5300 users's manual - · pdf filect/pt detection ... application literature for proper...
TRANSCRIPT
Model 5300Model 5300Model 5300Model 5300Model 5300
Three PhaseThree PhaseThree PhaseThree PhaseThree PhasePPPPPower Analyzerower Analyzerower Analyzerower Analyzerower Analyzer
UserUserUserUserUser’s Manual’s Manual’s Manual’s Manual’s Manual
While every precaution has been exercised in the compilation ofthis document, Magtrol, Inc. assumes no responsibility for errorsor omissions. Additionally, no liability is assumed for any damagesthat may result from the use of the information contained withinthis publication.
Trademark Acknowledgments
GPIB-PC is a trademark of National Instruments Corporation.
IBM is a registered trademark International Business Machines Corporation.
QuickBASIC is a registered trademark of Microsoft Corporation.
GE-MOV is a registered trademark of the General Electric Corporation.
FLUKE is a registered trademark of the John Fluke Mfg. Company.
Microsoft is a registered trademark of Microsoft Corporation.
Supercon is a registered trademark of the Superior Electric Company.
wwwwwwwwwww.w.w.w.w.mmmmmagtragtragtragtragtroooool.cl.cl.cl.cl.cooooommmmm
Sales and TSales and TSales and TSales and TSales and Technical Assistanceechnical Assistanceechnical Assistanceechnical Assistanceechnical Assistance
Manufacturers of:
Motor Test Equipment!
Hysteresis Brakes and Clutches
70 Gardenville ParkwayBuffalo, New York 14224 USA
Tel: (716) 668-5555 or 1-800-828-7844Fax: (716) 668-8705
MAGTROL, INC.MAGTROL, INC.MAGTROL, INC.MAGTROL, INC.MAGTROL, INC.
Rev. A 08/00
iii
TTTTTable of Contentsable of Contentsable of Contentsable of Contentsable of Contents
SALES AND TECHNICAL ASSISTANCE .............................................................................................. ii
1 - INTRODUCTION ................................................................................................................................ 1Abbreviations ...................................................................................................................................................... 1
Unpacking ........................................................................................................................................................... 1
Power .................................................................................................................................................................. 1
Fuse Replacement ............................................................................................................................................... 1
Safety .................................................................................................................................................................. 1
Connectors .......................................................................................................................................................... 1
Maximum Ratings............................................................................................................................................... 1
Installation ........................................................................................................................................................... 2ORIENTATION .................................................................................................................................................................... 2ELECTRICAL LOAD ............................................................................................................................................................ 2IEEE-488 (GPIB) ........................................................................................................................................................... 2
Initial Checkout ................................................................................................................................................... 2
Transient Overloads ............................................................................................................................................ 2
Current Overload................................................................................................................................................. 2
2 - SPECIFICATIONS ............................................................................................................................. 3Voltage ................................................................................................................................................................ 3
Current ................................................................................................................................................................ 3
Meter Impedance ................................................................................................................................................. 3
Resolution ........................................................................................................................................................... 3Isolation ............................................................................................................................................................... 3
Display Auto Zero ............................................................................................................................................... 3
Analog Outputs ................................................................................................................................................... 3
Data Acquisition ................................................................................................................................................. 3ANALOG ........................................................................................................................................................................... 3DIGITAL ........................................................................................................................................................................... 4
Measurement Accuracy ....................................................................................................................................... 4
Accuracy Certification ........................................................................................................................................ 4
3 - CONNECTING THE 5300 .................................................................................................................. 5Surge Protection .................................................................................................................................................. 5
Figure 1. Transient Voltage Suppression ..................................................................................................... 5
Connectors .......................................................................................................................................................... 5AMPS ............................................................................................................................................................................... 5VOLTS .............................................................................................................................................................................. 5
Single Phase AC or DC Connections ................................................................................................................. 6Figure 2. Single Phase AC or DC Connections ........................................................................................... 6
3-Phase 3-Wire Delta Connections ..................................................................................................................... 7Figure 3. 3-Phase 3-Wire Delta Connections .............................................................................................. 7
3-phase, 3-Wire WYE Connections .................................................................................................................... 7
iv
Figure 4. 3-phase, 3-Wire WYE Connections ............................................................................................... 7
3-Phase, 4-Wire WYE Connections ................................................................................................................... 8Figure 5. 3-Phase, 4-Wire WYE Connections .............................................................................................. 8
3-Phase, Current and Potential Transformer Connections.................................................................................. 8Figure 6. 3-Phase, Current and Potential Transformer Connections ......................................................... 8
4 - OPERATION ...................................................................................................................................... 9General ................................................................................................................................................................ 9
Amperes Display ................................................................................................................................................. 9
Voltage Display .................................................................................................................................................. 9
Watts or Power Factor ........................................................................................................................................ 9Mode Selections ................................................................................................................................................ 10
Figure 7. Mode Selections .......................................................................................................................... 10MODE HOLD ................................................................................................................................................................... 10MODE AVG ................................................................................................................................................................... 10MODE POWER FACTOR (PF) ........................................................................................................................................... 10MODE PH. V. ................................................................................................................................................................ 10
Display Selections ............................................................................................................................................. 11Figure 8. Display Selections ....................................................................................................................... 11
DISPLAY Ø1, Ø2, Ø3 ..................................................................................................................................................... 11DISPLAY SKW ............................................................................................................................................................... 11
Voltage Ranges ................................................................................................................................................. 11Figure 9. Voltage Range Selections ............................................................................................................ 11
Amperes Range ................................................................................................................................................. 12Figure 10. Current Range Selections ........................................................................................................... 12
Analog Output Option ...................................................................................................................................... 12Figure 11. Analog Output Connections ........................................................................................................ 12
5 - CT/PT INSTALLATION .................................................................................................................... 13Calibration ......................................................................................................................................................... 13
CT/PT Detection ............................................................................................................................................... 13Figure 12. Current & Potential Transformer Selections ............................................................................. 13
CT/PT Ratio Range ........................................................................................................................................... 13
Digital Range .................................................................................................................................................... 13
GPIB-CT/PT Programming .............................................................................................................................. 13
Changing or Removing CT/PT Values ............................................................................................................. 14
6 - GPIB COMMUNICATION................................................................................................................. 15GPIB (IEEE-488) .............................................................................................................................................. 15
Hardware Installation ........................................................................................................................................ 15
Software Installation ......................................................................................................................................... 15
Primary Address ................................................................................................................................................ 15Figure 13. GPIB Address Selection .............................................................................................................. 15
7 - 5300 PA INSTRUCTION SET .......................................................................................................... 16PC to 5300 PA .................................................................................................................................................. 16
5300 PA to PC .................................................................................................................................................. 16
v
"SGL" INSTRUCTION ....................................................................................................................................................... 16"FULL" INSTRUCTION ....................................................................................................................................................... 16
Data Rate ........................................................................................................................................................... 17
“Open” Instruction ............................................................................................................................................ 17
Instruction ......................................................................................................................................................... 17
Programming Example ..................................................................................................................................... 17
8 - OPERATING PRINCIPLES.............................................................................................................. 19Amperes Transducing ....................................................................................................................................... 19
Figure 14. 5300 Current Shunt Inputs .......................................................................................................... 19
Voltage Sensing ................................................................................................................................................ 19Analog Processing ............................................................................................................................................ 19
Figure 15. 5300 Block Diagram ................................................................................................................... 20
Digital Processing ............................................................................................................................................. 20
Display “Help” .................................................................................................................................................. 20
Polyphase Line Balance .................................................................................................................................... 20
9 - CALIBRATION ................................................................................................................................. 21General .............................................................................................................................................................. 21
Figure 16. Calibration Verification Test Setup ............................................................................................ 21
Test Setup.......................................................................................................................................................... 21
Calibration Verification .................................................................................................................................... 22VOLTS CALIBRATION CHECK F1 ....................................................................................................................................... 22AMPERES CALIBRATION CHECK ........................................................................................................................................ 23WATTS CALIBRATION CHECK ........................................................................................................................................... 23
Minor Adjustment (If Needed) ......................................................................................................................... 23Figure 17. Trimpot Adjustment Locations .................................................................................................... 24
VOLTS ZERO ................................................................................................................................................................... 24AMPERES ZERO ............................................................................................................................................................... 24VOLTS SCALE FACTOR ..................................................................................................................................................... 24AMPERES SCALE FACTOR ................................................................................................................................................. 24VOLTS BALANCE ............................................................................................................................................................. 25CURRENT BALANCE ......................................................................................................................................................... 25WATTS SCALE FACTOR .................................................................................................................................................... 25
APPENDIX A: SCHEMATIC DRAWINGS ........................................................................................... 26Circuit Board 78B128 - LED Display .............................................................................................................. 26Circuit Board 78B145 - Digital Readout & MPU ............................................................................................ 27
Circuit Board 78B146 - Analog Input board .................................................................................................... 28
Circuit Board 78B147 - Converter Board ......................................................................................................... 29
Circuit Board 78B149 - Switchboard ............................................................................................................... 30
Circuit Board 78B153 - Switch Interface ......................................................................................................... 31
Circuit Board 78B154 - Counters Board .......................................................................................................... 32
Circuit Board 78B175 ....................................................................................................................................... 33
MAGTROL LIMITED WARRANTY ....................................................................................................... 34
vi
This page intentionally left blank.
1
ABBREVIATIONS
PA - Model 5300 Power Analyzer.
GPIB - IEEE-488 Instrument Bus Standard.
LED - front panel indicator light.
A, V, W, PF and VA: Amperes, Volts, Watts, PowerFactor and Volt Amperes, respectively
MPU - Microprocessor unit.
LSD, LSB - least significant digit or bit.
CMRR - common mode rejection ratio.
UNPACKING
The Model 5300 is packed in reusable, shock resistantpacking material that will protect the instrument duringnormal handling. In the event of shipping damage,immediately notify the carrier and Magtrol CustomerService Dept. Save all shipping materials for reuse whenreturning the instrument for calibration or servicing.
POWER
The 5300 PA is factory wired for either 120 or 240Vrms, 50/60 Hz, power at 120 volt amps, max. Theline cord is a detachable NEMA standard 3 wire whichplugs into the rear access power entry and filter moduleof the 5300 PA. The line cord must be detached fromthe PA during servicing.
NOTE: The standard 5300 is factorywired for 120 Vrms power.Wiring for 240 Vrms is availableon special order.
FUSE REPLACEMENT
Remove the line cord and carefully pry up and removethe fuse holder. Use a 2 Amp slow blow fuse for 120Vrms or a 1 Amp slow blow fuse for 240 Vrms power.
1 - Introduction1 - Introduction1 - Introduction1 - Introduction1 - Introduction
SAFETY
Securely ground the 5300 PA case by connecting a goodearth ground at the ground stud that is located on therear panel. Use a number 12 AWG wire, or larger.
CONNECTORS
The following plugs mate with 5300 PA connectors:
Superior Electric Supercon®
INPUT (plug, red, female) - PS100GR
OUTPUT (plug, red, male) - PP100GR
VOLTS HIGH (plug, black, female) - PS25GB
VOLTS LOW (plug, white, female) - PS25GWT
For your convenience, the above connectors are suppliedwith your 5300 PA.
Use only the above connectors.
NOTE : GPIB (IEEE-488) 24 Pin busstandard cable is not includedwith the 5300 PA and must beordered separately.
MAXIMUM RATINGS
LOAD current: 100 Amperes rms, continuous.
200 Amperes rms, 5 sec. max.
REMOTE VOLTAGE SENSE: Line to line is 600Vrms. Also, do not exceed 600 Vrms differentialbetween the VOLTS INPUT and AMPS OUTPUTterminals.
2
Magtrol Model 5300 Three Phase Power AnalyzerChapter 1 - Introduction
INSTALLATION
ORIENTATION
The 5300 PA must be mounted within ± 20 degreesfrom horizontal. This ensures proper operation of themercury shunt bypass relays.
ELECTRICAL LOAD
Use wire rated for the maximum load current and voltageexpected.
