a major cause of vent related fires is failure to …kellywalsh.org/building_manual/03 maintenance...

15
INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models eVent SD, eVent, Event Plus, and eVent Plus2 (Condensing Boiler Systems) IMPORTANT: DO NOT INSTALL VENTING SYSTEM WITHOUT FIRST READING THESE INSTRUCTIONS. A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF UTMOST IMPORTANCE THAT THIS VENT BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS. US C

Upload: others

Post on 17-Aug-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

INSTALLATION INSTRUCTIONS

OPERATION AND MAINTENANCE MANUALModels eVent SD, eVent, Event Plus, and eVent Plus2

(Condensing Boiler Systems)

IMPORTANT: DO NOT INSTALL VENTING SYSTEM WITHOUT FIRST READING THESE INSTRUCTIONS.

A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS

OF UTMOST IMPORTANCE THAT THIS VENT BE INSTALLED ONLY IN ACCORDANCE WITH THESE

INSTRUCTIONS.

USC

Page 2: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

223

3 & 77333

13134-5456788999

9-10101010111111111111121212139

13131414

Horizontal Termination Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Termination (HT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Different manufacturers have different joint systems and adhesives. Do not mix pipe, fittings or joining methods from different manufacturers.

Proper joint construction is essential for a safe installation. Follow these instructions exactly as written.

Examine all components for possible damage prior to installation. Contact your local Schebler distributor with any questions.

These instructions cover installation requirements for the Schebler listed double wall special stainless steel venting systems: eVent SD, eVent, eVentPLUS and eVentPLUS2. Schebler models eVent SD, eVent, eVentPLUS and eVentPLUS2 must be installed in accordance with local building code and as well as national codes.

Check for unrestricted vent movement through, walls, ceiling, and roof penetrations.

UL LISTING

The venting system shall terminate in accordance with the requirements of CAN/CGA-b149.1, Natural Gas Installation code, or CAN/CGA-B149.2 Propane Installation code.

Refer to The Schebler Company Venting System catalog for the description of all necessary parts.

Full Angle Ring (FR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Flashing (FL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rain Collar (RC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Individual Part Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Pipe and Fitting Assembly for Models eVent, eVentPlus and eVentPLUS2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Support Plate (SP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Wall Support (WS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wall Guide (WG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Floor Roof Guide (FRG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Half Angle Ring (HR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Elbows (30L, 45L and 90L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Venting Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Boiler Adapter Kits (BKF and BKR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 Degree Tee (90T) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Part Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

45 Degree Lateral Tee (45LT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Degree Wye (90Y) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TABLE OF CONTENTS

Termination Height Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vent Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . .

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL Listing USA and Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Clearances and Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Support Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Insulated Thimble (IT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rain Cap (CC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Top Section (TS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exit Cone (EXC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Guy Section (GS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .End Cap (EC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Drain Tee Cap (DTC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Drain (HD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Drain Section (Ds) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL

Check for proper joint construction when joining pipe to fittings.

All Schebler eVent series Models are listed to UL 1738 and ULC 5636-95 for installations manufactured in even and odd diameters.

The venting system must be free to expand and contract. This venting system must be supported in accordance with these instructions.

The Schebler Models eVentSD, eVent, eVentPLUS, and eVentPLUS2 maybe utilized in the same system. Proper installation methods must be followed as called for in these instructions.

Basic Pipe and Fitting Assembly for Models eVentSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Variable Straight (VS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Page 3: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Recommendations that exterior mounted venting systems be enclosed below the roof line to limit condensation and protect against mechanical damage. Methods of providing additional insulation may be specified.

It is suggested that a vent being installed in a corrosive atmosphere be constructed of Type 304, 430 or 316 stainless steel for the outer shell material.

Note: For vertically terminated systems it is recommended that longer horizontal runs be pitched ¼" per foot back

toward the appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance

itself if permitted by the appliance manufacturer.

A requirement to check the joints and seams for gas tightness when using the venting system with a Category III or IV appliance.

MR

These instructions and the catalog identify parts by name followed by a part code. Part numbers are made up of the model, part code, flue inside diameter and material code. The part number is shown on the UL label. EXAMPLE: The part number for a Model eVent (EV), 35” long Straight Section (35S), 8” ID (08), with a AL 29-4C stainless steel liner and an aluminized steel shell (K) would be EV35S08K. eVent Series material codes are shown in the following chart:

Venting systems are to be sized in accordance the ASHRAE Handbook, Equipment Volume, the appliance manufacturer’s instructions, or by contacting The Schebler Company.

