Warning Always read this instruction sheet thoroughly before using DVP EH digital I/O extension unit. This is an OPEN TYPE extension unit. The extension unit should be kept in an enclosure away from airborne, dust, high humidity, electric shock risk and vibration. Also, it is equipped with protective methods such as special tools or keys to open the enclosure, so as to avoid the hazard to users and damage the extension unit. DO NOT connect AC main circuit power supply to any of the input/output terminals, as it will damage the extension unit. Check all the wiring prior to power up. DO NOT touch terminals when power on. Introduction Thank you for choosing Delta DVP-EH series PLC. The main processing units offer 8 ~ 48 points and the maximum input/output can be extended up to 256 points. Product Profile and Outline 1 3 4 3 5 5 2 7 7 2 1 5 5 3 3 4 7 7 Dimension (mm) Model Length Width Height DVP08HM11N 90 40 82 DVP16HM11N 90 55 82 DVP08HN11R/T 90 40 82 DVP16HP11R/T 90 55 82 3 4 2 6 6 6 7 7 3 3 8 9 1 10 11 Dimension (mm) Model Length Width Height DVP32HN00R/T 90 143.5 82.2 DVP32HP00R/T 90 143.5 82.2 DVP48HP00R/T 90 174 82.2 1. Power, low voltage indicators 5. Extension wiring 9. Cover 2. I/O terminals 6. Extension port cover 10. Input indicators 3. DIN rail clip 7. Direct mounting holes 11. Output indicators 4. DIN rail 8. Model name DVP EH Series Model Input unit Output unit Model Power Points Type Points Type DVP08HM11N 8 0 DVP16HM11N 16 0 N/A DVP08HN11R 0 8 DVP08HP11R 4 4 DVP16HP11R 8 8 Relay: 250V AC/30V DC 2A/1point DVP08HN11T 0 8 DVP08HP11T 4 4 DVP16HP11T 24V DC 8 DC Type Sink/Source 8 Transistor: 5 ~ 30V DC 0.3A/1point at 40°C ENGLISH Specifications Electrical Specification Model Item 08HM11N 16HM11N 08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T 32HP00R/T 48HP00R/T Power supply voltage 24V DC (20.4 ~ 28.8V DC) (-15% ~ 20%) 100~240V AC (-15%~10%), 50/60Hz ± 5% Power consumption 1W/1.5W 1.5W 1.5W 2W 30VA 30VA 30VA 24V DC supply current NA NA NA NA NA 500mA 500mA Power protection 24V DC output with short-circuit protection Voltage withstand 1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) Insulation resistance > 5 Mat 500V DC (Between all input/output and earth) Noise immunity ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m Grounding The diameter of grounding wire cannot be smaller than the wire diameter of the terminals Land N (All DVP units should be grounded directly to the ground pole.) Environment Operation: 0 C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2; Storage: -25 C ~ 70 C (temperature), 5 ~ 95% (humidity) Vibration/shock resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) Weight (g) 124/160 130/120 136/116 225/210 660/590 438/398 616/576 Approvals I/O Terminal Specification Input point Input point type DC Input type DC (SINK or SOURCE) Input current 24V DC 5mA Off On, above 16.5V DC Active level On Off, below 8V DC Reaction time About 20ms Circuit isolation /operation indicator Photocoupler/LED On Output point Output point type Relay-R Transistor-T Current specification 1.5A/1point (5A/COM) 55°C 0.1A/1point, 50°C 0.15A/1point, 45°C 0.2A/1point, 40°C 0.3A/1point (2A/COM) Voltage specification Below 250V AC, 30V DC 30V DC 75VA (inductive) Maximum load 90W (resistive) 9W Reaction time About 10ms Off On 15us On Off 25us Input unit Output unit Model Power Points Type Points Type DVP32HN00R 0 32 DVP32HP00R 16 16 DVP48HP00R 24 24 Relay: 250V AC/30V DC 2A/1point DVP32HN00T 0 32 DVP32HP00T 16 16 DVP48HP00T 100 ~ 240V AC 24 DC Type Sink/Source 24 Transistor: 5 ~ 30V DC 0.3A/1 point at 40°C Installation and Wiring Digital I/O Terminal Wiring 08HM DVP-08HM (8in) X0 X X X X X X X S/S 08HN DVP-08HN (8out) Y0 Y1 Y3 Y4 Y5 Y7 C0 Y2 C1 Y6 08HP DVP-08HP (4in/4out) X0 Y1 Y3 C0 Y2 Y0 X2 S/S X1 X3 16HM DVP-16HM (16in) X10 X11 S/S X1 X3 S/S X12 X13 X14 X15 X16 X17 X0 X2 X4 X5 X7 X6 16HP DVP-16HP (8in/8out) X4 X5 X1 X3 S/S X6 X7 Y3 Y4 Y5 Y6 X0 X2 C0 Y0 Y2 Y1 Y7 32HN X15 X14 C3 Y12 Y11 Y10 Y7 Y6 C2 Y5 Y4 Y3 C1 Y2 Y1 Y16 Y20 Y21 Y22 Y23 Y24 C7 C6 C5 C4 Y25 Y30 Y31 Y35 Y36 Y34 Y32 Y27 Y26 C0 DVP-32HN(32out) (AC Power IN) Y33 Y37 32HP X17 X16 X15 X14 X13 X12 X11 X10 X7 X6 X5 X4 X3 X2 X1 X0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 C3 C2 C1 C0 Y7 Y12 Y13 Y16 Y17 Y15 Y14 Y11 Y10 S/S DVP-32HP(16in/16out) (AC Power IN,DC Signal IN) 48HP X17 X16 X15 X14 X13 X12 X11 X10 X7 X6 X5 X4 X3 X2 X1 X0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 C3 C2 C1 C0 Y7 Y12 Y13 Y16 Y17 Y15 Y14 Y11 Y10 S/S X27 X26 X25 X24 X23 X22 X21 X20 C4 Y21 Y22 Y27 Y23 Y26 Y24 Y20 Y25 DVP-48HP(24in/24out) (AC Power IN,DC Signal IN) Mounting Arrangements and Wiring Notes DIN Rail Installation: The DVP-PLC can be secured to a cabinet by using the DIN rail that is 35mm high with a depth of 7.5mm. When mounting the PLC on the DIN rail, be sure to use the end bracket to stop any side-to-side motion of the PLC, thus to reduce the chance of the wires being pulled loose. On the bottom of the PLC is a small retaining clip. To secure the PLC to the DIN rail, place it onto the rail and gently push up on the clip. To remove it, pull down on the retaining clip and gently pull the PLC away from the DIN rail. Please see the figure on the right: Direct Mounting: Use the specified dimensions and install with M4 screws. For heat dissipation. Make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet. (shown as below) DVP MPU > 50mm > 50mm > 50mm > 50mm Wiring: Below 6.2 To suit M3.5 screw terminal Below 6.2 1. Please use O-type or Y-type terminals for I/O wiring terminals. The specification for the terminals is as shown on the left. PLC terminal screws should be tightened to between 5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs). Use copper conductor only, 60°C/75°C. 2. DO NOT wire to the No Function terminals . I/O signal wires or power supply should not run through the same multi-wire cable or conduit. 3. When tightening the screws and performing wiring, please avoid that metallic particles fall into PLC. After completing wiring, please remove the label which is used to obstruct the metallic particles on the ventilation hole for well heat dissipation. 4. There should be a 50mm or more distance between the PLC and other control component. Also, keep the PLC away from high voltage line and power equipment. Environment: 1. DO NOT store the PLC in an airborne dust, smoky, metallic particles, corrosive or flammable gases. 2. DO NOT store the PLC in a location where temperatures and humidity will exceed specification. 