Hint: Use wire gauge large enough to ensure goodconnector set screw compression on the wire leads.Soldering may be used instead of, or in addition to theset screw.
IEEE-488 (GPIB)
Use only high quality shielded cable conforming to thebus standards.
INITIAL CHECKOUT1. Make sure the circuit is completely de-energized
by removing all voltage sources.
2. Plug the 5300 PA into the 50/60 Hz power mains.
3. Switch the POWER rocker switch (red) to ON andobserve that the digit readouts flash on-off-on andthen indicate zero or a small number.
4. The VOLTS and AMPERES range switch indicatorlights will all illuminate. The voltage ranges willsequence down from 600 through 150, and thecurrent ranges will sequence down from 100 through5.
5. The 150 Volt and 5 Amp and AUTO indicatorsremain illuminated. The MODE indicators will notlight during this power-on sequencing.
6. Your 5300 PA has passed the initial check.
TRANSIENT OVERLOADS
Connect an appropriate transient suppressor in parallelwith all inductive loads. Consult the suppressor vendor'sapplication literature for proper selection and sizing.
Damage to the 5300 can result fromexcessive voltage transients generatedby unsuppressed inductive loads. Thisdamage is not within the scope of thenormal instrument service and is notcovered by the Magtrol Warranty.
CURRENT OVERLOAD
There are no fuses in the 5300 PA measuring circuits.Therefore, excessive current passed through the AMPSterminals will cause excessive internal heating andpossible unit damage.
This overload abuse is not covered bythe Magtrol Warranty.
Know your load conditions and double check allconnections. If an overload should occur, immediatelyremove all power, and locate and correct the problembefore re-energizing your circuit. If a circuit breaker isinstalled, it must be installed on the LOAD side of the5300 (downstream). This will keep the low impedanceof the input line connected to the 5300 PA for surgesuppression. If the line side must also contain a breaker,it should be delayed in operation to open after the loadside breaker has opened.
3
2 - Specifications2 - Specifications2 - Specifications2 - Specifications2 - Specifications
VOLTAGE
Three DC and AC Ranges:
• 150, 300, and 600 Volts DC and Volts rms.
Remote Voltage Sensing:
• Differential input - 110 dB CMRR.
• Maximum of 30 Volts peak, volts low terminalto amps output terminal.
CURRENT
Three DC and AC Ranges:
• 5, 25 and 100 Amps DC and Amps rms.
METER IMPEDANCE
Voltage, DC or AC:
• 3 Megohm load on each voltage range.
Current, DC or AC Ranges:
• 0.016 Ohm shunt resistance for 5 Amp range.
• 0.003 Ohm shunt resistance for 25 Amp ranges.
• 0.001 Ohm shunt resistance for 100 Amp range.
RESOLUTION
Processing resolution is 16 binary bits.
Voltage Display Resolution:
• All ranges < 9.999 V is ± 0.001 Volt.• Ranges > 10 V and < 99.9 V is ± 0.01 Volt.
• Ranges > 100 V is ± 0.1 Volt.
Current Display Resolution:
• All ranges < 9.999 A is ± 0.001 Amp.
• Ranges > 10 A and < 50 A is ± 0.01 Amp.
Power Display Resolution:
• Better than 0.015 % of the product of the activeVoltage and Amperes ranges.
GPIB: Amps, Volts and Watts
• Same as display resolution.
ISOLATION
1500 Vrms break down from input circuit to chassis(ground).
DISPLAY AUTO ZERO
When the A and V display indication is less than 0.5 %of range, the displayed value is set to ZERO. Refer toSection 5 - CT/PT Installation to disable the AUTOZERO function.
ANALOG OUTPUTS
This is an optional feature.
Analog AMPS, VOLTS and WATTS output signalsare DC proportional signals of 5.00 volts at full scale,for each AMPS, VOLTS and WATTS range. Ripple isless than 5 millivolts. The outputs are low impedanceoperational amplifiers <1 Ohm and <4 milliamperescurrent capacity. Each monitor signal and the commonare electrically isolated from the monitored circuits.Isolation voltage is 750 Volts continuous and 2500 Voltstest breakdown. Leakage current is less than 0.3 microAmps at 240 Vrms, 60 Hz. Vrms
DATA ACQUISITION
ANALOG
The conversion of true rms to DC is expressed as:
Vrms ≡ ( )1 2
0Tv t dt
T
∫• Rms to DC conversion averaging time constant:
Volts and Amps time constant TC ≅ 60 msec.
Watts time constant TC ≅ 120 msec.
Watts = V × I × cos θ (instantaneous)
4
Magtrol Model 5300 Three Phase Power AnalyzerChapter 2 - Specifications
DIGITAL
• Processing:
Integration period = 0.10 second.
Display update time = 2 readings per second.
• IEEE-488 (GPIB):
Synchronized = 0.1 sec. per reading
Non-synchronized is 0.04 to 0.07 sec perreading.
MEASUREMENT ACCURACY
Specified test conditions: Ambient temperature of 72°± 10°F and power factor of 0.1 to 1.0, lead or lag.
VOLTAGE - DC + (0.1% of reading + 0.2% of range)
VOLTAGE - AC:
10 Hz to < 20 Hz + 1.0% of range
20 Hz to < 45 Hz + (0.2% of reading + 0.3% of range)
45 Hz to < 10 kHz + (0.1% of reading + 0.2% of range)
10 kHz to 20 kHz + (0.2% of reading + 0.5% of range)
CURRENT - DC 25 and 100 Amp Ranges
+ (0.1% of reading + 0.2% of range)
CURRENT - AC: 5 Amp Range
10 Hz to < 20 Hz + 1.0% of range
20 Hz to < 45 Hz + (0.2% of reading + 0.3% of range)
45 Hz to < 1 kHz + (0.1% of reading + 0.2% of range)
1 kHz to < 5 kHz + (0.2% of reading + 0.3% of range)
5 kHz to < 10 kHz + (1.0% of reading + 1.0% of range)
10 kHz to 20 kHz + (2.0% of reading + 2.0% of range)
25 Amp Range
10 Hz to < 5 kHz same as 5 Amp range
5 kHz to 10 kHz + (2.0% of reading + 2.0% of range)
100 Amp Range
10 Hz to < 1 kHz + 0.5% of rng
1 kHz to 2 kHz + (2.0% of reading + 2.0% of range)
POWER - DC + (0.1% of reading + 0.2% of VA range)
POWER - AC ± [(0.1% of reading + 0.2% of (Ampsrange × Volts range)]
POWER FACTOR + (VA error ± W error)
CREST FACTOR Exceeds 3:1 (at 50% of range full scale)
TEMPERATURECOEFFICIENT + 0.01% of range per deg. C maximum
DISPLAY Digital display error ± 1 LSB.
ACCURACY CERTIFICATION
All instruments are shipped with a Certificate ofCalibration from Magtrol Inc. Magtrol policies andprocedures comply with MIL-STD-45662A.Measurement standards are traceable to the NationalInstitute of Standards and Technology (NIST).
Instrument calibration every six calendar months isnecessary to maintain full compliance with allspecifications. If a one year calibration cycle is used,all accuracy specifications are reduced by 0.1%. Afterone calendar year, the instrument is considered to beout of calibration.
5
3 - Connecting the 53003 - Connecting the 53003 - Connecting the 53003 - Connecting the 53003 - Connecting the 5300
Always install a properly rated circuitbreaker or fuse between the 5300 analyzerand the load. Also, make sure that yourpower source has its own fast-actingdisconnect and overload protection. See"Current Overload" in Chapter 1 -Introduction. Wire according to allapplicable wiring codes, making sure thewire gauge and insulation ratings areadequate for your application.
SURGE PROTECTION
Use Metal Oxide Varistors (MOV) or other equivalenttransient suppressors connected between lines at the load(across the load). These suppressors are an absolutenecessity when inductive loads are used. In 3-phasesystems, each load must have a suppressor. See Figure1 below.
CONNECTORS
Use the supplied Supercon® connectors.
AMPS
INPUT - PLUG, RED, FEMALE-(PS100GR)
OUTPUT - PLUG, RED, MALE-(PP100GR)
VOLTS
HIGH - PLUG, BLACK, FEMALE-(PS25GB)
LOW - PLUG, WHITE, FEMALE-(PS25GWT)
SINGLE PHASE AC or DC CONNECTIONS
Figure 1. Transient Voltage Suppression
MOVMOV
MOV MOV
MOV
MOV
MOV
L1
L2
L3
(LOAD)(LINE 1)
VMOV >VLINE TO LINE
LINE TO LINEMOV >V V
LINE TO LINEVVMOV > 31
L1
L2
L3
NEUTRAL
(LOAD)(LINE 1)
(LOAD)(LINE)
HIGHLINE
LINELOW
DELTA CONNECTEDTHREE PHASE LOAD
WYE CONNECTEDTHREE PHASE LOAD
SINGLE PHASE TWO WIRE LOAD
6
Magtrol Model 5300 Three Phase Power AnalyzerChapter 3 - Connecting the 5300
SINGLE PHASE AC OR DCCONNECTIONS
See figure 2.
NOTE: Connections are shown groupedin cables.
This diagram shows the phase 1 (Ø1) voltage and currentinputs connected for measurement. However, any ofthe 3-phase inputs can be used. The unused two inputsare jumpered to insure zero inputs.
Power in watts is calculated as follows:
P = E × I × cos q
( where q is the phase angle between E and I)
On the 5300, select DISPLAY - Ø1 and
MODE -PH. V.
The 5300 displays VOLTS, AMPS and WATTS.
This circuit uses the 5300 PA remote voltage sensefeature by measuring the voltage at the load. Thisincreases measurement accuracy by eliminating linevoltage drop from the power measurement. For safety,an overload circuit breaker (CB) removes all loadvoltage during an over-current condition. The voltagesense lines are connected at the line side of CB to helpprevent inductive transients from entering the PA asthe CB opens. Make sure that connections from CB tothe load are heavy conductors and short as possible.
If a circuit breaker is used in the input lineto the 5300 PA, a circuit should be usedthat prevents the breaker from opening untilafter the load side breaker has opened.Otherwise, potentially damaging inductivetransients can be applied to the 5300 PA.Damage caused by these transients areoutside the scope of the MAGTROLWARRANTY.
For voltage sense lines less than 25 feet inlength, a twisted pair of #20 gauge (orlarger) wire can be used. For lines longerthan 25 feet or lines grouped with other ACconductors, shielded cable should be used.Connect the shield at the 5300 PA GNDterminal. If the wires connecting the load tothe 5300 PA OUTPUT are short and theresulting voltage drop is insignificant, thevoltage sense connections can be made atthe rear panel of the 5300 PA.
Connect the chassis ground terminal toa good earth ground. Use at least #12gauge insulated copper wire.
Figure 2. Single Phase AC or DC Connections
INPUT AMPS OUTPUT VOLTS
Ø1
Ø2
Ø3
HIGHLOWLOW
(WHITE)
CB
LOAD
EARTH(BLACK)
HIGH
VOLTAGE SENSE
LOAD
VLINE = VLOAD1
1 SURGE PROTECTION NOT SHOWN
5300 PA
2 INDICATES CABLING WITH 2 CONDUCTORS.
CABLE MUST BE FULL LOAD
2
2
ILINE = ILOAD
R
R W B
BW
W BR
Ø1
Ø2
Ø3
R
R
R
7
Magtrol Model 5300 Three Phase Power Analyzer Chapter 3 - Connecting the 5300
3-PHASE 3-WIRE DELTA CONNECTIONS
The power dissipated in each phase (PØ) is equal to the product of phase voltage ( Ephase), phase current (Iphase) andcosine of the phase angle θ between the phase voltage and phase current:
PØ = Ephase × Iphase × cos θ
Each phase power is displayed on the 5300 PA by selecting DISPLAY - Ø1,Ø2 or Ø3 push switch. Total powerconsumed by the load is the algebraic sum of the 3-phases power measurements:
PTOTAL = PØ1 + PØ2 + PØ3
The total power is displayed on the 5300 PA by selecting the DISPLAY - ΣKW push switch.
