Page 1 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016 ADDENDUM 3.0 November 16, 2016 Project: Liberal Arts Entry & Basement Remodel University of Montana Bid Date: 2:00 pm – Tuesday, November 22, 2016 (A&E Division Offices in Helena) Acknowledgment of receipt of this addendum is required. NOTICE TO BIDDERS: You are hereby notified of the following clarification of, or revisions to, the Bid Documents for the above referenced project. This Addendum is hereby made part of the project requirements and contract documents for “Entry & Basement Remodel” - prepared by Comma-Q Architecture, Inc. and dated October 28, 2016. Be sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record as of the date of this Addendum. It is the responsibility of each Bidder to notify his/her sub-contractors, suppliers, etc., and to verify all items covered by the Contract Documents, including Addenda, as related to their bids, prior to bid submittal. CHANGES TO SPECIFICATIONS: SECTION 00 0110 TABLE OF CONTECTS ITEM 1. ADD section 26 5669 CEILING FANS to the TOC. SECTION 02 8210 CHAIN LINK FENCE ITEM 2. ADD item to Paragraph 2.4 FITTINGS “K. Portable fence base with staking.” ITEM 3. DELETE Paragraph 2.5 CAST-IN-PLACE CONCRETE in its entirety. ITEM 4. DELETE Paragraph 2.6 GROUT AND ANCHORING CEMENT in its entirety. SECTION 05 7373 GLASS RAILING SYSTEMS ITEM 5. ADD item to Paragraph 2.1 MANUFACTURERS “C. Livers Bronze Co.” SECTION 06 2000 FINISH CARPENTRY ITEM 6. REVISE Paragraph 2.2 LUMBER MATERIALS to read: A. Hardwood Lumber: Birch species, Quarter sawn, maximum moisture content of 6 percent, Select & Better grade. Thickness: per drawings. 1. Window sills, in sizes and profiles as shown on drawings. B. Hardwood Lumber: Paint-grade, finger-jointed pine. Thickness: per drawings. 2. Wood Base

Upload: others

Post on 27-Apr-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 1 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

ADDENDUM 3.0 November 16, 2016

Project: Liberal Arts Entry & Basement Remodel University of Montana Bid Date: 2:00 pm – Tuesday, November 22, 2016 (A&E Division Offices in Helena) Acknowledgment of receipt of this addendum is required.

NOTICE TO BIDDERS: You are hereby notified of the following clarification of, or revisions to, the Bid Documents for the above referenced project.

This Addendum is hereby made part of the project requirements and contract documents for “Entry & Basement Remodel” - prepared by Comma-Q Architecture, Inc. and dated October 28, 2016. Be sure to acknowledge this Addendum on your Bid Proposal.

The following information is being issued to all plan holders of record as of the date of this Addendum. It is the responsibility of each Bidder to notify his/her sub-contractors, suppliers, etc., and to verify all items covered by the Contract Documents, including Addenda, as related to their bids, prior to bid submittal.

CHANGES TO SPECIFICATIONS: SECTION 00 0110 – TABLE OF CONTECTS ITEM 1. ADD section 26 5669 CEILING FANS to the TOC.

SECTION 02 8210 – CHAIN LINK FENCE ITEM 2. ADD item to Paragraph 2.4 FITTINGS

“K. Portable fence base with staking.”

ITEM 3. DELETE Paragraph 2.5 CAST-IN-PLACE CONCRETE in its entirety.

ITEM 4. DELETE Paragraph 2.6 GROUT AND ANCHORING CEMENT in its entirety.

SECTION 05 7373 – GLASS RAILING SYSTEMS ITEM 5. ADD item to Paragraph 2.1 MANUFACTURERS

“C. Livers Bronze Co.”

SECTION 06 2000 – FINISH CARPENTRY ITEM 6. REVISE Paragraph 2.2 LUMBER MATERIALS to read:

A. Hardwood Lumber: Birch species, Quarter sawn, maximum moisture content of 6 percent, Select & Better grade. Thickness: per drawings.

1. Window sills, in sizes and profiles as shown on drawings.

B. Hardwood Lumber: Paint-grade, finger-jointed pine. Thickness: per drawings.

2. Wood Base

Page 2: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 2 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

a. Size: 6” along flat surfaces. At stair risers, run parallel at 6” above stair nosings as shown in drawings. b. Profile: Square edge c. Finish: Painted PT-1

SECTION 08 7100 – DOOR HARDWARE ITEM 7. REPLACE AT Paragraph 3.8 DOOR HARDWARE SCHEDULE, B. HARDWARE SETS:

FROM Hardware Group No. 01 PR 6' 0" X 7' 0" X 1 3/4" X HMD X HMF X RATED For use on door #(s): 200A EACH TO HAVE: Qty Description Catalog Number FIN Mfr 6 EA HW HINGE 5BB1HW 4.5 X 4.5 639 IVE 1 EA FIRE EXIT HARDWARE 9849-EO-F-LBL 612 VON 1 EA FIRE EXIT HARDWARE 9849-L-F-06-LBL 612 VON 1 EA CYLINDER MATCH EXISTING KEYWAY 612 C-R 2 EA SURFACE CLOSER 4111 EDA 691 LCN 2 EA FIRE/LIFE WALL MAG SEM7850 695 LCN 1 SET SEALS PK33D @ HEAD & JAMBS DKB PEM 1 EA TWO PIECE MEETING STILE 18041CNB AL PEM 1 EA N/C FA CONTACT BY FIRE ALARM CONTRACTOR Operational Description 1. Doors are normally held open on magnetic hold opens. 2. Upon loss of power or signal from fire alarm; magnetic hold opens release doors, allowing

doors to close and latch TO   Hardware Group No. 01

For use on mark/door #(s): 100B 200A

EACH TO HAVE: Qty Description Catalog Number FIN Mfr 3 EA HW HINGE 5BB1HW 5 X 4.5 639 IVE 1 EA FIRE EXIT HARDWARE 98-L-F-06 612 VON 1 EA CYLINDER MATCH EXISTING KEYWAY 612 C-R 1 EA SURFACE CLOSER 4111 EDA 691 LCN 1 EA FIRE/LIFE WALL MAG SEM7850 695 LCN

1 SET SEALS PK33D @ HEAD & JAMBS DKB PEM 1 EA N/C FA CONTACT BY FIRE ALARM CONTRACTOR

OPERATIONAL DESCRIPTION 1. DOOR IS NORMALLY HELD OPEN ON MAGNETIC HOLD OPEN. 2. UPON LOSS OF POWER OR SIGNAL FROM FIRE ALARM; MAGNETIC HOLD OPEN

RELEASES DOOR, ALLOWING DOOR TO CLOSE AND LATCH. 3. DOOR FRAME TO BE A MINIMUM OF 3 INCHES AWAY FROM ADJACENT WALL.

SECTION 09 6500 – RESILIENT FLOORING AND ACCESSORIES ITEM 8. REPLACE in Paragraph 2.1 LUXURY VINYL TILE FLOORING, A. LVT-1 (Level 2 Student

Lounge), 1. Approved Products: FROM

Page 3: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 3 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

a. Johnsonite ID Freedom, Stone. Size 18x36 (Special Order), or 12x24 inches, nominal. TO a. Mannington, Amtico, Stone. Size 12x24 inches, nominal.

ITEM 9. ADD in Paragraph 2.1 LUXURY VINYL TILE FLOORING, B. LVT-2 (IT Offices), 1. Approved Products: c. Mannington, Spacia, Abstract. Size 18x18 inches, nominal.

SECTION 10 1400 – SIGNS ITEM 10. ADD the attached 10 1400 SIGNS specification in its entirety.

SECTION 23 0516 – Expansion Joints and Fittings ITEM 11. ADD Twin City Hose as an approved manufacturer of Flexible-hose Packless Expansion

Joints, Rubber Packless Expansion Joints and Alignment Guides.

SECTION 23 0593 – Testing Adjusting and Balancing for HVAC ITEM 12. ADD Testcomm LLC and Air Commander as approved providers of Testing and

Balancing.

SECTION 23 2116 – Hydronic Specialties ITEM 13. ADD General Treatment Products as an approved manufacturer of Automatic Glycol

Feeders.

SECTION 23 2123 – Hydronic Pumps ITEM 14. ADD Armstrong as an approved manufacturer of Separately Coupled Vertical Inline

Pumps.

ITEM 15. ADD Crane/Barnes as an approved manufacturer of Automatic Condensate Pump Units

SECTION 23 3113 – Metal Ducts ITEM 16. ADD Lewis and Lambert as an approved manufacturer of metal ducts.

ITEM 17. ADD West Coast Omni Duct as an approved manufacturer of metal ducts.

SECTION 23 8236 – Finned-Tube Radiation Heaters ITEM 18. ADD Sterling as an approved manufacturer of Finned-Tube Radiation Heaters

SECTION 23 8239 – Cabinet Unit Heaters ITEM 19. ADD Sterling as an approved manufacturer of Cabinet Unit Heaters

SECTION 23 8240 – Buffer Tanks with Steam Heat ITEM 20. ADD John Wood as an approved manufacturer of Buffer Tanks With Steam Heat.

SECTION 26 5669 – CEILING FANS ITEM 21. ADD attached 26 5669 CEILING FANS specification in its entirety.

Page 4: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 4 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

ITEM 22. LIGHTING PRIORS

#1 MMR LIGHTING:

1. TYPE P1 – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN SILVER. 2. TYPE P3 & P3A – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN

SILVER. 3. TYPE P4 – MANUFACTURER APPROVED. 4. TYPE P6 – MANUFACTURER APPROVED.

