37090f d321a-d324a d336a installation...

12
D321A-D324A/D336A EN Installation Guide Analog Detection Devices

Upload: vobao

Post on 09-Apr-2018

224 views

Category:

Documents


1 download

TRANSCRIPT

D321A-D324A/D336A

ENInstallation Guide

Analog DetectionDevices

Bosch | 12/04 | 37090F2

D321A-D324A/D336A | Installation Guide |

TrademarkWeatherban™ is a trademark of 3M Company.

NoticeThese instructions cover the installation of the D321A-D324A/D336A detection heads and bases in an analogsystem controlled by a D8024, D9024, or D10024Analog Fire Alarm Control Panel (FACP) using theadvanced digital transmission protocol.

Install, test, and maintain these devices according tothese instructions, NFPA 72, local codes, and theAuthority Having Jurisdiction (AHJ).

Follow the procedures in this guide to avoid personal injury and damage to equipment. Failure to follow these procedures can cause the device to not properly operate. Bosch is not responsible for improperly installed, tested, or maintained devices.

NFPA 72 requires a complete system-wide functional test be performed after modifying, repairing, upgrading, or adjusting the system’s components, hardware, wiring, programming, software, and firmware.

1.0 DescriptionIn an analog system, devices receive power andcommunicate with the FACP over the same circuit. TheBosch analog system uses two-piece detection devicescomprised of a detector base and an interchangeabledetector head.

The D321A Base (6-in. [15-cm] diameter) and theD336A Base (4-in. [10-cm] diameter) are compatiblewith the D8024, D9024, and D10024 Analog FACPs,the D322A Analog Heat Detector Head, the D323AAnalog Photoelectric Detector Head, and the D324AAnalog Ionization Smoke Detector Head.

The D321A and D336A can be installed in either aClass “A” (four-wire) or Class “B” (two-wire) analogpolling circuit. Both bases provide standard data in anddata out screw terminals and feature base securitylocking tabs to prevent tampering. The detector headsused with these bases are interchangeable and can beeasily removed for cleaning, servicing, or replacingwithout disconnecting the wiring.

The D322A provides property protection and is suitablefor use in high indoor ambient temperature, such askitchens, boiler rooms, or drying rooms. The D322Aalso accurately detects fast-flaming fires. Two LEDsflash each time the FACP polls the head (approximatelyonce every 18 sec) and latches on red when the head

goes into an alarm condition. Fixed temperatureactivation points for the D322A are programmable fromthe FACP. The default alarm threshold setting is +142°F(+61°C).

The D323A and D324A provide early warning fireprotection for life safety. The D323A is an analogphotoelectric detector head that senses dense smoketypically given off by plastic, foam, paper, wood, andother materials that tend to smolder. The D324A is ananalog ionization detector head suited for applicationsinvolving extreme humidity and temperature, andvibration. The D324A reacts best to small particulate-type smoke such as flare fires. This head also detectscertain invisible products such as flue gases.Additionally, the D323A and D324A detect fast-flamingfires.

Two LEDs on the D323A and D324A flash every timethe FACP polls the heads, approximately once every18 sec, and latch on red when the heads alarm.

2.0 Setting the Detector AddressEach analog detector head is assigned a specific addressthat is set by programming an EEPROM microchip. Itis not necessary to wire the devices to the FACP’spolling circuit in any particular order.

2.1 D5070 Analog Device Programmer

Use the D5070 Analog Device Programmer (Figure 1) to set the D322A, D323A, and D324A addresses before connecting them to the FACP’s polling circuit. Ensure the D5070’s battery is connected before programming.

Refer to Table 1 for a description of the D5070’sprogramming buttons.

Table 1: Programming Buttons

Button Color Description

Red Stores the shown addresses in the detector; reads the analog level.

(left)

Gray Powers on; automatically reads the detector’s address; advances the address by ten.

(right)

Gray Powers off; advances the address by one.

Trademark

3Bosch | 12/04 | 37090F

D321A-D324A/D336A | Installation Guide | 2.0 Setting the Address

2.1.2 Setting the Address Using the D5070 AnalogDevice Programmer

1. Place the detector head on the programmer, aligningthe head tabs with the programmer grooves.

2. Press the left gray button to power on the D5070.

A battery check message appears followed by thedevice’s address. Detectors that are not programmedread “Address 127.”