3. DO NOT mount the PLC in a location where vibration and shock will exceed specification. I/O Point Serial Sequence When connecting MPU with less than 32 points to extension unit, the input number of 1 st extension unit is started from X20 in sequence and the output number is started from Y20 in sequence. If connecting MPU with more than 32 points to extension unit, the input number of the 1 st extension unit is started from the last input number of the MPU in sequence and the output number is started form the last output number of the MPU in sequence. MPU EXT1 EXT2 EXT3 EXT4 PLC Model Input points Output points Input number Output number MPU 16EH/32EH/64EH 8/16/32 8/16/32 X0~X7/X0~X17/X0~X37 Y0~Y7/Y0~Y17/Y0~Y37 EXT1 32HP 16 16 X20~X37/X20~X37/X40~X57 Y20~Y37/Y20~Y37/Y40~Y57 EXT2 48HP 24 24 X40~X67/X40~X67/X60~X107 Y40~Y67/Y40~Y67/Y60~Y107 EXT3 08HP 4 4 X70~X73/X70~X73/X110~X113 Y70~Y73/Y70~Y73/Y110~Y113 EXT4 08HN 0 8 - Y74~Y103/Y74~Y103/Y114~Y123 In system application example, if the input/output of the 1 st MPU are less than 16, its input/output will be defined as 16 and thus there are no corresponding input/output for higher numbers. The input/output number of extension number is the sequential number from the last number of the MPU. Power Input Wiring and Specification The power input for DVP-EH series PLC is AC input. Please pay particular attention to the following notes: 1. Connect the AC input (100 ~ 240V) to terminals L and N. Any 110V AC or 220V AC connected to the +24V terminal or input points will permanently damage the PLC. 2. The AC power inputs for the MPU and the I/O Extension Unit should be ON or OFF at the same time. 3. Please use wires of 1.6mm or above for the grounding of the MPU. 4. If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too long or the power voltage drops, the PLC will stop operation and all outputs will be off. Once power is on again, the PLC will resume automatically. (There are latched auxiliary relays and registers inside of the PLC, please be aware when programming.) AC Input Type L N 2.0 A DC/DC +5V +24V 24G S/S X0 X1 X2 100~240VAC The +24V supply output is rated at 0.5A as max. from MPU. DO NOT connect external power supply to this termianl. Moreover, it takes 6 ~ 7mA to drive each input point, so total of 100mA is needed for 16 input points. As a result, the output load of +24V should not exceed 400mA. Since the PLC is in control of numerous devices, operation of either one device could affect the operation of other devices; therefore, the breakdown of either one device would consequently be detrimental to the whole auto control system, and danger will thus be resulted. Please use the recommended wiring below for the power input: Power supply for AC loads Fuse for circuit protection (3A limit) Power on pilot indicator Emergency stop: a manual stop button is provided for emergency to disconnect system power. Circuit isolation device (System Power Disconnect): use electromagnetic contactor and the relay to be the isolation unit of the power circuit to prevent the possible instability of the system when the power is supplied on and off. DVP PLC MPU (main processing unit) Class three grounding. OV 24VDC MC MC N L 1 1 2 3 4 5 6 6 8 Guard Limit Power supply: AC: 100 ~ 240V AC, 50/60Hz DC: 24V DC Input/Output Point Wiring Input Point Wiring There are SINK and SOURCE types for the input signal of the input point with DC input. Definition as follows: Sink = Current flow into common terminal S/S Source = Current flows out of common terminal S/S S/S X0 Sinking S/S X0 Sourcing Input point loop equivalent circuit Wiring loop DC Type (DC Signal IN) SINK Mode (Current flows into the common terminal S/S) 24VDC 24G X0 S/S +24V SINK +5V 24G S/S X0 X1 X2 +24V Sink Type Input point loop equivalent circuit Wiring loop DC Type (DC Signal IN) SOURCE Mode (Current flows out of common terminal S/S) 24VDC 24G X0 S/S +24V SOURCE +5V 24G S/S X0 X1 X2 +24V Source Type Output Point Wiring DO NOT wire to the No Function terminals Fuse Diode in reverse direction to protect the relay*1 Mutually exclusive outputs*2 Emergency stop: use an external switch Surge absorber*3 Conductive loading Incandescent lamp (resistive loading) DC supply Relay output wiring MC2 MC1 9 10 C0 C1 Y0 Y4 C2 Y2 Y3 Y5 Y1 5 2 3 7 8 1 6 7 2 5 4 MC2 MC1 AC supply *1: There is no protection circuit for the Relay output in the PLC. If DC conductive loading is on, add a diode in reverse direction in parallel to extend the life of the Relay. The diode in reverse direction should correspond to the following specification: - The diode is able to withstand 5~10+ times loading voltage as maximum. - The forward current of the diode must be greater than loading current. *2: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection. *3: There is no protection circuit for the Relay in the PLC. If AC conductive loading is on, connect a surge absorber (0.1uF+ “100ohm to 120ohm”) to reduce interference and extend the life of the Relay. DO NOT wire to the No Function terminals Emergency stop Fuse Mutually exclusive output*1 DC apply Incandescent lamp (resistive loading) Diode in reverse direction to protect the transistor*2 Conductive loading Transistor output wiring MC2 MC1 C0 C1 Y0 Y4 C2 Y2 Y3 Y5 Y1 5 7 8 1 6 6 4 MC2 MC1 2 3 3 9 Resistive loading *1: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection. *2: Use Zener diode (39V) inside the PLC to protect the transistor. If conductive loading is on, adding a diode in reverse direction in parallel is recommended. (OPEN TYPE) / ( : ) / DVP-EH EH 8 ~ 48 / 256 1 3 4 3 5 5 2 7 7 2 1 5 5 3 3 4 7 7 (mm) DVP08HM11N 90 40 82 DVP16HM11N 90 55 82 DVP08HN11R/T 90 40 82 DVP16HP11R/T 90 55 82 3 4 2 6 6 6 7 7 3 3 8 9 1 10 11 (mm) (w) DVP32HN00R/T 90 143.5 82.2 DVP32HP00R/T 90 143.5 82.2 DVP48HP00R/T 90 174 82.2 1. 5. 9. 2. / 6. 10. 3. DIN 7. 11. 4. DIN 8. DVP08HM11N 8 0 DVP16HM11N 16 0 DVP08HN11R 0 8 DVP08HP11R 4 4 DVP16HP11R 8 8 Relay 250V AC/30V DC 2A/1 DVP08HN11T 0 8 DVP08HP11T 4 4 DVP16HP11T 24V DC 8 DC Type Sink/Source 8 Transistor 5 ~ 30V DC 0.3A/1 @40°C DVP32HN00R 0 32 DVP32HP00R 16 16 DVP48HP00R 24 24 Relay 250V AC/30V DC 2A/1 DVP32HN00T 0 32 DVP32HP00T 16 16 DVP48HP00T 100 ~ 240V AC 24 DC Type Sink/Source 24 Transistor 5 ~ 30V DC 0.3A/1 @40 C 08HM11N 16HM11N 08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T 32HP00R/T 48HP00R/T 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ 20%) 100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5% 1W / 1.5W 1.5W 1.5W 2W 30VA 30 VA 30 VA 24V DC NA NA NA NA NA 500 mA 500 mA 24V DC 24V DC 1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) 5 M/ 500V DC ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m L, N PLC / 0 ~ 55°C 50 ~ 95% 2 -25 ~ 70°C 5 ~ 95% / IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) (g) 124/160 130/120 136/116 225/210 660/590 438/398 616/576 / SINK SOURCE 24V DC 5mA Off On 16.5V DC On Off 8V DC 20ms / /LED On -R -T 1.5A/1 5A/COM 55°C 0.1A/1 50°C 0.15A/1 45°C 0.2A/1 40°C 0.3A/1 2A/COM 250V AC,30V DC 30V DC 75VA 90 W 9W 10 ms Off On 15us On Off 25us