#2 ILLUMINATION SYSTEMS:

1. TYPE P4 – MANUFACTURER APPROVED. PROVIDE P0R0PD…, PENDANT MOUNT. 2. TYPE P6 – MANUFACTURER APPROVED. PROVIDE P0R0PD…, PENDANT MOUNT.

#3 NRA:

1. TYPE P1 – ARCHITECTURAL LOOK NOT APPROVED. 2. TYPE P3 & P3A – ARCHITECTURAL LOOK NOT APPROVED. 3. TYPE P5 – MANUFACTURER APPROVED.

#4 PRIME WEST:

1. TYPE P1 – MANUFACTURER APPROVED. a. P1 ALT – ARCHITECTURAL LOOK NOT APPROVED.

2. TYPE P2 – MANUFACTURER APPROVED. a. P2 ALT – ARCHITECTURAL LOOK NOT APPROVED.

3. TYPE P3 & P3A – MANUFACTURER APPROVED. a. P3 & P3A ALT – ARCHITECTURAL LOOK NOT APPROVED.

4. TYPE P4 – MANUFACTURER APPROVED. PROVIDE PENDANT MOUNT. 5. TYPE P5 – MANUFACTURER APPROVED. 6. TYPE P6 – MANUFACTURER APPROVED. PROVIDE PENDANT MOUNT. 7. TYPE P7 – MANUFACTURER APPROVED.

a. P7 ALT – ARCHITECTURAL LOOK NOT APPROVED.

#5 CASCADE LIGHTING:

1. TYPE P1 – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN SILVER. 2. TYPE P3 & 3A – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN SILVER. 3. TYPE P4 – MANUFACTURER APPROVED. 4. TYPE P5 – ARCHITECTURAL LOOK NOT APPROVED. VERIFY FIXTURE IS CIRCULAR. 5. TYPE P6 – MANUFACTURER APPROVED.

#1 MMR LIGHTING:

1. TYPE P1 – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN SILVER. 2. TYPE P3 & P3A – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN

SILVER. 3. TYPE P4 – MANUFACTURER APPROVED. 4. TYPE P6 – MANUFACTURER APPROVED.

#2 ILLUMINATION SYSTEMS:

Page 5: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 5 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

1. TYPE P4 – MANUFACTURER APPROVED. PROVIDE P0R0PD…, PENDANT MOUNT. PROVIDE FIXTURE WITH 3.5” OPTICS.

2. TYPE P6 – MANUFACTURER APPROVED. PROVIDE P0R0PD…, PENDANT MOUNT. PROVIDE FIXTURE WITH 3.5” OPTICS.

#3 NRA:

1. TYPE P1 – ARCHITECTURAL LOOK NOT APPROVED. 2. TYPE P3 & P3A – ARCHITECTURAL LOOK NOT APPROVED. 3. TYPE P5 – MANUFACTURER APPROVED.

#4 PRIME WEST:

1. TYPE P1 – MANUFACTURER APPROVED. a. P1 ALT – ARCHITECTURAL LOOK NOT APPROVED.

2. TYPE P2 – MANUFACTURER APPROVED. a. P2 ALT – ARCHITECTURAL LOOK NOT APPROVED.

3. TYPE P3 & P3A – MANUFACTURER APPROVED. a. P3 & P3A ALT – ARCHITECTURAL LOOK NOT APPROVED.

4. TYPE P4 – MANUFACTURER APPROVED. PROVIDE PENDANT MOUNT. 5. TYPE P5 – MANUFACTURER APPROVED. 6. TYPE P6 – MANUFACTURER APPROVED. PROVIDE PENDANT MOUNT. 7. TYPE P7 – MANUFACTURER APPROVED.

a. P7 ALT – ARCHITECTURAL LOOK NOT APPROVED.

#5 CASCADE LIGHTING:

1. TYPE P1 – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN SILVER. 2. TYPE P3 & 3A – MANUFACTURER APPROVED. VERIFY FIXTURE FINISH IS AVAILABLE IN SILVER. 3. TYPE P4 – MANUFACTURER APPROVED. 4. TYPE P5 – ARCHITECTURAL LOOK NOT APPROVED. VERIFY FIXTURE IS CIRCULAR. 5. TYPE P6 – MANUFACTURER APPROVED.

Page 6: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 6 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

CHANGES TO DRAWINGS:

A0.6 ABATEMENT PLANS ITEM 23. REVISE the quantity of VINYL ASBESTOS TILE WITH MASTIC in the ABATEMENT

LEGEND from 3800 SQFT to 4520 SQFT.

C1.00 DEMOLITION PLAN ITEM 24. REVISE window well leader notes to call them “…Existing West Window Well…” (with key

notes 2 & 6 referenced), and “Existing East Window Well.”

