ISO/IEC JTC 1/SC 25 N 1643 Date 2009-04-21 Secretary - ISO/IEC JTC 1/SC 25 - Dr.-Ing. Walter P. von Pattay Member of ZVEI FV 7 & FV 8, Germany Tel.: +49/89/923 967 57, Tfx.: +49/89/923 967 59 (on request only) EM: [email protected] Home page: ” http://sc25.iec.ch/” 2 nd Final Committee Draft ISO/IEC FCD 24764 Date: 2009-04-21 Reference number: ISO/IEC JTC 1/SC 25 N 1643 Supersedes document SC 25 N/A THIS DOCUMENT IS STILL UNDER STUDY AND SUBJECT TO CHANGE. IT SHOULD NOT BE USED FOR REFERENCE PURPOSES. ISO/IEC JTC 1/SC 25 INTERCONNECTION OF INFORMATION TECHNOLOGY EQUIPMENT Secretariat: Germany (DIN) Circulated to P- and O-members, and to technical committees and organizations in liaison for: - voting by (P-members only) 2009-08-22 Please return all votes and comments in electronic form using the attached template directly to the SC 25 Secretariat by the due date indicated. ISO/IEC 2nd FCD 24764 Title: Information technology - Generic cabling systems for Data Centres Project: 1.25.03.10 Introductory note: This FCD is distributed for approval as FDIS. The NWIP was distributed with SC 25 N 1063 and JTC 1 N 7919. It was approved as recorded in SC 25 N 942. CDs were distributed with SC 25 N 1297, N 1463 and N 1576. A 1 st FCD was distributed with SC 25 N 1603A Id did not find substantial support as recorded in SC 25 N 1633. The comments received on N 1633 have been resolved by SC 25/WG 3 at its meeting los Cabos, Mexico, 2009-03-23/27 as recorded in SC 25 N 1642. The text has been updated accordingly and is distributed with this document for approval as FDIS. REQUESTED: National Member Bodies of ISO/IEC JTC 1/SC 25 are ACTION requested to vote on this document. Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights (not listed in the draft) of which they are aware and to provide supporting documentation. Medium: Defined No. of pages: 43

Upload: others

Post on 16-May-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 Date 2009-04-21

Secretary - ISO/IEC JTC 1/SC 25 - Dr.-Ing. Walter P. von Pattay Member of ZVEI FV 7 & FV 8, Germany Tel.: +49/89/923 967 57, Tfx.: +49/89/923 967 59 (on request only) EM: [email protected]

Home page: ” http://sc25.iec.ch/”

2nd Final Committee Draft ISO/IEC FCD 24764

Date: 2009-04-21 Reference number: ISO/IEC JTC 1/SC 25 N 1643

Supersedes document SC 25 N/A

THIS DOCUMENT IS STILL UNDER STUDY AND SUBJECT TO CHANGE. IT SHOULD NOT BE USED FOR REFERENCE PURPOSES.

ISO/IEC JTC 1/SC 25 INTERCONNECTION OF INFORMATION TECHNOLOGY EQUIPMENT

Secretariat: Germany (DIN)

Circulated to P- and O-members, and to technical committees and organizations in liaison for: - voting by (P-members only)

2009-08-22

Please return all votes and comments in electronic form using the attached template

directly to the SC 25 Secretariat by the due date indicated.

ISO/IEC 2nd FCD 24764

Title: Information technology - Generic cabling systems for Data Centres

Project: 1.25.03.10

Introductory note: This FCD is distributed for approval as FDIS.

The NWIP was distributed with SC 25 N 1063 and JTC 1 N 7919. It was approved as recorded in SC 25 N 942.

CDs were distributed with SC 25 N 1297, N 1463 and N 1576. A 1st FCD was distributed with SC 25 N 1603A Id did not find substantial support as recorded in SC 25N 1633. The comments received on N 1633 have been resolved by SC 25/WG 3 at its meeting los Cabos, Mexico, 2009-03-23/27 as recorded in SC 25 N 1642. The text has been updated accordingly and is distributed with this document for approval as FDIS.

REQUESTED: National Member Bodies of ISO/IEC JTC 1/SC 25 are ACTION requested to vote on this document.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights (not listed in the draft) of which they are aware and to provide supporting documentation.

Medium: Defined

No. of pages: 43

Page 2: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 1 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

Information technology - Generic cabling systems for Data Centres

CONTENTS

Introduction ..........................................................................................................................5 1 Scope ............................................................................................................................7 2 Normative references .....................................................................................................7 3 Definitions and abbreviations ..........................................................................................8

3.1 Definitions .............................................................................................................8 3.1.7 main distribution cable ...............................................................................9

3.2 Abbreviations ........................................................................................................9 4 Conformance................................................................................................................10 5 Structure of the generic cabling system in data centres .................................................11

5.1 General ...............................................................................................................11 5.2 Functional elements.............................................................................................11 5.3 General structure and hierarchy ...........................................................................11 5.4 Cabling subsystems.............................................................................................12

5.4.1 Network access cabling subsystem ..........................................................13 5.4.2 Main distribution cabling subsystem .........................................................13 5.4.3 Zone distribution cabling subsystem .........................................................13 5.4.4 Design objectives.....................................................................................13

5.5 Accommodation of functional elements.................................................................14 5.6 Interfaces ............................................................................................................14

5.6.1 Equipment interfaces and test interfaces ..................................................14 5.6.2 Channels and links...................................................................................14

5.7 Dimensioning and configuring ..............................................................................16 5.7.1 Distributors ..............................................................................................16 5.7.2 Redundancy.............................................................................................16 5.7.3 External network interface ........................................................................17 5.7.4 Cables .....................................................................................................18 5.7.5 Equipment cords ......................................................................................18 5.7.6 Patch cords and jumpers ..........................................................................18 5.7.7 Equipment outlets ....................................................................................18 5.7.8 LDP .........................................................................................................18 5.7.9 Building entrance facilities........................................................................19

5.8 Earthing and equipotential bonding ......................................................................19 6 Channel performance in data centres ............................................................................19

6.1 General ...............................................................................................................19 6.2 Transmission performance ...................................................................................20

6.2.1 General ...................................................................................................20 6.2.2 Balanced cabling .....................................................................................20 6.2.3 Optical fibre cabling .................................................................................20

7 Reference implementations in data centres ...................................................................21 7.1 General ...............................................................................................................21 7.2 Balanced cabling .................................................................................................21

Page 3: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 2 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84 85

86

87

88

89

7.2.1 Assumptions ............................................................................................21 7.2.2 Zone distribution cabling ..........................................................................21 7.2.3 Main distribution cabling...........................................................................24 7.2.4 Network access cabling............................................................................26

7.3 Optical fibre cabling .............................................................................................28 7.3.1 Assumptions ............................................................................................28 7.3.2 Component choice ...................................................................................28 7.3.3 Optical fibre cabling channel lengths ........................................................28

8 Cable requirements in data centres ...............................................................................29 8.1 General ...............................................................................................................29 8.2 Balanced cables ..................................................................................................29 8.3 Optical fibre cables ..............................................................................................29

9 Connecting hardware requirements in data centres .......................................................29 9.1 General requirements ..........................................................................................29

9.1.1 Applicability .............................................................................................29 9.1.2 Location...................................................................................................29 9.1.3 Design .....................................................................................................29 9.1.4 Operating Environment ............................................................................29 9.1.5 Mounting..................................................................................................29 9.1.6 Installation practices ................................................................................29 9.1.7 Marking and colour Coding.......................................................................30

9.2 Connecting hardware for balanced cabling ...........................................................30 9.2.1 General requirements...............................................................................30 9.2.2 Performance marking ...............................................................................30 9.2.3 Mechanical characteristics .......................................................................30

9.3 Connecting hardware for optical fibre cabling .......................................................32 9.3.1 General requirements...............................................................................32 9.3.2 ENI requirements .....................................................................................32 9.3.3 EO requirements ......................................................................................32 9.3.4 Optical fibre pin assignments at the EO ....................................................33

10 Requirements for cords and jumpers in data centres .....................................................33 10.1 Jumpers ..............................................................................................................33 10.2 Balanced cords....................................................................................................33 10.3 Optical fibre cords ...............................................................................................33

Annex A (normative) Link performance limits ......................................................................34 A.1 General ........................................................................................................................34 A.2 Balanced cabling ..........................................................................................................35 A.3 Optical fibre cabling......................................................................................................36 Annex B (informative) Usage of high density connecting hardware within optical fibre

cabling .........................................................................................................................37 B.1 General ........................................................................................................................37 B.2 Structure of cabling subsystems....................................................................................37 Bibliography .......................................................................................................................40

Page 4: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 3 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

90

91 92

93

94

95

96

97

98

99

100

101

102

103

104 105

106

107

108 109

110 111

112

113 114

115

116 117

118

119

120

121

122

Figures

Figure 1 - Schematic relationship between the ISO/IEC 11801 series and other standards relevant for information technology cabling systems ..............................................6 Figure 2 - Structure of generic cabling within a data centre ..................................................12 Figure 3 - Hierarchical structure of generic cabling within a data centre ...............................12 Figure 4 - Example of accommodation of functional elements ..............................................14 Figure 5 - Test and equipment interfaces.............................................................................15 Figure 6 - Connection of functional elements providing redundancy .....................................17 Figure 7 – Examples of external service cabling connections to the ENI ...............................18 Figure 8 – Example of a channel with 4 connections ............................................................19 Figure 9 - Example of a system showing the location of cabling interfaces ...........................20 Figure 10 - Zone distribution cabling models........................................................................22 Figure 11 - Main distribution cabling models ........................................................................25 Figure 12 - Network access cabling models .........................................................................27 Figure 13 - Pin grouping and pair assignments at the EO, front view of fixed connector (jack) ..................................................................................................................................31 Figure 14 - Optical fibre pin assignments at the EO, front view of fixed connector ................33 Figure A. 1 - Link options ....................................................................................................35 Figure B. 1 - Examples of high density connecting hardware within main distribution cabling ...............................................................................................................................38 Figure B. 2 - Examples of high density connecting hardware at the LDP and EO within zone distribution cabling .....................................................................................................39

