34786407-8-shortcircuit-iec
TRANSCRIPT
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Short-Circuit AnalysisIEC Standard
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 2
CORTO CIRCUITO
Estándar de ANSI/IEEE & IEC.
Análisis de fallas transitorias (IEC 61363).
Efecto de Arco (NFPA 70E-2000)
Integrado con coordinación de dispositivos de protección.
Evaluación automática de dispositivos.
Características principales:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 3
Purpose of Short-Circuit Studies• A Short-Circuit Study can be used to determine
any or all of the following:
– Verify protective device close and latch capability
– Verify protective device interrupting capability
– Protect equipment from large mechanical forces (maximum fault kA)
– I2t protection for equipment (thermal stress)
– Selecting ratings or settings for relay coordination
Types of Short-Circuit Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 4
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 5
Types of SC Faults•Three-Phase Ungrounded Fault•Three-Phase Grounded Fault•Phase to Phase Ungrounded Fault•Phase to Phase Grounded Fault•Phase to Ground Fault
Fault Current
•IL-G can range in utility systems from a few percent to
possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all faults).
•In industrial systems the situation IL-G > I3-phase is rare.
Typically IL-G .87 * I3-phase
•In an industrial system, the three-phase fault condition is frequently the only one considered, since this type of fault generally results in Maximum current.
Types of Short-Circuit Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 6
)tSin(Vmv(t)
i(t)v(t)
Short-Circuit Phenomenon
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 7
Offset) (DC
TransientState Steady
t) - sin(
Z
Vm ) - tsin(
Z
Vmi(t)
(1) ) t Sin(Vmdt
di L Riv(t)
LR
-e
expression following theyields 1equation Solving
i(t)v(t)
DC Current
AC Current (Symmetrical) with No AC Decay
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 8
AC Fault Current Including the DC Offset (No AC Decay)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 9
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 10
Machine Reactance ( λ = L I )
AC Decay Current
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 11
Fault Current Including AC & DC Decay
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 12
IEC Short-Circuit Calculation (IEC 909)
• Initial Symmetrical Short-Circuit Current (I"k)
• Peak Short-Circuit Current (ip)
• Symmetrical Short-Circuit Breaking Current (Ib)
• Steady-State Short-Circuit Current (Ik)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 13
IEC Short-Circuit Calculation Method
• Ik” = Equivalent V @ fault location divided by equivalent Z
• Equivalent V is based bus nominal kV and c factor
• XFMR and machine Z adjusted based on cmax, component Z & operating conditions
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 14
Transformer Z Adjustment
• KT -- Network XFMR
• KS,KSO – Unit XFMR for faults on system side
• KT,S,KT,SO – Unit XFMR for faults in auxiliary system, not between Gen & XFMR
• K=1 – Unit XFMR for faults between Gen & XFMR
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 15
Syn Machine Z Adjustment
• KG – Synchronous machine w/o unit XFMR
• KS,KSO – With unit XFMR for faults on system side
• KG,S,KG,SO – With unit XFMR for faults in auxiliary system, including points between Gen & XFMR
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 16
Types of Short-Circuits
• Near-To-Generator Short-Circuit
– This is a short-circuit condition to which at least one synchronous machine contributes a prospective initial short-circuit current which is more than twice the generator’s rated current, or a short-circuit condition to which synchronous and asynchronous motors contribute more than 5% of the initial symmetrical short-circuit current ( I"k) without motors.
Near-To-Generator Short-Circuit
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 17
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 18
Types of Short-Circuits
• Far-From-Generator Short-Circuit
– This is a short-circuit condition during which the
magnitude of the symmetrical ac component of
available short-circuit current remains essentially
constant.
Far-From-Generator Short-Circuit
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 19
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 20
Factors Used in If Calc
• κ – calc ip based on Ik”
• μ – calc ib for near-to-gen & not meshed network
• q – calc induction machine ib for near-to-gen & not meshed network
• Equation (75) of Std 60909-0, adjusting Ik for near-to-gen & meshed network
• λmin & λmax – calc ik
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 21
IEC Short-Circuit Study Case
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 22
Types of Short-Circuits
• Maximum voltage factor is used
• Minimum impedance is used (all negative
tolerances are applied and minimum
resistance temperature is considered)
When these options are selected
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 23
Types of Short-Circuits
• Minimum voltage factor is used
• Maximum impedance is used (all positive
tolerances are applied and maximum
resistance temperature is considered)
When this option is selected
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 24
Voltage Factor (c)
• Ratio between equivalent voltage &
nominal voltage
• Required to account for:
• Variations due to time & place
• Transformer taps
• Static loads & capacitances
• Generator & motor subtransient behavior
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 25
Calculation Method
• Breaking kA is more conservative if the option No Motor Decay is selected
IEC SC 909 Calculation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 26
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 27
Device Duty Comparison
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 28
Mesh & Non-Mesh If
• ETAP automatically determines mesh & non-meshed contributions according to individual contributions
• IEC Short Circuit Mesh Determination Method – 0, 1, or 2 (default)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 29
L-G FaultsL-G Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 30
Symmetrical Components
L-G Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 31
Sequence Networks
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 32
0
ZZZ
V3I
I3I
021
efaultPrf
af 0
g Zif
L-G Fault Sequence Network Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 33
21
efaultPrf
aa
ZZ
V3I
II12
L-L Fault Sequence Network Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 34
0
ZZZZ
Z
VI
I0III
20
201
efaultPrf
aaaa 012
g Zif
L-L-G Fault Sequence Network Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 35
Transformer Zero Sequence Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 36
grounded.
solidly areer transformConnected Y/
or Generators if case thebemay This
I
: then trueare conditions thisIf
&
: ifgreater
becan faultsG -L case. severemost
theisfault phase-3 aGenerally
1f3
1021
fI
ZZZZ
Solid Grounded Devices and L-G Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 37
Zero Sequence Model
• Branch susceptances and static loads including capacitors will be considered when this option is checked
• Recommended by IEC for systems with isolated neutral, resonant earthed neutrals & earthed neutrals with earth fault factor > 1.4
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 38
Complete reports that include individual branch contributions for:
•L-G Faults
•L-L-G Faults
•L-L Faults
One-line diagram displayed results that include:
•L-G/L-L-G/L-L fault current contributions
•Sequence voltage and currents
•Phase Voltages
Unbalanced Faults Display & Reports
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 39
Total Fault Current Waveform
Transient Fault Current Calculation (IEC 61363)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 40
Percent DC Current Waveform
Transient Fault Current Calculation (IEC 61363)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 41
AC Component of Fault Current Waveform
Transient Fault Current Calculation (IEC 61363)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 42
Top Envelope of Fault Current Waveform
Transient Fault Current Calculation (IEC 61363)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 43
Top Envelope of Fault Current Waveform
Transient Fault Current Calculation (IEC 61363)
IEC Transient Fault Current Calculation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 44
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 45
Complete reports that include individual branch contributions for:
•L-G Faults
•L-L-G Faults
•L-L Faults
One-line diagram displayed results that include:
•L-G/L-L-G/L-L fault current contributions
•Sequence voltage and currents
•Phase Voltages
Unbalanced Faults Display & Reports
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 46
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 47
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 48
TEMA 2
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Protective Device Coordination
ETAP Star
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 50
ETAP START PROTECCION Y COORDINACION
Curvas para más de 75,000 dispositivos.
Actualización automática de Corriente de Corto Circuito.
Coordinación tiempo-corriente de dispositivos.
Auto-coordinación de dispositivos.
Integrados a los diagramas unifilares.
Rastreo o cálculos en diferentes tiempos.
Características principales:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 51
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 52
Agenda
• Concepts & Applications
• Star Overview
• Features & Capabilities
• Protective Device Type
• TCC Curves
• STAR Short-circuit
• PD Sequence of Operation
• Normalized TCC curves
• Device Libraries
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 53
Definition
• Overcurrent Coordination
– A systematic study of current responsive devices in an electrical power system.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 54
Objective
• To determine the ratings and settings of fuses, breakers, relay, etc.
• To isolate the fault or overloads.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 55
Criteria
• Economics
• Available Measures of Fault
• Operating Practices
• Previous Experience
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 56
Design
• Open only PD nearest (upstream) of the fault or overload
• Provide satisfactory protection for overloads
• Interrupt SC as rapidly (instantaneously) as possible
• Comply with all applicable standards and codes
• Plot the Time Current Characteristics of different PDs
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 57
Analysis
When:
• New electrical systems
• Plant electrical system expansion/retrofits
• Coordination failure in an existing plant
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 58
Spectrum Of Currents
• Load Current
– Up to 100% of full-load
– 115-125% (mild overload)
• Overcurrent
– Abnormal loading condition (Locked-Rotor)
• Fault Current
– Fault condition
– Ten times the full-load current and higher
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 59
Protection
• Prevent injury to personnel
• Minimize damage to components
– Quickly isolate the affected portion of the system
– Minimize the magnitude of available short-circuit
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 60
Coordination
• Limit the extent and duration of service interruption
• Selective fault isolation
• Provide alternate circuits
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 61
Coordination
t
I
C B A
C
D
D B
A
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 62
Protection vs. Coordination
• Coordination is not an exact science
• Compromise between protection and coordination
– Reliability
– Speed
– Performance
– Economics
– Simplicity
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 63
Required Data• One-line diagrams (Relay diagrams)
• Power Grid Settings
• Generator Data
• Transformer Data– Transformer kVA, impedance, and connection
Motor Data
• Load Data
• Fault Currents
• Cable / Conductor Data
• Bus / Switchgear Data
• Instrument Transformer Data (CT, PT)
• Protective Device (PD) Data– Manufacturer and type of protective devices (PDs)
– One-line diagrams (Relay diagrams)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 64
Study Procedure
• Prepare an accurate one-line diagram (relay diagrams)
• Obtain the available system current spectrum (operating load, overloads, fault kA)
• Determine the equipment protection guidelines
• Select the appropriate devices / settings
• Plot the fixed points (damage curves, …)
• Obtain / plot the device characteristics curves
• Analyze the results
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 65
Time Current Characteristics
• TCC Curve / Plot / Graphs
• 4.5 x 5-cycle log-log graph
• X-axis: Current (0.5 – 10,000 amperes)
• Y-axis: Time (.01 – 1000 seconds)
• Current Scaling (…x1, x10, x100, x100…)
• Voltage Scaling (plot kV reference)
• Use ETAP Star Auto-Scale
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 66
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 67
TCC Scaling Example
• Situation:
– A scaling factor of 10 @ 4.16 kV is selected for TCC curve plots.
• Question
– What are the scaling factors to plot the 0.48 kV and 13.8 kV TCC curves?
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 68
TCC Scaling Example• Solution
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 69
Fixed Points
• Cable damage curves
• Cable ampacities
• Transformer damage curves & inrush points
• Motor starting curves
• Generator damage curve / Decrement curve
• SC maximum fault points
Points or curves which do not change regardless of protective device settings:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 70
Capability / Damage Curves
t
I
I2
2t
Gen
I2t
MotorXfmr
I2t
Cable
I2t
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 71
Cable Protection
• Standards & References– IEEE Std 835-1994 IEEE Standard Power Cable
Ampacity Tables
– IEEE Std 848-1996 IEEE Standard Procedure for the Determination of the Ampacity Derating of Fire-Protected Cables
– IEEE Std 738-1993 IEEE Standard for Calculating the Current- Temperature Relationship of Bare Overhead Conductors
– The Okonite Company Engineering Data for Copper and Aluminum Conductor Electrical Cables, Bulletin EHB-98
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 72
Cable Protection
2
2
1
tA
T 2340.0297log
T 234
The actual temperature rise of a cable when exposed to a short circuit current for a known time is calculated by:
Where:A= Conductor area in circular-mils
I = Short circuit current in ampst = Time of short circuit in seconds
T1= Initial operation temperature (750C)
T2=Maximum short circuit temperature
(1500C)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 73
Cable Short-Circuit Heating LimitsRecommended
temperature rise: B) CU 75-200C
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 74
Shielded Cable
The normal tape width is 1½
inches
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 75
NEC Section 110‑14 C
• (c) Temperature limitations. The temperature rating associated with the ampacity of a conductor shall be so selected and coordinated as to not exceed the lowest temperature rating of anylowest temperature rating of any connected terminationconnected termination, conductor, or device. Conductors with temperature ratings higher than specified for terminations shall be permitted to be used for ampacity adjustment, correction, or both.