Upload: others

Post on 06-Jan-2022

11 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: 24VDC - cncthai.com

Warning Always read this instruction sheet thoroughly before using DVP EH digital I/O extension unit.

This is an OPEN TYPE extension unit. The extension unit should be kept in an enclosure away from airborne, dust,

high humidity, electric shock risk and vibration. Also, it is equipped with protective methods such as special tools or

keys to open the enclosure, so as to avoid the hazard to users and damage the extension unit.

DO NOT connect AC main circuit power supply to any of the input/output terminals, as it will damage the extension

unit. Check all the wiring prior to power up. DO NOT touch terminals when power on.

Introduction

Thank you for choosing Delta DVP-EH series PLC. The main processing units offer 8 ~ 48 points and the maximum input/output can be extended up to 256 points.

Product Profile and Outline

1

3

4

3

55 2 7

7

21

55

3

3

4

7

7

Dimension (mm) Model

Length Width Height

DVP08HM11N 90 40 82

DVP16HM11N 90 55 82

DVP08HN11R/T 90 40 82

DVP16HP11R/T 90 55 82

3

4

26

6 67

733

8 9 1

10

11

Dimension (mm) Model

Length Width Height

DVP32HN00R/T 90 143.5 82.2

DVP32HP00R/T 90 143.5 82.2

DVP48HP00R/T 90 174 82.2

1. Power, low voltage indicators 5. Extension wiring 9. Cover

2. I/O terminals 6. Extension port cover 10. Input indicators

3. DIN rail clip 7. Direct mounting holes 11. Output indicators

4. DIN rail 8. Model name

DVP EH Series Model

Input unit Output unit Model Power

Points Type Points Type

DVP08HM11N 8 0

DVP16HM11N 16 0 N/A

DVP08HN11R 0 8

DVP08HP11R 4 4

DVP16HP11R 8 8

Relay: 250V AC/30V DC 2A/1point

DVP08HN11T 0 8

DVP08HP11T 4 4

DVP16HP11T

24V DC

8

DC Type

Sink/Source

8

Transistor: 5 ~ 30V DC 0.3A/1point at 40°C

ENGLISH

Specifications

Electrical Specification Model

Item

08HM11N

16HM11N 08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T 32HP00R/T 48HP00R/T

Power supply voltage 24V DC (20.4 ~ 28.8V DC) (-15% ~ 20%) 100~240V AC (-15%~10%), 50/60Hz ± 5%

Power consumption 1W/1.5W 1.5W 1.5W 2W 30VA 30VA 30VA

24V DC supply current NA NA NA NA NA 500mA 500mA

Power protection 24V DC output with short-circuit protection

Voltage withstand 1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE)

Insulation resistance > 5 MΩ at 500V DC (Between all input/output and earth)

Noise immunity

ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog &

Communication I/O: 250V,

Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m

Grounding The diameter of grounding wire cannot be smaller than the wire diameter of the terminals Land

N (All DVP units should be grounded directly to the ground pole.)

Environment Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;

Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

Vibration/shock

resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

Weight (g) 124/160 130/120 136/116 225/210 660/590 438/398 616/576

Approvals

I/O Terminal Specification Input point

Input point type DC

Input type DC (SINK or SOURCE)

Input current 24V DC 5mA

Off→On, above 16.5V DC Active level

On→Off, below 8V DC

Reaction time About 20ms

Circuit isolation

/operation indicator Photocoupler/LED On

Output point

Output point type Relay-R Transistor-T

Current specification 1.5A/1point (5A/COM) 55°C 0.1A/1point, 50°C 0.15A/1point,

45°C 0.2A/1point, 40°C 0.3A/1point (2A/COM)

Voltage specification Below 250V AC, 30V DC 30V DC

75VA (inductive) Maximum load

90W (resistive) 9W

Reaction time About 10ms Off→On 15us On→Off 25us

Input unit Output unit Model Power

Points Type Points Type

DVP32HN00R 0 32

DVP32HP00R 16 16

DVP48HP00R 24 24

Relay: 250V AC/30V DC 2A/1point

DVP32HN00T 0 32

DVP32HP00T 16 16

DVP48HP00T

100 ~ 240V AC

24

DC Type

Sink/Source

24

Transistor: 5 ~ 30V DC 0.3A/1 point at 40°C

Installation and Wiring Digital I/O Terminal Wiring

08HM DVP-08HM (8in)

X0 X2 X4 X6X1 X3 X5 X7S/S

08HN DVP-08HN (8out)

Y0 Y1 Y3 Y4 Y5 Y7

C0 Y2 C1 Y6

08HP DVP-08HP (4in/4out)

X 0 Y1 Y 3

C0 Y2

Y0X 2

S /S X 1 X3

16HM DVP-16HM (16in)

X10 X 11

S /S X1 X 3

S/S X12 X13 X 14 X15 X16 X 17

X 0 X2 X4 X5 X7X6

16HP DVP-16HP (8in/8out)

X4 X5

X 1 X3

S /S X6 X7

Y3

Y4 Y5 Y 6

X0 X 2 C 0 Y 0 Y2Y 1

Y 7

32HN

X15

X14C3

Y12

Y11

Y10

Y7

Y6

C2

Y5

Y4

Y3

C1

Y2

Y1

Y16

Y20

Y21 Y22 Y23

Y24 C7C6C5C4

Y25

Y30

Y31

Y35

Y36Y34Y32Y27Y26

C0

DVP-32HN(32out)

(AC Power IN)

Y33 Y37

32HP

X17X16

X15X14

X13X12

X11X10

X7X6

X5X4

X3X2

X1X0

Y0 Y1Y2

Y3 Y4 Y5

Y6 C3C2C1C0Y7

Y12Y13

Y16Y17Y15Y14Y11Y10

S/S

DVP-32HP(16in/16out)

(AC Power IN,DC Signal IN)

48HP

X17X16

X15X14

X13X12

X11X10

X7X6

X5

X4X3

X2

X1X0

Y0 Y1Y2

Y3 Y4 Y5

Y6 C3C2C1C0Y7

Y12Y13

Y16Y17Y15Y14Y11Y10

S/SX27

X26X25

X24X23

X22X21

X20

C4 Y21Y22

Y27Y23Y26Y24Y20

Y25

DVP-48HP(24in/24out)

(AC Power IN,DC Signal IN)

Mounting Arrangements and Wiring Notes DIN Rail Installation:

The DVP-PLC can be secured to a cabinet by using the DIN rail that is 35mm high with a depth of 7.5mm. When mounting the PLC on the DIN rail, be sure to use the end bracket to stop any side-to-side motion of the PLC, thus to reduce the chance of the wires being pulled loose. On the bottom of the PLC is a small retaining clip. To secure the PLC to the DIN rail, place it onto the rail and gently push up on the clip. To remove it, pull down on the retaining clip and gently pull the PLC away from the DIN rail. Please see the figure on the right:

Direct Mounting: Use the specified dimensions and install with M4 screws.

