7. wa police building code custodial design guidelines

Upload: kazz-bastidas

Post on 10-Feb-2018

265 views

Category:

Documents


8 download

TRANSCRIPT

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    1/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 1

    1 CUSTODIAL DESIGN GUIDELINES1.1 BACKGROUNDUntil convicted by a Court, a person detained by the police is presumed innocent and afforded a number of rights.Custodial facilities enable the police to detain people charged with an offence. The detainee may be in a stimulated/ aggressive condition. Once convicted of an offence, a prisoner may serve their sentence in the facility.

    With the number of deaths in custody during the 1980's, the community became increasingly concerned with the

    treatment of detainees within both the Prison system and Police Lockups, culminating with the Royal Commissioninto Black Deaths in Custody.

    In response to these concerns and the Royal Commission, the Australian Police Ministers Council endorsed anindicative model for the design and operation of custodial facilities in all jurisdictions. See Standard Guidelines forPolice Custodial Facilities in Australia.

    Using this model, the Western Australia Police Service developed a set of standards, comprising the

    Lockup Management Manual, and Custodial Design Guidelines (previously the Safe Cell Guidelines).ACKNOWLEDGEMENTThe Police Service acknowledges the involvement of the Department of Housing & Works (DHW), previously theDepartment of Contract & Services, Western Australian Building Management Authority, in the development of theSafe Cell Guidelines.

    1.2 INTRODUCTIONThe Custodial Design Guidelines

    outline the specialised technical requirements for the design of custodial facilities, and standardises the critical building components / elements required in a safe cell. The approved components (see

    page 26) have been selected after extensive testing. Ongoing testing will result in regular updating of this

    guide.

    Variations from these guidelines must be approved by Police Land & Building Management Branch or a delegatedrepresentative.

    1.2.1 STANDARD DETAILSA complete set of standard details stamped preliminary will be issued with the brief. The commissioned consultant

    shall advise the DHW Contract Manager of the standard details required for incorporation into the contractdocuments. A non-preliminary set of required standard details will be issued. These shall be bound unalteredin thecontract specification.

    Please notify the Client Manager (Police) - Client Services - Department of Housing & Works Services of anyerrors or discrepancies in the standard details.

    Refer to the Standard Detail section for an index of the current standard details.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    2/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 2

    1.3 DESIGN PHILOSOPHY1.3.1 CUSTODIAL FACILITIESThe basic philosophy behind the design standards is that all detainees are entitled to certain recognised standards of

    care which provide for their basic human rights in an environment that ensures respect for human dignity andsafeguards the individuals health and well-being.

    Detainees should have access to certain services and in some cases, be given control over those services, i.e. toilet,drinking water from a hygienic source, etc.

    The design should emphasise human interaction between detainees and personnel and allow an appropriate meansof visual and / or audible communications between them.

    The custodial facilities cell and office areas should not appear overtly punitive or repressive.

    The purpose of a custodial facilities is seen to be for the secure custody / detention of a person while awaiting bail,court attendance, or serving a short sentence. The level of security should reflect the majority of the types of

    charges individuals are detained for, rather than the possibility of the need to detain a maximum security prisoner.For example, in an area where the majority of charges relate to offences against good order, cells should bedesigned for that level of security while providing for the environment of that particular region.

    1.3.2 SAFE CELLSThe philosophy of safe cell design is to create a cell environment that is:

    not degrading or unsafe to the detainee; not unsafe to the police; and assists the police in the supervision of detainees.

    1.3.3 DUTY OF CAREThe operational requirements associated with exercising "a duty of care" have resulted in custodial facilities onlybeing provided in District Complexes and isolated stations. In all other stations, holding rooms will be provided toenable short term secure detention for a detainee awaiting charging or transfer to a overnight custody / detentionfacility.

    The provision of electronic surveillance is intended as a further aid to assist operational staff in determining the

    health of detainees held in custody. These systems are intended to provide on-site surveillance only. The WA PoliceBuilding Code does not address the issue of off-site monitoring.

    1.4 DESIGN OBJECTIVES1.4.1 CUSTODIAL FACILITIESWithin a custodial facility there are two secure areas:

    Office Areas where detainees are bailed and receive visitors, processed and questioned with access to medical facilities;

    Cell Areas where detainees are detained.The size and complexity of these areas varies.

    The design of a custodial facilities should take into account:

    the purpose of a custodial facilities; the need to restrict public visibility; the ethnicity or culture of the majority of the detainees coupled with the need to detain a variety of cultural

    backgrounds;

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    3/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 3

    the type of offence the person is detained for; the provision to the detainee of an environment which is pleasant and provides access to basic facilities; the elimination of all potential suicide aids within cells; the need to detain a maximum security prisoner without the risk of escape or placing police at risk; that if a courthouse is located in town, the number of detainees held will increase; the recommendations of the final report of the Royal Commission into Aboriginal Deaths in Custody.The design process of such facilities should include consultation with relevant groups.

    Detainees considered at risk of self harm, both in the metropolitan area and near country centres, will be transferredto East Perth Custodial facilities.

    1.4.2 SAFE CELLSTo design a totally suicide proof cell is almost impossible. These guidelines seek to eliminate the opportunitiespresented in the construction of the cell to inflict self harm.

    For ease of supervision and access, cells need to be grouped together and in close proximity to staff areas e.g.

    General Office, Charge Room, Staff Entry, etc.

    Separation of male and female detainees is required.

    1.4.3 CUSTODIAL FACILITIES TYPESCustodial facilities design can be divided into three broad categories, depending on locality. These are considered to

    be ideal for the specified area. However, the design should reflect the unique requirements of each town or area,while adhering to the basic philosophy of custodial facilities design.

    1.4.3.1 REMOTE AREA CUSTODIAL FACILITIESThe custodial facilities population is substantially aboriginal, usually male and generally detained for offencesagainst good order. There is also the likelihood of a number of sentenced prisoners (trustees) serving short terms ofimprisonment.

    The design of the custodial facilities should provide for maximum security prisoners (male, female and juveniles)who can be detained separately with access to secure but separate exercise yards.

    The majority of aboriginal detainees / prisoners prefer to share a cell with access to a security compound wherethey can sleep when the weather is hot, and cook and consume food. The security compound should be in line ofsight, or at least within hearing, of the General Office, enabling detainees / prisoners to attract the attention of anofficer.

    A visiting area should be provided to allow families to visit detainee / prisoners while maintaining some level ofsecurity. This area should:

    be fenced and grassed allowing detainees / prisoners contact visits, or where practicable, visitor access throughthe dual security compound fences;

    have trees or shelters; and have a drinking fountain.The custodial facilities should be designed to take advantage of prevailing winds and be sited in such a way as toavoid the harshness of the prevailing climate.

    This is recommended for places like Fitzroy Crossing, Roebourne or Laverton. The custodial facilities at Halls

    Creek is an example of this design.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    4/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 4

    1.4.3.2 COUNTRY CUSTODIAL FACILITIES DESIGNThis is recommended for towns in the wheatbelt or the south west of the State where the custodial facilitiespopulation is predominantly aboriginal. There will be fewer prisoners serving short sentences as each station wouldhave access to a prison. A shaded and grassed fenced visiting area should be incorporated to allow detainees /

    prisoners contact visits, or where practicable, visitor access through the exercise compound fence. The extent of the

    custodial facilities office area is increased over that provided in a Remote Area Custodial facilities.

    1.4.3.3 CITY / MAJOR CENTRE CUSTODIAL FACILITIES - OVERNIGHTDETENTION

    This design is recommended for the city / metropolitan area or for larger country towns where the custodial

    facilities population is likely to be more transient and diverse. In addition, detainees face a wider variety of charges,often of a more serious nature. There will be fewer prisoners serving short sentences as each station would haveaccess to a prison.The custodial facilities at Kalgoorlie and Joondalup are examples of this design.

    1.4.3.4 CITY / MAJOR CENTRE CUSTODIAL FACILITIES - NO OVERNIGHTDETENTIONThis design is recommended for the city / metropolitan area or for larger country towns where the custodialfacilities population is likely to be more transient and diverse. In addition, detainees face a wider variety of charges,

    often of a more serious nature. If overnight detention is required the detainees are transferred to another facility.There will be no prisoners serving short sentences.

    The custodial facilities at Cannington and Australind are examples of this design.

    1.4.4 CELL TYPEThe five types of safe cell, which are described in detail on the activity space data sheets, are:

    Padded Cell; General Cell Level A, B and C; Trustee Cell; Police Holding Cell Type A; and Court Holding Cell Type B.

    1.4.4.1 DETERMINATION OF CELL TYPE AND NUMBERThe number and type of cells provided in a station varies. However, General Cell Type B and Holding Cell Type Aare considered to be standards.

    The following criteria shall be used in assessing the number and type of cells required:

    length of custody / detention time; number and sex of detainees; number of detainees held in isolation; availability of other cells; staff numbers available for detainee supervision; distance of cells from continually manned location; number of detainees likely to attempt self harm; type of offences committed by detainees; and number of trustees located in the custodial facilities.