CLEARANCES AND ENCLOSURES

VENT ENVIRONMENT

Note: Horizontally terminated systems must be pitched ¼" per foot back toward the appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance itself if permitted by the appliance manufacturer.

AL 29-4C Stainless Steel / 304 Stainless Steel

TERMINATION HEIGHT REQUIREMENTS

KLINER/SHELL MATERIAL

L

AL 29-4C Stainless Steel / 430 Stainless Steel

AL 29-4C Stainless Steel / Aluminized Steel

VENTING APPLICATIONSCODE

If a drain fitting is required by the appliance manufacturer, it must be located as close to the flue outlet as possible.

Models eVent SD, eVent, eVentPLUS and eVentPLUS2 are to be installed as a complete system connecting the appliance(s) to the outdoors, while operating under positive forced draft, negative induced draft, or neutral gravity flow internal pressure conditions using only Schebler models eVent SD, eVent, eVentPLUS and eVentPLUS2 vent parts. No vent part from another manufacturer should ever be mixed with models eVent SD, eVent, eVentPLUS and eVentPLUS2.

Models eVent SD, eVent, eVentPLUS and eVentPLUS2 shall not be routed into, through, to within any other vent such as an existing masonry or factory-built vent that is connected to another appliance.

Vents installed in open rooms or fully ventilated areas on the same story as the equipment connected to it shall have a minimum clearance to combustibles as shown in the following tables:

Multiple category II, III & IV appliances may not be common vented unless approved by the manufacturers. Do not mix natural draft and forced draft appliances together.

AL 29-4C Stainless Steel / 316 Stainless Steel

The maximum rated pressure for which the venting system is intended to be used.

PART IDENTIFICATION

This vent is to be installed unenclosed or with enclosures. If the vent passes through any zone or story of a building above that on which the connected appliance is located, it is to be enclosed in construction having a fire rating equal to or greater than that of the floor or roof assemblies through which it passes. NOTE: Always check with the Authority Having Jurisdiction for material with an appropriate fire rating. If a portion of the vent passes between a dropped ceiling and roof, that portion is to be enclosed in a fire rated enclosure or proper clearance to combustibles are maintained. Vents are not intended to pass through combustible walls. Any wall through which the vent passes must be of non-combustible construction unless proper clearance to combustibles are maintained.

Clearances to non-combustibles shall be necessary for installation, inspection and maintenance.

38-46 965-1168 5" (127mm)47-48

SYSTEMS TERMINATING HORIZONTALLY

inches

1194-1219 6" (152mm)

27-36 686-914 4" (102mm)

mm

Vents are to terminate a minimum of 3-ft. (0.92 m) above the highest point of the roof penetration and 2-ft. (0.61m) minimum

above any portion of a building within 10-ft (3.1 m) horizontally. Consult the Authority Having Jurisdiction about restrictions in

your area. See NFPA 211.

11-16 279-406 2" ( 51mm)17-26 432-660 3" (76mm)

CAUTION – DO NOT PLACE ANY TYPE OF INSULATION OR COMBUSTIBLE MATERIALS IN THE REQUIRED CLEARANCE SPACES SURROUNDING THE VENT.

4 - 6 102 - 152 1" (25mm)7-10 178-254 1.5" (38mm)

44 - 48 1118 - 1219 5" (127mm)

SYSTEMS TERMINATING VERTICALLY

381 - 508 1.5" (38mm)21 - 24 533 - 610 2" ( 51mm)

eVent Series Vent Clearances - Vertically Terminating Systems

550° F (288° C)

102 - 356 1" (25mm)15 - 20

Inside Diameter

34 - 43 864 - 1092 4" (102mm)25 - 33 635 - 838 3" (76mm)

Models eVent SD, eVent, eVentPLUS and eVentPLUS2 are a double wall special stainless steel venting system for gas fired appliances listed as Category II, III, & IV with a maximum flue gas temperature of 550° F, and 40" w.c. positive pressure. Gas vent - BH, Class I/Class II - 245° C . Models eVent SD, eVent, eVentPLUS and eVentPLUS2 is also suitable for other applications that call for an AL 29-4C vent.