C2.00 CIVIL SITE PLAN ITEM 25. REVISE “Proposed East Window Well” leader note to “Proposed East Side Window

Well,” and add a hexagon reference to Key Note #5.

ITEM 26. ADD, to “Proposed West Window Well” leader note, a hexagon reference to Key Note #5.

ITEM 27. REVISE Key Note #4 from “…the West Planter and replacement of the West Window Well…” to “…the Proposed East Planter and the Proposed West Window Well…”

ITEM 28. REVISE Key Note #5 from “Reconstruct West Window Well as specified and…” to “Construct Window Wells as specified and…”

C3.00 GRADING & DRAINAGE PLAN ITEM 29. REVISE “Proposed Planter” leader notes for the two planters to read “Proposed West

Planter” (no key note reference) and “Proposed East Planter” (with hexagon reference to Key Note #1).

ITEM 30. REVISE “Proposed South Window Well” leader note to “Proposed West Window Well,” and revise “Existing Window Well” leader note to “Existing East Window Well.”

ITEM 31. REVISE Key Note #1 from “…the West Planter and replacement of the West Window Well …” to “…the Proposed East Planter and the Proposed West Window Well…”

C4.00 DETAILS ITEM 32. REVISE Detail 1 text “West Planter” to “Proposed West Planter,” and revise leader note

“Grade Break Line” to “Grade Break Line (Typ.).

ITEM 33. REVISE title of Section B detail, to “Typ. Section - Drainage at Proposed West Planter”

A2.10 FLOOR PLANS – LECTURE HALL 011 ITEM 34. REVISE note at 1/A2.10 from “FIXED TABLE 12 6000” to “FIXED TABLE 12 7000.”

ITEM 35. ADD note at 1/A2.10 at all seating reading “FIXED SEATS & FIXED SWIVEL SEATS 12 7000.”

A6.1 WINDOW AND DOOR INFO ITEM 36. REVISE HARDWARE GROUP for door numbers 100B and 200A from “02” to “01”.

SKA-10 BUILDING SIGNAGE ITEM 37. ADD three (3) cast acrylic signs and one (1) sign back per drawing/schedule on SKA-10.

Page 7: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

Page 7 of 7 UMLA Entry & Basement Remodel – Addendum 2.0 November 16, 2016

ITEM 38. REVISE dimensional lettering at exterior canopy per SKA-10 and specs.

SKA-11 WINDOW WELL GUARDRAIL ITEM 39. REVISE Window well guardrail height from 2’-6” to 2’-8 ½”

SKA-12 LECTURE HALL HANDRAIL ITEM 40. ADD a second handrail at the Lecture Hall ramp per drawings.

SKA-13 LECTURE HALL HANDRAIL ITEM 41. ADD a second handrail at the Lecture Hall ramp per drawings.

S1.01 FOUNDATION PLAN ITEM 42. REVISE text IN note next to western-most concrete wall in 1/S1.01 from “6” CIP CONC

PLANTER WALL W/ #4 @ 12” OC HORIZ & VERT (MAX HEIGHT = 4’-0”)” to “6” CIP CONC PLANTER WALL W/ #4 @ 12” OC HORIZ & VERT (MAX HEIGHT = 4’-0”) AND ¾” DIA. WEEP HOLES @ 6’-0” OC”

M0.1 MECHANICAL EQUIPMENT SCHEDULES ITEM 43. DELETE Delete requirement to install 1” acoustic liner in round supply or return

ductwork.

M0.2 MECHANICAL SCHEDULES & DETAILS ITEM 44. REVISE detail 1/M0.2 to include an air separator on the inlet to pumps P-1 & P-2 and

revised the piping connections to buffer tank BT-1.

E0.5 LUMINAIRE SCHEDULE ITEM 45. ADD light fixture D3 to Luminaire Schedule.

E1.1 LEVEL 2 & 3 LIGHTING PLANS ITEM 46. REVISE

Level 2:

Alternate note added to P8 fixtures in student lounge.

Keynote #4 added to denote fan model number and controls.

B3 light fixture replaced with new fixture D3 in alternate coffee shop.

Level 3:

Keynote #5 added to denote fan model number and controls.

END OF ADDENDUM

Page 8: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

UM Liberal Arts Building SIGNS Entry & Basement Remodel 10 1400 - Page 1

SECTION 10 1400 – SIGNS

PART 1 - PART 1 - GENERAL

1.1 SUMMARY A. Section Includes:

1. Cast acrylic panel signs. 2. Metal dimensional letters.

1.2 DEFINITIONS A. Braille: Grade 2 Braille including 189 part-word or whole word contractions in addition to Grade 1Braille

63 characters. Tactile is required whenever braille is required. B. Non-tactile: Letters and numbers on signs with width-to-height ratio between 3:5 and 1:1 and stroke

width ratio between 1:5 and 1:10 using upper case "X" to calculate ratios. Use type styles with medium weight; upper and lower case lettering is permitted; serif typestyles are permitted.

