CALEFFI ACCREDITED ISO 9001 No. 0003 ISO 9001 FM 21654 ThermoProtec boiler protection high-flow thermostatic mixing valve 280 series 01223/17 NA Function The ThermoProtec boiler protection high-flow thermostatic mixing valve is used in hydronic heating systems with non-condensing boilers, including solid fuel, biomass, gas, LP or oil-fired. It can be installed with steel, cast iron and copper tube style boilers, automatically controlling the return water temperature, preventing condensation of the water vapor contained in the flue gas. The 280 series ThermoProtec valve mixes by-pass flow from the boiler with return flow from the system, sending a fixed temperature flow to the boiler which protects against corrosion from condensation occurring when a minimum flue gas temperature is not otherwise maintained. Changeable thermostatic sensor cartridge changes valve temperature setting. The thermostatic sensor cartridge can easily be removed for maintenance or to change the valve set temperature, with out removing the valve body from the piping. Product range 280 series ThermoProtec boiler protection valve ......................................................................... connections 1" and 1-1/4" NPT male or sweat union Technical specifications Materials - body: brass - lower body plug: brass - shutter: PSU - spring: stainless steel - seal: EPDM - union seals: fiber - thermostatic sensor: wax Performance Suitable fluids: water, glycol solutions Max. percentage of glycol: 50% Max. working pressure: 150 psi (10 bar) Working temperature range: 40–212°F (5–100°C) Thermostatic sensor cartridge: 130°F (55°C) Tset standard Optional cartridges Tset (field replaceable): 115°F (45°C) 140°F (60°C) 160°F (70°C) Sensor cartridge accuracy: ±4°F (±2°C) By-pass closed temperature: Tset +18°F (+10°C) Fully open flow characteristic: 10 Cv (size 1") 14 Cv (size 1-1/4") Connections: - NPT male union: 1" and 1-1/4" - sweat union: 1" and 1-1/4" Dimensions Code A B C D E F 280165A 1" NPT 3 1 /2" 7" 6" 1 5 /8" 4 3 /8" 280965A 1" SWT 3 1 /2" 7" 6" 1 5 /8" 4 3 /8" 280175A 1 1 /4" NPT 3 13 /16" 7 5 /8" 6 13 /16" 1 9 /16" 4 3 /8" 280975A 1 1 /4" SWT 3 13 /16" 7 5 /8" 6 13 /16" 1 9 /16" 4 3 /8" Replaces 01223/13 NA

Upload: others

Post on 24-Aug-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 280 series - Amazon S3 · CALEFFI ACCREDITED ISO 9001 FM 21654 ISO 9001 No. 0003 ThermoProtec™ boiler protection high-flow thermostatic mixing valve 280 series 01223/17 NA Function

CALEFFIACCREDITED

ISO 9001 No. 0003ISO 9001 FM 21654

ThermoProtec™ boiler protection high-flow thermostatic mixing valve280 series

01223/17 NA

Function

The ThermoProtec™ boiler protection high-flow thermostatic mixing valve is used in hydronic heating systems with non-condensing boilers, including solid fuel, biomass, gas, LP or oil-fired. It can be installed with steel, cast iron and copper tube style boilers, automatically controlling the return water temperature, preventing condensation of the water vapor contained in the flue gas. The 280 series ThermoProtec™ valve mixes by-pass flow from the boiler with return flow from the system, sending a fixed temperature flow to the boiler which protects against corrosion from condensation occurring when a minimum flue gas temperature is not otherwise maintained.

Changeable thermostatic sensor cartridge changes valve temperature setting. The thermostatic sensor cartridge can easily be removed for maintenance or to change the valve set temperature, with out removing the valve body from the piping.

Product range

280 series ThermoProtec™ boiler protection valve .........................................................................connections 1" and 1-1/4" NPT male or sweat union

Technical specifications

Materials - body: brass- lower body plug: brass- shutter: PSU- spring: stainless steel- seal: EPDM- union seals: fiber- thermostatic sensor: wax

PerformanceSuitable fluids: water, glycol solutionsMax. percentage of glycol: 50%Max. working pressure: 150 psi (10 bar)Working temperature range: 40–212°F (5–100°C)Thermostatic sensor cartridge: 130°F (55°C) Tset standardOptional cartridges Tset (field replaceable): 115°F (45°C)

140°F (60°C)160°F (70°C)

Sensor cartridge accuracy: ±4°F (±2°C)By-pass closed temperature: Tset +18°F (+10°C)Fully open flow characteristic: 10 Cv (size 1")

14 Cv (size 1-1/4")

Connections: - NPT male union: 1" and 1-1/4"- sweat union: 1" and 1-1/4"

Dimensions

Code A B C D E F

280165A 1" NPT 31⁄2" 7" 6" 15⁄8" 43⁄8"

280965A 1" SWT 31⁄2" 7" 6" 15⁄8" 43⁄8"

