10 s block to generate an individual setof measurements every two minutes; in total there were 203measurement sets. A moving window of N = 8 measurementpoints, spanning 16min, was used to estimate the impedanceand admittance parameters of the line in real-time. Thus, 196estimated values were computed for each of R,X and B.

In order to test the effectiveness of the method, different setsof systematic errors were applied to the measurements. In eachcase, the magnitude and phase errors were selected randomlyfrom a uniform distribution in the interval [0.01, 0.01]. Intotal, 100 000 cases were studied, giving sufficiently smallconfidence intervals on the relevant metrics, which will bedefined in section III-C.

B. Existing Linear Least Squares Method

The proposed method was applied to identify correctionconstants a,, b, to improve the accuracy of the calculated Zand Y values. For comparison, an existing linear least squares(LS) method was also applied to each window to obtainparameter estimates [15]. This method models the transmissionline as a general two-port network, in which voltages andcurrents are related by

Vs

= A Vr

+B Ir

(21)

Is

= C Vr

+D Ir

, (22)

where A,B,C,D 2 C are constants.For the eight measure-ment sets in a given window, (21) was expanded into twoequations by taking the real and imaginary parts to give 16real equations in total. The real and imaginary parts of Aand B were computed through unbiased linear least squaresestimation.

TABLE ISYSTEMATIC ERRORS IN THE SYNCHROPHASOR MEASUREMENTS

Magnitude Phase Angle TVEVs as = 0.0008 s = 0.0059 0.60%Vr ar = 0.0021 r = 0.0076 0.78%Is bs = 0.0016 s = 0.0095 1.02%Ir br = 0.0037 r = 0.0034 0.38%

By assuming a pi circuit (Fig. 1) inside the two-portnetwork, constants A,B,C,D can be expressed in terms ofimpedance Z and admittance Y :

A = 1 + Y Z/2 (23)

B = Z (24)

C = Y (1 + Y Z/4) (25)

D = 1 + Y Z/2. (26)

Z and Y are calculated from least squares estimates of Aand B using (23) and (24):

Z = B (27)

Y = 2(A 1)/B. (28)

C. Metrics for Evaluation of Method Performance

Two metrics are used to evaluate the accuracy of theimpedance and admittance parameter estimates over the sim-ulation period. The first is the rms error EP

calculated overall parameter estimates; it indicates how far the estimates arefrom the true values.

Let the errors in the individual parameter estimates beP

i

= Pi

P0, where Pi

refers to the parameter estimatesR

i

, Xi

, Bi

at each time instant ti

, i = [1 . . . 196] and P0 to thenominal parameter values R0, X0, B0. Then

EP

=1

P0

vuut 1

196

196X

i=1

P 2i

. (29)

The second metric is P

, the standard deviation of theparameter errors as a fraction of the nominal values. Thismetric indicates the variability of the parameter error over thesimulation period. P

is given by

P

=1

P0

vuut 1

195

196X

i=1

(Pi

µP

)2, (30)

where µP

= 1/196P196

i=1 Pi

is the mean parameter error.EP

and P

are not defined for conductance G as itsnominal value is zero.

D. Results

The results of the case study are presented in two parts: first,one individual case with a specific set of systematic errors isconsidered; then the aggregated results from 100 000 cases ofsystematic errors are presented.

Page 8: A method for accurate transmission line impedance

6

Time ti (h)

0 1 2 3 4 5 6 7

Corr

ecti

on C

onst

ants

×10-3

-15

-10

-5

0

5

a

φ

b

θ

Fig. 5. This plot shows the values of the identified correction constants overtime for the individual simulation case.

Time ti (h)

0 1 2 3 4 5 6 7

Res

ista

nce

R

)

2.6

2.8

3

3.2

3.4

3.6

3.8Nominal Value

Proposed Method

Least Squares Method

Fig. 6. This plot shows the nominal and estimated values of resistance Rover time for the individual simulation case.

Time ti (h)

0 1 2 3 4 5 6 7

Rea

ctan

ce

X (Ω

)

32.3

32.4

32.5

32.6

Nominal Value

Proposed Method

Least Squares Method

Fig. 7. This plot shows the nominal and estimated values of reactance Xover time for the individual simulation case.