• (1) Termination provisions of equipment for circuits rated 100 amperes or less, or marked for Nos. 14 through 1 conductors, shall be used only for conductors rated 600C (1400F).
• Exception No. 1: Conductors with higher temperature ratings shall be permitted to be used, provided the ampacity of such conductors is determined based on the 6O0C (1400F) ampacity of the conductor size used.
• Exception No. 2: Equipment termination provisions shall be permitted to be used with higher rated conductors at the ampacity of the higher rated conductors, provided the equipment is listed and identified for use with the higher rated conductors.
• (2) Termination provisions of equipment for circuits rated over 100 amperes, or marked for conductors larger than No. 1, shall be used only with conductors rated 750C (1670F).
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 76
Transformer Protection• Standards & References
– National Electric Code 2002 Edition
– C37.91-2000; IEEE Guide for Protective Relay Applications to Power Transformers
– C57.12.59; IEEE Guide for Dry-Type Transformer Through-Fault Current Duration.
– C57.109-1985; IEEE Guide for Liquid-Immersed Transformer Through-Fault-Current Duration
– APPLIED PROCTIVE RELAYING; J.L. Blackburn; Westinghouse Electric Corp; 1976
– PROTECTIVE RELAYING, PRINCIPLES AND APPLICATIONS; J.L. Blackburn; Marcel Dekker, Inc; 1987
– IEEE Std 242-1986; IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems
–
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 77
Transformer CategoryANSI/IEEE C-57.109
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 78
Transformer Categories I, II
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 79
Transformer Categories III
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 80
Transformer
t(sec)
I (pu)
Thermal200
2.5
I2t = 1250
2
25Isc
Mechanical
K=(1/Z)2t
(D-D LL) 0.87
(D-R LG) 0.58
Frequent Fault
Infrequent Fault
Inrush
FLA
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 81
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 82
Transformer Protection
MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE
PRIMARY SECONDARY
Over 600 Volts Over 600 Volts 600 Volts or Below
Transformer
Rated Impedance
Circuit Breaker Setting
Fuse
Rating
Circuit Breaker Setting
Fuse
Rating
Circuit Breaker Setting or Fuse
Rating
Not more than 6%
600 %
300 %
300 %
250%
125%
(250% supervised)
More than 6% and not more
than 10%
400 %
300 %
250%
225%
125%
(250% supervised)
Table 450-3(a) source: NEC
Any Location – Non-Supervised
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 83
Transformer Protection
• Turn on or inrush current
• Internal transformer faults
• External or through faults of major magnitude
• Repeated large motor starts on the transformer. The motor represents a major portion or the transformers KVA rating.
• Harmonics
• Over current protection – Device 50/51
• Ground current protection – Device 50/51G
• Differential – Device 87
• Over or under excitation – volts/ Hz – Device 24
• Sudden tank pressure – Device 63
• Dissolved gas detection
• Oil Level
• Fans
• Oil Pumps
• Pilot wire – Device 85
• Fault withstand
• Thermal protection – hot spot, top of oil temperature, winding temperature
• Devices 26 & 49
• Reverse over current – Device 67
• Gas accumulation – Buckholz relay
• Over voltage –Device 59
• Voltage or current balance – Device 60
• Tertiary Winding Protection if supplied
• Relay Failure Scheme
• Breaker Failure Scheme
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 84
Recommended Minimum Transformer Protection
Protective systemWinding and/or power system
grounded neutral groundedWinding and/or power system
neutral ungrounded
Up to 10 MVA Above 10 MVA Up to 10 MVAAbove
10 MVA
Differential - √ - √
Time over current √ √ √ √
Instantaneous restricted ground fault √ √ - -
Time delayed ground fault √ √ - -
Gas detection√ - √
Over excitation - √ √ √ Overheating - √ - √
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 85
Question
What is ANSI Shift Curve?
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 86
Answer
• For delta-delta connected transformers, with line-to-line faults on the secondary side, the curve must be reduced to 87% (shift to the left by a factor of 0.87)
• For delta-wye connection, with single line-to-ground faults on the secondary side, the curve values must be reduced to 58% (shift to the left by a factor of 0.58)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 87
Question
What is meant by Frequent andInfrequent for transformers?
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 88
Infrequent Fault Incidence Zones for Category II & III Transformers
* Should be selected by reference to the frequent-fault-incidence protection curve or for transformers serving industrial, commercial and institutional power systems with secondary-side conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by reference to the infrequent-fault-incidence protection curve.
Source: IEEE C57
Source
Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) may be selected by reference to the infrequent-fault-incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer primary-side protective device
Optional main secondary –side protective device. May be selected by reference to the infrequent-fault-incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side protective device or by optional main secondary-side protection device
Fault will be cleared by feeder protective device
Infrequent-Fault Incidence Zone*
Feeders
Frequent-Fault Incidence Zone*
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 89
Motor Protection
• Standards & References
– IEEE Std 620-1996 IEEE Guide for the Presentation of Thermal Limit Curves for Squirrel Cage Induction Machines.
– IEEE Std 1255-2000 IEEE Guide for Evaluation of Torque Pulsations During Starting of Synchronous Motors
– ANSI/ IEEE C37.96-2000 Guide for AC Motor Protection
– The Art of Protective Relaying – General Electric
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 90
Motor Protection
• Motor Starting Curve
• Thermal Protection
• Locked Rotor Protection
• Fault Protection
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 91
Motor Overload Protection (NEC Art 430-32 – Continuous-Duty Motors)
• Thermal O/L (Device 49)
• Motors with SF not less than 1.15
– 125% of FLA
• Motors with temp. rise not over 40°C
– 125% of FLA
• All other motors
– 115% of FLA
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 92
Motor Protection – Inst. Pickup
LOCKED ROTOR S d
1 I
X X "
PICK UP
LOCKED ROTOR
I RELAY PICK UP 1.2 TO 1.2
I
PICK UP
LOCKED ROTOR
I RELAY PICK UP 1.6 TO 2
I
with a time delay of 0.10 s (six cycles at 60 Hz)
Recommended Instantaneous Setting:
If the recommended setting criteria cannot be met, or where more sensitive protection is desired, the in stantaneous relay (or a second relay) can be set more
sensitively if delayed by a timer. This permits the asymmetricalasymmetrical starting component to decay out. A typical setting for this is:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 93
Locked Rotor Protection
• Thermal Locked Rotor (Device 51)
• Starting Time (TS < TLR)
• LRA
– LRA sym
– LRA asym (1.5-1.6 x LRA sym) + 10% margin
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 94
Fault Protection (NEC Art / Table 430-52)
• Non-Time Delay Fuses
– 300% of FLA
• Dual Element (Time-Delay Fuses)
– 175% of FLA
• Instantaneous Trip Breaker
– 800% - 1300% of FLA*
• Inverse Time Breakers
– 250% of FLA
*can be set up to 1700% for Design B (energy efficient) Motor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 95
Low Voltage Motor Protection
• Usually pre-engineered (selected from Catalogs)
• Typically, motors larger than 2 Hp are protected by combination starters
• Overload / Short-circuit protection
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 96
Low-voltage MotorRatings Range of ratingsContinuous amperes 9-250 —
Nominal voltage (V) 240-600 —
Horsepower 1.5-1000 —
Starter size (NEMA) — 00-9
Types of protection Quantity NEMA designation
Overload: overload relay elements 3 OL
Short circuit: circuit breaker current
trip elements3 CB
Fuses 3 FUUndervoltage: inherent with integral control supply and three-wire control circuit — —
Ground fault (when speci fied): ground relay with toroidal CT — —
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 97
Minimum Required Sizes of a NEMA
Combination Motor Starter System
MAXIMUM CONDUCTOR LENGTH FOR ABOVE AND
BELOW GROUND CONDUIT SYSTEMS. ABOVE GROUND SYSTEMS HAVE DIRECT SOLAR EXPOSURE. 750 C
CONDUCTOR TEMPERATURE, 450 C AMBIENT
CIRCUIT BREAKER SIZE
FU
SE
SIZ
E
CLA
SS
J
FU
SE
MO
TO
R H
P
460V
NE
C F
LC
ST
AR
TE
R
SIZ
E
MIN
IMU
M
SIZ
E
GR
OU
ND
ING
C
ON
DU
CT
OR
F
OR
A 5
0 %
CU
RR
EN
T C
AP
AC
ITY
MIN
IMU
M
WIR
E
SIZ
E
MA
XIM
UM
LE
NG
TH
FO
R 1
%
VO
LTA
GE
D
RO
P
NE
XT
LA
RG
ES
T
WIR
E
SIZ
E
US
E N
EX
T
LA
RG
ER
GR
OU
ND
C
ON
DU
CT
OR
MA
XIM
UM
LE
NG
TH
FO
R 1
%
VO
LTA
GE
D
RO
P W
ITH
LA
RG
ER
WIR
E
250%
200%
150%
1 2.1 0 12 12 759 10 1251 15 15 15 5
1½ 3 0 12 12 531 10 875 15 15 15 6 2 3.4 0 12 12 468 10 772 15 15 15 7
3 4.8 0 12 12 332 10 547 20 20 15 10
5 7.6 0 12 12 209 10 345 20 20 15 15
7½ 11 1 12 10 144 8 360 30 25 20 20
10 14 1 10 8 283 6 439 35 30 25 30
15 21 2 10 8 189 6 292 50 40 30 45
20 27 2 10 6 227 4 347 70 50 40 60
25 34 2 8 4 276 2 407 80 70 50 70
30 40 3 6 2 346 2/0 610 100 70 60 90
40 52 3 6 2 266 2/0 469 150 110 90 110
50 65 3 2 2/0 375 4/0 530 175 150 100 125
60 77 4 2 2/0 317 4/0 447 200 175 125 150
75 96 4 2 4/0 358 250 393 250 200 150 200
100 124 4 1 250 304 350 375 350 250 200 250
125 156 5 2/0 350 298 500 355 400 300 250 350
150 180 5 4/0 500 307 750 356 450 350 300 400
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 98
Required Data - Protection of a Medium Voltage Motor• Rated full load current
• Service factor
• Locked rotor current
• Maximum locked rotor time (thermal limit curve) with the motor at ambient and/or operating temperature
• Minimum no load current
• Starting power factor
• Running power factor
• Motor and connected load accelerating time
• System phase rotation and nominal frequency
• Type and location of resistance temperature devices (RTDs), if used
• Expected fault current magnitudes
• First ½ cycle current
• Maximum motor starts per hour
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 99
Medium-Voltage Class E Motor Controller
RatingsClass El
(without fuses)
Class E2 (with fuses)
Nominal system voltage 2300-6900 2300-6900Horsepower 0-8000 0-8000
Symmetrical MVA interrupting capacity at nominal system voltage
25-75 160-570
Types of Protective Devices QuantityNEMA Designation
Overload, or locked Rotor, or both:
Thermal overload relayTOC relay
IOC relay plus time delay
333
OL OC TR/O
Thermal overload relay 3 OL
TOC relay 3 OC
IOC relay plus time delay 3 TR/OC
Short Circuit:
Fuses, Class E2 3 FU
IOC relay, Class E1 3 OC
Ground Fault
TOC residual relay 1 GP
Overcurrent relay with toroidal CT
1 GP
NEMA Class E2 medium voltage starter
NEMA Class E1 medium voltage starter
Phase Balance
Current balance relay 1 BC
Negative-sequence voltage relay (per bus), or both
1 —
Undervoltage:Inherent with integral control supply and three-wire control circuit, when voltage falls suffi ciently to permit the contractor to open and break the seal-in circuit
— UV
Temperature:Temperature relay, operating from resistance sensor or ther mocouple in stator winding
— OL
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 100
Starting Current of a 4000Hp, 12 kV, 1800 rpm Motor
First half cycle current showing current offset.