For heat dissipation. Make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet. (shown as below)

DVP MPU > 50 mm > 50mm

> 50mm

> 50mm

Wiring:

Below 6.2

To suit M3.5 screw terminal

Below 6.2

1. Please use O-type or Y-type terminals for I/O wiring terminals. The specification for the terminals is as shown on the left. PLC terminal screws should be tightened to between 5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs). Use copper conductor only, 60°C/75°C.

2. DO NOT wire to the No Function terminals • . I/O signal wires or power supply should not run through the same multi-wire cable or conduit.

3. When tightening the screws and performing wiring, please avoid that metallic particles fall into PLC. After completing wiring, please remove the label which is used to obstruct the metallic particles on the ventilation hole for well heat dissipation.

4. There should be a 50mm or more distance between the PLC and other control component. Also, keep the PLC away from high voltage line and power equipment.

Environment:

1. DO NOT store the PLC in an airborne dust, smoky, metallic particles, corrosive or flammable gases.

2. DO NOT store the PLC in a location where temperatures and humidity will exceed specification.

3. DO NOT mount the PLC in a location where vibration and shock will exceed specification.

I/O Point Serial Sequence When connecting MPU with less than 32 points to extension unit, the input number of 1st extension unit is started from X20 in sequence and the output number is started from Y20 in sequence. If connecting MPU with more than 32 points to extension unit, the input number of the 1st extension unit is started from the last input number of the MPU in sequence and the output number is started form the last output number of the MPU in sequence.

MPU EXT1 EXT2 EXT3 EXT4

PLC Model Input

points

Output

points Input number Output number

MPU 16EH/32EH/64EH 8/16/32 8/16/32 X0~X7/X0~X17/X0~X37 Y0~Y7/Y0~Y17/Y0~Y37

EXT1 32HP 16 16 X20~X37/X20~X37/X40~X57 Y20~Y37/Y20~Y37/Y40~Y57

EXT2 48HP 24 24 X40~X67/X40~X67/X60~X107 Y40~Y67/Y40~Y67/Y60~Y107

EXT3 08HP 4 4 X70~X73/X70~X73/X110~X113 Y70~Y73/Y70~Y73/Y110~Y113

EXT4 08HN 0 8 - Y74~Y103/Y74~Y103/Y114~Y123

In system application example, if the input/output of the 1st MPU are less than 16, its input/output will be defined as 16 and thus there are no corresponding input/output for higher numbers. The input/output number of extension number is the sequential number from the last number of the MPU.

Power Input Wiring and Specification The power input for DVP-EH series PLC is AC input. Please pay particular attention to the following notes: 1. Connect the AC input (100 ~ 240V) to terminals L and N. Any 110V AC or 220V AC connected to the +24V

terminal or input points will permanently damage the PLC. 2. The AC power inputs for the MPU and the I/O Extension Unit should be ON or OFF at the same time. 3. Please use wires of 1.6mm or above for the grounding of the MPU. 4. If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too long or

the power voltage drops, the PLC will stop operation and all outputs will be off. Once power is on again, the PLC will resume automatically. (There are latched auxiliary relays and registers inside of the PLC, please be aware when programming.)

AC Input

Type

L N 2.0 A

DC/DC +5V +24V 24G S/S X0 X1 X2 100~240VAC

The +24V supply output is rated at 0.5A as max. from MPU. DO NOT connect external power supply to this termianl. Moreover, it takes 6 ~ 7mA to drive each input point, so total of 100mA is needed for 16 input points. As a result, the output load of +24V should not exceed 400mA.

Since the PLC is in control of numerous devices, operation of either one device could affect the operation of other devices; therefore, the breakdown of either one device would consequently be detrimental to the whole auto control system, and danger will thus be resulted. Please use the recommended wiring below for the power input:

Power supply for AC loads

Fuse for circuit protection (3A limit)

Power on pilot indicator

Emergency stop: a manual stop button is provided for emergency

to disconnect system power.

Circuit isolation device (System Power Disconnect): use

electromagnetic contactor and the relay to be the isolation unit of

the power circuit to prevent the possible instability of the system

when the power is supplied on and off.

DVP PLC MPU (main processing unit)

Class three grounding. OV24VDC

MCMC

NL

1

1

2

3

4

5

66

78

Guard

Limit

Power supply:

AC: 100 ~ 240V AC, 50/60Hz

DC: 24V DC

Input/Output Point Wiring Input Point Wiring

There are SINK and SOURCE types for the input signal of the input point with DC input. Definition as follows:

Sink = Current flow into common terminal S/S Source = Current flows out of common terminal S/S S/S

X0

Sinking

S/S

X0

Sourcing

Input point loop equivalent circuit Wiring loop DC Type

(DC Signal IN)

SINK Mode (Current flows into the common terminal S/S)

24VDC

24G

X0

S/S

+24VSINK

+5V

24G S/S X0 X1 X2+24V

Sink Type

Input point loop equivalent circuit Wiring loop DC Type

(DC Signal IN)

SOURCE Mode (Current flows out of

common terminal S/S)

24VDC

24G

X0

S/S

+24VSOURCE

+5V

24G S/S X0 X1 X2+24V

Source Type

Output Point Wiring

DO NOT wire to the No Function terminals •

Fuse

Diode in reverse direction to protect the relay*1

Mutually exclusive outputs*2

Emergency stop: use an external switch

Surge absorber*3

Conductive loading

Incandescent lamp (resistive loading)

DC supply

Relay output wiring

MC2MC19

10

C0 C1Y0 Y4C2 Y2 Y3 Y5Y1

5 2

3 7

8

1

6

7

2

5 4

MC2 MC1

AC supply

*1: There is no protection circuit for the Relay output in the PLC. If DC conductive loading is on, add a diode in reverse direction in parallel to extend the life of the Relay. The diode in reverse direction should correspond to the following specification: - The diode is able to withstand 5~10+ times loading voltage as maximum. - The forward current of the diode must be greater than loading current.

*2: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection. *3: There is no protection circuit for the Relay in the PLC. If AC conductive loading is on, connect a surge absorber (0.1uF+ “100ohm to

120ohm”) to reduce interference and extend the life of the Relay.

DO NOT wire to the No Function terminals •

Emergency stop

Fuse

Mutually exclusive output*1

DC apply

Incandescent lamp (resistive loading)

Diode in reverse direction to protect the transistor*2

Conductive loading

Transistor output wiring

MC2MC1

C0 C1Y0 Y4C2 Y2 Y3 Y5Y1

5 7 8

1

6

64

MC2 MC1

2

3

3

9

Resistive loading

*1: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection.

*2: Use Zener diode (39V) inside the PLC to protect the transistor. If conductive loading is on, adding a diode in reverse direction in parallel is recommended.