280175A 11⁄4" NPT 313⁄16" 75⁄8" 613⁄16" 19⁄16" 43⁄8"

280975A 11⁄4" SWT 313⁄16" 75⁄8" 613⁄16" 19⁄16" 43⁄8"

Replaces 01223/13 NA

Page 2: 280 series - Amazon S3 · CALEFFI ACCREDITED ISO 9001 FM 21654 ISO 9001 No. 0003 ThermoProtec™ boiler protection high-flow thermostatic mixing valve 280 series 01223/17 NA Function

1

Tmix = Tset + 18°F BY-PASS CLOSINGby-pass closedsystem return open

Tf > Tmix ≥ Tset +18°F, Tmix=Tr

3

Tf ≤ Tset SYSTEM START UPby-pass opensystem return closed

Tf ≤ Tset, Tmix=Tf

f

Tmix > Tset + 18°F SYSTEM LOADEDby-pass closedsystem return open

Tf > Tmix > Tset +18°F, Tmix=Tr

Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open

Tf > Tset, Tr < Tset, Tmix=Tset

2

4

f

f

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

Zone of condensationformingTar depositsCorrosionReduction in heat exchanger efficiencyFlammability

Primary andsecondary airCombustion efficiency

BOILER PROTECTIONVALVE

Accumulation of ashand residues

Flue gas andemissioncontrol

By-passfrom boiler

Ret

urn

fro

m s

yste

m

Mix

edto

bo

iler

Valve body

Spring

Thermostaticsensor

Plug

Shutter

System return

Temp gauge pocket wells (4)

1

Tmix = Tset + 18°F BY-PASS CLOSINGby-pass closedsystem return open

Tf > Tmix ≥ Tset +18°F, Tmix=Tr

3

Tf ≤ Tset SYSTEM START UPby-pass opensystem return closed

Tf ≤ Tset, Tmix=Tf

f

Tmix > Tset + 18°F SYSTEM LOADEDby-pass closedsystem return open

Tf > Tmix > Tset +18°F, Tmix=Tr

Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open

Tf > Tset, Tr < Tset, Tmix=Tset

2

4

f

f

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

1

Tmix = Tset + 18°F BY-PASS CLOSINGby-pass closedsystem return open

Tf > Tmix ≥ Tset +18°F, Tmix=Tr

3

Tf ≤ Tset SYSTEM START UPby-pass opensystem return closed

Tf ≤ Tset, Tmix=Tf

f

Tmix > Tset + 18°F SYSTEM LOADEDby-pass closedsystem return open

Tf > Tmix > Tset +18°F, Tmix=Tr

Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open

Tf > Tset, Tr < Tset, Tmix=Tset

2

4

f

f

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

Wood biomass and condensation build-up

Characteristic components

Wood contains a variable moisture content depending on the type (logs, pellets, woodchips, etc.). Water vapor is released during the solid fuel drying phase inside the combustion chamber. The presence of cold surfaces in the boiler or flue gas chimney can lower the temperature of the flue gas down to the dew point, causing condensation. Water vapor condenses on the boiler surfaces, together with soot and part of the unburnt hydrocarbons contained in the flue gas, producing tar deposits. These substances stick to the walls of the boiler, covering most of the inner surfaces. In addition to being dangerous due to its flammability, tar is damaging to the integrity of the boiler and limits the efficiency of the flue gas-system water exchanger.

By keeping the boiler walls at the highest possible temperature, the boiler protection valve limits the formation of these substances thereby increasing combustion efficiency, controlling emissions into the environment and prolonging boiler life.

Operating principle

The thermostatic sensor, completely immersed in the medium, controls the movement of a shutter that regulates the by-pass flow from the boiler and toward the system. At boiler startup, the boiler protection thermostatic mixing valve recirculates the by-pass flow from the boiler to bring the boiler up to temperature as quickly as possible (fig. 1). When the by-pass flow from the boiler Tf exceeds the setting of the boiler protection mixing valve Tset, the valve’s return from the system port starts opening to produce the water mixing Tmix: in this phase the system loading begins (fig. 2). When the mixed flow to the boiler temperature Tmix is greater than the set point of the boiler protection mixing valve by approximately 18°F (10°C), the by-pass flow from the boiler port closes and water returns to the boiler at the same temperature as the return flow from the system (fig. 3).