Inside Diameter550° F (288° C)

eVent Series Vent Clearances - Horizontally Terminating Systems

inches mm

4 - 14

3

Page 4: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Step 1:

Clean Flanges

Step 2:

Step 4A:

Step 4:

Step 5:

S600 cure time is 3 days at ambient temperature.

Step 3:

This section identifies Models eVent, eVentPLUS and eVentPLUS2 by name and part number or part code. See the section titled “Part Identification” on page 3 of these instructions for part number details. When referring to parts always include the model and flue size to

avoid confusion.

(For eVentPLUS2) Wrap inner band tightly with 4" wide insulation strip provided with the system.

Apply a continuous bead of Schebler part number S600 sealant covering the 1/2" flange of one of the two parts being joined. Fill the "V" groove of the inner band with the S600 sealant provided. See figure 2.

BASIC PIPE AND FITTING ASSEMBLY

Once properly installed, sealant will ooze out from between the band and eVent liner at the

inner band connection. This is a indication that the proper amount of sealant has been applied

and should not be removed. The sealant may be smoothed for a finished appearance.

These instructions comprise both general and specific requirements for all parts in the eVent, eVentPLUS and eVentPLUS2 series product lines only. (For Model eVent SD please refer to the specific instructions for Model eVentSD.

Before beginning an installation, thoroughly review these instructions.

Models eVent, eVentPLUS and eVentPLUS2 INDIVIDUAL PART INSTALLATION

Place outer band around both sections covering the space between the shells. The flanges on the outer band fit into the grooves on the shells. Install nuts/screws and tighten using screwdriver.

Note: For outdoor installations, or installations in areas of moisture, apply a bead of S600 sealant in the groove at upper end of the outer band and at the band overlap.

Figure 4 - Horizontal Installation Orientation

Figure 2

Figure 3

Note:

Figure 5

SEALANT APPLICATION

Join flanged ends of two sections. Install inner band around the two flanges, and use a screw driver to tighten inner band around sections. -See figure 4 for correct orientation . Tap on inner band with rubber or rawhide mallet to ensure a proper tight joint.

Figure 1 - Straight Section

Flange

"V" of Inner Band

Inner Band

Outer Band

4

Page 5: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Step 1:

Step 2:

Step 3:

Step 4:

Step 5:

Model eVentSD INDIVIDUAL PART INSTALLATION

Figure 9

Apply a 3/4" continuous bead of Schebler S600 sealant provided to the outside of the male end approximately 3/8" from the edge. Apply a second 3/8" continuous bead of sealant on the inside of the female end, approximately 3/8" from the edge. Fill the vee groove of the SD inner band with S600.

Insert male end of the eVent SD into the female end until it stops at the end of the stopping bead. Install SD inner band around the joint spacer clips, using a screwdriver to tighten the SD inner band around the clips with provided hardware. Lightly tap on SD inner band with rubber or rawhide mallet to ensure proper tight joint.

S600 cure time is 5 days at ambient temperature.

Figure 8 - Final Inner Joint Connection Figure 10 - Final Outer band Connection

Center outer band over gap between the outer shells of the two sections and tighten with supplied hardware.

Note:

Figure 6 - Typical Straight Section

This section identifies Model eVentSD by name and part number or part code. See the section titled “Part Identification” on page 3 of these instructions for part number details. When referring to parts always include the model and flue size to avoid confusion.

These instructions comprise both general and specific requirements for all parts in the eVent, eVentPLUS and eVentPLUS2 series product lines only. (For Models eVent, eVentPLUS and eVentPLUS2 please refer to the specific instructions for Model eVentSD.

Before beginning an installation, thoroughly review these instructions.

BASIC PIPE AND FITTING ASSEMBLY

Figure 7 - Sealant Application

Clean inside of female end, outside of male and, and vee groove of SD inner band.

Once properly installed, sealant will ooze out from between the band and eVent liner

at the inner band connection. This is a indication that the proper amount of sealant

has been applied and should not be removed.

5

Page 6: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Models eVent, eVentPLUS and eVent PLUS2 only . Refer to specific instructions for Model eVentSD

Variable Straight instructions.

