5 24 glands
TRANSCRIPT
-
8/2/2019 5 24 Glands
1/12
SAUDI CONSOLIDATED ELECTRIC COMPANY
CENTRAL REGION
SPECIFICATION NO: 5/24
HV CABLE GLANDS FOR 13. 8kV & 33 kV SWITCHGEAR
AND TRANSFORMER
APPROVEDDIVISION
MANAGER
REVISION C
DATE 15/10/1407H
ENDORSED -----------------------------------------
Director Tech. Studies Date24/10/1407H
APPROVED --------------------------------
Vice President for Engineering Date27/11/1407H
012/74320/AB-mza.
-
8/2/2019 5 24 Glands
2/12
Specification No: 5/24 Rev. No: C
Page 2 of 12
Revisions
Original
Rev. A
Rev.B February-1981.
Rev.C Shawwal-1407 Revisions sheet and Contents sheet added
(June-1987) Addition of 33kV glands.
-
8/2/2019 5 24 Glands
3/12
Specification No: 5/24 Rev. No: C
Page 3 of 12
CONTENTS
1. Scope2. Design 3. Insulated Cable Glands4. Covering Sleeve5. Form of Supply6. Detailed Instruction7. Packing8. Schedule of Particulars9. Drawings: SC/P/665/48
SC/P/665/50
SC/P/665/51
http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/ -
8/2/2019 5 24 Glands
4/12
Specification No: 5/24 Rev. No: C
Page 4 of 12
H.V. CABLE GLANDS FOR 13.8kV & 33kV SWITCH GEAR:
1. SCOPE:This specification covers the requirements of SCECO, Central Region, of the manufacture and
supply of H.V. cable Glands for 13.8kV & 33kV switchgear and transformers.
These cable glands can he insulated or uninsulated.
2. DESIGN:
2..1 The purpose of the cable gland is to provide an adequate, corrosion resistant earth bond for the
metallic cable armours together with means of sealing the cable sheath terminations.
2.2 These cable glands are designed to accommodate 3-phase HV XLPE cables specified in SCECO,Central Region, specifications Nos. 5/2 and 5/3 (Latest Editions)
2.3 The particular options regarding cable dimensions are summarized in the table below:Tension Cable Size
(sq.mm)
Approximate
Diameter Underneath
The Armour (mm)
Diameter of
Armour Wires
(mm)
33Kv 3 x 240 91 3.15
13.8kV
3 x 300
3 x 185
3 x 50
81
69
49
3.15
2.5
2.5
2.4 The cable glands are designed to allow enough space inside the switchgear cable box to allow
cross core connection and ease interchange of phase. Details are shown in drawing No.
SC/P/665/48.
2.5 Contact between armour and gland is ensured by two worm drive clips. This contact should be
designed to withstand 21kA for 1 second for 13.8kV network and 25kA for 1 second for 33kV
network.
2.6 A stud (M10) is welded on the cable gland to connect an earthing cable. Adequate nut and
washer are provided.
2.7 The cable glands should be made of galvanised steel to prevent corrosion.
http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/ -
8/2/2019 5 24 Glands
5/12
Specification No: 5/24 Rev. No: C
Page 5 of 12
3. INSULATED CABLE GLANDS:
3.1 Where insulated cable glands are used; the glands are insulated from the metalwork of the
switchgear by a square insulating insert.
The fitting must be secured by 4 insulated nuts, bolts and washers or by ordinary nuts, bolts and
washers in conjunction with insulating devices. Details are shown in drawing No.
SC/P/665/51.
3.2 In this case all insulated accessories (insert, nuts and bolts) must be designed to withstand a
power frequency test voltage of 10kV for 3 sec.
3.3 The thickness of the insulating insert must be not less than 9 mm.4. COVERING SLEEVE
Connection between armour, gland and conductor will be covered with a heat shrinkable
internally coated sleeve which seals the gland to the cable sheath as shown on SCECO, Central
Region, drawing No. SC/P/665/50 and in accordance with general specification No.5/12 -"Heat
Shrinkable Cable Terminations and Joints" (latest edition).
Dimensions of the sleeve are given in the following table:
S L E E V E
Nominal DiameterTension Cable
Size
(sq. mm)
Length
(mm)
Minimum Thickness
After re-cover (mm)Expanded Re-covered
33Kv 3 X 240 300 3 160 55
13.8Kv
3 X 300
3 X 185
3 X 50
300
300
250
3
3
3
160
160
115
55
55
30
5. FORM OF SUPPLY:
The cable glands should be supplied in the form of 4 different kits as given below:
Type 1: Non-insulated Cable Gland 3x240, 3x300 or 3x185 mm2 cable including:
1- Gland, type A.
2- Worm drive clips.
http://0.0.0.0/http://0.0.0.0/ -
8/2/2019 5 24 Glands
6/12
Specification No: 5/24 Rev. No: C
Page 6 of 12
1- Heat shrinkable sleeve.
4- Steel nuts, bolts and washers.
1- Nut and washer (for connection of earthing cable).
