4_purge unit technical documentation
TRANSCRIPT
-
7/22/2019 4_Purge Unit Technical Documentation
1/34
An der Hartbrcke 8D-64625 Bensheim
Tel.: 06251/63736FAX: 06251/63729
client order number code motor system number sheet no. of sheets
VEM 45089428 1 34
title
TECHNICAL DOCUMENTATION Ex p SYSTEM F-361.C4
for purge volume 200 up to 450 Nm/hdate of change revision originator format Ident.-no. file
Reinig A4 vem45089428c4e.doc
Rev. originator: release:
originate (date / sign) checked: (date / sign) release: (date / sign )
06.12.2008 Bachmann
Technicaldocumentation
EExxppssyysstteemmffoorrmmoottoorrooppeerraattiioonniinnEExx--aarreeaass
-
7/22/2019 4_Purge Unit Technical Documentation
2/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 2 of 34
Description of Ex p system F-361.C4
Principle of pressurizing system
To operate motors in hazardous areas some especially requirements are needed forthe electrical and mechanical equipment.On the base of the Ex-protection p, internal overpressure, motors can operate inthese areas. For this the cabinets of the motors should be sealed in a way that theleakage of compressed air is very low. Furthermore a pressure supply with sufficientair supply has to be in reserve.
The principle sequence of a safety device for a pressurizing system is shown asfollowed:
After the start of the functional sequence the air flow of the purge gas and the
thereby in the motor growing overpressure are monitored.
If a minimum of air flow streams through the motor enclosure (measure pointin the outlet valve) and a fixed motor enclosure overpressure has beenreached the purge time starts. After the purge time ran off, the motor can bestarted.
If some faults appear the control sequence is set to the start point of thefunctional sequence.
The safety device has to be combined with a main control system, whichprevents the start of the motor until the purging sequence has finished.
The EEx p pressurization system F-361.C4serves to create and maintain anoverpressure in an EEx p motor enclosure to prevent the ingress of the ambient(potentially explosive) atmosphere, according to EN 60079-2.In addition a compensation of the leakage air is realized in unique redundancycombination of a mechanical valve and electronic controlled proportional valvefor safe and reliable operation.
Motors with kind of Ex-protection EEx p can operate in combination with theEEx p system F-361.C4 in Ex areas 1 and 2 (according to ATEX 95).
Combined with an enclosure which is suitable for use with overpressure theEx protection class
II 2G Ex px IIC T4
according to EN 60079-2 can be obtained.
-
7/22/2019 4_Purge Unit Technical Documentation
3/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 3 of 34
Before commissioning take note of the following points:
1. Clean the connected air pipe or tubing system of the installation plant toensure that the supplied air tube is free of dirt or small parts which will causea malfunction of the purging system, if no air filter is used.
2. The internal volume of the motor enclosure must be purged with non-explosivecompressed air, to reduce a possible explosive gas concentrationto safe limits. The overpressure has to be monitored permanent.
3. After purging the motor enclosure, an overpressure must be maintained insidethe motor to prevent ambient air which can contain explosive gas.
If the pressure drops under the reference value an alarm signal is given and themotor has to be switched off.
The EEx p System F-361.C4 comprises the following components:
control cabinet ST-200C
consists of: main air valve for pressure supply, pressure reducer with gauge,purge valve, proportional valve for operating pressure (leakagecompensation), adjustment valves for purge- and leakage volume,measure points (to acquire leakage volume and the pressureinside the motor enclosure), Ex d box GUB 02,Ex d box GUB, Ex e main switch, control unit F-351.P.
Potential free signals:
PURGING IN PROGRESS START/STOP
With mounted F-369 additional signals:
PRE-ALARM MIN PRE-ALARM MAX FAILURE
The control cabinet ST-200C monitors the air flow of the outlet valve and thepressure inside the motor enclosure. Simultaneous the control automatic works inaccordance with EN 60079-2 and ATEX 94/9.