C. Symbols: Symbol itself is not required to be tactile but equivalent verbal description is required both in tactile letters and braille.

D. Tactile: 1/32" raised capital letters without serifs at least 5/8" height and not more than 2" height based on upper case "X". Braille is required whenever tactile is required.

1.3 SYSTEM DESCRIPTION A. Signage under this section is intended to include items for identification, direction, control, and

information of building where installed as complete integrated system from a single manufacturer. B. ADA design requirements:

1. Signage requiring tactile graphics: a. Wall mounted signs designating permanent rooms and spaces such as, room numbers and

restroom, department, office, and fire exit identifications. b. Individually applied characters are prohibited.

2. Signage not requiring tactile graphics but require compliance to other ADA requirements: All other signs providing direction to or information about function of space such as, directional signs (signs with arrow), informational signs (operating hours, policies, etc.), regulatory signs (no smoking, do not enter), and ceiling and projected wall mount signs.

C. ADA performance requirements: 1. Tactile graphics signs mounting requirements:

a. Height: The tops of all signs to be the same height unless noted otherwise. Verify this with Architect prior to installation. The bottom of the uppermost line of tactile text cannot be greater than 60 inches and the lowest tactile or braille cannot be below 48” above finish floor.

b. Single doors: Mount signs on wall adjacent to latch side of door where possible. c. Openings: Mount signs on wall adjacent opening. d. No wall space adjacent latch side of door, opening, or double doors: Mount sign on nearest

adjacent wall.

1.4 SUBMITTALS A. General: Submit in accordance with Section 01 3000. B. Product Data: Submit product data for each type of sign specified, including details of construction

relative to materials, dimensions, profiles, and finishes. C. Shop Drawings:

1. Submit shop drawings which include fabrication, installation of, and finish of specified systems for the Cast Acrylic Panel signs and Dimensional Lettering.

2. Include following: a. Fully dimensioned plans and elevations with detail coordination keys. b. Locations of exposed fasteners and joints. c. Message list for each sign required. d. Large-scale details of wording and metal letter spacing layouts. e. Installation details.

3. Setting drawings, templates, and directions for installation of anchor bolts and other anchors to be installed as a unit of Work in other Sections.

4. Templates: Furnish full-size spacing templates for mounted dimensional letters. D. Samples:

Page 9: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

UM Liberal Arts Building SIGNS Entry & Basement Remodel 10 1400 - Page 2

1. Cast Acrylic Sheet and Plastic Laminate: Panel 8-inch square minimum for each material, color, texture, and pattern required. Include sample of graphic image process required, showing graphic style, and colors and finishes of letters, numbers, and other graphic devices.

2. Aluminum Letters: Full Size Letter Sample & support mountings for each different lettering type. 3. Aluminum Plate: Finish sample for color, thickness and graphic cut out. 4. Aluminum Sign Standoffs: One full size sample.

1.5 QUALITY ASSURANCE A. Single-Source Responsibility: For each separate sign type required, obtain signs from one source of a

single manufacturer. B. Furnish appropriate checklist for aiding in reordering after the Date of Substantial Completion by the

Owner. Maintain schedule of signs for five years.

PART 2 - PRODUCTS

2.1 MANUFACTURERS A. Acceptable Manufacturers of Panel Signs:

1. APCO Signs. 2. ASI Sign Systems, Inc. 3. Best Sign Co. 4. Inland Pacific.

B. Acceptable Manufacturers of Letters: 1. Metallic Arts 2. Gemini Incorporated 3. Approved Equal.

2.2 MATERIALS A. Aluminum:

1. Aluminum Sheet and Plate: ASTM B 209 alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated, and with at least the strength and durability properties of Alloy 5005-H32.

2. Aluminum Extrusions: ASTM B 221, alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated, and with at least the strength and durability properties of Alloy 6063-T5.

B. Cast Acrylic Sheet: Provide cast (not extruded or continuous cast) methyl methacrylate monomer plastic sheet, in sizes and thicknesses indicated, with a minimum flexural strength of 16,000 psi when tested according to ASTM D 790, with a minimum allowable continuous service temperature of 176 deg F (80 deg C), and of the following general types Opaque Sheet: Provide colored opaque acrylic sheet in colors and finishes from the manufacturer's standards for Architect to choose from.

C. Fasteners: Use concealed fasteners fabricated from metals that are not corrosive to sign material and mounting surface.

D. Colored Coatings for Acrylic Plastic Sheet: Colored coatings, including inks and paints for copy and background colors; recommended by acrylic manufacturers for optimum adherence to acrylic surface, and nonfading for application intended.

