ISO/IEC JTC 1/SC 25 N 1643 Date 2009-04-21
Secretary - ISO/IEC JTC 1/SC 25 - Dr.-Ing. Walter P. von Pattay Member of ZVEI FV 7 & FV 8, Germany Tel.: +49/89/923 967 57, Tfx.: +49/89/923 967 59 (on request only) EM: [email protected]
Home page: ” http://sc25.iec.ch/”
2nd Final Committee Draft ISO/IEC FCD 24764
Date: 2009-04-21 Reference number: ISO/IEC JTC 1/SC 25 N 1643
Supersedes document SC 25 N/A
THIS DOCUMENT IS STILL UNDER STUDY AND SUBJECT TO CHANGE. IT SHOULD NOT BE USED FOR REFERENCE PURPOSES.
ISO/IEC JTC 1/SC 25 INTERCONNECTION OF INFORMATION TECHNOLOGY EQUIPMENT
Secretariat: Germany (DIN)
Circulated to P- and O-members, and to technical committees and organizations in liaison for: - voting by (P-members only)
2009-08-22
Please return all votes and comments in electronic form using the attached template
directly to the SC 25 Secretariat by the due date indicated.
ISO/IEC 2nd FCD 24764
Title: Information technology - Generic cabling systems for Data Centres
Project: 1.25.03.10
Introductory note: This FCD is distributed for approval as FDIS.
The NWIP was distributed with SC 25 N 1063 and JTC 1 N 7919. It was approved as recorded in SC 25 N 942.
CDs were distributed with SC 25 N 1297, N 1463 and N 1576. A 1st FCD was distributed with SC 25 N 1603A Id did not find substantial support as recorded in SC 25N 1633. The comments received on N 1633 have been resolved by SC 25/WG 3 at its meeting los Cabos, Mexico, 2009-03-23/27 as recorded in SC 25 N 1642. The text has been updated accordingly and is distributed with this document for approval as FDIS.
REQUESTED: National Member Bodies of ISO/IEC JTC 1/SC 25 are ACTION requested to vote on this document.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights (not listed in the draft) of which they are aware and to provide supporting documentation.
Medium: Defined
No. of pages: 43
ISO/IEC JTC 1/SC 25 N 1643 - 1 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
Information technology - Generic cabling systems for Data Centres
CONTENTS
Introduction ..........................................................................................................................5 1 Scope ............................................................................................................................7 2 Normative references .....................................................................................................7 3 Definitions and abbreviations ..........................................................................................8
3.1 Definitions .............................................................................................................8 3.1.7 main distribution cable ...............................................................................9
3.2 Abbreviations ........................................................................................................9 4 Conformance................................................................................................................10 5 Structure of the generic cabling system in data centres .................................................11
5.1 General ...............................................................................................................11 5.2 Functional elements.............................................................................................11 5.3 General structure and hierarchy ...........................................................................11 5.4 Cabling subsystems.............................................................................................12
5.4.1 Network access cabling subsystem ..........................................................13 5.4.2 Main distribution cabling subsystem .........................................................13 5.4.3 Zone distribution cabling subsystem .........................................................13 5.4.4 Design objectives.....................................................................................13
5.5 Accommodation of functional elements.................................................................14 5.6 Interfaces ............................................................................................................14
5.6.1 Equipment interfaces and test interfaces ..................................................14 5.6.2 Channels and links...................................................................................14
5.7 Dimensioning and configuring ..............................................................................16 5.7.1 Distributors ..............................................................................................16 5.7.2 Redundancy.............................................................................................16 5.7.3 External network interface ........................................................................17 5.7.4 Cables .....................................................................................................18 5.7.5 Equipment cords ......................................................................................18 5.7.6 Patch cords and jumpers ..........................................................................18 5.7.7 Equipment outlets ....................................................................................18 5.7.8 LDP .........................................................................................................18 5.7.9 Building entrance facilities........................................................................19
5.8 Earthing and equipotential bonding ......................................................................19 6 Channel performance in data centres ............................................................................19
6.1 General ...............................................................................................................19 6.2 Transmission performance ...................................................................................20
6.2.1 General ...................................................................................................20 6.2.2 Balanced cabling .....................................................................................20 6.2.3 Optical fibre cabling .................................................................................20
7 Reference implementations in data centres ...................................................................21 7.1 General ...............................................................................................................21 7.2 Balanced cabling .................................................................................................21
ISO/IEC JTC 1/SC 25 N 1643 - 2 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84 85
86
87
88
89
7.2.1 Assumptions ............................................................................................21 7.2.2 Zone distribution cabling ..........................................................................21 7.2.3 Main distribution cabling...........................................................................24 7.2.4 Network access cabling............................................................................26
7.3 Optical fibre cabling .............................................................................................28 7.3.1 Assumptions ............................................................................................28 7.3.2 Component choice ...................................................................................28 7.3.3 Optical fibre cabling channel lengths ........................................................28
8 Cable requirements in data centres ...............................................................................29 8.1 General ...............................................................................................................29 8.2 Balanced cables ..................................................................................................29 8.3 Optical fibre cables ..............................................................................................29
9 Connecting hardware requirements in data centres .......................................................29 9.1 General requirements ..........................................................................................29
9.1.1 Applicability .............................................................................................29 9.1.2 Location...................................................................................................29 9.1.3 Design .....................................................................................................29 9.1.4 Operating Environment ............................................................................29 9.1.5 Mounting..................................................................................................29 9.1.6 Installation practices ................................................................................29 9.1.7 Marking and colour Coding.......................................................................30
9.2 Connecting hardware for balanced cabling ...........................................................30 9.2.1 General requirements...............................................................................30 9.2.2 Performance marking ...............................................................................30 9.2.3 Mechanical characteristics .......................................................................30
9.3 Connecting hardware for optical fibre cabling .......................................................32 9.3.1 General requirements...............................................................................32 9.3.2 ENI requirements .....................................................................................32 9.3.3 EO requirements ......................................................................................32 9.3.4 Optical fibre pin assignments at the EO ....................................................33
10 Requirements for cords and jumpers in data centres .....................................................33 10.1 Jumpers ..............................................................................................................33 10.2 Balanced cords....................................................................................................33 10.3 Optical fibre cords ...............................................................................................33
Annex A (normative) Link performance limits ......................................................................34 A.1 General ........................................................................................................................34 A.2 Balanced cabling ..........................................................................................................35 A.3 Optical fibre cabling......................................................................................................36 Annex B (informative) Usage of high density connecting hardware within optical fibre
cabling .........................................................................................................................37 B.1 General ........................................................................................................................37 B.2 Structure of cabling subsystems....................................................................................37 Bibliography .......................................................................................................................40
ISO/IEC JTC 1/SC 25 N 1643 - 3 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
90
91 92
93
94
95
96
97
98
99
100
101
102
103
104 105
106
107
108 109
110 111
112
113 114
115
116 117
118
119
120
121
122
Figures
Figure 1 - Schematic relationship between the ISO/IEC 11801 series and other standards relevant for information technology cabling systems ..............................................6 Figure 2 - Structure of generic cabling within a data centre ..................................................12 Figure 3 - Hierarchical structure of generic cabling within a data centre ...............................12 Figure 4 - Example of accommodation of functional elements ..............................................14 Figure 5 - Test and equipment interfaces.............................................................................15 Figure 6 - Connection of functional elements providing redundancy .....................................17 Figure 7 – Examples of external service cabling connections to the ENI ...............................18 Figure 8 – Example of a channel with 4 connections ............................................................19 Figure 9 - Example of a system showing the location of cabling interfaces ...........................20 Figure 10 - Zone distribution cabling models........................................................................22 Figure 11 - Main distribution cabling models ........................................................................25 Figure 12 - Network access cabling models .........................................................................27 Figure 13 - Pin grouping and pair assignments at the EO, front view of fixed connector (jack) ..................................................................................................................................31 Figure 14 - Optical fibre pin assignments at the EO, front view of fixed connector ................33 Figure A. 1 - Link options ....................................................................................................35 Figure B. 1 - Examples of high density connecting hardware within main distribution cabling ...............................................................................................................................38 Figure B. 2 - Examples of high density connecting hardware at the LDP and EO within zone distribution cabling .....................................................................................................39
Tables
Table 1 – Length assumptions used in the mathematical modelling of balanced zone distribution cabling..............................................................................................................23 Table 2 - Zone distribution channel length equations ...........................................................24 Table 3 – Length assumptions used in the mathematical modelling of balanced main distribution cabling..............................................................................................................25 Table 4 - Main distribution channel length equations............................................................26 Table 5 - Network access cabling channel equations ...........................................................28 Table 6 - Connecting hardware of the type used at the ENI ..................................................30 Table 7 - Connecting hardware of the type used at the EO...................................................30
ISO/IEC JTC 1/SC 25 N 1643 - 4 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
123
124 125 126 127 128 129
130 131 132
134 135
137 138 139
141 142 143
145
148 149 150 151
153
155
156
157 158 159
160
161 162 163
FOREWORD
1) ISO (International Organization for Standardization) and IEC (International Electrotechnical Commission) form the specialized system for worldwide standardization. National bodies that are members of ISO or IEC participate in the development of International Standards through technical committees established by the respective organization to deal with particular fields of technical activity. ISO and IEC technical committees collaborate in fields of mutual interest. Other international organizations, governmental and non-governmental, in liaison with ISO and IEC, also take part in the work.
2) In the field of information technology, ISO and IEC have established a joint technical committee, ISO/IEC JTC 1. Draft International Standards adopted by the joint technical committee are circulated to national bodies for voting. Publication as an International Standard requires approval by at least 75 % of the national bodies casting a vote.
