58889354-oc-relay-ion
TRANSCRIPT
-
7/29/2019 58889354-Oc-Relay-ion
1/47
Basic Information
O/C E/F Relay & Time Coordination 1
O/C E/F Relay &Time Coordination
Basic
Information
-
7/29/2019 58889354-Oc-Relay-ion
2/47
O/C E/F Relay & Time Coordination 2
General Circuit Diagram200/1 Amp
R Ph O/C (51R)
E/F (51N)
B Ph O/C (51B)
150 Amp
150 Amp
150 Amp
0.75 Amp
0.75 Amp
0.75 Amp
0.0 Amp
C11
C31
C51
C71
S1
S1
S1
S2
P1 P2
-
7/29/2019 58889354-Oc-Relay-ion
3/47
O/C E/F Relay & Time Coordination 31S1R
1S2R
1S3R
1S1Y
1S2Y
1S3Y1S1B
1S2B
1S3B
2S1R
2S2R
2S3R
2S1Y2S2Y
2S3Y
2S1B
2S2B
2S3B
3S1R
3S2R3S3R
3S1Y
3S2Y
3S3Y
3S1B
3S2B
3S3B
R Ph CT
Y Ph CT
B Ph CT
Core-1Core-2Core-3
Core-1Core-2Core-3
Core-1Core-2Core-3
A11
A31
A51
A71
C11
C31
C51
C71
D71
D11
D31
D51
Yard MB Wiring
-
7/29/2019 58889354-Oc-Relay-ion
4/47
O/C E/F Relay & Time Coordination 41S1R
1S2R
1S3R
1S1Y
1S2Y
1S3Y1S1B
1S2B
1S3B
2S1R
2S2R
2S3R
2S1Y2S2Y
2S3Y
2S1B
2S2B
2S3B
3S1R
3S2R3S3R
3S1Y
3S2Y
3S3Y
3S1B
3S2B
3S3B
R Ph CT
Y Ph CT
B Ph CT
Core-1Core-2Core-3
Core-1Core-2Core-3
Core-1Core-2Core-3
A11
A31
A51
A71
C11
C31
C51
C71
D71
D11
D31
D51
Yard MB Wiring
-
7/29/2019 58889354-Oc-Relay-ion
5/47
Terminal Diagram of MiComP141
O/C E/F Relay & Time Coordination 5
-
7/29/2019 58889354-Oc-Relay-ion
6/47
O/C E/F Relay & Time Coordination 6
Single Line to Ground Fault200/1 Amp
R Ph O/C (51R)
E/F (51N)
B Ph O/C (51B)
1500 Amp
7.5 Amp
7.5 Amp
C11
C31
C51
C71
S1
S1
S1
S2
P1 P2
-
7/29/2019 58889354-Oc-Relay-ion
7/47
O/C E/F Relay & Time Coordination 7
Electromagnetic Induction relays
50%75%100%125%150%
200%
1 2
-
7/29/2019 58889354-Oc-Relay-ion
8/47
Relay Operation Time - 1
O/C E/F Relay & Time Coordination 8
E/F PSM 30% i.e. 0.3 Amp
E/F Relay Current 7.5 AmpE/F Relay Current is 7.5/0.3 = 25 Times
its operating current
From Graph for 25 Times relay operating
current for TMS = 0.15 relay time of
operation would be @ 0.35 Sec
O/C PSM 100%
O/C Relay Current 7.5 Amp
It is 7.5 times relay operating current
From graph for 7.5 Times relay operating
current and for TMS = 0.1 time of
operation for the relay would be 0.35 Sec
( Zoom out Graph)
http://iec-a%20normal%20inverse%20jpeg.jpg/http://iec-a%20normal%20inverse%20jpeg.jpg/ -
7/29/2019 58889354-Oc-Relay-ion
9/47
Relay Operation Time - 2
O/C E/F Relay & Time Coordination 9
Actually our problem is to decide relay settings and not relay time of
operations as shown previously
Hence Unknowns are
Relay PSM
Relay TMS
Whereas known facts areRelay placement and purpose of use
Relay current during fault ( i.e. CT secondary current during fault. )
Relay desired time of operation.