This monitoring system is a highly secure and redundancy controlling unitcertified according toEN954-1(security class Cat. 3, see certificate TV 02ATEX 1801).
Outlet valve VA-100-3HM
The outlet valve with integrated spark arrestor / particle barrier opens duringthe purging sequence to ensure the purging of the motor enclosure according
-
7/22/2019 4_Purge Unit Technical Documentation
4/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 4 of 34
to EN 60079-2. The outlet valve itself can be mounted in any position. Thevalve closes complete after the purging sequence.The volume flow sensor at the outlet of the valve maintains a correct purgevolume measuring in comparison to systems measuring only the air inletvolume.
Test certificate
The motor system is provided with a test certificate 2.2 according EN 10204.
Mounting example
2
Ex p motor10
1
89
543
7
B AP
6
1: control cabinet ST-200C2: two measure lines motor inside pressure3 and 4: measure points air volume
5: pilot line to outlet valve6: outlet valve VA-100-3HM7: measure points motor inside pressure8: compressed air connector for supply9: compressed air connector to motor10: motor enclosure
-
7/22/2019 4_Purge Unit Technical Documentation
5/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 5 of 34
Dimensions of ST-200C
600
370
air inletcable plate
air outlet
p min A B
p
50
100
17030
640
100
955
earthing point (M8)
12
1805.0
2750.5
600
800
air comp. IP55
173
277
25
25
Outlet valve VA-100-3HM
450
4 x 18 mmhole arrangement according to DIN 2527NW 100 PN 16
100.
0 200.0
50.0450
PAB
300.0
300.0
67
.5
180.0
-
7/22/2019 4_Purge Unit Technical Documentation
6/34
-
7/22/2019 4_Purge Unit Technical Documentation
7/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 7 of 34
Internal view control cabinet ST-200C
4
1
0 6
2
3
5
1
2
3
4
5
78
9
10
1112
13
14151617
18
19
21
PE
4 6
53
4N
21
L1
53
6
PE
K3
F1
N
PE
20
23 22
K2
7
7
8
8
9
9
10
10
11
12
11
12
F-369
PE PE
6
1: control unit F-351.P 18: adjustment valve purge volume2: protection cabinet 19: test conn. pilot pressure outlet valve3: EEx d enclosure GUB 0 20: main switch
4: EEx d enclosure GUB 02 21: connector outlet valve5: Type code 22: connectors diff. pressure6: earthing terminal rail 23: connectors motor inside pressure7: cable plate8: test connector diff. pressure9: air outlet to motor10: main air connector11: main air valve12: grill panel13: pressure reducer14: adjustment valve leakage volume
15: pressure gauge16: prop. valve17: purge valve
-
7/22/2019 4_Purge Unit Technical Documentation
8/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 8 of 34
Technical data
1: Control unit F-351.PEx-protection class: II2G Ex mb e ia [px] [ia] IIC T4Protection class: IP 65
Temperature range: -30C ... +60CCertified by: TV02 ATEX 1801Security class: AK4, acc. to EN 954-1, cat. 3
Resolution of pressure sensors: 0,05 mbar (5 Pa)Pressure switch Purge (p): 0,3 15 mbar (30 1500 Pa)Pressure switch Min: 0,8 25 mbar (80 2500 Pa)Pressure switch Max: 10 - 25 mbar (1000 2500 Pa)
2: Protection cabinetType: ST-200CMaterial: sheet steel, 2 mm
Colour: RAL 7030Protection class: IP 55
All inside mounted modules with IP rating: IP 65
3: Control- and junction box GUB 0Ex-protection class: II 2GD EEx d IIC T6Protection class: max. IP 66Temperature range: -20C ... +55CCertified by: CESI 01 ATEX 036Bore holes: 3 x NPT, 2 x NPT
Material: Aluminium4: Control- and junction box GUB 02