注意事項 請在使用之前,詳細閱讀本使用說明書。

本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊意外之外殼配線箱內。另必須具備保護措施 (如: 特殊之工具或鑰匙才可打開) 防止非維護人員操作或意外衝擊本體,造成危險及損壞。

交流輸入電源不可連接於直流類型之輸入/出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。請勿在上電時觸摸任何端子。

產品簡介 謝謝您採用台達 DVP-EH可程式控制器。EH 8 ~ 48點擴充,含主機最大數位輸入/輸出擴充分別可達 256點。

產品外觀及各部介紹

1

3

4

3

55 2 7

7

21

55

3

3

4

7

7

尺寸 (mm) 機種名稱 長 寬 高

DVP08HM11N 90 40 82

DVP16HM11N 90 55 82

DVP08HN11R/T 90 40 82

DVP16HP11R/T 90 55 82

3

4

26

6 67

733

8 9 1

10

11

尺寸 (mm) 機種名稱 長 寬 (w) 高

DVP32HN00R/T 90 143.5 82.2

DVP32HP00R/T 90 143.5 82.2

DVP48HP00R/T 90 174 82.2

1. 電源、低電壓指示燈 5. 擴充排線 9. 上蓋

2. 輸出/入端子 6. 擴充機連接口上蓋 10. 輸入指示燈

3. DIN軌固定扣 7. 直接固定孔 11. 輸出燈示燈

4. DIN軌固定槽 8. 機種名稱

機種型號 輸入單元 輸出單元 機種 電源 點數 形式 點數 形式

DVP08HM11N 8 0

DVP16HM11N 16 0 無

DVP08HN11R 0 8

DVP08HP11R 4 4

DVP16HP11R 8 8

繼電器 Relay 250V AC/30V DC 2A/1點

DVP08HN11T 0 8

DVP08HP11T 4 4

DVP16HP11T

24V DC

8

DC Type

Sink/Source

8

電晶體 Transistor 5 ~ 30V DC 0.3A/1 點@40°C

繁體中文

輸入單元 輸出單元 機種 電源 點數 形式 點數 形式

DVP32HN00R 0 32

DVP32HP00R 16 16

DVP48HP00R 24 24

繼電器 Relay 250V AC/30V DC 2A/1點

DVP32HN00T 0 32

DVP32HP00T 16 16

DVP48HP00T

100 ~ 240V

AC

24

DC Type

Sink/Source

24

電晶體 Transistor 5 ~ 30V DC 0.3A/1 點@40°C

規格 電氣規格

機種

項目

08HM11N

16HM11N 08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T 32HP00R/T 48HP00R/T 電源電壓 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ 20%)

100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5% 消耗電力 1W / 1.5W 1.5W 1.5W 2W 30VA 30 VA 30 VA

24V DC供應電流 NA NA NA NA NA 500 mA 500 mA

24V DC輸出具短路保護 24V DC輸出具短路保護 突波電壓耐受量 1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) 絕緣阻抗 5 MΩ以上(所有輸出/入點對地之間 500V DC) 雜訊免疫力

ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog &

Communication I/O: 250V,

Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 接地 接地配線之線徑不得小於電源端 L, N之線徑(多台 PLC同時使用時,請務必單點接地) 操作/儲存環境 操作:0 ~ 55°C(溫度), 50 ~ 95%(濕度), 污染等級 2 儲存:-25 ~ 70°C(溫度),5 ~ 95%(濕度) 耐振動/衝擊 國際標準規範 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 重量(約)(g) 124/160 130/120 136/116 225/210 660/590 438/398 616/576 認證

輸入/出點規格 輸入點電氣規格 輸入點形式 直流 輸入形式 直流(SINK或 SOURCE) 輸入電壓電流 24V DC 5mA

Off → On 16.5V DC以上 動作位準 On → Off 8V DC以下 反應時間 約 20ms 電路隔離/操作指示 光耦合器/LED On

輸出點電氣規格 輸出點形式 繼電器-R 電晶體-T 電流規格 1.5A/1點(5A/COM) 55°C 0.1A/1點、50°C 0.15A/1點、

45°C 0.2A/1點、40°C 0.3A/1點(2A/COM) 電壓規格 250V AC,30V DC以下 30V DC

75VA(電感性) 最大負載 90 W(電阻性)

9W 反應時間 約 10 ms Off → On 15us On → Off 25us

Page 2: 24VDC - cncthai.com

安裝及配線 數位 I/O擴充機之端子配置圖

08HM DVP-08HM (8in)

X0 X2 X4 X6X1 X3 X5 X7S/ S

08HN DVP-08HN (8out)

Y0 Y1 Y3 Y4 Y5 Y7

C0 Y2 C1 Y6

08HP DVP-08HP (4in/4out)

X0 Y1 Y3

C0 Y2

Y0X2

S/S X1 X3

16HM DVP-16HM (16in)

X 10 X 11

S/S X1 X3

S /S X12 X13 X14 X15 X16 X 17

X0 X2 X 4 X5 X 7X 6

16HP DVP-16HP (8in/8out)

X4 X5

X1 X3

S/S X6 X7

Y3

Y4 Y5 Y6

X0 X2 C0 Y0 Y2Y1

Y7

32HN

X15

X14C3

Y12

Y11

Y10

Y7

Y6

C2

Y5

Y4

Y3

C1

Y2

Y1

Y16

Y20

Y21 Y22 Y23

Y24 C7C6C5C4

Y25

Y30

Y31

Y35

Y36Y34Y32Y27Y26

C0

DVP-32HN(32out)

(AC Power IN)

Y33 Y37

32HP

X17X16

X15X14

X13X12

X11X10

X7X6

X5X4

X3X2

X1X0

Y0 Y1Y2

Y3 Y4 Y5

Y6 C3C2C1C0

Y7

Y12Y13

Y16Y17Y15Y14Y11Y10

S/S

DVP-32HP(16in/16out)

(AC Power IN,DC Signal IN)

48HP

X17X16

X15X14

X13X12

X11X10

X7X6

X5X4

X3X2

X1X0

Y0 Y1Y2

Y3 Y4 Y5

Y6 C3C2C1C0Y7

Y12Y13

Y16Y17Y15Y14Y11Y10

S/SX27

X26X25

X24X23

X22X21

X20

C4 Y21Y22

Y27Y23Y26Y24Y20

Y25

DVP-48HP(24in/24out)

(AC Power IN,DC Signal IN)

盤內安裝及配線

DIN鋁軌之安裝方法: 適合 35mm之 DIN鋁軌,主機欲掛於鋁軌時,先將 PLC下方之固定塑膠片壓入,再將 PLC由上方掛上再往下壓即可。欲取下 PLC時,PLC底部下之固定塑膠片,以起子插入凹槽,向上撐開即可,該固定機構塑膠片為保持型,當所有的固定片撐開後,再將 PLC往上外方取出,如右圖所示: 直接鎖鏍絲方式:請依產品外型尺寸並使用 M4鏍絲。

PLC在安裝時,請裝配於封閉式之控制箱內,其周圍應保持一定之空間(如下圖所示),以確保 PLC散熱功能正常。

DVP MPU50mm以上50mm以上 50mm以上

50mm以上 配線:

6.2 以下M3.5 使用

6.2 以下

1. 出/入配線端請使用 O型或 Y型端子,端子規格如左所示。PLC端子鏍絲扭力為5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs)。只能使用 60/75°C的銅導線。