    1.4.4.2 CELL COMPONENTSThe following table outlines the building components / elements that shall typically be provided in each cell type.Refer to activity space data sheets for more information.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    5/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 5

    BUILDING

    COMPONENTS /

    ELEMENTS

    TYPE A

    HIGH RISK

    GENERAL

    CELL

    TYPE B

    MEDIUM RISK

    GENERAL

    CELL

    TYPE C

    LOW RISK

    GENERAL

    CELL

    PADDED

    CELLTRUSTEE

    CELL

    GLASS FRONT Yes Yes Yes No YesTOILET Yes Yes Yes No YesSHOWER No No No No NoDRINKING UNIT Yes Yes Yes No YesBENCH No No No No NoBED PLINTH Yes Yes Yes No YesMECHANICALSYSTEMS

    Yes Yes Yes Yes Yes

    CELL ALARM Yes Yes Yes No YesINTERCOM Yes Yes No No YesAUDIO MONITORING Yes No No Yes NoCCTV Yes Yes Yes Yes YesSMOKE DETECTION Yes Yes Yes Yes Yes

    COURT

    HOLDING

    CELL

    TYPE B

    POLICE

    HOLDING

    CELL

    TYPE A

    POLICE

    WAITING

    ROOM

    GLASS FRONT Yes Yes YesTOILET No Yes NoSHOWER No No NoDRINKING UNIT No Yes YesBENCH Yes Yes YesBED PLINTH No No NoMECHANICALSYSTEMS

    Yes Yes Yes

    CELL ALARM Yes Yes YesINTERCOM No Yes NoAUDIO MONITORING No No NoCCTV Yes Yes YesSMOKE DETECTION Yes Yes Yes

    1.5 DESIGN CRITERIA1.5.1 CUSTODIAL FACILITIESGenerally, the technical requirements for custodial facilities, excluding cells, is described in the Technical CriteriaSection. The following outlines unique or specialised technical requirements for the design of custodial facilities.

    1.5.1.1 GENERALThe design shall allow for the easy movement of sick / injured detainees by stretcher from the custodial facilities to

    an Ambulance.

    All glass in the custodial facilities areas, where detainee may be left unattended, shall be of the approved type andpane size. Elsewhere, a laminated glass shall be used. Each pane of glass shall have the brand name indeliblymarked in one corner.

    Walls in heavy wear areas such as Charge Rooms, cell corridors etc. shall have approved anti- vandal paint applied

    to a height of 1550 mm.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    6/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 6

    The cleaning of custodial facilities, usually undertaken by detainees, often involves the use of considerable volumeof water. Accordingly, adequate drainage both internally and externally shall be provided.

    Man holes shall not be located in those spaces where detainees may be left unattended e.g. search room, as they canbe used as an escape route.

    1.5.1.1.1 CONTROLSAll mechanical system controls that to be used by the occupiers shall be clearly labelled indicating the name, as perthe brief, of activity space(s) served and the type of system. e.g. Charge Room Exhaust Fan, etc.

    All electrical switches that to be used by the occupiers shall be clearly labelled indicating the name, as per the brief,of activity space(s) served and the type of system. e.g. Holding Room Lights, Security Compound Power Point

    Isolating Switch, etc. Where a large control panel is provided, typically in the Charge Room, the switches shall begrouped by function.

    1.5.1.2 ELECTRICALEmergency lighting and exit lighting shall be installed in all detainee handling areas in accordance with theBuilding Code of Australia.

    To minimise the risk of electrocution, should a light fitting be dismantled, lighting to cells and exercise yards shallbe put on separate final sub circuit(s) and fed from 30mA residual current circuit breakers.

    1.5.1.2.1 POWERNo GPO's shall be installed in detainee handling corridors or exercise yards.

    Electrical accessories located in the Charge Room and the associated Custodial facilities areas shall be Clipsal flush

    stainless steel plate type or similar. Secure switch mechanisms to the flush plate with fixing screws.

    1.5.1.2.2 COMMUNICATION SYSTEMSThere are a range of communication systems which may be installed in custodial facilities to assist operational staffin determining the well being of detainees held in custody. These systems are intended to provide on-sitesurveillance and monitoring only.

    The operation of the systems is to be as simple as possible, so that police officers transferring to a station can be

    quickly instructed in its operation.

    The activity space data sheets indicate the communication systems, which shall be provided in each activity space.The detailed requirements for each system are described below.

    1.5.1.2.2.1 CELL ALARMS AND AUDIO MONITORINGThese systems provide detainees with a mechanism to instigate calls for staff assistance.

    1.5.1.2.2.1.1CUSTODIAL FACILITIES ALARM CONTROL PANELDepending on the systems installed, the following shall be incorporated on the Control Panel:

    Custodial facilities layout, including illuminated cell numbers / room names. LED's for staff duress alarmbuttons outside area of layout should be located under the layout and clearly labelled. Different colour LEDsshall be used to differentiate between cell and staff alarm points.

    Cell Alarm System - illuminated buzzer mute buttons (yellow LED steady), when muted light to remain on; tamper indicator lights (red LED steady); buzzer test switch;

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    7/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 7

    duress indicator lights (red LED flashing); and power on switch (green LED steady).

    Audio Monitoring System - illuminated cell selection switches (yellow LED flashing call request, green LED steady call

    accepted);

    cell audio monitoring volume controls,

    illuminated cell radio / music selection switches, audio monitoring speaker including volume control, and microphone;

    Brief instructions (up to 4 lines) covering system(s) operation. An illuminated text display indicating location and type of alarm.

    The control panel shall be mounted flush with finished wall or cupboard, depending on location, surface.

    The control panel shall be duplicated in the Security / Communications Room or a continually manned location i.e.General Office and the Charge Room, unless these two rooms are immediately adjacent, or the Charge Room isoccupied on a 24-hour basis.

    In large custodial facilities, a dedicated printer or Personal Computer shall be attached to the Cell Alarm and AudioMonitoring system for alarm logging. The logging device should be located in the Security / CommunicationsRoom or Communications Room / Alcove and shall be programmed to log the time, date and cell number of alldefined activities. The defined list of activities includes buzzer mute on / off, cell alarm call and reset, cell callacknowledge and cell call reset and tamper. The control panel shall hold up to 1,000 events before over writing thefirst event. The event log shall not be lost if the control panel looses power.

    When the station is not manned 24 hours a day the Cell Alarm System and Audio Monitoring System shall becapable of being switched to the Officer in Charge's residence. Provide a duplicate alarm panel in a discretelocation within the quarters. Ensure the buzzer can be clearly heard in the main bedroom. For off-site cellmonitoring see also Duty of Care on page 2.

    1.5.1.2.2.1.2CELL ALARM SYSTEMA push button cell alarm enabling a detainee to call for assistance.

    When activated by depressing the cell alarm button an intermittent buzzer on the control panel(s) and / or otherwiselocated, shall sound and a yellow LED on the control panel(s) indicating the cell calling and will remain flashinguntil the call is acknowledged. Furthermore, an LED, incorporated in the cell alarm button and in the cell alarmreset button located outside the cell / holding room requiring assistance, shall be illuminated to show the call hasregistered. This alarm shall only be reset outside the cell / holding room in alarm. The intermittent buzzer shall becapable of being muted at the control panel if a detainee is creating a nuisance in using the alarm. The mute shallautomatically reset after a predetermined time period, typically five minutes. The loudness of the buzzer on the

    mimic panel in the General Office shall enable staff to clearly hear it. Consideration shall also be given to theinstallation of a small ceiling mounted strobe light activated when the buzzer sounds. The mute must automatically

    reset upon the alarm being reset at the alarm reset button. Muting the Cell Alarm buzzer shall not alter the operationof the indicating LED, which shall remain on until the reset button is depressed and the alarm call cleared from thesystem.

    The alarm call shall electrically latch, so that only momentary use of the alarm push button in the cell will activatethe alarm, remaining on at the both nominated locations until the alarm reset button outside the calling cell / holding

    room is depressed.

    All wiring to the cell alarms in the detainee areas (including cells / holding rooms) is to be at maximum 24V (a.c. ord.c.).

    The cell alarm system shall be tamper monitored at the control panel.

    For details of the cell alarm push-button plate see page 25.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    8/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 8

    1.5.1.2.2.1.3CELL INTERCOMIn Custodial facilities where a Audio Monitoring System is not provided, the Trustee's and General Type A cellsshall be fitted with an intercom that will enable the trustee / detainee to communicate with police officers in acontinually manned location (i.e. Security / Communications Room or General Office).

    In the Trustee and General Type A cell the approved intercom stainless steel front plate and button shall bemounted 1300 mm above floor level and contain:

    an alarm / intercom button as detailed under Cell Alarms; a microphone; and a speaker.The stainless steel front plate shall be fixed to triple gang wall box with six off 3mm stainless steel pop rivets. Referto details L-329 or L-330.

    In acknowledging a cell alarm, the normal operation of the cell intercom system is -1. mute Cell Alarm buzzer2. use the telephone handset to talk to the caller and

    3. reset the Cell Alarm outside the cellorwhere CCTV is installed in the cell on the control panel.