Tables

Table 1 – Length assumptions used in the mathematical modelling of balanced zone distribution cabling..............................................................................................................23 Table 2 - Zone distribution channel length equations ...........................................................24 Table 3 – Length assumptions used in the mathematical modelling of balanced main distribution cabling..............................................................................................................25 Table 4 - Main distribution channel length equations............................................................26 Table 5 - Network access cabling channel equations ...........................................................28 Table 6 - Connecting hardware of the type used at the ENI ..................................................30 Table 7 - Connecting hardware of the type used at the EO...................................................30

Page 5: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 4 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

123

124 125 126 127 128 129

130 131 132

134 135

137 138 139

141 142 143

145

148 149 150 151

153

155

156

157 158 159

160

161 162 163

FOREWORD

1) ISO (International Organization for Standardization) and IEC (International Electrotechnical Commission) form the specialized system for worldwide standardization. National bodies that are members of ISO or IEC participate in the development of International Standards through technical committees established by the respective organization to deal with particular fields of technical activity. ISO and IEC technical committees collaborate in fields of mutual interest. Other international organizations, governmental and non-governmental, in liaison with ISO and IEC, also take part in the work.

2) In the field of information technology, ISO and IEC have established a joint technical committee, ISO/IEC JTC 1. Draft International Standards adopted by the joint technical committee are circulated to national bodies for voting. Publication as an International Standard requires approval by at least 75 % of the national bodies casting a vote.

3) The former decisions or agreements of IEC and ISO on technical matters express, as nearly as possible, an 133 international consensus of opinion on the relevant subjects since each technical committee has representation from all interested IEC and ISO member bodies.

4) IEC, ISO and ISO/IEC publications have the form of recommendations for international use and are accepted 136 by IEC and ISO member bodies in that sense. Why on all reasonable efforts are made to ensure that the technical content of IEC, ISO and ISO/IEC publications is accurate, IEC or ISO cannot be held responsible for the way in which they are used or for any misinterpretation by any end user.

5) In order to promote international uniformity, IEC and ISO member bodies undertake to apply IEC, ISO and 140 ISO/IEC publications transparency to the maximum extent possible in their national and regional publications. Any divergence between any ISO/IEC publication and the corresponding national or regional publication should be clearly indicated in the latter.

6) ISO and IEC provide no marking procedure to indicate their approval and cannot be rendered responsible for any 144 equipment declared to be in conformity with and ISO/IEC publication.

7) All users should ensure that they have the latest edition of this publication. 146

8) No liability shall attach to IEC or ISO or its directors, employees, servants or agents including individual experts 147 and members of their technical committees and IEC or ISO member bodies for any personal injury, property damage or other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising out of the publication of, use of, or reliance upon, this ISO/IEC publication or any other IEC, ISO or ISO/IEC publications.

9) Attention is drawn to the normative references cited in this publication. Use of the referenced publications is 152 indispensable for the correct application of this publication.

10) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject of 154 patent rights. ISO and IEC shall not be held responsible for identifying any or all such patent rights.

This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment, of ISO/IEC joint technical committee 1: Information technology.

This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

This International Standard has taken into account requirements specified in application standards listed in Annex F of ISO/IEC 11801. It refers to International Standards for components and test methods whenever appropriate International Standards are available.

Page 6: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 5 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

164

165 166 167 168 169

170 171 172 173 174 175

176

178

180

182 183

185

186

187 188

189

190 191 192

193 194

195 196

———————

Introduction

Within premises, the importance of the information technology cabling infrastructure is similar to that of other fundamental building utilities such as heating, lighting and mains power. As with other utilities, interruptions to service can have serious impact. Poor quality of service due to lack of design foresight, use of inappropriate components, incorrect installation, poor administration or inadequate support can threaten an organisation's effectiveness.

Cabling within data centres comprises both application-specific and multipurpose networks that are mission-critical. Generic cabling designs in accordance with ISO/IEC 11801 have supported the development of high data rate applications based upon a defined cabling model. This International standard recognizes the benefit of generic cabling to provision multiple services and to connect large quantities of equipment within the limited space of data centre premises, and is to be used in conjunction with ISO/IEC 11801.

This International Standard provides:

a) data centre users with an application independent generic cabling system capable of 177 supporting a wide range of applications;

b) data centre users with a flexible cabling scheme such that modifications are both easy 179 and economical;

c) data centre professionals (for example, data centre architects) with guidance allowing the 181 accommodation of cabling before specific requirements are known; that is, in the initial planning either for construction or refurbishment;

d) industry and applications standardization bodies with a cabling system which supports 184 current products and provides a basis for future product development.

This International Standard specifies multi-vendor cabling, and is related to:

the associated standard covering general requirements for generic cabling within premises (ISO/IEC 11801);

standards for cabling components developed by Technical Committees of the IEC;

standards for the quality assurance, installation and administration of information technology cabling (ISO/IEC 14763-2) and testing of installed cabling (IEC 61935-1 and ISO/IEC 14763-3);

applications developed by the technical committees of IEC, subcommittees of ISO/IEC JTC 1 and study groups of ITU-T 1).

It is anticipated that the generic cabling system meeting the requirements of this International Standard will have a life expectancy up to ten years.

1) International Telecommunication Union - Telecommunications Standardization Sector.

Page 7: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 6 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

197 198 199 200

Figure 1 shows the schematic and contextual relationships between the standards produced by ISO/IEC JTC 1/SC 25 for information technology cabling, namely this and other generic cabling design standards (ISO/IEC 11801), cabling installation standards (ISO/IEC 14763-2), testing of installed cabling (IEC 61935-1 and ISO/IEC 14763-3).

ISO/IEC 11801: Information technology: Generic cabling for customer premises

ISO/IEC 24764: Information technology: Generic cabling systems for Data Centres

ISO/IEC 18010: Information technology. Pathways and spaces for customer premises cabling

ISO/IEC 14763-2: Information technology. Quality assurance, installation and administration

IEC 61935-1: Generic cabling systemsSpecifications for the testing of balanced communication cabling

IEC 60364-1: Electrical installations of buildings: Fundamental principles, assessment of general characteristics, definitions

ISO/IEC 14763-3: Information technology: Testing of optical fibre cabling

ISO/IEC 11801: Information technology: Generic cabling for customer premises

ISO/IEC 24764: Information technology: Generic cabling systems for Data Centres

ISO/IEC 18010: Information technology. Pathways and spaces for customer premises cabling

ISO/IEC 14763-2: Information technology. Quality assurance, installation and administration

IEC 61935-1: Generic cabling systemsSpecifications for the testing of balanced communication cabling

IEC 60364-1: Electrical installations of buildings: Fundamental principles, assessment of general characteristics, definitions

ISO/IEC 14763-3: Information technology: Testing of optical fibre cabling

201

202 203

Figure 1 - Schematic relationship between the ISO/IEC 11801 series and other standards relevant for information technology cabling systems

Page 8: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 7 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

204 205 206

208 209 210

211

212 213 214 215

216

218

220 221 222

223 224 225 226 227

229 230 231

232 233 234

235 236

237 238 239

240 241

242 243

244 245

INFORMATION TECHNOLOGY – GENERIC CABLING SYSTEMS FOR DATA CENTRES

1 Scope 207

This International Standard specifies generic cabling that supports a wide range of communications services for use within a data centre. It covers balanced cabling and optical fibre cabling.

This International Standard is based upon and references the requirements of ISO/IEC 11801.

This International Standard contains additional requirements that are appropriate to data centres in which the maximum distance over which communications services have to be distributed is 2 000 m. The principles of this International Standard may also be applied to data centre installations that do not fall within this range.

In addition to the requirements of ISO/IEC 11801, this International Standard specifies:

a) a modified structure and configuration for generic cabling within data centres used to 217 support existing and emerging applications;

b) a reference implementation specific to data centre infrastructures; 219

Data centres have specific pathway and space requirements that are specified in ISO/IEC 14763-2. Until ISO/IEC 14763-2 is published, relevant information may be found in ISO/IEC 18010.

Safety (electrical safety and protection, fire, optical power etc.) and electromagnetic compatibility (EMC) requirements are outside the scope of this International Standard and are covered by other standards and regulations. However, information given in this International Standard and those identified in Figure 1 can be of assistance in meeting these other standards and regulations.

2 Normative references 228

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

ISO/IEC 11801, Information technology – Generic cabling for customer premises NOTE 1 Parts of this international standard depend on the publication of amendments to ISO/IEC 11801. Until these are published conformance can not be met for links.

NOTE 2 References to ISO/IEC 11801:2008 refer to ISO/IEC Ed.2.1 plus Amendment 2, presently voted on as FPDAM with SC 25 N 1645.