PTOTAL = ΣKW
Also, the general discussion for Figure 1 (surge protection) and Figure 2 (single phase AC & DC connection) apply.
Figure 3. 3-Phase 3-Wire Delta Connections
INPUT AMPS OUTPUT VOLTS
Ø1
Ø2
Ø3
HIGHLOW
EARTH
1 SURGE PROTECTION NOT SHOWN
5300 PA
2 INDICATES CABLING WITH 2 CONDUCTORS.
CABLE MUST BE FULL LOAD
R
R W B
BW
W BR
Ø1
Ø2
Ø3
R
R
R
L1
L2
L3
LINE
1
FOR BALANCED SYSTEM
3I LINE PHASE= I
LOAD
LOA
D
LOA
D
CB
VOLTAGE SENSE
LOAD
2
2
LINE TO LINEV VPHASE=
3-PHASE, 3-WIRE WYE CONNECTIONS
Power conversion formulas for the 3-phase WYE connection are the same as for the DELTA connection as describedabove. Each phase power is displayed on the 5300 PA by selecting the DISPLAY - Ø1,Ø2 or Ø3 push switch. Thetotal power is displayed on the 5300 PA by selecting DISPLAY - ΣKW push switch. Also, the general discussion forFigure 1 (surge protection) and Figure 2 (single phase & DC connection) apply.
Figure 4. 3-phase, 3-Wire WYE Connections
INPUT AMPS OUTPUT VOLTS
Ø1
Ø2
Ø3
HIGHLOW
EARTH
1 SURGE PROTECTION NOT SHOWN
5300 PA
R
R W B
BW
W BR
Ø1
Ø2
Ø3
R
R
R
L1
L2
L3
LINE
1
FOR BALANCED SYSTEM
LINEI PHASE= ILOAD
CB
VOLTAGE SENSE
LOAD
3LINE TO LINEV VPHASE=
LOAD
LOAD
8
Magtrol Model 5300 Three Phase Power AnalyzerChapter 3 - Connecting the 5300
3-PHASE, 4-WIRE WYE CONNECTIONS
Figure 5. 3-Phase, 4-Wire WYE Connections
INPUT AMPS OUTPUT VOLTS
Ø1
Ø2
Ø3
HIGHLOW
EARTH
1 SURGE PROTECTION NOT SHOWN
5300 PA
R
R W B
BW
W BR
Ø1
Ø2
Ø3
R
R
R
L1
L2
L3
NEUTRAL
LINE
1
FOR BALANCED SYSTEM
LINEI PHASE= ILOAD
CB
VOLTAGE SENSE
LOAD
3LINE TO LINEV VPHASE=
LOAD
LOAD
Power conversion formulas for the 3-phase 4-wire WYE connection are the same as for the DELTA connection,above. Each phase power is displayed on the 5300 PA by selecting the DISPLAY - Ø1,Ø2 or Ø3 push switch. Thetotal power is displayed on the 5300 PA by selecting DISPLAY - ΣKW push switch. Also, the general discussion forFigure 1 (surge protection) and Figure 2 (single phase & DC connection) apply.
3-PHASE, CURRENT AND POTENTIAL TRANSFORMER CONNECTIONS
Figure 6. 3-Phase, Current and Potential Transformer Connections
INPUT AMPS OUTPUT VOLTS
R
R
W B
BW
BW
R
R
R
1O
2O
3O3O
O2
O1
HIGHLOW
EARTH
5300PA
PT
CT
CT
CT
PT
PT
PHASE1
LINE
PHASE2
PHASE
PHASE1
PHASE2
PHASE
LOAD
MAINTAIN POLARITY
THREE PHASE CURRENT
AND POTENTIAL TRANSFORMER
CONNECTIONSR
Voltage and current measurement ranges can be extended by using current and potential transformers. Frequencyresponse of the measurements will be determined by the characteristics of the transformers used. The currenttransformer (CT) and the potential transformer (PT) are shown located near the 5300 PA. The line voltage drop canbe eliminated from the power calculations by connecting the PT at the load.
Also, the general discussion from Figure 1 (surge protection) and Figure 2 (single phase & DC connection) apply.See Section 5, CT/PT Installation for more information.
9
4 - Operation4 - Operation4 - Operation4 - Operation4 - Operation
Read Section 1 and make sure unit is connected properly(see Section 3) before proceeding.
GENERAL1. Using Sections 1 and 3 as a guide, connect the 5300.
Before connecting the power mains, double checkall connections (an Ohmmeter is helpful). Verify that the overcurrent circuit breaker is openand connect the power mains.
2. Observing the 5300 front panel indicators, turn the5300 power switch ON and confirm properoperation - see "Initial Checkout" in Section 1 -Introduction.
3. Energize the power mains and apply power to theload by closing circuit breaker CB. If improperoperation occurs, immediately disconnect powermains. Locate and correct the problem.
The 5300 has:
• Four MODES - HOLD; AVG (averaging), PF(Power factor) and PH. V. (phase voltage)
• Three AMPS ranges plus AUTO (auto ranging)
• Four DISPLAY selections -Ø1, Ø2, Ø3, (phases1 through 3) and ΣKW (sum of kilowatts)
• Three VOLTS ranges plus AUTO.
All have adjacent red LEDs indicating the active modeor measurement range.
AMPERES DISPLAY
The AMPS display is a four digit, unsigned floatingpoint display of true AC rms or DC current flowinginto the AMPS INPUT connector (red) on the rear panel.For detailed information see Section 2, Specifications.
The 5300 defaults to AUTO (auto ranging) at DISPLAYpower turn on. AUTO up-ranging occurs if the rmscurrent exceeds the top of the range value plus about 5%. AUTO down ranging occurs when the current is justless than the full range value of the next lower range.
Selection of any amps range push-button activates theselected range by overriding the AUTO- range selection- the AUTO LED goes off and selected AMPS LEDilluminates. However, the AUTO up-range function is
always silently monitoring the current and is ready toup-range the instrument if the current increases above105% of the range full scale. If the current falls belowthe value of the selected range, that range will thenreactivate. The instrument will automatically up-rangefrom the measured current but will down-range only tothe selected range. The display will show "HELP" whenthe maximum rating is exceeded.
VOLTAGE DISPLAY
The VOLTS display is a four digit, unsigned floatingpoint display of AC rms or DC voltage differencebetween the rear panel HIGH (black) and LOW (white)terminals. The voltage input is differential (neitherterminal tied to common) allowing connection at aremotely located load. This remote connection removesthe voltage drop in the load connection wires from thepower measurement. The VOLTS - LOW terminal(WHITE) must be connected to the AMPS -OUTPUTline at the load - see Figure 1.
The AUTO and manual VOLTS range selection isidentical in operation to the AMPS, as described above.
WATTS OR POWER FACTOR
The WATTS display is five digit, unsigned floatingpoint display of power in WATTS or POWER FACTOR(PF) as a decimal number. WATTS is the power ONdefault MODE. Press the MODE - PF button to measurePOWER FACTOR.
Watts measurements are from about 100 milliwatts (autozero off) through 60 kilowatts, and Power Factors from0.0001 through 0.9999. WATTS = V * I * cos * =TRUE POWER The WATTS range is set by the AMPSand VOLTS active ranges.
Power Factor is:
PFV I
V I =
× × ×
cos θ =
POWER
POWER
TRUE
APPARENT
10
Magtrol Model 5300 Three Phase Power AnalyzerChapter 4 - Operation
MODE SELECTIONS
Figure 7. Mode Selections
HOLD AVG PF PH.V.
MODE HOLD
The HOLD push-button may be depressed at any time.When depressed, the displayed values are held and dataaccumulation stops. If the AVG (averaging) function isactive when the HOLD button is depressed, the lastrunning average value of AMPS, VOLTS and WATTSwill be held. The HOLD and AVG functions can becombined to provide added functions.
MODE AVG
The AVG MODE is an integration or averaging functionfor the display of VOLTS , AMPS and WATTS. The VOLTS,AMPS and WATTS data are sampled at 10 readings persecond and a running average is computed by dividing thesummed values of each parameter by the total number ofsummations. When averaging is turned off, the VOLTS,AMPS and WATTS data, their summations, and the samplecount are stored in non-volatile RAM memory. Theaveraging function is useful in stabilizing the display whendigits are changing because of slowly varying values.Integration periods from seconds to minutes may be neededto stabilize the displayed values.
The HOLD and AVG functions can work together.When entering AVG with HOLD off, the averagingregisters are cleared and integration starts from a zerovalue. With the HOLD function active first, pressingAVG starts the integration point from the last RAMstored values of AMPS, VOLTS or WATTS. TheHOLD automatically resets off.
When AVG is turned off, non-averaged values aredisplayed and the averaged values are then stored innon-volatile RAM memory. Upon re-entering the AVG
mode, the stored values will be returned as the newaveraging starting points. This function allows you toexit the AVG mode, perform some other task, thenreturn and continue averaging where you left off. Also,it can be used simply to retain and recall data.
While in AVG mode and the PA power is turned off,the last averaged values stored will be held in non-volatile RAM and returned to the display when the PApower is turned on and the AVG mode is reactivated.
The HOLD - AVG function permits truly integratedpower measurements where power is appliedintermittently, or where a combination of devices requireintegrated measurements, with interruptions betweenmeasurements.
NOTE: WATT-HOURS can bedetermined by using the AVGfunction and a timing clock.
Watt-hours = (watts avg × timein hours).
NOTE: Power Factor (PF) can not beaveraged.
MODE POWER FACTOR (PF)
Pressing the PF (power factor) push switch displays thepower factor on the WATTS display. Power factor iscomputed by:
PFP P P
V I V I V I =
+ + + +
φ φ φ
φ φ φ φ φ φ
1 2 3
1 1 2 2 3 3
AVG mode is not active while in PF mode
MODE PH. V.
Pressing the PH. V push switch modifies the phaseVOLTS measurement to indicate line to line voltage onthe display by applying:
E E LINE PHASE = × 3 This relation is valid for a balanced system. For anunbalanced system, there can be a difference betweenthe displayed voltage and the true line to line value.
11
Magtrol Model 5300 Three Phase Power Analyzer Chapter 4 - Operation
DISPLAY SELECTIONS
Figure 8. Display Selections
Ø1 Ø2 Ø3 KWΣ
DISPLAY Ø1, Ø2, Ø3
Individually selects Phase 1, Phase 2 or Phase 3WATTS for display.
If all three push-buttons are simultaneously pressed, thefour LEDs illuminate, indicating that the AMPS displayreads the SUM of the three phase currents, the VOLTSreads the AVERAGE of the three phase voltages andthe WATTS reads SUM of the three phase powers, asfollows:
AMPERES I I I= + +φ φ φ1 2 3 (SUM)
VOLTSV V V= + +φ φ φ1 2 3
3(AVERAGE)
KILOWATTSW W W= + +φ φ φ1 2 3
1000(SUM)
DISPLAY ΣΣΣΣΣKW
The WATTS display indicated the total 3-phase powerin kilowatts.
KWW W W
= + + φ φ φ 1 2 3
1000 (SUM)
VOLTAGE RANGES
Figure 9. Voltage Range Selections
150 300 600 AUTO
150, 300 and 600 volts rms plus AUTO range. At powerturn on, the 150 volt range and AUTO (auto-ranging)are active, by default. Up ranging occurs when themeasured voltage on any phase exceeds that rangemaximum voltage by 5% (>105%). This feature is activein either AUTO (LED on) or manual (LED off).Automatic down ranging occurs only in AUTO whenthe measured voltage falls to about 1/4% below thatrange maximum value.
If MODE PH. V. is off, up ranging occurs at 105% ofthe range times 3 .
The PA up-ranging feature protects the instrument fromoverload and ensures accurate measurements.Exceeding the PA maximum voltage of 600 volts causesthe instrument to display "HELP." This means thatyou must reduce your input voltage.