These sections identifies Models eVentSD, eVent, eVentPLUS and eVentPLUS2 by name and part number or part code. See the section titled “Part Identification” on page 3 of these instructions for part number details. Refer to the correct models installation instructions for

specific joint connection instructions. When referring to parts always include the model and flue size to avoid confusion.

GAS FLOW CONDENSATE FLOW

Variable Straights (VS)

Model eVentSD only . Refer to specific instructions for Models eVent, eVentPLUS and eVent

PLUS2 Variable Straight instructions.

Figure 12 – Cutting to Length RequiredFigure 14

Variable Straights (VS)

Apply a bead of sealant between the slip collar and inner liner near the flanged end.

Note:

Figure 11 – Measuring length Variable Straight Length

The inner liner is completed by using the inner liner section and slip collar. The inner liner section is cut to length. Take great care in measuring the length required so both joints can be properly secured before the section is cut. The slip collar will slide on to the inner liner section once cut to complete the ducts inner liner. The crimped end of the liner will connect the same as standard straight sections and is not to be cut. The Variable Straight is not designed to support any load.

The inner liner is completed by using the inner liner section and slip collar. The inner liner section can be cut to length or slipped inside of the next fixed section of pipe. The slip collar will slide on to the inner liner section and will be drawn tight around the raw end of the inner liner. The flanged ends of the liner and slip collar will connect the same as standard straight sections. The outer comes in two halves. The outer can be cut to length or slipped over the adjacent section. The two halves are drawn together on the sides with the supplied hardware. The Variable Straight is not designed to support any load.

Do not cut the crimped end of the Variable Length Section . First cut back the outer shell of the section. Once completed cut back the inner liner of the same section the same distance as the outer shell. Slide on the slip collar over the inner liner and install section as per the instructions found on page 5.

Note:

Figure 13GAS FLOW CONDENSATE FLOW

GAS FLOW

Once properly installed, sealant will ooze out from between the band and eVent liner

at the inner band connection. This is a indication that the proper amount of sealant

has been applied and should not be removed.

Figure 15

CONDENSATE FLOW

FIXED JOINT SECTIONS TO     BE JOINED

SLIP COLLARINNER LINER

INNER "V"BAND ON FLANGED END

SLIP COLLAR BUTTED AGAINST FLANGE INNER "V" BAND

6

Page 7: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Step 1:

Up To 6'

Up To 12'

Up To 8'

Up To 12'

Step 2:

Step 3:

Step 4:

Figure 16 – Horizontal Termination Assembly

Figure 21 – Termination Requirements Above a Flat Roof

Note: For vertically terminated systems it is recommended that long horizontal runs be pitched ¼" per foot back toward the

appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance itself if permitted

by the appliance manufacturer.

Utilizing the Wall Thimble Clips, secure the Wall thimble to the inside of the wall by fastening the clips to the Wall Thimble and the wall being penetrated. Space the clips equally around the perimeter of the Wall Thimble to ensure tight installation.

eVent Series Horizontal Support Spacing

eVentSD When Terminating Vertically

eVent, eVentPlus & eVentPlus2

Mount the Wall Flashing over the Wall Termination sealing the gap between the Wall Thimble and the wall opening. Level the Flashing and seal around perimeter of the Inner Liner with a bead of S600 sealant.

HORIZONTAL TERMINATION (HT)

BASIC eVentSD WALL TERMINATION ASSEMBLY

Figure 19 – Final Horizontal Termination InstallationThe Horizontal Termination is utilized when an appliance is exhausted out the sidewall of a building. The system includes a duct Horizontal Termination, Wall Thimble, Thimble Clips, and Wall Flashing.

Note: Minimum horizontal clearance from appliance outlet to wall of final termination is 3'.

Figure 17 – Installation of the Wall Thimble

eVentSD When Terminating Horizontally

HORIZONTAL TERMINATION REQUIREMENTS

Exhaust systems terminating out a buildings sidewall have additional considerations as compared with

traditional through roof terminations. Please refer to specific instructions contained in this section.

Center the Horizontal Termination in the Wall Thimble. A minimum of 3" of inner liner of the Horizontal Termination must penetrate past the outside of the wall and Wall Thimble. See figure 18.