ISO/IEC 14763-2 (under consideration), Information technology - Implementation and operation of customer premises cabling - Part 2: Quality assurance, installation and administration

ISO/IEC 14763-3, Information technology - Implementation and operation of customer premises cabling - Part 3: Testing of optical fibre cabling

IEC 60603-7, Connectors for electronic equipment - Part 7: Detail specification for 8-way, unshielded, free and fixed connectors

IEC 60603-7-1, Connectors for electronic equipment - Part 7-1: Detail specification for 8-way, shielded free and fixed connectors with common mating features, with assessed quality

Page 9: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 8 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

246 247

248 249

250 251

252 253 254

255 256

257 258 259

260 261

262 263 264

265 266 267

268 269 270

271

272

273 274 275

276 277

280 281

283 284 285

IEC 60603-7-2, Connectors for electronic equipment - Part 7-2: Detail specification for 8-way, unshielded, free and fixed connectors, for data transmissions with frequencies up to 100 MHz

IEC 60603-7-3, Connectors for electronic equipment - Part 7-3: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with frequencies up to 100 MHz

IEC 60603-7-4, Connectors for electronic equipment - Part 7-4: Detail specification for 8-way, unshielded, free and fixed connectors, for data transmissions with frequencies up to 250 MHz

IEC 60603-7-41, Connectors for electronic equipment - Part 7-41: Detail specification for 8-way, unshielded, free and fixed connectors, for data transmission with frequencies up to 500 MHz (under consideration)

IEC 60603-7-5, Connectors for electronic equipment - Part 7-5: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with frequencies up to 250 MHz

IEC 60603-7-51, Connectors for electronic equipment - Part 7-51: Detail specification for 8-way, shielded, free and fixed connectors, for data transmission with frequencies up to 500 MHz (under consideration)

IEC 60603-7-7, Connectors for electronic equipment - Part 7-7: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with frequencies up to 600 MHz

IEC 60603-7-71, Connectors for electronic equipment - Part 7-71: Detail specification for 8-way, shielded, free and fixed connectors, for data transmission with frequencies up to 1 000 MHz (under consideration)

IEC 61076-3-104, Connectors for electronic equipment - Product requirements - Part 3-104: Detail specification for 8-way, shielded free and fixed connectors for data transmissions with frequencies up to 1 000 MHz

IEC 61156-5, Multicore and symmetrical pair/quad cables for digital communications - Part 5: Symmetrical pair/quad cables with transmission characteristics up to 1 000 MHz-horizontal floor wiring - Sectional specification

IEC 61754-7, Fibre optic connector interfaces – Part 7: Type MPO connector family

IEC 61754-20, Fibre optic connector interfaces - Part 20: Type LC connector family

IEC 61755-3-2, Fibre optic connector optical interfaces - Part 3-2: Optical interface, 2,5 mm and 1,25 mm diameter cylindrical full zirconia ferrules for 8 degrees angled-PC single mode fibres

IEC 61935-1, Generic specification for the testing of elements of generic cabling in accordance with ISO/IEC 11801 – Part 1: Test methods

3 Definitions and abbreviations 278

3.1 Definitions 279

For the purposes of this International Standard the following definitions apply in addition to those of ISO/IEC 11801.

3.1.1 282 cabled optical fibre Category system of defining requirements for the cabled optical fibre performance within optical fibre channels and links.

Page 10: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 9 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

287 288 289

291 292 293

295 296 297

299 300

302 303 304

306 307

309 310 311 312

314 315

317 318

320 321 322 323

325 326

327

328

329

330

3.1.2 286 equipment outlet fixed connecting device for terminating the zone distribution cabling and providing the interface to the equipment cabling

3.1.3 290 fixed zone distribution cable cable connecting the zone distributor to either the equipment outlet or, if present, the local distribution point

3.1.4 294 local distribution point connection point in the zone distribution cabling subsystem between a zone distributor and an equipment outlet

3.1.5 298 local distribution point cable cable connecting a local distribution point to an equipment outlet

3.1.6 301 local distribution point link transmission path between a local distribution point and the interface at the other end of the fixed zone distribution cable including the connecting hardware at each end

3.1.7 305 main distribution cable cable connecting the main distributor to the zone distributor

3.1.8 308

main distributor distributor used to make connections between the main distribution cabling subsystem, network access cabling subsystem and cabling subsystems specified in ISO/IEC 11801 and active equipment

3.1.9 313 network access cable cable connecting the external network interface to the main distributor or zone distributor

3.1.10 316 zone distribution cable cable connecting the zone distributor to the equipment outlet(s) or local distribution point(s)

3.1.11 319 zone distributor distributor used to make connections between the main distribution cabling subsystem, zone distribution cabling subsystem, network access cabling subsystem and cabling subsystems specified in ISO/IEC 11801 series and active equipment

3.2 Abbreviations 324

For the purposes of this International Standard the following abbreviations apply in addition to those of ISO/IEC 11801.

BEF Building entrance facility

ENI External network interface

EO Equipment outlet

LDP Local distribution point

Page 11: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 10 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

331

332

333

335

336

337 338 339

340 341

342 343 344 345

346 347 348

349 350

351 352

353

354 355

356 357 358 359 360

361 362

363 364 365 366

367 368

MD Main distributor

OE EQP Opto-electronic equipment

ZD Zone distributor

4 Conformance 334

For a cabling system to conform to this International Standard:

a) The configuration and structure shall conform to the requirements of Clause 5;

b) The performance of balanced channels shall conform to the transmission performance and environmental requirements of Clause 6. This shall be achieved by one of the following:

1) a channel design and implementation ensuring that the prescribed channel performance is met;

2) Attachment of appropriate components to a link design meeting the prescribed performance class of Clause 6 and Annex A Channel performance shall be ensured where a channel is created by adding more than one cord to either end of a link meeting the requirements of Clause 6 and Annex A;

3) Using the reference implementations of Clause 7 and compatible cabling components conforming to the requirements of Clauses 8, 9 and 10, based upon a statistical approach of performance modelling.

c) The implementation and performance of optical fibre cabling channels shall meet the requirements specified in Clause 6.

d) The interfaces to the cabling shall conform to the requirements of Clause 9 with respect to mating interfaces and performance

e) If present, screens shall be handled as specified in Clause 11 of ISO/IEC 11801:2008.

f) Regulations on safety and EMC applicable at the location of the installation shall be met.

Test methods to assess conformance with the channel and link requirements of Clause 6 and Annex A respectively are specified in IEC 61935-1 for balanced cabling and ISO/IEC 14763-3 for optical cabling. The treatment of measured results that fail to meet the requirements of this clause, or lie within the relevant measurement accuracy, shall be clearly documented within a quality plan as described in ISO/IEC 14763-2.

Installation and administration of cabling in accordance with this International standard shall be undertaken in accordance with ISO/IEC 14763-2.

This standard does not specify which tests and sampling levels should be adopted. The test parameters to be measured and the sampling levels to be applied for a particular installation shall be defined in the installation specification and quality plans for that installation prepared in accordance with ISO/IEC 14763-2.

Specifications marked "ffs" (for further study) in ISO/IEC 11801 are preliminary and are not required for conformance to this International Standard.

Page 12: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 11 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

371 372 373

374 375

376 377 378 379 380

382 383

393

395 396 397 398

399 400 401 402

403 404

405 406 407 408 409 410

5 Structure of the generic cabling system in data centres 369

5.1 General 370

This clause identifies the functional elements of generic cabling for data centres, describes how they are connected together to form subsystems and identifies the interfaces at which application-specific components are connected to the generic cabling.

Applications listed in Annex F of ISO/IEC 11801:2008 are supported by connecting active equipment at the external network interfaces, equipment outlets and the distributors.

The structured cabling system specified by this International Standard is intended to restrict the use of cords for point-to-point cabling within data centres, which can be detrimental to the administration and operation of the data centre. Exceptions are permitted between equipment located in close proximity or between equipment that cannot communicate over the generic cabling system.

5.2 Functional elements 381

In addition to the distributors specified in ISO/IEC 11801, this standard specifies the following functional elements and interfaces of generic cabling:

a) external network interface (ENI); 384

b) network access cable; 385

c) main distributor (MD); 386

d) main distribution cable; 387

e) zone distributor (ZD); 388

f) zone distribution cable; 389

g) local distribution point (LDP); 390

h) local distribution point cable (LDP cable); 391

i) equipment outlet (EO). 392

Groups of these functional elements are connected together to form cabling subsystems.

5.3 General structure and hierarchy 394

Generic cabling systems in data centres contain up to three cabling subsystems: network access cabling, main distribution cabling and zone distribution cabling. Where present within the premises, a distributor in accordance with ISO/IEC 11801 is connected to the generic cabling within the data centre using the network access cabling.

The cabling subsystems are connected together to create a generic cabling system with a structure as shown in Figure 2. The composition of the cabling subsystems is described in 5.4.1, 5.4.2 and 5.4.3. The functional elements of the cabling subsystems are interconnected to form a basic hierarchical topology as shown in Figure 3.

Where the functions of distributors are combined (see 5.7.1) the intermediate cabling subsystem(s) are not required.

Connections between cabling subsystems are either active, requiring application-specific equipment, or passive. Connection to application-specific equipment at an MD and ZD adopts either an interconnect or a cross-connect approach (see ISO/IEC 11801). Connection to application-specific equipment at an ENI and EO adopts an interconnect approach (see ISO/IEC 11801). Passive connections between cabling subsystems adopt either a cross-connect approach, by way of either patch cords or jumpers, or an interconnect approach.

Page 13: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 12 - 2nd FCD ISO/IEC 24764:2009-04-21

Networkaccess cabling

subsystem

Main distributioncabling

subsystem

Zone distributioncabling subsystem

Generic cabling system

Distributorin accordancewith ISO/IEC 11801

ENI LDPMD ZD EO

Equipmentcabling

EQP

Networkaccess cabling

subsystem

Main distributioncabling

subsystem

Zone distributioncabling subsystem

Generic cabling system

Distributorin accordancewith ISO/IEC 11801

ENI LDPMD ZD EO

Equipmentcabling

EQPEQPEQP

411

412 Figure 2 - Structure of generic cabling within a data centre

Main distribution cabling subsystem

Network access cabling subsystem

Zone distributioncabling subsystem

optional cables

ZD

LDP LDP

ZD

LDP LDP

MD

ENI ENIDistributorin accordancewith ISO/IEC 11801

EO EO EO EO EO EO EO EO EO EO

Main distribution cabling subsystem

Network access cabling subsystem

Zone distributioncabling subsystem

optional cables

ZD

LDP LDP

ZD

LDP LDP

MD

ENI ENIDistributorin accordancewith ISO/IEC 11801

EO EO EO EO EO EO EO EO EO EO

413

414

416 417

NOTE Network access cabling is also used to connect ENI to ZD.