1) Individual Case: Table I lists the values of one set ofsystematic errors that was applied to the voltage and currentphasors as well as the resulting Total Vector Errors (TVE). Theplot in Fig. 5 shows the values of the correction constantsthat were identified using a moving window of N = 8measurements as described in section II-C. It can be observedthat a 0.003 a

r

as

(from Table I), which is consistentwith the assumption that a corrects the net error. Similarobservations can be made for , b, . Fig. 6 to Fig. 8 showthe final parameter estimates over the simulation period.

In Table II the root-mean-square and standard deviation ofthe parameter errors are given. For R,X,B the rms errorof the proposed method is significantly smaller than for theexisting estimator. Similarly, the standard deviation of the error

Time ti (h)

0 1 2 3 4 5 6 7

Su

scep

tan

ce

B (

S)

×10-4

2

4

6

8

10

Nominal Value

Proposed Method

Least Squares Method

Fig. 8. This plot shows the nominal and estimated values of susceptance Bover time for the individual simulation case.

TABLE IIPARAMETER ERRORS FOR ONE INDIVIDUAL CASE

R X B

E (%) PM1 3.51 0.111 1.11LS2 11.9 0.212 38.7

(%) PM1 0.974 0.0855 1.09LS2 2.85 0.111 20.8

1 Proposed Method2 Least Squares Method

TABLE IIIERRORS IN RESISTANCE R FOR 100 000 CASES

Percentile50th 75th 95th

ER (%) PM1 6.35(10) 10.8(1) 16.7(1)LS2 7.07(10) 11.4(1) 17.4(1)

R (%) PM1 0.925(1) 0.998(1) 1.20(1)LS2 2.85(1) 2.86(1) 2.89(1)

1 Proposed Method2 Least Squares Method

is lower, indicating less variability in the parameter estimates.

2) Large Number of Cases: Tables III to V summarizethe results from the simulation of 100 000 different cases ofsystematic error sets. The 50th, 75th and 95th percentile of thedistributions of the root-mean-square and standard deviation ofparameter errors are listed to give an indication of the levelof accuracy and consistency of the applied methods. For eachpercentile the 95% confidence interval is given in brackets. Forresistance R, the distributions of rms error occupy a similarrange for both the proposed and the existing method, withthe 95th percentile at 17%. However, the proposed methodyields significantly lower standard deviations of error at around1%, whereas the existing method yields 2.9%. Both methodsproduce lower errors in reactance X , with rms errors of theorder of 1% and standard deviation of error of approximately0.1%. In contrast, for susceptance B the level of error differsgreatly between the methods. While the proposed methodgives rms errors of 1% to 2%, the existing method resultsin rms errors of over 100%. The standard deviation of errorsis also an order of magnitude larger for the existing method.

Page 9: A method for accurate transmission line impedance

7

TABLE IVERRORS IN REACTANCE X FOR 100 000 CASES

Percentile50th 75th 95th

EX (%) PM1 0.581(10) 0.984(10) 1.52(1)LS2 0.597(10) 1.01(1) 1.56(1)

X (%) PM1 0.0818(10) 0.0890(10) 0.108(1)LS2 0.110(1) 0.111(1) 0.112(1)

1 Proposed Method2 Least Squares Method

TABLE VERRORS IN SUSCEPTANCE B FOR 100 000 CASES

Percentile50th 75th 95th

EB (%) PM1 1.18(1) 1.39(1) 1.82(1)LS2 99.8(10) 168(1) 261(1)

B (%) PM1 1.05(1) 1.06(1) 1.08(1)LS2 21.6(1) 21.9(1) 22.4(1)

1 Proposed Method2 Least Squares Method

IV. DISCUSSION

A. Comparison of Methods

Based on the results presented in the previous section, theproposed method demonstrated equal or better performancecompared to the existing linear least squares-based method.

The linear least squares method finds an optimal estimatefor the parameters of a two-port network; these are then usedto calculate impedance and admittance parameters of the piline. The advantage of this approach over estimating the piline parameters directly, is that it makes use of redundantmeasurements such that constant systematic errors, as mod-elled in this paper, either cancel or only cause a constantoffset in the estimated parameters. However, the linear leastsquares method also assumes constant parameters in time, andeven small variations over a moving window lead to variableparameter errors. This robustness to systematic errors, yetweak accuracy for variable parameters, explains the relativelysimilar results in the accuracy of the resistance and reactanceparameters in the case study for both methods. Thereforeit may appear that there is no significant advantage in thesuggested method. However, one of the crucial differencesis that the proposed method has demonstrated approximately50% less variability in the errors of resistance values. Theresistance is the parameter with the highest temperature sen-sitivity, hence, it is desirable to monitor changes in its value.This can be done to good accuracy even if there is a constanterror in the estimated values, however, the accuracy of theestimated changes deteriorates quickly with increasing errorvariability.