General Steps
1) Decide PSM2) Find out fault current
3) Find out multiple of relay set current as per decided PSM in step-1
4) Find out time of operation for above multiple of current and TMS=1 using
relay characteristic curve
5) Decide relay time of operation as per protection needs
6) Find out TMS = Required Time of operation /Time of operation with TMS =1
-
7/29/2019 58889354-Oc-Relay-ion
10/47
Basic Information Selection of PSM
O/C E/F Relay & Time Coordination 10
E/F PSM generally selected as 30% ( Other than 30% settings may also be selected but about thisdiscussed somewhere else in the presentation)
For O/C PSM is selection depends upon place and purpose of use for example
1.Transformer O/C protection
a) Transformer HV or LV side O/C relay PSM settings should be in commensuration with transformer
full load current and respective CT ratio such that PSM = T/F Full load current / CT ratio
( Generally expressed in %)
b) For example for a 25 MVA transformer HV side full load current is 109 A if HV CT ratio is 200/1
Amp then PSM =109/200 55% ( exact value 54.5%)
c) For old type numerical relay it was not possible to go as near as possible to value calculated fromabove formula due to large steps available
d) Under such condition it is decision as per local condition to select higher or lower nearest PSM
e) In above example it is customary to select 50%, however due to this selection there is apparent
loss of about 10% capacity of the T/F
f) It is also possible to select 75% but load on transformer is to be monitored carefully ( and manually
)2.For 220-132 kV feeder
Here generally it is customary to select relay PSM as per-
a) Line conductor allowable loading limit
b) CT primary normal current
c) Substations capacity/normal load feed by the line
d) Considering above facts it is very common to select 100% PSM for 132kV lines with CT ratio 400/1
Amp
e) For 220kV lines with CT ratio 800/1 amp and conductor 0.4 ACSR or 0.525 AAAC it is 100%
a)For 33-11kV feedera) As per local feeder condition, load pattern and needs ranging between 50% to 100%
-
7/29/2019 58889354-Oc-Relay-ion
11/47
Relay Operation Time - 3
Desired time of operation will depend upon
a) Equipment being protected
b) Time discrimination from down stream protection (150 ms 250 ms)
c) Time of operation of main protection etc.
For transformer LV side protection it is common to adopt 250 ms as operating
time. This is so as to have 150 ms time discrimination from 100 ms relay time of
operation for lower (feeder) protection.
When relays are used as backup protection of 132kV lines its time of
operation shall be equal to Z-2 time of operation (300 350 ms).
Once these two things decided there remains only mathematical part
O/C E/F Relay & Time Coordination 11
-
7/29/2019 58889354-Oc-Relay-ion
12/47
Worked out Example
O/C E/F Relay & Time Coordination 12
400/1 A
132 kV 33 kV400/1 A
25 MVA
33kV Bus fault level
1Ph 170 MVA , 3Ph 210 MVARelay current during fault
1Ph 7.43 Amp, 3 Ph 9.18 Amp
Relay PSM
E/F 30%,O/C 100 %
Multiple of relay current
E/F 25, O/C 9.
Time of operation with TMS = 1
E/F 2.2 s, O/C 3.0 Sec
Desired time of operation
E/F 250 ms, O/C 250 ms
TMS
E/F 0.114, O/C 0.083
Roundup to
E/F 0.125, O/C 0.1
-
7/29/2019 58889354-Oc-Relay-ion
13/47
More Information
O/C E/F Relay & Time Coordination 13
O/C E/F Relay &Time Coordination
More
Information
-
7/29/2019 58889354-Oc-Relay-ion
14/47
Introduction
Fuse wire is simplest protection
Fusing ampere of copper wire of diameter d
expressed in Cm is given by the formula A =
2530*d3/2
Time taken by fuse to blow off depends up onfusing amperes
O/C E/F Relay & Time Coordination 14
15
-
7/29/2019 58889354-Oc-Relay-ion
15/47
Introduction
For a wire of length L carrying current I
and diameter d heat produced is H = I2R
H = I2 (L/A)
H = I2 ( L/(d2/4))
Heat dissipated = K (d)L ( i.e.
proportional to surface area where K
is constant of proportionality) Temperature will be steady state if heat
generated is equal heat dissipated or
I2 ( L/(d2/4)) = K (d)L
I2 ( 1/(d2/4)) = K d
I2 =K d3
I = K d 3/2
And by experiments for normal ambient
temperature value of K for copper is
determined as 2530 for d expressed in
Cm.