Ex-protection class: II 2GD EEx d IIC T6Protection class: max. IP 66Temperature range: -20C ... +55CCertified by: CESI 01 ATEX 036Bore holes: 5 x M20, 5 x M25Material: Aluminium
Ex d cable glands FL1Ex-protection class: II 2 GD EEx d IIC T4
Temperature range: -20C ... +80CCertified by: CESI 00 ATEX 052Cable diameter: 6 12 mm (M25: 12 17 mm)
For customer: 1 x M20 and 1 x M25
5: Type plate Identification of the systemwith serial number and project data
Material: stainless steel
6: earthing terminal rail
-
7/22/2019 4_Purge Unit Technical Documentation
9/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 9 of 34
7: Cable plateW x H x D: 160 x 120 x 10 mmCut out in cabinet: 80 x 60 mm
8: Test connector
Differential pressure Dim. for air volumeConnector: quick disconnect coupling DN 5Material: brass
9: Air connector to motor: flange DIN 2566, C50 x 60,3ND 10-16, raw material 1.4571
10: Compressed air inlet: flange ASME B16.5 150 lbs RF 3raw material 1.4571
11: Ball valve with hand lever main air valve
Material: stainless steel
12: Breather for air compensationMaterial: stainless steel
13: Pressure regulatorInlet pressure: max. 40 barOutlet pressure: 0 6 barmax adjustment: 4 bar, before purge sequence startsMaterial: brass
14: Adjustment valve Leakage volumeAdjustment range with control valve: max. 85 Nm/h, at adjusted 3 barMaterial: stainless steel
15: Pressure gauge, glycerine filledIndication range: 0 6 barMaterial: 1.4404 (316 L)
16: Control valve Operating pressureEx-protection class: II 2 G EEx m II T4Ambient temperature: -30C ... +60CCertified by: PTB 00 ATEX 2129 XOperating range: see leakage diagramMaterial: brass
17: Purge valveEx-protection class: II 2 G EEx em II T4Temperature range: -30C ... +60CCertified by: PTB No. 00 ATEX 2129 XOperating range: max. 450 Nm/hMaterial: brass
18: Ball valve with rotating lever Adjustment purge volumeAdjustment range, if pre-pressure 3 bar: min. 200 450 Nm/hMaterial: brass, nickel-plated
-
7/22/2019 4_Purge Unit Technical Documentation
10/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 10 of 34
19: Test connector Pilot pressure outlet valveConnector: quick disconnect coupling DN 5Pilot pressure: approx. 1 barMaterial: brass
20: Main switchEx-protection class: II 2 G EEx ed IIC T6Temperature range: -20C ... +60CProtection class: max. IP66Certified by: PTB 01 ATEX 1105
21: Connector outlet valve Pilot line outlet valveConnection: male adapter union, tube 10 mmMaterial: stainless steel 1.4571
22: Connectors diff. pressure Differential pressure for air flowConnection: male adapter union, tube 10 mmMaterial: stainless steel 1.4571
23: Connector motor pressure motor enclosure overpressureConnection: male adapter union, tube 10 mmMaterial: stainless steel 1.4571
Electrical data
Power supply Purge Operate
230 V / 60 Hz 150 mA 125 mA
Temperature range F-361.C4
Tamb: -20C ... +55C
Weight
Control cabinet ST-200C: 88 kgOutlet valve VA-100-3H: 27 kg
Minimum requirements for air pressure
Minimum working pressure air volume: 200 450 m3/h at 3 bar / 20C
Inert gas quality acc. to DIN ISO 8573-1:
Particles Class 5/3 Particle size 40 m Particle density 5 mg/mWater Class 4 Dew point +3C Water content 6000 mg/ mOil Class 3 Oil concentration 1 mg/m
If the air quality is not guaranteed special filters can be delivered on inquiry.
-
7/22/2019 4_Purge Unit Technical Documentation
11/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 11 of 34
Basicfunctional description F-351, execution P
For a detailed description see manual F-350.