12
Magtrol Model 5300 Three Phase Power AnalyzerChapter 4 - Operation
AMPERES RANGE
Figure 10. Current Range Selections
5 25 100 AUTO
5, 25 and 100 Amperes rms plus AUTO range: At powerturn on, the 5 Amps range and AUTO (auto ranging)are active, by default. Up ranging occurs when themeasured current on any phase exceeds that rangemaximum current by 5% (>105%). This feature is activein either AUTO (LED on) or manual (LED off).Automatic down ranging occurs only in AUTO whenthe measured current falls to about ¼% below thatrange's maximum value.
The PA up-ranging feature protects the instrument fromoverload and ensures accurate measurements.Exceeding the PA maximum current of 100 Amps onany phase causes the instrument to display "HELP."This means that you must reduce your input currentuntil the normal display reappears.
ANALOG OUTPUT OPTION
This option provides analog output signals for AMPS,VOLTS and WATTS.
These three analog outputs with their common areisolated from the measured circuits at 750 Voltscontinuous breakdown.
The outputs are provided through a standard 5 pin DINstyle connector located on the rear panel of the 5300 -see figure 11 for connections. The analog output voltageis 5.00 volts at each AMPS, VOLTS or WATTS rangemaximum value.
See Section 2 - Specifications.
NOTE: Analog output of POWERFACTOR is not provided
Figure 11. Analog Output Connections
N/C 5 1 COM
WATTS 4 2 AMPS3
VOLTS
13
5 - CT/PT Installation5 - CT/PT Installation5 - CT/PT Installation5 - CT/PT Installation5 - CT/PT Installation
External current and potential transformers can be usedto extend the measuring ranges of the PA. See Section4, Figure 6 for a connection diagram.
CALIBRATION
The 5300 has special provisions allowing entry oftransformer ratios into the non-volatile RAM via theGPIB (IEEE-488) rear panel input. The PA displaythen includes the transformer ratios and reads actualcurrent, voltage and power directly.
CT/PT DETECTION
At power turn on initialization, the MPU interrogatesthat portion of memory where the CT and PTcompensation values reside. If a value is found, the MPUlooks to see if the rear panel CT/PT slide switch (seeFigure 12) is set to the "IN" position (to include thetransformer ratios). If it is, normal calibration factorsare revised by applying the transformer factors. Thedisplays indicate actual load values.
Figure 12. Current & Potential Transformer Selections
IN
OUT
GND EXTCT/PT
Since the above interrogation and scale factor setupoccurs only at power turn on, the scale factors are activeuntil power is turned off, the CP/PT switch turned to"OUT" and power turned "ON." The CP/PT factorsare now removed and the standard factory calibrationfactors become active.
CT/PT RATIO RANGE
The 5300 PA compensates all display values fortransformer ratios from 0.01 to 255.
DIGITAL RANGE
The digital display holds four digits for AMPS andVOLTS, and five digits for WATTS or KW. When avalue exceeds these limits, the decimal point is turnedoff. This is a warning that the compensated value isabove the display capability and is in error. If this shouldoccur during GPIB use, an exclamation mark issubstituted immediately to the right of the leastsignificant digit (i.e. !=ASCII033) to signal that thereis an unknown magnitude.
GPIB-CT/PT PROGRAMMING
The 5300 PA accepts either upper or lower casecharacters, and whole numbers in any numerical format.
For CT installation: CTnnncl
For PT installation: PTnnncl
Where: nnn=0.01 to 255.
("cl" denotes a carriage return/line feed terminationcharacter.)
For example:A CT with 250:1 ratio is: CT250.cl
A PT with 10:1 ratio is: PT10.0ct
The PA will ignore any value outside of the range of0.01 to 255. If an out of range entry is attempted, thedisplay will warn by showing "HELP." Correct and re-enter your factor.
14
Magtrol Model 5300 Three Phase Power AnalyzerChapter 5 - CT/PT Installation
CHANGING OR REMOVING CT/PTVALUES
To modify a value, simply overwrite the existingvalue(s).
To remove a CT or PT value, output a CT(cl) or PT(cl),only.
To remove both, and save the data, switch the rear panelslide switch to "OUT," and toggle the power OFF thenON.
If you remove both the CT and PT value correctionfactors by GPIB instructions, the PA will automaticallyreset, eliminating the need to cycle power OFF/ON.
NOTE: When removing transformerconversion factors and measuringwithout CT(s) or PT(s), set therear panel CT/PT switch to the"OUT" position.
15
6 - GPIB Communication6 - GPIB Communication6 - GPIB Communication6 - GPIB Communication6 - GPIB Communication
GPIB (IEEE-488)
The IEEE-488 or GPIB (General Purpose Interface Bus)provides direct connection and control of the 5300 fromany appropriately equipped computer for the purposeof data acquisition and display. MAGTROL factoryassistance is available if required.
HARDWARE INSTALLATION
A GPIB interface requires installation of an interfacecard in the host computer and driver software residenton the PC's hard disk. MAGTROL can supply theNational Instruments Corp. GPIB-PC2A® interface forIBM® or compatible PCs.
SOFTWARE INSTALLATION
Formatting and initialization assistance is available fromMAGTROL Customer Service.
All GPIB data acquisition systems require the use oftermination characters to signal the conclusion of a dataexchange. The 5300 uses the Hewlett Packard - HPIB™standard ASCII termination characters "Carriage Return(CR) and Line Feed (LF)," in that order. On a read cycle,the 5300 looks for the CR-LF to signal completion ofan instruction and transmits these characters uponconclusion of a data write cycle.
PRIMARY ADDRESS
All instruments serviced on the bus have a separateprimary address code. The factory setting for the 5300is fourteen (14). This code can be changed by changingthe settings of the DIP switch that are located on therear panel next to the GPIB connector. Change thisaddress only if there is a bus addressing conflict withother instrumentation. Refer to the table in Figure 13to set the DIP switch pattern - set to address 14.
Some PC interfaces (National GPIB-PC2A) will access0 to 15 (4 bit) primary address numbers only. Otherinterfaces may access up to 31 (5 bit code). The 5300PA code range uses the 5 bit code format. Beforeselecting a value greater than 15, check that yourparticular interface has the 5 bit code capability.
Figure 13. GPIB Address Selection
(Address 14 shown)
SWITCH SEGMENT
1 2 3 4 5LSB MSB
ADDRESS
01010101010101010101010101010101
00110011001100110011001100110011
00001111000011110000111100001111
00000000111111110000000011111111
00000000000000001111111111111111
012345678910111213141516171819202122232425262728293031
1 2 4 8 16
1
0
1 2 3 4 5 6 7 8
Not Used
16
7 - 5300 P7 - 5300 P7 - 5300 P7 - 5300 P7 - 5300 PA Instruction SetA Instruction SetA Instruction SetA Instruction SetA Instruction Set
PC TO 5300 PA
A5, A25, A100 AMPERES RANGE selection.
V150, V300, V600 VOLTAGE RANGE selection.
AA AMPS AUTO range ON.
VA VOLTS AUTO range ON.
FULLSets data FORMAT to AMPS,VOLTS, WATTS for 3 phases.See 5300 PA TO PC.
SGLSets data output format = tofront panel display. See 5300PA to PC.
SYNCGPIB data output rate issynchronized to 0.10 sec. busoutput rate. See DATA RATE.
OPENData OUTPUT is transmittedupon request. See OPENINSTRUCTION.
SP1, SP2, SP3 Selects PHASE 1, 2, or 3.
SPASelects ALL PHASES (sameas pressing Ø1, Ø2 and Ø3simultaneously).
LV Select to read LINE VOLTAGE.
PV Select to read each PHASEVOLTAGE.
KW select to read KILOWATTS
W Select to read PHASE WATTS.
P Select to read POWERFACTOR.
I, IC Averaging ON, Averaging OFF.
H, HC HOLD ON, HOLD OFF.
L, LCLOCKOUT, and LOCKOUTCLEAR of all front panel pushswitches.
AZ Cancel of AUTO ZEROfunction.
CT, PTCANCEL, or ENTER data forcurrent or potential transformercalibration.
RES Soft RESET of PA (same aspower on).
In addition to the standard instructions listed in the tableon the left, there are special instructions for reading andwriting directly to the PA memory elements.
A specific program running in the host computer isnecessary. If you have a special situation where youwant direct memory access to alter 5300 PA functionsor change calibration, please contact Magtrol forsoftware assistance.
5300 PA TO PC
There are two choices for VOLTS, AMPS and WATTSdata format. Before you execute a read statement, it isnecessary to instruct the PA as to which data formatyou wish to receive. This selection is retained by thePA and becomes the default mode used for subsequentdata transmissions.
"SGL" INSTRUCTION
Sets the data format to a string length of 24 ASCIIcharacters, including carriage return and line feedcombination (••).
A=nn.nnV=nnn.nW=nnnn.n••n (as shown) is any integer number 0 through 9
V (as shown) is volts
W (as shown) is watts
P is power factor
K is kilowatts
•• is carriage return and line feed combination
NOTE: Use leading zeros to maintain afixed string length.
"FULL" INSTRUCTION
Data for all 3-phases is supplied. The string is 68contiguous ASCII characters:
A=xx.xxV=xxx.xW=xxxx.xA=yy.yyV=yyy.yW=yyyy.yA=zz.zzV=zzz.zW=zzzz.z••
x is an integer number 0 through 9 for phase 1.
y is an integer number 0 through 9 for phase 2.z is an integer number 0 through 9 for phase 3.
17
Magtrol Model 5300 Three Phase Power Analyzer Chapter 7 - Instruction Set
This string transmits volts, watts and amps. To get linevoltage, power factor (PF) or kilowatts (KW), the hostcomputer must make the following calculations:
PFW W W
E I E I E I =
+ + + +
∅ ∅ ∅
∅ ∅ ∅ ∅ ∅ ∅
1 2 3
1 1 2 2 3 3
E E LINE n PHASE n ( ) ( ) = 3 (Where “n” is the phase number)
KWW W W
= + + φ φ φ 1 2 3
1000
DATA RATE
The OPEN and SYNC commands affect bus timing.Selection is dependent upon what other instruments areon the bus, their acquisition rate, and how you wish toprocess the data.
“OPEN” INSTRUCTION
If your data acquisition is random, or you don't want towait for the full 0.1 second data sampling rate, you canuse the OPEN instruction. Data output is nearlyimmediate, depending upon the MPU status at the timeof request. If multiple data
requests are made within the MPU's 0.1 second samplerate, you will receive multiple transmissions of the samedata. If your program is accumulating data in an array,you will want to include a routine to ignore the secondof any two identical received data words.
INSTRUCTION
The host PC will be held by the 5300 PA until thesampling period is over. In this mode, data will alwaysbe the result of the most recent sampling period.However, if you are using a Magtrol controller like theModel 4629B or 5240, the two instruments should besynchronized to avoid a timing conflict. Thissynchronization is done as follows:
Output any instruction (except "RES") to eachof the instruments without including thecombination carriage return/line feed (oo)terminating instruction. Now, both instrumentsare "hung up" at fixed program locationswaiting for the carriage return/line feedinstruction. Synchronization is accomplished byrestarting both programs by outputting only thecarriage return/line feed instruction (oo) insuccessive statements to both instruments.
At restarting, the instrument will be synchronized, butwill slowly drift apart and require re-synchronization.If you are acquiring data in batches, execute the abovesynchronization routine just prior to each data inputroutine.
PROGRAMMING EXAMPLE
The following program sets the 5300 PA in the "SYNC"mode with "FULL" data format. The CRT monitordisplays:
Amperes - summed for total 3-phase line.
Voltage - average 3-phase line.
Power - 3-phase kilowatts.
This example (on the following page) assumes that theNational GPI-PC interface hardware and MicrosoftQuick Basic are used.