O/C E/F Relay & Time Coordination 15
SWG D in mm D in Inch Amp FusingAmp
Fusing Amp byFormula
40 0.122 0.0048 1.5 3 3.41
39 0.132 0.0052 2.5 4 3.84
38 0.152 0.006 3 5 4.74
37 0.173 0.0681 3.5 6 5.76
36 0.193 0.0076 4.5 7 6.78
35 0.213 0.0084 5 8 7.86
34 0.234 0.00921 5.5 9 9.06
33 0.254 0.01 6 10 10.24
32 0.274 0.0108 7 11 11.47
31 0.29464 0.0116 8 12 12.80
30 0.315 0.0124 8.5 13 14.14
29 0.345 0.0136 10 16 16.21
28 0.376 0.0148 12 18 18.45
27 0.416 0.0164 13 23 21.47
26 0.457 0.018 14 27 24.72
25 0.508 0.02 15 30 28.97
24 0.559 0.022 17 33 33.44
23 0.61 0.024 20 38 38.12 More
16
http://9%20annexure.doc/http://9%20annexure.doc/http://9%20annexure.doc/ -
7/29/2019 58889354-Oc-Relay-ion
16/47
Protection of transformer by a fuse
O/C E/F Relay & Time Coordination 16
For T/F with normal load of 100 AmpFuse Transformer
Current FusingTime
Current SafeOperation Timeas perIEEE
SafeOperationTime WithFOS 2.5
200 10000 200 1800 720
430 5 300 300 120
1200 0.4 475 60 24
1800 0.2 630 30 12
2800 0.1 1130 10 4
2500 2 0.8
17
-
7/29/2019 58889354-Oc-Relay-ion
17/47
Simplest Protection Fuse
Thesecharacteristicgraphs aregenerally double
log graph This is due to
including from verysmall to very largevalues on both axis
O/C E/F Relay & Time Coordination 17
-
7/29/2019 58889354-Oc-Relay-ion
18/47
19
-
7/29/2019 58889354-Oc-Relay-ion
19/47
General mathematical formula for timecharacteristic of the relay as per IEC
Standards
K
Time Of Operation = ---------------------
( ( Is/I
b) - 1 )
O/C E/F Relay & Time Coordination 19
O/C / & C 20
-
7/29/2019 58889354-Oc-Relay-ion
20/47
General mathematical formula for time characteristic
of the relay shown on previous slide, with parameter
values for different curves are shown here
O/C E/F Relay & Time Coordination 20
Characteristic K
Normal Inverse 0.02 0.14
Very Inverse 1 13.5
Extremely Inverse 2 80
Long Time Inverse 1 120
-
7/29/2019 58889354-Oc-Relay-ion
21/47
O/C E/F R l & Ti C di ti 22
-
7/29/2019 58889354-Oc-Relay-ion
22/47
Use of Log Scale-2
O/C E/F Relay & Time Coordination 22
O/C E/F R l & Ti C di ti 23
-
7/29/2019 58889354-Oc-Relay-ion
23/47
Use of Log Scale-3
O/C E/F Relay & Time Coordination 23
O/C E/F R l & Ti C di ti 24
-
7/29/2019 58889354-Oc-Relay-ion
24/47
Use of Log Scale-4
O/C E/F Relay & Time Coordination 24
-
7/29/2019 58889354-Oc-Relay-ion
25/47
O/C E/F R l & Ti C di ti 26
-
7/29/2019 58889354-Oc-Relay-ion
26/47
Transformer Protection Damage Curve
Transformer damage curve as per IEEE
57.109 for class III transformers ( 5 MVA to
30 MVA )
O/C E/F Relay & Time Coordination 26
O/C E/F Relay & Time Coordination 27
-
7/29/2019 58889354-Oc-Relay-ion
27/47
Protection of Transformer by O/C Relay
O/C E/F Relay & Time Coordination 27
Trafo
Damage
Curve
Long Time
Inverse
Extremely Inverse
Normal Inverse
O/C E/F Relay & Time Coordination 28
-
7/29/2019 58889354-Oc-Relay-ion
28/47
End of More Information
O/C E/F Relay & Time Coordination 28
After understanding basics of relaycharacteristic curves and its selection
according to protection needs we will
turn to allied information about O/C E//Frelaying
This allied information will prove helpful
in overall understanding aboutdevelopment of protective relays and its
use in power system
O/C E/F Relay & Time Coordination 29
-
7/29/2019 58889354-Oc-Relay-ion
29/47
Basic Information
O/C E/F Relay & Time Coordination 9
O/C E/F Relay &Time Coordination
Allied
Information
O/C E/F Relay & Time Coordination 30
-
7/29/2019 58889354-Oc-Relay-ion
30/47
Disadvantages of fuses
Though simple less accurate ( If Rewirable)
Because of previous heating effect
Ambient Temperature
In consistencies in material
Limitations for breaking capacities hence suitable for LV and to
some extent MV HRC Fuses
More accurate
Higher rupturing capacities
Requires time for replacement
Suitable for LV and to some extent MV
O/C E/F Relay & Time Coordination
-
7/29/2019 58889354-Oc-Relay-ion
31/47
-
7/29/2019 58889354-Oc-Relay-ion
32/47
O/C E/F Relay & Time Coordination 33
-
7/29/2019 58889354-Oc-Relay-ion
33/47
General Requirements of Protective Scheme
For any protective device following Functional
Characteristic are important.