PE L NIN
+ -(DC) +
OUTL
- (DC)
N PE VALVEK1
INFO
OK
MENU
cable glands
3-line Display
pneumatic connectorsdifferential pressure, enclosure overpressure
terminal rail
OK/INFO button and Wheel Shuttle
safety glas
1(-)3
2(+)
1 2 3 4 5 6 7 8 9 10
PneumaticconnectorsInstalled with tubes to the cabinet wallDigital display3-line display with each 12 charactars showing the statusCable glands2 x M20, 2 x M16 for power supply, valve and signalsTerminal rail
Wire cross section max. 4 mmOK/INFO buttonSwitches the display over between measuring data and info menu. Confirmation ofadjusted values and parametersWheel shuttleRotary switch, activated if in action. Switches between different menues and sub-menues.Safety glasAcrylic glass with magnification of the display
-
7/22/2019 4_Purge Unit Technical Documentation
12/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 12 of 34
Menu
planF-351.P
-
7/22/2019 4_Purge Unit Technical Documentation
13/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 13 of 34
Structure and Function
In conjunction with an enclosure (motor enclosure, junction box), the EEx-p systemF-361.C4 provides a pressurized motor that is in compliance with EN 60079-2.For this purpose, it has all the facilities and sensors needed to monitor the necessary
purging phase and then to monitor and maintain an overpressure within the EEx-penclosure (motor cabinet).
1 Structure
The controlling system consists mainly of two components which must be installedseparately:
- controlling cabinet ST-200C, with built-in piping ,valves, electronic and- the outlet valve VA-100-3H.
The controller F-351.P itself monitors and regulates the overpressure in theenclosure, while the digital/proportional valves doses the air quantity needed toachieve the pressurized apparatus.
2 General Functional Description
After a functional test and start-up, the controller F-351.P in the control cabinetST-200C monitors the flowrate of the compressed air or inert gas during the initial
purging process, and then monitors and regulates the internal pressure of the EEx-penclosure with regard to the surrounding atmosphere during normal operation.
Display
In three lines of 12 characters each, the digital display shows the enclosuresinternal pressure during normal operation, and the remaining purging time inminutes and seconds during the initial purging process. During normal operation,you can call up further information by pressing the button "OK / Info". Faultswhich are detected during the self-check are shown here with a number.
OK-button
The button on the left side (OK / INFO) is used in normal operation to call upthe stored parameters Enclosure Pressure, Purging Time, Function ofRelay 3, Function of Relay 4, Switchpoint of Purge Start, Switchpoint ofMinimum Pressure, Switchpoint of Overpressure and Regulation. During theparametrization, this button is used to select and confirm the variousparameters.
-
7/22/2019 4_Purge Unit Technical Documentation
14/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 14 of 34
Rotary switch
The right field (Menu) permits access to the Wheel Shuttlewith a tool (e.g. ascrewdriver) for parametrizing the controller. With this Wheel Shuttle, you canstart the parametrization and set the individual parameter values.
Screw terminal in the control unit F-351.P
In the lower part of the cover (see page 1), the terminal assignment of thecontroller is shown. Terminals 1 to 3 are inputs; they provide electrical power tothe controller. Contact K1 at the terminals 4 and 5 is potentialfree and freeprogrammable. The operating release is given at the terminals 6 and 7. At theterminal 8,9 and 10 the proportional valve for leakage compensation isconnected.
Immediately after the compressed air supply is opened and the main voltage isapplied, the internal self-check of the controller begins automatically. Any faultoccurring during the self-check sequence is indicated by
An explanation of the fault numbers (XX) is given in the manual, section 3.5 Faultsand Troubleshooting, Table 1: Faults detected during the self-check.
If the self-check is carried out successfully, the initial purging of the enclosurecommences, ending when at least five times the enclosure volume has beencirculated. The purging process is indicated by the message
in the display. All the time, the remaining purging time is counted down to 00 min and00 seconds.
After the end of the purging sequence, the Non-Ex units in the enclosure areswitched on. The overpressure in the enclosure then constantly monitored foradherence to the setpoint value (factory setting: 2.0 mbar) and also for transgressingof the Min value (factory setting: 0.8 mbar) and exceeding of the Max value (factorysetting: 25.0 mbar). Normal operation is indicated by the message
in the display.
