1 YATES TANK INSPECTION SERVICES P.O. Box 505 PRINCETON, KY. 42445 (270) 625-4898 CELL 2019 VISUAL INSPECTION REPORT 200,000 GALLON ELEVATED STORAGE LOCATED AT DOWNTOWN TANK SITE WAS INSPECTED FOR CITY OF ALGOOD UTILITY DISTRICT ON TUESDAY JUNE 11, 2019

Upload: others

Post on 13-Mar-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

1

YATES TANK INSPECTION SERVICES P.O. Box 505

PRINCETON, KY. 42445

(270) 625-4898 CELL

2019 VISUAL INSPECTION REPORT

200,000 GALLON ELEVATED STORAGE

LOCATED AT DOWNTOWN TANK SITE

WAS INSPECTED FOR

CITY OF ALGOOD UTILITY DISTRICT

ON TUESDAY JUNE 11, 2019

2

YATES TANK INSPECTION

P.O. Box 505 Princeton, KY. 42445 PH. (270)625-4898 FX. (270)365-2123

INTRODUCTION:

WE ARE AN EVALUATION FIRM THAT SPECIALIZES IN PROFESSIONAL

UNDERWATER TANK INSPECTIONS.

WE PERFORMED VISUAL TANK INSPECTED ON 06-11-2019 IN A CLEAN AND

SANITARY MANNER.

WE HAVE PROVIDED A COMPLETE AND DETAILED REPORT OF THE

FOLLOWING SANITARY CONDITIONS, STRUCTURAL INTEGRITY,

FOUNDATION, COATING AND SURFACE CONDITIONS, SAFETY AND SECURITY

REQUIREMENTS ACCORDING TO THE FOLLOWING AGENCIES.

• (AWWA) AMERICAN WATER WORKS ASSOCIATION

• (ANSI) AMERICAN NATIONAL STANDARDS INSTITUTE

• (OSHA) OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

• (EPA) ENVIRO PROTECTION AGENCIES

• (NSF) NATIONAL SANITATION FOUNDATION

• (NFPA) NATIONAL FIRE PROTECTION ASSOCIATION

• (NACE) NATIONAL ASSOCIATION OF CORROSION ENGINEERS

• (SSPC) STEEL STRUCTURES PAINTING COUNCIL

• FACTORY MUTUAL

• STATE AND FEDERAL STANDARDS

THE REPORT REPRESENTS THE OPINIONS OF YATES TANK INSPECTION.

BECAUSE WE REMAIN INDEPENDENT OF PAINTING AND FABRICATION YOU

CAN BE ASSURED OF AN UNBIASED INSPECTION. WHILE EVERY PRECAUTION

WAS TAKEN TO INSURE THAT ALL INFORMATION GATHERED AND

PRESENTED IS ACCURATE, COMPLETE AND TECHNICALLY CORRECT, IT IS

BASED ON THE INFORMATION, DATA, TIME, MATERIAL, ETC. SUPPLIED TO US

DURING THE INSPECTION.

3

YATES TANK INSPECTION

TECHNICAL SPECIFICATIONS:

INSPECTOR’S NAME: DARRIN YATES

UTILITY: CITY OF ALGOOD

OWNER’S REPRESENTATIVE:

MATTHEW R. TUCKER

TITLE: ENGINEER

FIRM: JAMES C. HAILEY & CO.

ADDRESS: 1619 GALLERIA

BRENTWOOD, TN. 37027

OFFICE: (615) 883-4933

CELL: (731) 697-3290

LOCATION OF TANK:

310 W. MAIN ST. COOKEVILLE, TN. 38506

IS TANK BELOW THE NORMAL DAILY MINIMUM 30 DEGREE ISOTHERMAL

LINE: NO

RECOMMENDED DEPTH OF SOIL COVERING OVER A WATER PIPE FOR THIS

LOCATION: 36 INCHES

TANK HAS HYDRANT TO FLUSH OR DRAIN THE STORAGE FACILITY WHILE IT

IS ISOLATED FROM THE SYSTEM. YES

4

TANK SPECIFICATIONS:

TYPE OF TANK:

GROUND __STANDPIPE X MULTI-LEGGED SINGLE PEDESTAL HYDRO PILLAR

__SINGLE PEDESTAL COMPOSITE __ PRE-STRESSED CONCRETE GROUND

TYPE OF MATERIAL:

X STEEL __CONCRETE __GLASS COATING __STAINLESS __OTHER

X WELDED __BOLTED __RIVETED

TANK MEASUREMENTS:

TANK MEASURES APPROXIMATELY 132’ +OR - IN HEIGHT

HEIGHT OF THE AREA ABOVE OVERFLOW TO VENT IS 6’-0”

TANK CAPACITY IS 200,000 GALLONS

TANK HIGH WATER LEVEL IS 126’-0” IN HEIGHT

TANK LOW WATER LEVEL IS 100’-0” (THE HEIGHT OF RISER PIPE)

TANK IS USED FOR:

__FIRE PROTECTION X POTABLE __WASTE __PROCESSING __WAX __FLOUR

__GRAIN __PLASTIC __CHEMICAL __FUEL __GAS __OIL

ORIGINAL MANUFACTURER: BROWN STEEL CONTR’S, INC.

YEAR BUILT: 1962 S/N: NOT ON TAG

TYPE OF FOUNDATION:

X CONCRETE __CONCRETE SLAB __BUILT WITHIN RING WALL

SUPPORTED ON GRAVEL BERMS __ON GRAVEL WITH STEEL RINGS

CONCRETE PIERS __CONCRETE CRADLES __STEEL CRADLES

TYPE OF ROOF:

X SELF SUPPORTED __SUPPORTED ROOF

X DOME __ELLIPSOIDAL __CONE __FLAT __KNUCKLE __CONE

IF ELEVATED WHAT TYPE OF COLUMNS: ROUND HOW MANY COLUMNS: 06

OVERALL HEIGHT OF BOWL AREA: 32’-0” DIAMETER: 39’-0”

OVERALL HEIGHT OF RISER: 100’-0” DIAMETER OF RISER: 48”

5

SECURITY AND SAFETY:

DOES TANK SITE HAVE “NO TRESPASSING” SIGNS POSTED? YES

TANK IS LOCATED AT 310 W. MAIN ST.

DOES TANK SITE HAVE A FENCE COMPLETELY AROUND IT? YES

IF YES, DOES IT APPEAR TO BE IN GOOD CONDITION? YES

DOES EXTERIOR LADDER HAVE A GUARD TO PREVENT ENTRY? NO

WERE ALL GATES, GUARDS, AND HATCHES LOCKED AT THIS TIME? YES

WAS THERE EVIDENCE OF VANDALISM AT TANK SITE? NO

ELECTRICAL:

DOES TANK HAVE LIGHTNING PROTECTION? NO

DOES TANK SITE HAVE ELECTRICAL OUTLETS? NO

DOES TANK HAVE ANTENNAS, WIRING OR OTHER OBSTRUCTIONS IN THE PATH

OF THE LADDER? YES

6

CONDITION OF FOUNDATION:

THE FOLLOWING ARE AWWA 12.6.1 AND 12.9 REQUIREMENTS

DOES AREA SURROUNDING FOUNDATION HAVE POSITIVE DRAINAGE? YES

DOES FOUNDATION HAVE ANY INDICATIONS OF SETTLING? NO

IS THERE INDICATION OF EROSION AROUND FOUNDATION DUE TO OVERFLOW

PIPE NOT BEING CONTINUED TO THE GRADE AND OVER A SPLASH-PAD? NO

DOES FOUNDATION EXTEND A MINIMUM OF SIX INCHES ABOVE EXISTING

GRADE AS REQUIRED BY AWWA? NO

IS THERE EVIDENCE OF CHIPPING, CRACKING, OR DETERIORATION IN

FOUNDATION THAT NEEDS TO BE REPAIRED? NO

ARE VOIDS BETWEEN BASE PLATES AND FOUNDATIONS SEALED? NO

7

PHOTOS OF FOUR FOUNDATION PIERS AND THE BASE PLATES

8

THE PIER THAT SUPPORTS THE RISER APPEARS TO BE IN GOOD CONDITION

9

RISER MAN-WAY:

DOES TANK HAVE A MAN-WAY IN THE RISER FOR EMERGENCY CONDITIONS?