Sensitive
Selectivity
Speed
Reliability
( Note:- 3 S & 1 R)
As a improvement over simple fuses (in aboveareas) other protective devices get developed
with the advancement of power system
O/C E/F Relay & Time Coordination
http://link-functional%20characteristics.jpg/http://link-functional%20characteristics.jpg/ -
7/29/2019 58889354-Oc-Relay-ion
34/47
O/C E/F Relay & Time Coordination 35
-
7/29/2019 58889354-Oc-Relay-ion
35/47
O/C E/F Relay & Time Coordination
Changing Trend In Protective Relaying
Protection relay is a tool for
protection engineer
During last 30 years relay
operating principles changed
very drastically
Electromagnetic Relays
Static Relays
Digital Relays
Numerical Relays
Though it is not required to
design a relay or repair a relay
at site it is customary to havesome working knowledge of
these relays for better
understanding and use of it
O/C E/F Relay & Time Coordination 36
-
7/29/2019 58889354-Oc-Relay-ion
36/47
O/C E/F Relay & Time Coordination
Electromagnetic Induction relays
O/C E/F Relay & Time Coordination 37
-
7/29/2019 58889354-Oc-Relay-ion
37/47
O/C E/F Relay & Time Coordination
Static Relays
-
7/29/2019 58889354-Oc-Relay-ion
38/47
O/C E/F Relay & Time Coordination 39
-
7/29/2019 58889354-Oc-Relay-ion
39/47
O/C E/F Relay & Time Coordination
Numerical Relay
Functions
Available
inNum
-
7/29/2019 58889354-Oc-Relay-ion
40/47
O/C E/F Relay & Time Coordination 41
-
7/29/2019 58889354-Oc-Relay-ion
41/47
Introduction
O/C E/F Relay & Time Coordination
R3 R2 R1
A B C
10 sec.25 sec.40 sec.
R3 R2 R1
A B C
200 ms220 ms180 ms
R3 R2 R1
110 ms350 ms500 ms
S
S
S
O/C E/F Relay & Time Coordination 42
-
7/29/2019 58889354-Oc-Relay-ion
42/47
Study of Time Co-ordination and its role in design of protection scheme.
Over Current and Earth Fault Protection is
used for
Protecting a equipment
Selective tripping of faulty section of the
power system
Backing up the main protection
O/C E/F Relay & Time Coordination
O/C E/F Relay & Time Coordination 43
-
7/29/2019 58889354-Oc-Relay-ion
43/47
Role of Over Current Relay in Protecting the Equipment
It is obvious that over current protective system should
act and interrupt the fault current before to damage ofequipment due to fault current through it.
Power system equipments include Line, Isolator, CT,
Breaker, Transformer
Obviously Transformer is most costliest and delicate (forfault currents) equipment first we will consider its
damage curve and decide parameters of protection
system so that it should act fast enough to protect the
transformer This can be ascertained with the help of Damage Curve
of the transformer and time-current curve of the
protective system
O/C E/F Relay & Time Coordination
O/C E/F Relay & Time Coordination 44
-
7/29/2019 58889354-Oc-Relay-ion
44/47
Role of Over Current Protection in Selective Tripping
It is obvious that only that part of the power system
should get disconnected where the fault exists Hence proper time co-ordination should be there so as to
let the down stream protection should act fast enough
and up-stream protection should give sufficient time for
down stream protection to act
Otherwise un-necessary larger area get affected
O/C E/F Relay & Time Coordination
O/C E/F Relay & Time Coordination 45
-
7/29/2019 58889354-Oc-Relay-ion
45/47
O/C E/F Relay & Time Coordination
Backup Protection
When ever main protection fails to separate the
faulty section backup protection take up this role As such there is inherent time delay in operation
of backup protection This backup protection can be employed in main
protection itself as additional function, butinvariably it is employed as a separate relay toensure its operation even if failure ofquantities/links which are common to bothfunctions such as- DC Source PT supply Relay hardware Main CTs
-
7/29/2019 58889354-Oc-Relay-ion
46/47
O/C E/F Relay & Time Coordination 47
-
7/29/2019 58889354-Oc-Relay-ion
47/47
y
Backup Relay Time Coordination
A C
E
F
X Y
Z
M