    Muting the Cell Alarm in one location shall cancel, for that cell, buzzers on duplicate panels . The mute willautomatically reset upon cancellation of the call. Muting the Cell Alarm buzzer shall not alter operation of theindicating light, which is to remain on until cancelled. The mute shall automatically reset after a predetermined timeperiod, typically five minutes.

    1.5.1.2.2.1.4AUDIO MONITORING SYSTEMAn Audio Monitoring system enables direct interaction between detainees and staff and is used in conjunction with

    the Cell Alarm system.

    The system shall be capable of:

    providing commercial radio to nominated cell(s). The system shall be capable of automatic interruption of theradio when the cell alarm system is activated;

    enabling voice communication with individual cells / holding rooms, via telephone handset; and providing continual sound monitoring of all cells / holding rooms. The volume of sound monitoring for each

    cell / holding room must be adjustable but not able to be switched off.

    In acknowledging a Cell Alarm, the normal operation of the audio monitoring system is -1. Corresponding Cell Alarm activation LED (yellow) flashes;2. Press corresponding cells / holding rooms call connect button to mute the Cell Alarm buzzer. On line LED

    green will light and yellow LED is off;3. Use the telephone handset to talk to the caller; and4. On completion of the call, cancel the connection by reseting the Cell Alarm outside the cell / holding roomby

    depressing the Cell Reset button orwhere CCTV is installed in the cell, by use of the Call Reset Button on the

    control panel when installed.

    Muting the Cell Alarm in one location shall cancel all buzzers. The mute will automatically reset upon cancellationof the call. Muting the Cell Alarm buzzer shall not alter operation of the indicating light. The yellow LED shall

    flash until the call is responded to or reset. which is to remain on until cancelled. The mute shall automatically resetto on and activate the buzzers after a predetermined mute time period, typically five minutes.

    The commercial radio receiver shall be rack mounted in the Communications Room, and shall be a commercialquality AM/FM radio tuner with manual and auto scan, and pre-set for 30 stations. The radio receiver shall beconnected to an aerial sufficient to receive without any audible interference all commercial AM and FM radiostations in the area.

    For details of the cell / holding room Audio Monitoring System plate see page 32.

    The cell speakers for the Audio Monitoring System shall be water resistant (for piped music and voicecommunication) and the microphone (for sound monitoring) shall be either:

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    9/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 9

    Behind an approved ceiling mounted stainless steel front plate(s). The plate shall be 2mm brushed stainlesswith tamper resistant screws. It shall have a 3 mm baffle with offset holes and a microphone on LED

    behind a polycarbonate lens. The stainless steel front plate shall be fixed to a heavy-duty wall box with sixoff 3 mm stainless steel pop rivets. Recess mount the above unit approximately in the centre of the ceiling.If this is not possible, recess in a wall immediately under the ceiling. The front face of the stainless steelplate shall be flush with the ceiling / wall surface and free of any gaps;

    Housed in a approved CCTV camera housing;A tamper alarm shall sound at the control panel if the unit is removed.

    Operation and adjustment of the system is critical to:

    Achieve a speaker volume level so as to be clearly heard within the cell / holding room; and Enable the microphone to detect responses at normal voice levels anywhere in the cell / cell holding room.

    1.5.1.2.2.2 CLOSED CIRCUIT TELEVISIONThe type of CCTV monitoring equipment required shall be determined on a custodial facilities by custodialfacilities basis.

    Only the CCTV camera(s) in the Charge Room and Sally-port or separate Detainee Entry shall be recorded.

    CCTV cameras to the staff entry shall not be recorded.

    All cameras shall produce a clear picture on the monitor with good contrast in full colour, when used with lightingranging from maximum natural lighting through to installed artificial lighting (allowing for appropriate

    maintenance and lamp depreciation factors). The lens shall be selected so as to ensure full coverage of the cell,including the area directly beneath the camera housing.

    To meet the performance criteria listed below the recording units shall be SVHS units. In order to enable viewing ofthe tapes one of VHS units provided as part the loose equipment shall have Super VHS playback capability.

    The following signage shall be installed in all areas under surveillance by CCTV systems except inside cells or

    holding rooms. The signage wording shall be

    This area is under CCTV Surveillance; or This area is under recorded CCTV Surveillance.

    The signage shall be designed and positioned to clearly readable and visible to all occupants.

    Refer to Technical Criteria CCTV section for further details.

    For details of the Cells, Exercise Yard or Security Compound closed circuit television camera housing refer to page

    20.

    1.5.1.2.2.2.1MONITORS

    The colour CCTV monitors shall be located in a continually manned location i.e. Security / Communications Roomor General Office. In a District Complex, the CCTV monitors should be duplicated in the Charge Room. Wheremonitors are mounted in the General Office or Charge Room they shall be placed to prevent viewing by the publicor detainees.

    Where a camera is provided in the padded cell, an additional monitor shall be mounted in the corridor adjacent tothe padded cell door.

    Provide monitors programmed, with a manual override, to switch from camera to camera, with a maximum of fourcameras per monitor. Any call from any cell shall cause that respective camera to lock on until the call is answeredor the automatic mode button on the control panel is pressed to cause automatic switching to recommence. The

    switcher should be mounted directly under the monitors.

    The facility for future recording capabilities is required.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    10/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 10

    1.5.1.2.2.2.2DIGITAL VIDEO / AUDIO RECORDER SYSTEMA colour CCTV camera(s) and Digital Video Recorder with inclusive Audio (DVRA) system shall be provided inthe Charge Rooms of all District Complexes and satellite stations with overnight detention facilities or a highcharge rate. The system, motion activated, shall record all CCTV cameras located in the Charge Room, Sally Port,

    Detainee Entry and the corridor outside all general & padded cells and holding rooms.

    The installed DVRA system shall meet the requirements of Detail LLXXXXX and have the following features:

    The DVRA system shall be 19 Rack mountable in a tamper monitored secure equipment enclosures or securecupboard located under full camera supervision in the Charge Area. The DVRA control unit, monitor andDVD burner shall be located in the rack/cupboard above 1200mm FFL to enable a person to stand at therack/cupboard and operate the DVRA, view the monitor and archive information without bending to carry outthe required DVRA operations.

    The DVRA shall have front panel controls and a LAN connection for remote operation under multiplepassword protection, (when connected). The requirements for a remote connection or remote PC for any or allfunction programming or viewing is not acceptable and rejected.

    Archiving and recovery of images may occur directly from the DVRA by connection of a DVD burner or othernominated archiving device. All controls on the front panel shall be displayable on the local monitor forviewing and programming. The video data burned to DVD, CD or floppy disk shall be auto starting once the

    images have been transferred from the DVRA to the disk. When the archived disk is inserted into anyWindows platform the video shall auto start and provide a high quality reproduction of the events recorded.

    The DVRA shall have a minimum of four audio inputs selectable to any camera and connect with an audiomixer as required to provide clear audio recording of all discussions in the Area under recording of thatcamera.

    The DVRA shall provide 91 days recording of a minimum of three cameras at SVHS image resolution (720 x576/288) with a minimum of 6 images per second per camera. Higher image rates may be provided ifavailable.

    Lower quality settings for recording to 91 days shall be rejected. The consultant shall ensure that where more than three cameras are required, allowance for the image quality

    and recording days are assessed to ensure all cameras are recorded for 91 days at the image quality stated.

    The DVRA shall be configurable to provide motion activated or alarm activated recording as nominated foreach camera/room and provide a minimum record, archive and playback resolutions of (720 x 576/288) in all

    operational modes for the frame rates required for all cameras. All recorded information shall be date time stamped and stored within event files for easy retrieval. Have both a 60 second pre buffer and minimum of 60 second post buffer. Both buffers shall be adjustable and

    operate in all modes of operation.

    Upon alarm activation, automatically and instantaneously record the pre buffer to the Hard Disk Drive (HDD),change individual or global picture record rates for associated alarm cameras, without effecting recordingcontinuity, record the event until the alarm resets or the movement ceases then record the post buffer.

    Have alarm inputs for movement detectors, cameras, NO/NC inputs, and relay outputs. The ability to view live, recorded or HDD archived images and audio simultaneously, while still recording. All

    recorded information shall be accessible without disruption to the recording process.

    Have a First In First Out (FIFO) recording to overwrite previously recorded information when the HDDstorage is full after 91 days.

    Have real time video and audio recording. Automatic recording guarantee regardless of power fluctuation, HDD failure or other equipment failure. Have continuous system status monitoring including recording failure of a HDD, video failure, camera failure

    and power failure alarms. The tamper alarm from the rack/cupboard and failure alarms provide via the outputconnector on the DVRA shall be input into the Cell Call or other nominated alarm notification systems.

    Have a UPS to supply all DVRA equipment including the cameras and have automatic reset and startup afterpower failure. UPS shall be sized to suit the DVRA system requirements and the Police Code.

    The DVRA HDD storage shall be expandable within the unit or with an add-on expansion module(s) matchedto the DVRA.

    The DVRA HDD shall be full formatted RAID 5 configuration to allow recovery of data from a HDD failure.Third party HDD configurations, which are not hot swappable with the DVRA are not acceptable and rejected.The DVRA HDD expansion units will allow configuration of each site depending on number of cameras anddisk storage to provide 91 days recording. Mirroring is not acceptable and rejected.