Beginning of run up current showing load torque pulsations.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 101
Starting Current of a 4000Hp, 12 kV, 1800 rpm Motor -
Motor pull in current showing motor reaching synchronous speed
Oscillographs
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 102
Thermal Limit Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 103
Thermal Limit Curve
Typical Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 104
200 HP
MCP
O/L
Starting Curve
I2T
(49)
MCP (50)
(51)ts
tLR
LRAs LRAasym
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 105
Protective Devices
• Fuse
• Overload Heater
• Thermal Magnetic
• Low Voltage Solid State Trip
• Electro-Mechanical
• Motor Circuit Protector (MCP)
• Relay (50/51 P, N, G, SG, 51V, 67, 49, 46, 79, 21, …)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 106
Fuse (Power Fuse)
• Non Adjustable Device (unless electronic)
• Continuous and Interrupting Rating
• Voltage Levels (Max kV)
• Interrupting Rating (sym, asym)
• Characteristic Curves
– Min. Melting
– Total Clearing
• Application (rating type: R, E, X, …)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 107
Fuse Types
• Expulsion Fuse (Non-CLF)
• Current Limiting Fuse (CLF)
• Electronic Fuse (S&C Fault Fiter)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 108
Minimum Melting Time Curve
Total Clearing Time Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 109
Current Limiting Fuse(CLF) • Limits the peak current of short-circuit
• Reduces magnetic stresses (mechanical damage)
• Reduces thermal energy
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 110
Current Limiting ActionC
urr
ent
(pea
k a
mp
s)
tm ta
Ip’
Ip
tc
ta = tc – tm
ta = Arcing Time
tm = Melting Time
tc = Clearing Time
Ip = Peak Current
Ip’ = Peak Let-thru Current
Time (cycles)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 111© 1996-2009 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 112
Symmetrical RMS Amperes
Pea
k L
et-T
hrou
gh A
mpe
res
100 A
60 A
7% PF (X/R = 14.3)
12,500
5,200
230,000
300 A
100,000
Let-Through Chart
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 113
Fuse
Generally:
• CLF is a better short-circuit protection
• Non-CLF (expulsion fuse) is a better Overload protection
• Electronic fuses are typically easier to coordinate due to the electronic control adjustments
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 114
Selectivity Criteria
Typically:
• Non-CLF: 140% of full load
• CLF: 150% of full load
• Safety Margin: 10% applied to Min Melting (consult the fuse manufacturer)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 115
Molded Case CB
• Thermal-Magnetic
• Magnetic Only
• Motor Circuit Protector (MCP)
• Integrally Fused (Limiters)
• Current Limiting
• High Interrupting Capacity
• Non-Interchangeable Parts
• Insulated Case (Interchange Parts)
Types
• Frame Size
• Poles
• Trip Rating
• Interrupting Capability
• Voltage
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 116
MCCB
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 117
MCCB with SST Device
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 118
Thermal Minimum
Thermal Maximum
Magnetic(instantaneous)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 119
LVPCB
• Voltage and Frequency Ratings
• Continuous Current / Frame Size / Sensor
• Interrupting Rating
• Short-Time Rating (30 cycle)
• Fairly Simple to Coordinate
• Phase / Ground Settings
• Inst. Override
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 120
CB 2CB 1
IT
ST PU
ST Band
LT PU
LT Band
480 kV
CB 2
CB 1
If =30 kA
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 121
Inst. Override
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 122
Overload Relay / Heater
• Motor overload protection is provided by a device that models the temperature rise of the winding
• When the temperature rise reaches a point that will damage the motor, the motor is de-energized
• Overload relays are either bimetallic, melting alloy or electronic
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 123
Overload Heater (Mfr. Data)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 124
QuestionWhat is Class 10 and Class 20 Thermal OLR curves?
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 125
Answer
• At 600% Current Rating:
– Class 10 for fast trip, 10 seconds or less
– Class 20 for, 20 seconds or less (commonly used)
– There is also Class 15, 30 for long trip time (typically provided with electronic overload relays)
6
20
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 126
Answer
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 127
Overload Relay / Heater• When the temperature at the combination motor starter is more than
±10 °C (±18 °F) different than the temperature at the motor, ambient temperature correction of the motor current is required.
• An adjustment is required because the output that a motor can safely deliver varies with temperature.
• The motor can deliver its full rated horsepower at an ambient temperature specified by the motor manufacturers, normally + 40 °C. At high temperatures (higher than + 40 °C) less than 100% of the normal rated current can be drawn from the motor without shortening the insulation life.
• At lower temperatures (less than + 40 °C) more than 100% of the normal rated current could be drawn from the motor without shortening the insulation life.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 128
Overcurrent Relay
• Time-Delay (51 – I>)
• Short-Time Instantaneous ( I>>)
• Instantaneous (50 – I>>>)
• Electromagnetic (induction Disc)
• Solid State (Multi Function / Multi Level)
• Application
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 129© 1996-2009 Operation Technology, Inc. – Workshop Notes: Protective Device Coordination
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 130
Time-Overcurrent Unit
• Ampere Tap Calculation
– Ampere Pickup (P.U.) = CT Ratio x A.T. Setting
– Relay Current (IR) = Actual Line Current (IL) / CT Ratio
– Multiples of A.T. = IR/A.T. Setting
= IL/(CT Ratio x A.T. Setting)
IL
IR
CT
51
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 131
Instantaneous Unit
• Instantaneous Calculation
– Ampere Pickup (P.U.) = CT Ratio x IT Setting
– Relay Current (IR) = Actual Line Current (IL) / CT Ratio
– Multiples of IT = IR/IT Setting
= IL/(CT Ratio x IT Setting)
IL
IR
CT
50
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 132
Relay Coordination
• Time margins should be maintained between T/C curves
• Adjustment should be made for CB opening time
• Shorter time intervals may be used for solid state relays
• Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream)
• Extremely inverse relays coordinates very well with CLFs
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 133
Situation
Calculate Relay Setting (Tap, Inst. Tap & Time Dial)For This System
4.16 kV
DS 5 MVA
Cable
1-3/C 500 kcmilCU - EPR
CB
Isc = 30,000 A
6 %
50/51 Relay: IFC 53CT 800:5
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 134
Solution
AInrsuh 328,869412I
A338.4800
5II LR
Transformer: AkV
kVAL 694
16.43
000,5I
IL
CTRIR
Set Relay:
A 55 1.52800
5328,8)50(
1
)38.1(6/4.338 0.6
4.5338.4%125
AInst
TD
ATAP
A
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 135
Question
What T/C Coordination interval should be maintained between relays?
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 136
Answer
At
I
B
CB Opening Time
+
Induction Disc Overtravel (0.1 sec)
+
Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 137
Recloser• Recloser protects electrical transmission systems from temporary
voltage surges and other unfavorable conditions.
• Reclosers can automatically "reclose" the circuit and restore normal power transmission once the problem is cleared.
• Reclosers are usually designed with failsafe mechanisms that prevent them from reclosing if the same fault occurs several times in succession over a short period. This insures that repetitive line faults don't cause power to switch on and off repeatedly, since this could cause damage or accelerated wear to electrical equipment.
• It also insures that temporary faults such as lightning strikes or transmission switching don't cause lengthy interruptions in service.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 138
Recloser Types
• Hydraulic
• Electronic
– Static Controller
– Microprocessor Controller
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 139
Recloser Curves
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 140
TEMA 3
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Transient Stability
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 142
Topics
• What is Transient Stability (TS)
• What Causes System Unstable
• Effects When System Is Instable
• Transient Stability Definition
• Modeling and Data Preparation
• ETAP TS Study Outputs
• Power System TS Studies
• Solutions to Stability Problems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 143
What is Transient Stability
• TS is also called Rotor Angle StabilitySomething between mechanical system and
electrical system – energy conversion
• It is a Electromechanical PhenomenonTime frame in milliseconds
• All Synchronous Machines Must Remain in Synchronism with One AnotherSynchronous generators and motorsThis is what system stable or unstable means
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 144
What is Transient Stability
• Torque Equation (generator case)
T = mechanical torque
P = number of poles
air = air-gap flux
Fr = rotor field MMF
= rotor angle
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 145
What is Transient Stability
• Swing Equation
M = inertia constant
D = damping constant
Pmech = input mechanical power
Pelec = output electrical power
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 146
What Causes System Unstable
• From Torque EquationT (prime mover)Rotor MMF (field winding)Air-Gap Flux (electrical system)
• From Swing EquationPmechPelecDifferent time constants in mechanical and
electrical systems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 147
What Causes System Unstable
• In real operationShort-circuitLoss of excitationPrime mover failureLoss of utility connectionsLoss of a portion of in-plant generationStarting of a large motorSwitching operationsImpact loading on motorsSudden large change in load and generation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 148
Effects When System Is Instable
Case 1: Steady-state stableCase 2: Transient stable Case 3: Small-signal unstable Case 4: First swing unstable
• Swing in Rotor Angle (as well as in V, I, P, Q and f)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 149
Effects When System Is Instable
• A 2-Machine Example
• At = -180º (Out-of-Step,Slip the Pole)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 150
Effects When System Is Instable
• Synchronous machine slip poles – generator tripping
• Power swing
• Misoperation of protective devices
• Interruption of critical loads
• Low-voltage conditions – motor drop-offs
• Damage to equipment
• Area wide blackout
• …
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 151
• Examine One Generator
• Power Output Capability Curve
is limited to 180º
Transient Stability Definition
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 152
Transient Stability Definition
• Transient and Dynamic Stability Limit
After a severe disturbance, the synchronous generator reaches a steady-state operating condition without a prolonged loss of synchronism
Limit: < 180 during swing
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 153
• Synchronous Machine
Machine Exciter and AVR Prime Mover and Governor / Load Torque Power System Stabilizer (PSS) (Generator)
Modeling and Data Preparation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 154
Modeling and Data Preparation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 155
Modeling and Data Preparation
• Typical synchronous machine data
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 156
Modeling and Data Preparation
• Induction Machine
Machine Load Torque
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 157
Modeling and Data Preparation
• Power Grid
Short-Circuit Capability Fixed internal voltage and infinite inertia
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 158
Modeling and Data Preparation
• Load
Voltage dependency Frequency dependency
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 159
Modeling and Data Preparation
• Load
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 160
Modeling and Data Preparation
• Events and Actions
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 161
Modeling and Data Preparation
Device Type Action
Bus 3-P Fault L-G Fault Clear Fault
Branch Fraction Fault
Clear Fault
PD Trip Close
Generator Droop / Isoch
Start Loss Exc. P Change V Change Delete
Grid P Change V Change Delete
Motor Accelerate Load Change
Delete
Lumped Load Load Change
Delete
MOV Start
Wind Turbine Disturbance Gust Ramp
MG Set Emergency Main
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 162
Power System TS Studies
• Fault3-phase and single phase faultClear faultCritical Fault Clearing Time (CFCT)Critical System Separation Time (CSST)
• Bus TransferFast load transferring
• Load SheddingUnder-frequencyUnder-voltage
• Motor Dynamic Acceleration Induction motorSynchronous motor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 163
Power System TS Studies
• Critical Fault Clearing Time (CFCT)
• Critical Separation Time (CSST)
unstable
unstableCycle
Clear faultClear fault
1 cycle
unstable
stable
1 cycle
Clear faultClear fault
CFCT
Fault
unstable
unstable
Cycle
1 cycleunstable
stable
1 cycle
CSST
SeparationSeparationSeparationSeparationFault
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 164
Power System TS Studies
-1
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
-1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1
Vmotor
s
• Fast Bus Transfer
Motor residual voltage
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 165
• Fast Bus Transfer
Ttransfer 10 cycles
90 degrees
ER 1.33 per unit (133%)
Power System TS Studies
ES = System equivalent per unit volts per hertz
EM = Motor residual per unit per hertz
ER = Resultant vectorial voltage in per unit volts per hertz
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 166
Power System TS Studies
• Load Shedding
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 167
Power System TS Studies
• Motor Dynamic AccelerationImportant for islanded system operationMotor starting impact Generator AVR actionReacceleration
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 168
• Improve System Design Increase synchronizing power
• Design and Selection of Rotating Equipment Use of induction machines Increase moment of inertia Reduce transient reactance Improve voltage regulator and exciter
characteristics
Solution to Stability Problems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 169
• Application of Power System Stabilizer (PSS)
• Add System Protections Fast fault clearance Load shedding System separationOut-Of-Step relay…
Solution to Stability Problems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 171
TEMA 4
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Harmonic Analysis
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 173
ARMONICAS
Exploración de frecuencia.