3) The former decisions or agreements of IEC and ISO on technical matters express, as nearly as possible, an 133 international consensus of opinion on the relevant subjects since each technical committee has representation from all interested IEC and ISO member bodies.
4) IEC, ISO and ISO/IEC publications have the form of recommendations for international use and are accepted 136 by IEC and ISO member bodies in that sense. Why on all reasonable efforts are made to ensure that the technical content of IEC, ISO and ISO/IEC publications is accurate, IEC or ISO cannot be held responsible for the way in which they are used or for any misinterpretation by any end user.
5) In order to promote international uniformity, IEC and ISO member bodies undertake to apply IEC, ISO and 140 ISO/IEC publications transparency to the maximum extent possible in their national and regional publications. Any divergence between any ISO/IEC publication and the corresponding national or regional publication should be clearly indicated in the latter.
6) ISO and IEC provide no marking procedure to indicate their approval and cannot be rendered responsible for any 144 equipment declared to be in conformity with and ISO/IEC publication.
7) All users should ensure that they have the latest edition of this publication. 146
8) No liability shall attach to IEC or ISO or its directors, employees, servants or agents including individual experts 147 and members of their technical committees and IEC or ISO member bodies for any personal injury, property damage or other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising out of the publication of, use of, or reliance upon, this ISO/IEC publication or any other IEC, ISO or ISO/IEC publications.
9) Attention is drawn to the normative references cited in this publication. Use of the referenced publications is 152 indispensable for the correct application of this publication.
10) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject of 154 patent rights. ISO and IEC shall not be held responsible for identifying any or all such patent rights.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
International Standard ISO/IEC 24764 was prepared by subcommittee 25: Interconnection of information technology equipment, of ISO/IEC joint technical committee 1: Information technology.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This International Standard has taken into account requirements specified in application standards listed in Annex F of ISO/IEC 11801. It refers to International Standards for components and test methods whenever appropriate International Standards are available.
ISO/IEC JTC 1/SC 25 N 1643 - 5 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
164
165 166 167 168 169
170 171 172 173 174 175
176
178
180
182 183
185
186
187 188
189
190 191 192
193 194
195 196
———————
Introduction
Within premises, the importance of the information technology cabling infrastructure is similar to that of other fundamental building utilities such as heating, lighting and mains power. As with other utilities, interruptions to service can have serious impact. Poor quality of service due to lack of design foresight, use of inappropriate components, incorrect installation, poor administration or inadequate support can threaten an organisation's effectiveness.
Cabling within data centres comprises both application-specific and multipurpose networks that are mission-critical. Generic cabling designs in accordance with ISO/IEC 11801 have supported the development of high data rate applications based upon a defined cabling model. This International standard recognizes the benefit of generic cabling to provision multiple services and to connect large quantities of equipment within the limited space of data centre premises, and is to be used in conjunction with ISO/IEC 11801.
This International Standard provides:
a) data centre users with an application independent generic cabling system capable of 177 supporting a wide range of applications;
b) data centre users with a flexible cabling scheme such that modifications are both easy 179 and economical;
c) data centre professionals (for example, data centre architects) with guidance allowing the 181 accommodation of cabling before specific requirements are known; that is, in the initial planning either for construction or refurbishment;
d) industry and applications standardization bodies with a cabling system which supports 184 current products and provides a basis for future product development.
This International Standard specifies multi-vendor cabling, and is related to:
the associated standard covering general requirements for generic cabling within premises (ISO/IEC 11801);
standards for cabling components developed by Technical Committees of the IEC;
standards for the quality assurance, installation and administration of information technology cabling (ISO/IEC 14763-2) and testing of installed cabling (IEC 61935-1 and ISO/IEC 14763-3);
applications developed by the technical committees of IEC, subcommittees of ISO/IEC JTC 1 and study groups of ITU-T 1).
It is anticipated that the generic cabling system meeting the requirements of this International Standard will have a life expectancy up to ten years.
1) International Telecommunication Union - Telecommunications Standardization Sector.
ISO/IEC JTC 1/SC 25 N 1643 - 6 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
197 198 199 200
Figure 1 shows the schematic and contextual relationships between the standards produced by ISO/IEC JTC 1/SC 25 for information technology cabling, namely this and other generic cabling design standards (ISO/IEC 11801), cabling installation standards (ISO/IEC 14763-2), testing of installed cabling (IEC 61935-1 and ISO/IEC 14763-3).
ISO/IEC 11801: Information technology: Generic cabling for customer premises
ISO/IEC 24764: Information technology: Generic cabling systems for Data Centres
ISO/IEC 18010: Information technology. Pathways and spaces for customer premises cabling
ISO/IEC 14763-2: Information technology. Quality assurance, installation and administration
IEC 61935-1: Generic cabling systemsSpecifications for the testing of balanced communication cabling
IEC 60364-1: Electrical installations of buildings: Fundamental principles, assessment of general characteristics, definitions
ISO/IEC 14763-3: Information technology: Testing of optical fibre cabling
ISO/IEC 11801: Information technology: Generic cabling for customer premises
ISO/IEC 24764: Information technology: Generic cabling systems for Data Centres
ISO/IEC 18010: Information technology. Pathways and spaces for customer premises cabling
ISO/IEC 14763-2: Information technology. Quality assurance, installation and administration
IEC 61935-1: Generic cabling systemsSpecifications for the testing of balanced communication cabling
IEC 60364-1: Electrical installations of buildings: Fundamental principles, assessment of general characteristics, definitions
ISO/IEC 14763-3: Information technology: Testing of optical fibre cabling
201
202 203
Figure 1 - Schematic relationship between the ISO/IEC 11801 series and other standards relevant for information technology cabling systems
ISO/IEC JTC 1/SC 25 N 1643 - 7 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
204 205 206
208 209 210
211
212 213 214 215
216
218
220 221 222
223 224 225 226 227
229 230 231
232 233 234
235 236
237 238 239
240 241
242 243
244 245
INFORMATION TECHNOLOGY – GENERIC CABLING SYSTEMS FOR DATA CENTRES
1 Scope 207
This International Standard specifies generic cabling that supports a wide range of communications services for use within a data centre. It covers balanced cabling and optical fibre cabling.
This International Standard is based upon and references the requirements of ISO/IEC 11801.
This International Standard contains additional requirements that are appropriate to data centres in which the maximum distance over which communications services have to be distributed is 2 000 m. The principles of this International Standard may also be applied to data centre installations that do not fall within this range.
In addition to the requirements of ISO/IEC 11801, this International Standard specifies:
a) a modified structure and configuration for generic cabling within data centres used to 217 support existing and emerging applications;
b) a reference implementation specific to data centre infrastructures; 219
Data centres have specific pathway and space requirements that are specified in ISO/IEC 14763-2. Until ISO/IEC 14763-2 is published, relevant information may be found in ISO/IEC 18010.
Safety (electrical safety and protection, fire, optical power etc.) and electromagnetic compatibility (EMC) requirements are outside the scope of this International Standard and are covered by other standards and regulations. However, information given in this International Standard and those identified in Figure 1 can be of assistance in meeting these other standards and regulations.
2 Normative references 228
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
ISO/IEC 11801, Information technology – Generic cabling for customer premises NOTE 1 Parts of this international standard depend on the publication of amendments to ISO/IEC 11801. Until these are published conformance can not be met for links.
NOTE 2 References to ISO/IEC 11801:2008 refer to ISO/IEC Ed.2.1 plus Amendment 2, presently voted on as FPDAM with SC 25 N 1645.
ISO/IEC 14763-2 (under consideration), Information technology - Implementation and operation of customer premises cabling - Part 2: Quality assurance, installation and administration
ISO/IEC 14763-3, Information technology - Implementation and operation of customer premises cabling - Part 3: Testing of optical fibre cabling
IEC 60603-7, Connectors for electronic equipment - Part 7: Detail specification for 8-way, unshielded, free and fixed connectors
IEC 60603-7-1, Connectors for electronic equipment - Part 7-1: Detail specification for 8-way, shielded free and fixed connectors with common mating features, with assessed quality
ISO/IEC JTC 1/SC 25 N 1643 - 8 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
246 247
248 249
250 251
252 253 254
255 256
257 258 259
260 261
262 263 264
265 266 267
268 269 270
271
272
273 274 275
276 277
280 281
283 284 285
IEC 60603-7-2, Connectors for electronic equipment - Part 7-2: Detail specification for 8-way, unshielded, free and fixed connectors, for data transmissions with frequencies up to 100 MHz
IEC 60603-7-3, Connectors for electronic equipment - Part 7-3: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with frequencies up to 100 MHz
IEC 60603-7-4, Connectors for electronic equipment - Part 7-4: Detail specification for 8-way, unshielded, free and fixed connectors, for data transmissions with frequencies up to 250 MHz
IEC 60603-7-41, Connectors for electronic equipment - Part 7-41: Detail specification for 8-way, unshielded, free and fixed connectors, for data transmission with frequencies up to 500 MHz (under consideration)
IEC 60603-7-5, Connectors for electronic equipment - Part 7-5: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with frequencies up to 250 MHz
IEC 60603-7-51, Connectors for electronic equipment - Part 7-51: Detail specification for 8-way, shielded, free and fixed connectors, for data transmission with frequencies up to 500 MHz (under consideration)
IEC 60603-7-7, Connectors for electronic equipment - Part 7-7: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with frequencies up to 600 MHz
IEC 60603-7-71, Connectors for electronic equipment - Part 7-71: Detail specification for 8-way, shielded, free and fixed connectors, for data transmission with frequencies up to 1 000 MHz (under consideration)
IEC 61076-3-104, Connectors for electronic equipment - Product requirements - Part 3-104: Detail specification for 8-way, shielded free and fixed connectors for data transmissions with frequencies up to 1 000 MHz
IEC 61156-5, Multicore and symmetrical pair/quad cables for digital communications - Part 5: Symmetrical pair/quad cables with transmission characteristics up to 1 000 MHz-horizontal floor wiring - Sectional specification
IEC 61754-7, Fibre optic connector interfaces – Part 7: Type MPO connector family
IEC 61754-20, Fibre optic connector interfaces - Part 20: Type LC connector family
IEC 61755-3-2, Fibre optic connector optical interfaces - Part 3-2: Optical interface, 2,5 mm and 1,25 mm diameter cylindrical full zirconia ferrules for 8 degrees angled-PC single mode fibres
IEC 61935-1, Generic specification for the testing of elements of generic cabling in accordance with ISO/IEC 11801 – Part 1: Test methods
3 Definitions and abbreviations 278
3.1 Definitions 279
For the purposes of this International Standard the following definitions apply in addition to those of ISO/IEC 11801.