Figure 20 – Termination Requirements Above a Pitched Roof

Cut a opening in the wall just large enough to allow the Wall Thimble to penetrate the wall. Keep the Wall Thimble flush with the outside face of the wall.

Figure 18 – Installation of the Horizontal Termination

VERTICAL TERMINATION REQUIREMENTS

eVent Series Horizontal Support Spacing

eVent, eVentPlus & eVentPlus2

Note: Horizontally terminated systems must be pitched ¼" per foot back toward the appliance being vented. Ensure any

condensate is collected by strategically placing drains, or the appliance itself if permitted by the appliance manufacturer.

7

Page 8: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

1.

2.

3.

1.

2.

90 DEGREE TEE (90T)

Place the starter section on the appliance outlet and tighten in place with the hardware provided. All other vent parts can now be installed (see joint assembly for the proper procedure).

The boiler kits include a seal ring that will cover the gap between the inner and the outer shell. The seal ring clamps around the outer shell pipe and is held in place with (4) ¼” x 1 ½” bolts.

Figure 23 - Raw Boiler Adapter

When properly supported, the 90-Degree Tee will support 50 feet of vertical vent. This fitting is used to connect horizontal pipe runs into the vertical vent as well as a drain and/or inspection opening. Where access for a drain or an inspection opening is required, the following method for support can be used:

Figure 24 - 90° Tees

A. Suspended Tee - Support Plate or Wall Support at upper tee joint as shown in Figure 17.

Figure 25 - Suspended Tee

Apply a continuous bead of the proper sealant to the

inner flange of the appliance outlet.

Apply a continuous bead of the proper sealant to the inner flange on one end of the Starter Section.

Place the required number of "C" clamps over the

boiler flange and starter ring and tighten clamps. The

flange can be field drilled to match the appliance

outlet if desired. All other vent parts can now be

installed (see joint assembly for the proper

procedure).

B. Two axis support - This method is recommended if the total thermal expansion is expected to be above ¼” as shown in Figure 18.For a raw appliance outlets the Boiler Kit Raw (BKR) should be

used. The Boiler Kit Raw consists of a collar type starter section. The Boiler Kit Raw is installed in the following procedure:

BOILER ADAPTER KITS (BKF and BKR)

For flanged appliance outlets, the Boiler Kit Flanged (BKF) should be used. The Boiler Kit Flanged consists of a split starter ring, starter section and the required number of "C" clamps for the installation. The Boiler Kit Flanged is installed in the following procedure:

Figure 22 - Flanged Boiler Adapter

Figure 25 - Two Axis Supported Tee

Center the starter section on the boiler flange and place the two piece Split Starter Ring over the bottom flange on the Starter Section. Be sure that the tabs on the Split Starter Ring overlap and all parts fit snug.

Starter Section"C" Clamp

Split Starter Ring Boiler outlet

Rolled Flange to be connected to next section of pipe

Raw end to connect to raw boiler outlet

8

Page 9: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

1.

2.

3.

4.

The Support Plate consists of a split clamp flange, split plate and necessary hardware. The split clamp flange and the split plate are used to clamp the inner flanges together and are turned 90 degrees apart. The notches in the split plate and in the clamp flange are to accommodate the inner band end clips, allowing the "V" to rest solidly on the split plate. The installation procedure is as follows:

Figure 26 - Drain Tee Cap

The eVent, eVent Plus and eVent Plus2 has a 1" drain pipe that must be connected to a suitable drain. The eVentSD has a 1/2" drain connection.

Figure 30 - Support Plate Attachment

Connect the joint to be supported by use of the inner band as previously discussed.

Connect the split clamp flange to the split plate with the provided hardware. The split plate should be below the finished joint and the clamp flange should be above the finished joint.

45 DEGREE LATERAL TEE (45LT)

The Support Plate offers the greatest strength for support of the eVent Series Venting System. It will provide vertical support and will provide for joint alignment and support for horizontal applications. Between any two fixed points in a system or whenever an adjustable length must be used to prevent the bending of tees and other fittings, locate and secure the Support Plate as necessary by means of structural ties to the building.

DRAIN TEE CAP (DTC) 90 DEGREE WYE (90Y)

The Support Plate must be secured to structural members of the building, which can adequately support the weight of the vent as shown on page 12 of these instructions.

These elbows must be protected from the effects of thermal expansion.