    A DVD burner for archiving shall be provided with the DVRA to archive selected images to DVD. As statedabove, selected images may be burned to disk at any time. These images shall auto played on any Windowsplatform. The requirement for special software to play back any archived disk is unacceptable and rejected.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    11/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 11

    Archiving to videotape or separate removable HDD shall also be available if required but not supplied with theDVRA.

    The camera(s) shall be positioned to provide complete CCTV and audio coverage of the Charge Room, Sally Portand Detainee Entry as required at each site.

    A monitor with built-in speaker for audio playback shall be provided with each installation and installed within therecording enclosure. The monitor shall be a LCD flat screen 12 or 15 to suit the enclosure. All programming,playback, review and archiving shall occur from the front panel controls on the DVRA with audio and videoviewing on the monitor.

    The ceiling mounted microphones in the Charge Room should be located as close as possible to the speech source;ie in front of the air grill at the top of the dock, and in front of the normal position of the police officer when talkingto the PIC.

    The recording equipment shall be 19 rack mounted and located in a locked security cupboard in full view of theCCTV camera within the Charge Room.

    No monitors are required for the Charge Room cameras. Sally-Port and Detainee Entry monitors shall be located inthe General Office.

    1.5.1.2.2.2.3CELL, EXERCISE YARD OR SECURITY COMPOUNDThe cell CCTV camera system shall be an independent system.

    The camera lens shall be capable of producing optimum picture quality to facilitate surveillance of all parts of thecell with 50% of installed lighting in operation.

    Cell cameras shall operate on 12DC or 24V AC supply only.

    1.5.1.2.2.3 DURESS ALARM - CUSTODIAL FACILITIESThese alarms shall be installed along cell block corridors, at six metre centres, in the Charge Room and Sally-port

    to enable a police officer or trustee to call for assistance. When activated, a continuous buzzer shall sound and alight appear on a control panel located in a continually manned location (i.e. Security / Communications Room orGeneral Office). A facility to mute this alarm shall not be provided. The activated alarm shall be key reset at theactivated push button switch only. Once the Duress Button is key reset, the alarm will cancel from the ControlPanel and the red LED extinguish.

    The push button Duress Alarm shall be an approved stainless steel front plate and push button mounted 1800 mm

    above floor level. The stainless steel front plate shall be fixed to a double gang wall box with six off stainless steelpop rivets. Refer to details L-329 or L-330.

    1.5.1.2.2.4 DETAINEE TELEVISIONIn country custodial facilities, with overnight detention a colour television monitor shall be provided for theentertainment of detainees. The monitor shall be located in one of the following locations Dining Room, ExerciseYard(s) or Security Compound and housed in a protective bulkhead with speaker outlets as per detail L-341. The

    local climatic conditions shall be taken into account if located externally. Periodic access to the monitor is requiredfor maintenance needs. The television shall be controlled by a hand-held remote control device operated by stationstaff.

    1.5.1.3 FIRE PROTECTION CRITERIA

    1.5.1.3.1 CLASSIFICATIONClassification as defined in the Building Code of Australia for:

    Custodial facilities is Class 3; and

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    12/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 12

    Police Stations is Class 5.

    1.5.1.3.2 GENERAL - BUILDING CODE OF AUSTRALIACustodial and Police Stations are to comply with the Building Code of Australia and Annexure 1 Building Code

    Alternative Solution For Custodial Accommodation Police Stations Condensed Report. The Design Requirementsare to be incorporated into cell and Police Station design. Where items are not listed and/or specified in the reportsthey are to comply with the Deemed to Satisfy (DTS) provisions of the Building Code of Australia.

    1.5.1.3.3 EGRESSThe Custodial facilities shall be designed to enable detainees, under police supervision, to exit the custodialfacilities into open space with the distance of travel minimised. A cell or holding room door should be within 6m ofeither an external exit or a point enabling a choice of two exit paths. A direct external exit shall be provided fromthe cell area of a custodial facility. This exit shall enable the evacuation of the custodial facilities should the stationbe on fire and should be in addition to the normal exit via the Charge Room. These doors shall be keyed alike with

    the cell doors. All doors shall open 180oand be able to be latched in the open position.

    The CSIRO Smoke Exhaust assessment, refer to Smoke Exhaust System on page 13, established that the Trusteecells should be fire isolated from the other cells because of the higher fire loading in the Trustee cells. The door of

    the fire-isolated cell shall be non-lockable, but the corridor in the vicinity of this cell shall be provided withlockable doors/gates. This allows the occupant of the Trustee cell to escape from the fire isolated compartment inthe event of a fire, but he or she is still locked in once outside of the fire affected cell.

    Egress Requirements1. The custodial facilities are to be designed in accordance with the Alternative Building Solution (Annexe

    1). Where the cell numbers are greater than 2, an additional egress point direct to open space is to beprovided;

    2. At least one of the egress points is to be into an enclosure which is open to the air (may have chain meshcover). The enclosure is to be a minimum of 1m in width and 2m long and not to be located so as openings

    are within 3m of the enclosure;3. The egress point from the building to the enclosure is to comply with D2.21 of the BCA (be openable at all

    times from the direction of egress);4. The enclosure is to have an alternative means of exit to unrestricted open space. This exit may be

    controlled to meet operational needs; or

    5. any other means as approved by an authorised person. Authorised person means Local Government, orappropriately qualified Building Surveyor.

    1.5.1.3.4 COMPARTMENTATIONWhere a Custodial facilities is attached to the Police station, a one-hour 'fire isolation' rated barrier shall be installedbetween the two occupancies and between these and special hazards such as plant rooms, store rooms etc. Refer toAnnexure 1 for ceiling fire rating requirements.

    Within a custodial facilities high risk areas such as kitchens, laundries and stores shall be separated from the cell

    areas and associated escape paths with a 1 hour fire barrier.

    The fire barrier shall be robust with minimum penetrations. Any penetrations must be well sealed.

    All fire doors within the custodial facilities shall be either monitored to prevent the door being propped open orfitted with magnetic hold open latches which release the fire door upon alarm.

    1.5.1.3.5 FIRE DETECTIONFire detection in custodial facilities requires special consideration so as to prevent the possibility of equipment

    damage and false alarms.

    All Custodial facilities shall be fitted with smoke detection in the exhaust systems.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    13/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 13

    1.5.1.3.5.1 SMOKE DETECTIONSmoke detectors / fire alarms shall be installed in all areas of the Police Station including custodial facilities.

    Consideration, based on life cycle cost, maintainability and reliability, should be given to the use early warningsmoke detectors

    The lack of combustible materials in cells and exercise yards means that smoke detectors provide more appropriateprotection than thermal detectors. One detector per cell or exercise yard is preferred and:

    located within the return or exhaust air ducts; duct mounted detectors shall be accessible via manholes located outside the cell / exercise yard area; and integrated with the mechanical services design.Additional smoke detector(s) shall be provided in high points in the ceiling where smoke from the cells or exerciseyards could collect. Such detectors should be no closer than 1500 mm from any openings in the cell exercise yardfronts large enough for a person's arm.

    The system shall sound an alarm and illuminate a location indicator on a control panel located / duplicated in theSecurity / Communications Room or a continually manned location i.e. General Office and the Charge Room,unless these two rooms are immediately adjacent, or the Charge Room is occupied on a 24-hour basis. When thestation is not manned 24 hours a day, the alarm shall be capable of being switched to the Officer in Charge'sresidence.

    The alarm shall be incorporated in the Electronic Control System. See Security Systems section in the TechnicalCriteria.

    1.5.1.3.5.2 SMOKE EXHAUST SYSTEMSmoke extraction from cells, holding and waiting rooms shall be designed in accordance with the following

    guidelines

    1.5.1.3.5.2.1BackgroundThe following design guide is based on the outcomes of a smoke exhaust assessment carried out by the CSIRO withassistance from the WA Police Service, Department of Housing & Works (previously Department of Contract andManagement Services) and the WA Fire Brigade. The CSIRO assessment was carried out to establish the minimum

    smoke exhaust rates in various cells, including holding rooms, taking into account the likely fire load and size ofthe cell(s) or holding room(s). The assessment included computer modeling and real fire tests using the flame

    retardant "Just Kidding" - Safe Guard - Proban P.U. S300" cell mattress

    Operational aspects relating to fire safety are to be in accordance with the Building Code of Australia.

    1.5.1.3.5.2.2Description of the cells.The smoke exhaust design guidelines are based on the following assumptions:

    the Trustee Cells are overnight and short-term detention cells where trustee detainees are locked in the cellovernight but not during the day.

    the General Cells are overnight and short-term detention cells and the occupants are locked in their cells at alltimes.

    the holding / waiting rooms are short-term detention cells and the occupants are locked in the cells during theday, but there is no overnight detention.

    the floor areas of the cells, holding / waiting rooms vary between 10 m2and 20 m2.