In field applications, the true value of the impedance andadmittance parameters can never be known; thus, the accuracyof estimated parameters has to be assessed on their repeatabil-ity and consistency with expected physical variations. Basedon these criteria, the proposed method has clear advantagesover other estimation techniques.

B. Requirements of the Proposed Method

While the proposed method has strong potential to improvethe accuracy of impedance parameter estimation, it also hassome limitations. The method relies on increased residuals thatare caused by systematic measurement errors to identify cor-rection constants. In the case where the errors have the samesize at both line ends (a

s

= ar

,s

= r

, bs

= br

, s

= r

)there would be no increase in residuals and hence the methodwould not yield any improvement. However, in these cases theerror in the estimated parameters is constant and only of theorder of the systematic errors; therefore the overall effect issmall. Increased residuals only occur if there is variation in theload of the transmission line, which is thus a requirement forthe method to identify correction constants. The required levelof load variation depends on the magnitude of the systematicerrors as well as the random noise in the synchrophasormeasurements. Measurement noise is in turn related to theoverall load level, as the noise increases towards the lower endof instrument scales. A conservative estimate of the minimumload variation would be 10% of maximum line loading.Furthermore, the method assumes that over the time windowthat spans the utilized measurements the parameters are eitherconstant or varying linearly. This implies that the minimumload variation has to occur within this time, which is limitedby the thermal time constant. Depending on the load profileof the transmission line, not all time windows may satisfythese requirements; one possibility of overcoming this issueis to reuse correction constants from previous time windowswith higher load variation. To summarize, the applicabilityand effectiveness of the proposed method depends on thespecific circumstances of the transmission line operation andmeasurement instruments as well as the accuracy requirementfor the estimated parameter values. Further work is needed tobetter understand and predict the relationship between thesefactors.

C. Limiting Assumptions

In presenting the new method in this paper, some assump-tions have been made. Firstly, the method has been definedon a single-phase transmission line model. Most transmissionlines in power networks have three phases, which couple andthus require more complex models. In the case of identicalconductors and symmetric geometry, the method may beapplied to the positive sequence components, provided thatthe behaviour of the systematic error can be modelled as aproportional error in amplitude and additive in phase angle.Further research is required to confirm whether the method canbe effective for various three-phase transmission line systems.

The systematic errors were assumed to be constant, directlyproportional in magnitude and additive in the phase angle.The systematic errors may follow different, non-linear models.Over small ranges, these variations may still be approximatedwell by the error model in this paper. More work is required toinvestigate if and how the method can be adapted to identifycorrection constants for other models and if it can be used toselect the most appropriate error model.

Page 10: A method for accurate transmission line impedance

8

V. CONCLUSION

The contribution of this paper is in the field of accurate,real-time synchrophasor-based transmission line impedanceparameter estimation.

A method was proposed for estimating the impedance pa-rameters of medium-length transmission lines in the presenceof systematic errors in the utilized synchrophasor measure-ments of voltage and current. The method assumes constantor linearly changing parameters over short periods of time andidentifies correction constants through optimization.

The effectiveness of the proposed method was comparedwith that of an existing linear least squares method in acase study of a simulated transmission line. The results arepromising and suggest that the method has significant potentialto improve parameter estimation accuracy in practical fieldapplications. Limits of the method and future work have beendiscussed.

Accurate, real-time synchrophasor-based transmission lineimpedance parameter estimation is a powerful factor in im-proving the performance of power system monitoring, protec-tion and control applications and thus in creating more reliableand resilient electricity networks.

APPENDIX AESTIMATION OF CONSTANTS IN LINEAR PARAMETER

FUNCTIONS

To estimate qR

, rR

from Ri

, i = [1, . . . , N ], vectors R 2RN ,QR 2 R2 and matrix HZ 2 RN2 are defined, where

R =R1 . . . R

N

T,QR =

qR

rR

,HZ =

t1 . . . t

N

1 1 1

T

.