3. Set the required address by pressing the left andright gray buttons until the desired address isreached.

The display shows three red flashing dots if theaddress being programmed is different from thedevice’s current address.

4. When the desired address appears, press the redbutton to program that address.

The three red dots on the display go out.

2.1.3 Reading the Analog Value

1. Install the detector and power up the D5070 asdescribed in the preceding section.

2. Press the red button.

An “A” appears on the display followed by theanalog value. This value continuously updates for3 min or until the detector is turned off.

The D324A Ionization Detectors require a 60-sec stabilization period. During this time, do not attempt to read the ionization detector head analog value.

2.1.4 D5070 Display Messages

Table 2 identifies each message that might appear on theD5070.

Table 2: D5070 Display Messages

Message Description bat Battery check. Appears at power up and

when the battery is low. A low battery is effective for approximately 3000 address setting operations.

E0 The control panel does not recognize addresses beyond 126.

E1 Attempting to program an address with no detector connected.

E2 Cannot find the detector after power up. Replace the detector.

E3 Invalid detector response. Replace the detector.

E4 Cannot find the detector to program. E5 Detector read error. E6 Failure during the analog value reading.

Replace the detector.

1

32

1 - Twist on the sensor head here.2 - Programming buttons3 - Display

Figure 1: D5070 Analog Device Programmer

Bosch | 12/04 | 37090F4

D321A-D324A/D336A | Installation Guide |

3.0 Wiring the Detector Base

Before connecting or disconnecting a detector, remove all AC and battery power from the FACP. Failure to do so can cause personal injury or damage to the equipment.

Analog polling circuits connect to the FACP over two-wire cable. The bus protocol resists interference frommost types of electromagnetic interface (EMI) and radiofrequency (RF) generated noise. Under extremely noisyconditions, use twisted pair wire to reduce interference.Use shielded cable when EMI is a problem. Refer toTable 3 for shielded cable guidelines.

Table 3: Sensor Circuit Wiring Requirements

Nominal Capacitance 28 pF/ft (m) Typical Cable Resistance 3 Ω/1000 ft (305 m) Maximum Loop Resistance 25 Ω Recommended Maximum Loop Capacitance

Not to exceed 0.25µF

3.1 Guidelines

3.1.1 Data Circuit Length

Data circuit length is the distance over the circuit wirefrom the connection at the D9067 Polling CircuitModule to the most distant device and back to theD9067 Module. Data circuit length must include thedistance to any device connected to the circuit in aT-tap. Refer to Table 4 for polling circuit lengths andacceptable wire gauges.

Table 4: Polling Circuit Length and Wire Gauge

Polling Circuit Length Wire Gauge Up to 4000 ft (1219 m) 18 AWG (1.2 mm) 4000 ft to 7000 ft (1219 m to 2134 m)

16 AWG (1.5 mm)

3.1.2 Shielded Cable

If using shielded cable of good quality it should nothave a significant effect on the polling circuit length.Good quality shielded cable allows 0.25 µfd ofcapacitance, 1 mH of inductance, and 25 Ω resistance.

Connect the drain wire for shielded cable to the DataTerminal Block’s Terminal E inside the FACP (Figure 2).

An improperly grounded shielded cable can aggravate rather than eliminate noise problems. Reconnect the cable drain each time the cable is cut to install a device.

3.0 Wiring the Detector Base

1 - Data/Power positive (+) return2 - Data/Power common (-) return

3 - Earth ground for shield cable drain4 - Data/Power positive (+) out5 - Data/Power common (-) out6 - Data terminal block

7 - D9067 Polling Circuit Module

Figure 2: Terminal E Location

5Bosch | 12/04 | 37090F

3.2 Circuit ConfigurationPolling circuits connect to the FACP in a Class “A” or Class “B’ configuration. T-tapping is acceptable in theClass “B” circuits. Refer to NFPA 72 for the specific Class “A” and Class “B” circuit installation requirements.

3.2.1 Connecting the Class “A” (Style 6) Circuit

1. Install the D321A or D336A in the polling circuit by connecting the Data/Power (+) and the Data/Power (-)terminals (Figure 3).

The polling circuit’s Data/Power (+) wire connects to the (+) terminal on the data terminal block, located at thetop of the FACP. The polling circuit’s Data/Power (-) wire connects to the (-) terminal on the data terminalblock.