YES REQUIRED BY OSHA 1910.36, 1910.37, NFPA-22 SECTION 11.6.2 AND AWWA.

DOES MAN-WAY COVER WEIGH OVER 50 LBS? YES

IS EACH COVER SUPPORTED WITH HINGES OR DAVIT ARM? YES

IS A “CONFINED SPACE” SIGN POSTED AT EACH ENTRY POINT? NO REQUIRED BY OSHA 1910.146 (C) (2).

DOES ANY MAN-WAY SHOW EVIDENCE OF PAST OR PRESENT LEAKS? NO

IS MAN-WAY OPENING A MINIMUM OF 24 INCHES IN DIAMETER? NO

WHAT IS THE DIAMETER OF THE MAN-WAY? 20”

DOES THE MAN-WAY HAVE ANY LEAKS? NO

10

RISER MAN-WAY CONTINUED:

IS MAN-WAY DOOR COVER DESIGNED TO WITHSTAND THE WEIGHT AND

PRESSURE OF TANKS CONTENTS? YES

IS EACH MAN-WAY EQUIPPED WITH BOLTS THAT ARE NON-CORROSIVE OR

PAINTED TO PREVENT METAL LOSS? YES

DO THE THREADS PROTRUDE THROUGH NUTS? YES

DO ALL BOLTS APPEAR TO BE TIGHT? YES

DOES THE FLANGE APPEAR TO BE STRAIGHT? YES

11

RISER PIPE:

DIAMETER OF RISER IS: 48”

HEIGHT OF RISER IS: 100’-0”

WHAT IS THE ULTRASONIC THICKNESS OF RISER PIPE? .235 TO .255

DOES RISER HAVE ANY EVIDENCE OF METAL LOSS? YES

IS THE RISER PIPE STRAIGHT? YES

ARE THERE SIGNS OF LEAKS IN THE RISER PIPE? NO

RISER HAS HOW MANY ANCHOR BOLTS: FOUR

ARE THERE ANY DENTS OR BULGES IN SURFACE OF RISER PIPE? NO

12

WATER LEVEL GAUGE: THE FOLLOWING ARE NFPA 22, SECTION 11-1. 11 REQUIREMENTS

TANK HAS A WATER LEVEL GAUGE THAT READS IN FEET

DOES GAUGE APPEAR TO BE ACCURATE? NO

CONDITION GAUGE APPEARS TO BE IN: NO LONGER WORKING

TYPE OF GAUGE: FLOAT CABLE TYPE

13

WATER LEVEL GAUGE CONTINUED:

WAS THE FLOAT BUILT WITH NON-CORROSIVE MATERIAL TO PREVENT METAL

LOSS? NO, HAS SUFFERED METAL LOSS AND HAS SUNK

ARE THE CABLES ATTACHED TO THE FLOAT NON-CORROSIVE? NO

ARE ALL HARDWARE AND CABLE CLAMPS USED ON INTERIOR MADE OF NON-

CORROSIVE MATERIAL? NO

IF EQUIPPED WITH PULLEYS DO THEY MOVE FREELY TO ALLOW GAUGE TO

READ ACCURATELY? NO IS TRACK FOR GAUGE SEALED TO PREVENT ENTRY OF DUST, INSECTS, ETC.? NO,

AS SEEN IN PHOTO BELOW

14

OVERFLOW PIPE:

THE FOLLOWING ARE AWWA, NFPA, AND STATE DIVISION OF WATER REQUIREMENTS.