The Wye fitting is used when the vertical vent is located between two boilers and a low-pressure loss system is required. The Wye should be installed with the usual precautions observed for thermal expansions.

Figure 29 - 90Y

The Drain Tee Cap must be connected at all times to a suitable drain. Upon entering the vent, rain will wash down and remove any corrosive combustible residue. The Drain Tee Cap must be installed with sealant at its mating surfaces with the flanged joint. This will ensure that moisture is drained through the drain as intended and will provide a tight seal. The Tee Cap can be installed for inspection access as required.

SUPPORT PLATE (SP)

3/8” x 1 ½” bolts should be used in all of the inner clamp flange holes. Tighten all bolts.

Figure 27 - 45°, 30° and 90° Elbows

Figure 28 - 45° Lateral Tee

30, 45 AND 90 DEGREE ELBOWS (30L, 45L AND 90L)

For venting systems that require a 45 degree entry to the vertical vent, the 45 Degree Lateral Tee (45LT) may be used. The 45 Degree Lateral Tee should be supported in the same way as the 90 Degree Tee. When properly supported, the 45 Degree Lateral Tee will support 50 feet of vertical vent and may be installed with a Drain Tee Cap or End Cap.

Install the special outer bands provided and seal with sealant.

9

Page 10: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

1.

2.

3.

4.

5.

6.

CAUTION: Always maintain proper clearances to combustibles when installing all guides and supports. Keep all insulation away from required clearance (air) spaces surrounding the vent. Guides and supports are only suitable for attachment to non-combustible construction due to possible heat conduction.

Figure 34 - Floor Roof Guide

WALL GUIDE (WG)

3 x 3 x 1/4

Locate and bolt the entire assembly to the wall with (8) ½” dia. bolts.

The Wall Support is intended for attachment to non-combustible structures. When attached, the Wall Support provides a fixed point in the vent system. Install a Variable Length below a Wall Support to provide the necessary expansion compensation. The Wall Support, when properly installed, will allow for the required clearances to combustibles along the wall and will support the length of pipe outlined on page 12 of these instructions.

Figure 33 - Wall Guide

3/8” x 1 1/2” bolts should be used in all of the inner clamp flange holes. Tighten all bolts.

Figure 31 - Support Plate Bracing

Bolt the wall brackets to the split plate assembly with the (6) 3/8” x 1 ½” bolts as provided.

Floor Roof Guides are used to provide lateral support for the vent in the roof and floor opening. The Floor Roof Guide is to be bolted to non-combustible construction in (4) four places.

eVent Series Size Framework Bracing

6 x 2 x 3/8 or equivalent 4 x 4 x 3/838" - 48"

The Wall Support consists of two split plates, brackets and all necessary hardware. The notches in the split plates on the Wall Support are to accommodate the inner band end clips, allowing the "V" to be clamped between the split plates. Installation for the Wall Support is accomplished with the following procedure:

Figure 32 - Wall Support

The wall guide is used to protect the vertical vent from lateral wind loads and to allow for thermal expansions. When assembled, the proper installation location is at a joint but below the outer band. The outer wall of the vent must be able to move away from the outer ring of the wall guide. When properly attached to a combustible wall, the Wall Guide will maintain the proper clearances to combustibles.

Wall Guides should be equally spaced along the wall at spacings no greater than 16’ for 4” through 10” diameters and 24’ for 12” through 48” diameters.

22" - 36" 5 x 2 x 3/16 to 6 x 2 x 3/16 or equivalent

2 x 2 x 3/16

WALL SUPPORT (WS)

Connect the joint to be supported by use of the inner band as previously discussed.

FLOOR ROOF GUIDE (FRG)

Connect the split clamp flange to the split plate with the provided hardware. The split plate should be below the finished joint and the clamp flange should be above the finished joint.

Apply sealant around outer Half Bands and support plate for exterior installations.

4" - 20" 2 x 1 x 3/16 to 5 x 2 x 3/16 or equivalent

Proper performance and long service life of the Model eVent Series Venting System requires that the vent be rigidly braced and supported. Every installation offers unique support and bracing requirements and the following guidelines will provide minimum acceptable sizes for the mechanical hardware supplied by others. When the support plate is bolted to framework 3/8” bolts should be used in all of the holes on the perimeter of the support plate.