18
Magtrol Model 5300 Three Phase Power AnalyzerChapter 7- Instruction Set
'Read 5300 PA full data - Magtrol Inc., 91 rt'Primary address set to 14
Bdname$ = "DEV14"CALL IBFIND(Bdname$, bd%) 'initialize GPIBcl$ = CHR$(13) + CHR$(10) 'assign carriage return and line feed.CLS
'Set PA for "FULL" datawrt$ = "FULL" + cl$CALL ibwrt(bd%, wrt$)
'Set PA for "SYNC" transfer timing.wrt$ = "SYNC" + cl$CALL ibdwrt(bd%, wrt$)
'Assign input word length.rd$ = SPACE$(68)
LOCATE 20,50: PRINT "Any key ends..."
DO: s$ = UCASE$(INKEY$) 'Loop starts here.CALL IBRD(bd%, rd$)
'Amps - convert from string to numeric and sum.ap1$ = MID$(rd$, 3, 5) 'Extract Phase 1 amps.ap2$ = MID$(rd$, 25, 5) 'phase 2.ap3$ = MID$(rd$, 47, 5) 'phase 3.amps = VAL(ap1$) + VAL(ap2$) + VAL(ap3$)
'Volts, conv' numeric, average, and conv' from phase to line voltage.vp1$ = MID$(rd$, 10, 5) 'extract phase 1 volts.vp2$ = MID$(rd$, 32, 5) 'phase 2.vp2$ = MID$(rd$, 54, 5) 'phase 3.volts = (VAL(vp1$) + VAL(vp2$) + VAL(vp3$) * .57735 ' = |3/3
'Power, convert to numeric, sum and convert to KW.wp1$ = MID$(rd$, 17, 6) 'extract phase 1 watts.wp2$ = MID$(rd$, 39, 6) 'phase 2 watts.wp3$ = MID$(rd$, 61, 6) 'phase 3 watts.Kw = (VAL(wp1$) + VAL(wp2$) + VAL(wp3$)) / 1000
LOCATE 12, 10: PRINT "Line Volts = ";PRINT USING "###.#"; voltsLOCATE 13, 10: PRINT "Amperes = ";PRINT USING "###.#"; ampsLOCATE 14,10: PRINT "3-phase KW = "; Kw
LOOP WHILE s$ = ""
END
19
8 - Operating P8 - Operating P8 - Operating P8 - Operating P8 - Operating Principlesrinciplesrinciplesrinciplesrinciples
The Magtrol 5300 PA uses the three wattmeter methodto measure true RMS power. Voltage and current aresensed and amplified in an isolated analog front end,analog to digital converted with 16 bit precision,processed through an 8 bit microprocessor (MPU) andoutput in BCD form for display on the front panelmeters. The PA provides a digital display for eachselected phase of rms volts, amps, and watts; averagerms volts, amps and watts; and total load power factor(PF).
AMPERES TRANSDUCING
Current measuring is accomplished using a three sectioncalibrated manganin resistance shunt per phase. The 5,25 and 100 amp sections are 0.016 Ohm (80 mV), 0.003Ohm (75 mV) and 0.001 Ohm (100 mV), respectively.See Figure 14.
The current flow through each shunt is determined bymeasuring the voltage drop across the shunt and theMPU, applying Ohm's Law. Current ranges are set bythe MPU and energize the appropriate shunt bypassrelays CR1 and CR2. The 5 amp range energizes (opensN/C contacts) of both CR1 and CR2; the 25 Amp. rangeenergizes CR1, and both relays remain de-energized forthe 100 Amp range. The CRs are very low resistance,high current mercury wetted relay contacts that bypassunused sections of the metering shunts.
VOLTAGE SENSING
Each VOLTS input terminal connects a 1.5 Megohmresistive voltage divider to provide scaled phase voltagefor measurements. The three 1.5 Megohm resistors forma classic "Y Box" neutral. The resulting phase voltagesignals are amplified and scaled for processing. SeeFigure 14.
NOTE: Connecting the Voltage Senseleads incorrectly (e.g. connectingthe voltage sense from phase 1 tophase 2 current lines) will causethe Watts display to show anincorrect value. If you areexperiencing poor readings, shutdown the system and carefullyreview your connections.
ANALOG PROCESSING
Input signals proportional to AMPS and VOLTS areamplified and calibrated for each range by amplifiers78B146-U7, U8, U9 and U10. These scaled signals passthrough true rms to DC converters 78B147-U1 & U4,voltage to frequency converters 78B147-U2 & U5 andoptical isolators 78B147-U3 & U6. The resultingfrequency signals represent true rms current and voltage(AF0 and VF0,) scaled to 0.0707 volts per 1.0 kilohertz.
5A25A100A
CR2CR1
CR2CR1
CR2CR1
01
02
03
INPUT
OUTPUT
01
02
03
OUTPUT
(LOAD)
(LOAD)
(LOAD)
VOLTS
VOLTS
VOLTS
01
02
03
(LOW)
(LOW)
(LOW)
VOLTS(HIGH)
E PH1
E PH2
E PH3
VOLTS(HIGH)
VOLTS(HIGH)
S
S
S
Figure 14. 5300 Current Shunt Inputs
20
Magtrol Model 5300 Three Phase Power AnalyzerChapter 8 - Operating Principles
Vrms= dtT 0
t1 V 2
Vo= 10XYCosQ
Vrms= dtt
1T 0
V 2
Vrms=t
dtT1
0V 2
V/F CONV.
KhzVOLT
.0707
U8
V/F CONV.
VOLT.0707 Khz
.0707
V/F CONV.
KhzVOLT ISO
OPTOVFo
ISOOPTO
WFo
ISOOPTO
AFo
I AMP5
I AMP25
I AMP100
AMPV
5A
25A
100A
V
OUTPUTSTO
MPU
ISOLATED CIRCUIT
AMPSINPUT(FROM
SHUNTS)
VOLTS INPUT(FROM
VOLTAGE DIVIDER)
78B146-U7
78B146-U8
78B146-U9
78B146-U10
78B147-U1 78B147-U2
78B147-U7 78B147-U9 78B147-U10
78B147-U4 78B147-U5
78B147-U3
78B147-U11
78B147-U6
RANGE
Y
X
(t)
(t)
(t)
Figure 15. 5300 Block Diagram
Also, the AMPS and VOLTS signals are input to aprecision four quadrant X-Y multiplier 78B147-U7,averaged by an active two pole Butterworth filter78B147-U8, converted to frequency in voltage tofrequency converter 78B147-U10 and isolated by opticalcoupler 78B147-U11. The resulting frequency signal,WF0 represents true power (V × I × Cos θ ), at a scalefactor of. 0.0707 volts per 1.0 kilohertz. There is 2500volts isolation between the measured circuit and the AF0,VF0 and WF0 frequency signals.
DIGITAL PROCESSING
Frequency proportional signals of AMPS, VOLTS andWATTS (AF0, VF0, and WF0) are integrated for a preciseperiod of 0.1 seconds for digital conversion andprocessing via an eight bit microcomputer (MPU). TheMPU controls functions of range control, auto-zero, finecalibration, BCD conversion and GPIB communications.
The MPU acquisition and conversion rate is 100 milliseconds(10 readings per second) and the display updates at 500milliseconds (2 updates per second). The MPU scans allfront panel push-button control inputs 25 times per second.When a push-button is pressed, the appropriate programloop is entered and the function is executed on the nextprogram cycle. No damage will result to the 5300 PA fromany combination of push-button selections.
In the AVG MODE (averaging), the 5300 PA integratesthe 10 data readings per second (AMPS, VOLTS andWATTS) and then samples the averaged value for
display. As the sampled readings accumulate, thechanging display digits will steady down to provide astable measurement of true power (computed fromaverage VOLTS and AMPS). This technique works wellwhen the displayed digits are changing too fast to berecognized as the power consumption changes.
DISPLAY “HELP”
If the AMPS or VOLTS displays show the word HELP,the maximum peak range of the 5300 PA has beenexceeded. This can occur from a high rms input or thepeak of a high crest factor wave form. "HELP" can bea transient condition resulting from high momentarystarting current and is of no danger if the "HELP"message disappears after a few seconds. The Auto up-ranging feature of the 5300 will automatically up rangethe instrument as the current or voltage increases overeach ranges maximum, up to the 100 amps range. The5300 can sustain an overload of up to 200 amps for 5seconds, maximum. Circuit breaker(s) should beinstalled for personal safety and protection of the 5300PA. See "Current Overload." in Section 1 - Introduction.
POLYPHASE LINE BALANCE
Good polyphase line operating efficiency dictates thatline voltages and currents be closely balanced. Usually,this requires putting some effort into balancing the loads.Also, power factor (PF) measurements will be inaccurateunless a good line balance is maintained.
21
9 - Calibration9 - Calibration9 - Calibration9 - Calibration9 - Calibration
GENERAL
Complete calibration of the 5300 PA is beyond thecapabilities of most users. Magtrol, Inc. recommendsthat the 5300 PA be returned to the factory for calibrationcertifying the instrument to full specifications.
However, this section includes Calibration AccuracyVerification procedures and steps to make minor trim-ups of calibration.
NOTE: To perform these steps, thefactory calibration seal will bebroken. This voids the factoryCalibration Certification thatcomes with the 5300 PA.
TEST SETUP
The recommended test setup for each phase is shown inFigure 16.
NOTE: The same test setup is repeatedfor each of the 3-phases.
The accuracy of the voltage and current standards usedfor calibration should be at least four times the accuracyof the 5300 PA specifications. The equipment shownin this test setup meets this requirement.
To accurately measure AC power it is important thatthe current source have a phase shifting control. Withsuch a phase adjustment, phase shift caused by incidentalcircuit inductances can be compensated for by adjustingthe phase of the current wave form to be exactly in phase(zero phase shift) with the voltage wave form. Sourcesof incidental circuit inductance include the current shuntswithin the 5300, output impedance of the calibrators,impedance of the load and wiring inductance.
OPTIONAL-FOR AMPS >2TRANSCONDUCTANCE AMP.
FLUKE 5725A;5205AGUIDELINE 7620A, OR
EQUIVALENT
GND
INPUT
AMPS
5300
OUTPUT
LOW
VOLTS
HIGH
EARTH
VOLTAGE CALIBRATOR
FLUKE 5700A ORFLUKE 5100A OR
EQUIVALENT
VOLTAGE CALIBRATOR
FLUKE 5700A OREQUIVALENT
VOLTS VOLTS, HIGH LOW
VARIABLEPHASEOUTPUT
PHASELOCK
IN
LOW CURRENTHIGH
UUT
(REF)
(EACH PHASE)
Figure 16. Calibration Verification Test Setup
(For Each Phase)
22
Magtrol Model 5300 Three Phase Power AnalyzerChapter 9 - Calibration
Since the current calibrator output is usually a lowimpedance with low compliance voltage, the 5300'scurrent measuring shunts are the circuit's majorresistance. Let's take a representative example andcompute the resulting phase shift:
Let L = 10 µhenries (total of shunt, wiring, etc.)
Let RSHUNT = 0.011 Ohm; RWIRING = 0.01 Ohm
R = 0.011 + 0.01 = 0.021 Ohms
Let F = 60 Hz ∴ 2 π FL ≈ 0.004
θ Arctan (2 π FL /R) = Arctan (0.004 /0.021)
θ ≈ 11 degrees, or about 1.8 % measurement error. Thiserror can be eliminated by adjusting the calibrator'svariable phase shift control. This demonstrates the needfor care in making power analyzer calibrationmeasurements.
CALIBRATION VERIFICATION
Refer to Figure 16 for the recommended test setup. Ifother test equipment is used, appropriately modify thetest steps for your equipment. Each of the 3-phases(φ1, φ2, φ3) are identical and are individually tested.The same procedure is used for each of the 3-phases.
Potentially lethal voltages are used inthe following test steps. Takeappropriate precautions to avoidelectrical shock. Refer to your calibratoroperator manual for operatinginstructions. Because these calibratorsgenerate lethal voltages, extreme care isnecessary.
