7/28/2019 268_pdfsam_2.3- Mechanical, HVAC & Plumbing Specification Novotel http://slidepdf.com/reader/full/268pdfsam23-mechanical-hvac-plumbing-specification-novotel 1/1 Gulf House Engineering January 2010 07-C106 NOVOTEL AL DANA RESORT TOWERS PAGE 266 SECTION 15850 AIR HANDLING UNITS AHU- Selector (H-O-A) switches position. AHU Healthystatus. If both are positive, BMS DDC controller will give an open command to AHU fresh air intake damper to open its minimum position for preset level. After a time delay it will give a start command to AHU supply air fan VFD. G. Humidity (Option) Fresh air and Return Air humidity and temperature is monitored by BMS DDC Controller through humidity sensors and the same will be used to calculate inside and outside Enthalpy. The difference in inside and outside Enthalpy will initiate free cooling operation of AHU. H. Temperature Control In the common areas AHU supply return and fresh air temperatures will be continuously measured by the duct mounted temperature sensor; which is installed in AHU supply air, return air and fresh air duct respectively. The temperature difference between the supply and the supply air temperature set point value will generate the cooling demand. The control loop within the controller will perform the mathematical calculations and compare the measured value and current set point value. If the measured value is more then the set point value, cooling loop will be initiated. The voltage level from sensor is converted into a number, which the sensor will scale into degree centigrade. The loop will then generate a proportional control output designed to reduce the error to the actuator fitted on the 2- way modulation valve and chilled water is allowed to enter the Coil. The above action results in the cooling and dehumidification process, thereby reducing the dry- bulb temperature and the moisture content of the air entering the room. The cooling is achieved by removing the sensible/ latent heat from the air. If the supply air temperature is lower than the set point the control loop shall modulate the valve up to 0% for less cooling and thereby reducing the level of reduction in the dry bulb temperature. I. CO2 or Fresh Air Quantity Control/ Indoor Air Quality In the common areas AHU CO2 concentration level will be measured by CO2 sensor installed in critical place where presumed more occupancy. (The concentration level ranges of 400 to 1200PPM or 700PPM above outdoor air). The BMS DDC controller will compare the measured value of CO2 concentration and set value. If the measured value is higher then the set value, DDC controller will generate the proportional control output to the fresh damper to open more and return air damper to close more so

Upload: batak-ranau

Post on 03-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 268_pdfsam_2.3- Mechanical, HVAC & Plumbing Specification Novotel

7/28/2019 268_pdfsam_2.3- Mechanical, HVAC & Plumbing Specification Novotel

http://slidepdf.com/reader/full/268pdfsam23-mechanical-hvac-plumbing-specification-novotel 1/1

Gulf House EngineeringJanuary 2010

07-C106 NOVOTEL AL DANA RESORT TOWERS PAGE 266 SECTION 15850 AIR HANDLING UNITS

AHU- Selector (H-O-A) switches position.AHU Healthy status.

If both are positive, BMS DDC controller will give an opencommand to AHU fresh air intake damper to open its minimumposition for preset level. After a time delay it will give a startcommand to AHU supply air fan VFD.

G. Humidity (Option)

Fresh air and Return Air humidity and temperature is monitored byBMS DDC Controller through humidity sensors and the same willbe used to calculate inside and outside Enthalpy. The difference ininside and outside Enthalpy will initiate free cooling operation of AHU.

H. Temperature Control

In the common areas AHU supply return and fresh airtemperatures will be continuously measured by the duct mountedtemperature sensor; which is installed in AHU supply air, return airand fresh air duct respectively.

The temperature difference between the supply and the supplyair temperature set point value will generate the coolingdemand. The control loop within the controller will perform themathematical calculations and compare the measured valueand current set point value. If the measured value is morethen the set point value, cooling loop will be initiated. Thevoltage level from sensor is converted into a number, whichthe sensor will scale into degree centigrade. The loop will thengenerate a proportional control output designed to reduce theerror to the actuator fitted on the 2- way modulation valve andchilled water is allowed to enter the Coil.

The above action results in the cooling and dehumidificationprocess, thereby reducing the dry- bulb temperature and themoisture content of the air entering the room. The cooling isachieved by removing the sensible/ latent heat from the air.

If the supply air temperature is lower than the set point thecontrol loop shall modulate the valve up to 0% for less

cooling and thereby reducing the level of reduction in thedry bulb temperature.

I. CO2 or Fresh Air Quantity Control/ Indoor Air Quality

In the common areas AHU CO2 concentration level will bemeasured by CO2 sensor installed in critical place wherepresumed more occupancy. (The concentration level ranges of 400to 1200PPM or 700PPM above outdoor air). The BMS DDCcontroller will compare the measured value of CO2 concentration

and set value. If the measured value is higher then the set value,DDC controller will generate the proportional control output to thefresh damper to open more and return air damper to close more so