    1.5.1.3.5.2.3Smoke Exhaust Options

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    14/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 14

    Smoke exhaust options include mechanical exhaust and natural smoke exhaust through the ceiling vents and wallvents. Wall vents are not as efficient as ceiling vents and therefore require larger areas to achieve the requiredresults. The smoke exhaust requirements and the various options are:

    Cell type Mechanical Smoke

    Exhaust

    Natural Ceiling

    Mounted Ventilation

    Natural Wall

    Mounted VentilationHolding / WaitingRoom(s)

    10 m2cell

    15 m2cell

    20 m2cell

    24 a/c per hour(0.2 m

    3/s)

    16 a/c per hour(0.2 m3/s)12 a/c per hour(0.2 m3/s)

    2x 0.29m x 0.29mfree area all cell sizes

    8x 0.29m x 0.29mfree area all cell sizes

    General CellAll sizes

    2x 0.29m x 0.29mfree area

    12x 0.29m x 0.29mfree area

    General Cell10 m2cell

    15 m2cell

    20 m2cell

    48 a/c per hour

    (0.4 m3

    /s)30 a/c per hour

    (0.375m3/s)

    24 a/c per hour0.4m

    3/s)

    Trustee Cell 24 air changes per hour 2x 0.29m x 0.29mfree area

    8x 0.29m x 0.29mfree area

    Where Trustee cells are intended to be used as General cells, smoke exhaust rates shall be determined from therelevant entries for General cells in the above table.

    Where cells have floor areas different from those listed it may be assumed that the mechanical smoke exhaust ratesincrease linearly. The listed sizes namely 10m2, 15 m2and 20 m2were used for modelling purposes.

    Make up air openings should be at low level and designed so that the face velocity of the make-up air withmechanical smoke exhaust does not exceed 1.0 m/s.

    In the case of natural ventilation the free area of the make-up air openings should be similar to the vent areas.

    The smoke exhaust system shall be activated by the smoke detection system and be connected to the emergencypower supply. Smoke spill fans shall be constructed to comply with AS 1668 - Part 1.

    Make up air for the smoke exhaust system shall not be drawn from areas likely to be contaminated by smoke.

    In the event of smoke being detected in a cell any supply system serving the cell shall shut down.

    Smoke exhaust grilles in cells shall be as per details L-331, L-332 or L-333.

    1.5.1.3.6 FIRE HOSE REELSFire hose reels, when required, shall be located in such a position that:

    all parts of the Custodial facilities floor area can be reached; and it is not accessible to detainees. In some custodial facilities detainees have free movement between Exercise

    Yards / Security Compounds and their Cells.

    1.5.1.3.7 FIRE EXTINGUISHERSWhere required, fire extinguishers that conform to relevant Codes and Standards are to be included. Their locationshall be limited to areas not accessible to detainees. Fire extinguishers shall be mounted on the latch side of doors.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    15/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 15

    1.5.1.3.8 HYDRANTSPolice stations with a floor area greater than 500m2and no street hydrant within 90 metres of the front door shallhave a hydrant located within the grounds.

    1.5.1.3.9 SALLY-PORTThe Sally-port is required to have a two hour 'fire isolation' rating as this area can be used to hold detainees in caseof a fire emergency. As this will required lockable doors, both handles, the Sally-port may not be able to be used as

    a required fire exit path. The Sally-port roller door needs to be constructed with an open mesh design so as toprovide ventilation. Alternatively, there needs to be sufficient smoke exhausting to render the area safe. If an openmesh roller door is used the door shall be located to prevent the public from seeing into the Sally-port.

    1.5.1.3.10EVACUATION PLANA fire emergency and evacuation plan shall be written for the custodial facilities in consultation with the FireBrigade. The evacuation plan shall be prominently displayed in the custodial facilities.

    For further information refer to the report by the Western Australian Fire Brigades Board (May 7,1990 "FireProtection For Existing Custodial facilities And Police Department Custodial facilities" on DHW Files BB 1546/85and BB 605/89.)

    1.5.1.4 MECHANICAL1.5.1.4.1 THERMAL COMFORT IN STAFF AREASStaff areas within the custodial facilities i.e. Charge Room, shall have the same standard of heating and cooling asthat provided in the station.

    1.5.1.4.1.1 CHARGE ROOMA mechanical extraction system with local controls shall be incorporated into the charge dock to assist in removalof odours.

    The ventilation grille shall be:

    vandal proof; located as high as possible preferably on the dock ceiling; devoid of any anchor points; and as per detail L-331, L-332 or L-333. Woven Mesh (5 mm Aperture x 2 mm diameter). High Tensile Wire may

    be used in lieu of perforated steel plate.

    1.5.1.5 HYDRAULICS1.5.1.5.1 SEWERAGEFrequent blockages of the Custodial facilities sewerage system due to detainees flushing large objects i.e. wholetoilet paper rolls, requires provision for adequate inspection / rodding openings.

    1.5.1.5.2 DOMESTIC HOT WATER TO SHOWERSHot water, usually at 45

    0C but not above 55

    0C, shall be provided via a suitable hotwater unit with a mixing valve

    to control the water temperature. The mixing valve shall be located in an area not accessible by detainees. e.g.

    plumbing duct.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    16/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 16

    1.5.1.5.3 GASNo gas appliances are to be provided in custodial facilities.

    1.5.1.5.4 HOSE COCKSHose cocks shall be provided to enable padded cells, general cells, trustee cells, exercise yards and the securitycompound to be hosed out.All hose cocks

    in custodial facilities areas, where a detainee may be left unattended, shall be in recessed cupboards, and in the Security Compound shall be in recessed cast iron valve boxes with non-removable lids.

    1.5.1.6 WALL ELEMENTS1.5.1.6.1 WALLSIn custodial and operational areas where walls may be subject to damage from equipment worn by police personnel,

    additional protection such as sheet vinyl to walls below dado level and corner guards should be provided. Thisfinish is required in all heavy traffic areas. e.g. main circulation corridors.

    1.5.1.6.2 DOORSAll doors should beAll doors should be

    solid core doors as per detail L-205 or steel clad doors as per detail L-307, L-308 or L309.All doors shall be hung on approved hinges.

    The door locks to doors within the Custodial Holding area shall be Chubb Custodian Lock, without a latch release

    button and keyed both sides and all keyed alike. Where the custody area is jointly used by Police and Department ofthe Attorney General all Chubb Custodian Locks in both facilities shall be keyed alike.

    The Chubb Custodian Lock shall be uniquely keyed for each police station custody area. Under no circumstancesare locks across multiple custody areas to be keyed alike.

    Other doors shall have commercial locks as per the remainder of the station.

    The flush pull shall be Stanco No 626, 150mm x 75mm, or equal approved.

    Consideration should be given to using 920 mm wide doors in major circulation corridors. Typically external entryto Charge Room and Charge Room to Holding Room(s) / Cells.

    All door handles should be lever handles. Adequate clearance shall be provided between the jamb and the handle toensure ease of use.

    All door closers shall have fully concealed arms.

    Door in custodial facilities passages should incorporate glass viewing panels but no louvered A/C vents as these areeasily kicked out providing a potential escape route.

    1.5.1.7 BUILT-IN FURNITURE1.5.1.7.1 BENCH SEATSFixed bench seats should have rounded edges and be set into a wall recess. A protruding bench can provide ahazard.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    17/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 17

    Refer to details L-208, L-319 or L-320.

    1.5.2 SPECIALISED ACTIVITY SPACE DETAILSThe following section outlines in greater detail the technical performance requirements for particular activity

    spaces.

    1.5.2.1 SALLY-PORTThe Sally-port shall be designed to accommodate both Police and Department of the Attorney General vehicles as

    outline in the table below.

    Dimension of Vehicles Using Sally-port

    WESTERN AUSTRALIA POLICE SERVICE

    VEHICLEMAKE / MODEL

    AS AT MARCH 1994

    WIDTH WIDTHINC. WING

    MIRRORS

    WIDTHWITH

    SIDE

    DOORSOPEN

    LENGTH LENGTHWITH

    REAR

    DOOROPEN

    HEIGHT

    W1 W2 W3 L1 L2 HFALCON PANEL VAN 1800 4800 2200

    FALCON UTE 1800 4800 2000MAZDA B SERIES 1700 4900 2200

    MAZDA T4000 2000 5500 2600HOLDEN RODEO 1700 4900 2050TOYOTA L/C UTE 1700 4900 2500TOYOTAPERSONNEL/C

    1700 4900 2750

    NISSAN PATROL UTE 1700 4900 2500

    OKA 4x4 2100 5800 2800

    Mercedes Benz Sprinter413CDi LWB HighRoof (Long wheel base)

    1994 2326 6600 2800

    NotesAll Measurements In MillimetresPolice Service Vehicles

    The height measurements are taken from the highest point i.e. blue light Aerials are excluded. Allow approximately 600 mm The length/width are vehicle dimensions only. As a general rule, add 1000 mm to the length to allow for roo bars and swinging steps fitted

    to some of the country based vehicles.

    For confirmation of Police Vehicle size contact Police Fleet Services on 08 9370 7111, Fax 08 9370 7187

    DEPARTMENT OF THE ATTORNEY GENERAL

    The Department of the Attorney General / Department of Corrective Services have advised that the standard hasbeen accepted for all new Courts and Prisons sally ports state wide.