2.3 CODE SIGNAGE A. Sign Schedule: Provide signage as required by codes and accessibility regulations and requirements.

2.4 ACRYLIC CAST SHEET PANEL SIGNS A. Produce smooth, even, level Acrylic Cast sign panel surfaces, constructed to remain flat under installed

conditions. B. Unframed Cast Panel Signs: Fabricate signs with edges mechanically and smoothly finished to

conform with following requirements: 1. Edge and Corner Condition: Square cut.

C. Size: As Scheduled on the Drawings. D. Graphic Content and Style: Sign copy that complies with requirements indicated for size, style, spacing,

content, position, material, finishes, and colors of letters, numbers, and other graphic devices. 1. Copy: Type style to be Helvetica Medium Condensed. 2. Copy Text: See Schedule on the Drawings.

E. Colors and Finishes: to be selected from Manufacturer’s standard selection.

Page 10: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

UM Liberal Arts Building SIGNS Entry & Basement Remodel 10 1400 - Page 3

2.5 DIMENSIONAL LETTERS AND NUMBERS A. Cut Metal Letters: Cut letters and numbers from solid plate material of 1” thickness. Produce precisely

cut characters with square cut, smooth edges. Comply with requirements indicated for finish, style, and size.

1. Metal: Painted Aluminum, Satin sheen. 2. Letter Height: 21” per drawings. 3. Letter Style: Helvetica Medium. 4. Letter Mount: Bottom rail-mounted with aluminum studs and rail as shown in drawings. Provide

threaded connection at top of each letter for tie-back connection.

2.6 FINISHES A. Metal Finishes: Comply with NAAMM "Metal Finishes Manual" for finish designations and applications

recommendations. B. Aluminum Finishes: Anodized clear.

PART 3 - EXECUTION

3.1 EXAMINATION A. Examine conditions and proceed with work in accordance with Section 01 7000. B. Examine supporting members to ensure surfaces are at proper elevation and are free from dirt or other

deleterious matter. C. Examine supporting members of soffit materials to receive cast metal letters are complete and ready to

receive letter installation.

3.2 INSTALLATION A. General:

1. Locate sign units and accessories where indicated on Drawings, using concealed mounting methods in compliance with manufacturer's instructions.

2. Install signs and letters level, plumb, and at height indicated, with sign surfaces free from distortion or other defects in appearance.

3. Wall-Mounted Panel Signs: Attach panel signs to surfaces using double-sided tape per Code requirements.

4. Metal Letter Signs: Attach letters & numbers to top of canopy with appropriate submaterial fasteners. See details.

3.3 CLEANING AND PROTECTION A. After installation, clean soiled sign surfaces according to manufacturer's instructions. B. Protect units from damage until acceptance by Owner and not more than 48 hours prior to Date of

Substantial Completion. C. Provide Owner with maintenance information and checklist for future re-ordering information.

3.4 SCHEDULE A. Cast Acrylic Panel Signs (See Signage Drawing SKA-10 for text, symbols & locations) B. Metal Letters & Numbers (See Exterior Elevations on Drawings for locations)

END OF SECTION

Page 11: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

UM Liberal Arts - Entry and Basement Remodel CEILING FANS State of Montana 265669 - Page 1

SECTION 265669 – CEILING FANS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes high volume low speed (HVLS) ceiling fans and accessories

1.2 SUBMITTALS

A. Product Data: 1. Ceiling Fans 2. Mounting Hardware 3. Controls

B. Application Drawings: Plan, section, elevation and isometric view necessary to convey all information required for installation and coordination with building features, lighting, fire protection and mechanical.

1.3 COORDINATION

A. A. The fan shall be capable of receiving a stop command from the fire panel, an ASD (Aspirating Smoke Detection) device, or any number of smoke, flame or heat detectors.

B. The fans shall be as follows: 1. The fan shall meet the air velocity requirements of FM Global’s 2.0 data sheet for

ESFR sprinklers. 2. The fan shall be wired into the building’s fire suppression system so that the fan

will automatically shut off within a maximum of 90 seconds after sprinklers are activated. To facilitate this automatic shut-down, the fan shall include a Variable Frequency Drive (VFD) within the control panel. The low voltage wire and relay needed to accomplish this must be supplied by the Fire Alarm installer.

3. Upon fire detection as described above, the fans shall coast to stop as required by NFPA guidelines.

1.4 WARRANTY

A. Lifetime warranty for airfoils, hub, frame and mounting

B. 50,000 hour warranty on all other components which include the following: 1. Motor 2. Integrated Drive 3. Controller / Remote

Page 12: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

UM Liberal Arts - Entry and Basement Remodel CEILING FANS State of Montana 265669 - Page 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: provide products by one of the following 1. Macro Air 2. Big Ass Fan 3. Prior approved equal

2.2 AIRFOILS

A. Material: Aluminum

B. Qty: 6

C. Finish: Anodized

2.3 MOTOR

A. Type: Brushless DC

2.4 DRIVE

A. 277V, 1PH

B. Operating frequency: 20-50KHz

C. Dynamic acceleration and deceleration

D. Communication Proptcol: Modbus 485, BACnet or LonWorks

2.5 MOUNTING

A. The fan mounting system shall be equipped with hardware, no less than SAE grade 5 for safe installation. The fan shall be equipped with a stress reliving swivel mount. The fan mount shall encompass multiple mounting options for I-beam, Purlin and Glulam applications (specified upon order).