2. 空端子 • 請勿配線。輸入點信號線與輸出點等動力線請勿置於同一線糟內。

3. 鎖鏍絲及配線時請避免微小的金屬導體掉入 PLC內部,並在配線完成後,將位於 PLC上方散熱孔位置的防異物掉入之貼紙撕去,以保持散熱良好。

4. PLC與其它之控制元件應保持 50mm以上之間隔,並應遠離高壓線及動力設備。 使用環境:

1. 請勿將 PLC裝置於落塵大、油煙、金屬性粉塵及腐蝕性或可燃性氣體的環境當中。

2. 請勿將 PLC裝置於高溫、結露之環境,勿將 PLC裝置有直接振動及衝擊的場所。

3. 輸入點信號線與輸出點等動力線請勿置於同一線糟內或使用同一多芯之電纜線。

輸出入點序號排列 使用 32點點數以下的主機連接擴充機,所連接的第一台擴充機,輸入點編號由 X20依序排列,輸出點編號亦由Y20開始依序排列,使用 32點點數以上的主機連接擴充機,所連接的第一台擴充機,輸入點編號以主機最後編號依序排列,輸出點編號亦由主機最後編號依序排列,若使用者所連接的系統如下:

MPU EXT1 EXT2 EXT3 EXT4

PLC 機種 輸入點數 輸出點數 輸入點編號 輸出點編號

MPU 16EH/32EH/64EH 8/16/32 8/16/32 X0~X7/X0~X17/X0~X37 Y0~Y7/Y0~Y17/Y0~Y37

EXT1 32HP 16 16 X20~X37/X20~X37/X40~X57 Y20~Y37/Y20~Y37/Y40~Y57

EXT2 48HP 24 24 X40~X67/X40~X67/X60~X107 Y40~Y67/Y40~Y67/Y60~Y107

EXT3 08HP 4 4 X70~X73/X70~X73/X110~X113 Y70~Y73/Y70~Y73/Y110~Y113

EXT4 08HN 0 8 - Y74~Y103/Y74~Y103/Y114~Y123 系統組合範例中,第 1台MPU主機輸入點數 16點以下會被視為 16點輸入,序號較高的幾個輸入點則沒有對應實際的輸入點,主機輸出點數 16點以下會被視為 16點輸出,序號較高的幾個輸出點則沒有對應實際的輸出點。擴充機輸出入點編號則依照主機最後編號依序排列。

電源端配線及規格

DVP-EH系列 PLC電源輸入為交流輸入,在使用上應注意下列事項:

1. 交流電源輸入電壓,範圍寬廣 (100V AC ~ 240V AC),電源請接於 L,N兩端,如果將 110V AC或 220V AC接 至+24V端或輸入點端,將使 PLC損壞,請使用者特別注意。

2. 主機及 I/O擴充機之交流電源輸入請同時作 On或 Off的動作。

3. 主機之接地端使用 1.6mm以上之電線接地。

4. 當停電時間低於 10ms時,PLC不受影響繼續運轉,當停電時間過長或電源電壓下降將使 PLC停止運轉,輸出全部 Off,當電源恢復正常時,PLC亦自動回復運轉。(PLC內部具有停電保持的輔助繼電器及暫存器,使用者在作程式設計規劃時應特別注意使用) 交流電源 輸入型式

L N 2.0 A

DC/DC +5V +24V 24G S/S X0 X1 X2 100~240VAC

+24V電源供應輸出端,最大為 0.5A,請勿將其它的外部電源連接至此端子。每個輸入點驅動必須 6 ~ 7mA,若以16點輸入計算,大約需 100mA,因此+24V輸出給外部負載不可大於400mA。 由於 PLC控制許多裝置,任一裝置的動作可能都會影響其它裝置的動作,因此任一裝置的故障都可能會造成整個自動控制系統失控,甚至造成危險。所以在電源端輸入回路,建議配置如下的保護回路:

交流電源負載

電源回路保護用保險絲 (3A)

電源指示燈

緊急停止: 為預防突發狀況發生,設置一緊急停止按鈕,可在狀況發生時,切斷系統電源。

系統回路隔離裝置: 使用電磁接觸器、繼電器等開關作為系統電源回路隔離裝置,可防止電源斷續供應時,造成系統的不穩定。

DVP PLC本體

第三種接地,接地阻抗 100Ω以下 OV24VDC

MCMC

NL

1

1

2

3

4

5

66

78

Guard

Limit

電源供應: 交流 (AC): 100 ~ 240V AC, 50/60Hz 直流 (DC): 24V DC

輸入/出點之配線 輸入點之配線 輸入點之入力信號為直流電源 DC輸入,DC型式共有兩種接法:SINK及 SOURCE,其定義如下:

Sink = 電流流入共用端 S/S Source = 電流流出共用端 S/S S/S

X0

Sinking S/S

X0

Sourcing 輸入點回路等效電路 配線回路 直流形式

(DC Signal IN)

SINK 模式

+24V

24G

S/S

X0

24VDC

SINK

+5V

+24V 24G

Sink Type

X1 X2S/S X0

輸入點回路等效電路 配線回路 直流形式

(DC Signal IN)

SOURCE 模式

+24V

24G

S/S

X0

24VDC

SOURCE

+5V

+24V 24G

Source Type

X1 X2S/S X0

輸出點之配線 空端子 • 請勿配線

保險絲

反向電流保護二極體*1

互斥輸出*2

緊急停止:使用外部開關

突波吸收器*3

電感性負載

白熾燈(電阻性負載)

9 直流電源供給

實用之繼電器輸出回路配線: MC2MC1

9

10

C0 C1Y0 Y4C2 Y2 Y3 Y5Y1

5 2

3 7

8

1

6

7

2

5 4

MC2 MC1

交流電源供給

*1: 在 PLC的輸出繼電器並沒有內部保護電路,因此若使用在直流電感性負載時,請並聯接上一個反向電流保護二極體,可增加接點壽命。反向電流保護二極體須符合下列規格:

1. 此二極體必須能承受最大 5 ~ 10+ 倍的負載電壓 2. 此二極體正向電流須大於負載電流

*2: 利用外部電路形成互鎖,配合 PLC內部程式,確保任何異常突發狀況發生時,均有安全的保護措施。

*3: 在 PLC 的輸出繼電器並沒有內部保護電路,因此若使用在交流電感性負載時,請並聯接上一個突波吸收器 (0.1uF +

“100ohm to 120ohm”) 可減少交流負載上的雜訊,可增加接點壽命。

空端子 • 請勿配線

緊急停止

保險絲

互斥輸出*1

直流電源供應

白熾燈(電阻性負載)

反向電流保護二極體*2

電感性負載

實用之電晶體輸出回路配線:

MC2MC1

C0 C1Y0 Y4C2 Y2 Y3 Y5Y1

5 7 8

1

6

64

MC2 MC1

2

3

3

9

9 電阻性負載

*1: 利用外部電路形成互鎖,配合 PLC內部程式,確保任何異常突發狀況發生時,均有安全的保護措施。

*2: 在 PLC內部使用濟納二極體 (39V) 來保護電晶體輸出,若驅動電感性負載時,建議並聯接上一個反向電流保護二極體。

注意事項 请在使用之前,详细阅读本使用说明书。

本机为开放型 (OPEN TYPE) 机壳,因此使用者使用本机时,必须将之安装于具防尘、防潮及免于电击/冲击意外之外壳配线箱内。另必须具备保护措施 (如: 特殊之工具或钥匙才可打开) 防止非维护人员操作或意外冲击本体,造成危险及损坏。