The N-dimensional model R, based on the theoretical modelfR

(ti

) = qR

ti

+ rR

, is given by the matrix equation

R = HZQR + ", (31)

where " = ["1, . . . , "N ]T are error terms. To satisfy the leastsquares criterion, min

PN

i=1 "2i

, QR is computed using

QR = (HTZHZ)

1HTZR. (32)

In the same manner, qX

, rX

are calculated using vectorsX 2 RN ,X =

X1 . . . X

N

T and QX 2 R2,QX =qX

rX

T.To estimate q

G

from Gi

, i = [1, . . . , N ] vectors G,HY 2RN and QG 2 R are defined, where

G =G1 . . . G

N

T,HY =

1 . . . 1

T,QG =

rG

.

The N-dimensional model G, based on the theoretical modelfG

(ti

) = rG

, is given by

G = HYQG + ", (33)

where " = ["1, . . . , "N ]T are error terms. To satisfy the leastsquares criterion, min

PN

i=1 "2i

, QG is computed by

QG = (HTYHY)1HT

YG. (34)

In the same manner, rB

is calculated using vector B 2RN ,B =

B1 . . . B

N

T and QB 2 R,QB =rB

.

APPENDIX BPARTIAL DERIVATIVES OF Z AND Y

Let Vs

, Is

, Vr

, Ir

2 C, = C4 \ Vs

Ir

+ Vr

Is

= 0 , =C4\V

s

+ Vr

= 0. Define complex functions Z : ! C, Y : ! C, where

Z = (V 2s

V 2r

)/(Vs

Ir

+ Vr

Is

) (35)

Y = 2(Is

Ir

)(Vs

+ Vr

). (36)

Rewrite Z as Z = h1/h2 and Y as Y = h3/h4, whereh1 : C2 ! C, h2 : ! C, h3 : C2 ! C, h4 : C2 \V

s

+ Vr

= 0 ! C,

h1 = V 2s

V 2r

, h2 = Vs

Ir

+ Vr

Is

(37)

h3 = 2(Is

Ir

), h4 = Vs

+ Vr

. (38)

Since h1, h2, h3, h4 are complex polynomials, Z and Y arerational functions. By the differentiability of complex polyno-mials and the quotient rule, Z and Y are differentiable at allpoints in and , respectively. The partial derivatives of Zwith respect to V

s

and Vr

are

@Z

@Vs

=2V

s

Vs

Ir

+ Vr

Is

(V 2s

V 2r

)Ir

(Vs

Ir

+ Vr

Is

)2

@Z

@Vr

=2V

r

Vs

Ir

+ Vr

Is

(V 2s

V 2r

)Is

(Vs

Ir

+ Vr

Is

)2.

(39)

The partial derivatives of Y with respect to Is

and Ir

are@Y

@Is

=2

Vs

+ Vr

,@Y

@Ir

= 2

Vs

+ Vr

. (40)

APPENDIX CAPPROXIMATION: ERRORS AT ONE LINE END

To a first order linear approximation, the change in Z causedby changes in V

s

and Vr

is given by

Z =@Z

@Vs

Vs

+@Z

@Vr

Vr

=2(V

s

Vs

Vr

Vr

)

Vs

Ir

+ Vr

Is

(V 2s

V 2r

)(Ir

Vs

+ Is

Vr

)

(Vs

Ir

+ Vr

Is

)2,

(41)

where results from Appendix B have been used. Let therelative change in Z be

Z =Z

Z=

2(Vs

Vs

Vr

Vr

)

V 2s

V 2r

Ir

Vs

+ Is

Vr

Vs

Ir

+ Vr

Is

. (42)

Suppose errors are modelled at both line ends by Vs

= (as

+j

s

)Vs

and Vr

= (ar

+ jr

)Vr

. Then the relative changearound V

s

, Vr

is

Zexact

=2((a

s

+ js

)Vs

2 (ar

+ jr

)Vr

2)

Vs

2 Vr

2 , (43)

where only the first, dominant term is considered. Now sup-pose all errors are modelled to be in V

r

, such that Vs

=0, V

r

= (a + j)Vr

where a = ar

as

, = r

s

. Thenthe relative error becomes

Zapp

=2(a

r

as

+ jr

js

)Vr

2

Vs

2 Vr

2 . (44)

Page 11: A method for accurate transmission line impedance

9

The difference between the exact and approximate relativeerror is

Zexact

Zapp

=2(a

s

+ js

)(Vs

2 Vr

2)

Vs

2 Vr

2 = 2(as

+ js

).