B. Provide 4ft (approx.) mounting extension. Contractor shall field verify fan mounting height with the owner prior to ordering.

2.6 SAFETY

A. The fan shall include retainers to prevent the airfoils from separating from unit as well and a safety cable to ensure the unit cannot fall to the ground.

Page 13: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

UM Liberal Arts - Entry and Basement Remodel CEILING FANS State of Montana 265669 - Page 3

PART 3 - EXECUTION

3.1 PREPARATION

A. Check accuracy of dimensions indicated for openings to receive fans.

B. Check location and availability of utility services to ensure proper voltage and installation preparation.

C. Coordinate location and installation of the Fans.

D. Ensure building structural members are sufficient to support the weight and operation of the fan. Consult professional engineer or registered architect as required.

3.2 INSTALLATION

A. Install units per manufacturer's written instructions.

B. Mount fan above manufacturers minimum recommended height.

C. All safety and support features must be installed. These include any guy wires and safety cables as well as airfoil retainer locking features.

D. Adjust unit as required for proper operation in accordance with manufacturer’s installation instructions.

E. Securely anchor units.

F. Ensure that operating parts turn freely prior to initial startup.

G. Repair or replace damaged parts, dents, buckles, abrasions or other damage affecting appearance or serviceability, as acceptable to Architect.

3.3 PROTECTION

A. Protect finished Work until date of Substantial Completion.

B. Touch-up, repair or replace damaged products before Substantial Completion.

3.4 CLEANING

A. Clean Work per Section 01 74 00.

B. Clean and inspect fans per manufacturer's instructions.

C. Remove temporary protective cover at date of Substantial Completion.

END OF SECTION 265669

Page 14: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

ENTRY

Type 'A' Type 'B'

EXIT

6"

Exit Doors (1)

Type 'C'

8"EXIT

5"

4" ACCESS

Exit AccessDoors (1)

6"

3/4" H3/4" H

3/4" H

3/4"

ADA Entry Signs (1)Exterior Mounted.

8"

Back 'D'

5"

4"

Exit AccessDoors (1)

2.8

2.H

ENTRYVESTIBULE

104A

NEW ENTRY104

(N) ACRYLIC SIGN - TYPE 'C'10 1400

(N) ACRYLIC SIGN - BACK 'D'10 1400

ALIGNED WITH SIGN ONOTHER SIDE OF GLAZING

(N) ACRYLIC SIGN - TYPE 'A'10 1400

(N) ACRYLIC SIGN - TYPE 'B'10 1400

ALIGNED WITH SIGN ONOTHER SIDE OF GLAZING

SIGNAGE SCHEDULE

BRAILLE, TYP

DATE:

PROJECT #:

ORIGINAL SIZE: 8.5" x 11"

Q:\_

Jobs

15\2

1 U

M -

Libe

ral A

rts B

uild

ing

Reno

vatio

n an

d Ad

ditio

n\02

Pha

se 1

.1\0

5 BI

D\D

raw

ings

\201

6-11

-02

UM

LA1.

1 - A

liV.rv

t

UNIVERSITY OF MTLA ENTRY AND

BASEMENT REMODEL

11/16/2016

SKA-101/2

15-21.02

STATE OF MONTANA

BUILDINGSIGNAGE

BID32 Campus Drive, University ofMontana

Missoula, MT 59812

1/4" = 1'-0"1 SIGNAGE PLAN

No. Description Date

Page 15: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

1

A5.01

1

A5.01

3

A5.02

3

A5.02

4

A7.04

ESF-1

EQEQ

DIM. LETTER SIGNAGE10 14 00

DIM LETTERING SIGNAGE 10 140015'-6"

1'-9

"

DATE:

PROJECT #:

ORIGINAL SIZE: 8.5" x 11"

Q:\_

Jobs

15\2

1 U

M -

Libe

ral A

rts B

uild

ing

Reno

vatio

n an

d Ad

ditio

n\02

Pha

se 1

.1\0

5 BI

D\D

raw

ings

\201

6-11

-02

UM

LA1.