The three steps of the calibration verification are asfollows:
1. Volts Calibration Check
2. Amperes Calibration Check
3. Watts Calibration
Set both the VOLTS and AMPERES calibrators tostandby mode.
VOLTS CALIBRATION CHECK φφφφφ1
DC:
1. On the 5300 PA, press the 150 volts range push-button.
2. Set the volts calibrator for zero volts DC and operatemode.
3. The 5300 VOLTS display should read zero +0.0001% max of volts full scale range.
4. Set volts calibrator for + 150 volts DC.
5. The 5300 VOLTS display should read 150.0 volts.Record the VOLTS readings.
6. Set the calibrator for - 150 volts DC and repeat theabove step. Record the VOLTS readings.
7. Repeat the above for the 300 and 600 volts ranges.
Lethal voltages are present. Takeappropriate safety precautions.
8. Compare the above readings to the values given inSection 2, Specifications.
The (+) and (-) readings should be within ± 2 leastsignificant digit (LSD) of each other.
AC:
1. Set the volts calibrator for 60 Hz and repeat thevolts checks as outlined in the DC test above.
NOTE: If a beat frequency effect isexperienced between thecalibrator output and the 60 Hzpower line frequency, try settingthe calibrator for 80 Hz instead of60 Hz.
2. Set the volts calibrator to standby mode.
23
Magtrol Model 5300 Three Phase Power Analyzer Chapter 9 - Calibration
AMPERES CALIBRATION CHECK
DC:
1. On the 5300, press the 5 AMPERES range push-button.
2. Set the current calibrator for zero amperes andoperate mode. The AMPERES display should readzero + 0.0001% max of range full scale.
3. Set the current calibrator for + 5 Amperes DC. TheAMPERES display should read 5.000 Amps.
Record the current readings.
4. Set the current calibrator for - 5 Amperes. TheAMPERES display should read 5.000.
5. Repeat the above for the 25 and 100 Amp ranges.
6. Compare the above readings to the values givenin Section 2 - Specifications.
The (+) and (-) readings should be within ± 2 leastsignificant digit (LSD) of each other.
AC:
1. Set the current calibrator for 60 Hz. and repeat thecurrent checks outlined above.
NOTE: If a beat frequency effect isexperienced between thecalibrator output and the 60 Hzpower line frequency, try settingthe calibrator for 80 Hz instead of60 Hz.
2. Set the current calibrator to standby mode.
WATTS CALIBRATION CHECK
This step calls for the simultaneous application ofvoltage and current to the 5300 PA.
DC:
1. On the 5300, select a VOLTS and AMPERESrange.
2. Set the volts and current calibrators for a voltageand current near the center of each selected range.
Switch the calibrators to OPERATE mode.
3. The WATTS readout should show a power that isthe product of the VOLTS and AMPS indications
( POWER = V × I ).
4. Compare the 5300 PA WATTS readout to theproduct of VOLTS and AMPS from the calibrator'soutput.
This difference is the WATTS error.
AC:
POWER = V × I × Cos θ
where = phase angle between volts and amps.
NOTE: Maximum true power isdelivered only when θ = zerodegrees (cos θ = 1). Therefore,the volts calibrator variable phaseadjustment is set for zero phasebetween the volts and amps at theinput to the 5300 PA. Refer tothe calibrator instruction manualsfor this adjustment procedure.
The phase shift control should be carefully set to providea peak 5300 PA WATTS indication, corresponding tozero volts to amps phase angle. Repeat the procedureas used for the DC power verification and recordreadings.
Compare the recorded reading to the values given inSection 2 - Specifications.
MINOR ADJUSTMENT (IF NEEDED)
NOTE: All trim pot adjustments arelocated on the 78B146 and78B147 circuit boards of the5300. See Figure 17 for trimpotadjustment locations.
Lethal voltages are present. Takeappropriate safety precautions.
24
Magtrol Model 5300 Three Phase Power AnalyzerChapter 9 - Calibration
VOLTS ZERO
1. Disable the auto zero function, refer to SpecialFunctions in Section 5.
2. Go to the 5300 VOLTS range that needs zeroadjustment.
3. Set the volts calibrator for zero volt DC output.
4. Adjust trim pot 78B146-R21 for zero (+ 0.0001%max) VOLTS display reading.
This sets all voltage ranges - all ranges should bezero + 0.0001% of range full scale.
AMPERES ZERO
1. Disable the auto zero function. See Section 5, CT/PT Installation.
2. Go to the 5300 AMPERES range(s) that needadjustment.
3. Set the current calibrator for zero amp DC output.
4. For the 5 amp range, adjust trim pot 78B146-R5,25 amp range adjust trimpot 78B146-R10, and the100 amp range adjust trimpot 78B146-R15 for zeroAMPERES display indication.
VOLTS SCALE FACTOR
1. Go to the 5300 VOLTS range(s) that needadjustment.
2. Set the volts calibrator for an output equal to therange maximum voltage.
3. Adjust the trim pot(s) so the VOLTS display readsthe full scale voltage as shown below:
For the 150 volt range, adjust 78B146-R27.
For the 300 volt range, adjust 78B146-R25.
For the 600 volt range, adjust 78B146-R23.
AMPERES SCALE FACTOR
1. Go to the AMPERES range(s) that need adjustment.
2. Set the current calibrator DC output to the rangemaximum current and adjust trim pot(s) so theAMPERES display reads the full scale current:
For the 5 Amp. range, adjust 78B146-R3.
For the 25 Amp. range, adjust 78B146-R8.
For the 100 amp range, adjust 78B146-R13.
Figure 17. Trimpot Adjustment Locations
Ø -R23Ø -R25Ø -R27Ø -R21
Ø -R13
Ø -R15
Ø -R8
Ø -R10
Ø -R3
Ø -R5
Ø -R23Ø -R25Ø -R27Ø -R21
Ø -R13
Ø -R15
Ø -R8
Ø -R10
Ø -R3
Ø -R5
Ø -R23Ø -R25Ø -R27Ø -R21
Ø -R13
Ø -R15
Ø -R8
Ø -R10
Ø -R3
Ø -R5
Ø -R29Ø -R26
Ø -R24Ø -R21
Ø -R18
Ø -R13
Ø -R10
Ø -R5
Ø -R2
Ø -R29Ø -R26
Ø -R24Ø -R21
Ø -R18
Ø -R13
Ø -R10
Ø -R5
Ø -R2
Ø -R29Ø -R26
Ø -R24Ø -R21
Ø -R18
Ø -R13
Ø -R10
Ø -R5
Ø -R2
78B146 78B147 78B146 78B147 78B146 78B147
Ø3 Ø2 Ø1
25
Magtrol Model 5300 Three Phase Power Analyzer Chapter 9 - Calibration
NOTE: Calibration on the 25 and 100Amps ranges may have to bedone at less than full range scale,depending on your calibrationequipment.
VOLTS BALANCE
1. Go to the 5300 PA 150 VOLTS range.
2. Set the voltage calibrator for + 150 volts DC output.Note the VOLTS display reading.
3. Reverse the calibrator polarity to -150 volts DC. Ifthe plus to minus display readings differ by morethan ± 2 LSD, connect a digital voltmeter atamplifier 78B147-U4 pin 14 and adjust trim pot78B147-R10 for zero ± 0.1 millivolt dc.
CURRENT BALANCE
1. Go to the 5300 PA 5 amp. range
2. Set the current calibrator for + 5 Amps DC output.
3. Note the AMPERES display reading. Reverse thecalibrator polarity to - 5 Amps DC. If the plus andminus display readings differ by more than ± 2 LSD,connect digital voltmeter at amplifier 78B147-U1pin 14 and adjust trim-pot 78B147-R2 for zero ±0.1 millivolt DC.
WATTS SCALE FACTOR
1. Set the volts and current calibrators for 150 VDCand 5 Amp DC output.
2. Adjust trim pot 78B147-R18 for 750.00 WATTSdisplay reading.
3. Confirm AC measurement accuracy by setting thecalibrators for 150 VRMS and 5 Amps RMS at 60Hz. The WATTS display should read close to750.00 watts and be within the specificationaccuracy. See Section 2 - Specifications.
NOTE: Adjust current calibrator's phaseshift control for zero phase anglebetween volts and amps (peak thewatts indication) - see"Calibration Verification--AC,"Step 3.
26
Appendix AAppendix AAppendix AAppendix AAppendix A: Schematic Drawings: Schematic Drawings: Schematic Drawings: Schematic Drawings: Schematic Drawings
CIRCUIT BOARD 78B128 - LED DISPLAY
ab
gf
cdp
ed
ab
gf
cdp
ed
HP
HD
SP
-550
1C
omm
on A
node
LED
Dis
play
s
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
ab
gf
cdp
ed
+ 1C
1
d7d8
Com
+5
ad
bdp
c
J7
ad
c
eg
f
d6
dp
d5
d3d4
d2
b
d1d3
d5d4
ef
g
d2d1
WA
TT
SLS
DM
SD
LSD
digi
t 8di
git 3
digi
t 4di
git 2
digi
t 1di
git 5
LSD
MS
D
AM
PS
MS
D
VO
LTS
digi
t 4di
git 5
digi
t 3di
git 1
digi
t 2di
git 6
digi
t 7
27
Magtrol Model 5300 Three Phase Power Analyzer Appendix A: Schematic Drawings
CIRCUIT BOARD 78B145 - DIGITAL READOUT & MPU
U6
4Q3Q6 92
74H
C37
3
1Q5
87
4D3D
41D
3
2Q2D
6Q 8Q7Q16 19
5Q5D
1512
18 118D7D LE
13 17146D
35P
32
P35
P34
P36
P33
34 33 313240
SC
1E
P30
373839 36
8 1110
P31
P20
RS
T
P23
P22
P21
932 5
EX
2MC
6803
4
X1
NM
IS
C2
6IR
Q
P43
P45
P44
22P
47P
46
25 24 23
P37
P41
P40
26P
42272930 28
17 1918 20
P15
P13
P14
P17
P16
1312 14 1615
P10
P24
P12
P11
7P
A4
PA
5P
A6
CA
1P
A7
8 40932
PA
1P
A0
PA
3P
A2
4 65
27 2628 36
D4
D5
RS
0
D6
D7
3233 30 2931
MC
6821
D1
D0
D3
D2
15P
B5
14 1716
CB
118 191211
PB
1
10 13P
B3
PB
2
39
38 37IR
QB
34P
B6
PB
4IR
QA
W
CB
2
PB
7R
ES
2335 2125
PB
0C
A2
CS
2
RS
1
R/
E
13
DQ
4D
Q3
14 1510D
Q0
11D
Q2
DQ
1
9
5 4A
3A
2
A4
36
DS
1220
A0
8
A1
7
18C
E
WE
OE
20 2116D
Q5
DQ
7D
Q6
17
22 19
A8
A9
A10
23
A5
2A
6A
71
Seg
d
DIG
IT 6
DIG
IT 3
24 2223
Vss
2728 2526
5 6 7
Seg
fD
A0
D.P
.
DP
inD
A1
21
Seg
b43
ICM
7218
C
Seg
c
Seg
gS
eg e
Seg
a
DIG
IT 8
1718 16 15
DIG
IT 7
DIG
IT 4
2021 19
D0
12 13 14
DIG
IT 5
D2
DIG
IT 2
DIG
IT 1
D3
98 1110
WR
ITE
MO
DE
Vdd
D1
DA
2
Seg
d
DIG
IT 6
DIG
IT 3
24 2223
Vss
2728 2526
5 6 7
Seg
fD
A0
D.P
.
DP
inD
A1
21
Seg
b43
ICM
7218
C
Seg
c
Seg
gS
eg e
Seg
a
DIG
IT 8
1718 16 15
DIG
IT 7
DIG
IT 4
2021 19
D0
12 13 14
DIG
IT 5
D2
DIG
IT 2
DIG
IT 1
D3
98 1110
WR
ITE
MO
DE
Vdd
D1
DA
2
P10
TO
P13
= C
OD
E B
DA
TA
P15
TO
P17
= D
IGIT
AD
DR
ES
SP
14 =
D.P
.