Figure 3 - Hierarchical structure of generic cabling within a data centre

5.4 Cabling subsystems 415

Although equipment cords are used to connect the equipment to a cabling subsystem, they are not considered part of the cabling subsystem.

ISO/IEC JTC 1/SC 25N1643.doc

Page 14: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 13 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

419 420

421

425

427 428

431

433 434

436 437

440

444 445 446

448 449

450

451 452

453 454

5.4.1 Network access cabling subsystem 418

The network access cabling subsystem extends from an MD (or ZD) to the ENIs and/or other distributors (in accordance with ISO/IEC 11801) connected to it.

The subsystem includes:

a) the network access cables; 422

b) the mechanical termination of the network access cables at the ENI(s); 423

c) the mechanical termination of the network access cables at the MD, ZD(s) or other 424 distributors in accordance with ISO/IEC 11801.

5.4.2 Main distribution cabling subsystem 426

The main distribution cabling subsystem extends from an MD to the ZD(s) connected to it. The subsystem includes:

a) the main distribution cables; 429

b) the mechanical termination of the main distribution cables at the MD together with 430 associated patch cords and/or jumpers at the MD;

c) the mechanical termination of the main distribution cables at the ZD(s). 432

Although equipment cords are used to connect the equipment to the cabling subsystem, they are not considered part of the cabling subsystem.

5.4.3 Zone distribution cabling subsystem 435

The zone distribution cabling subsystem extends from a ZD to the EO(s) connected to it. The subsystem includes:

a) the zone distribution cables; 438

b) the mechanical termination of the zone distribution cables at the EO(s) and the ZD 439 together with associated patch cords and/or jumpers at the ZD;

c) LDP(s) (optional); 441

d) LDP cable(s) (optional) ; 442

e) the EO(s). 443

Although equipment cords are used to connect the equipment to the cabling subsystem, they are not considered part of the cabling subsystem. Zone distribution cables shall be continuous from the ZD to the EO(s) unless (an) LDP(s) is installed (see 5.7.8).

5.4.4 Design objectives 447

In order to provide the longest operational life while minimising the disruption and cost associated with re-cabling, the fixed installed cabling should be designed to:

support the broadest set of existing and emerging applications;

accommodate the anticipated growth in volume of supported applications throughout the predicted lifetime of the installation.

In addition the provision of redundancy within a cabling design should be considered (also see 5.7.1)

Page 15: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 14 - 2nd FCD ISO/IEC 24764:2009-04-21

5.5 Accommodation of functional elements 455

ISO/IEC JTC 1/SC 25N1643.doc

456 457

458 459

460 461

Figure 4 shows an example of how the functional elements are accommodated in a building (only a single floor of the building is shown for simplicity).

The MD, ZD and LDP shall be housed in permanent and accessible locations within the data centre.

The ENI shall be housed in permanent and accessible location either internal or external to the data centre.

ENI

BEF

MD ZD

Distributorin accordancewith ISO/IEC 11801

Equipment/telecommunications roomin accordancewith ISO/IEC 11801

Data centre

EO

LDP

ENI

BEF

MD ZD

Distributorin accordancewith ISO/IEC 11801

Equipment/telecommunications roomin accordancewith ISO/IEC 11801

Data centre

EO

LDP 462

463

466 467 468

469 470

472 473

474 475 476 477 478 479

480 481 482 483 484 485

Figure 4 - Example of accommodation of functional elements

5.6 Interfaces 464

5.6.1 Equipment interfaces and test interfaces 465

Potential equipment interfaces for data centres are located at the ends of the cabling subsystems (as shown in Figure 5). An LDP does not provide an equipment interface to the generic cabling system.

Potential test interfaces for data centres are located at the ends of the cabling subsystems and at the LDP, if present (as shown in Figure 5).

5.6.2 Channels and links 471

The transmission performance of generic cabling between specific test interfaces is detailed in Clause 6 for channels and Annex A for links.

The channel is the transmission path between data centre equipment such as a switches and servers (EQP in Figure 5). A typical channel in a data centre would consist of the zone distribution cabling subsystem together with an equipment cord at each end. For longer reach services the channel would be formed by the connection of two or more subsystems (including patch cords and equipment cords). The performance of the channel excludes the connections at the application-specific equipment.

The permanent link is the transmission path of an installed cabling subsystem including the connecting hardware at the ends of the installed cable. In a data centre zone distribution cabling subsystem, the permanent link consists of the equipment outlet, the zone distribution cable, an optional LDP, an optional LDP cable and the termination of the zone distribution cable at the zone distributor. The permanent link includes the connections at the ends of the installed cabling.

Page 16: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 15 - 2nd FCD ISO/IEC 24764:2009-04-21

a) Zone distribution cabling

b) Main distribution cabling

EQPC CEQP C C

TI TI

EI EI EI

TI

C

EI

MD ZD

TI

C

LDP

EOEQPC CEQP C C

TI TI

EI EI EI

TI

C

ZD

TI TI

C

a) Zone distribution cabling

b) Main distribution cabling

EQPC CEQP C C

TI TI

EI EI EI

TI

C

EI

MD ZD

TI

C

LDP

EOEQPC CEQP C C

TI TI

EI EI EI

TI

C

ZD

TI TI

C

486

c) Network access cabling from MD to distributor in accordance with ISO/IEC 11801

d) Network access cabling from MD to ENI

EQPC CEQP C C

TI TI

EI EI EI

TI

C

EI

MD

TI

C

Distributor in accordancewith ISO/IEC 11801

ENIEQPC CEQP C C

TI TI

EI EI EI

MD

TI TI

C

See NOTE

c) Network access cabling from MD to distributor in accordance with ISO/IEC 11801

d) Network access cabling from MD to ENI

EQPC CEQP C C

TI TI

EI EI EI

TI

C

EI

MD

TI

C

Distributor in accordancewith ISO/IEC 11801

ENIEQPC CEQP C C

TI TI

EI EI EI

MD

TI TI

C

See NOTE 487

491

NOTE Where the EQP connected to the ENI lies outside the premises containing the data centres, the 488 interconnecting cord will typically comprise a combination of fixed cabling and cords that are outside the scope of 489 this standard. In such cases the connection to the EQP may not provide a TI. 490

Figure 5 - Test and equipment interfaces

ISO/IEC JTC 1/SC 25N1643.doc

Page 17: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 16 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

494 495

496 497 498 499

500 501 502 503

504 505

507 508 509

510 511 512 513 514 515

5.7 Dimensioning and configuring 492

5.7.1 Distributors 493

The number and type of subsystems that are included in a generic cabling implementation depends upon the layout and size of the data centre and upon the strategy of the user.

The design of distributors shall ensure that the length of patch cords, jumpers and equipment cords are minimized and administration should ensure that the design lengths are maintained during operation. Distributors should be located such that the resulting cable lengths are consistent with the channel performance requirements of Clause 6.

Where the components of Clauses 8, 9 and 10 are used the distributors shall be located in accordance with the reference implementations of Clause 7. Where other components are used, distributors shall be located so that the desired performance Class of Clause 6 is delivered.

The functions of multiple distributors may be combined into a single distributor. For example, a MD may serve the function of a ZD. However, every data centre must have at least one MD.

5.7.2 Redundancy 506

Consideration should be given to the resilience of the data centre with respect to the cabling infrastructure. This may be enhanced by the provision of redundant distributors, cabling, and pathways.

In certain circumstances, for example for security or reliability reasons, redundancy may be built into a cabling design. Figure 6 shows one of many possible examples of the connection of functional elements within the structured framework to provide such protection against failure in one or more parts of the cabling infrastructure. This might form the basis for the design of generic cabling for a data centre providing some protection against such hazards as fire damage or the failure of an external network.

Page 18: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 17 - 2nd FCD ISO/IEC 24764:2009-04-21

Distributorin accordancewith ISO/IEC 11801

MDMD

ENI ENI

ZDZD

LDPLDP

EO EO EO EO EO EO EO EOEO EO EO EO

Distributorin accordancewith ISO/IEC 11801

MDMD

ENI ENI

ZDZD

LDPLDP

EO EO EO EO EO EO EO EOEO EO EO EO 516

517

518 519

520 521

523 524

525

526

527 528

Figure 6 - Connection of functional elements providing redundancy

Additionally, redundancy may be provided by utilizing multiple cables between distributors, with cables following different routes.

NOTE: Connections between ZD and ZD are in addition to the connection between MD and ZD and not a replacement for the MD to ZD connection

5.7.3 External network interface 522

The External Network Interface (ENI) is a termination of the network access cabling that allows connection of external services to the network access cabling as shown in Figure 7.

NOTE: The multiple service providers should have diverse routes to each of the multiple ENIs.

The ENI interface shall be in accordance with Clause 9.

Where the components of Clauses 8, 9 and 10 are used the ENIs shall be located in accordance with the reference implementations of Clause 7.

ISO/IEC JTC 1/SC 25N1643.doc

Page 19: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 18 - 2nd FCD ISO/IEC 24764:2009-04-21

EQP

Network access cabling

ENI

C

ENI

C

ENI

C

External service cabling(beyond the scope of this standard)

Interconnection

Crossconnection

Connection of networkaccess cabling to externalservice cabling may includepassive or active equipment

EQP

Network access cabling

ENI

C

ENI

C

ENI

C

External service cabling(beyond the scope of this standard)

Interconnection

Crossconnection

Connection of networkaccess cabling to externalservice cabling may includepassive or active equipment

529

530

532

534

536 537 538

540 541 542 543

544

545

547 548 549 550 551

552 553 554 555

Figure 7 – Examples of external service cabling connections to the ENI

5.7.4 Cables 531

Cable types used in the reference implementations of Clause 7 are specified in Clause 8.