交流输入电源不可连接于直流类型之输入/出信号端,否则可能造成严重的损坏,因此请在上电之前再次确认电源配线。请勿在上电时触摸任何端子。

產品簡介 谢谢您采用台达 DVP-EH可编程序控器。EH 8 ~ 48点扩展,含主机最大数字输入/输出扩展分别可达 256点。

产品外观及各部介绍 1

3

4

3

55 2 7

7

21

55

3

3

4

7

7

尺寸 (mm) 机种名称 长 宽 高

DVP08HM11N 90 40 82

DVP16HM11N 90 55 82

DVP08HN11R/T 90 40 82

DVP16HP11R/T 90 55 82

3

4

26

6 67

733

8 91

10

11

尺寸 (mm) 机种名称 长 宽 (w) 高

DVP32HN00R/T 90 143.5 82.2

DVP32HP00R/T 90 143.5 82.2

DVP48HP00R/T 90 174 82.2

1. 电源、低电压指示灯 5. 扩充排线 9. 上盖

2. 输出/入端子 6. 扩充机连接口上盖 10. 输入指示灯

3. DIN轨固定扣 7. 直接固定孔 11. 输出灯示灯

4. DIN轨固定槽 8. 机种名称

机种型号 输入单元 输出单元 机种 电源 点数 形式 点数 形式

DVP08HM11N 8 0

DVP16HM11N 16 0 无

DVP08HN11R 0 8

DVP08HP11R 4 4

DVP16HP11R 8 8

继电器 Relay 250V AC /30V DC 2A/1 点

DVP08HN11T 0 8

DVP08HP11T 4 4

DVP16HP11T

24V DC

8

DC Type

Sink/Source

8

晶体管 Transistor 5 ~ 30V DC 0.3A/1 点@40°C

简体中文

输入单元 输出单元 机种 电源 点数 形式 点数 形式

DVP32HN00R 0 32

DVP32HP00R 16 16

DVP48HP00R 24 24

继电器 Relay250V AC /30V DC 2A/1 点

DVP32HN00T 0 32

DVP32HP00T 16 16

DVP48HP00T

100 ~ 240V AC

24

DC Type

Sink/Source

24

晶体管 Transistor 5~30V DC 0.3A/1 点@40°C

規格

电气规格 机种 项目 08HM11N

16HM11N 08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T 32HP00R/T 48HP00R/T 电源电压 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ 20%)

100 ~ 240V AC (-15% ~ 10%), 50/60Hz

± 5% 消耗电力 1W/1.5W 1.5W 1.5W 2W 30VA 30VA 30VA

24V DC 供应电流 NA NA NA NA NA 500mA 500mA

24V DC 输出具短路保护 DC24V 输出具短路保护 突波电压耐受量 1,500V AC(Primary-secondary), 1,500V AC(Primary-PE), 500V AC(Secondary-PE) 绝缘阻抗 5 MΩ以上 (所有输出/入点对地之间 500V DC) 噪声免疫力

ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog &

Communication I/O: 250V, Digital I/O: 1KV, RS: 26MHz~1GHz, 10V/m 接地 接地配线之线径不得小于电源端 L, N 之线径(多台 PLC 同时使用时,请务必单点接地) 操作/储存环境 操作:0°C ~ 55°C(温度), 50 ~ 95%(湿度), 污染等级 2; 储存:-25°C ~ 70°C(温度), 5 ~ 95%(湿度) 耐振动/冲击 国际标准规范 IEC61131-2, IEC 68-2-6(TEST Fc)/IEC61131-2 & IEC 68-2-27(TEST Ea) 重量(约)(g) 124/160 130/120 136/116 225/210 660/590 438/398 616/576 认证

输入/出点规格 输入点电气规格 输入点形式 直流 输入形式 直流(SINK 或 SOURCE) 输入电压电流 24V DC 5mA

Off → On 16.5V DC 以上 动作位准 On → Off 8V DC 以下 反应时间 约 20ms 电路隔离/操作指示 光耦合器/LED On

输出点电气规格 输出点形式 继电器-R 晶体管-T 电流规格 1.5A/1 点(5A/COM) 55°C 0.1A/1 点、50°C 0.15A/1 点、

45°C 0.2A/1 点、40°C 0.3A/1 点(2A/COM) 电压规格 250V AC,30V DC 以下 30V DC

75VA(电感性) 最大负载 90W(电阻性)

9W 反应时间 约 10 ms Off → On 15us On → Off 25us

安裝及配線

数字 I/O 扩展机之端子配置图 08HM

DVP-08HM (8in)

X0 X2 X4 X6X1 X3 X5 X7S/S

08HN DVP-08HN (8out)

Y0 Y1 Y3 Y4 Y5 Y7

C0 Y2 C1 Y6

08HP DVP-08HP (4in/4out)

X 0 Y1 Y 3

C0 Y2

Y0X 2

S /S X 1 X3

16HM DVP-16HM (16in)

X10 X 11

S /S X1 X 3

S/S X12 X13 X 14 X15 X16 X 17

X 0 X2 X4 X5 X7X6

16HP DVP-16HP (8in/8out)

X4 X5

X 1 X3

S /S X6 X7

Y3

Y4 Y5 Y 6

X0 X 2 C 0 Y 0 Y2Y 1

Y 7

32HN

X15

X14C3

Y12

Y11

Y10

Y7

Y6

C2

Y5

Y4

Y3

C1

Y2

Y1

Y16

Y20

Y21 Y22 Y23

Y24 C7C6C5C4

Y25

Y30

Y31

Y35

Y36Y34Y32Y27Y26

C0

DVP-32HN(32out)

(AC Power IN)

Y33 Y37

32HP

X17X16

X15X14

X13X12

X11X10

X7X6

X5X4

X3X2

X1X0

Y0 Y1Y2

Y3 Y4 Y5

Y6 C3C2C1C0Y7

Y12Y13

Y16Y17Y15Y14Y11Y10

S/S

DVP-32HP(16in/16out)

(AC Power IN,DC Signal IN)

48HP

X17X16

X15X14

X13X12

X11X10

X7X6

X5X4

X3X2

X1X0

Y0 Y1Y2

Y3 Y4 Y5Y6 C3C2C1C0

Y7Y12

Y13Y16

Y17Y15Y14Y11Y10

S/SX27

X26X25

X24X23

X22

X21X20

C4 Y21Y22

Y27Y23Y26Y24Y20

Y25

DVP-48HP(24in/24out)

(AC Power IN,DC Signal IN)

盘内安装及配线 DIN 铝轨之安装方法: 适合 35mm之 DIN铝轨,主机欲挂于铝轨时,先将 PLC下方之固定塑料片压入,再将 PLC由上方挂上再往下压即可。欲取下 PLC时,PLC底部下之固定塑料片,以起子插入凹槽,向上撑开即可,该固定机构塑料片为保持型,当所有的固定片撑开后,再将 PLC往上外方取出,如右图所示: 直接锁镙丝方式:请依产品外型尺寸并使用M4镙丝。