000
0 00
0 000
0
0000
00 0
00
0
080
10 D
DR
B/O
RB
PIA
8000
DD
RA
/OR
A80
01 C
RA
00
10
00 0
GP
IAC
001
R1
180
11 C
RB
C00
0 R
00
01
0 01
100 1
0 11
AD
DR
ES
S B
US
(A
D15
-0) 0
0 01
00
101
000
FF
FF
=81
920
E00
0R
OM
CO
DE
11
10
0
0 127
FF
(N
ON
VO
L.)
0IN
T R
AM
80
TO
FF
EX
T. R
AM
200
0 T
O0 1
1
00 0
00 0
00
01
0
10 0
00
00 00
11
11 10
00 0
00
0
00
00
00
000
00
00
000
00
11
0
10
0
01
11
1
10 0
00
00
01
00 0
1 01
00 1
11 0
100
11
110
00
1 00 00
VO
LTS
100
0V
OLT
S 1
00
AM
PS
100
0
VO
LTS
1
AM
PS
1
VO
LTS
10
P17
P16
P
15
DIG
IT
AM
PS
100
AM
PS
10
CO
DE
B
0 1
2 3
4 5
6 7
8 9
- E
H
L
P
(BLA
NK
)
DE
CIM
AL
0 1
2 3
4 5
6 7
8 9
10
11
12
13
14
15
WA
TT
S 1
00W
AT
TS
10
WA
TT
S 1
WA
TT
S 1
0000
WA
TT
S 1
000
00
10
00
00
00
0 $400
0
1C
007
R7
1
$600
0
0
00 0
000
0 00
00
0
00
000 0
00
00
0 01
C00
3 R
301
C00
2 R
20
1 1
00
0
0C
005
R5
C00
6 R
6
0C
OO
4 R
41
111
10 0
11 0
0
0 0
0 100 0 11
11 1
0 01 0 0
11 00
00
0
110
0 0 00 100 1
0 001
1
00 0
00 0
11
111 1
00 0
10 0
11 1
1 11
00
0 00
00 0
00
0
00 0
00
00
0 00
00
AD
6U
7A
8A
D7
AD
4A
D5
AD
7A
D6
CO
M
A1
A2
713
DQ
1
15D
Q2
2764
10D
Q0
A0
11 12
A12
9A
118
A3
A2
A0
A10A9
A1
PB
1R
NG
RE
S
PA
7R
LP
B4
FC
TP
B2
PB
3
PB
0
A6
A7
AD
7A
0A
1
PA
5P
A6
PA
4
PB
1D
AV
PB
0C
TP
A7
AD
2A
D3
PB
5
AD
0A
D1
PB
3P
B2
PB
4
AD
0A
D1
4MH
z27pf
AD
3
AD
4A
D2
AD
5
AD
1
AD
2A
D0
+47
27pf
1N48
2x2
CO
M
EJ1
A1
AD
3A
2P
A2
AD
2P
A3
AD
3
A0
AD
1
U3
PA
1A
D0
PA
0
PB
6P
B5
+5
LL2
LL1
PB
7+
1
A5
AD
5P
A5
PA
6A
D6
A3
A4
PA
4A
D4
171-
4S
R
1S
R0
11S
R6
B1
2 4B
24
D1
5D
2
S R
5
MC
3447
322 20218
12 11A
D5
D0
AD
4
14A
D6
13A
D7
35 33
T R
2IB
1D
5D
4IB
3
T R
128 27
D7
D6
78
D0
D3
AD
1D
PA
D0
10 9D
3D
1A
D3
D2
AD
2
D1
18S
RQ
RF
D
29IB
531
IB7
D2
23
5B
2
B4
B3
5D
3D
2
6
MC
3447
U10 31
B1
3D
14
CO
M21 20 19
J322
dac
B6
ifcB
7D
6eo
iD
710
D4
7
D5
B5
dav
2D
07
16 15
B0
23 18
+5
CO
M
32IB
2IB
430
A1
38 39A
2R
S1
MC
6848
836
RS
034
IB0
3C
S37
A0
40 6 54.
7kx5
RS
219
2125
IFC
EE
OI
R W
16 179
DA
VIB
6
IRQ
RE
SD
AC
AD
7
AD
3A
D2
AD
5A
D6
AD
4
A10
U5
A2
A4
A5
A3
1+
ca
DPb
D5
D8
e D6g
dD7f
4 512
24
Unl
ess
othe
rwis
e no
ted
Not
e:
All
capa
cito
rs in
uF
U
All
resi
stor
s in
OH
MS
20,2
2,24
141,
27,2
81
J7
3
Y6
7Y
7
8
7,21
1,108
1,2
201
1612
6
1110
167
20
98
18D
Q5
19D
Q7
DQ
6A
D7
AD
6
U4
16D
Q3
17D
Q4
AD
4A
D5
A6
25A
7A
64
A8
A7
3
A4
A5
A3
6
A5
5A
4
EA
15
AD
1A
D0
G22 20
A14
A13
A12
A11
23A
11
A12
2
A9
A10
A9
24
A10
21
12kx
2
PA
0
CO
M
PB
6P
B7
PA
2P
A3
PA
1
A1
Y0
214
74F
138
15
Y5
10 9
Y2
13 12 115
Y4
G2A
G2B
63 4
Y1
CB
Y3
G1
U2
+5
U12
15G
2
g
U1
A1
A7
A6
A0
A8
A9
D2D1
D4D3
D3D4
D1D2
DP
e
adf
D5bc
D5
rfd
D7
ren
9D
610
D4
D3
D0
6 7218 1516
srq
B5
atn
B7
B6
19 23
6B
3B
48
B0
sw2
S R
S R
51-4
sw5
sw1
sw4
CO
M
8J2
U11
17A
D0
A15
A8
U8
DA
0
DA
2
A13
A14
DA
1
sw3
3274
HC
367
Y1
A1
26
RE
N22
4A
TN U
9AS
E
AD
113
AD
4A
D2
AD
314
1
Y5
A5
Y6
G1
A6
A2
64
A3
12
5Y
2
11Y
37
CO
M+
5
36
54
02
113
1211
1415
87
109
28
Magtrol Model 5300 Three Phase Power AnalyzerAppendix A: Schematic Drawings
CIRCUIT BOARD 78B146 - ANALOG INPUT BOARD
U9x200x100
9
14
x1010
15
1612
113
-
7
8-
INA110KPx500
+6
3
+2
11
C8
.1
-15V
+15V
R15
200K
R28
2K
R29
2K
R21
200K
U10x200x100
9
14
x1010
15
1612
113
-
7
8-
INA110KPx500
+6
3
+2
11
-15V
+15VP135
P145
P137
P127
R17
470
P147
R16
470
U2
21
45
4N366
U1
21
45
4N366
U7x200x100
9
14
x1010
15
1612
113
-
7
8-
INA110KPx500
+6
3
+2
11
+15V
-15V
C2
.1
-15V
R5
200K
U8x200x100
9
14
x1010
15
1612
113
-
7
8-
INA110KPx500
+6
3
+2
11
C22.1
-15V
C5
.1
R10
200K
+15V
P123
P129
U11
Vdd1314
1615
3
Vss4
12
ADG201HSKN
9
121110
87
56
GND
P125
C23.1
+15V
CR12FDH300
CR10FDH300
-15V
CR5FDH300
-15V
R6
10.0K
+15V
CR8FDH300R7
10.0K
CR6FDH300
CR9FDH300
CR11FDH300
P136
P134
P132
P138
25A SHUNT
5A SHUNT
SHUNT COM
100A SHUNTR11
10.0K
R19
10.0K
P133
P131
V HIGH
V LOW
R12
10.0K
R39
1.5M
C6
.1
-15V
R13100
C7560pF
C9
.1
-15V
R14
80.6
CR3FDH300
CR4FDH300
CR2FDH300
-15V
R1
10.0K CR1FDH300
R2
10.0K
+15V
C4180pF
CR7FDH300
R4
80.6
C3
.1
R3100
C1180pF
R9
80.6
-15V
C25180pF
R8100
C18
1
C14
1
C121000
C15
.1
VR1
LM340T15
C17
.1VR2
LM320T15
C16
1
+15V P117
P115
U6
21
45
4N366
5V
C19
.1
VR3
LM340T5
P118
P116
P119
-15V
R31
2K
R30
2K
C11
.1
C10
.1
R33
2K
R32
2K
+15V
R35
470
P148
R36
470
P146
R18
470
P149
U5
21
45
4N366
U4
21
45
4N366
U3
21
45
4N366
R37
470 P143
P150
U12
Vdd1314
1615
3
Vss4
12
ADG201HSKN
9
121110
87
56
GND
T1
14A-10R-36
P12
C20.1
J2
P11
J1
J3
BR1
PD05
R22
301K
R23
100K
C131000
R20
10.0K
CR14FDH300
CR13FDH300
R3415.8K
+15V
R40
1.5M
R3815.8K
C21.1
-15V
CR15FDH300
CR16FDH300
-15V
R27
5K
R25
10K
-15V
R24
23.2K+15V
R26
4.64K
5VVOLTS COM
A100 COM
VOLTS
25A SELECT
5A SELECT
AMPS
A5 COM
A25 COM
+
+
+
+15V
+5V
SIGNAL COM
POWER COM
-15V
150V SELECT
300V SELECT
100A SELECT
600V SELECT
CHASSIS COM
AC LINE
FOR 120 VOLT OPERATION JUMP J1 AND J3
FOR 240 VOLT OPERATION JUMP J2 ONLY
3
AC LINE
600V
4
1 7
9
+
+
126
10
300V
150V
29
Magtrol Model 5300 Three Phase Power Analyzer Appendix A: Schematic Drawings
CIRCUIT BOARD 78B147 - CONVERTER BOARD
R24
20K
+15V C
13
.001
U5
Vo
+V12
+IN
14 132 3 41
-IN
9 8
CO
MC
OM
P
11 106 7
Fo
VF
C32
0CG
5-V C
+15V
U6
7 682 31
54
6N13
7
-15V
R15
1.5K
R22
34.8
K
U9
Vo
+V12
+IN
14 132 3 41
-IN
9 8
CO
MC
OM
P
11 106 7
Fo
VF
C32
0CG
5-V C
R23
10M
-15V
R21 20
K
C12
.1
R29
20K
R28
10M
C15
.001
P1
48
+15V
-15V
R16
470
C10
.1
U10
Vo
+V12
+IN
13142 3 41
-IN
9 811C
OM
CO
MP
106 7
Fo
VF
C32
0CG
5-V C
+15V
R27
32.4
K
R26
20K
+15V
U2
Vo
+V12
+IN
14 132 3 41
-IN
9 8
CO
MC
OM
P
11 106 7
Fo
VF
C32
0CG
5-V C
R7
1.5K
C3
.001
C4
330p
f
R5
20K
+15V
-15V
-15V
C8
.001
-15V
C9
330p
f+15V
R12
10M
C5
.1R
847
0P
146
5V+1
5VU
3
7 682 31
54
6N13
7
+15V C27
.01
5V
C29
.01
+15V
C6
2.7
U4
Vin
12 11
BFo
14 132 3
CO
M41
BFi
Cav
RM
So810
+V -V9
7D
EN
i
AD
637K
Q
dBo
5 6
OFF
SC
S
R9
24.3
KP
1 35P1 37
U7 O
UT
12 11
+V1314
3X
221
X1
-V
AD
534L
D
8
Z1
Z2
10 96 7
Y1
Y2
SF
4 5
-15V
R10
50K
+15V
R47 75
0K
R11
34.8
K+1
5V
R13
20K
-15V
-15V
R20
301K
C42
.1
C28 .0
1C
7
2.2 +1
5V
C41
.1
C1
2.7
P1 23 P1 25P1 29
R46 75
0K
P1 27
R2
50K
-15V
+15V
R3
34.8
K+1
5V
R4
10M
-15V
U1
Vin
12 11
BF
o14 13
2 3C
OM
41B
Fi
Cav
RM
So810
+V -V9
7D
ENi
AD
637K
Q
dBo
5 6
OF
FS
CS
R1
24.3
K
C39
.1
C26 .0
1C
40.1
C2
2.2
C22
.1U
14
4521
64N
36
C19
.1R
391.