5.7.5 Equipment cords 533

Equipment cords are non-permanent and can be application-specific.

5.7.6 Patch cords and jumpers 535

Patch cords and jumpers are used within cross-connect implementations at distributors. The performance contribution of these cords shall be taken into account in the design of the channel. Clause 7 provides guidance on cord/jumper lengths for reference implementations of generic cabling.

5.7.7 Equipment outlets 539

The design of generic cabling should provide for EOs to be installed with a high density and located in close proximity to the application-specific equipment to which they are to be connected. The number of cable elements presented at the EO is not restricted by this standard.

A group of EOs can be served directly by multiple ZDs or by multiple ZDs via multiple LDPs.

The EO interface presented shall be in accordance with Clause 9.

5.7.8 LDP 546

The installation of an LDP in the zone distribution cabling between the ZD and the EO may be useful where frequent additions or movements of equipment are required. One LDP is permitted between a ZD and any EO. The LDP shall be an interconnect, not a cross-connect, because the LDP adds one connection per channel. There shall be no active equipment in the LDP area with the exception of DC powering equipment.

Where an LDP is used, it shall have sufficient capacity to support the area of the data centre which it is designed to serve during its intended operational life. The area served may be defined in terms of number of frames/cabinets/closures to be supported and should include allowance for growth.

ISO/IEC JTC 1/SC 25N1643.doc

Page 20: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 19 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

556 557

558 559 560

562

564

567 568 569 570 571

Provided that the requirements of 5.5 are met, LDP(s) may be located in ceiling voids or under floors.

For balanced cabling, the effect of multiple connections in close proximity on transmission performance should be taken into consideration when planning the cable lengths between the ZD and the LDP.

5.7.9 Building entrance facilities 561

See ISO/IEC 11801.

5.8 Earthing and equipotential bonding 563

See ISO/IEC 11801 and ISO/IEC 14763-2.

6 Channel performance in data centres 565

6.1 General 566

This clause specifies the minimum channel performance of balanced and optical fibre cabling in terms of the Classes as specified in Clause 6.2. The transmission performance of channels is specified at and between the connections to active equipment as shown in Figure 8. The channel comprises only passive sections of cable, connections, equipment cords, patch cords and jumpers.

EQPCEQP C C

Equipment cord

Patch cord/Jumper

Channel

CC

Patch cord/Jumper

Equipment cord

C

572

573

574 575 576

577

578

579

580

581

582 583 584 585 586

Figure 8 – Example of a channel with 4 connections

Application support depends on channel performance only, which in turn depends on cable length, number of connections, connector termination practices and workmanship, and performance.

Channels are implemented using either:

network access cabling only;

main distribution cabling only;

zone distribution cabling only;

combinations of the above.

Figure 9 shows an example of equipment at the MD connected to equipment at the EO using two channels, an optical fibre cabling channel and a balanced cabling channel. The optical fibre and balanced cabling channels are connected together using an optical fibre to balanced cable converter. There are four channel interfaces; one at each end of the balanced channel, and one at each end of the optical fibre cabling channel.

Page 21: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 20 - 2nd FCD ISO/IEC 24764:2009-04-21

EQPC

EO

ZD

C

EQP

C

C

C

C

OE EQP

C

C

C C

C

MD

Balanced cabling channel

Optical fibre channel

C = optional connection 587

588

589

592 593

594 595 596 597

598 599 600

601 602

603

605 606

608 609 610 611

612 613 614 615

Figure 9 - Example of a system showing the location of cabling interfaces

6.2 Transmission performance 590

6.2.1 General 591

The channel transmission performance specifications are separated into Classes that allow for the transmission of the applications in Annex F of ISO/IEC 11801:2008.

The channel performance requirements described in this clause shall be used for the design and may be used for verification of any implementation of this international standard, using the test methods defined, or referred to, by this clause. In addition, these requirements can be used for application development and trouble shooting.

The channel specifications in this clause allow for the transmission of defined Classes of applications over distances other than those of Clause 7, and/or using media and components with different transmission performance than those of Clauses 8, 9 and 10.

Consideration should be given to measuring performance at worst case temperatures, or calculating worst case performance based on measurements made at other temperatures.

Link performance requirements are specified in Annex A.

6.2.2 Balanced cabling 604

The main distribution and zone distribution cabling shall be designed to provide a minimum of Class EA channel performance as specified in ISO/IEC 11801.

6.2.3 Optical fibre cabling 607

Optical fibre cabling shall be designed using cabled optical fibre Categories specified in Clause 8. Where multimode optical fibre is used, the main distribution and zone distribution cabling shall provide channel performance as specified in ISO/IEC 11801 using a minimum of Category OM3 cabled optical fibre and optical connecting hardware as specified in 9.3.

Editors Note: Resolution of US02 resulted in the above text, which is wrong in its first sentence “Optical fibre cabling shall be designed as specified in Clause 8.” Clause 8 specifies optical fibre cables and not any design rules. The text should have been stating that the design shall use the fibre cables specified in Clause 8. The use of fibre optical connecting hardware has been resolved in IE06 and therefore the text amended.

ISO/IEC JTC 1/SC 25N1643.doc

Page 22: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 21 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

618 619 620 621

624 625 626 627

628 629 630

633 634

635

636

637

638

639 640 641

643 644

7 Reference implementations in data centres 616

7.1 General 617

This clause describes implementations of generic cabling that utilise components referenced in Clauses 8, 9 and 10. These reference implementations meet the requirements of Clause 5 and, when installed in accordance with ISO/IEC 14763-2, comply with the channel performance requirements of Clause 6.

7.2 Balanced cabling 622

7.2.1 Assumptions 623

Balanced cabling components referenced in Clauses 8, 9 and 10 are defined in terms of Category. In the reference implementations of this clause, the components used in each cabling channel shall have the same nominal characteristic impedance in accordance with 7.2 of ISO/IEC 11801:2008.

The implementations are based on component performance at 20 °C. The effect of temperature on the performance of cables shall be taken into account as shown in Table 2, Table 4 and Table 5.

7.2.2 Zone distribution cabling 631

7.2.2.1 Component choice 632

The selection of balanced cabling components will be determined by the Class of applications to be supported by the cabling. Refer to Annex F of ISO/IEC 11801:2008, for guidance.

Using the models of 7.2.2.2:

Category 6A components provide Class EA balanced cabling performance;

Category 7 components provide Class F balanced cabling performance;

Category 7A components provide Class FA balanced cabling performance.

Cables and connections of different Categories should not be mixed within a channel. If different Categories are mixed, the resultant cabling performance will be determined by the Category of the lowest performing component.

7.2.2.2 Dimensions 642

Figure 10 shows the models used to correlate zone distribution cabling dimensions specified in this clause with the channel specifications in Clause 6.

Page 23: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 22 - 2nd FCD ISO/IEC 24764:2009-04-21

Equipment cord

Patch cord/Jumper

Fixed zone distribution

cable

EQPC CEQP C

Equipment cord

EOZD

Channel = 100 m max.

b) Cross-connect - EO model

C C

Equipment cord

Fixed zone distribution

cable

EQPCEQP C

Equipment cord

EO

ZD

Channel = 100 m max.

C C

a) Interconnect - EO model

Equipment cord

Patch cord/Jumper

Fixed zone distribution

cable

EQPC CEQP C

Equipment cord

EOZD

Channel = 100 m max.

b) Cross-connect - EO model

C C

Equipment cord

Fixed zone distribution

cable

EQPCEQP C

Equipment cord

EO

ZD

Channel = 100 m max.

C C

a) Interconnect - EO model

645

Equipment cord

Patch cord/Jumper

EQPCEQP

Equipment cord

ZD

Channel = 100 m max.

d) Cross-connect - LDP - EO model

C C

Equipment cord

EQPCEQP C

Equipment cord

EO

ZD

Channel = 100 m max.

C C

c) Interconnect - LDP - EO model

Fixed zone distribution

cable

C

LDP cable

LDP

CCEO

Fixed zone distribution

cable

C

LDP cable

LDP

Equipment cord

Patch cord/Jumper

EQPCEQP

Equipment cord

ZD

Channel = 100 m max.

d) Cross-connect - LDP - EO model

C C

Equipment cord

EQPCEQP C

Equipment cord

EO

ZD

Channel = 100 m max.

C C

c) Interconnect - LDP - EO model

Fixed zone distribution

cable

C

LDP cable

LDP

CCEO

Fixed zone distribution

cable

C

LDP cable

LDP

646

647 Figure 10 - Zone distribution cabling models

ISO/IEC JTC 1/SC 25N1643.doc

Page 24: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 23 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

648 649 650 651

652 653 654 655 656

657 658 659 660

661 662 663

664

666

668

669

670 671 672

673 674 675 676 677

678 679

Figure 10a shows a channel containing only an interconnect and an EO. Figure 10b contains an additional connection as a cross-connect. In both cases the fixed horizontal cable connects the ZD to the EO. The channel includes patch cords and equipment cords. For the purposes of this sub clause, jumpers used in place of patch cords are treated as cords.

Figure 10c shows a channel containing an interconnect, an LDP and an EO. Figure 10d contains an additional connection as a cross-connect. In both cases the fixed zone distribution cable connects the ZD to the LDP. The channel includes patch cords and equipment cords. For the purposes of this sub clause, jumpers used in place of patch cords are treated as cords.