10

Page 11: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Up To 6'Up To 8'

Up To 12'

Up To 16'Up To 24'

1.

2.

3.4.

All eVent Series Diameters 11" to 48"

Event, eVentPlus & eVentPLUS2

eVentSD When Terminating Horizontally

eVent Series Vertical Guide SpacingAll eVent Series Diameters 5" to 10"

Figure 37 - Insulated Thimble

Figure 35 - Full Ring and Half Ring

FLASHING AND RAIN COLLAR (FL AND RC)

Apply a silicon sealant to fill any gaps and joints on the collar and tighten all bolts.

INSULATED THIMBLE (IT)

Apply a bead of the proper sealant to the flange of the inner pipe to receive the Rain Cap.

The Rain Collar is secured around the pipe immediately above the flashing and should be sealed with a silicone sealant.

Install the provided collar as shown.

Figure 36 - Roof Penetration

The insulated thimble is used in conjunction with the flashing and rain collar when clearances to combustibles cannot be maintained at a roof penetration.

The full and half rings are used to guide the vent either vertically or horizontally. The rings should be placed at intervals shown in the chart below and securely connected to the building structure. The diameter of the Full Ring is slightly larger than the pipe. This will allow the pipe to slide within the ring. This movement must be allowed to compensate for thermal expansion.

Both the Flashing and the Rain Collar are designed to fit the outside of the Model eVent Series Venting System. They are constructed of galvanized steel and should be protected from corrosion by cleaning and painting. The Flashing is non-ventilated and for non-combustible and combustible flat roofs. Flashings of a special pitch are available upon request.

RAIN CAP (CC)

The Insulated Thimble should be dropped through the roof opening. The (4) four tabs will set upon the roof deck and nailed or bolted down. The flashing is then set over the Insulated Thimble.

FULL AND HALF ANGLE RINGS (FR AND HR)

Place the Rain Cap on the existing inner flange and attach the "V" band as previously mentioned.

The Rain Cap provides partial protection from rain and debris. The Rain Cap is mounted on the end of a standard pipe section with the use of a inner band. A closure ring is provided to close off the space between the inner and outer liners. A minimum clearance of 8 feet (2.44 m) is recommended to ensure that all exhausted products are dispersed away from the building and intakes. To install the Rain Cap, the following procedure should be used:

The Flashing should be protected from lateral movement of the stack by use of the Full Ring or the floor/Roof Guide.

eVentSD When Terminating Vertically

Figure 38 - Rain Cap Assembly

eVent Series Horizontal Support Spacing

11

Page 12: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

Figure 42 – Rigid Guying Angle

When the height above the roof line exceeds 12 feet, a Guy Section is recommended. The inner flanges of the Guy Section are connected in the same procedure as the typical pipe sections. The outer shell is then sealed by using special half bands and sealant. Guy wires or braces are to be attached to the horizontal flanges of the Guy Section (See Figure 35). The cables and pipe guys must be slightly loose to allow for thermal expansions. To reduce the thermal expansion effects on rigid bracing or guy wires, a Support Plate (SP) or Wall Support (WS) may be installed at or below the roof line. Guy tensioners may be required if the thermal expansion exceeds the allowable slack in cables.

Figure 43 – Bracing Requirements

Figure 44 – Maximum Freestanding Height

The Exit Cone is installed using the same procedure as the Rain Cap (CC).

Figure 41 - Guy Section

The Top Section is installed using the same procedures as a Rain Cap (CC).

Figure 39 - Top Section

TOP SECTION (TS)

EXIT CONE (EXC)

GUY SECTION (GS)

Figure 40 - Exit Cone

To clean the flue or replace the Rain Cap, reverse the above procedure. To reinstall, follow the installation procedure .