3.1.1 282 cabled optical fibre Category system of defining requirements for the cabled optical fibre performance within optical fibre channels and links.
ISO/IEC JTC 1/SC 25 N 1643 - 9 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
287 288 289
291 292 293
295 296 297
299 300
302 303 304
306 307
309 310 311 312
314 315
317 318
320 321 322 323
325 326
327
328
329
330
3.1.2 286 equipment outlet fixed connecting device for terminating the zone distribution cabling and providing the interface to the equipment cabling
3.1.3 290 fixed zone distribution cable cable connecting the zone distributor to either the equipment outlet or, if present, the local distribution point
3.1.4 294 local distribution point connection point in the zone distribution cabling subsystem between a zone distributor and an equipment outlet
3.1.5 298 local distribution point cable cable connecting a local distribution point to an equipment outlet
3.1.6 301 local distribution point link transmission path between a local distribution point and the interface at the other end of the fixed zone distribution cable including the connecting hardware at each end
3.1.7 305 main distribution cable cable connecting the main distributor to the zone distributor
3.1.8 308
main distributor distributor used to make connections between the main distribution cabling subsystem, network access cabling subsystem and cabling subsystems specified in ISO/IEC 11801 and active equipment
3.1.9 313 network access cable cable connecting the external network interface to the main distributor or zone distributor
3.1.10 316 zone distribution cable cable connecting the zone distributor to the equipment outlet(s) or local distribution point(s)
3.1.11 319 zone distributor distributor used to make connections between the main distribution cabling subsystem, zone distribution cabling subsystem, network access cabling subsystem and cabling subsystems specified in ISO/IEC 11801 series and active equipment
3.2 Abbreviations 324
For the purposes of this International Standard the following abbreviations apply in addition to those of ISO/IEC 11801.
BEF Building entrance facility
ENI External network interface
EO Equipment outlet
LDP Local distribution point
ISO/IEC JTC 1/SC 25 N 1643 - 10 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
331
332
333
335
336
337 338 339
340 341
342 343 344 345
346 347 348
349 350
351 352
353
354 355
356 357 358 359 360
361 362
363 364 365 366
367 368
MD Main distributor
OE EQP Opto-electronic equipment
ZD Zone distributor
4 Conformance 334
For a cabling system to conform to this International Standard:
a) The configuration and structure shall conform to the requirements of Clause 5;
b) The performance of balanced channels shall conform to the transmission performance and environmental requirements of Clause 6. This shall be achieved by one of the following:
1) a channel design and implementation ensuring that the prescribed channel performance is met;
2) Attachment of appropriate components to a link design meeting the prescribed performance class of Clause 6 and Annex A Channel performance shall be ensured where a channel is created by adding more than one cord to either end of a link meeting the requirements of Clause 6 and Annex A;
3) Using the reference implementations of Clause 7 and compatible cabling components conforming to the requirements of Clauses 8, 9 and 10, based upon a statistical approach of performance modelling.
c) The implementation and performance of optical fibre cabling channels shall meet the requirements specified in Clause 6.
d) The interfaces to the cabling shall conform to the requirements of Clause 9 with respect to mating interfaces and performance
e) If present, screens shall be handled as specified in Clause 11 of ISO/IEC 11801:2008.
f) Regulations on safety and EMC applicable at the location of the installation shall be met.
Test methods to assess conformance with the channel and link requirements of Clause 6 and Annex A respectively are specified in IEC 61935-1 for balanced cabling and ISO/IEC 14763-3 for optical cabling. The treatment of measured results that fail to meet the requirements of this clause, or lie within the relevant measurement accuracy, shall be clearly documented within a quality plan as described in ISO/IEC 14763-2.
Installation and administration of cabling in accordance with this International standard shall be undertaken in accordance with ISO/IEC 14763-2.
This standard does not specify which tests and sampling levels should be adopted. The test parameters to be measured and the sampling levels to be applied for a particular installation shall be defined in the installation specification and quality plans for that installation prepared in accordance with ISO/IEC 14763-2.
Specifications marked "ffs" (for further study) in ISO/IEC 11801 are preliminary and are not required for conformance to this International Standard.
ISO/IEC JTC 1/SC 25 N 1643 - 11 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
371 372 373
374 375
376 377 378 379 380
382 383
393
395 396 397 398
399 400 401 402
403 404
405 406 407 408 409 410
5 Structure of the generic cabling system in data centres 369
5.1 General 370
This clause identifies the functional elements of generic cabling for data centres, describes how they are connected together to form subsystems and identifies the interfaces at which application-specific components are connected to the generic cabling.
Applications listed in Annex F of ISO/IEC 11801:2008 are supported by connecting active equipment at the external network interfaces, equipment outlets and the distributors.
The structured cabling system specified by this International Standard is intended to restrict the use of cords for point-to-point cabling within data centres, which can be detrimental to the administration and operation of the data centre. Exceptions are permitted between equipment located in close proximity or between equipment that cannot communicate over the generic cabling system.
5.2 Functional elements 381
In addition to the distributors specified in ISO/IEC 11801, this standard specifies the following functional elements and interfaces of generic cabling:
a) external network interface (ENI); 384
b) network access cable; 385
c) main distributor (MD); 386
d) main distribution cable; 387
e) zone distributor (ZD); 388
f) zone distribution cable; 389
g) local distribution point (LDP); 390
h) local distribution point cable (LDP cable); 391
i) equipment outlet (EO). 392
Groups of these functional elements are connected together to form cabling subsystems.
5.3 General structure and hierarchy 394
Generic cabling systems in data centres contain up to three cabling subsystems: network access cabling, main distribution cabling and zone distribution cabling. Where present within the premises, a distributor in accordance with ISO/IEC 11801 is connected to the generic cabling within the data centre using the network access cabling.
The cabling subsystems are connected together to create a generic cabling system with a structure as shown in Figure 2. The composition of the cabling subsystems is described in 5.4.1, 5.4.2 and 5.4.3. The functional elements of the cabling subsystems are interconnected to form a basic hierarchical topology as shown in Figure 3.
Where the functions of distributors are combined (see 5.7.1) the intermediate cabling subsystem(s) are not required.
Connections between cabling subsystems are either active, requiring application-specific equipment, or passive. Connection to application-specific equipment at an MD and ZD adopts either an interconnect or a cross-connect approach (see ISO/IEC 11801). Connection to application-specific equipment at an ENI and EO adopts an interconnect approach (see ISO/IEC 11801). Passive connections between cabling subsystems adopt either a cross-connect approach, by way of either patch cords or jumpers, or an interconnect approach.
ISO/IEC JTC 1/SC 25 N 1643 - 12 - 2nd FCD ISO/IEC 24764:2009-04-21
Networkaccess cabling
subsystem
Main distributioncabling
subsystem
Zone distributioncabling subsystem
Generic cabling system
Distributorin accordancewith ISO/IEC 11801
ENI LDPMD ZD EO
Equipmentcabling
EQP
Networkaccess cabling
subsystem
Main distributioncabling
subsystem
Zone distributioncabling subsystem
Generic cabling system
Distributorin accordancewith ISO/IEC 11801
ENI LDPMD ZD EO
Equipmentcabling
EQPEQPEQP
411
412 Figure 2 - Structure of generic cabling within a data centre
Main distribution cabling subsystem
Network access cabling subsystem
Zone distributioncabling subsystem
optional cables
ZD
LDP LDP
ZD
LDP LDP
MD
ENI ENIDistributorin accordancewith ISO/IEC 11801
EO EO EO EO EO EO EO EO EO EO
Main distribution cabling subsystem
Network access cabling subsystem
Zone distributioncabling subsystem
optional cables
ZD
LDP LDP
ZD
LDP LDP
MD
ENI ENIDistributorin accordancewith ISO/IEC 11801
EO EO EO EO EO EO EO EO EO EO
413
414
416 417
NOTE Network access cabling is also used to connect ENI to ZD.
Figure 3 - Hierarchical structure of generic cabling within a data centre
5.4 Cabling subsystems 415
Although equipment cords are used to connect the equipment to a cabling subsystem, they are not considered part of the cabling subsystem.
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 13 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
419 420
421
425
427 428
431
433 434
436 437
440
444 445 446
448 449
450
451 452
453 454
5.4.1 Network access cabling subsystem 418
The network access cabling subsystem extends from an MD (or ZD) to the ENIs and/or other distributors (in accordance with ISO/IEC 11801) connected to it.