    Type and Model of Vehicle: ISUZU FVY 1400 Long

    Length of Vehicle: 11,875 (11,145mm vehicle+ 750mm for bull bar and tow bar) Height of Vehicle: 3,450mm Width of Vehicle: 2,500mm

    It is important to leave sufficient room along both sides and at the rear of the vehicle to allow doors to open widewithout forcing the officers to work in a confined space with prisoners.

    GENERALClear access of 1500 mm shall be provided around the sides and rear of a vehicle parked in the Sally-port with the

    roller door down.

    Adequate access to the Sally-port through the roller door shall be provided for the largest vehicle nominated fromthe above table. The minimum clear opening of the roller door shall be 3000 mm wide by 2850 mm high. The

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    18/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 18

    Sally-port roller door shall be electronically operated remotely from the Charge Room and Security /Communications Room.

    Sally-ports shall be naturally vented. Where natural ventilation is either unable to be provided or is inadequate amechanical ventilation is to be provided. If an open mesh roller door is used, the door shall be located to prevent the

    public seeing into the Sally-port, as this presents a potential hazard to detainees.

    The door from the Sally-port to the Charge Room should be located at the rear of the Sally-port and include a glasspanel to provide visibility between Charge Room counter / Custodial facilities Corridor and Sally-port.

    1.5.2.1.1 SIGNAGESign outside Roller Door to read

    Vehicles to be Reversed into Sally-port.

    Sign inside Sally-port, adjacent to internal door to read

    No Firearms Past This Point.

    All lettering shall be equal or similar to Helvetica Medium 100 mm high, mixed case to suit.

    1.5.2.1.2 DISTRICT COMPLEXIn a District Complex:

    the door from the Sally-port to the Charge Room shall be electronically operated remotely from Charge Roomand Security / Communications Room and / or key operated only;

    provide reed type switches to the roller shutter and to the door from the Sally-port to Charge Room / Custodialfacilities Corridor to allow these doors to be interlocked (so one cannot be opened unless the other is closed);

    CCTV cameras shall be provided to enable monitoring of the external entrance to and from the area within theSally-port . The CCTV monitors shall be located in the Charge Room and Security / Communications Room.Refer to Technical Criteria, CCTV Section;

    an intercom / buzzer system is required to enable communication between officers entering the Sally-port andthe Charge Room. It shall be located:

    externally, by the Sally-port Roller Door; within the Sally-port adjacent to the door into the custodial facility.

    1.5.2.2 DETAINEE ENTRYWhen a Sally-port is not provided and a separate detainee entry is required, the entry shall be a half glazed door,fitted with an electric strike door lock, and operated by an external proximity card reader. Inside handle always free.

    Inside handle to be operated by proximity card.

    If the entry is a required fire exit the proximity card reader shall be replaced with door release button located nearthe door. In the event of a fire alarm the outside handle shall fail secure and the inside handle shall fail open.

    Additionally, for a District Complex only, an intercom and CCTV system connected to either the Security /Communications Room or General Office (101-8) shall be provided. The CCTV camera shall be located to

    principally enable the observation of detainees being removed from a vehicle, reversed parked, and secondlyidentification of the person using the intercom. Refer to Technical Criteria - Proximity Card System and Staff Entry

    in the Project Information - Notes on Activity Spaces section.

    1.5.2.3 DETAINEE EXITA detainees shall be released directly into an external public area. The escorting of detainees through the station to

    the public foyer or releasing them into the Police Vehicle Parking Compound presents a risk to police staff andproperty. The exit shall:

    be well lit externally;

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    19/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 19

    have CCTV coverage to an internal monitor above the door; not be a fire escape; have an internal staff duress button adjacent to the door; and have no glazing in the door or adjacent to the exit

    The door shall open out and be fitted with an internal handle and proximity card reader, which shall operate anelectric strike door lock. No external door hardware or proximity card reader shall be provided. The door shall beinterlinked with the staff entry in a manner that prevents both doors being open at the same time.

    1.5.2.4 CHARGE ROOMAny corners of built-in furniture protruding into the charge room shall be chamfered and rounded. A protrudingbench can provide a hazard.

    A clear full height wall area 2000 mm wide, minimum, used as background for detainee photographs, shall be

    painted with a wash and wear low sheen paint. Colour Dulux Master Palette Galactic Blue 10BG 72/080.

    1.5.2.4.1 LIVE SCAN UNITWA Police Corporate Programs and Development shall be consulted in regards to the provision of a Live ScanUnit. If provided it shall be located in the Charge Room adjacent to the fingerprint bench. Refer to Standard DetailL-201. The fingerprint bench is required to enable fingerprinting of detainees during periods when the Live ScanUnit is non operational due to power failure or break down.

    1.5.2.5 CELL BLOCK CORRIDORSThe corridor width outside a cell shall be 1800 mm to enable access past the cell door when it is open 90o.

    Where practical, all fittings and controls in corridors shall be flush with the wall so as not to provide hand grasp

    points for detainees. Striker plates, lock cylinder face plates, handles and hinges on duct doors should be flushunless located above 2000 mm or below 600 mm.

    Recorded CCTV coverage shall be provided in all cell block corridors outside holding rooms, general and paddedcells to provide recorded coverage of officers undertaking cell checks and persons in custody being escorted to and

    from cells. Refer to Digital Video / Audio Recorder System for details.

    1.5.2.6 CLOTHES DRYING AREAThis area is used for the drying of blankets, detainee clothing and the like washed by detainees. The clotheslineshould be kept as simple and maintenance free as possible. Refer to detail L-210. Rotary clothesline should beavoided.

    The drying area should be adjacent to the custodial facilities laundry and within the Security Compound or Police

    Vehicle Parking Compound.

    1.5.2.7 SECURITY COMPOUND1.5.2.7.1 FLOORSThe floor shall be constructed from a combination of

    brush finished monolithic reinforced concrete, and lawn.The perimeter of the compound shall consist of a two metre wide (minimum) strip of reinforced concrete.

    1.5.2.7.2 WALLSThe walls shall be constructed from a combination of:

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    20/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 20

    6.3 mm diameter high tensile rods with a 50 mm aperture woven mesh with each rod welded to a minimum 40mm x 40 mm x 5 mm galvanised mild steel angle frame. The angle frames shall be either welded or bolted

    together. The bolts shall be a minimum 8 mm diameter at a minimum of 500 mm centres with the nut spotwelded to prevent removal; and

    safe cell wall construction. An approved anti vandal paint shall be applied over the specified finish.The construction shall ensure no gaps larger than 50 mm x 50 mm.

    An approved anti-vandal paint shall be applied over the specified finish.

    The painting of walls in remote and country custodial facilities with aboriginal motifs by the local communityshould be encouraged. These shall be applied over the specified finish.

    To prevent visitors passing objects to detainees, a fence shall be provided between the visitors area and the

    Security Compound. It shall

    be a two rail heavy duty link mesh fence and provide a continuous secure 1500 mm gap between the fence and the Security Compound.The 1500 mm gap shall have a link mesh roof to prevent items being thrown in the gap and retrieved by detainees.

    1.5.2.7.3 ROOFThe roof shall be constructed from a combination of:

    6.3 mm diameter high tensile rods with a 50 mm aperture woven mesh with each rod welded to a minimum 40mm x 40 mm x 5 mm galvanised mild steel angle frame. The angle frames shall be either welded or boltedtogether. The bolts shall be a minimum 8 mm diameter at a minimum of 500 mm centres with the nut spotwelded to prevent removal;

    metal roof sheeting with a combined 50 mm (R1.2) fibreglass blanket and perforated Sisalation or equalapproved under, all supported by tensioned knitted shade cloth. The fibreglass blanket shall have a moistureabsorption capacity of not more than 0.2% by volume. The Sisalation perforations shall be 1.5 mm diameterand comprise 10% of the surface area and face downward. The shade cloth shall have a 70% shade coefficient,overlapped by joints at 25 mm and laced together at 200 mm centres with continuous nylon thread.

    1.5.2.7.4 LIGHT FITTINGSThe light fittings shall be safe cell fittings switched from the Charge Room.

    1.5.2.7.5 POWERThe facility to isolate any power points provided within the compound shall be in the Charge Room.

    1.5.2.7.6 CLOSED CIRCUIT TELEVISIONThe CCTV camera(s) shall be positioned within a security compound to enable complete observation of that space.

    The selected camera lens shall provide a good quality picture under all lighting conditions and regardless of sunangle.

    All cameras shall be located immediately below the ceiling / roof level in a corner mounting. The camera housingshall be an approved high security triangular housing with a polycarbonate lens cover. Fill any gaps between

    camera housing and wall / ceiling / roof with Sikaflex 1A or equal approved epoxy filler. Ensure front coverremains removable.

    1.5.2.8 POLICE STATION / COURT HOUSE SECURE LINKThe secure link between court and police custodial facilities shall only be designed to assist offices transferdetainees. It is not practical or cost effective to design this space to minimize the opportunity for detainees to inflictself harm.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    21/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 21

    Signage, worded DETAINEES ARE NOT TO BE LEFT UNATTENDED IN THIS AREA, shall be installedadjacent to each entry to the secure link.

    1.5.3

    SAFE CELLSThe size and shape of cells can be varied to suit overall planning. However, the ability of the Police to view the

    whole cell before entering is critical.