FAULTXX
REMAININGPURGE TIME:XX MIN XX SEC
ENCLOSUREPRESSURE:XXX.X MBAR
-
7/22/2019 4_Purge Unit Technical Documentation
15/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 15 of 34
Functional sequence of the Ex px control system
For a reliable operation of the Ex p control system different states have to be fulfilled.
State 1: Minimum conditions to start purge
adjustment valve"leakage air compensation/operating pressure"
adjustment valve"purge volume"
main valve
ST-X00
operating pressuremin 4,2 max 7,0 barg pressure regulatorwith gauge
prop. valve
purge valve
p = 3,5 ... max. 4 bar
motor enclosure
control unit F-351.P
0,8 ... 10 mbar
minp
P
outlet valveVA-100-3H
A
P
B
P
measuring pointdifferential pressure13
15
1716
10 12
14
1
19
8
22 21
2
1. Overpressure in the motor enclosure has to be > 50 Pa against atmosphere.2. The max. overpressure (adjusted in F-351) not exceeded.3. Purge flow V1is smaller than the adjusted Min. value in the F-351.4. Purge time incomplete.
If all four conditions are fulfilled, hence it follows the state Minimum conditions tostart purge.
While the power supply is switched off and the adjustment of the secondary pressure(pressure after the pressure regulator Pos. 11) is p2= 3,5 4 bar,the operate pressure/leakage compensation is adjusted by the leakage valve(Pos. 12). Herewith the first condition overpressure > 50 Pa is fulfilled.
The value is in a range of 80 Pa and 1000 Pa (it depends on the construction of themotor enclosure). So the second condition max. overpressure not exceeded is alsofulfilled. The purge flow is smaller than the adjusted minimum,while the purge valve is closed and in the outlet valve (VA-100-3H) no air flowcan be measured. The third condition is fulfilled. The fourth condition is fulfilled, whilethe system is not powered.
Signal conditions at the terminals in the connection box GUB 02 at this time
Signal Relay Terminal ConditionPurging in progress F-351.P/K1 11 12 Contact openedStart/Stop K2 + K3 9 10 Contact opened
Pre-alarm MIN F-369/K2 7 8 Contact openedPre-alarm MAX F-369/K3 5 6 Contact openedFailure F-369/K4 3 4 Contact opened
-
7/22/2019 4_Purge Unit Technical Documentation
16/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 16 of 34
State 2: Purging
ST-X00 pmin
BA
P P P
p = 3,0 bar
0,8 ... 25mbar10 12
14
15
13
8
16
19
17
1
22 21
2
main va lve pressure regulatorwith gauge
adjustment valve"leakage air compensation/operating pressure"
prop. valve
purge valve adjustment valve"purge volume"
outlet valveVA-100-3H
motor enclosure
measuring pointdifferential pressure
control unit F-351.P
operating pressuremin 4,2 max 7,0 barg
1. Overpressure in the motor enclosure has to be > 50 Pa against atmosphere.2. The max. overpressure (adjusted in F-351) not exceeded.3. Purge flow V1is higher than the adjusted Min. value in the F-351.4. Purge time incomplete.
If all four conditions are fulfilled, hence it follows the state Purging.
Condition 1 and 2 are fulfilled from state 1. If the control unit is powered now, thepurge valve (Pos. 15) and the prop. valve (Pos. 14) are open.Also the outlet valve (VA-100-3H) opens. The compressed air streams through theEx p system and a part of it expands in the motor enclosure. A little overpressuresubsists in the motor enclosure. Through the opened outlet valve (VA-100-3H) thecompressed air streams in the environment.In the outlet valve a measuring point for pressure difference is installed.If the air volume at the end of the outlet valve is measured with an additional
instrument, the start point for the purging can be fixed by the measured air flow andthe differential pressure at this point of time.
The air flow is at this point of time higher than the adjusted value in the control unit.So the third condition is fulfilled. Hence it follows combined with the condition Purgetime incomplete the state Purging. The purge time starts.