The subsystem includes:
a) the network access cables; 422
b) the mechanical termination of the network access cables at the ENI(s); 423
c) the mechanical termination of the network access cables at the MD, ZD(s) or other 424 distributors in accordance with ISO/IEC 11801.
5.4.2 Main distribution cabling subsystem 426
The main distribution cabling subsystem extends from an MD to the ZD(s) connected to it. The subsystem includes:
a) the main distribution cables; 429
b) the mechanical termination of the main distribution cables at the MD together with 430 associated patch cords and/or jumpers at the MD;
c) the mechanical termination of the main distribution cables at the ZD(s). 432
Although equipment cords are used to connect the equipment to the cabling subsystem, they are not considered part of the cabling subsystem.
5.4.3 Zone distribution cabling subsystem 435
The zone distribution cabling subsystem extends from a ZD to the EO(s) connected to it. The subsystem includes:
a) the zone distribution cables; 438
b) the mechanical termination of the zone distribution cables at the EO(s) and the ZD 439 together with associated patch cords and/or jumpers at the ZD;
c) LDP(s) (optional); 441
d) LDP cable(s) (optional) ; 442
e) the EO(s). 443
Although equipment cords are used to connect the equipment to the cabling subsystem, they are not considered part of the cabling subsystem. Zone distribution cables shall be continuous from the ZD to the EO(s) unless (an) LDP(s) is installed (see 5.7.8).
5.4.4 Design objectives 447
In order to provide the longest operational life while minimising the disruption and cost associated with re-cabling, the fixed installed cabling should be designed to:
support the broadest set of existing and emerging applications;
accommodate the anticipated growth in volume of supported applications throughout the predicted lifetime of the installation.
In addition the provision of redundancy within a cabling design should be considered (also see 5.7.1)
ISO/IEC JTC 1/SC 25 N 1643 - 14 - 2nd FCD ISO/IEC 24764:2009-04-21
5.5 Accommodation of functional elements 455
ISO/IEC JTC 1/SC 25N1643.doc
456 457
458 459
460 461
Figure 4 shows an example of how the functional elements are accommodated in a building (only a single floor of the building is shown for simplicity).
The MD, ZD and LDP shall be housed in permanent and accessible locations within the data centre.
The ENI shall be housed in permanent and accessible location either internal or external to the data centre.
ENI
BEF
MD ZD
Distributorin accordancewith ISO/IEC 11801
Equipment/telecommunications roomin accordancewith ISO/IEC 11801
Data centre
EO
LDP
ENI
BEF
MD ZD
Distributorin accordancewith ISO/IEC 11801
Equipment/telecommunications roomin accordancewith ISO/IEC 11801
Data centre
EO
LDP 462
463
466 467 468
469 470
472 473
474 475 476 477 478 479
480 481 482 483 484 485
Figure 4 - Example of accommodation of functional elements
5.6 Interfaces 464
5.6.1 Equipment interfaces and test interfaces 465
Potential equipment interfaces for data centres are located at the ends of the cabling subsystems (as shown in Figure 5). An LDP does not provide an equipment interface to the generic cabling system.
Potential test interfaces for data centres are located at the ends of the cabling subsystems and at the LDP, if present (as shown in Figure 5).
5.6.2 Channels and links 471
The transmission performance of generic cabling between specific test interfaces is detailed in Clause 6 for channels and Annex A for links.
The channel is the transmission path between data centre equipment such as a switches and servers (EQP in Figure 5). A typical channel in a data centre would consist of the zone distribution cabling subsystem together with an equipment cord at each end. For longer reach services the channel would be formed by the connection of two or more subsystems (including patch cords and equipment cords). The performance of the channel excludes the connections at the application-specific equipment.
The permanent link is the transmission path of an installed cabling subsystem including the connecting hardware at the ends of the installed cable. In a data centre zone distribution cabling subsystem, the permanent link consists of the equipment outlet, the zone distribution cable, an optional LDP, an optional LDP cable and the termination of the zone distribution cable at the zone distributor. The permanent link includes the connections at the ends of the installed cabling.
ISO/IEC JTC 1/SC 25 N 1643 - 15 - 2nd FCD ISO/IEC 24764:2009-04-21
a) Zone distribution cabling
b) Main distribution cabling
EQPC CEQP C C
TI TI
EI EI EI
TI
C
EI
MD ZD
TI
C
LDP
EOEQPC CEQP C C
TI TI
EI EI EI
TI
C
ZD
TI TI
C
a) Zone distribution cabling
b) Main distribution cabling
EQPC CEQP C C
TI TI
EI EI EI
TI
C
EI
MD ZD
TI
C
LDP
EOEQPC CEQP C C
TI TI
EI EI EI
TI
C
ZD
TI TI
C
486
c) Network access cabling from MD to distributor in accordance with ISO/IEC 11801
d) Network access cabling from MD to ENI
EQPC CEQP C C
TI TI
EI EI EI
TI
C
EI
MD
TI
C
Distributor in accordancewith ISO/IEC 11801
ENIEQPC CEQP C C
TI TI
EI EI EI
MD
TI TI
C
See NOTE
c) Network access cabling from MD to distributor in accordance with ISO/IEC 11801
d) Network access cabling from MD to ENI
EQPC CEQP C C
TI TI
EI EI EI
TI
C
EI
MD
TI
C
Distributor in accordancewith ISO/IEC 11801
ENIEQPC CEQP C C
TI TI
EI EI EI
MD
TI TI
C
See NOTE 487
491
NOTE Where the EQP connected to the ENI lies outside the premises containing the data centres, the 488 interconnecting cord will typically comprise a combination of fixed cabling and cords that are outside the scope of 489 this standard. In such cases the connection to the EQP may not provide a TI. 490
Figure 5 - Test and equipment interfaces
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 16 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
494 495
496 497 498 499
500 501 502 503
504 505
507 508 509
510 511 512 513 514 515
5.7 Dimensioning and configuring 492
5.7.1 Distributors 493
The number and type of subsystems that are included in a generic cabling implementation depends upon the layout and size of the data centre and upon the strategy of the user.
The design of distributors shall ensure that the length of patch cords, jumpers and equipment cords are minimized and administration should ensure that the design lengths are maintained during operation. Distributors should be located such that the resulting cable lengths are consistent with the channel performance requirements of Clause 6.
Where the components of Clauses 8, 9 and 10 are used the distributors shall be located in accordance with the reference implementations of Clause 7. Where other components are used, distributors shall be located so that the desired performance Class of Clause 6 is delivered.
The functions of multiple distributors may be combined into a single distributor. For example, a MD may serve the function of a ZD. However, every data centre must have at least one MD.
5.7.2 Redundancy 506
Consideration should be given to the resilience of the data centre with respect to the cabling infrastructure. This may be enhanced by the provision of redundant distributors, cabling, and pathways.
In certain circumstances, for example for security or reliability reasons, redundancy may be built into a cabling design. Figure 6 shows one of many possible examples of the connection of functional elements within the structured framework to provide such protection against failure in one or more parts of the cabling infrastructure. This might form the basis for the design of generic cabling for a data centre providing some protection against such hazards as fire damage or the failure of an external network.
ISO/IEC JTC 1/SC 25 N 1643 - 17 - 2nd FCD ISO/IEC 24764:2009-04-21
Distributorin accordancewith ISO/IEC 11801
MDMD
ENI ENI
ZDZD
LDPLDP
EO EO EO EO EO EO EO EOEO EO EO EO
Distributorin accordancewith ISO/IEC 11801
MDMD
ENI ENI
ZDZD
LDPLDP
EO EO EO EO EO EO EO EOEO EO EO EO 516
517
518 519
520 521
523 524
525
526
527 528
Figure 6 - Connection of functional elements providing redundancy
Additionally, redundancy may be provided by utilizing multiple cables between distributors, with cables following different routes.
NOTE: Connections between ZD and ZD are in addition to the connection between MD and ZD and not a replacement for the MD to ZD connection
5.7.3 External network interface 522
The External Network Interface (ENI) is a termination of the network access cabling that allows connection of external services to the network access cabling as shown in Figure 7.
NOTE: The multiple service providers should have diverse routes to each of the multiple ENIs.
The ENI interface shall be in accordance with Clause 9.
Where the components of Clauses 8, 9 and 10 are used the ENIs shall be located in accordance with the reference implementations of Clause 7.
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 18 - 2nd FCD ISO/IEC 24764:2009-04-21
EQP
Network access cabling
ENI
C
ENI
C
ENI
C
External service cabling(beyond the scope of this standard)
Interconnection
Crossconnection
Connection of networkaccess cabling to externalservice cabling may includepassive or active equipment
EQP
Network access cabling
ENI
C
ENI
C
ENI
C
External service cabling(beyond the scope of this standard)
Interconnection
Crossconnection
Connection of networkaccess cabling to externalservice cabling may includepassive or active equipment
529
530
532
534
536 537 538
540 541 542 543
544
545
547 548 549 550 551
552 553 554 555
Figure 7 – Examples of external service cabling connections to the ENI
5.7.4 Cables 531
Cable types used in the reference implementations of Clause 7 are specified in Clause 8.
5.7.5 Equipment cords 533
Equipment cords are non-permanent and can be application-specific.
5.7.6 Patch cords and jumpers 535
Patch cords and jumpers are used within cross-connect implementations at distributors. The performance contribution of these cords shall be taken into account in the design of the channel. Clause 7 provides guidance on cord/jumper lengths for reference implementations of generic cabling.
5.7.7 Equipment outlets 539
The design of generic cabling should provide for EOs to be installed with a high density and located in close proximity to the application-specific equipment to which they are to be connected. The number of cable elements presented at the EO is not restricted by this standard.
A group of EOs can be served directly by multiple ZDs or by multiple ZDs via multiple LDPs.