12

Page 13: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

inches mm feet meters feet meters

4-6 152 306 93.27 193 58.83

7-8 203 269 81.99 171 52.12

9-10 254 255 77.72 164 49.99

11-12 305 237 72.24 153 46.63

13-14 356 227 69.19 148 45.11

15-16 406 213 64.92 140 42.67

17-18 457 201 61.26 134 40.84

19-20 508 192 58.52 129 39.32

21-22 559 180 54.86 123 37.49

23-24 610 172 52.43 119 36.27

25-26 660 161 49.07 113 34.44

27-28 711 151 46.02 108 32.92

29-30 762 142 43.28 103 31.38

31-32 813 161 49.07 120 36.58

33-34 864 151 46.02 114 34.75

35-36 914 113 34.44 88 26.82

37-38 965 101 30.78 81 24.69

39-40 1016 93 28.35 77 23.47

41-42 1067 85 25.91 73 22.25

43-44 1118 76 23.16 68 20.73

45-46 1168 68 20.73 64 19.51

47-48 1219 60 18.29 60 18.29

If the height above the roof line is less than that specified above, no guying or bracing is required. However, a Insulated Thimble (IT), Floor/Roof Guide (FRG) or Full Ring (FR) at the roof line is necessary to protect the Flashing (FL) from side loads caused by wind. For heights above the roof line greater than that shown above, the vent must be guyed or braced. Guying or bracing is accomplished by use of the Guy Section (GS) Full Ring (FR) or Wall Guide (WG). Guy wires or braces are to be attached to the horizontal flanges of the Guy Section. While 3 guys are usually sufficient, it is recommended that 4 equally spaced wires at an angle of 45° from the vertical be utilized. The cables and guys must be slightly loose to allow for the thermal expansion. Rigid bracing requires two braces with not less than 60 angle between them. The braces must be attached to a Guy Section (GS) or Full Ring (FR).

12” - 48” (305-1219mm) 12 feet (3.66m)

Figure 46 - Drain Section

8 feet (2.44m)Maximum Height

Whenever the end cap is removed for inspection purposes the flanges must be cleaned and resealed when reinstalling the part.

MAXIMUM HEIGHT ABOVE TOP LATERAL BRACE OR GUY

LIMITATIONS

Vent Inside Diameter4” - 10” (102-254mm)

The drain section is used to drain rain water and condensation from within the stack. The NPT nipple should be connected to a suitable drain.

DRAIN SECTION (DS)

END CAP (EC)

HORIZONTAL DRAIN (HD)

Figure 47 - Horizontal Drain

The horizontal drain is used to drain rain water and condensation from within the breeching. The NPT nipple should be connected to a suitable drain.

Figure 45 - End Cap

eVent SERIES SUPPORT LIMITS

SUPPORT PLATE (SP) WALL SUPPORT (WS)SECTION INSIDE DIA.

DRAIN TEE CAP (DTC)

The drain tee cap is installed exactly the same as the end cap.

The end cap is installed by connecting the inner cone to the adjacent pipe section with a inner band and sealant. The outer cover piece is then fitted over the outer shell and bolted into place with (2) ¼” x 1 ½” stainless steel bolts.

The end cap is used to cap off a tee and to allow a means to enter the system for inspection and cleaning.

13

Page 14: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

1.

2.

3.

4.

5.

6.

A licensed or qualified vent sweep should be contacted to clean the vent. Contact local building or fire officials about restrictions and installation inspection in your area.

It is recommended that exterior mounted venting systems located in geographical areas which experience sustained low ambient temperatures be enclosed to reduce or limit condensation, creosote buildup and poor draft.

For tee caps, adequate clearance is required around clean-outs to assure accessibility for removal of caps and products accumulated within the vent.

For further information see NFPA 211, latest edition, chapter titled Maintenance.

OPERATING PRECAUTIONS

Supports, guys, braces, etc. should be inspected at least annually to make sure bolts are tight.

After the installation of the vent or exhaust system,

ensure that the required clearances are maintained and

that the system continues to be supported properly.The venting system should be inspected if there is any evidence of damage to the vent system, and at least annually, for internal deposits, soundness and correct clearances. Cleaning and repairs shall be as needed.

Painted portions of the vent shall be cleaned and touched-up or repainted as required to prevent corrosion.

MAINTENANCE

Caulking on exterior portions of the vent, flashing, rain collar, etc. should be inspected and repaired or replaced as needed to prevent leakage.

Venting and Exhaust Systems

14

Page 15: A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO …kellywalsh.org/building_manual/03 Maintenance Data... · Lightly tap on SD inner band with rubber or rawhide mallet to ensure

5665 Fenno Rd.Bettendorf, IA 52722

Jan 2012 Phone: 563-359-0110 Fax: 563-359-8430www.Schebler.com

15