In addition to the cords, the channels shown in Figure 10c and Figure 10d contain an LDP cable. The insertion loss specification for the LDP cable may differ from that of both the fixed zone distribution cable and the flexible cables. The channel of Figure 10d is recognized as the maximum implementation used to define the channel performance limits of Clause 6.

In order to accommodate cables used for LDP cables, patch cords, jumpers and equipment cords with different insertion loss specifications, the maximum cable length used within a channel shall be determined by the equations shown in Table 2.

In Table 2 it is assumed that

a) the flexible cable within these cords has a higher insertion loss specification than that 665 used in the fixed zone distribution cable (see Clause 10),

b) the cables within these cords in the channel have a common insertion loss specification. 667

The following general restrictions apply:

a) the physical length of the channel shall not exceed 100 m;

b) the physical length of the fixed zone distribution cable shall not exceed 90 m and may be less depending on the length of LDP cables and cords used and the number of connections;

Table 1 contains the length assumptions of the mathematical model used to validate channel performance using components specified in clauses 8, 9 & 10 when configured within the range of implementations provided by Figure 10 and Table 1. They do not represent absolute restrictions on the implementation of channels and permanent links, but may be used for guidance in reference implementations.

Table 1 – Length assumptions used in the mathematical modelling of balanced zone distribution cabling

Segment Minimumm

Maximum m

ZD-LDP 15 85

LDP-EO 5 -

ZD-EO (no LDP) 15 90

Equipment cord at the EO 2a 5

Patch cord 2 -

Equipment cord at the ZD 2b 5

All cords - 10

a If there is no LDP, the minimum length of the equipment cord is 1 m.

b If there is no cross-connect, the minimum length of the equipment cord is 1 m.

Page 25: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 24 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

680 681 682

683

During the operation of the installed cabling, an administration system, see ISO/IEC 14763-2, should be implemented to ensure that the length of cords and, where appropriate, the length of LDP cables used to create the channel conform to the design rules of this Standard.

Table 2 - Zone distribution channel length equations

Model Figure Implementation equations

Class E A Class F and Class F A

Interconnect-EO 10a Z =104a - FX Z =105a - FX

Cross-connect-EO 10b Z =103a - FX Z =103a - FX

Interconnect-LDP-EO 10c Z =103a - FX - LY Z =103a - FX - LY

Cross-connect-LDP-EO 10d Z =102a - FX - LY Z =102a - FX - LY

Z maximum length of the fixed zone distribution cable (m)

F combined length of patch cords, jumpers and equipment cords (m)

L length of the LDP cable (m)

X ratio of flexible cable insertion loss (dB/m) to fixed zone distribution cable insertion loss (dB/m) - see Clause 10

Y ratio of LDP cable insertion loss (dB/m) to fixed zone distribution cable insertion loss (dB/m) - see Clause 10

a This includes a length reduction allocation to accommodate ILD.

Note: To be confirmed when Amendment 2 of ISO/IEC 11801 2nd Edition has been approved as FDAM.

For operating temperatures above 20 °C, Z should be reduced by 0,2% per °C for screened cables and 0,4% per °C (20 oC to 40 oC) and 0,6% per °C (40 oC to 60 oC) for unscreened cables.

684

687 688

689

690

691

692

693 694 695

697 698 699 700

701 702 703

704 705 706

7.2.3 Main distribution cabling 685

7.2.3.1 Component choice 686

The selection of balanced cabling components will be determined by the Class of applications to be supported by the cabling. Refer to Annex F of ISO/IEC 11801:2008 for guidance.

Using the models of 7.2.3.2:

Category 6A components provide Class E A balanced cabling performance;

Category 7 components provide Class F balanced cabling performance;

Category 7 A components provide Class F A balanced cabling performance.

Cables and connections of different Categories should not be mixed within a channel. If different Categories are mixed, the resultant cabling performance will be determined by the Category of the lowest performing component.

7.2.3.2 Dimensions 696

The connection of application-specific equipment to the main distribution cabling at the MD and ZDs adopts either an interconnect or cross-connect approach (see ISO/IEC 11801). The channel includes patch cords and equipment cords. For the purposes of this sub clause, jumpers used in place of patch cords are treated as cords.

Figure 11 shows the model used to correlate main distribution cabling dimensions specified in this clause with the channel specifications in Clause 5. This figure represents the full configuration for the main distribution channel.

Table 3 contains the length assumptions of the mathematical model used to validate Channel performance using components specified in Clauses 8, 9 & 10 when configured within the range of implementations provided by Figure 10 and Table 3. They do not represent absolute

Page 26: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 25 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

707 708

709 710

restrictions on the implementation of channels and permanent links, but may be used for guidance in reference implementations.

Table 3 – Length assumptions used in the mathematical modelling of balanced main distribution cabling

Segment Minimum m

Maximumm

MD-ZD 15 90

Equipment cord at the MD 2a 5

Equipment cord at the ZD 2b 5

Patch cord 2 -

All cords - 10 a If there is no cross-connect at the MD, the minimum length of the equipment cord at the MD is 1m. b If there is no cross-connect at the ZD, the minimum length of the equipment cord at the ZD is 1m.

711 712 713 714

The maximum length of the fixed main distribution cable will depend on the total length of cords to be supported within a channel. During the operation of the installed cabling, an administration system, see ISO/IEC 14763-2, should be implemented to ensure that the length of cords used to create the channel conform to the design rules of this Standard.

Equipment cord

Patch cord/Jumper

Fixed main distribution

cable

EQPC CEQP C C CC

Equipment cord

MD

Patch cord/Jumper

Channel

ZD

Equipment cord

Patch cord/Jumper

Fixed main distribution

cable

EQPC CEQP C C CC

Equipment cord

MD

Patch cord/Jumper

Channel

ZD

715

716

717 718 719

720

722

724

725

726 727

Figure 11 - Main distribution cabling models

In order to accommodate the higher insertion loss of flexible cables used for cords, the length of the cables used within a channel of a given Class (see Clause 6) shall be determined by the equations shown in Table 4.

In Table 4 it is assumed that

c) the flexible cable within these cords has a higher insertion loss specification than that 721 used in the fixed main distribution cable (see Clause 10),

d) the cables within these cords in the channel have a common insertion loss specification. 723

The following general restrictions apply:

a) the physical length of the channel shall not exceed 100 m;

b) the physical length of the fixed main distribution cable shall not exceed 90 m and may be less depending on the length of cords used and the number of connections;

Page 27: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 26 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

728 Table 4 - Main distribution channel length equations

Model Implementation equations

Class E A Class F and Class F A

Interconnect-interconnect M =104a - FX M =105a - FX

Interconnect-cross-connect M =103a - FX M =103a - FX

Cross-connect—cross-connect M =102a - FX M =102a - FX

M maximum length of the fixed main distribution cable (m)

F combined length of patch cords, jumpers and equipment cords (m)

X ratio of flexible cable insertion loss (dB/m) to fixed main distribution cable insertion loss (dB/m) – see Clause 10

a This includes a length reduction allocation to accommodate ILD.

For operating temperatures above 20 oC, M should be reduced by 0,2 % per °C for screened cables and 0,4% per °C (20 oC to 40 oC) and 0,6 % per °C (40 oC to 60 oC) for unscreened cables.

7.2.4 Network access cabling 729

7.2.4.1 Component choice 730

The selection of balanced cabling components will be determined by the channel lengths required and the Class of applications to be supported. Refer to Annex F to ISO/IEC 11801:2008 for guidance.

731 732 733

735 736 737 738 739

740 741

742

744

746

747 748 749

750 751

752 753 754 755 756

7.2.4.2 Dimensions 734

Figure 12 shows the model used to correlate cabling dimensions specified in this clause with the channel specifications in Clause 5. The network access channel shown contains a cross-connect at both ends and represents the worst-case configuration for a network access cabling channel between an MD and distributor in accordance with ISO/IEC 11801. A channel between an ENI and an MD contains an interconnect at the ENI.

The channel includes patch cords and equipment cords. For the purposes of this clause, jumpers used in place of patch cords are treated as cords.

In Table 5 it is assumed that

a) the flexible cable within these cords has a higher insertion loss specification than that 743 used in the fixed network access cable,

b) the cables within all these cords in the channel have a common insertion loss 745 specification.

In order to accommodate the higher insertion loss of flexible cables used for cords, the length of the cables used within a channel of a given Class (see clause 6) shall be determined by the equations shown in Table 5.

When four connections are used in a channel, the physical length of the network access cable should be at least 15 m.

The maximum length of the fixed network access cable will depend on the total length of cords to be supported within a channel. The maximum lengths of cords shall be fixed for ENIs and distributors. During the operation of the installed cabling, an administration system, see ISO/IEC 14763-2, should be implemented to ensure that the length of cords used to create the channel conform to these design rules of this Standard.