The EO interface presented shall be in accordance with Clause 9.
5.7.8 LDP 546
The installation of an LDP in the zone distribution cabling between the ZD and the EO may be useful where frequent additions or movements of equipment are required. One LDP is permitted between a ZD and any EO. The LDP shall be an interconnect, not a cross-connect, because the LDP adds one connection per channel. There shall be no active equipment in the LDP area with the exception of DC powering equipment.
Where an LDP is used, it shall have sufficient capacity to support the area of the data centre which it is designed to serve during its intended operational life. The area served may be defined in terms of number of frames/cabinets/closures to be supported and should include allowance for growth.
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 19 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
556 557
558 559 560
562
564
567 568 569 570 571
Provided that the requirements of 5.5 are met, LDP(s) may be located in ceiling voids or under floors.
For balanced cabling, the effect of multiple connections in close proximity on transmission performance should be taken into consideration when planning the cable lengths between the ZD and the LDP.
5.7.9 Building entrance facilities 561
See ISO/IEC 11801.
5.8 Earthing and equipotential bonding 563
See ISO/IEC 11801 and ISO/IEC 14763-2.
6 Channel performance in data centres 565
6.1 General 566
This clause specifies the minimum channel performance of balanced and optical fibre cabling in terms of the Classes as specified in Clause 6.2. The transmission performance of channels is specified at and between the connections to active equipment as shown in Figure 8. The channel comprises only passive sections of cable, connections, equipment cords, patch cords and jumpers.
EQPCEQP C C
Equipment cord
Patch cord/Jumper
Channel
CC
Patch cord/Jumper
Equipment cord
C
572
573
574 575 576
577
578
579
580
581
582 583 584 585 586
Figure 8 – Example of a channel with 4 connections
Application support depends on channel performance only, which in turn depends on cable length, number of connections, connector termination practices and workmanship, and performance.
Channels are implemented using either:
network access cabling only;
main distribution cabling only;
zone distribution cabling only;
combinations of the above.
Figure 9 shows an example of equipment at the MD connected to equipment at the EO using two channels, an optical fibre cabling channel and a balanced cabling channel. The optical fibre and balanced cabling channels are connected together using an optical fibre to balanced cable converter. There are four channel interfaces; one at each end of the balanced channel, and one at each end of the optical fibre cabling channel.
ISO/IEC JTC 1/SC 25 N 1643 - 20 - 2nd FCD ISO/IEC 24764:2009-04-21
EQPC
EO
ZD
C
EQP
C
C
C
C
OE EQP
C
C
C C
C
MD
Balanced cabling channel
Optical fibre channel
C = optional connection 587
588
589
592 593
594 595 596 597
598 599 600
601 602
603
605 606
608 609 610 611
612 613 614 615
Figure 9 - Example of a system showing the location of cabling interfaces
6.2 Transmission performance 590
6.2.1 General 591
The channel transmission performance specifications are separated into Classes that allow for the transmission of the applications in Annex F of ISO/IEC 11801:2008.
The channel performance requirements described in this clause shall be used for the design and may be used for verification of any implementation of this international standard, using the test methods defined, or referred to, by this clause. In addition, these requirements can be used for application development and trouble shooting.
The channel specifications in this clause allow for the transmission of defined Classes of applications over distances other than those of Clause 7, and/or using media and components with different transmission performance than those of Clauses 8, 9 and 10.
Consideration should be given to measuring performance at worst case temperatures, or calculating worst case performance based on measurements made at other temperatures.
Link performance requirements are specified in Annex A.
6.2.2 Balanced cabling 604
The main distribution and zone distribution cabling shall be designed to provide a minimum of Class EA channel performance as specified in ISO/IEC 11801.
6.2.3 Optical fibre cabling 607
Optical fibre cabling shall be designed using cabled optical fibre Categories specified in Clause 8. Where multimode optical fibre is used, the main distribution and zone distribution cabling shall provide channel performance as specified in ISO/IEC 11801 using a minimum of Category OM3 cabled optical fibre and optical connecting hardware as specified in 9.3.
Editors Note: Resolution of US02 resulted in the above text, which is wrong in its first sentence “Optical fibre cabling shall be designed as specified in Clause 8.” Clause 8 specifies optical fibre cables and not any design rules. The text should have been stating that the design shall use the fibre cables specified in Clause 8. The use of fibre optical connecting hardware has been resolved in IE06 and therefore the text amended.
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 21 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
618 619 620 621
624 625 626 627
628 629 630
633 634
635
636
637
638
639 640 641
643 644
7 Reference implementations in data centres 616
7.1 General 617
This clause describes implementations of generic cabling that utilise components referenced in Clauses 8, 9 and 10. These reference implementations meet the requirements of Clause 5 and, when installed in accordance with ISO/IEC 14763-2, comply with the channel performance requirements of Clause 6.
7.2 Balanced cabling 622
7.2.1 Assumptions 623
Balanced cabling components referenced in Clauses 8, 9 and 10 are defined in terms of Category. In the reference implementations of this clause, the components used in each cabling channel shall have the same nominal characteristic impedance in accordance with 7.2 of ISO/IEC 11801:2008.
The implementations are based on component performance at 20 °C. The effect of temperature on the performance of cables shall be taken into account as shown in Table 2, Table 4 and Table 5.
7.2.2 Zone distribution cabling 631
7.2.2.1 Component choice 632
The selection of balanced cabling components will be determined by the Class of applications to be supported by the cabling. Refer to Annex F of ISO/IEC 11801:2008, for guidance.
Using the models of 7.2.2.2:
Category 6A components provide Class EA balanced cabling performance;
Category 7 components provide Class F balanced cabling performance;
Category 7A components provide Class FA balanced cabling performance.
Cables and connections of different Categories should not be mixed within a channel. If different Categories are mixed, the resultant cabling performance will be determined by the Category of the lowest performing component.
7.2.2.2 Dimensions 642
Figure 10 shows the models used to correlate zone distribution cabling dimensions specified in this clause with the channel specifications in Clause 6.
ISO/IEC JTC 1/SC 25 N 1643 - 22 - 2nd FCD ISO/IEC 24764:2009-04-21
Equipment cord
Patch cord/Jumper
Fixed zone distribution
cable
EQPC CEQP C
Equipment cord
EOZD
Channel = 100 m max.
b) Cross-connect - EO model
C C
Equipment cord
Fixed zone distribution
cable
EQPCEQP C
Equipment cord
EO
ZD
Channel = 100 m max.
C C
a) Interconnect - EO model
Equipment cord
Patch cord/Jumper
Fixed zone distribution
cable
EQPC CEQP C
Equipment cord
EOZD
Channel = 100 m max.
b) Cross-connect - EO model
C C
Equipment cord
Fixed zone distribution
cable
EQPCEQP C
Equipment cord
EO
ZD
Channel = 100 m max.
C C
a) Interconnect - EO model
645
Equipment cord
Patch cord/Jumper
EQPCEQP
Equipment cord
ZD
Channel = 100 m max.
d) Cross-connect - LDP - EO model
C C
Equipment cord
EQPCEQP C
Equipment cord
EO
ZD
Channel = 100 m max.
C C
c) Interconnect - LDP - EO model
Fixed zone distribution
cable
C
LDP cable
LDP
CCEO
Fixed zone distribution
cable
C
LDP cable
LDP
Equipment cord
Patch cord/Jumper
EQPCEQP
Equipment cord
ZD
Channel = 100 m max.
d) Cross-connect - LDP - EO model
C C
Equipment cord
EQPCEQP C
Equipment cord
EO
ZD
Channel = 100 m max.
C C
c) Interconnect - LDP - EO model
Fixed zone distribution
cable
C
LDP cable
LDP
CCEO
Fixed zone distribution
cable
C
LDP cable
LDP
646
647 Figure 10 - Zone distribution cabling models
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 23 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
648 649 650 651
652 653 654 655 656
657 658 659 660
661 662 663
664
666
668
669
670 671 672
673 674 675 676 677
678 679
Figure 10a shows a channel containing only an interconnect and an EO. Figure 10b contains an additional connection as a cross-connect. In both cases the fixed horizontal cable connects the ZD to the EO. The channel includes patch cords and equipment cords. For the purposes of this sub clause, jumpers used in place of patch cords are treated as cords.
Figure 10c shows a channel containing an interconnect, an LDP and an EO. Figure 10d contains an additional connection as a cross-connect. In both cases the fixed zone distribution cable connects the ZD to the LDP. The channel includes patch cords and equipment cords. For the purposes of this sub clause, jumpers used in place of patch cords are treated as cords.
In addition to the cords, the channels shown in Figure 10c and Figure 10d contain an LDP cable. The insertion loss specification for the LDP cable may differ from that of both the fixed zone distribution cable and the flexible cables. The channel of Figure 10d is recognized as the maximum implementation used to define the channel performance limits of Clause 6.
In order to accommodate cables used for LDP cables, patch cords, jumpers and equipment cords with different insertion loss specifications, the maximum cable length used within a channel shall be determined by the equations shown in Table 2.
In Table 2 it is assumed that
a) the flexible cable within these cords has a higher insertion loss specification than that 665 used in the fixed zone distribution cable (see Clause 10),
b) the cables within these cords in the channel have a common insertion loss specification. 667
The following general restrictions apply:
a) the physical length of the channel shall not exceed 100 m;
b) the physical length of the fixed zone distribution cable shall not exceed 90 m and may be less depending on the length of LDP cables and cords used and the number of connections;
Table 1 contains the length assumptions of the mathematical model used to validate channel performance using components specified in clauses 8, 9 & 10 when configured within the range of implementations provided by Figure 10 and Table 1. They do not represent absolute restrictions on the implementation of channels and permanent links, but may be used for guidance in reference implementations.