    The construction of cells (especially junctions) shall withstand vigorous washing down.

    No fixtures, fitting and finishes other than those specified shall be provided in a cell without prior approval.

    1.5.3.1 STRUCTURE1.5.3.1.1 FLOORSThe cell floor finish shall be either: smooth machine trowelled monolithic reinforced concrete; or reinforced granolithic finish; or butt jointed 24 mm compressed fibre cement sheets with a clear sealed finish on 16 gauge sheet steel and fixed

    joists at 450 mm centres with counter sunk screws. All joints to be filled with an approved filler. All screwholes to be epoxy filled and ground flush.

    In all cells except padded cells the monolithic / granolithic floor shall:

    be laid to fall (1:60) to a floor gully in the shower recess. If no floor gully is provided, the floor, in Custodialfacilities only, should fall to the door way; and

    have a 50 mm coved skirting integral with the floor.The padded cell shall have a structural floor level 60 mm above the adjacent finished floor level.

    1.5.3.1.2 WALLSThe cell wall construction shall be one of the following:

    the brickwork is to be 110 mm thick with 75 mm wide brick reinforcement (two courses above floor level, fourcourses below top of wall and every six courses and built with cement mortar), or

    cell walls adjoining areas with security rating other than category A are to be a minimum of 230 mm thick (orof cavity wall construction), or

    blockwork (internal Cell Walls) 140 mm minimum hollow concrete blockwork voids, course reinforced andfilled with grout. Vertical voids reinforcing bars set into the concrete floor slab. Well lap and tie when joiningbars, and

    have, except in padded cells, a rendered glass faced cement finish, 20 mm thick, reinforced with expanded steel

    mesh equal to 'Lysaghts Metalath F1 25'. The junction between the render and the monolithic / granolithic floorshall be coved.

    butt jointed 18 mm compressed fibre cement sheets fixed to stud work with 50 mm long counter sunk screws at450 mm centres (max.). The compressed sheets shall have vertical butt joints only, located centrally over stud

    work. All joints to be filled with an approved filler. All screw holes to be epoxy filled and ground flush; or

    reinforced concrete having a minimum thickness of 150 mm. The concrete must have a smooth finish withflush joints.

    1.5.3.1.3 CEILINGSCell ceiling height shall generally be 3000 mm with the absolute minimum height being 2750 mm. In stations with

    only holding / waiting rooms for short term custody, no overnight detention, the ceiling height shall be 2700mm.

    The ceiling shall be constructed from either: reinforced concrete with a skim coat of plaster; or

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    22/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 22

    butt jointed 18 mm compressed fibre cement sheets fixed to stud work with 50 mm long counter sunk screws at450 mm centres (max.). The compressed sheets shall have butt joints only, located centrally over joists. All

    joints to be filled with an approved filler. All screw holes to be epoxy filled and ground flush. or

    1.6 mm galvanised steel sheet pop riveted, at 450 mm centres to underside of galvanised steel ceiling joistswelded together. 10 mm villaboard sheets shall be fully laminated to the underside of the galvanised sheet withLiquid Nails or equal equivalent and fixed with 40 mm counter sunk screws at a max of 450 mm centres.The galvanised sheet and villaboard sheets joints shall be staggered. The villaboard sheets shall have butt joints

    only, located centrally over joists. All screw holes to be filled with an epoxy filler and ground flush. All jointsto be filled with an approved filler.

    No cornice is to be provided and the walls are to be butt jointed to the ceiling.

    No manholes or access panels shall be located in the Cells.

    1.5.3.2 FINISHES1.5.3.2.1 FLOORSAn approved anti-vandal paint (colour grey) shall be applied to the floor. Consideration shall be given to a low levelnon-slip finish.

    The waiting room shall have indoor / outdoor carpet securely fixed to the floor using a high strength adhesive. Thecarpet shall be terminated under the door with a securely fixed brass covering strip. The adhesive along the edge of

    the carpet shall be continuous to prevent occupants lifting the carpet.

    1.5.3.2.2 WALLSThe walls shall:

    be suitable to receive a non porous semi gloss acrylic paint; be one colour from floor to a height of 1200 mm and a contrasting colour above so as to provide a point of

    reference for intoxicated detainees awaking.

    Pigment mixed into render is a suitable alternative for rendered surfaces. Colours of paint / render are to be

    psychologically neutral. Avoid blues, greens, blacks and reds.

    Suggested colour combinations (Dulux Chroma Range) are as follows:

    Raw Sugar 36131 Above 1200 mm

    Confetti 36583 Below 1200 mm

    Billow 37302 Above 1200 mm

    Quicksand 36585 Below 1200 mm

    Surfcrest 36502 Above 1200 mm

    Moonshadow 37231 Below 1200 mm

    White spice 36581 Above 1200 mm

    Swansdown 37272 Below 1200 mm

    Caravan 37072 Above 1200 mm

    Moodyblue 37233 Below 1200 mm

    An approved anti-vandal paint shall be applied to the walls.

    The painting of cell walls in remote and country custodial facilities with aboriginal motifs by the local communityshould be encouraged. This shall be applied over the specified finish.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    23/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 23

    1.5.3.2.3 PADDED CELLThe padded cell wall and floor finish shall be either an approved:

    Reconstituted rubber will be made from recycled truck tyres shredded to produce rubber particles of 16mesh and 12 mesh sizes bonded together with a polyurethane based binder and compressed into sheets. In

    situ rubber will be brought to site as a slurry of the same constitution as preformed sheets.

    The method of installation shall comply with the following principles:

    Reconstituted Rubber To Walls - Sheet out walls from floor to ceiling using reconstituted rubber sheetnominal 20mm thick glued and mechanically fixed to walls. Seal with a polyurethane binder and thenroller coat with a dyed binder. All fixings will be sealed and rolled again with a dyed polyurethanebinder. The cell door will be sheeted generally as detailed with the same sheeting as the walls.

    Reconstituted Rubber To Floor - Screed floor and cove to wall sheeting using a slurry of reconstitutedrubber of the same constitution as the sheet material.

    Refer to WAPS file 00416 99 FV001 for specification. or

    An approved propriety product. Refer to Approved Components / Elements Section.All internal corners shall be 35mm coved corners. All external corners shall be rounded.

    Refer to standard detail L-301.

    1.5.3.2.4 CEILINGSThe ceiling shall have a flat white acrylic paint finish with an approved anti-vandal paint to reinforced concrete or18 mm compressed fibre cement sheets.

    1.5.3.3 MECHANICAL1.5.3.3.1 CELL BLOCK CLIMATE CONTROLA combination of natural and mechanical systems is required in all general and trustee cells.

    Natural ventilation systems reduce running costs, and provide an alternative in case of power or plant failure.

    Mechanical systems provide cooling and / or heating an extraction system to remove odours and smoke, and supplementary ventilation, where natural ventilation is either unable to be provided or is inadequate.

    1.5.3.3.1.1 THERMAL COMFORTIn areas where the daily maximum dry bulb temperature, during the hottest three months of the year, exceeds 350Cfor 75% of that period, cooling is required. (refer Bureau of Meteorological Climatic Data for daily maximumtemperatures).

    Due to the design of cell blocks i.e. external doorways into security compounds permanently open, strict adherenceto standard cooling design criteria is not required. The system should be designed to reduce the discomfort of hightemperatures and minimise running costs.

    As detainees are provided with blankets, the need for heating shall be assessed on a station by station basis.

    Controls for the mechanical systems shall be located in the Charge Room or General Office.

    Refer to the Technical Criteria - Thermal Comfort.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    24/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 24

    1.5.3.3.1.2 NATURAL VENTILATIONCells in Remote Area and Country Custodial facilities shall be naturally vented. Cells in City / Major Centrecustodial facilities should be naturally vented wherever practical.

    Where natural ventilation is provided the design shall provide for:

    adequate air flow through the cell preferably at the occupant level; sufficient air changes; and manual restriction of air flow through the cell in winter.One method of naturally venting the cell is to draw air into the cell via the cell door and external grilles in thecorridor and expel the air through cell ceiling grilles.

    1.5.3.3.1.3 MECHANICAL SYSTEMSMechanical systems designed for summer conditions shall be able to provide satisfactory winter requirements, inaddition to meeting AS1688 Part 2.

    The design of mechanical systems shall ensure that: each heating and cooling system serves an optimum grouping of cells to provide a cost effective solution in

    terms of capital and running costs;

    no short circuiting of air occurs between supply and exhaust grilles; sufficient air circulation occurs within the cell; temperature sensors are located in the exhaust system and are accessible from outside the cell; cell air is recycled, if required, only within the cell areas. It shall not be recycled with staff areas; and requirements of AS 1668 Part 2 are satisfied.

    1.5.3.3.1.3.1MECHANICAL VENTILATIONThe ventilation system shall be capable of providing :

    normal ventilation. Consideration should be given to drawing make-up air from a conditioned space; and smoke exhaust during fire conditions (See Smoke Exhaust System, Page 11).

    1.5.3.3.1.3.2COOLINGThe cell design air temperature in the cooling mode shall be a maximum of 27

    oduring the intended periods of

    occupancy, which may vary from station to station.

