Unit 31 Three-Phase Alternators
Objectives:• Discuss the operation of a three-phase
alternator.• Explain the effect of rotation speed on
frequency.• Explain the effect of field excitation on
output voltage.
![Page 2: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/2.jpg)
Unit 31 Three-Phase Alternators
Power Generation• Three-phase AC generators called
alternators provide most of the electrical power we use today.
• Electrical power companies use alternators rated in gigawatts.
• 1 gigawatt = 1,000,000,000 watts
![Page 3: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/3.jpg)
Unit 31 Three-Phase Alternators
Power Generation• The entire North American continent is
powered by AC generators connected together in parallel.
• These alternators are powered by steam turbines.
• The turbines called prime movers use oil, coal, natural gas, or nuclear energy.
![Page 4: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/4.jpg)
Unit 31 Three-Phase Alternators
Construction• Alternators use the same operating
principle as direct-current generators.• However, alternators have no commutator
to change the armature AC into DC.• Most alternators are three-phase.
![Page 5: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/5.jpg)
Unit 31 Three-Phase Alternators
Basic design of a three-phase armature.
![Page 6: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/6.jpg)
Unit 31 Three-Phase Alternators
Construction• There are two basic types of alternators:
– revolving-armature-type alternators– Revolving-field-type alternators
![Page 7: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/7.jpg)
Unit 31 Three-Phase Alternators
Revolving armature design.
![Page 8: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/8.jpg)
Unit 31 Three-Phase Alternators
Revolving field design.
![Page 9: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/9.jpg)
Unit 31 Three-Phase Alternators
Revolving-Armature-Type Alternators• The revolving-armature type is the least
used of the two basic types.• This type uses sliprings instead of a
commutator.• The armature windings are rotated inside
a magnetic field.• This type has very limited output power.
![Page 10: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/10.jpg)
Unit 31 Three-Phase Alternators
Revolving-Field-Type Alternators• The revolving-field type uses a stationary
armature called a stator and a rotating magnetic field.
• This design permits much higher power output.
![Page 11: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/11.jpg)
Unit 31 Three-Phase Alternators
Rotor• The rotor is the rotating part of an
alternator.• The rotor is an electromagnet that
provides the magnetic field needed to induce a voltage into the stator windings.
• Excitation current (DC) in the rotor is required to establish the magnetic field.
![Page 12: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/12.jpg)
Unit 31 Three-Phase Alternators
The alternator produces three sine wave voltages 120 out of phase with each other.
![Page 13: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/13.jpg)
Unit 31 Three-Phase Alternators
Rotator pole pieces become electromagnets.
![Page 14: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/14.jpg)
Unit 31 Three-Phase Alternators
Brushless Exciter• Most large alternators use an exciter that
contains no brushes.• A separate small alternator of the
armature type is added to the shaft of the rotor. The armature rotates between wound electromagnets.
• This current is then rectified and used as excitation current.
![Page 15: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/15.jpg)
Unit 31 Three-Phase Alternators
The brushless exciter uses stationary electromagnets.
![Page 16: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/16.jpg)
Unit 31 Three-Phase Alternators
Brushless exciter schematic.
![Page 17: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/17.jpg)
Unit 31 Three-Phase Alternators
Frequency• The output frequency (Hz) of an
alternator is determined by two factors:1. the number of stator poles2. the speed of rotation
![Page 18: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/18.jpg)
Unit 31 Three-Phase Alternators
RPM STATOR POLES
3600 2
1800 4
1200 6
900 8
![Page 19: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/19.jpg)
Unit 31 Three-Phase Alternators
Output Voltage• Three factors that determine the output
voltage of an alternator are:1. the conductor length of the armature or
stator winding.2. the strength of the rotator magnetic
field.3. the speed of the rotor.
![Page 20: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/20.jpg)
Unit 31 Three-Phase Alternators
Paralleling Alternators• Before two alternators can be connected
in parallel:– the output voltage of the two machines
should be the same.– the phase rotation of the machines must
be the same.– the output voltages must be in phase.
![Page 21: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/21.jpg)
Unit 31 Three-Phase Alternators
Phase Rotation• Three lamps connected between the two
alternators can be used to test for phase rotation.
• A synchroscope can be used to determine phase rotation and difference of frequency between two alternators.
![Page 22: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/22.jpg)
Unit 31 Three-Phase Alternators
Determining phase rotation using lights.
![Page 23: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/23.jpg)
Unit 31 Three-Phase Alternators
Checking phase alignment using a voltmeter.
![Page 24: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/24.jpg)
Unit 31 Three-Phase Alternators
Field Discharge Protection• When the DC excitation current is
disconnected, the collapsing field can cause contacts to arc and damages to the rotor windings.
• Two devices used to prevent a high voltage being induced in the rotor when the DC excitation current is stopped are a field-discharge resistor and a diode.
![Page 25: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/25.jpg)
Unit 31 Three-Phase Alternators
Field-discharge resistor schematic switch open.
![Page 26: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/26.jpg)
Unit 31 Three-Phase Alternators
Field-discharge resistor schematic switch closed.
![Page 27: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/27.jpg)
Unit 31 Three-Phase Alternators
Field-discharge diode schematic normal flow.
![Page 28: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/28.jpg)
Unit 31 Three-Phase Alternators
Field-discharge diode schematic induced flow.
![Page 29: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/29.jpg)
Unit 31 Three-Phase Alternators
Review:1. The two basic types of three phase
alternators are: the rotating-armature type and the rotating-field type.
2. The rotating-armature type is the least used because of its limited voltage and power rating.
![Page 30: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/30.jpg)
Unit 31 Three-Phase Alternators
Review:3. The rotating-field-type alternator contains
electromagnets.4. Direct current must be supplied to the field
before the alternator can produce an output voltage.
5. The direct current supplied to the field is called excitation current.
![Page 31: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/31.jpg)
Unit 31 Three-Phase Alternators
Review:6. The output frequency of an alternator is
determined by the number of stator poles and the speed of rotation.
7. The output voltage is controlled by the amount of DC excitation current.
![Page 32: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/32.jpg)
Unit 31 Three-Phase Alternators
Review:8. Three factors that determine the output
voltage of an alternator are:a. the conductor length of the armature or
stator winding.b. the strength of the rotator magnetic
field.c. the speed of the rotor.
![Page 33: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/33.jpg)
Unit 31 Three-Phase Alternators
Review:9. Before two alternators can be connected
in parallel, the output voltage of the two machines should be the same, the phase rotation of the machines must be the same, and the output voltages must be in phase.
![Page 34: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/34.jpg)
Unit 31 Three-Phase Alternators
Review:10.Three lamps connected between the two
alternators can be used to test for phase rotation.
11.A synchroscope can be used to determine phase rotation and difference of frequency between two alternators.
![Page 35: 3 phase alternator](https://reader034.vdocuments.mx/reader034/viewer/2022052208/557d4985d8b42ae3298b48c6/html5/thumbnails/35.jpg)
Unit 31 Three-Phase Alternators
Review:12.Two devices used to prevent a high
voltage being induced in the rotor when the DC excitation current is stopped are a field-discharge resistor and a diode.
13.Many large alternators use a brushless exciter to supply direct current to the rotor winding.