(45)Hence, by modelling all error to be in V

r

, an approximationof 2(a

s

+ js

) is made in the relative error of the impedance,which is constant and of a lower order than the overall errorZ

exact

. Using an equivalent expression for Y , a similarargument can be produced for modelling all errors in currentin I

r

.

REFERENCES

[1] G. Sivanagaraju, S. Chakrabarti, and S. Srivastava, “Uncertainty intransmission line parameters: estimation and impact on line currentdifferential protection,” IEEE Trans. Instrum. Meas., vol. 63, no. 6, pp.1496–1504, Jun 2014.

[2] J.-a. Jiang, J.-z. Yang, Y.-h. Lin, C.-w. Liu, and J.-c. Ma, “An adaptivePMU based fault detection/location technique for transmission lines. I.Theory and algorithms,” IEEE Trans. Power Deliv., vol. 15, no. 2, pp.486–493, Apr 2000.

[3] J. Zaborszky and J. W. Rittenhouse, Electric Power Transmission: thePower System in the Steady State. New York, NY, USA: The RonaldPress Company, 1954.

[4] H. Dommel, “Overhead line parameters from handbook formulas andcomputer programs,” IEEE Trans. Power Appar. Syst., vol. PAS-104,no. 2, pp. 366–372, Feb 1985.

[5] R. Schulze, P. Schegner, and R. Zivanovic, “Parameter identificationof unsymmetrical transmission lines using fault records obtained fromprotective relays,” IEEE Trans. Power Deliv., vol. 26, no. 2, pp.1265–1272, Apr 2011.

[6] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke,“Synchronized phasor measurement applications in power systems,”IEEE Trans. Smart Grid, vol. 1, no. 1, pp. 20–27, Jun 2010.

[7] L. Philippot and J.-C. Maun, “An application of synchronous phasormeasurement to the estimation of the parameters of an overheadtransmission line,” in Fault Disturb. Anal. Precise Meas. Power Syst.,Arlington, VA, 1995.

[8] R. E. Wilson, G. A. Zevenbergen, D. L. Mah, and A. J. Murphy,“Calculation of transmission line parameters from synchronizedmeasurements,” Electr. Mach. Power Syst., vol. 27, no. 12, pp.1269–1278, Nov 1999.

[9] I.-D. Kim and R. K. Aggarwal, “A study on the on-line measurementof transmission line impedances for improved relaying protection,” Int.J. Electr. Power Energy Syst., vol. 28, no. 6, pp. 359–366, Jul 2006.

[10] R. Mai, L. Fu, and Xu HaiBo, “Dynamic line rating estimator withsynchronized phasor measurement,” in 2011 Int. Conf. Adv. Power Syst.Autom. Prot., Oct 2011, pp. 940–945.

[11] M. Bockarjova and G. Andersson, “Transmission line conductortemperature impact on state estimation accuracy,” in 2007 IEEELausanne Power Tech, 2007, pp. 701–706.

[12] IEEE Standard for Synchrophasor Measurements for Power Systems,IEEE Standard C37.118.1, 2011.

[13] “Model 1133a power sentinel GPS-synchronized power quality revenuestandard operation manual,” Arbiter Systems, Paso Robles, CA, USA,Tech. Rep., 2009.

[14] IEEE Guide for Synchronization, Calibration, Testing, and Installationof Phasor Measurement Units (PMUs) for Power System Protection andControl, IEEE Standard C37.242, 2013.

[15] D. Shi, D. J. Tylavsky, N. Logic, and K. M. Koellner, “Identification ofshort transmission-line parameters from synchrophasor measurements,”in 40th North Am. Power Symp., Sep 2008, pp. 1–8.

[16] D. Shi, D. J. Tylavsky, K. M. Koellner, N. Logic, and D. E. Wheeler,“Transmission line parameter identification using PMU measurements,”Eur. Trans. Electr. Power, vol. 21, no. 4, pp. 1574–1588, 2011.

[17] C. Indulkar and K. Ramalingam, “Estimation of transmission lineparameters from measurements,” Int. J. Electr. Power Energy Syst.,vol. 30, no. 5, pp. 337–342, Jun 2008.