Signal conditions at the terminals in the connection box GUB 02 at this time
Signal Relay Terminal ConditionPurging in progress F-351.P/K1 11 12 Contact closedStart/Stop K2 + K3 9 10 Contact openedPre-alarm MIN F-369/K2 7 8 Contact openedPre-alarm MAX F-369/K3 5 6 Contact openedFailure F-369/K4 3 4 Contact opened
-
7/22/2019 4_Purge Unit Technical Documentation
17/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 17 of 34
To prevent a false alarm, as a result of pressure oscillations through the motorhousing during the purging sequence, a drop-out time delay of ca. 5 sec isprogrammed in the control unit. This prevents a prompt reset of the purge time to thestart value. The purge time is stopped, if the adjusted diff. pressure is reached withinthe 5 sec, the purge time starts at the stopped time. Otherwise the purge time will be
resetted.
The required purging time depends on the setting of the purge volume (normally 10times the free volume of the motor cabinet) and the presetted inlet pressure at thepressure regulator (Pos.11).
State 3: Purging complete, power connected, leakage compensation
ST-X00
6 - 8 bar
3,5 ... max. 4 bar
0,8 ... 10 mbar
P
pmin
PP
A B
if operating pressure dropsthis valve is active
10 12
1413
15
8
16 17
19
22 21
1
main valve pressure regulatorwith gauge
adjustment valve"leakage air compensation/operating pressure"
prop. valve
purge valve adjustment valve"purge volume"
outlet valveVA-100-3H
motor enclosure
measuring pointdifferential pressure
control unit F-351.P
operating pressuremin 4,2 max 7,0 barg
1. Overpressure in the motor enclosure has to be > 50 Pa against atmosphere.2. The max. overpressure (adjusted in F-351) not exceeded.3. Purge time complete.
If all three conditions are fulfilled, hence it follows the state Purging complete, .
After the regular purging the Ex [p] system switches automatically the power.The purge valve (Pos. 15) is dead and closes. Likewise the outlet valve is closing.Leakage compensation (operating overpressure) in the motor enclosure is performedby the adjustment valve leakage compensation (Pos. 12) and if needed with theproportional valve (Pos. 14). The start sequence of the motor can be initiated.
Signal conditions at the terminals in the connection box GUB 02 at this time
Signal Relay Terminal ConditionPurging in progress F-351.P/K1 11 12 Contact openedStart/Stop K2 + K3 9 10 Contact closedPre-alarm MIN F-369/K2 7 8 Contact openedPre-alarm MAX F-369/K3 5 6 Contact openedFailure F-369/K4 3 4 Contact opened
-
7/22/2019 4_Purge Unit Technical Documentation
18/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 18 of 34
During the operating time of the motor enclosure can be leaking. This is corrected bythe proportional valve (Pos. 15). The deviation control is supervised by the controlunit (Pos. 1) to the adjusted operating pressure. The operating pressure can also bereadjusted with the manual valve (Pos. 13).
The overpressure in the motor enclosure is supervised by the pressure sensors"Min"and "Max"in the control unit F-351.P. Drops the overpressure below theadjusted value of "Min", or increases the overpressure over the adjusted value of"Max", the operating release (PURGE READY) is cancelled. The signalFAILURE is given.
If the motor enclosure overpressure increases over the value of"Max", against thereference pressure (ambient air), the outlet valve opens in addition to the cancelledoperating release. After the decrease of the overpressure below the adjusted valueof "Max" the operating release is given again without starting a new purgingsequence.
-
7/22/2019 4_Purge Unit Technical Documentation
19/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 19 of 34
Ex d IIC control- and junction box GUB 02
In this Ex d box are all needed relays and terminals mounted, which are required forwiring the electrical system. The relays are wired together that the signalSTART/STOP is built. The connection for the power supply and signals are located
in this box . Terminals for the control signals PRE-ALARM MIN, PRE-ALARM MAXand FAILURE are located in this Ex d box.