Flujo Armónico de Carga.
Dimensionamiento y Diseño de Filtros.
Evaluación Automática del límite de distorsión.
Factores de la influencia del teléfono (TIF & I*T)
Características principales:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 174
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 175
Types of Power Quality Problems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 176
Waveform Distortion
• Primary Types of Waveform Distortion
– DC Offset
– Harmonics
– Interharmonics
– Notching
– Noise
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 177
Harmonics
• One special category of power quality problems
• “Harmonics are voltages and/or currents present in an electrical system at some multiple of the fundamental frequency.”(IEEE Std 399, Brown Book)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 178
Nonlinear Loads
• Sinusoidal voltage applied to a simple nonlinear resistor
• Increasing the voltage by a few percent may cause current to double
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 179
Fourier Representation
• Any periodic waveform can be expressed as a sum of sinusoids
• The sum of the sinusoids is referred to as Fourier Series (6-pulse)
)cos(
13cos13
111cos
11
17cos
7
13cos
5
1(cos
32
1h
hh
dac
thI
tttttII
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 180
Harmonic Sources
• Utilities (Power Grid)
– Known as “Background Harmonic”
– Pollution from other irresponsible customers
– SVC, HVDC, FACTS, …
– Usually a voltage source
• Synchronous Generators
– Due to Pitch (can be eliminated by fractional-pitch winding) and Saturation
– Usually a voltage source
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 181
Harmonic Sources (cont’d)
• Transformers
– Due to magnetizing branch saturation
– Only at lightly loaded condition
– Usually a current source
• Power Electronic Devices
– Charger, Converter, Inverter, UPS, VFD, SVC, HVDC, FACTS (Flexible alternating current transmission systems) …
– Due to switching actions
– Either a voltage source or a current source
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 182
Harmonic Sources (cont’d)
• Other Non-Linear Loads
– Arc furnaces, discharge lighting, …
– Due to unstable and non-linear process
– Either a voltage source or a current source
• In general, any load that is applied to a power system that requires other than a sinusoidal current
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 183
Harmonic I and V
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 184
Classification of Harmonics
• Harmonics may be classified as:
– Characteristic Harmonics
Generally produced by power converters
– Non-Characteristic Harmonics
Typically produced by arc furnaces and discharge lighting (from non-periodical waveforms)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 185
Phase Angle Relationship
• Fundamental Frequency
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 186
Phase Angle Relationship
• Third Order
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 187
Phase Angle Relationship
• Fifth Order
• Seventh Order
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 188
Order vs. Sequence
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 189
Characteristic Harmonics
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 190
Characteristic Harmonics (cont’d)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 191
Harmonic Spectrum
%
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 192
Harmonic-Related Problems
• Motors and Generators
– Increased heating due to iron and copper losses
– Reduced efficiency and torque
– Higher audible noise
– Cogging or crawling
– Mechanical oscillations
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 193
Harmonic-Related Problems (cont’d)• Transformers
– Parasitic heating
– Increased copper, stray flux and iron losses
• Capacitors (var compensators)
– Possibility of system resonance
– Increased heating and voltage stress
– Shortened capacitor life
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 194
Harmonic-Related Problems (cont’d)• Power Cables
– Involved in system resonance
– Voltage stress and corona leading to dielectric failure
– Heating and derating
• Neutrals of four-wire systems (480/277V; 120/208V)
– Overheating
• Fuses
– Blowing
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 195
Harmonic-Related Problems (cont’d)• Switchgears
– Increased heating and losses
– Reduced steady-state current carrying capability
– Shortened insulation components life
• Relays
– Possibility of misoperation
• Metering
– Affected readings
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 196
Harmonic-Related Problems (cont’d)• Communication Systems
– Interference by higher frequency electromagnetic field
• Electronic Equipment (computers, PLC)
– Misoperation
• System
– Resonance (serial and parallel)
– Poor power factor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 197
Parallel Resonance
• Total impedance at resonance frequency increases
• High circulating current will flow in the capacitance-inductance loop
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 198
Parallel Resonance
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 199
Capacitor Banks
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 200
Capacitor Banks
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 201
Capacitor Banks
Say, Seventh Harmonic Current = 5% of 1100A = 55 A
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 202
Capacitor Banks
Resistance = 1% including cable and transformerCAF = X/R = 7*0.0069/0.0012 =40.25Resonant Current = 55*40.25 = 2214 A
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 203
Parallel Resonance (cont’d)
Cause:
Impacts: 1. Excessive capacitor fuse operation
2. Capacitor failures3. Incorrect relay tripping4. Telephone interference5. Overheating of equipment
Source inductance resonates with capacitor bank at a frequency excited by the facilities harmonic sources
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 204
Harmonic Distortion Measurements
• Total Harmonic Distortion (THD)
– Also known as Harmonic Distortion Factor (HDF), is the most popular index to measure the level of harmonic distortion to voltage and current
– Ratio of the RMS of all harmonics to the fundamental component
– For an ideal system THD = 0%
– Potential heating value of the harmonics relative to the fundamental
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 205
Harmonic Distortion Measurements (cont’d)
1
2
2
F
F
THDi
Where Fi is the amplitude of the ith harmonic,
and F1 is that for the fundamental component.
– Good indicator of additional losses due to current flowing through a conductor
– Not a good indicator of voltage stress in a capacitor (related to peak value of voltage waveform, not its heating value)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 206
Harmonic Distortion Example
Find THD for this waveform
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 207
Harmonic Example
• Find THD for this Harmonic Spectrum
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 208
Adjustable Speed Drive – Current Distortion
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 209
Adjustable Speed Drive – Voltage Distortion
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 210
Harmonic Distortion Measurements (cont’d)• Individual Harmonic Distortion (IHD)
- Ratio of a given harmonic to fundamental- To track magnitude of individual harmonic
1F
FIHD i
• Root Mean Square (RMS) - Total- Root Mean Square of fundamental plus all harmonics
- Equal to fundamental RMS if Harmonics are zero
1
2iFRMS
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 211
Harmonic Distortion Measurements (cont’d)• Arithmetic Summation (ASUM)
– Arithmetic summation of magnitudes of all components (fundamental and all harmonics)
– Directly adds magnitudes of all components to estimate crest value of voltage and current
– Evaluation of the maximum withstanding ratings of a device
1
iFASUM
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 212
Harmonic Distortion Measurements (cont’d)• Telephone Influence Factor (TIF)
– Weighted THD
– Weights based on interference to an audio signal in the same frequency range
– Current TIF shows impact on adjacent communication systems
2
1
2
1
i
ii
F
FW
TIF
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 213
Harmonic Distortion Measurements (cont’d)
• I*T Product (I*T)
– A product current components (fundamental and harmonics) and weighting factors
H
hhh TITI
1
2)(
where Ih = current component
Th= weighting factor
h = harmonic order (h=1 for fundamental)H = maximum harmonic order to account
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 214
Triplen Harmonics
• Odd multiples of thethird harmonic(h = 3, 9, 15, 21, …)
• Important issue forgrounded-wye systemswith neutral current
• Overloading and TIF problems
• Misoperation of devices due to presence of harmonics on the neutral
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 215
Triplen Harmonics
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 216
Winding Connections
• Delta winding provides ampere turn balance
• Triplen Harmonics cannot flow
• When currents are balanced Triplens behave as Zero Sequence currents
• Used in Utility Distribution Substations
• Delta winding connected to Transmission
• Balanced Triplens can flow
• Present in equal proportions on both sides
• Many loads are served in this fashion
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 217
Implications
• Neutral connections are susceptible to overheating when serving single-phase loads on the Y side that have high 3rd Harmonic
• Measuring current on delta side will not show the triplens and therefore do not give a true idea of the heating the transformer is subjected to
• The flow of triplens can be interrupted by appropriate isolation transformer connection
• Removing the neutral connection in one or both Y windings blocks the flow of Triplen harmonic current
• Three legged core transformers behave as if they have a “phantom” delta tertiary winding
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 218
Modeling in Harmonic Analysis
• Motors and Machines
– Represented by their equivalent negative sequence reactance
• Lines and Cables
– Series impedance for low frequencies
– Long line correction including transposition and distributed capacitance
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 219
Modeling in Harmonic Analysis (cont’d)
• Transformers
– Leakage impedance
– Magnetizing impedance
• Loads
– Static loads reduce peak resonant impedance
– Motor loads shift resonant frequency due to motor inductance
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 220
Reducing System Harmonics
• Add Passive Filters
– Shunt or Single Tuned Filters– Broadband Filters or Band Pass Filters– Provide low impedance path for harmonic
current– Least expensive
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 221
Reducing System Harmonics (cont’d)
• Increase Pulse Numbers
– Increasing pulse number of convert circuits
– Limited by practical control problems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 222
Reducing System Harmonics (cont’d)• Apply Transformer Phase Shifting
– Using Phase Shifting Transformers
– Achieve higher pulse operation of the total converter installation
• In ETAP
– Phase shift is specified in the tab page of the transformer editor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 223
Reducing System Harmonics (cont’d)• Either standard phase shift or special phase
shift can be used
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 224
Reducing System Harmonics (cont’d)• Add Active Filters
– Instantly adapts to changing source and load conditions
– Costly
– MVA Limitation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 225
Voltage Distortion Limits
Recommended Practices for Utilities (IEEE 519): Bus Voltage
At
PCC
Individual Distortion
(%)
Total Voltage Distortion
THD (%)
69 kV and below 3.0 5.0
69.001 kV through 161kV 1.5 2.5
161.001 and above 1.0 1.5
In ETAP:
Specify Harmonic Distortion Limits in Harmonic Page of Bus Editor:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 226
Current Distortion Limits
Recommended Practices for General Distribution Systems (IEEE 519):
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 227
TEMA 5
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Motor StartingDynamic Acceleration
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 229
ARRANQUE DE MOTORES
Aceleración dinámica de motores.