Table 1 – Length assumptions used in the mathematical modelling of balanced zone distribution cabling
Segment Minimumm
Maximum m
ZD-LDP 15 85
LDP-EO 5 -
ZD-EO (no LDP) 15 90
Equipment cord at the EO 2a 5
Patch cord 2 -
Equipment cord at the ZD 2b 5
All cords - 10
a If there is no LDP, the minimum length of the equipment cord is 1 m.
b If there is no cross-connect, the minimum length of the equipment cord is 1 m.
ISO/IEC JTC 1/SC 25 N 1643 - 24 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
680 681 682
683
During the operation of the installed cabling, an administration system, see ISO/IEC 14763-2, should be implemented to ensure that the length of cords and, where appropriate, the length of LDP cables used to create the channel conform to the design rules of this Standard.
Table 2 - Zone distribution channel length equations
Model Figure Implementation equations
Class E A Class F and Class F A
Interconnect-EO 10a Z =104a - FX Z =105a - FX
Cross-connect-EO 10b Z =103a - FX Z =103a - FX
Interconnect-LDP-EO 10c Z =103a - FX - LY Z =103a - FX - LY
Cross-connect-LDP-EO 10d Z =102a - FX - LY Z =102a - FX - LY
Z maximum length of the fixed zone distribution cable (m)
F combined length of patch cords, jumpers and equipment cords (m)
L length of the LDP cable (m)
X ratio of flexible cable insertion loss (dB/m) to fixed zone distribution cable insertion loss (dB/m) - see Clause 10
Y ratio of LDP cable insertion loss (dB/m) to fixed zone distribution cable insertion loss (dB/m) - see Clause 10
a This includes a length reduction allocation to accommodate ILD.
Note: To be confirmed when Amendment 2 of ISO/IEC 11801 2nd Edition has been approved as FDAM.
For operating temperatures above 20 °C, Z should be reduced by 0,2% per °C for screened cables and 0,4% per °C (20 oC to 40 oC) and 0,6% per °C (40 oC to 60 oC) for unscreened cables.
684
687 688
689
690
691
692
693 694 695
697 698 699 700
701 702 703
704 705 706
7.2.3 Main distribution cabling 685
7.2.3.1 Component choice 686
The selection of balanced cabling components will be determined by the Class of applications to be supported by the cabling. Refer to Annex F of ISO/IEC 11801:2008 for guidance.
Using the models of 7.2.3.2:
Category 6A components provide Class E A balanced cabling performance;
Category 7 components provide Class F balanced cabling performance;
Category 7 A components provide Class F A balanced cabling performance.
Cables and connections of different Categories should not be mixed within a channel. If different Categories are mixed, the resultant cabling performance will be determined by the Category of the lowest performing component.
7.2.3.2 Dimensions 696
The connection of application-specific equipment to the main distribution cabling at the MD and ZDs adopts either an interconnect or cross-connect approach (see ISO/IEC 11801). The channel includes patch cords and equipment cords. For the purposes of this sub clause, jumpers used in place of patch cords are treated as cords.
Figure 11 shows the model used to correlate main distribution cabling dimensions specified in this clause with the channel specifications in Clause 5. This figure represents the full configuration for the main distribution channel.
Table 3 contains the length assumptions of the mathematical model used to validate Channel performance using components specified in Clauses 8, 9 & 10 when configured within the range of implementations provided by Figure 10 and Table 3. They do not represent absolute
ISO/IEC JTC 1/SC 25 N 1643 - 25 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
707 708
709 710
restrictions on the implementation of channels and permanent links, but may be used for guidance in reference implementations.
Table 3 – Length assumptions used in the mathematical modelling of balanced main distribution cabling
Segment Minimum m
Maximumm
MD-ZD 15 90
Equipment cord at the MD 2a 5
Equipment cord at the ZD 2b 5
Patch cord 2 -
All cords - 10 a If there is no cross-connect at the MD, the minimum length of the equipment cord at the MD is 1m. b If there is no cross-connect at the ZD, the minimum length of the equipment cord at the ZD is 1m.
711 712 713 714
The maximum length of the fixed main distribution cable will depend on the total length of cords to be supported within a channel. During the operation of the installed cabling, an administration system, see ISO/IEC 14763-2, should be implemented to ensure that the length of cords used to create the channel conform to the design rules of this Standard.
Equipment cord
Patch cord/Jumper
Fixed main distribution
cable
EQPC CEQP C C CC
Equipment cord
MD
Patch cord/Jumper
Channel
ZD
Equipment cord
Patch cord/Jumper
Fixed main distribution
cable
EQPC CEQP C C CC
Equipment cord
MD
Patch cord/Jumper
Channel
ZD
715
716
717 718 719
720
722
724
725
726 727
Figure 11 - Main distribution cabling models
In order to accommodate the higher insertion loss of flexible cables used for cords, the length of the cables used within a channel of a given Class (see Clause 6) shall be determined by the equations shown in Table 4.
In Table 4 it is assumed that
c) the flexible cable within these cords has a higher insertion loss specification than that 721 used in the fixed main distribution cable (see Clause 10),
d) the cables within these cords in the channel have a common insertion loss specification. 723
The following general restrictions apply:
a) the physical length of the channel shall not exceed 100 m;
b) the physical length of the fixed main distribution cable shall not exceed 90 m and may be less depending on the length of cords used and the number of connections;
ISO/IEC JTC 1/SC 25 N 1643 - 26 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
728 Table 4 - Main distribution channel length equations
Model Implementation equations
Class E A Class F and Class F A
Interconnect-interconnect M =104a - FX M =105a - FX
Interconnect-cross-connect M =103a - FX M =103a - FX
Cross-connect—cross-connect M =102a - FX M =102a - FX
M maximum length of the fixed main distribution cable (m)
F combined length of patch cords, jumpers and equipment cords (m)
X ratio of flexible cable insertion loss (dB/m) to fixed main distribution cable insertion loss (dB/m) – see Clause 10
a This includes a length reduction allocation to accommodate ILD.
For operating temperatures above 20 oC, M should be reduced by 0,2 % per °C for screened cables and 0,4% per °C (20 oC to 40 oC) and 0,6 % per °C (40 oC to 60 oC) for unscreened cables.
7.2.4 Network access cabling 729
7.2.4.1 Component choice 730
The selection of balanced cabling components will be determined by the channel lengths required and the Class of applications to be supported. Refer to Annex F to ISO/IEC 11801:2008 for guidance.
731 732 733
735 736 737 738 739
740 741
742
744
746
747 748 749
750 751
752 753 754 755 756
7.2.4.2 Dimensions 734
Figure 12 shows the model used to correlate cabling dimensions specified in this clause with the channel specifications in Clause 5. The network access channel shown contains a cross-connect at both ends and represents the worst-case configuration for a network access cabling channel between an MD and distributor in accordance with ISO/IEC 11801. A channel between an ENI and an MD contains an interconnect at the ENI.
The channel includes patch cords and equipment cords. For the purposes of this clause, jumpers used in place of patch cords are treated as cords.
In Table 5 it is assumed that
a) the flexible cable within these cords has a higher insertion loss specification than that 743 used in the fixed network access cable,
b) the cables within all these cords in the channel have a common insertion loss 745 specification.
In order to accommodate the higher insertion loss of flexible cables used for cords, the length of the cables used within a channel of a given Class (see clause 6) shall be determined by the equations shown in Table 5.
When four connections are used in a channel, the physical length of the network access cable should be at least 15 m.
The maximum length of the fixed network access cable will depend on the total length of cords to be supported within a channel. The maximum lengths of cords shall be fixed for ENIs and distributors. During the operation of the installed cabling, an administration system, see ISO/IEC 14763-2, should be implemented to ensure that the length of cords used to create the channel conform to these design rules of this Standard.
ISO/IEC JTC 1/SC 25 N 1643 - 27 - 2nd FCD ISO/IEC 24764:2009-04-21
Equipment cord
Patch cord/Jumper
EQPCEQP
Equipment cord
MD
Channel
b) Network access cabling from MD to distributor in accordance with ISO/IEC 11801
C C
a) Network access cabling from MD to ENI
CC
Fixed network access
cable
C
Patch cord/Jumper
Distributor in accordancewith ISO/IEC 11801
Equipment cord
Patch cord/Jumper
EQPCEQP
Equipment cord
MD
Channel
C CCC
Fixed network access
cable
C
Patch cord/Jumper
ENI
Equipment cord
Patch cord/Jumper
EQPCEQP
Equipment cord
MD
Channel
b) Network access cabling from MD to distributor in accordance with ISO/IEC 11801
C C
a) Network access cabling from MD to ENI
CC
Fixed network access
cable
C
Patch cord/Jumper
Distributor in accordancewith ISO/IEC 11801
Equipment cord
Patch cord/Jumper
EQPCEQP
Equipment cord
MD
Channel
C CCC
Fixed network access
cable
C
Patch cord/Jumper
ENI
757
761
NOTE Where the EQP connected to the ENI lies outside the premises containing the data centres, the 758 interconnecting cord will typically comprise a combination of fixed cabling and cords that are outside the scope of 759 this standard. In such cases the connection to the EQP may not provide a TI. 760
Figure 12 - Network access cabling models
ISO/IEC JTC 1/SC 25N1643.doc
ISO/IEC JTC 1/SC 25 N 1643 - 28 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
762 Table 5 - Network access cabling channel equations
Component Implementation equations a
Category Class A Class B Class C Class D Class E Class E A Class F Class F A
5 2 000 N = 250 - FX
N = 170 - FX
N = 105 - FX
6 2 000 N = 260 - FX
N = 185 - FX
N = 111 - FX
N = 102b- FX
6 A 2 000 N = 260 - FX
N = 185 - FX
N = 111 - FX
N = 102b- FX
N = 102b- FX
7 2 000 N = 260 - FX
N = 190 - FX
N = 115 - FX
N = 104b - FX
N = 104b - FX
N = 102b- FX
7 A 2 000 N = 260 - FX
N = 190 - FX
N = 115 - FX
N = 104b - FX
N = 104b - FX
N = 102b- FX
N = 102b- FX
N length of the fixed backbone cable (m)
F combined length of patch cords, jumpers and equipment cords (m)
X ratio of flexible cable insertion loss (dB/m) to fixed network access cable insertion loss (dB/m) – see Clause 10
a Applications limited by propagation delay or skew may not be supported if channel lengths exceed 100 m.
b This includes a length reduction allocation to accommodate ILD.