2. Connect the returning Data/Power wires to their respective terminal. Refer to Figure 3 and Figure 4 for details.

Figure 3: Detector Base Connections

1 - D321A Base 5 - Data/Power (-) In2 - D336A Base 6 - Data/Power (-) Out3 - Data/Power (+) In 7 - Align LED here4 - Data/Power (+) Out

1 23

1 2

4

5 6

7

1 23

5

4

6

7

1 - D321A Base 5 - Data/Power (-) Out

2 - Data/Power (+) In 6 - Align LED here3 - Data/Power (+) Out 7 - Data terminal block4 - Data/Power (-) In 8 - D9067 Polling Circuit Module

Figure 4: Class “A” (Style 6) Circuit Connections

1

1 2 1 2

+ - E + - LOOP1

+ - E + - LOOP2

2

1

2 3 3

44 5 5

6 6

7

8 8

D321A-D324A/D336A | Installation Guide | 3.0 Wiring the Detector Base

Bosch | 12/04 | 37090F6

D321A-D324A/D336A | Installation Guide |

3.2.2 Connecting the Class “B” (Style 4) Circuit

1. Install the D321A or D336A in the polling circuit by connecting the Data/Power (+) and the Data/Power (-)terminals (Figure 3 on page 5 and Figure 5).

The polling circuit’s Data/Power (+) wire connects to the (+) terminal on the data terminal block (at the top ofthe FACP). The polling circuit’s Data/Power (-) wire connects to the (-) terminal on the data terminal block(Figure 5).

2. Connect the (+) and (-) terminals on the data terminal block with the jumper wires as shown in Figure 5.

3.2.3 Remote AnnunciationTerminals 3 and 4 on the D321A and D336A serve as connection points for a remote LED (Figure 6).

1

1 2

23

4

5

6

1 - D321A Base 4 - To control panel power supply (24 VDC)

2 - Cathode (-) 5 - To Terminal 3 or Terminal 43 - Anode (+) 6 - Align LED here

Figure 6: Wiring for Remote Annunciation

3.0 Wiring the Detector Base

1 1

7

88

6

1 21 2

LOOP2

+ - E + -+ - E + - LOOP1

232

45

6

4

Figure 5: Class “B” (Style 4) Circuit Connections

1 - D321A Base 5 - Data/Power (-) Out2 - Data/Power (+) In 6 - Align LED here3 - Data/Power (+) Out 7 - Jumper wires4 - Data/Power (-) In 8 - D9067 Polling Circuit Module

7Bosch | 12/04 | 37090F

4.0 Mounting the D321A andD336A Bases

The D321A mounts on a 3-in. (8-cm) or 4-in. (10 cm)square back box or a 4-in. (10 cm) octagonal box. TheD336A mounts on a 3-in. (8-cm) octagonal box.

Mount the base to an appropriate back box using themounting holes. Refer to Figure 7 and Figure 8 fordetails.

Use 3M Weatherban™ #606 nonflammable sealingcompound to seal the field wiring openings in themounting back box to reduce stack effect.

According to NFPA 72, wall-mounted smoke and heat detectors must be at least 4 in.(10 cm) and no more than 12 in. (30 cm) below the ceiling.

D321A-D324A/D336A | Installation Guide | 4.0 Mounting the D321A and D336A Bases

1

1

4

3

2

5

3

1 - D321A Base2 - Remove knockouts (2)3 - Align LED here

4 - 4-in. (10-cm) square back box5 - 4-in. (10-cm) octagonal back box

Figure 7: Mounting the D321A Base

1

1 2

3

2

1 - D336A Base2 - Align LED here3 - 3-in (8-cm) octagonal back box

Figure 8: Mounting the D336A Base

Bosch | 12/04 | 37090F8

D321A-D324A/D336A | Installation Guide |

5.0 Base Security TabWhen you activate the base security tab you prevent anunauthorized detector from being removed.

1. Position the detector head so the bottom of thedetector head is facing up (Figure 9).

2. Break the tab using a small flathead screwdriver,allowing the base security tab to remain elevated toprevent the removal of the detector head.