Page 28: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 27 - 2nd FCD ISO/IEC 24764:2009-04-21

Equipment cord

Patch cord/Jumper

EQPCEQP

Equipment cord

MD

Channel

b) Network access cabling from MD to distributor in accordance with ISO/IEC 11801

C C

a) Network access cabling from MD to ENI

CC

Fixed network access

cable

C

Patch cord/Jumper

Distributor in accordancewith ISO/IEC 11801

Equipment cord

Patch cord/Jumper

EQPCEQP

Equipment cord

MD

Channel

C CCC

Fixed network access

cable

C

Patch cord/Jumper

ENI

Equipment cord

Patch cord/Jumper

EQPCEQP

Equipment cord

MD

Channel

b) Network access cabling from MD to distributor in accordance with ISO/IEC 11801

C C

a) Network access cabling from MD to ENI

CC

Fixed network access

cable

C

Patch cord/Jumper

Distributor in accordancewith ISO/IEC 11801

Equipment cord

Patch cord/Jumper

EQPCEQP

Equipment cord

MD

Channel

C CCC

Fixed network access

cable

C

Patch cord/Jumper

ENI

757

761

NOTE Where the EQP connected to the ENI lies outside the premises containing the data centres, the 758 interconnecting cord will typically comprise a combination of fixed cabling and cords that are outside the scope of 759 this standard. In such cases the connection to the EQP may not provide a TI. 760

Figure 12 - Network access cabling models

ISO/IEC JTC 1/SC 25N1643.doc

Page 29: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 28 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

762 Table 5 - Network access cabling channel equations

Component Implementation equations a

Category Class A Class B Class C Class D Class E Class E A Class F Class F A

5 2 000 N = 250 - FX

N = 170 - FX

N = 105 - FX

6 2 000 N = 260 - FX

N = 185 - FX

N = 111 - FX

N = 102b- FX

6 A 2 000 N = 260 - FX

N = 185 - FX

N = 111 - FX

N = 102b- FX

N = 102b- FX

7 2 000 N = 260 - FX

N = 190 - FX

N = 115 - FX

N = 104b - FX

N = 104b - FX

N = 102b- FX

7 A 2 000 N = 260 - FX

N = 190 - FX

N = 115 - FX

N = 104b - FX

N = 104b - FX

N = 102b- FX

N = 102b- FX

N length of the fixed backbone cable (m)

F combined length of patch cords, jumpers and equipment cords (m)

X ratio of flexible cable insertion loss (dB/m) to fixed network access cable insertion loss (dB/m) – see Clause 10

a Applications limited by propagation delay or skew may not be supported if channel lengths exceed 100 m.

b This includes a length reduction allocation to accommodate ILD.

NOTE 1 Where channels contain a different number of connections than in the model shown in Figure 12, the fixed cable length shall be reduced (where more connections exist) or may be increased (where fewer connections exist) by 2 m per connection for Category 5 connections and 1 m per connection for Category 6 and above connections. Additionally, the NEXT, Return Loss (RL) and ACR-F performance should be verified. Category 5 and Category 6 components and Class A through Class E channels only may be used for network access cabling.

NOTE 2 For operating temperatures above 20 °C, N should be reduced by 0,2 % per °C for screened cables and 0,4 % per °C (20 °C to 40 °C) and 0,6 % per °C (40 °C to 60 °C) for unscreened cables.

7.3 Optical fibre cabling 763

7.3.1 Assumptions 764

Optical fibre components are referenced in Clauses 8, 9 and 10. The optical fibres are defined in terms of physical construction (core/cladding diameter) and their transmission performance Category within a cable. Within the reference implementations of this clause, the cabled optical fibres used in each cabling channel shall be of the same specification.

765 766 767 768

770 771

773 774 775 776 777 778 779

7.3.2 Component choice 769

The selection of optical fibre components will be determined by the channel lengths required and the applications to be supported. Refer to Annex F of ISO/IEC 11801:2008 for guidance.

7.3.3 Optical fibre cabling channel lengths 772

The models of Figure 10, Figure 11 and Figure 12 are applicable to optical fibre cabling for zone distribution cabling, main distribution cabling and network access cabling respectively. The channel length restriction of Figure 10 does not apply, but is instead limited by channel length restrictions of the cabled optical fibre Category used. It should be noted that the connection systems used to terminate fixed optical fibre cabling may contain mated connections and splices (permanent or re-useable) and that cross-connects may comprise re-useable splices.

Page 30: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 29 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

782

784

786

789 790 791

793

796 797 798

800

802

808

810

812

814

8 Cable requirements in data centres 780

8.1 General 781

This clause defines the minimum requirements for

a) cables installed in the main distribution, zone distribution and network access cabling 783 subsystems specified in Clause 5 and used in the reference implementations of Clause 7,

b) flexible balanced cables to be assembled as cords as specified in Clause 10 and used in 785 the reference implementations of Clause 7,

c) balanced cables or cable elements to be used as jumpers. 787

8.2 Balanced cables 788

The electrical performance of balanced cables, other than for network access cabling, shall meet a minimum of Category 6A, requirements according to Clause 9.2 of ISO/IEC 11801:2008.

8.3 Optical fibre cables 792

See 9.4 of ISO/IEC 11801:2008.

9 Connecting hardware requirements in data centres 794

9.1 General requirements 795

Hardware for connecting cables shall only provide direct onward attachment for each conductor and shall not provide any contact between more than one incoming and one outgoing conductor (e.g. bridge taps shall not be used).

9.1.1 Applicability 799

See 10.1.1 of ISO/IEC 11801:2008.

9.1.2 Location 801

Connecting hardware is installed at the:

a) ENI, 803

b) MD and ZD, 804

c) LDP (if provided), 805

d) EO. 806

9.1.3 Design 807

See 10.1.3 of ISO/IEC 11801:2008.

9.1.4 Operating Environment 809

See 10.1.4 of ISO/IEC 11801:2008.

9.1.5 Mounting 811

See 10.1.5 of ISO/IEC 11801:2008.

9.1.6 Installation practices 813

See 10.1.6 of ISO/IEC 11801:2008.

Page 31: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 30 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

816

819

821

824 825

826

9.1.7 Marking and colour Coding 815

See 10.1.7 of ISO/IEC 11801:2008.

9.2 Connecting hardware for balanced cabling 817

9.2.1 General requirements 818

See 10.2.1 of ISO/IEC 11801:2008.

9.2.2 Performance marking 820

See 10.2.2 of ISO/IEC 11801:2008.

9.2.3 Mechanical characteristics 822

9.2.3.1 Connecting hardware of the type used at the ENI 823

Balanced cabling connecting hardware shall be in accordance with Clause 10.2.3 of ISO/IEC 11801:2008 as amended by the requirements of Table 6.

Table 6 - Connecting hardware of the type used at the ENI

Category Standard

Category 5 unscreened IEC 60603-7-2

Category 5 screened IEC 60603-7-3

Category 6 unscreened IEC 60603-7-4

Category 6 A unscreened IEC 60603-7-41 b

Category 6 screened IEC 60603-7-5

Category 6 A screened IEC 60603-7-51 b

Category 7 screened IEC 60603-7-7a

Category 7 A screened IEC 60603-7-71a a In installations where other factors such as cable sharing take preference over backward compatibility offered by the IEC 60603-7-7 and IEC 60603-7-71 interface, the interface specified in IEC 61076-3-104 may be used.

827

829 830

831

9.2.3.2 Connecting hardware of the type used at the EO 828

Balanced cabling connecting hardware shall be in accordance with Clause 10.2.3 of ISO/IEC 11801:2008 as amended by the requirements of Table 7.

Table 7 - Connecting hardware of the type used at the EO

Category Standard

Category 6 A unscreened IEC 60603-7-41

Category 6 A screened IEC 60603-7-51

Category 7 screened IEC 60603-7-7a

Category 7 A screened IEC 60603-7-71a a In installations where other factors such as cable sharing take preference over backward compatibility offered by the IEC 60603-7-7 and IEC 60603-7-71 interface, the interface specified in IEC 61076-3-104 may be used.

Page 32: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 31 - 2nd FCD ISO/IEC 24764:2009-04-21

9.2.3.3 Pin and pair assignments at the EO 832

ISO/IEC JTC 1/SC 25N1643.doc

833 834

835 836

837 838 839

For the connecting hardware in 9.2.3.2 the pin grouping and pair assignments shall be as shown in Figure 13.

Pair rearrangement should not involve modification of the cable terminations. If pair rearrangement is used, the configuration of the terminations shall be clearly identified.

NOTE When two physically similar cabling links are used in the same installation (for example, different performance Categories and cables with different nominal impedance) special precautions are required to ensure that they are identified.

a) IEC 60603-7 series interface for Category 5, 6 and 6A (not to scale)

1 2 3 4 5 6 7 8

b) IEC 60603-7 series interface for Category 7 and 7A (not to scale)

1 2 3 4 5 6 7 8

6I 3I 4I 5I

NOTE: the pin designations 1, 2, 3I, 4I, 5I, 6I, 7 and 8 for Category 7 and 7A correspond to 1, 2, 3, 4, 5, 6, 7 and 8 for Category 5, 6 and 6A

1 2 3 4 5 6 7 8

6I 3I 4I 5I

1 2 3 4 5 6 7 8

6I 3I 4I 5I

NOTE: the pin designations 1, 2, 3I, 4I, 5I, 6I, 7 and 8 for Category 7 and 7A correspond to 1, 2, 3, 4, 5, 6, 7 and 8 for Category 5, 6 and 6A

c) IEC 61076-3-104 interface for Category 7 and 7A (not to scale)

1 2 7 8

6 3 4 5

NOTE: the pin designations correspond to those of IEC 60603-7

series interfaces

LATCH

1 2 7 8

6 3 4 5

1 2 7 8

6 3 4 5

NOTE: the pin designations correspond to those of IEC 60603-7

series interfaces

LATCH

Figure 13 - Pin grouping and pair assignments at the EO, front view of fixed connector (jack)

840 841

Page 33: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 32 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

842 843 844 845

848

849 850 851 852 853

855 856

857 858 859 860

863

865 866 867

868 869

870 871

873 874

875 876

877 878

If the connecting hardware type at a distributor, LDP or EO in the same link or channel is different to each other, the cabling connections shall be configured with consistent pin/pair assignments to ensure end-to-end connectivity. Pair rearrangement at the equipment outlet should not involve modification of the horizontal cable terminations.

9.2.3.4 Electrical Characteristics 846

9.2.3.4.1 ENI and EO requirements 847

See 10.2.4.1 and 10.2.4.2 of ISO/IEC 11801:2008.