Parpadeo (Flicker) de tensión.
Modelos dinámicos de motores.
Arranque estático de motores.
Varios dispositivos de arranque.
Transición de carga.
Características principales:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 230
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 231
Why to Do MS Studies?
• Ensure that motor will start with voltage drop• If Tst<Tload at s=1, then motor will not start
• If Tm=Tload at s<sr, motor can not reach rated speed
• Torque varies as (voltage)^2
• Ensure that voltage drop will not disrupt other loads• Utility bus voltage >95%
• 3% Sag represents a point when light flicker becomes visible
• 5% Sag represents a point when light flicker becomes irritating
• MCC bus voltage >80%
• Generation bus voltage > 93%
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 232
Why to Do MS Studies?
• Ensure motor feeders sized adequately (Assuming 100% voltage at Switchboard or MCC)
• LV cable voltage drop at starting < 20%
• LV cable voltage drop when running at full-load < 5%
• HV cable voltage drop at starting < 15%
• HV cable voltage drop when running at full-load < 3%
• Maximum motor size that can be started across the line• Motor kW < 1/6 kW rating of generator (islanded)
• For 6 MW of islanded generation, largest motor size < 1 MW
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 233
Motor Sizing
• Positive Displacement Pumps / Rotary Pumps
• p = Pressure in psi
• Q = fluid flow in gpm
• n = efficiency
• Centrifugal Pumps
• H = fluid head in feet
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 234
Motor Types
• Synchronous• Salient Pole
• Round Rotor
• Induction• Wound Rotor (slip-ring)
• Single Cage CKT Model
• Squirrel Cage (brushless) • Double Cage CKT Model
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 235
Induction Motor Advantages
• Squirrel Cage• Slightly higher efficiency and power factor
• Explosive proof
• Wound Rotor• Higher starting torque
• Lower starting current
• Speed varied by using external resistances
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 236
Typical Rotor Construction
• Rotor slots are not parallel to the shaft but skewed
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 237
Wound Rotor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 238
Operation of Induction Motor• AC applied to stator winding
• Creates a rotating stator magnetic field in air gap
• Field induces currents (voltages) in rotor
• Rotor currents create rotor magnetic field in air gap
• Torque is produced by interaction of air gap fields
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 239
Slip Frequency
• Slip represents the inability of the rotor to keep up with the stator magnetic field
• Slip frequencyS = (ωs-ωn)/ωs where ωs = 120f/P
ωn = mech speed
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 240
Static Start - Example
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 241
Static Start - Example
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 242
Service Factor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 243
Inrush Current
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 244
Resistance / Reactance
• Torque Slip Curve is changed by altering resistance / reactance of rotor bars.
• Resistance ↑ by ↓cross sectional area or using higher resistivity material like brass.
• Reactance ↑ by placing conductor deeper in the rotor cylinder or by closing the slot at the air gap.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 245
Rotor Bar Resistance ↑
• Increase Starting Torque
• Lower Starting Current
• Lower Full Load Speed
• Lower Efficiency
• No Effect on Breakdown Torque
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 246
Rotor Bar Reactance ↑
• Lower Starting Torque
• Lower Starting Current
• Lower Breakdown Torque
• No effect on Full Load Conditions
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 247
Motor Torque Curves
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 248
Rotor Bar Design
• Cross section Large (low resistance) and positioned deep in the rotor (high reactance). (Starting Torque is normal and starting current is low).
• Double Deck with small conductor of high resistance. During starting, most current flows through the upper deck due to high reactance of lower deck. (Starting Torque is high and starting current is low).
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 249
Rotor Bar Design
• Bars are made of Brass or similar high resistance material. Bars are close to surface to reduce leakage reactance. (Starting torque is high and starting current is low).
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 250
Load Torque – ID Fan
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 251
Load Torque – FD Fan
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 252
Load Torque – C. Pump
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 253
Motor Torque – Speed Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 254
Double Cage Motor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 255
Motor Full Load Torque
• For example, 30 HP 1765 RPM Motor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 256
Motor Efficiency
• kW Saved = HP * 0.746 (1/Old – 1/New)
• $ Savings = kW Saved * Hrs /Year * $/kWh
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 257
Acceleration Torque
• Greater Acceleration Torque means higher inertia that can be handled by the motor without approaching thermal limits
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 258
Acceleration Torque
P
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 259
Operating Range
• Motor, Generator, or Brake
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 260
0.8 1.0
kvar
Loa
d(k
va)
Terminal Voltage
Ter
min
al C
urre
nt
Terminal Voltage0.8 1.0
P = Tm Wm , As Vt ( terminal voltage ) changes from 0.8 to 1.1 pu, Wm changes by a very small amount. There fore, P is approx constant since Tm (α w²m) is approx. constant
L1 Ir
Rated Conditions• Constant Power
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 261
0.9 1.0
Kva LR
Terminal Voltage Terminal Voltage0.9 1.0
.8 kvaLR
Vt (pu)
Vt (pu)
.9 I LR
I LR
PIt
KVA LR = Loched - rotor KVA at rated voltage = 2HP
2 ≡ Code letter factor ≡ Locked – rotor KVA ∕ HP
Z st = KVA B KVR ²
KVA LR KVB
Pu, Rst = Zst cos θ st , Xst= Zst sin θ st ______ ____
KVR = rated voltage KVB = Base voltage KVAB = Base power
Starting Conditions• Constant Impedance
Starting Conditions Constant Impedance
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 262
ws wm
v1
p
R
Load
Voltage Variation
0
I
80% voltage
100% voltage
ws wm0
TT st T’ st
Tst α ( operating voltage) ²
Rated voltage_____________
Rated voltage_____________Ist α ( operating voltage)
• Torque is proportional to V^2
• Current is proportional to V
I
80% V
100% V
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 263
Frequency Variation• As frequency decreases, peak torque shifts toward lower
speed as synchronous speed decreases.
• As frequency decrease, current increases due reduced impedance.
Tem
WS1 WS2 Wm
F1
F2 › F1
0
I
WS1 WS2 Wm
F1
F2 › F1
0
W3 = 120f
P ___ RPM
Adjustable speed drive : Typical speed range for variable torque loads such as pumps and fans is 3/1,maximun is 8/1 ( 1.5 to 60 Hz)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 264
Number of Poles Variation
• As Pole number increases, peak torque shifts toward lower speed as synchronous speed decreases.
Tem
W′S WSWm0
2 P - poles
P - poles
P
RLoad
Nro. of poles variation
W′S = WS___
2
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 265
Rotor Z Variation
• Increasing rotor Z will shift peak torque towards lower speed.
S
RQ
P
r1
r2 r3 r4
r1 › r2 › r3 › r4
Rotor – Resistance Variation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 266
Modeling of Elements
• Switching motors – Zlr, circuit model, or characteristic model
• Synch generator - constant voltage behind X’d
• Utility - constant voltage behind X”d
• Branches – Same as in Load Flow
• Non-switching Load – Same as Load flow
• All elements must be initially energized, including motors to start
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 267
Motor Modeling
1. Operating Motor
– Constant KVA Load
2. Starting Motor
– During Acceleration – Constant Impedance
– Locked-Rotor Impedance
– Circuit Models
Characteristic Curves
After Acceleration – Constant KVA Load
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 268
Locked-Rotor Impedance
• ZLR = RLR +j XLR (10 – 25 %)
• PFLR is much lower than operating PD. Approximate starting PF of typical squirrel cage induction motor:
PO
WE
R F
AC
TO
R
HORSE POWER RATING
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 269
Circuit Model I
• Single Cage Rotor
– “Single1” – constant rotor resistance and reactance
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 270
Circuit Model II
• Single Cage Rotor
– “Single2” - deep bar effect, rotor resistance and reactance vary with speed [Xm is removed]
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 271
Circuit Model III
• Double Cage Rotor
– “DB1” – integrated rotor cages
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 272
Circuit Model IV
• Double Cage Rotor
– “DB2” – independent rotor cages
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 273
Characteristic Model
• Motor Torque, I, and PF as function of Slip
– Static Model
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 274
Calculation Methods I
• Static Motor Starting
– Time domain using static model
– Switching motors modeled as Zlr during starting and constant kVA load after starting
– Run load flow when any change in system
• Dynamic Motor Starting
– Time domain using dynamic model and inertia model
– Dynamic model used for the entire simulation
– Requires motor and load dynamic (characteristic) model
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 275
Calculation Methods II
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 276
Static versus Dynamic
• Use Static Model When
– Concerned with effect of motor starting on other loads
– Missing dynamic motor information
• Use Dynamic Model When
– Concerned with actual acceleration time
– Concerned if motor will actually start
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 277
MS Simulation Features
• Start/Stop induction/synchronous motors
• Switching on/off static load at specified loading category
• Simulate MOV opening/closing operations
• Change grid or generator operating category
• Simulate transformer LTC operation
• Simulate global load transition
• Simulate various types of starting devices
• Simulate load ramping after motor acceleration
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 278
Automatic Alert• Starting motor terminal V
• Motor acceleration failure
• Motor thermal damage
• Generator rating
• Generator engine continuous & peak rating
• Generator exciter peak rating
• Bus voltage
• Starting motor bus
• Grid/generator bus
• HV, MV, and LV bus
• User definable minimum time span
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 279
Starting Devices Types
• Auto-Transformer
• Stator Resistor
• Stator Reactor
• Capacitor at Bus
• Capacitor at Motor Terminal
• Rotor External Resistor
• Rotor External Reactor
• Y/D Winding
• Partial Wing
• Soft Starter
• Stator Current Limit
– Stator Current Control
– Voltage Control
– Torque Control
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 280
Starting Device
• Comparison of starting conditions
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 281
Starting Device – AutoXFMR
• C4 and C3 closed initially
• C4 opened, C2 is closed with C3 still closed. Finally C3 is open
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 282
Starting Device – AutoXFMR
• Autotransformer starting
MCCM
Autotransformer starter
line
Vmcc
EX. 50% Tap
VMCC50%
tap
5VMCC IST
3IST
VM
PFST ( with autotransformer) = PFST ( without autotransformer)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 283
Starting Device – YD Start
• During Y connection Vs = VL / √3
• Phase current Iy = Id / √3 and 3 to 1 reduction in torque
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 284
Starting Device – Rotor R
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 285
Starting Device – Stator R• Resistor
VMCC50%
tap
5VMCC VMRLR
XLR
RL XL
PFST ( with resistor) = 1-[pu tap setting ]² * [ 1- (PFST without resistor)²]
= 1- (0.5)² * [1-(PFST)²]
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 286
VMCC50%
tap
5VMCC VMRLR
XLR
RL XL
Starting Device Stator X
• Reactor
PFST ( with reactor) = [pu tap setting ] * PFST (without reactor)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 287
Transformer LTC Modeling
• LTC operations can be simulated in motor starting studies
• Use global or individual Tit and Tot
V limit
Tit Tot
T
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 288
MOV Modeling I
• Represented as an impedance load during operation– Each stage has own impedance based on I, pf, Vr
– User specifies duration and load current for each stage
• Operation type depends on MOV status– Open statusclosing operation
– Close statusopening operation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 289
MOV Modeling II
• Five stages of operationOpening ClosingAcceleration Acceleration
No load No load
Unseating Travel
Travel Seating
Stall Stall
• Without hammer blow Skip “No Load” period
• With a micro switch Skip “Stall” period
• Operating stage time extended if Vmtr < Vlimit
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 290
MOV Closing
• With Hammer Blow- MOV Closing
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 291
MOV Opening
• With Hammer Blow- MOV Opening
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 292
UNSETTING
TRAVEL
VMTR < V LIMIT
STALLACCL
I
MOV Voltage Limit• Effect of Voltage Limit Violation
Tacc TposTravel Tstl
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 293
TEMA 6
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Short-CircuitANSI Standard
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 295
CORTO CIRCUITO
Estándar de ANSI/IEEE & IEC.