5KR
401.
2K
+15V
5V
R45
1.2K
U15
4521
64N
36C
25.1
5V
R44
1.5K
C24
.1
+15V
U11
7 682 31
54
6N13
7R
3147
0P
1 44P1 50
CR
2
1N41
48
CR
1
1N41
48
C38 1
P1 47P1 45 P1 49
5V
-15V
C31
.01
R19
100K
R18
20K
U8
6
15
-2
7LF35
1+
4
3C
1433
0pf
C16
330p
f
C32 .0
1
+15V
-15V
C11
.47
C30 .0
1+5
V5V
C33
.01
+15V
-15V
C17
.1R
3247
0R
2582
0R
3082
0
R42 10
.0K
+15V
R41 10
.0K
P1 19
-15V
P1 17
C37
1
+5V C35
1C
36 1P
1 18 P1 16P1 15
R43 24
9KU
16 -+
+V8 7
21G
ND
LM31
1N
5B
AL
ST
R6
-V43
U13 -+
+V8 7
21G
ND
LM31
1N
5B
AL
ST
R6
-V43
-15V
C21
.1 C23
.1 C34
.1-1
5V
U12
6
7-
2
OP
74
3+
R34
17.8
K
R33 1.69
K
R35 10
.0K
+15V
C18
.1-1
5VC
R3
1N82
1
+15V
-15V
R38 24
9KR17
200K
C20
.1
R36 10
.0K
R37 10
.0K
VO
LTS
OU
T
AM
PS
OU
T
+
VO
LTS
CO
M
VO
LTS
+
+
A5
CO
M
AM
PS
A10
0 C
OM
A25
CO
M
+
VO
LTS
OL
WA
TT
S O
UT
CH
AS
SIS
CO
M
AM
PS
OL
+5V
+
-15V
+15V
+
++
PO
WE
R C
OM
SIG
NA
L C
OM
+5V
30
Magtrol Model 5300 Three Phase Power AnalyzerAppendix A: Schematic Drawings
CIRCUIT BOARD 78B149 - SWITCHBOARD
C1
R3200
R4200
R1200
R2200
J4
SW3FRONT VIEW
SW4
RIGHT
SW1
LEFT
SW2
31
Magtrol Model 5300 Three Phase Power Analyzer Appendix A: Schematic Drawings
CIRCUIT BOARD 78B153 - SWITCH INTERFACE
CD4518
EN10
Q314
RST
CD4518
EN2
6RST
Q3
7
CD4518CK
1
Q3
ENRST
72
CD4518
EN2
Q36
RST7
CD451811
Q0
RSTEN
1510
CD4518
EN10
Q314
RST
15
15
11255
01
01000
Unless otherwise noted
Note: All capacitors in uFAll resistors in OHMS
3,4,6U +5 COM
20 1,10
1,8,98,9
11,20 10
10 16
5,7168,9
3D4
2
2D3
J4 FunctionØVPF
65D6D
7
5
Ø2Ø1 SwitchJ4 Phase
PA4PA3
1817
2QPA1PA2
1D 1QPA019
PA1
U9aPA0
PA2
15
6Q5Q
PA4PA514
3Q4Q4D
PA316
R15
25
R2
J1
600CT
150300
74HC573PA6PA5
FCT
PA7Hold SwitchAVG
100
+5
+5
COM
1
E
U10b
6U10a
RNG
CTDAVRES
LL1RL
LL2
3
74HC5731D
11LE U38D
PA0 2PA1
.001
PA0
5
7
4D6
5D
42D
3Q3D
PA5PA4PA5PA4
PA1PA2PA2PA3PA3
ØV
H LED
181Q
19
AVGPF
Ø1 LEDØ2
4Q5Q6Q
1514
2Q
1617
53Q3D
4D
34
74HC573
2D1D
PA3PA2PA2PA3
PA0PA1
2PA1PA0
97D
8Q7Q
67
5D6Q6D
PA6PA7
8PA6PA7
PA4PA4PA5PA5
J5
2Q
1617
1918
1Q
1312
4Q15
5Q14
COM12kx8U2
Range R1 R2
136Q7Q
PA6 U8a1415 PA4
PA58
6D7D
4D67
4Q5Q5D
OC
U8b.001
128Q
U7
PA798D
1
U1 12kx8
Auto Switch
COMU9b.001
12 PA7PA6
1
74HC573
8DU5OC
7D89
13
8Q7Q
16PA2PA3
19 PA0PA1
43D
5
2Q17
3Q
1D23
1Q18
2D
86Q
136D
4D5Q5D
1514PA5
PA6PA6
PA4PA4 67PA5
8DLE
8QU6
7D12
7Q
.001
PA7PA7 911
150
A LED
150
A Sw
J4 Volts
600300
A LED
COM
300600
118D
U4LE
7D8
7Q6D
8Q.001
9PA6PA6PA7PA7
43Q3D
5
274HC573
2D1D
PA3PA2PA2PA3
PA0PA1PA0
3PA1
J4 Amps
3ØKWØ3
12 3ØKW13 Ø3
25 25100
5 5
1716
4Q100
1Q18
2Q
19
32
Magtrol Model 5300 Three Phase Power AnalyzerAppendix A: Schematic Drawings
CIRCUIT BOARD 78B154 - COUNTERS BOARD
U31
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
U32
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U26OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U25OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
U30
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U24OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U38OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U37OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U36OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
U33
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U27OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U39OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U14OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U13OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
U7
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q314
Q2
1211
13RST
15EN Q1
109
Q0CK
U8
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U12OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
U6
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q314
Q2
1211
13RST
15EN Q1
109
Q0CK
U20
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
U19
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
U18
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U15OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
U9
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
U21
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
U28
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q314
Q2
1211
13RST
15EN Q1
109
Q0CK
U2
345
56
74HC154
21
43
21
18
C20
G1
D
2322
10
2BA
1514
1617
131110
14
11
15
89
1312
10
19G2
76
97 8
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U22OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
10111213
4365
21
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U34OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
U29
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U23OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U35OC
128Q
5D6Q5Q
1413
118D
9
LE1
6D7
7D8
3Q4Q
1615
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U10OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
U4
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q314
Q2
1211
13RST
15EN Q1
109
Q0CK
U16
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
U3
345
56
74HC154
21
43
21
18
C20
G1
D
2322
10
2BA
1514
1617
131110
14
11
15
89
1312
10
19 G276
97 8
3Q4Q 16
15
1974HC573
1Q1817
6
3D4
4D5
23
1D2Q2D
7Q
U11OC
128Q
5D6Q5Q
1413
118D9
LE1
6D7
7D8
U5
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q314
Q2
1211
13RST
15EN Q1
109
Q0CK
U17
Q3Q2
6
43
527
EN Q1RST
14520
Q0CK
Q3 14Q2
1211
13RST15EN Q110
9 Q0CK
PA7
PA0PA1
PA2PA3
PA5PA6
PA4
PA7PA6
PA1PA0
PA3PA2
PA5PA4
PA7
PA2PA1PA0
PA3PA2
PA5PA6
PA4
VOLTSPA0PA1
PA4PA3
PA5
PA7PA6
CD4520EN1
X
PA0PA1
CL
0
1X
PA7
PA1PA0
PA3PA4
PA2
PA6PA5
X QoX Z
D74HC573LE Q
H HL L
XX LL
XH
Qx
INCX
INCHL
OC
HL
PA7PA6PA5
AMPSPA1PA0
PA2PA1PA0
PA3PA4
PA1PA2
PA7PA6
PA0
PA7
PA1PA0
PA4PA3
PA6PA5
A3Fin
W3FinV3Fin
A3OLV3OL
1+5
A1OL
W1Fin
A2OLV2OL
V1FinA1Fin
V1OL
PA1
PA4PA3PA2
PA5
W2Fin
J6
PA0
A2FinV2Fin
PA2
PA4PA3
PA1
PA5
PA0
PA7PA6
PA7
U1 74HC04
LL2LL1RL
+51
PB7PB6
PB4PB5
PA7
J1
DAV
FCTRNG
RES
PA2PA3
PA0PA1
PB3
PA4
PB2
PB0PB1
PA7
PA5PA6
PA7
PA0
PA3PA2PA1
PA4PA3PA2
PA5PA6
PA3PA2PA1
PA6PA5PA4
PA6PA5PA4
PA7
PA0
PA2PA3
PA7
PA5PA4
PA4PA3PA2
PA5PA6
PA1PA0
PA3PA4
PA2
PA5PA6
WATTS
PA7PA6
PA0PA1
127,9
10
8
Note: All capacitors in uF
Unless otherwise notedAll resistors in ohms
COM
22,23,2413,14,15
37,38,3934,35,3625,26,27
32,3330,31
2010,11,12
8,9,16,174,5,6,7
2,3
21,28,2918,19,20
+51U
2416
14
PA7PA6
PA3PA2
PA5PA4
PA0
PA2PA1
PA3PA4
PA2
PA7PA6PA5
PA7
PA1PA0
PA4PA3
PA6PA5
33
Magtrol Model 5300 Three Phase Power Analyzer Appendix A: Schematic Drawings
CIRCUIT BOARD 78B175
BR1
PD05
T1
14A-20-10
94
6 7
12
10
1
3C4.1uF
C31uF
C14700uF
C21uF
OI
+5V7805
Line
120
Com
C
Neu
(Heatsinkto chassis)
25V120
240
Magtrol, Inc. warrants its products to be free from defects in material and workmanship under normal use andservice for a period of one (1) year from the date of shipment. Software is warranted to operate in accordance withits programmed instructions on appropriate Magtrol instruments. This warranty extends only to the original purchaserand shall not apply to fuses, computer media, or any other product which, in Magtrol’s sole opinion, has beensubject to misuse, alteration, abuse or abnormal conditions of operation or shipping.
Magtrol’s obligation under this warranty is limited to repair or replacement of a product which is returned to thefactory within the warranty period and is determined, upon examination by Magtrol, to be defective. If Magtroldetermines that the defect or malfunction has been caused by misuse, alteration, abuse or abnormal conditions ofoperation or shipping, Magtrol will repair the product and bill the purchaser for the reasonable cost of repair. If theproduct is not covered by this warranty, Magtrol will, if requested by purchaser, submit an estimate of the repaircosts before work is started.
To obtain repair service under this warranty, purchaser must forward the product (transportation prepaid) and adescription of the malfunction to the factory. The instrument shall be repaired at the factory and returned to purchaser,transportation prepaid. MAGTROL ASSUMES NO RISK FOR IN-TRANSIT DAMAGE.
THE FOREGOING WARRANTY IS PURCHASER’S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OFALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIEDWARRANTY OF MERCHANTABILITY, OR FITNESS FOR ANY PARTICULAR PURPOSE OR USE.MAGTROL SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIALDAMAGES OR LOSS WHETHER IN CONTRACT, TORT, OR OTHERWISE.
CLAIMSImmediately upon arrival, purchaser shall check the packing container against the enclosed packing list and shall,within thirty (30) days of arrival, give Magtrol notice of shortages or any nonconformity with the terms of the order.If purchaser fails to give notice, the delivery shall be deemed to conform with the terms of the order.
The purchaser assumes all risk of loss or damage to products upon delivery by Magtrol to the carrier. If a product isdamaged in transit, PURCHASER MUST FILE ALL CLAIMS FOR DAMAGE WITH THE CARRIER to obtaincompensation. Upon request by purchaser, Magtrol will submit an estimate of the cost to repair shipment damage.
Magtrol Limited WMagtrol Limited WMagtrol Limited WMagtrol Limited WMagtrol Limited Warrantyarrantyarrantyarrantyarranty