6.6 pressure sensor
TRANSCRIPT
www.distech-controls.com
PDIGR-LP2 Series Low Pressure Transducers
Overview
The PDIGR-LP2 Series are low pressure transducers. These devices can be used to measure positive, negative or differential pressure in the ranges of 1”W.C. to 12”W.C. (200 to 2000Pa). The piezoresistive sensor is ideal for monitoring the pressure of air or other clean inert gases and is limited only to those media which will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM and neoprene seals.
The PDIGR-LP2 Series features field selectable pressure ranges and output signal types for the most flexible applications. The output signal is factory calibrated and temperature compensated for highest startup accuracy and trouble-free operation. Available options include LCDs and integrated static pressure probes.
This product offers a cost effective solution for customers who wish to have ease of installation to their Building Automation System.
Applications
Used for monitoring filters.
Used for measuring duct static pressure.
Used for measuring velocity pressure.
Features & Benefits
Attractive enclosures are well received by architects and building owners
Economical
Optional LCD
Optional integrated pressure probe
Accurate pressure monitoring for increased comfort
Functional weather resistant ABS enclosure
24V AC/DC power supply is standard
Field selectable pressure ranges and output signals
Models with ranges in Pascals
PDIGR-LP2 Series
www.distech-controls.com
Product Warranty & Total Quality Commitment
Distech Controls PDIGR-LP2 Series product line is built to meet rigorous quality standards and carries a five-year warranty. Distech Controls is an ISO 9001 registered company. Distech Controls’ products provide both the contractor and the end user with the flexibility of using “best-of-breed” products in system design.
Available Low Pressure Transducer Models
PDIGR-LP2Ayy Low Pressure Transducer
- Monitor duct static pressure, static pressure across filters
- ABS Enclosure
PDIGR LP2AyyS Low Pressure Transducer with Integrated Static Pressure Probe
- Monitor Duct static pressure, static pressure across filters
- ABS Enclosure
PDIGR-LP2Byy Low Pressure Transducer with LCD
- Monitor Duct static pressure, static pressure across filters
- ABS Enclosure
PDIGR-LP2ByyS Low Pressure Transducer with Integrated Static Pressure Probe and LCD
- Monitor Duct static pressure, static pressure across filters
- ABS Enclosure
Model Options yy – Pressure Range Option
Related Products
Pitot/Static Tubes
HFO-0016 7.5” aluminum pitot tube
HSO-0016 7.5” aluminum static tube
HFO-0016-K Two 7.5” aluminum pitot tubes c/w 6’ pneumatic tubing
HSO-0016-K 7.5” aluminum static tube c/w 3’ pneumatic tubing
Flow Sensors
SSS-1002 Differential pressure flow sensor 4” ABS
SSS-1003 Differential pressure flow sensor 6” ABS
SSS-1004 Differential pressure flow sensor 8” ABS
SSS-1005 Differential pressure flow sensor 10” ABS
Calibration
PDIGR-LP2-NST NIST calibration certificate
For more information on these or other Distech Controls products please refer to our web site at www.distech-controls.com or contact [email protected].
*05DI-DSLP2XX-10*
05DI-DSLP2XX-10
PDIGR-LP2 Series
www.distech-controls.com
Product Specifications
Environmental Electrical
Operating Temperature: 0oC to 60
oC; 32
oF to 140
oF Input Power: 12 to 28Vac; 15 to 35Vdc (non isolated half
Storage Temperature: 0oC to 70
oC; 32
oF to 158
oF wave rectified)
Relative Humidity: 10 to 90% Non-condensing Supply Current @ 24Vdc: < 4mA
Enclosure Output: User selectable:
Material: High impact ABS, plenum rated with optional 4-20mA (2 wire), 0-5Vdc and 0-10Vdc (3 wire)
gasket around cover Accuracy: ±1% F.S.O.
Color: Black Long Term Stability: < ± 1% F.S.O. per year
Dimensions (overall): 4.55” x 3.30” x 2.10” (111mm x 84mm x 53mm) Thermal Effects: < ± 3% F.S.O. over compensated range
Shipping Weight: Input Voltage Effects: Negligible over specified operating range
- PDIGR-LP2Ayy 0.45lbs (0.99kg) Current Drive Capability: 400 ohms maximum @ 24Vdc
- PDIGR-LP2AyyS 0.60lbs (1.32kg) Voltage Drive Capability: 2kΩ minimum for 0-5Vdc signal
- PDIGR-LP2Byy 0.50lbs (1.10kg) 10kΩ minimum for 0-10Vdc signal
- PDIGR-LP2ByyS 0.65lbs (1.43kg) Protection Circuitry: Reverse voltage protected and output limited
Pressure Connections: Barbed ports for 0.17" (4.3mm) ID flexible tubes Response Time: 1ms maximum
Wiring Connections: Screw terminal block (14 to 22 AWG) Zero Adjust: Push button auto-zero
Elec. Conduit Connection: Access hole for ½" NPT conduit or cable gland Pressure
Temp. compensated range: 10°C to 50°C; 50°F to 122°F Over Pressure: 20 psi or 2X range (whichever is greater)
Media Compatibility: Limited only to those that will not attack Pressure Ranges: 00 - ±0.5", ±1.0", 0-1.0", 0-2.0" W.C.
polyetherimide, silicon, fluorosilicone, EPDM 01 - ±1.5", ±3.0", 0-3.0", 0-6.0" W.C.
and neoprene seals. Typically dry air or inert 02 - ±2.0", ±4.0", 0-4.0", 0-8.0" W.C.
gas, but liquid is allowed. 03 - ±2.5", ±5.0", 0-5.0", 0-10.0" W.C.
Agency Approvals 04 - ±3.0", ±6.0", 0-6.0", 0-12.0" W.C.
Material1: UL94-VB 05 - ±100, ±200, 0-200 / 0-400 Pa
06 - ±250, ±500, 0-500 / 0-1000 Pa
07 - ±400, ±800, 0-800 / 0-1600 Pa
08 - ±500, ±1000, 0-1000 / 0-2000 Pa
Electromagnetic Compatibility
1. All materials and manufacturing processes comply with the RoHS directive .
Specifications subject to change without notice. Distech Controls logo is a trademark of Distech Controls Inc.; All other trademarks are property of their respective owners.