IS OVERFLOW SECURED TO EXTERIOR EVERY 10 FEET? YES

IS THE TOP OF OVERFLOW DESIGNED TO PREVENT WHIRLPOOLING? YES

IS THERE ANY EVIDENCE OF LEAKS IN THE OVERFLOW? NO

IS INTERIOR PART OF OVERFLOW CONSTRUCTED OF NON-CORROSIVE MATERIAL

OR PAINTED TO PREVENT METAL LOSS? NO

IF COATING IS DAMAGED HAS METAL LOSS OCCURRED? YES

IF EQUIPPED WITH FLANGES ON THE INTERIOR IS THE HARDWARE

CONSTRUCTED OF NON-CORROSIVE MATERIAL? N/A

ARE THE STAND OFF BRACKETS THAT SECURE OVERFLOW TO SHELL

CONSTRUCTED OF NON-CORROSIVE MATERIAL OR PAINTED? YES

15

OVERFLOW PIPE CONTINUED:

STATE DIAMETER OF OVERFLOW PIPE: 4 INCHES

DOES PIPE APPEAR TO BE SIZED TO CARRY MORE THAN THE LARGEST FILLING

RATE? NO

DOES TANK HAVE AN OVERFLOW PIPE THAT DISCHARGES AT AN ELEVATION NO

HIGHER THAN 24 INCHES ABOVE THE GRADE? NO

IS OVERFLOW EQUIPPED WITH AN EPA APPROVED FLAPPER VALVE? NO

DOES THE FLAPPER MOVE FREELY TO PREVENT A BLOCKAGE? N/A

IS THE FLAPPER DESIGNED TO CLOSE WHEN NOT IN USE? N/A

IS OVERFLOW EQUIPPED WITH A SPLASH-PAD? NO

WHAT TYPE OF MATERIAL WAS USED TO CONSTRUCT SPLASH PAD? N/A

IS THERE ANY EVIDENCE OF EROSION AROUND OVERFLOW? NO

16

OVERFLOW PIPE CONTINUED:

IS OVERFLOW EQUIPPED WITH A NON-CORROSIVE MESH SCREEN? YES

WHAT IS THE CONDITION OF SCREEN? FAIR

DOES IT APPEAR THAT SCREEN CAN WITHSTAND THE FORCE OF WATER WHEN

TANK IS OVERFLOWING? YES

IS THE PIPE DESIGNED WITH A BOLT ON FLANGE TO SECURE SCREEN TO

PREVENT IT FROM COMING LOOSE? YES

DOES IT APPEAR THAT ALL BOLTS IN THE FLANGE ARE TIGHT? YES

17

EXTERIOR LADDER: THE FOLLOWING ARE AWWA, NFPA & OSHA 29 CFR 1910 REQUIREMENTS.

DOES TANK HAVE A LADDER TO GAIN ACCESS BEGINNING AT 8 FEET (OR AS

SPECIFIED) FROM GROUND THAT EXTENDS TO THE ROOF TO BE ABLE TO

MAINTAIN TANK? YES

IS LADDER SECURED TO STRUCTURE EVERY 10 FEET? YES

DOES LADDER HAVE A FALL PREVENTION DEVICE THAT ATTACHES HARNESSES

ONTO THE LADDER? NO

WHAT TYPE OF FALL PREVENTION DEVICE? NONE

EXPLAIN CONDITION: N/A

18

EXTERIOR LADDERS CONTINUED:

WHAT IS THE WIDTH AND HEIGHT OF LADDER? 16” X 90’