PLC在安装时,请装配于封闭式之控制箱内,其周围应保持一定之空间(如下图所示),以确保 PLC散热功能正常。

D VP MPU50m m以上50m m以上 50m m以上

50m m以上 配线:

6.2 以下M3.5 使用

6.2 以下

1. 出/入配线端请使用 O型或 Y型端子,端子规格如左所示。PLC端子镙丝扭力为 5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs)。只能使用 60/75°C的铜导线。

2. 空端子 • 请勿配线。输入点信号线与输出点等动力线请勿置于同一线糟内。 3. 锁镙丝及配线时请避免微小的金属导体掉入 PLC内部,并在配线完成后,将位于 PLC上方散热孔位置的防异物掉入之贴纸撕去,以保持散热良好。

4. PLC与其它之控制组件应保持 50mm以上之间隔,并应远离高压线及动力设备。 使用环境:

1. 请勿将 PLC装置于落尘大、油烟、金属性粉尘及腐蚀性或可燃性气体的环境当中。

2. 请勿将 PLC装置于高温、结露之环境,勿将 PLC装置有直接振动及冲击的场所。

3. 输入点信号线与输出点等动力线请勿置于同一线糟内或使用同一多芯之电缆线。

输出入点序号排列 使用 32点点数以下的主机连接扩展,所连接的第一台扩展,输入点编号由 X20依序排列,输出点编号亦由 Y20开始依序排列,使用 32点点数以上的主机连接扩展,所连接的第一台扩展,输入点编号以主机最后编号依序排列,输出点编号亦由主机最后编号依序排列,若使用者所连接的系统如下:

MPU EXT1 EXT2 EXT3 EXT4

PLC 机种 输入点数 输出点数 输入点编号 输出点编号

MPU 16EH/32EH/64EH 8/16/32 8/16/32 X0~X7/X0~X17/X0~X37 Y0~Y7/Y0~Y17/Y0~Y37

EXT1 32HP 16 16 X20~X37 / X20~X37/X40~X57 Y20~Y37/Y20~Y37/Y40~Y57

EXT2 48HP 24 24 X40~X67/X40~X67/X60~X107 Y40~Y67/Y40~Y67/Y60~Y107

EXT3 08HP 4 4 X70~X73/X70~X73/X110~X113 Y70~Y73/Y70~Y73/Y110~Y113

EXT4 08HN 0 8 - Y74~Y103/Y74~Y103/Y114~Y123 系统组合范例中,第 1台MPU主机输入点数 16点以下会被视为 16点输入,序号较高的几个输入点则没有对应实际的输入点,主机输出点数 16点以下会被视为 16点输出,序号较高的几个输出点则没有对应实际的输出点。扩展输出入点编号则依照主机最后编号依序排列。

电源端配线及规格 DVP-EH系列 PLC电源输入为交流输入,在使用上应注意下列事项: 1. 交流电源输入电压,范围宽广(100V AC ~ 240V AC),电源请接于 L,N两端,如果将 110V AC或 220V AC接至

+24V端或输入点端,将使 PLC损坏,请使用者特别注意。 2. 主机及 I/O扩展机之交流电源输入请同时作 On或 Off的动作。 3. 主机之接地端使用 1.6mm以上之电线接地。

4. 当停电时间低于 10ms时,PLC不受影响继续运行,当停电时间过长或电源电压下降将使 PLC停止运行,输出 全部 Off, 当电源恢复正常时,PLC亦自动回复运行。( PLC内部具有停电保持的辅助继电器及缓存器,使用者在作程序设计规划时应特别注意使用) 交流电源 输入型式

L N 2.0 A

DC/DC +5V +24V 24G S/S X0 X1 X2 100~240VAC

+24V电源供应输出端,最大为 0.5A,请勿将其它的外部电源连接至此端子。每个输入点驱动必须 6 ~ 7mA,若以 16点输入计算,大约需 100mA,因此+24V输出给外部负载不可大于 400mA。 由于 PLC控制许多装置,任一装置的动作可能都会影响其它装置的动作,因此任一装置的故障都可能会造成整个自动控制系统失控,甚至造成危险。所以在电源端输入回路,建议配置如下的保护回路:

交流电源负载

电源回路保护用保险丝 (3A)

电源指示灯

紧急停止:为预防突发状况发生,设置一紧急停止按钮,可在状况发生时,切断系统电源。

系统回路隔离装置:使用电磁接触器、继电器等开关作为系统电源回路隔离装置,可防止电源断续供应时,造成系统的不稳定。 DVP PLC本体

第三种接地,接地阻抗 100Ω以下

OV24VDC

MCMC

NL

1

1

2

3

4

5

66

78

Guard

Lim it

电源供应: 交流 (AC): 100 ~ 240V AC, 50/60Hz 直流 (DC): 24V DC

输入/出点之配线 输入点之配线 输入点之入力信号为直流电源 DC输入,DC型式共有两种接法:SINK及 SOURCE,其定义如下:

Sink = 电流流入共享端 S/S Source = 电流流出共享端 S/S

S/S

X0

Sinking

S/S

X0

Sourcing 输 入 点 回 路 等 效 电 路 配 线 回 路 直流形式

(DC Signal IN)

SINK 模式

+24V

24G

S/S

X0

24VDC

SINK

+5 V

+24V 24G

Sink Type

X1 X2S/S X0

输 入 点 回 路 等 效 电 路 配 线 回 路 直流形式

(DC Signal IN)

SOURCE 模式

+24V

24G

S/S

X0

24VDC

SOURCE

+5V

+24V 24G

Source Type

X1 X2S/S X0

输出点之配线

空端子 • 请勿配线

保险丝

反向电流保护二极管*1

互斥输出*2

紧急停止:使用外部开关

突波吸收器*3

电感性负载

白炽灯(电阻性负载)

9 直流电源供给

实用之继电器输出回路配线

MC2MC19

10

C0 C1Y0 Y4C2 Y2 Y3 Y5Y1

5 2

3 7

8

1

6

7

2

5 4

MC2 MC1

交流电源供给

*1: 在 PLC的输出继电器并没有内部保护电路,因此若使用在直流电感性负载时,请并联接上一个反向电流保护二极管,可增加接点寿命。反向电流保护二极管须符合下列规格: 1. 此二极管必须能承受最大 5 ~ 10+ 倍的负载电压 2. 此二极管正向电流须大于负载电流

*2: 利用外部电路形成互锁,配合 PLC内部程序,确保任何异常突发状况发生时,均有安全的保护措施。 *3: 在 PLC的输出继电器并没有内部保护电路,因此若使用在交流电感性负载时,请并联接上一个突波吸收器 (0.1uF +

“100ohm to 120ohm”) 可减少交流负载上的噪声,可增加接点寿命。

*1: 利用外部电路形成互锁,配合 PLC内部程序,确保任何异常突发状况发生时,均有安全的保护措施。 *2: 在 PLC内部使用济纳二极管 (39V) 来保护晶体管输出,若驱动电感性负载时,建议并联接上一个反向电流保护二极管。

空端子 • 请勿配线

紧急停止

保险丝

互斥输出*1

直流电源供应

白炽灯(电阻性负载)

反向电流保护二极管*2

电感性负载

实用之晶体管输出回路配线

MC2MC1

C0 C1Y0 Y4C2 Y2 Y3 Y5Y1

5 7 8

1

6

64

MC2 MC1

2

3

3

9

9 电阻性负载