N
PE
L1
K2 K3
3
4 8
75
6 12
11
10
9
21 3
N
F1 PE
4 8
7
6
5
12
11
10
9 PE
For the power supply a cable with a diameter of max. 17 mm can be installed, samefor signal cable. It has to be secured that the installed cable through the Ex d cablegland is accurate sealed, because of the direct wiring in the Ex d box. Not used bore
holes have to be closed with certified plugs.Do not connect Ex i circuits to these contacts
Terminal block
K2 K3
PE
L1 N
1 2
5
64
3 9
10
7
8
11
12
PEF1
N
5
64
3 9
10
7
8
PE11
12
Terminals for power feeder are suitable for cable size of 4 mm.
-
7/22/2019 4_Purge Unit Technical Documentation
20/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 20 of 34
Ex d IIC control- and junction box GUB 0
F-369
PE PE
In this box the opto-relay F-369 is mounted. The signals are wired in the Ex d boxGUB 02.
-
7/22/2019 4_Purge Unit Technical Documentation
21/34
-
7/22/2019 4_Purge Unit Technical Documentation
22/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 22 of 34
Type code
For the identification of the system a stainless steel plate is fixed at the enclosureof the control cabinet.
Leakage compensation diagram
To determine the approx. leakage of your purged motor enclosure during operationplease count the turnarounds of the adjustment valve leakage comp. (Pos.14) anduse this diagram.
.L.B.EX-GERTE
TV 02 ATEX 1801Operating voltage: 230 V
Motor Manufacturer: VEM
Project name:
Serial no.:
VAC/48-62 Hz VDC
Order no.: 45089428
Project no.:
Date of pass:
EEx-p System Type F-361.C4
Leakagecompensation F-361.C4
05
1015202530354045
505560657075808590
0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75 3,00 3,25
Turns for adjustment valve"leakage comp." (Pos.12)
Leakagein
Nm
3/h
bei 3 Bar Max.leakage compensation with proportional valvel
-
7/22/2019 4_Purge Unit Technical Documentation
23/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 23 of 34
Checklist and test certificate
Test certificate and checklist for motor systems
VEM Sachsenwerk GmbH
Pirnaer Landstrae 176D-01257 Dresden
Motor system: F-361.C4
Power supply: 230 V / 50/60 Hz
Date of pass:
Serial number:
Order number: 45089428
Code:
Job number: 27099
checked by E.L.B.
date:
name:
-
7/22/2019 4_Purge Unit Technical Documentation
24/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 24 of 34
Appendix A
Timing diagram purging sequence
T1: Switching on power supply and opening air pressure supply the control unit begins with a self test and the purgingsequence of the EEx p motor enclosure starts. With an air flow which is higher than the adjusted value min air flow andthe air flow is adequate the adjusted purge volume (min. 10-fold inner free motor volume), the motor enclosure is purged.
T2: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation(see chapter 5 of main manual). The Non- Ex units can be powered.
T3: Normal operation starts.
Timing diagram operating modus
T1: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation(see chapter 5 of main manual). The Non- Ex units can be powered.
T2: Normal operation starts. The internal enclosure overpressure is regulated to the setpoint value.
T3: The internal enclosure pressure rises.
T4: The increased overpressure is controlled down with the proportional valve.
T5: Normal operation begins.
-
7/22/2019 4_Purge Unit Technical Documentation
25/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 25 of 34
Timing diagram errors during purging sequence
T1: Switching on power supply and opening air pressure supply the control unit begins with a self test and the purgingsequence of the EEx p motor enclosure starts. With an air flow which is higher than the adjusted value min air flow andthe air flow is adequate the adjusted purge volume (min. 10-fold inner free motor volume), the motor enclosure is purged.
T2: During the purging sequence the internal overpressure increases to an excessively high value.The purge operation is aborted.
T3: During the purging sequence the minimum air volume flow falls. The purging sequence is resetted.
Timing diagram errors during the operating modus
T1: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation(see chapter 5 of main manual). The Non- Ex units can be powered.