NOTE 1 Where channels contain a different number of connections than in the model shown in Figure 12, the fixed cable length shall be reduced (where more connections exist) or may be increased (where fewer connections exist) by 2 m per connection for Category 5 connections and 1 m per connection for Category 6 and above connections. Additionally, the NEXT, Return Loss (RL) and ACR-F performance should be verified. Category 5 and Category 6 components and Class A through Class E channels only may be used for network access cabling.
NOTE 2 For operating temperatures above 20 °C, N should be reduced by 0,2 % per °C for screened cables and 0,4 % per °C (20 °C to 40 °C) and 0,6 % per °C (40 °C to 60 °C) for unscreened cables.
7.3 Optical fibre cabling 763
7.3.1 Assumptions 764
Optical fibre components are referenced in Clauses 8, 9 and 10. The optical fibres are defined in terms of physical construction (core/cladding diameter) and their transmission performance Category within a cable. Within the reference implementations of this clause, the cabled optical fibres used in each cabling channel shall be of the same specification.
765 766 767 768
770 771
773 774 775 776 777 778 779
7.3.2 Component choice 769
The selection of optical fibre components will be determined by the channel lengths required and the applications to be supported. Refer to Annex F of ISO/IEC 11801:2008 for guidance.
7.3.3 Optical fibre cabling channel lengths 772
The models of Figure 10, Figure 11 and Figure 12 are applicable to optical fibre cabling for zone distribution cabling, main distribution cabling and network access cabling respectively. The channel length restriction of Figure 10 does not apply, but is instead limited by channel length restrictions of the cabled optical fibre Category used. It should be noted that the connection systems used to terminate fixed optical fibre cabling may contain mated connections and splices (permanent or re-useable) and that cross-connects may comprise re-useable splices.
ISO/IEC JTC 1/SC 25 N 1643 - 29 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
782
784
786
789 790 791
793
796 797 798
800
802
808
810
812
814
8 Cable requirements in data centres 780
8.1 General 781
This clause defines the minimum requirements for
a) cables installed in the main distribution, zone distribution and network access cabling 783 subsystems specified in Clause 5 and used in the reference implementations of Clause 7,
b) flexible balanced cables to be assembled as cords as specified in Clause 10 and used in 785 the reference implementations of Clause 7,
c) balanced cables or cable elements to be used as jumpers. 787
8.2 Balanced cables 788
The electrical performance of balanced cables, other than for network access cabling, shall meet a minimum of Category 6A, requirements according to Clause 9.2 of ISO/IEC 11801:2008.
8.3 Optical fibre cables 792
See 9.4 of ISO/IEC 11801:2008.
9 Connecting hardware requirements in data centres 794
9.1 General requirements 795
Hardware for connecting cables shall only provide direct onward attachment for each conductor and shall not provide any contact between more than one incoming and one outgoing conductor (e.g. bridge taps shall not be used).
9.1.1 Applicability 799
See 10.1.1 of ISO/IEC 11801:2008.
9.1.2 Location 801
Connecting hardware is installed at the:
a) ENI, 803
b) MD and ZD, 804
c) LDP (if provided), 805
d) EO. 806
9.1.3 Design 807
See 10.1.3 of ISO/IEC 11801:2008.
9.1.4 Operating Environment 809
See 10.1.4 of ISO/IEC 11801:2008.
9.1.5 Mounting 811
See 10.1.5 of ISO/IEC 11801:2008.
9.1.6 Installation practices 813
See 10.1.6 of ISO/IEC 11801:2008.
ISO/IEC JTC 1/SC 25 N 1643 - 30 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
816
819
821
824 825
826
9.1.7 Marking and colour Coding 815
See 10.1.7 of ISO/IEC 11801:2008.
9.2 Connecting hardware for balanced cabling 817
9.2.1 General requirements 818
See 10.2.1 of ISO/IEC 11801:2008.
9.2.2 Performance marking 820
See 10.2.2 of ISO/IEC 11801:2008.
9.2.3 Mechanical characteristics 822
9.2.3.1 Connecting hardware of the type used at the ENI 823
Balanced cabling connecting hardware shall be in accordance with Clause 10.2.3 of ISO/IEC 11801:2008 as amended by the requirements of Table 6.
Table 6 - Connecting hardware of the type used at the ENI
Category Standard
Category 5 unscreened IEC 60603-7-2
Category 5 screened IEC 60603-7-3
Category 6 unscreened IEC 60603-7-4
Category 6 A unscreened IEC 60603-7-41 b
Category 6 screened IEC 60603-7-5
Category 6 A screened IEC 60603-7-51 b
Category 7 screened IEC 60603-7-7a
Category 7 A screened IEC 60603-7-71a a In installations where other factors such as cable sharing take preference over backward compatibility offered by the IEC 60603-7-7 and IEC 60603-7-71 interface, the interface specified in IEC 61076-3-104 may be used.
827
829 830
831
9.2.3.2 Connecting hardware of the type used at the EO 828
Balanced cabling connecting hardware shall be in accordance with Clause 10.2.3 of ISO/IEC 11801:2008 as amended by the requirements of Table 7.
Table 7 - Connecting hardware of the type used at the EO
Category Standard
Category 6 A unscreened IEC 60603-7-41
Category 6 A screened IEC 60603-7-51
Category 7 screened IEC 60603-7-7a
Category 7 A screened IEC 60603-7-71a a In installations where other factors such as cable sharing take preference over backward compatibility offered by the IEC 60603-7-7 and IEC 60603-7-71 interface, the interface specified in IEC 61076-3-104 may be used.
ISO/IEC JTC 1/SC 25 N 1643 - 31 - 2nd FCD ISO/IEC 24764:2009-04-21
9.2.3.3 Pin and pair assignments at the EO 832
ISO/IEC JTC 1/SC 25N1643.doc
833 834
835 836
837 838 839
For the connecting hardware in 9.2.3.2 the pin grouping and pair assignments shall be as shown in Figure 13.
Pair rearrangement should not involve modification of the cable terminations. If pair rearrangement is used, the configuration of the terminations shall be clearly identified.
NOTE When two physically similar cabling links are used in the same installation (for example, different performance Categories and cables with different nominal impedance) special precautions are required to ensure that they are identified.
a) IEC 60603-7 series interface for Category 5, 6 and 6A (not to scale)
1 2 3 4 5 6 7 8
b) IEC 60603-7 series interface for Category 7 and 7A (not to scale)
1 2 3 4 5 6 7 8
6I 3I 4I 5I
NOTE: the pin designations 1, 2, 3I, 4I, 5I, 6I, 7 and 8 for Category 7 and 7A correspond to 1, 2, 3, 4, 5, 6, 7 and 8 for Category 5, 6 and 6A
1 2 3 4 5 6 7 8
6I 3I 4I 5I
1 2 3 4 5 6 7 8
6I 3I 4I 5I
NOTE: the pin designations 1, 2, 3I, 4I, 5I, 6I, 7 and 8 for Category 7 and 7A correspond to 1, 2, 3, 4, 5, 6, 7 and 8 for Category 5, 6 and 6A
c) IEC 61076-3-104 interface for Category 7 and 7A (not to scale)
1 2 7 8
6 3 4 5
NOTE: the pin designations correspond to those of IEC 60603-7
series interfaces
LATCH
1 2 7 8
6 3 4 5
1 2 7 8
6 3 4 5
NOTE: the pin designations correspond to those of IEC 60603-7
series interfaces
LATCH
Figure 13 - Pin grouping and pair assignments at the EO, front view of fixed connector (jack)
840 841
ISO/IEC JTC 1/SC 25 N 1643 - 32 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
842 843 844 845
848
849 850 851 852 853
855 856
857 858 859 860
863
865 866 867
868 869
870 871
873 874
875 876
877 878
If the connecting hardware type at a distributor, LDP or EO in the same link or channel is different to each other, the cabling connections shall be configured with consistent pin/pair assignments to ensure end-to-end connectivity. Pair rearrangement at the equipment outlet should not involve modification of the horizontal cable terminations.
9.2.3.4 Electrical Characteristics 846
9.2.3.4.1 ENI and EO requirements 847
See 10.2.4.1 and 10.2.4.2 of ISO/IEC 11801:2008.
Free and fixed connectors (plugs and jacks) that are intermateable shall be backward compatible with those of different performance categories. Backward compatibility means that mated connections with free and fixed connectors (plugs and jacks) from different categories shall meet all of the requirements for the lower category component. See Clause 10 of ISO/IEC 11801:2008.
9.2.3.4.2 Other connecting hardware 854
Connecting hardware for use in distributors and LDPs of a given category shall meet the corresponding performance requirements specified in 10.2.4.3 of ISO/IEC 11801:2008.