Análisis de fallas transitorias (IEC 61363).
Efecto de Arco (NFPA 70E-2000)
Integrado con coordinación de dispositivos de protección.
Evaluación automática de dispositivos.
Características principales:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 296
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 297
Types of SC Faults•Three-Phase Ungrounded Fault•Three-Phase Grounded Fault•Phase to Phase Ungrounded Fault•Phase to Phase Grounded Fault•Phase to Ground Fault
Fault Current
•IL-G can range in utility systems from a few percent to
possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all faults).
•In industrial systems the situation IL-G > I3-phase is rare.
Typically IL-G .87 * I3-phase
•In an industrial system, the three-phase fault condition is frequently the only one considered, since this type of fault generally results in Maximum current.
Short-Circuit Analysis
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 298
Purpose of Short-Circuit Studies• A Short-Circuit Study can be used to determine
any or all of the following:
– Verify protective device close and latch capability
– Verify protective device Interrupting capability
– Protect equipment from large mechanical forces (maximum fault kA)
– I2t protection for equipment (thermal stress)
– Selecting ratings or settings for relay coordination
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 299
System Components Involved in SC Calculations• Power Company Supply
• In-Plant Generators
• Transformers (using negative tolerance)
• Reactors (using negative tolerance)
• Feeder Cables and Bus Duct Systems (at lower temperature limits)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 300
System Components Involved in SC Calculations• Overhead Lines (at lower temperature limit)
• Synchronous Motors
• Induction Motors
• Protective Devices
• Y0 from Static Load and Line Cable
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 301
Elements That Contribute Current to a Short-Circuit
• Generator
• Power Grid
• Synchronous Motors
• Induction Machines
• Lumped Loads(with some % motor load)
• Inverters
• I0 from Yg-Delta Connected Transformer
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 302
Elements Do Not Contribute Current in PowerStation
• Static Loads
• Motor Operated Valves
• All Shunt Y Connected Branches
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 303
)tSin(Vmv(t)
i(t)v(t)
Short-Circuit Phenomenon
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 304
Offset) (DC
TransientState Steady
t) - sin(
Z
Vm ) - tsin(
Z
Vmi(t)
(1) ) t Sin(Vmdt
di L Riv(t)
LR
-e
expression following theyields 1equation Solving
i(t)v(t)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 305
DC Current
AC Current (Symmetrical) with No AC Decay
© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 305
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 306
AC Fault Current Including the DC Offset (No AC Decay)
© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 306
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 307
Machine Reactance ( λ = L I )
AC Decay Current
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 308
Fault Current Including AC & DC Decay
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 309
1) The ANSI standards handle the AC Decay by varying machine impedance during a fault.
2) The ANSI standards handle the the dc offset by applying multiplying factors. The ANSI Terms for this current are:
•Momentary Current•Close and Latch Current•First Cycle Asymmetrical Current
ANSI
ANSI Calculation Methods
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 310
Sources•Synchronous Generators•Synchronous Motors & Condensers•Induction Machines•Electric Utility Systems (Power Grids)
ModelsAll sources are modeled by an internalvoltage behind its impedance.
E = Prefault VoltageR = Machine Armature ResistanceX = Machine Reactance (X”d, X’d, Xd)
Sources and Models of Fault Currents in ANSI Standards
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 311
Synchronous Reactance
Transient Reactance
Subtransient Reactance
Synchronous GeneratorsSynchronous Generators are modeled in three stages.
Synchronous Motors & CondensersAct as a generator to supply fault current. This current diminishes as the magnetic field in the machine decays.
Induction MachinesTreated the same as synchronous motors except they do not contribute to the fault after 2 sec.
Electric Utility SystemsThe fault current contribution tends to remain constant.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 312
½ Cycle Network
This is the network used to calculate momentary short-circuit current and protective device duties at the ½ cycle after the fault.
1 ½ to 4 Cycle Network
This network is used to calculate the interrupting short-circuit current and protective device duties 1.5-4 cycles after the fault.
30-Cycle Network
This is the network used to calculate the steady-state short-circuit current and settings for over current relays after 30 cycles.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 313
½ Cycle 1 ½ to 4 Cycle 30 Cycle
UtilityX”d X”d X”d
Turbo GeneratorX”d X”d X’d
Hydro-Gen with Amortisseur
winding
X”d X”d X’d
Hydro-Gen without Amortisseur
winding
0.75*X”d 0.75*X”d X’d
CondenserX”d X”d
Synchronous Motor
X”d 1.5*X”d
Reactance Representation forUtility and Synchronous Machine
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 314
½ Cycle 1 ½ to 4 Cycle
>1000 hp , <= 1800 rpm
X”d 1.5*X”d
>250, at 3600 rpm X”d 1.5*X”d
All others, >= 50 hp 1.2*X”d 3.0*X”d
< 50 hp 1.67*X”d
Reactance Representation for Induction Machine
Note: X”d = 1 / LRCpu
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 315
½ Cycle Currents(Subtransient
Network)
1 ½ to 4 Cycle Currents
(Transient Network)
HV Circuit BreakerClosing and Latching
CapabilityInterruptingCapability
LV Circuit Breaker Interrupting Capability ---
Fuse Interrupting Capability
---
SWGR / MCC Bus Bracing ---
Relay Instantaneous Settings
---
Device Duty and Usage of Fault Currents
from Different Networks
30 Cycle currents are used for determining overcurrent settings.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 316
MFm is calculated based on:• Fault X/R (Separate R & X Networks)• Location of fault (Remote / Local generation)
SC Current Duty Device Rating
HV CB Asymmetrical RMSCrest
C&L RMSC&L RMS
HV Bus Asymmetrical RMSCrest
Asymmetrical RMSCrest
LV Bus Symmetrical RMSAsymmetrical RMS
Symmetrical RMSAsymmetrical RMS
Comparisons of Momentary capability (1/2 Cycle)
Momentary Multiplying Factor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 317
SC Current Duty Device Rating
HV CBAdj. Symmetrical RMS* Adj. Symmetrical RMS*
LV CB & FuseAdj. Symmetrical RMS*** Symmetrical RMS
Comparisons of Interrupting Capability (1 ½ to 4 Cycle)
MFi is calculated based on:• Fault X/R (Separate R & X Networks)• Location of Fault (Remote / Local generation)• Type and Rating of CB
Interrupting Multiplying Factor
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 318
Calculate ½ Cycle Current (Imom, rms, sym) using ½ Cycle Network.
• Calculate X/R ratio and Multiplying factor MFm
• Imom, rms, Asym = MFm * Imom, rms, sym
HV CB Closing and Latching Duty
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 319
Calculate 1½ to 4 Cycle Current (Imom, rms, sym) using ½ Cycle Network.
• Determine Local and Remote contributions (A “local” contribution is fed predominantly from generators through no more than one transformation or with external reactances in series that is less than 1.5 times generator subtransient reactance. Otherwise the contribution is defined as “remote”).
• Calculate no AC Decay ratio (NACD) and multiplying factor MFi
NACD = IRemote / ITotal
ITotal = ILocal + IRemote
(NACD = 0 if all local & NACD = 1 if all remote)
• Calculate Iint, rms, adj = MFi * Iint, rms, Symm
HV CB Interrupting Duty
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 320
• CB Interrupting kA varies between Max kA and Rated kA as applied kV changes – MVAsc capability.
• ETAP’s comparison between CB Duty of Adj. Symmetrical kA and CB capability of Adjusted Int. kA verifies both symmetrical and asymmetrical rating.
• The Option of C37.010-1999 standard allows user to specify CPT.
• Generator CB has higher DC rating and is always compared against maximum through SC kA.
HV CB Interrupting Capability
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 321
LV CB Interrupting Duty
• LV CB take instantaneous action.
• Calculate ½ Cycle current Irms, Symm (I’f) from the ½
cycle network.
• Calculate X/R ratio and MFi (based on CB type).
• Calculate adjusted interrupting current Iadj, rms, symm =
MFi * Irms, Symm
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 322
Calculate ½ Cycle current Iint, rms, symm from ½ Cycle Network.
• Same procedure to calculate Iint, rms, asymm as for CB.
Fuse Interrupting Duty
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 323
L-G FaultsL-G Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 324
Symmetrical Components
L-G Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 325
Sequence Networks
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 326
0
ZZZ
V3I
I3I
021
efaultPrf
af 0
g Zif
L-G Fault Sequence Network Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 327
21
efaultPrf
aa
ZZ
V3I
II12
L-L Fault Sequence Network Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 328
0
ZZZZ
Z
VI
I0III
20
201
efaultPrf
aaaa 012
g Zif
L-L-G Fault Sequence Network Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 329
Transformer Zero Sequence Connections
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 330
grounded.
solidly areer transformConnected Y/
or Generators if case thebemay This
I
: then trueare conditions thisIf
&
: ifgreater
becan faultsG -L case. severemost
theisfault phase-3 aGenerally
1f3
1021
fI
ZZZZ
Solid Grounded Devices and L-G Faults
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 331
Complete reports that include individual branch contributions for:
•L-G Faults
•L-L-G Faults
•L-L Faults
One-line diagram displayed results that include:
•L-G/L-L-G/L-L fault current contributions
•Sequence voltage and currents
•Phase Voltages
Unbalanced Faults Display & Reports
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 332© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 332
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 333© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 333
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 334
SC Study Case Info Page
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 335
SC Study Case Standard Page
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 336
Tolerance Adjustments
•Transformer Impedance
•Reactor Resistance
•Overload Heater Resistance Temperature
Corrections
•Transmission Line Resistance
•Cable Resistance
Adjust Fault Impedance
•L-G fault Impedance
SC Study Case Adjustments Page
Length Adjustments
•Cable Length
•Transmission Line Length
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 337
ToleranceLengthLength
ToleranceLengthLength
ToleranceZZ
onLineTransmissionLineTransmissi
CableCable
rTransformerTransforme
)1(*'
)1(*'
)1(*'
Adjustments can be applied Individually or Globally
Tolerance Adjustments
Positive tolerance value is used for IEC Minimum If calculation.
Negative tolerance value is used for all other calculations.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 338
C in limit etemperatur ConductorTc
C in etemperatur base ConductorTb
etemperatur operating at ResistanceR'
retempereatu base at ResistanceR
Tb
TcRR
Tb
TcRR
BASE
BASEAlumi
BASECopper
)1.228(
)1.228(*'
)5.234(
)5.234(*''
Temperature Correction can be appliedIndividually or Globally
Temperature Correction
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 339
TransformersT1 X/R PS =12PT =12ST =12T2 X/R = 12
Power Grid U1X/R = 55
Lump1Y open grounded
Gen1Voltage ControlDesign Setting:%Pf = 85MW = 4 Max Q = 9Min Q = -3
System for SC Study
© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 339
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 340
System for SC Study
Tmin = 40, Tmax = 90
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 341
System for SC Study
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 342
Short-Circuit Alerts
• Bus Alert
• Protective Device Alert
• Marginal Device Limit
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 343
Type of Device Monitored Parameter Condition Reported
MV Bus (> 1000 Volts)Momentary Asymmetrical. rms kA Bracing Asymmetrical
Momentary Asymmetrical. crest kA Bracing Crest
LV Bus (<1000Volts)Momentary Symmetrical. rms kA Bracing Symmetrical
Momentary Asymmetrical. rms kA Bracing Asymmetrical
Bus SC Rating
Device Type ANSI Monitored Parameters IEC Monitored Parameters
LVCB Interrupting Adjusted Symmetrical. rms kA Breaking
HV CB
Momentary C&L Making
Momentary C&L Crest kA N/A
Interrupting Adjusted Symmetrical. rms kA Breaking
Fuse Interrupting Adjusted Symmetrical. rms kA Breaking
SPDT Momentary Asymmetrical. rms kA Making
SPST Switches Momentary Asymmetrical. rms kA Making
Protective Device Rating
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 344
Run a 3-phase Duty SC calculation for a fault on Bus4. The display shows the Initial Symmetrical Short-Circuit Current.