To deactivate the base security tab so the detector hadcan be removed from the base:

1. Insert a small flathead screwdriver in the hole onthe outer rim of the detector head (Figure 10).

2. Rotate the detector head counterclockwise enoughto clear the base security tab while pushing down onthe tab.

3. Remove the detector head.

While pushing down on the base security tab only enough force to remove the detector head.

6.0 Testing the Detector HeadTest detection devices immediately after installation.Test smoke detectors according to Chapter 7 of NFPA72, or more often as required by local code.

A Smoke Test is the approved testing method for theD323A and the D324A. Use a D1002 Smoke Test Poleto perform a Smoke Test on the D323A and D324A.

NFPA regulations require a Calibration Test on thedetector. The D1002 does not meet NFPA requirementsfor a Calibration Test, but it does provide a simpleFunctional Test. For NFPA requirements, use the FACPas a calibrated testing device.

Test the D322A with a controlled heat source, not an open flame.

5.0 Base Security Tab

12

3

4

56

1 - Typical D322A, D323A, and D324A bottom view2 - Base security lock release access hole

3 - Small, flathead screwdriver4 - Break off tab to implement security feature5 - Base security locking tab6 - Align LED here

Figure 9: Activating the Base Security Tab3

1

2

1 - Detector head2 - Base security lock release access hole3 - Small, flathead screwdriver

Figure 10: Deactivating the Base Security Tab

9Bosch | 12/04 | 37090F

7.0 SpecificationsTable 5: D321A and D336A Base Specifications

Operating Voltage 17 VDC to 41 VDC

Nominal Supply Voltage 24 VDC

Standby Current Refer to the specific detector head.

Polling Current Refer to the specific detector head.

Alarm Current Refer to the specific detector head.

Operating Temperature +32° F to +120° F (0° C to +49° C

Maximum Humidity 95% RH-non condensing at +104° F (+40° C)

Listed Detector Spacing 30 ft (9 m) on a smooth ceiling

Dimensions (H x D) 0.375 in. (1 cm) x 6 in. (15 cm)

Weight 2.3 oz. (65.2 g)

Color Ivory ACS

Table 6: Detector Head Specifications

D322A D323A D324A Operating Voltage 17 VDC to 41 VDC 17 VDC to 41 VDC 17 VDC to 41 VDC Nominal Supply Voltage 24 VDC 24 VDC 24 VDC Standby Current 390 µA (typical) 390 µA (typical) 390 µA (typical) Polling Current 22 mA ± 20% 22 mA ± 20% 22 mA ± 20% Alarm Current 8 mA* 8 mA* 8 mA* Operating Temperature +32° F to +120° F

(0° C to +49° C) +32° F to +120° F (0° C to +49° C)

+32° F to +120° F (0° C to +49° C)

Alarm Threshold Range (adjustable by the FACP)

+136°F to +149° (+58° C to +65° C)

N/A N/A

Default Pre-alarm Threshold

+113° F (+45° C) N/A N/A

Default Alarm Threshold +142° F (+61° C) N/A N/A Maximum Humidity 95% RH-non condensing

at +104°F (+40°C) 95% RH-non condensing at +104°F (+40°C)

95% RH-non condensing at +104°F (+40°C)

Listed Detector Spacing Refer to NFPA 72, Appendix B.

Refer to NFPA 72, Appendix B.

Refer to NFPA 72, Appendix B.

Dimensions (H x D) with Base

2 in. (4 cm) x 4 in. (10 cm) 1 in. (5 cm) x 4 in. (10 cm) 3 in. (7 cm) x 4 in. (10 cm)

Weight 3 oz. (91 g) without base; 5.5 oz. (156 g) with base

3 oz. (91 g) without base; 5.5 oz. (156 g) with base

3 oz. (91 g) without base; 5.5 oz. (156 g) with base

Color Ivory ACS Ivory ACS Ivory ACS * 25 mA maximum. The control panel latches the LED onto the first four devices. Add 8 mA for remote LED.

D321A-D324A/D336A | Installation Guide | 7.0 Specifications

Bosch | 12/04 | 37090F10

D321A-D324A/D336A | Installation Guide | Notes

Notes

11Bosch | 12/04 | 37090F

D321A-D324A/D336A | Installation Guide | Notes

Notes

Bosch130 Perinton ParkwayFairport, NY 14450-9199 USACustomer Service: (800) 289-0096Technical Support: (888) 886-6189

© 2004 Bosch37090F