IS THE DIAMETER OF EACH LADDER RUNG MORE THAN ¾ OF AN INCH? YES

ARE LADDER RUNGS COMPLETELY WELDED TO SIDE RAILS? YES

ARE THE LADDER RUNGS 12” APART TO ALLOW FOR SAFE PASSAGE? YES

DOES THE LADDER HAVE A MINIMUM OF 8” BETWEEN BOTH SHELL AND LADDER

TO ALLOW CLEARANCE FOR FEET WHEN CLIMBING? YES

ARE STAND OFF BRACKETS SECURED TO BOTH LADDER AND SHELL? YES

19

ARE THE WING PLATES COMPLETELY WELDED TO THE SUPPORT

COLUMNS? YES

ARE THE STRUTS COMPLETELY WELDED TO THE WING PLATES TO

PREVENT SEPARATION WHERE THEY CONNECT? NO

WERE THERE ANY SIGNS OF SEPARATION BETWEEN PLATES AND

STRUTS? NO

ARE THERE ANY SIGNS OF METAL LOSS IN THIS AREA? NO

WERE THERE ANY WING PLATES BENT? NO

EXPLAIN CONDITION OF WING PLATES AND STRUTS: GOOD

20

ARE ALL CONNECTION POINTS PAINTED? YES

DOES IT APPEAR THAT ALL PINS IN TURNBUCKLE ARE TIGHT AND

NOT MISSING ANY HARDWARE? YES

ARE THE TURNBUCKLES STRAIGHT? YES

ARE THEY FREE OF METAL LOSS? YES

WERE ALL BOLTS ON PINS TIGHT AND TACK WELDED TO PREVENT

THEM FROM COMING LOOSE IN HI WINDS OR SEISMIC ACTIVITY? NO

21

HOW MANY WIND-AGE RODS? 36

HOW MANY RISER RODS? 12

WERE THE COLUMNS STRAIGHT? YES

WERE THERE ANY SIGNS OF DENTS OR CRACKS IN THE COLUMNS?

NO

DO ALL RODS APPEAR TO BE IN GOOD ADJUSTMENT? YES

WERE THERE ANY SIGNS OF BENDS IN THE WIND-AGE RODS? NO

WERE THERE ANY SIGNS OF DAMAGES IN THE UNDER STRUCTURE?

NO

22

HANDRAIL AND BALCONIES: THE FOLLOWING ARE OSHA 1926.501, 1910.23, AWWA AND NFPA 22 SECTION 10-7 REQUIREMENTS.

DOES THE CATWALK HAVE HANDRAIL FOR FALL PROTECTION? YES

DOES THE HANDRAIL HAVE A FOUR INCH TOE PLATE? YES

DOES THE HANDRAIL HAVE A MID RAIL? YES

IS COATING ON FLOOR OF CATWALK PROTECTING THE SURFACE? YES

DOES THE CATWALK HAVE DRAIN HOLES IN THE FLOOR? YES

IS WATER PONDING ON CATWALK FLOOR? NO

23

HANDRAIL CONTINUED:

IS LADDER OPENING GUARDED BY AN OSHA APPROVED SAFETY GATE FOR FALL

PROTECTION? NO

IS PATH OF CATWALK FREE OF OBSTRUCTIONS? NO

WHAT TYPE OF MATERIAL IS THE HANDRAIL CONSTRUCTED OF? STEEL

STATE HEIGHT OF HANDRAIL: 36 INCHES

IS THE CATWALK FULLY WELDED TO SHELL OF TANK? YES

24

EXTERIOR ROOF LADDER:

DOES ROOF LADDER HAVE A FALL PREVENTION DEVICE THAT ATTACHES

HARNESSES ONTO THE LADDER? NO

IF YES, WHAT IS ITS’ CONDITION? N/A

WHAT TYPE OF FALL PREVENTION DEVICE DOES LADDER HAVE? N/A

IS LADDER WELDED EVERY 10 FEET? NO

DOES ROOF LADDER APPEAR TO BE IN GOOD CONDITION? YES

IS LADDER AN OSHA APPROVED DESIGN? YES

IS PATH OF LADDER FREE OF OBSTRUCTIONS? NO, IT’S BLOCKED BY WIRING

FOR CELL SERVICES.

25

PATH OF ROOF LADDER IS BLOCKED MAKING CLIMBING DANGEROUS

26

EXTERIOR ROOF SURFACE:

IS ALGAE GROWING ON ROOF? VERY LITTLE

IS ROOF SLOPED TO WHERE THERE IS NO DRAINAGE PROBLEM? YES

DOES ROOF HAVE BULGES OR DENTS THAT MAY HAVE BEEN CAUSED BY VENT

OR OVERFLOW PIPE BEING BLOCKED DURING DAILY OPERATION? NO

ROOF IS CONSTRUCTED OF: STEEL

IS ROOF SEALED TO PREVENT ENTRY OF DUST, INSECTS, ETC.? NO

DOES ROOF SHOW SIGNS OF DETERIORATION IN THE STEEL? NO

IF ROOF IS WELDED ON EXTERIOR ARE WELDS IN GOOD CONDITION? YES

DO WELD SEAMS SHOW EVIDENCE OF LEAKS? NO

27

SANITARY CONDITIONS:

STORAGE RESERVOIRS, BOTH POTABLE AND FIRE PROTECTION, ARE DESIGNED TO BE WATER TIGHT TO

PREVENT LEAKAGE AND THE ENTRY OF DUST, SAND, INSECTS, BIRDS, BATS AND ANIMALS THAT MAY

CAUSE WATER BORN DISEASE OR CAN CAUSE BLOCKAGES IN FIRE PROTECTION SYSTEMS. REQUIRED BY

AWWA, NFPA, STATE DIVISION OF WATER AND DEPT. OF NATURAL RESOURCES.

ROOF VENT:

DOES TANK APPEAR TO HAVE ADEQUATE VENTILATION? NO

DOES VENT HAVE A SHIELD OVER ITS’ TOP AND SIDES TO PROTECT AGAINST

BIRD DROPPINGS, DUST, RAIN, ICE, ETC.? YES

IS VENT EQUIPPED WITH A #24 NON-CORRODING MESH SCREEN? YES

IS ROOF VENT WATERTIGHT TO PREVENT CONTAMINATES SUCH AS BIRD

DROPPINGS AND DIRT FROM WASHING INTO THE FACILITY BY RAIN? YES

DOES TANK HAVE A SECONDARY CENTER ROOF OPENING USED AS A MAN-WAY

AND TO SECURE VENTILATION FANS DURING PAINTING PROJECTS? NO

28

ROOF VENT CONTINUED:

DUE TO GEOGRAPHIC LOCATION IS VENT REQUIRED TO BE SHIELDED TO

PREVENT FREEZING RAIN FROM STOPPING VENTILATION? YES

DUE TO GEOGRAPHIC LOCATION DOES IT APPEAR THAT THE VENT EXTENDS

ABOVE NORMAL SNOW LEVEL WHICH COULD BLOCK VENTILATION? YES

DOES IT APPEAR THAT THE ROOF IS SLOPED ENOUGH TO PREVENT MELTING

SNOW FROM ENTERING THROUGH THE VENT? YES

IF VENT IS ALSO USED AS A MAN-WAY WAS ANY HARDWARE MISSING? NO

DOES IT APPEAR THAT ALL HARDWARE IS TIGHT? YES

WERE THERE ANY VOIDS IN OR AROUND VENT SCREEN THAT MAY ALLOW

BIRDS TO ROOST? NO

IF VENT IS BOLTED TO THE ROOF WAS A GASKET USED BETWEEN THE FLANGES

TO COMPLETELY SEAL THE CONNECTION? YES

29

ROOF HATCHES AND MAN-WAYS: THE FOLLOWING ARE AWWA, NFPA-22 SECTION 3-7 AND OSHA 1910.36 AND 37 REQUIREMENTS.

HOW MANY ROOF MAN-WAYS DOES TANK HAVE? ONE

ARE THE ROOF OPENING FRAMES CURBED 4 INCHES UPWARD AND DO THEY

HAVE 2 INCH OVERLAPPING COVERS TO PREVENT PRECIPITATION ON THE

ROOF’S SURFACE FROM DRAINING INTO THE FACILITY? YES

ARE ROOF OPENINGS A MINIMUM OF 24 INCHES IN DIAMETER? YES

DOES EACH ROOF OPENING HAVE A LOCK TO PREVENT ENTRY? YES

DOES EACH ROOF OPENING HAVE A “CONFINED SPACE” SIGN POSTED AT EACH

MAN-WAY AS REQUIRED BY OSHA 1910.146 (C) (2)? NO

30

ROOF MAN-WAYS CONTINUED:

IS EACH MAN-WAY EQUIPPED WITH BOLTS THAT ARE NON-CORROSIVE OR

PAINTED TO PREVENT METAL LOSS? N/A

IS EACH MAN-WAY EQUIPPED WITH HINGES TO SUPPORT COVER? YES

DO ALL BOLTS APPEAR TO BE TIGHT? N/A

DOES THE COVER APPEAR TO BE STRAIGHT? YES

ARE MAN-WAYS CIRCULAR OR RECTANGLE DESIGN? SQUARE

STATE THE DIAMETER OF MAN-WAY OPENING: 24”