3-Phase Duty SC Results
© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 344
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 345
Unbalance Fault Calculation
© 1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit ANSI Slide 345
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 346
TEMA 7
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Transient Stability
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 348
Time Frame of Power System Dynamic Phenomena
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 349
Introduction
• TS is also called Rotor Stability, Dynamic Stability
• Electromechanical Phenomenon
• All synchronous machines must remain in synchronism with one another
• TS is no longer only the utility’s concern
• Co-generation plants face TS problems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 350
Analogy
• Which vehicles will pushed hardest?
• How much energy gained by each vehicle?
• Which direction will they move?
• Height of the hill must they climb to go over?
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 351
Introduction (cont’d)
• System protection requires consideration of:Critical Fault Clearing Time (CFCT)Critical Separation Time (CST)Fast load transferringLoad Shedding…
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 352
Causes of Instability
• Short-circuits
• Loss of utility connections
• Loss of a portion of in-plant generation
• Starting of a large motor
• Switching operations (lines or capacitors)
• Impact loading on motors
• Sudden large change in load and generation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 353
Consequences of Instability
• Synchronous machine slip poles – generator tripping
• Power swing
• Misoperation of protective devices
• Interruption of critical loads
• Low-voltage conditions – motor drop-offs
• Damage to equipment
• Area wide blackout
• …
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 354
Synchronous Machines
• Torque Equation (generator case)
T = mechanical torque
P = number of poles
air = air-gap flux
Fr = rotor field MMF
= rotor angle
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 355
Swing Equation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 356
Synchronous Machines (cont’d)• Swing Equation
M = inertia constant
D = damping constant
Pmech = input mechanical power
Pelec = output electrical power
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 357
Rotor Angle Responses
• Case 1: Steady-state stable
• Case 2: Transient stable
• Case 3: Small-signal unstable
• Case 4: First swing unstable
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 358
Power and Rotor Angle (Classical 2-Machine Example)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 359
Power and Rotor Angle (cont’d)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 360
Power and Rotor Angle (Parallel Lines)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 361
Both Lines In Service
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 362
One Line Out of Service
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 363
Equal Area Criterion
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 364
Equal Area Criterion
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 365
Equal Area - Stable
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 366
Equal Area – Unstable
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 367
Equal Area - Unstable
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 368
Power System Stability Limit
• Steady-State Stability Limit
After small disturbance, the synchronous generator reaches a steady state operating condition identical or close to the pre-disturbance
Limit: < 90
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 369
Power System Stability Limit (con’d)• Transient and Dynamic Stability Limit
After a severe disturbance, the synchronous generator reaches a steady-state operating condition without a prolonged loss of synchronism
Limit: < 180 during swing
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 370
Generator Modeling
• MachineEquivalent Model / Transient Model / Subtransient Model
• Exciter and Automatic Voltage Regulator (AVR)
• Prime Mover and Speed Governor
• Power System Stabilizer (PSS)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 371
Generator Modeling (con’d)
• Typical synchronous machine data
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 372
Factors Influencing TS
• Post-Disturbance Reactance seen from generator. Reactance Pmax
• Duration of the fault clearing time.
Fault time Rotor Acceleration Kinetic Energy Dissipation Time during deceleration
• Generator Inertia.
Inertia Rate of change of Angle Kinetic Energy
• Generator Internal Voltage Internal Voltage Pmax
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 373
Factors Influencing TS
• Generator Loading Prior To Disturbance Loading Closer to Pmax. Unstable during acceleration
• Generator Internal Reactance
Reactance Peak Power Initial Rotor Angle Dissipation Time during deceleration
• Generator Output During Fault
Function of Fault Location and Type of Fault
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 374
Solution to Stability Problems• Improve system design Increase synchronizing power
• Design and selection of rotating equipment Use of induction machines Increase moment of inertia Reduce transient reactance Improve voltage regulator and exciter
characteristics
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 375
Solution to Stability Problems• Reduction of Transmission System
Reactance
• High Speed Fault Clearing
• Dynamic Braking
• Regulate Shunt Compensation
• Steam Turbine Fast Valving
• Generator Tripping
• Adjustable Speed Synchronous Machines
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 376
Solution to Stability Problems• HVDC Link Control
• Current Injection from VSI devices
• Application of Power System Stabilizer (PSS)
• Add system protections Fast fault clearance Load Shedding System separation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 377
TEMA 8
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC
Load Flow Analysis
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 379
FLUJO DE CARGA
Cálculo de los flujos de potencia.
Diversas representaciones de las cargas.
Cálculo de los perfiles de tensión.
Corrección del factor de potencia.
Diagnóstico automático de equipos.
Corrección automática de impedancias por temperatura.
Cálculo de pérdidas activas y reactivas.
Características principales:
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 380
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 381
System ConceptsSystem Concepts
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 382
jQP
IV
SS
IVS
LL
LN
*
13
*1
3
3
Lagging Power Factor Leading Power Factor
Inductive loads have lagging Power Factors. Capacitive loads have leading Power Factors.
Current and Voltage
Power in Balanced 3-Phase Systems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 383
Leading Power Factor
Lagging Power Factor
ETAP displays lagging Power Factors as positive and leading Power Factors as negative. The Power Factor is displayed in percent.
jQ P
Leading & Lagging Power Factors
P - jQ P + jQ
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 384
B
2B
B
B
BB
MVA
)kV(Z
kV3
kVAI
B
actualpu
B
actualpu
Z
ZZ
I
II
B
actualpu
B
actualpu
S
SS
V
VV
B
2B
B
B
BB
S
VZ
V3
SI
ZI3V
VI3S If you have two bases:
Then you may calculate the other two by using the relationships enclosed in brackets. The different bases are:
•IB (Base Current)
•ZB (Base Impedance)
•VB (Base Voltage)
•SB (Base Power)
ETAP selects for LF:
•100 MVA for SB which is fixed for the entire system.
•The kV rating of reference point is used along with the transformer turn ratios are applied to determine the base voltage for different parts of the system.
3-Phase Per Unit System
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 385
Example 1: The diagram shows a simple radial system. ETAP converts the branch impedance values to the correct base for Load Flow calculations. The LF reports show the branch impedance values in percent. The transformer turn ratio (N1/N2) is 3.31 and the X/R = 12.14
2B
1B kV
2N
1NkV
Transformer Turn Ratio: The transformer turn ratio is used by ETAP to determine the base voltage for different parts of the system. Different turn ratios are applied starting from the utility kV rating.
To determine base voltage use:
2
pu
pu
RX
1
RX
ZX
Transformer T7: The following equations are used to find the impedance of transformer T7 in 100 MVA base.
RX
xR pu
pu
1BkV
2BkV
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 386
Impedance Z1: The base voltage is determined by using the transformer turn ratio. The base impedance for Z1 is determined using the base voltage at Bus5 and the MVA base.
06478.0)14.12(1
)14.12(065.0X
2pu
005336.014.12
06478.0R pu
The transformer impedance must be converted to 100 MVA base and therefore the following relation must be used, where “n” stands for new and “o” stands for old.
)3538.1j1115.0(5
100
5.13
8.13)06478.0j1033.5(
S
S
V
VZZ
23
oB
nB
2
nB
oBo
punpu
38.135j15.11Z100Z% pu
0695.431.3
5.13
2N1N
kVV utility
B
165608.0100
)0695.4(
MVA
VZ
22B
B
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 387
8.603j38.60Z100Z% pu
)0382.6j6038.0(1656.0
)1j1.0(
Z
ZZ
B
actualpu
The per-unit value of the impedance may be determined as soon as the base impedance is known. The per-unit value is multiplied by one hundred to obtain the percent impedance. This value will be the value displayed on the LF report.
The LF report generated by ETAP displays the following percent impedance values in 100 MVA base
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 388
Load Flow AnalysisLoad Flow Analysis
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 389
Load Flow Problem• Given
– Load Power Consumption at all buses
– Configuration
– Power Production at each generator
• Basic Requirement
– Power Flow in each line and transformer
– Voltage Magnitude and Phase Angle at each bus
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 390
Load Flow Studies• Determine Steady State Operating Conditions
– Voltage Profile
– Power Flows
– Current Flows
– Power Factors
– Transformer LTC Settings
– Voltage Drops
– Generator’s Mvar Demand (Qmax & Qmin)
– Total Generation & Power Demand
– Steady State Stability Limits
– MW & Mvar Losses
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 391
Size & Determine System Equipment & Parameters• Cable / Feeder Capacity
• Capacitor Size
• Transformer MVA & kV Ratings (Turn Ratios)
• Transformer Impedance & Tap Setting
• Current Limiting Reactor Rating & Imp.
• MCC & Switchgear Current Ratings
• Generator Operating Mode (Isochronous / Droop)
• Generator’s Mvar Demand
• Transmission, Distribution & Utilization kV
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 392
Optimize Operating Conditions• Bus Voltages are Within Acceptable Limits
• Voltages are Within Rated Insulation Limits of Equipment
• Power & Current Flows Do Not Exceed the Maximum Ratings
• System MW & Mvar Losses are Determined
• Circulating Mvar Flows are Eliminated
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 393
Assume VR
Calc: I = Sload / VR
Calc: Vd = I * Z
Re-Calc VR = Vs - Vd
Calculation Process
• Non-Linear System
• Calculated Iteratively
– Assume the LoadVoltage (Initial Conditions)
– Calculate the Current I
– Based on the Current,Calculate Voltage Drop Vd
– Re-Calculate Load Voltage VR
– Re-use Load Voltage as initial condition until the results are within the specified precision.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 394
1. Accelerated Gauss-Seidel Method
• Low Requirements on initial values, but slow in speed.
2. Newton-Raphson Method
• Fast in speed, but high requirement on initial values.
• First order derivative is used to speed up calculation.
3. Fast-Decoupled Method
• Two sets of iteration equations: real power – voltage angle, reactive power – voltage magnitude.
• Fast in speed, but low in solution precision.
• Better for radial systems and systems with long lines.
Load Flow Calculation Methods
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 395
kV
kVAFLA
kV
kVAFLA
EffPF
HP
EffPF
kWkVA
Rated
Rated
RatedRated
1
33
7457.0
Where PF and Efficiency are taken at 100 % loading conditions
kV
kVA1000I
)kV3(
kVA1000I
kVA
kWPF
)kVar()kW(kVA
1
3
22
Load Nameplate Data
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 396
Constant Power Loads
• In Load Flow calculations induction, synchronous and lump loads are treated as constant power loads.
• The power output remains constant even if the input voltage changes (constant kVA).
• The lump load power output behaves like a constant power load for the specified % motor load.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 397
• In Load Flow calculations Static Loads, Lump Loads (% static), Capacitors and Harmonic Filters and Motor Operated Valves are treated as Constant Impedance Loads.