The creation of Class FA Configuration PL3 permanent link (See Figure A. 1), where the LDP cable is in accordance with IEC 61156-5, requires the connecting hardware at the LDP to provide NEXT and PSNEXT performance 6 dB better than the Category 7A components specified in Clause 9.2.
9.3 Connecting hardware for optical fibre cabling 861
9.3.1 General requirements 862
See 10.3.1, 10.3.2, 10.3.3 and 10.3.5 of ISO/IEC 11801:2008.
9.3.2 ENI requirements 864
For single-mode optical fibre the interface shall be IEC 61754-20 (the LC interface); it shall have a minimum return loss performance of 55 dB provided by an angled face connection, in accordance with IEC 61755-3-2.
It is recommended that the interface at the other end of the network access cabling permanent link should maintain this return loss performance.
For the termination of one or two multimode optical fibres the interface shall be IEC 61754-20 (the LC interface); it shall have a minimum return loss performance of 20 dB.
9.3.3 EO requirements 872
For the termination of one or two single-mode optical fibres the interface shall be IEC 61754-20 (the LC interface)
For the termination of one or two multimode optical fibres the interface shall be IEC 61754-20 (the LC interface)
For the termination of more than two optical fibres the interface shall be IEC 61754-7 (the MPO interface). See ISO/IEC 14763-2 regarding optical fibre polarity management.
ISO/IEC JTC 1/SC 25 N 1643 - 33 - 2nd FCD ISO/IEC 24764:2009-04-21
9.3.4 Optical fibre pin assignments at the EO 879
ISO/IEC JTC 1/SC 25N1643.doc
880 881
882 883
For the optical fibre connecting hardware in 9.3.3 the optical fibre pin assignments shall be as shown in Figure 14.
Polarity of fibres should be identified at the EO, by means of any combination of latching, keying or labelling.
a) IEC 61754-20 interface for one or two optical fibres (not to scale)
B AB A
b) IEC 61754-7 interface for more than two optical fibres (not to scale)
12 11 10 9 8 7 6 5 34 2 112 11 10 9 8 7 6 5 34 2 1
Figure 14 - Optical fibre pin assignments at the EO, front view of fixed connector 884
887
889
890
892
893
10 Requirements for cords and jumpers in data centres 885
10.1 Jumpers 886
See Clause 8.
10.2 Balanced cords 888
See Clause 13 of ISO/IEC 11801:2008.
Field-terminated cords should not be used.
10.3 Optical fibre cords 891
Optical fibre cables used for cords shall meet IEC 60794-2-11.
Field-terminated cords should not be used.
ISO/IEC JTC 1/SC 25 N 1643 - 34 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
894 895 896 897
899 900
901 902 903 904 905
906 907 908
Annex A (normative)
Link performance limits
A.1 General 898
This annex contains performance requirements for permanent links and LDP links as shown in Figure A. 1 and relates to Annex A of ISO/IEC 11801:2008.
The cabling under test in configurations PL1, PL2 and PL3 is termed the permanent link. The configurations PL1 and PL2 comprise fixed cabling only. Configuration PL3 comprises fixed cabling and a LDP cable between the LDP and the EO. If the LDP cable is changed, performance of this configuration will change. The cabling under test in configuration LDP1 contains fixed cabling only and is termed the LDP link.
In all configurations the test reference plane of a permanent link or LDP link is within the test cord. The test cord connection which mates with the termination point of the permanent link or LDP under test is part of the link under test.
ISO/IEC JTC 1/SC 25 N 1643 - 35 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
909
a) Configuration PL1
C
PP
TesterCTester C C
PP/ENI
Permanent link
Network access/
Main distribution cabling
C
PP
TesterCTester C C
PP/ENI
Permanent link
Network access/
Main distribution cabling
b) Configuration PL2
C
PP
TesterCTester C C
EO
Permanent link
Zone distribution cabling
C
PP
TesterCTester C C
EO
Permanent link
Zone distribution cabling
c) Configuration PL3
Tester
EOLDP
C C
PP
Tester C C C
Permanent link
Zone distribution cabling
Tester
EOLDP
C C
PP
Tester C C C
Permanent link
Zone distribution cabling
d) Configuration LDP1
LDP
C C
PP
Tester C TesterC
LDP link
Zone distribution cabling
LDP
C C
PP
Tester C TesterC
LDP link
Zone distribution cabling
C = connection; PP = Patch panel; ENI = External network interface; EO = Equipment outlet; LDP = Local distribution point
Figure A. 1 - Link options 910
912 913
914 915
916 917 918 919
A.2 Balanced cabling 911
Consideration should be given to measuring performance at worst case temperatures, or calculating worst case performance based on measurements made at other temperatures.
Link performance shall meet the requirements of ISO/IEC 11801 Annex A.2, for Class EA, F and FA.
The creation of Class FA Configuration PL3 permanent link (See Figure A.1), where the LDP cable is in accordance with IEC 61156-5, requires the connecting hardware at the LDP to provide NEXT and PSNEXT performance 6 dB better than the Category 7A components specified in Clause 9.2.
ISO/IEC JTC 1/SC 25 N 1643 - 36 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
920 921
923 924 925 926
927 928
929
930 931 932
In the case of cable sharing, additional requirements shall be taken into account for balanced cabling. The additional crosstalk requirements are specified in Clause 9.3 of ISO/IEC 11801:2008.
A.3 Optical fibre cabling 922
The attenuation of a link at a specified wavelength shall not exceed the sum of the specified attenuation values for the cabling components at that wavelength (where the attenuation of a length of optical fibre cable is calculated from its attenuation coefficient multiplied by its length).
Measurements made shall be consistent with the design values of cable length and cabling materials used.
The attenuation of a link shall be measured according to ISO/IEC 14763-3.
NOTE The test methods have been developed for conventional optical fibre connection systems comprising two plugs and an adaptor. In some cases the methods are not appropriate for Small Form Factor connectors that comprise a plug and socket.
ISO/IEC JTC 1/SC 25 N 1643 - 37 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
933 934 935 936
938 939
940
941 942
943
944
945
946
947
948
949
950
951 952
954 955
Annex B (informative)
Usage of high density connecting hardware within optical fibre cabling
B.1 General 937
For the purposes of this Annex, the term “high density connecting hardware” refers to optical fibre connecting hardware that provides interconnection:
of multi-element cabling (more than two optical fibres)
at a greater density than is possible using groups of the duplex optical fibre interface as specified at the EO (see Clause 9)
through a transition assembly, or a fan-out cord
High density connecting hardware may be required in the following locations:
interfaces to switchblades for high density switches;
interfaces to equipment using parallel optics sources and detectors;
one or both ends of equipment cords at distributors;
one or both ends of patch cords at distributors;
LDPs;
interfaces that replace duplex EO connectors.
High density connecting hardware may be used as replacement or in combination with the duplex interface specified Clause 9.
B.2 Structure of cabling subsystems 953
Examples of high density connecting hardware within cabling subsystems in accordance with Clause 5 are shown in Figure B. 1 (main distribution cabling) and
ISO/IEC JTC 1/SC 25 N 1643 - 38 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
956 Figure B. 2 (zone distribution cabling).
EQP
MD
H H
ZD
H EQPH
Channel
H = high density connecting hardware
HC
C
C
C
C
EQP
MD
EQP
ZD
CH
C
C
C
C
CC
EQP
MD
H H H
ZD
EQPH H H
Transition assembly
High density equipment
cord
High density equipment
cord
Equipment cord
High density equipment
cord
Transition assembly
High density equipment
cord
Equipment cord
C = connecting hardware
EQP
MD
H H
ZD
H EQPH
Channel
H = high density connecting hardwareH = high density connecting hardware
HC
C
C
C
C
HHC
C
C
C
C
EQP
MD
EQP
ZD
CH
C
C
C
C
CC
EQP
MD
H H H
ZD
EQPH H H
Transition assembly
High density equipment
cord
High density equipment
cord
Equipment cord
High density equipment
cord
Transition assembly
High density equipment
cord
Equipment cord
C = connecting hardware 957
958 959
Figure B. 1 - Examples of high density connecting hardware within main distribution cabling
ISO/IEC JTC 1/SC 25 N 1643 - 39 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
960
EQPCH
C
C
C
C
C
EO
CH
C
C
C
C
LDP
EO
EQPC
Transition assembly
Equipment cord
Equipment cord
LDP cord
EQPCH
C
C
C
C
C
EO
CH
C
C
C
C
LDP
EO
EQPC
Transition assembly
Equipment cord
Equipment cord
LDP cord
H EQPH
EO
H EQPH
EO
H
LDP
High density equipment
cord
High density equipment
cord
LDP cord
H EQP
EO
Transition assembly
C
C
C
C
C
H = high density connecting hardware C = connecting hardware
H EQPH
EO
H EQPH
EO
H
LDP
High density equipment
cord
High density equipment
cord
LDP cord
H EQP
EO
Transition assembly
C
C
C
C
C
H = high density connecting hardwareH = high density connecting hardware C = connecting hardware
961
962 963
Figure B. 2 - Examples of high density connecting hardware at the LDP and EO within zone distribution cabling
ISO/IEC JTC 1/SC 25 N 1643 - 40 - 2nd FCD ISO/IEC 24764:2009-04-21
ISO/IEC JTC 1/SC 25N1643.doc
964
965 966
967 968
969
Bibliography
ISO/IEC 18010, Information technology – Pathways and spaces for customer premises cabling
IEC 60794-2-10, Optical fibre cables - Part 2-10: Indoor cables - Family specification for simplex and duplex cables