IS THE ROOF HATCH EQUIPPED WITH A HANDLE? YES

IS ROOF OPENING GUARDED WITH FALL PROTECTION? NO

31

INTERIOR COATING:

THE INTERIOR WAS LAST PAINTED: 1962

LIFE OF COATING APPEARS TO BE: INTERIOR HAS SUFFERED METAL LOSS

DRY FILM THICKNESS OF COATING IS: 0 TO 10 MILS

COLOR IS: UNKNOWN AND HAS A FOOD WAX OVER IT

STATE COATING CONDITIONS: POOR, NEEDS TO BE REPLACED

INTERIOR COATING CONDITIONS OF STRUCTURE:

ROOF AND SHELL ABOVE WATER LEVEL: POOR

BELOW WATER: POOR

FLOOR: POOR

WAX WILL NEED TO BE REMOVED BEFORE SANDBLASTING.

32

INTERIOR SURFACE:

IS THERE EVIDENCE OF METAL LOSS SUCH AS PITS OR RUST TUBERCLES? YES

TANK IS CONSTRUCTED OF: STEEL

IS TANK SEALED TO PREVENT ENTRY OF DUST, INSECTS, ETC.? NO

33

INTERIOR ROOF:

IS INTERIOR ROOF WELDED? YES

IS UNDERSIDE OF ROOF SEAM SEALED? NO

IS TANK EQUIPPED WITH A PAINTERS RING ON SHELL? YES

IS THERE CORROSION ON UNDERSIDE OF ROOF? YES, 75% OF SURFACE

ARE THERE ANY ERECTION CLIPS OR SPIDER RODS ON THE INTERIOR THAT NEED

TO BE REMOVED DUE TO DETERIORATION? YES

ARE THERE ANY SIGNS OF NEW METAL LOSS ON THE INTERIOR ROOF? VERY

LITTLE

34

INTERIOR SURFACE CONTINUED:

DOES INTERIOR SHELL HAVE SIGNS OF CORROSION? YES

ARE THERE SIGNS OF DENTS OR THE FLOOR SAGGING? NO

IS THERE EVIDENCE THAT THE FLOOR MAY BE LEAKING? NO

IF SHELL IS WELDED WHAT IS CONDITION OF WELD SEAMS? FAIR

DOES SHELL HAVE SIGNS OF LEAKS? NO

IS THERE ANY SEDIMENT ON FLOOR? YES

DOES THE TOP OF RISER HAVE A GUARD OVER IT? NO

35

INTERIOR LADDER: THE FOLLOWING ARE AWWA, NFPA & OSHA REQUIREMENTS

DOES TANK HAVE AN INTERIOR LADDER FOR PAINT CONTRACTORS TO

MAINTAIN INTERIOR COATING? IT SHOULD NOT BE USED DUE TO METAL LOSS

HOW IS LADDER SECURED TO INTERIOR? BOLTED

36

SURFACE PREPARATION AND COATING:

ALL PAINT USED ON WATER TANKS MUST BE (ANSI/NSF) CERTIFIED FOR POTABLE WATER. ALL

SURFACES TO BE REFINISHED SHALL BE PREPARED IN ACCORDANCE WITH THE REQUIREMENTS

OF THE STEEL STRUCTURE PAINTING COUNCIL (SSPC). ALL PAINTS SHALL COMPLY WITH (ASTM)

SPECIFICATIONS AND BE DELIVERED IN SEALED CONTAINERS & LABELED BY MANUFACTURER.