• The Input Power increases proportionally to the square of the Input Voltage.
• In Load Flow Harmonic Filters may be used as capacitive loads for Power Factor Correction.
• MOVs are modeled as constant impedance loads because of their operating characteristics.
Constant Impedance Loads
© 1996-2008 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 397
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 398
• The current remains constant even if the voltage changes.
• DC Constant current loads are used to test Battery discharge capacity.
• AC constant current loads may be used to test UPS systems performance.
• DC Constant Current Loads may be defined in ETAP by defining Load Duty Cycles used for Battery Sizing & Discharge purposes.
Constant Current Loads
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 399
Constant Current Loads
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 400
Exponential Load
Polynomial Load
Comprehensive Load
Generic Loads
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 401
Feedback Voltage •AVR: Automatic Voltage Regulation•Fixed: Fixed Excitation (no AVR action)
Generator Operation Modes
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 402
Governor Operating Modes• Isochronous: This governor setting allows the
generator’s power output to be adjusted based on the system demand.
• Droop: This governor setting allows the generator to be Base Loaded, meaning that the MW output is fixed.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 403
Isochronous Mode
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 404
Droop Mode
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 405
Droop Mode
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 406
Droop Mode
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 407
Adjusting Steam Flow
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 408
Adjusting Excitation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 409
Swing Mode•Governor is operating in Isochronous mode•Automatic Voltage Regulator
Voltage Control•Governor is operating in Droop Mode•Automatic Voltage Regulator
Mvar Control•Governor is operating in Droop Mode•Fixed Field Excitation (no AVR action)
PF Control•Governor is operating in Droop Mode•AVR Adjusts to Power Factor Setting
In ETAP Generators and Power Grids have four operating modes that are used in Load Flow calculations.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 410
• If in Voltage Control Mode, the limits of P & Q are reached, the model is changed to a Load Model (P & Q are kept fixed)
• In the Swing Mode, the voltage is kept fixed. P & Q can vary based on the Power Demand
• In the Voltage Control Mode, P & V are kept fixed while Q & are varied
• In the Mvar Control Mode, P and Q are kept fixed while V & are varied
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 411
Generator Capability Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 412
Generator Capability Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 413
Generator Capability Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 414
Field Winding Heating Limit
Armature Winding Heating Limit
Machine Rating (Power Factor Point)
Steady State Stability Curve
Maximum & Minimum Reactive Power
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 415
Field Winding Heating Limit Machine Rating
(Power Factor Point)
Steady State Stability Curve
Generator Capability Curve
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 416
Load Flow Loading Page
Generator/Power Grid Rating Page
10 Different Generation Categories for Every Generator or Power Grid in the System
Generation Categories
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 417
X
V)*COS(
X
*VVQ
)(*SINX
*VVP
X
V)(*COS
X
*VVj)(*SIN
X
*VV
jQPI*VS
22
2121
2121
22
2121
2121
222
111
VV
VV
Power Flow
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 418
Example: Two voltage sources designated as V1 and V2 are connected as shown. If V1= 100 /0° , V2 = 100 /30° and X = 0 +j5 determine the power flow in the system.
I
var536535.10X|I|
268j1000)68.2j10)(50j6.86(IV
268j1000)68.2j10(100IV
68.2j10I
5j
)50j6.86(0j100
X
VVI
22
*2
*1
21
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 419
2
1
0
1
Real Power FlowReactive Power Flow
Power Flow1
2
V E( )
Xsin
V E( )
Xcos
V2
X
0
The following graph shows the power flow from Machine M2. This machine behaves as a generator supplying real power and absorbing reactive power from machine M1.
S
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 420
ETAP displays bus voltage values in two ways
•kV value
•Percent of Nominal Bus kV
%83.97100%
5.13
min
alNo
Calculated
Calculated
kV
kVV
kV 8.13min alNokV
%85.96100%
03.4
min
alNo
Calculated
Calculated
kV
kVV
kV 16.4min alNokV
For Bus4:
For Bus5:
Bus Voltage
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 421
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 422
Lump Load Negative Loading
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 423
Load Flow Adjustments• Transformer Impedance
– Adjust transformer impedance based on possible length variation tolerance
• Reactor Impedance– Adjust reactor impedance based on specified tolerance
• Overload Heater– Adjust Overload Heater resistance based on specified tolerance
• Transmission Line Length– Adjust Transmission Line Impedance based on possible length
variation tolerance
• Cable Length– Adjust Cable Impedance based on possible length variation tolerance
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 424
Adjustments applied
•Individual
•Global
Temperature Correction
• Cable Resistance
• Transmission LineResistance
Load Flow Study Case Adjustment Page
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 425
Allowable Voltage DropNEC and ANSI C84.1
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 426
Load Flow Example 1 Part 1
© 1996-2009 Operation Technology, Inc. - Workshop Notes: Load Flow AnalysisSlide 426
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 427
Load Flow Example 1 Part 2
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 428
Load Flow Alerts
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 429
Bus Alerts Monitor Continuous Amps
Cable Monitor Continuous Amps
Reactor Monitor Continuous Amps
Line Monitor Line Ampacity
Transformer Monitor Maximum MVA Output
UPS/Panel Monitor Panel Continuous Amps
Generator Monitor Generator Rated MW
Equipment Overload Alerts
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 430
Protective Devices Monitored parameters % Condition reported
Low Voltage Circuit Breaker Continuous rated Current OverLoad
High Voltage Circuit Breaker Continuous rated Current OverLoad
Fuses Rated Current OverLoad
Contactors Continuous rated Current OverLoad
SPDT / SPST switches Continuous rated Current OverLoad
Protective Device Alerts
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 431
If the Auto Display feature is active, the Alert View Window will appear as soon as the Load Flow calculation has finished.
© 1996-2009 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 431
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 432
Advanced LF TopicsAdvanced LF Topics
Load Flow Convergence
Voltage Control
Mvar Control
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 433
Load Flow Convergence
• Negative Impedance
• Zero or Very Small Impedance
• Widely Different Branch Impedance Values
• Long Radial System Configurations
• Bad Bus Voltage Initial Values
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 434
Voltage Control
• Under/Over Voltage Conditions must be fixed for proper equipment operation and insulation ratings be met.
• Methods of Improving Voltage Conditions:
– Transformer Replacement
– Capacitor Addition
– Transformer Tap Adjustment
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 435
Under-Voltage Example• Create Under Voltage
Condition
– Change Syn2 Quantity to 6. (Info Page, Quantity Field)
– Run LF
– Bus8 Turns Magenta (Under Voltage Condition)
• Method 1 - Change Xfmr
– Change T4 from 3 MVA to 8 MVA, will notice slight improvement on the Bus8 kV
– Too Expensive and time consuming
• Method 2 - Shunt Capacitor
– Add Shunt Capacitor to Bus8
– 300 kvar 3 Banks
– Voltage is improved
• Method 3 - Change Tap
– Place LTC on Primary of T6
– Select Bus8 for Control Bus
– Select Update LTC in the Study Case
– Run LF
– Bus Voltage Comes within specified limits
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 436
Mvar Control
• Vars from Utility
– Add Switch to CAP1
– Open Switch
– Run LF
• Method 1 – Generator
– Change Generator from Voltage Control to Mvar Control
– Set Mvar Design Setting to 5 Mvars
• Method 2 – Add Capacitor
– Close Switch
– Run Load Flow
– Var Contribution from the Utility reduces
• Method 3 – Xfmr MVA
– Change T1 Mva to 40 MVA
– Will notice decrease in the contribution from the Utility
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 437
Panel SystemsPanel Systems
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 438
Panel Boards• They are a collection of branch circuits
feeding system loads
• Panel System is used for representing power and lighting panels in electrical systems
Click to drop once on OLVDouble-Click to drop multiple panels
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 439
A panel branch circuit load can be modeled as an internal or external load
Advantages:1. Easier Data Entry2. Concise System Representation
Representation
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 440
Pin 0 is the top pin of the panel ETAP allows up to 24 external load connections
Pin Assignment
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 441
Assumptions
• Vrated (internal load) = Vrated (Panel Voltage)
• Note that if a 1-Phase load is connected to a 3-Phase panel circuit, the rated voltage of the panel circuit is (1/√3) times the rated panel voltage
• The voltage of L1 or L2 phase in a 1-Phase 3-Wire panel is (1/2) times the rated voltage of the panel
• There are no losses in the feeders connecting a load to the panel
• Static loads are calculated based on their rated voltage
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 442
Line-Line ConnectionsLoad Connected Between Two Phases of a3-Phase System
A
B
C
Load
IBCIC = -IBC
A
B
C
LoadB
IB = IBC
Angle by which load current IBC lags the load voltage = θ Therefore, for load connected between phases B and C: SBC = VBC.IBC
PBC = VBC.IBC.cos θ
QBC = VBC.IBC.sin θ
For load connected to phase B SB = VB.IBPB = VB.IB.cos (θ - 30)QB = VB.IB.sin (θ - 30) And, for load connected to phase C SC = VC.ICPC = VC.IC.cos (θ + 30)QC = VC.IC.sin (θ + 30)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 443
3-Phase 4-Wire Panel3-Phase 3-Wire Panel1-Phase 3-Wire Panel1-Phase 2-Wire Panel
NEC SelectionA, B, C from top to bottom or left to right from the front of the panel
Phase B shall be the highest voltage (LG) on a 3-phase, 4-wire delta connected system (midpoint grounded)
Info Page
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 444
Intelligent kV CalculationIf a 1-Phase panel is connected to a 3-Phase bus having a nominal voltage equal to 0.48 kV, the default rated kV of the panel is set to (0.48/1.732 =) 0.277 kV
For IEC, Enclosure Type is Ingress Protection (IPxy), where IP00 means no protection or shielding on the panel
Select ANSI or IEC Breakers or Fuses from Main Device Library
Rating Page
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 445
Schedule Page
Circuit Numbers with Column Layout
Circuit Numbers with
Standard Layout
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 446
Description TabFirst 14 load items in the list are based on NEC 1999Last 10 load types in the Panel Code Factor Table are user-definedLoad Type is used to determine the Code Factors used in calculating the total panel loadExternal loads are classified as motor load or static load according to the element typeFor External links the load status is determined from the connected load’s demand factor status
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 447
Rating Tab
Enter per phase VA, W, or Amperes for this load.
For example, if total Watts for a 3-phase load are 1200, enter W as 400 (=1200/3)
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 448
Loading Tab
For internal loads, enter the % loading for the selected loading category
For both internal and external loads, Amp values are calculated based on terminal bus nominal kV
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 449
Protective Device Tab
Library Quick Pick - LV Circuit Breaker (Molded Case, with Thermal Magnetic Trip Device) or
Library Quick Pick – Fuse will appear depending on the Type of protective device selected.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 450
Feeder Tab
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 451
Action Buttons
Copy the content of the selected row to clipboard. Circuit number, Phase, Pole, Load Name, Link and State are not copied.
Paste the entire content (of the copied row) in the selected row. This will work when the Link Type is other than space or unusable, and only for fields which are not blocked.
Blank out the contents of the entire selected row.
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 452
Summary Page
Continuous Load – Per Phase and Total
Non-Continuous Load – Per Phase and Total
Connected Load – Per Phase and Total (Continuous + Non-Continuous Load)
Code Demand – Per Phase and Total
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 453
Output Report
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 454
Panel Code Factors
Code demand load depends on Panel Code Factors
The first fourteen have fixed formats per NEC 1999
Code demand load calculation for internal loads are done for each types of load separately and then summed up