Type 2: Non-insulated Cable Gland 3 x 50 mm2
cable including:
1- Gland, type B.
2- Worm drive clips.
1- Heat shrinkable sleeve.
4- Steel nuts, bolts and washers1- Nut and washer (for connection of earthing cable).
Type 3: Insulated Cable Gland 3x240, 3x300 or 3x185 mm2
cable including:
1- Gland, type A.
2- Worm drive clips.
1- Square insulating insert.
1- Heat shrinkable sleeve.
4- Steel nuts, bolts and washers (insulated or with insulating devices).
1- Nut and washer (for connection of earthing cable).
Type 4: Insulated Cable Gland 3 x 50 mm2
cable including:
1- Gland, type B.
2- Worm drive clips.
1- Square insulating insert.
1- Heat shrinkable sleeve.
4- Steel nuts, bolts and washers (insulated or with insulating devices).
1- Nut and washer (for connection of earthing cable)
6. DETAILED INSTRUCTION
A detailed instruction shall be included with each gland.
7. PACKING
Glands will be individually packed for shipment.
-----------------------
-
8/2/2019 5 24 Glands
7/12
Specification No: 5/24 Rev. No: C
Page 7 of 12
8. SCHEDULE OF PARTICULARS
S
No. Description Unit
SCECO(C)
Requirements Bidders Data
SCECO(C) 5/2
SCECO(C) 5/3
91
81
69
49
3.15
3.15
2.52.5
Required
SC/P/655/48
A Type
B Type
Type A Type B Type A Type B
15100
95
86
150
125
115
1.5
3
62.5
57.5
1170
66
66
140
90
90
1
2.5
45
45
1.
2.
3.
4
5.
Cable Specification
13.8kV
33 kV
Cable dimensions that theglands must accept.
-Diameter underneath armour:
3x240 sq. mm 33kV
3x300 sq. mm
3x185 sq. mm 13.8kV
3x50 sq. mm
-Diameter of armour wires:
3x240 sq. mm 33kV
3x300 sq. mm
3x185 sq. mm 13.8kV3x50 sq. mm
Cross core connection and
Interchange of phase.
Reference Drawings
- 3x240 3x300 3x185sq.mm
- 3x 50 sq.mm
Dimensions
- B- D- E- F- L- M- N- S- T- X- Y
mm
mm
mm
mm
mm
mm
mmmm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
-
8/2/2019 5 24 Glands
8/12
Specification No: 5/24 Rev. No: C
Page 8 of 12
SCHEDULE OF PARTICULARSSheet 2 of 3
S
No. Description Unit
SCECO(C)
Requirements Bidders Data
Two worm
drive clips
21 for 1 sec.
25 for 2 sec.
Required
Required
Coated or
Anticorrosiontreated steel
9
10 for 3 sec.
Insulated or
Insulating
Devices.
SC/P/665/51
SC/P/665/50
SCECO(C) 5/12
Type A Type B Type A Type B
300
3
160
55
250
3
115
30
6.
7.
8.
9.
10.
Contact between cable armour
and gland:
-Design
-Rating -13.8Kv
-33Kv
Connection of earthing cable.
-Welded Stud M10
-Nut and Washer
Material
Insulated Gland
-insulated insert thickness
-insulation level
-Nuts, bolts, washers
-reference drawing
Covering Sleeve
-reference drawing
-reference specification
-dimensions:
length min. thickness after
recover
nominal diameterexpanded
nominal diameterrecovered
kA
kA
mm
kV
mm
mm
mm
mm
http://0.0.0.0/http://0.0.0.0/ -
8/2/2019 5 24 Glands
9/12
Specification No: 5/24 Rev. No: C
Page 9 of 12
SCHEDULE OF PARTICULARSS.
No. Description Unit
SCECO(C)
Requirements
Bidders date
11.
12.13.
Kit Composition
Type 1 non-insulated gland for
3x240, 3x300 or 3x185 sq.mm
cables
-Type A gland
-Worm drive clips-Sleeve
-Steel nuts, bolts & washers
-Nut & washer for earthing cable
Type 2 non-insulated gland for
3x50 sq.mm cables.
-Type B gland
-Worm drive clips
-Sleeve
-Steel nuts, bolts & washers
-Nut & washer for earthing cable
Type 3 insulated gland for
3x240, 3x300 or 3x185 sq.mm cables
-Type A gland
-Worm drive clips
-Insulating insert
-Sleeve
Steel nuts, bolts & washers (insulated or
with insulating devices)
-Nut & washer for earthing cable
Type 4: Insulated gland for
3x50. Sq. mm cables
-Type B gland
-Worm drive clips
-Insulating insert
-Sleeve
-Steel nuts, bolts & washers
(insulated or with insulating devices)
-Nut & washer for earthing cable
Detailed instructionPacking
1
2
14
1
1
2
1
4
1
1
2
1
1
4
1
1
2
1
1
4
1
1 per glandIndividual
-
8/2/2019 5 24 Glands
10/12
-
8/2/2019 5 24 Glands
11/12
-
8/2/2019 5 24 Glands
12/12