Free and fixed connectors (plugs and jacks) that are intermateable shall be backward compatible with those of different performance categories. Backward compatibility means that mated connections with free and fixed connectors (plugs and jacks) from different categories shall meet all of the requirements for the lower category component. See Clause 10 of ISO/IEC 11801:2008.

9.2.3.4.2 Other connecting hardware 854

Connecting hardware for use in distributors and LDPs of a given category shall meet the corresponding performance requirements specified in 10.2.4.3 of ISO/IEC 11801:2008.

The creation of Class FA Configuration PL3 permanent link (See Figure A. 1), where the LDP cable is in accordance with IEC 61156-5, requires the connecting hardware at the LDP to provide NEXT and PSNEXT performance 6 dB better than the Category 7A components specified in Clause 9.2.

9.3 Connecting hardware for optical fibre cabling 861

9.3.1 General requirements 862

See 10.3.1, 10.3.2, 10.3.3 and 10.3.5 of ISO/IEC 11801:2008.

9.3.2 ENI requirements 864

For single-mode optical fibre the interface shall be IEC 61754-20 (the LC interface); it shall have a minimum return loss performance of 55 dB provided by an angled face connection, in accordance with IEC 61755-3-2.

It is recommended that the interface at the other end of the network access cabling permanent link should maintain this return loss performance.

For the termination of one or two multimode optical fibres the interface shall be IEC 61754-20 (the LC interface); it shall have a minimum return loss performance of 20 dB.

9.3.3 EO requirements 872

For the termination of one or two single-mode optical fibres the interface shall be IEC 61754-20 (the LC interface)

For the termination of one or two multimode optical fibres the interface shall be IEC 61754-20 (the LC interface)

For the termination of more than two optical fibres the interface shall be IEC 61754-7 (the MPO interface). See ISO/IEC 14763-2 regarding optical fibre polarity management.

Page 34: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 33 - 2nd FCD ISO/IEC 24764:2009-04-21

9.3.4 Optical fibre pin assignments at the EO 879

ISO/IEC JTC 1/SC 25N1643.doc

880 881

882 883

For the optical fibre connecting hardware in 9.3.3 the optical fibre pin assignments shall be as shown in Figure 14.

Polarity of fibres should be identified at the EO, by means of any combination of latching, keying or labelling.

a) IEC 61754-20 interface for one or two optical fibres (not to scale)

B AB A

b) IEC 61754-7 interface for more than two optical fibres (not to scale)

12 11 10 9 8 7 6 5 34 2 112 11 10 9 8 7 6 5 34 2 1

Figure 14 - Optical fibre pin assignments at the EO, front view of fixed connector 884

887

889

890

892

893

10 Requirements for cords and jumpers in data centres 885

10.1 Jumpers 886

See Clause 8.

10.2 Balanced cords 888

See Clause 13 of ISO/IEC 11801:2008.

Field-terminated cords should not be used.

10.3 Optical fibre cords 891

Optical fibre cables used for cords shall meet IEC 60794-2-11.

Field-terminated cords should not be used.

Page 35: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 34 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

894 895 896 897

899 900

901 902 903 904 905

906 907 908

Annex A (normative)

Link performance limits

A.1 General 898

This annex contains performance requirements for permanent links and LDP links as shown in Figure A. 1 and relates to Annex A of ISO/IEC 11801:2008.

The cabling under test in configurations PL1, PL2 and PL3 is termed the permanent link. The configurations PL1 and PL2 comprise fixed cabling only. Configuration PL3 comprises fixed cabling and a LDP cable between the LDP and the EO. If the LDP cable is changed, performance of this configuration will change. The cabling under test in configuration LDP1 contains fixed cabling only and is termed the LDP link.

In all configurations the test reference plane of a permanent link or LDP link is within the test cord. The test cord connection which mates with the termination point of the permanent link or LDP under test is part of the link under test.

Page 36: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 35 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

909

a) Configuration PL1

C

PP

TesterCTester C C

PP/ENI

Permanent link

Network access/

Main distribution cabling

C

PP

TesterCTester C C

PP/ENI

Permanent link

Network access/

Main distribution cabling

b) Configuration PL2

C

PP

TesterCTester C C

EO

Permanent link

Zone distribution cabling

C

PP

TesterCTester C C

EO

Permanent link

Zone distribution cabling

c) Configuration PL3

Tester

EOLDP

C C

PP

Tester C C C

Permanent link

Zone distribution cabling

Tester

EOLDP

C C

PP

Tester C C C

Permanent link

Zone distribution cabling

d) Configuration LDP1

LDP

C C

PP

Tester C TesterC

LDP link

Zone distribution cabling

LDP

C C

PP

Tester C TesterC

LDP link

Zone distribution cabling

C = connection; PP = Patch panel; ENI = External network interface; EO = Equipment outlet; LDP = Local distribution point

Figure A. 1 - Link options 910

912 913

914 915

916 917 918 919

A.2 Balanced cabling 911

Consideration should be given to measuring performance at worst case temperatures, or calculating worst case performance based on measurements made at other temperatures.

Link performance shall meet the requirements of ISO/IEC 11801 Annex A.2, for Class EA, F and FA.

The creation of Class FA Configuration PL3 permanent link (See Figure A.1), where the LDP cable is in accordance with IEC 61156-5, requires the connecting hardware at the LDP to provide NEXT and PSNEXT performance 6 dB better than the Category 7A components specified in Clause 9.2.

Page 37: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 36 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

920 921

923 924 925 926

927 928

929

930 931 932

In the case of cable sharing, additional requirements shall be taken into account for balanced cabling. The additional crosstalk requirements are specified in Clause 9.3 of ISO/IEC 11801:2008.

A.3 Optical fibre cabling 922

The attenuation of a link at a specified wavelength shall not exceed the sum of the specified attenuation values for the cabling components at that wavelength (where the attenuation of a length of optical fibre cable is calculated from its attenuation coefficient multiplied by its length).

Measurements made shall be consistent with the design values of cable length and cabling materials used.

The attenuation of a link shall be measured according to ISO/IEC 14763-3.

NOTE The test methods have been developed for conventional optical fibre connection systems comprising two plugs and an adaptor. In some cases the methods are not appropriate for Small Form Factor connectors that comprise a plug and socket.

Page 38: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 37 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

933 934 935 936

938 939

940

941 942

943

944

945

946

947

948

949

950

951 952

954 955

Annex B (informative)

Usage of high density connecting hardware within optical fibre cabling

B.1 General 937

For the purposes of this Annex, the term “high density connecting hardware” refers to optical fibre connecting hardware that provides interconnection:

of multi-element cabling (more than two optical fibres)

at a greater density than is possible using groups of the duplex optical fibre interface as specified at the EO (see Clause 9)

through a transition assembly, or a fan-out cord

High density connecting hardware may be required in the following locations:

interfaces to switchblades for high density switches;

interfaces to equipment using parallel optics sources and detectors;

one or both ends of equipment cords at distributors;

one or both ends of patch cords at distributors;

LDPs;

interfaces that replace duplex EO connectors.

High density connecting hardware may be used as replacement or in combination with the duplex interface specified Clause 9.

B.2 Structure of cabling subsystems 953

Examples of high density connecting hardware within cabling subsystems in accordance with Clause 5 are shown in Figure B. 1 (main distribution cabling) and

Page 39: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 38 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

956 Figure B. 2 (zone distribution cabling).

EQP

MD

H H

ZD

H EQPH

Channel

H = high density connecting hardware

HC

C

C

C

C

EQP

MD

EQP

ZD

CH

C

C

C

C

CC

EQP

MD

H H H

ZD

EQPH H H

Transition assembly

High density equipment

cord

High density equipment

cord

Equipment cord

High density equipment

cord

Transition assembly

High density equipment

cord

Equipment cord

C = connecting hardware

EQP

MD

H H

ZD

H EQPH

Channel

H = high density connecting hardwareH = high density connecting hardware

HC

C

C

C

C

HHC

C

C

C

C

EQP

MD

EQP

ZD

CH

C

C

C

C

CC

EQP

MD

H H H

ZD

EQPH H H

Transition assembly

High density equipment

cord

High density equipment

cord

Equipment cord

High density equipment

cord

Transition assembly

High density equipment

cord

Equipment cord

C = connecting hardware 957

958 959

Figure B. 1 - Examples of high density connecting hardware within main distribution cabling

Page 40: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 39 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

960

EQPCH

C

C

C

C

C

EO

CH

C

C

C

C

LDP

EO

EQPC

Transition assembly

Equipment cord

Equipment cord

LDP cord

EQPCH

C

C

C

C

C

EO

CH

C

C

C

C

LDP

EO

EQPC

Transition assembly

Equipment cord

Equipment cord

LDP cord

H EQPH

EO

H EQPH

EO

H

LDP

High density equipment

cord

High density equipment

cord

LDP cord

H EQP

EO

Transition assembly

C

C

C

C

C

H = high density connecting hardware C = connecting hardware

H EQPH

EO

H EQPH

EO

H

LDP

High density equipment

cord

High density equipment

cord

LDP cord

H EQP

EO

Transition assembly

C

C

C

C

C

H = high density connecting hardwareH = high density connecting hardware C = connecting hardware

961

962 963

Figure B. 2 - Examples of high density connecting hardware at the LDP and EO within zone distribution cabling

Page 41: 2nd Final Committee Draft ISO/IEC FCD 24764 2009-04-21 N 1643 · International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment,

ISO/IEC JTC 1/SC 25 N 1643 - 40 - 2nd FCD ISO/IEC 24764:2009-04-21

ISO/IEC JTC 1/SC 25N1643.doc

964

965 966

967 968

969

Bibliography

ISO/IEC 18010, Information technology – Pathways and spaces for customer premises cabling

IEC 60794-2-10, Optical fibre cables - Part 2-10: Indoor cables - Family specification for simplex and duplex cables