T2: Normal operation starts. The internal enclosure overpressure is regulated to the setpoint value.
T3: The internal enclosure pressure drops. If the pressure value falls below the switchpoint Minimum pressure in relation tothe external pressure, the Non- Ex units are switched off.
T4: Renewed purge.
T5: Normal operation begins.
T6: The internal enclosure pressure rises. The increased internal enclosure pressure cannot controlled down.
T7: If the internal pressure value exceeds the switchpoint Overpressure, the Non- Ex units are switched off. The purgevalve is powered, so the outlet valve opens. The increased overpresse sinks to operation values.
T8: After the pressure decrease, normal operation begins without purging.
-
7/22/2019 4_Purge Unit Technical Documentation
26/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 26 of 34
Detail menu 1
OK
Francais(in compilation)
OK
English
German
OK
OK
Language ?
1
MENU
-
7/22/2019 4_Purge Unit Technical Documentation
27/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 27 of 34
Detail menu 2
Enterpurge time ?
OK
Enterpurge time00:10 min
Parameter range:00:10 ... 99:50 min
OK
preset parameter 00:10 min
OK
Confirmpurge timexx.xx min
2
-
7/22/2019 4_Purge Unit Technical Documentation
28/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 28 of 34
Detail menu 3
Switchpointmin pressure ?
OK
0.05/step
1 mbar/ step
OK
Parameter range: 0,8 - 25 mbar
preset parameter: 0,8
Confirmmin pressurexx.xx mbar
OK
OK
Switchpoint
min pressure xx.xx mbar
3
+
-
7/22/2019 4_Purge Unit Technical Documentation
29/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 29 of 34
Detail menu 4
Switchpointoverpressure ?
OK
1 mbar/ step
0.05/step
OK
Confirmoverpressurexx.xx mbar
OK
preset parameter: 25,0
Parameter range: 0,8 - 25 mbar
Switchpointoverpressurexx.xx mbar
4
+OK
-
7/22/2019 4_Purge Unit Technical Documentation
30/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 30 of 34
Detail menu 5
Switchpointpurge start ?
OK
Switchpointpurge startxx.xx mbar
1 mbar/ step
0.05/step
OK
Confirmswp.purging
xx.xx mbar
OK
preset parameter: 0,5
OK
Parameter range: 0,8 - 25 mbar updated flow (yy.yy mbar)
stored as purge start parameter (xx.xx mbar)set point = feedback value
ConfirmSwp. purging
yy.yy mbar
OK
Swp purgingxx.xx mbaryy.yy mbar
(set point)
(feedback value)
press for 3 sec
5
Standby/operate modus
during purging sequence and operationp > switchpoint p
OK
enclosure min
OK +
-
7/22/2019 4_Purge Unit Technical Documentation
31/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 31 of 34
Detail menu 6
Displaycontrast####____
OK
preset parameter: 5
Parameter range: 1 - 8
OK
Displaycontrast ?
6
-
7/22/2019 4_Purge Unit Technical Documentation
32/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 32 of 34
Detail menu 7
OK
OK
Function ofrelay K1 XXXXX
Input data- Isolation
Function of relay K1 ?
- System Fault- Fault 1 min
- Fault flash- Pre-al. MIN- Pre-al. MAX- Purging- Bypass
preset parameter: Purging
7
- Purge failure
-
7/22/2019 4_Purge Unit Technical Documentation
33/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
06.12.2008 page 33 of 34
Detail menu 8
PressureregulationXXXXX
OK
Pressureregulation ?
OK
- Two-position- pulsed- proportional
preset parameter: pulsed
Input data
8
-
7/22/2019 4_Purge Unit Technical Documentation
34/34
45089428 Description Ex-p System F-361.C4
nd./
Mod.
Detail menu 9
OK
Functionbypass ?
Enter
Password 5112
OK
Function Bypass / OFF
OK
OK
Function BypassON /
QuitBypass menue YES / NO
OK OK
9
QuitBypass menue YES / NO