EXTERIOR ROOF COATING:

ROOF WAS LAST PAINTED IN: UNKNOWN

COLOR OF TOP COAT: WHITE

DRY FILM THICKNESS OF EXTERIOR COATING IS: 0 TO 8 MILS

EXPLAIN ROOF COATING CONDITIONS: POOR, IS FLAKING OFF

37

EXTERIOR SHELL COATING:

SHELL WAS LAST PAINTED IN: UNKNOWN

COLOR OF TOP COAT: WHITE

DRY FILM THICKNESS OF EXTERIOR COATING IS: 3 TO 9 MILS

EXTERIOR COATING CONDITIONS OF STRUCTURE:

ROOF: POOR, RUSTING WHERE COATING HAS FLAKED OFF

RISER PIPE: POOR, RUSTING WHERE COATING HAS FLAKED OFF

SHELL AND BELLY: POOR, RUSTING WHERE COATING HAS FLAKED OFF

UNDER STRUCTURE: POOR, RUSTING WHERE COATING HAS FLAKED OFF

CATWALK: POOR, RUSTING WHERE COATING HAS FLAKED OFF

38

COATING NEEDS TO BE COMPLETELY REMOVED DUE TO POOR

ADHESION

39

COATING NEEDS TO BE COMPLETELY REMOVED DUE TO POOR

ADHESION

40

EXTERIOR SHELL SURFACE:

DOES TANK HAVE ANY GRAFFITI ON ITS SURFACE? NO

DOES SHELL SHOW SIGNS OF LEAKS? NO

STATE APPROXIMATE AMOUNT OF SEDIMENT: WAX MIXED WITH SEDIMENT

DO INLET AND OUTLET PIPES EXTEND ABOVE SEDIMENT? YES

STATE WATER LEVEL AT TIME OF INSPECTION: 90’- 0”

41

LOGO:

STATE THE CONDITION OF LOGO: HAS FADED

ARE THERE ANY LIGHTS POINTING TOWARDS LOGO? NO

HOW MANY SIDES OF TANK IS LOGO ON? ONE

METHOD USED TO APPLY LETTERING, VINYL LOGO OR COATING? COATING

42

Recommendations:

1) The exterior has surface rust due to coating flaking off. I recommend

sand blasting all to a commercial finish SSPC-SP6 or NACE 3.

43

Recommendations:

2) The 4” overflow pipe is undersized and will not discharge excess water

fast enough to prevent damage to roof. I recommend replacing using a

steel 6” pipe that will continue to ground and over a concrete splash

pad. Also, screen with flapper valve over end of pipe needs to be

installed to prevent insects and animals from entering tank.

44

Recommendations:

3) Do not use interior ladder, it is unsafe due to metal loss. Also, ladder

should have never been installed from center of roof to shell due to not

allowing climber to get on and off safely.

I recommend replacing ladder and installing a 2nd roof man-way above

ladder on shell. Ladder will need to be welded 5’ off shell wall so it will

line up with man-way.

45

Recommendations:

4) The interior coating has failed with wide spread rust and metal loss and

at some point was coated over top of with food wax. Food wax should

not be used on interior of tanks due to not being a long-term method of

repair and very costly to remove. I recommend removing all wax before

sandblasting to a near white finish. (SSPC SP10 or NACE 2)

46

Recommendations:

5) The roof ladder is unsafe due to cell communication wiring being

installed in its climbing path. Also, ladder is not welded every 10’to roof

surface and does not have a safety climb device. I recommend installing

another roof ladder that is OSHA approved and equipped with safety

climb device for fall protection. Leave old ladder for wiring.

47

Recommendations:

6) The ladder that runs between ground and catwalk needs a cable type

safety climb installed for fall protection.

48

Recommendations:

7) The handrail on catwalk is 36” tall and not an OSHA approved

designed. I recommend raising to 42” and installing an OSHA approved

self-closing safety gate over ladder opening.

49

Recommendations:

8) The water level gauge no longer works due to poor design and metal

loss. Also, the track system needs to be replaced due to allowing insects

to enter where it is connected to roof. I recommend installing a complete

cable type gauge using stainless steel hardware and cables. Also, float

needs to be made of non-corrosive material.

50

Recommendations:

9) The man-way on riser pipe at ground level needs to be replaced to due

being under sized. I recommend installing a 24”man-way with

“confined space signs”.

51

Recommendations:

10. Voids between foundations and base plates need to be resealed using

grout.

52

Recommendations:

11. The tank needs a second roof vent installed to allow for positive air

flow.

53

Recommendations:

12. I recommend installing handrail all the way around top of interior

riser pipe for fall protection.