    1.5.3.3.1.3.3HEATINGThe cell design air temperature in the heating mode shall be a minimum of 18

    oduring the intended periods of

    occupancy, which may vary from station to station.

    1.5.3.3.1.3.4VENTILATION / MECHANICAL GRILLESCell grilles shall be:

    vandal proof; located as high as possible/preferably on the ceiling; devoid of any anchor points; and as per detail L-331, L-332 or L-333. Woven Mesh (5 mm Aperture x 2 mm diameter. High Tensile Wire) may

    be used in lieu of perforated steel plate.

    1.5.3.4 ELECTRICALAll wiring shall be in a fully concealed conduit.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    25/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 25

    Surface mounted equipment such as light fittings and camera enclosures shall be installed to produce absolutely nogaps at the ceiling or walls.

    1.5.3.4.1 LIGHTINGCell lighting shall be included on the essential power supply, if provided, and have a minimum illuminance of 150lux so as to enable detainees to read or participate in chosen activities without injury to eyesight.

    Centralised lighting control is required for the cell area with control from a labelled stainless steel switch panel,normal located in the Charge Room.

    The luminaire mounting positions should provide adequate illumination to all parts of the cell to allow observationof detainees from the observation windows and CCTV camera(s), but should not be located where detainees can

    stand on the benches or modesty panels and touch them.

    To ensure adequate observation of detainees is readily achieved, the level of illumination in the cells shall not beless than in the corridor or other observation locations.

    Light fittings used near showers must be both water resistant and corrosion resistant.

    1.5.3.4.1.1 LIGHT FITTINGSThe light fitting shall be an approved surface mounted luminaire, 3x36 watts, suitable for high abuse areas and

    switched from the Charge Room or for holding cells outside the cell.

    To enable the observation of sleeping detainees / prisoners using low light levels, an approved low light levelcompact fluorescent lamp shall be incorporated within the surface mounted luminaire and separately switched fromthe change room.

    For cells with no permanent emergency power supply, e.g an onsite generator, an approved emergency lamp shallbe incorporated within the surface mounted luminaire to provide light in the event of a power failure.

    The surface mounted luminaire diffuser shall be fixed with a minimum of 6 allenhead large diameter screws. Wherethe fitting is fixed to an uneven ceiling the pack around the screw fixings to prevent the base of the light fittingtwisting when fixed.

    Fixing of light fittings to a concrete ceiling shall be as per detail L-326, L-327 or L-328. Fixing of light fittings to18 mm compressed fibre cement sheet ceilings shall be to trimmers with 40 mm long x 6 mm diameter allenhead

    screws.

    1.5.3.4.2 POWERNo GPO's shall be installed in cells, except innominated trustee cells. The facility to isolate this power point shall

    be in the Charge Room.

    1.5.3.4.3 CELL MONITORING AND ALARMS1.5.3.4.3.1 CELL ALARMSThe push button alarm and reset button shall be an approved stainless steel front plate and push button mounted1000 mm above floor level. The button shall be a robust, vandal resistant push button manufactured from stainlesssteel. The push button shall activate a micro switch and bear against a solid shoulder, which will resist knockthrough. An internal neoprene gland shall seal the button. A cell LED protected by a flush polycarbonate lens shalloperate when the call button is pushed. A tamper alarm separate to the call alarm shall notify the central control of aunit's removal. The stainless steel front plate shall be fixed to a double gang wall box with six, 3 mm stainless steel

    pop rivets.

    The reset push-button shall be 1200 mm away from any openings, in the cell front, large enough for a person's arm.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    26/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 26

    Refer to details L-329 and L-330 and custodial facilities Communications Systems section on page 6.

    1.5.3.4.3.2 AUDIO MONITORING SYSTEMThe water-resistant speaker (for piped music and voice communication) and microphone (for sound monitoring)shall be either:

    behind an approved ceiling mounted stainless steel front plate(s). The plate shall be 2 mm brushed stainlesswith tamper resistant screws. It shall have a 3 mm baffle with offset holes and a "microphone on" LED behinda polycarbonate lens. The stainless steel front plate shall be fixed to a heavy-duty wall box with six off 3 mm

    stainless steel pop rivets. Recess mount the above unit approximately in the centre of the ceiling. If this is notpossible, recess in a wall immediately under the ceiling. In either case, use a heavy duty wall box with the front

    face of the plate flush with the surface and without any gaps around the plate;

    housed in an approved CCTV camera housing.A tamper alarm shall notify the central control of a unit's removal.

    Operation and adjustment of the system is critical to

    achieve a speaker volume level so as to be clearly heard within the cell, and enable the microphone to detect responses at normal voice levels anywhere in the cell.In both cases, operation, including voice switching, with typical cell background noise conditions, is to be possible.

    Refer to details L-329 and L-330 and custodial facilities Audio Monitoring section on page 8.

    1.5.3.4.3.3 CLOSED CIRCUIT TELEVISIONThe CCTV camera(s) shall be positioned within a general / padded cell(s), holding / waiting room(s) or exerciseyard or to enable complete observation of that space. The camera(s) shall be located to provide full observation ofareas not visible from the corridor observation windows. e.g. the area behind modesty screens. The CCTV camerahousing should not be located where detainees can stand on the benches or modesty panels and touch them or block

    the image by sticking CCTV housing.

    All cameras shall be located immediately below the ceiling level in a corner mounting. In the padded cell a centralcamera mounting may used if the curvature of the wall prevent the proper installation of a corner mounting Thecamera housing shall be an approved high security approved camera housing securely fixed with a minimum of 4 x25mm long mechanical fixings. The commissioned consultant shall select and fully specify the fixings to suit thespecified housing and wall / ceiling construction. Fill any gaps between camera housing and wall / ceiling withSikaflex 1A or equal approved epoxy filler. Ensure front cover remains removable.

    To enable the observation of detainees in a darkened padded cell, an infra red imager shall be recess mounted in the

    ceiling, or at high level in the wall in an approved high security camera housing. Due to the imager's heat output,ensure adequate rear ventilation is provided.

    See custodial facilities Closed Circuit Television section on page 9.

    1.5.3.5 WALL ELEMENTS1.5.3.5.1 GLASSThe approved glass types and pane sizes have been selected after testing by the CSIRO Division of Building,Construction & Engineering in accordance with AS2208 - 1978 Safety Glazing Materials for use in Building(Human Impact Considerations). Cracking of the glass was considered failure. No variation from the approvedglass manufacturer and type is permitted. Minimal variation from the approved pane size is permitted. Site measureall pane sizes prior to ordering.

    Each pane of glass shall the brand name indelibly marked in one corner.

  • 7/22/2019 7. Wa Police Building Code Custodial Design Guidelines

    27/39

    WESTERN AUSTRALIA POLICE BUILDING CODE

    CUSTODIAL DESIGN GUIDELINES

    REVISION 4 October 2011/ PRINTED 17:22 09/08/2012 27

    For further information refer Western Australia Police Service file Accommodation Buildings WA Police ServiceBuilding Code 01039 04 FV002

    1.5.3.5.2 DOORSAll cell doors except the padded cell door shall be as per details L-334A, L-335A and L-336. The padded cell doorshall be as per detail L-301.

    Pressed cell door frames shall be formed from a minimum 3 mm thick Galvabond coated sheet steel and have acontinuous stop to the head and jambs.

    The doors are to be hung on approved hinges, which allow for 180ooutwards opening. The doors shall open awayfrom the direction of access and be easily latched in the open position. Mounting height of hold open device shallbe 2000 mm. Door stoppers shall be provided to prevent damage to walls.

    Door locks shall be approved deadlocks, key operated from the corridor side only and keyed alike as part of a

    station master key system. It should be noted that certain models of "Chubb" locks cannot be keyed alike with other"Chubb" lock models.

    Provide four keys for each set of keyed alike locks. It should be noted that Chubb keys are supplied and charged forseparately from the lock.

    Provide a white board within the centre rail of the door as indicated on the standard details. No pen tray is required.

    Luminous cell numbers shall be provided to enable easy identification at night or during a power failure. Numbersshall be fixed to door frame head.

    Doors are not to be painted. Door frames shall be painted to match the lower wall colour. Refer to page 22 forcolour. An approved anti-vandal paint shall be applied to the door frame.

    1.5.3.5.3 OBSERVATION WINDOWSAll General, Trustee and Holding Cells shall be provided with observation windows, as per details L-305 or L-306,where all areas within the cell cannot be viewed via the door observation window. No observation windows shall beprovided in the Padded Cell.

    An observation window shall be located:

    so that the ability of male detainees to view into female cells and vice versa is avoided; and out of public view.Observation windows:

    frames shall be - steel framed, be painted using an approved anti-vandal paint to match the wall colour. Refer to page 22 for wall colours, securely fixed to the wall, and flush with the cell wall finish;

    shall have a nominal sill height of 1200 mm; and glazing shall be Pilkingtons 15 mm thick glass, toughened to AS 2208, with a standard pane size of 620 mm x

    395 mm and glazed as per detail L-310. Multiple panes may be used to increase the overall window size.However, each pane must be fully glazed to the steel frame. Each pane of glass shall have the brand nameindelibly marked in one corner.