[18] Y. Liao and M. Kezunovic, “Online optimal transmission line parameterestimation for relaying applications,” IEEE Trans. Power Deliv., vol. 24,no. 1, pp. 96–102, Jan 2009.

[19] C. Borda, A. Olarte, and H. Diaz, “PMU-based line and transformerparameter estimation,” in 2009 IEEE/PES Power Syst. Conf. Expo.,Mar 2009, pp. 1–8.

[20] K. Dasgupta and S. A. Soman, “Line parameter estimation usingphasor measurements by the total least squares approach,” in 2013IEEE Power Energy Soc. Gen. Meet., 2013, pp. 1–5.

[21] A. M. Dan and D. Raisz, “Estimation of transmission line parametersusing wide-area measurement method,” in 2011 IEEE TrondheimPowerTech, Jun 2011, pp. 1–6.

[22] D. Ritzmann, W. Holderbaum, B. Potter, and P. S. Wright, “Improvingthe accuracy of synchrophasor-based overhead line impedance measure-ment,” in IEEE Int. Work. Appl. Meas. Power Syst., 2015, pp. 132–137.

[23] IEEE Standard Requirements for Instrument Transformers, IEEE Stan-dard C57.13-2008, 2008.

[24] IEEE Standard for Calculating the Current-Temperature Relationship ofBare Overhead Conductors, IEEE Standard 738-2012, 2013.

[25] R. H. Byrd, M. E. Hribar, and J. Nocedal, “An Interior Point Algorithmfor Large-Scale Nonlinear Programming,” SIAM J. Optim., vol. 9,no. 4, pp. 877–900, Jan 1999.

[26] “Electricity Ten Year Statement, Appendix B - System Data,” NationalGrid, Warwick, UK, Tech. Rep., 2014.

Deborah Ritzmann (S’15) was born in Germany. She received the B.Sc.degree in mathematics and physics from University College London, London,UK, in 2012 and is currently pursuing the Ph.D. degree at the University ofReading, Reading, UK, in collaboration with the National Physical Laboratory,Teddington, UK.

The focus of her research is synchrophasor-based overhead line impedancemeasurement for dynamic line rating applications.

Paul S. Wright received the B.Sc. and Ph.D. degrees in electrical andelectronic engineering from the University of Surrey, Surrey, UK, in 1987and 2002.

He spent three years as a research fellow at the University of Surrey work-ing in the field of spacecraft sensors and attitude control. This was followed bythree years at the Central Electricity Research Laboratory where he worked onadvanced control systems. In 1992 he joined the National Physical Laboratory,Teddington, UK, where he is a Principle Research Scientist specializing in a.c.measurements and waveform analysis. His present research interests includea.c. power standards, a.c./d.c. transfer measurements, digital sampling systemsand the analysis of non-sinusoidal / non-stationary waveforms applied topower-quality measurements and smart grid development.

Dr. Wright is a Chartered Engineer and member of the Institution ofEngineering and Technology.

William Holderbaum (M’01) received the Ph.D. degree in automatic controlfrom the University of Lille, Lille, France, in 1999.

He was a Research Assistant at the University of Glasgow, Glasgow, UK,from 1999 to 2001. Currently, he is a Professor in the School of SystemsEngineering at the University of Reading, Reading, UK. His research interestsare in control theory and its applications. These are mainly focused ongeometric control theory in particular Hamiltonian systems and optimizationproblems. This research uses the mathematical engineering skills in order tominimize the energy consumption. Further research relates to control theoryin the definition of multiple agent systems for distributed network composedof storages, loads and generators.

Ben Potter (S’97–M’01) received the M.Eng. degree in engineering sciencefrom the University of Oxford, Oxford, UK, in 2001 and the Ph.D. degree inthe modelling of induction machines from the University of Reading, Reading,UK, in 2005.

He subsequently managed research and development activity for severalyears at Moog Components Group Ltd., including development work onwireless power transfer. He joined the University of Reading in 2009 and iscurrently Associate Professor of Energy Systems Engineering. His academicresearch has been focused on energy systems and power electronics, of variousflavours, for over twelve years, with applications including energy storage,electric machines, wind turbines and wireless power transfer. In 2010, hefounded the Energy Research Lab within the School of Systems Engineering,and this lab focuses on the development of control methods for the newgeneration of energy networks the smart grid to ensure that the integrationof active elements such as renewable energy resources, electric vehicles andenergy storage devices will have positive impacts for both network operatorsand end users.