Page 3: 280 series - Amazon S3 · CALEFFI ACCREDITED ISO 9001 FM 21654 ISO 9001 No. 0003 ThermoProtec™ boiler protection high-flow thermostatic mixing valve 280 series 01223/17 NA Function

1

Tmix = Tset + 18°F BY-PASS CLOSINGby-pass closedsystem return open

Tf > Tmix ≥ Tset +18°F, Tmix=Tr

3

Tf ≤ Tset SYSTEM START UPby-pass opensystem return closed

Tf ≤ Tset, Tmix=Tf

f

Tmix > Tset + 18°F SYSTEM LOADEDby-pass closedsystem return open

Tf > Tmix > Tset +18°F, Tmix=Tr

Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open

Tf > Tset, Tr < Tset, Tmix=Tset

2

4

f

f

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

1" 1-1/4" ∆p

(2)

(4)

.16

.33

.83

1.6

3.3

5.5

(88)

(44)

(22)

(9)

ft of hd (psi)48 (21)

33 (14.5)

16 (7)

10 (4.3)

7 (3)

3.5 (1.5)

1.6 (0.7)

∆p kPa150

100

50

30

20

10

5

Cv: size 1", 10size 1-1/4", 14

Flow

rate

l/s (g

pm)

Air separator

Dirt separator

Pump

Shut-off valve

Expansion vessel

Check valve

Motorized mixing valve

Pressure reducing valve

Filling unit

Backflow preventer

Safety relief valve

Dirt separator for vertical pipes

Air separator for vertical pipes

Hydraulic separator

Y-strainer

NON-CONDENSING

BOILER

Air separator

Dirt separator

Pump

Shut-off valve

Expansion vessel

Check valve

Motorized mixing valve

Pressure reducing valve

Filling unit

Backflow preventer

Safety relief valve

Dirt separator for vertical pipes

Air separator for vertical pipes

Hydraulic separator

Y-strainer

NON-CONDENSING

BOILER

1

Tmix = Tset + 18°F BY-PASS CLOSINGby-pass closedsystem return open

Tf > Tmix ≥ Tset +18°F, Tmix=Tr

3

Tf ≤ Tset SYSTEM START UPby-pass opensystem return closed

Tf ≤ Tset, Tmix=Tf

f

Tmix > Tset + 18°F SYSTEM LOADEDby-pass closedsystem return open

Tf > Tmix > Tset +18°F, Tmix=Tr

Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open

Tf > Tset, Tr < Tset, Tmix=Tset

2

4

f

f

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

Sizing method/set point selection

Knowing the BTU output and thermal head on the boiler, the boiler flow rate can be calculated. Use the hydraulic characteristics graph to identify the pressure drop of the valve. The valve size can then be selected from the pressure drop value with the available head of the system pump. The thermostatic set point (°F) must be selected to control a mixed return to the boiler temperature that is high enough to prevent condensation, also using the information or instructions supplied by the manufacturers of solid fuel boilers.

Installation

The valve can be installed on both sides of the boiler in any position, vertical or horizontal. Installation is recommended on the return to the boiler in mixing mode. It can also be installed on the flow from the boiler in diverting mode.

Installation in mixing mode (boiler protection)

Construction details

Hydraulic characteristics

Installation in diverting mode (system control)

Application diagrams

Non-condensing boiler, direct supply to the system

Brass bodyThe brass body prevents the formation of ferrous residues in the system, prolonging boiler operating life.

Thermostatic sensor replacement to modify the settingThe thermostatic sensor can be easily replaced for maintenance or set point change without removing.

Code DescriptionF29633 115°FF29634 130°FF29635 140°FF29636 160°F

Temperature gauge pocket wellsThe boiler protection mixing valve body features temperature gauge pocket wells on front and rear sides, allowing installation of a temperature gauge (code F29571) for monitoring the working temperatures: by-pass from boiler, return from system, and mixed to boiler.

Use safety devices according to local regulations

*Air purge recommended for boiler loop

*

Page 4: 280 series - Amazon S3 · CALEFFI ACCREDITED ISO 9001 FM 21654 ISO 9001 No. 0003 ThermoProtec™ boiler protection high-flow thermostatic mixing valve 280 series 01223/17 NA Function

We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice.

Caleffi North America, Inc. 3883 W. Milwaukee Road Milwaukee, WI 53208 Tel: 414-238-2360 · Fax: [email protected] · www.caleffi.com© Copyright 2017 Caleffi North America, Inc.

M M

NON-CONDENSING

BOILER

M M

SOLIDFUEL

BOILER

M M

NON-CONDENSING

BOILER

NON-CONDENSING

BOILER

ThermoProtec™ 280 seriesBoiler protection thermostatic mixing valve. Connections 1" to 1-1/4" NPT male or sweat with union. Brass body. Brass lower body plug. PSU shutter. Stainless steel spring. EPDM seal. Wax thermostatic sensor. Suitable for water and glycol solutions. Maximum percentage of glycol 50%. Maximum working pressure 150 psi (10 bar). Working temperature range 40–212°F (5–100°C). Set point temperature 130°F (55°C) standard; 115°F (45°C); 140°F (60°C); and 160°F (70°C) optional. Sensor cartridge accuracy ±4°F (±2°C). Hot inlet from boiler complete closed temperature Tset +18°F (10°C).

SPECIFICATION SUMMARIES

System with buffer tank storage

Non-condensing boiler, connection to buffer tank storage in parallel

Use safety devices according to local regulations

Use safety devices according to local regulations

*Air purge recommended for boiler loop

*Air purge recommended for boiler loop

*

*