1 - A

liV.rv

t

UNIVERSITY OF MTLA ENTRY AND

BASEMENT REMODEL

11/16/2016

SKA-102/2

15-21.02

STATE OF MONTANA

BUILDINGSIGNAGE

BID32 Campus Drive, University ofMontana

Missoula, MT 59812

1/8" = 1'-0"1

SKA-10 Partial Revision to 3/A4.01 SOUTHELEVATION

No. Description Date3 Addendum 3 11/16/2016

Page 16: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

ALTERNATE 1ADD WINDOWS, WINDOW WELL &ASSOCIATED COMPONENTS. SEEPROJECT MANUAL SECTION 01 2300.

2 1/2" x 2" STL TUBE TOP RAIL

1 1/2" x 1/2" STL BAR

1" x 2" STL TUBE BALUSTER @ MIN 48"O.C. U.N.O.WELD TO OUTSIDE EDGES OF 1 1/2" X1/2" STL BARS AND TO B.O. TOP RAIL

T.O. PRECAST CONCRETE PANELSTL EMBED PLATE AT EACH BALUSTERW/ HAS (PER PRECAST MFR)

NOTE:ENTIRE STL ASSEMBLY PAINTED AS PER PT-6,SEE FINISH LEGEND ON A8.01 & PROJECTMANUAL SECTION 09 9000.

2'-8 1

/2"6"

3 1/2" LEVEL 1 = 100'-0"

HIGHEST POINT OF ADJACENTWALKING SURFACE

MAIN

TAIN

42" A

BOVE

ADJ

ACEN

T W

ALKI

NG S

URFA

CE3'-

6"

EQEQ

EQEQ

EQEQ

EQ3 3

/8"

3

LEVEL 1100'-0"

BASEMENT FLOOR88'-3"

PLANTINGBED

PRECAST CONC. PANELRETAINING WALL; SSDREINFORCEMENT& GEOGRID; SSD

6"2'-

8 1/2"

ALTERNATE 1ADD WINDOWS, WINDOW WELL &ASSOCIATED COMPONENTS. SEEPROJECT MANUAL SECTION 01 2300.

3

DATE:

PROJECT #:

ORIGINAL SIZE: 8.5" x 11"

Q:\_J

obs1

5\21 U

M - L

ibera

l Arts

Buil

ding R

enov

ation

and A

dditio

n\02 P

hase

1.1\0

5 BID

\Dra

wing

s\201

6-11

-02 U

MLA1

.1 - A

liV.rv

t

UNIVERSITY OF MTLA ENTRY AND

BASEMENT REMODEL

11/16/2016

SKA-111/1

15-21.02

STATE OF MONTANA

WINDOW WELLGUARDRAIL

BID32 Campus Drive, University ofMontana

Missoula, MT 59812

No. Description Date3 Addendum 3 11/16/2016

1" = 1'-0"1

SKA-11 - Revision to 9/A5.01EXTERIOR RAILING DETAIL

1/4" = 1'-0"2

SK-11 Revision to Partial 8/A5.01 BUILDINGSECTION @ NEW WINDOW WELL

Page 17: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

A8.02

1

3

A8.0213

1112

1" /

12"

DN

UP

4'-0"

3 RISERS @ 6"2 TREADS @ 12"

SKA-121/1

2

MTL HANDRAIL05 5000

2"

3

MTL HANDRAIL05 50001'-0" MIN

1'-0" MIN

10 1/2"

9"

3'-0

"

ATTACH SIM 6/S5.01END CONDITION

ATTACH W/ STL FLANGE.PROVIDE BLOCKING.

DATE:

PROJECT #:

ORIGINAL SIZE: 8.5" x 11"

Q:\_

Jobs

15\2

1 U

M -

Libe

ral A

rts B

uild

ing

Reno

vatio

n an

d Ad

ditio

n\02

Pha

se 1

.1\0

5 BI

D\D

raw

ings

\201

6-11

-02

UM

LA1.

1 - A

liV.rv

t

UNIVERSITY OF MTLA ENTRY AND

BASEMENT REMODEL

11/16/2016

SKA-121/1

15-21.02

STATE OF MONTANA

LECTURE HALLHANDRAIL

BID32 Campus Drive, University ofMontana

Missoula, MT 59812

1/4" = 1'-0"1

SKA-12 Partial Revision to 1/A2.10 FINISHFLOOR PLAN - LECTURE HALL 011

1/4" = 1'-0"2 SKA-12 New RAMP HANDRAIL ELEVATION

3

No. Description Date3 Addendum 3 11/16/2016

Page 18: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

SKA-131/1 2

18 (N) BIKE RACKS ON(N) CONCRETE SLAB

RELOCATE (E) BIKERACKS TO CREATERAILING

ALTERNATE 1ADD WINDOWS,WINDOW WELL,ASSOCIATEDCOMPONENTS, ANDBIKE RACK WORK. SEEPROJECT MANUALSECTION 01 2300.

REPLACE SODWHERE DISTURBED

76'-8

1/2"

APP

ROX.

3WELD 5/8" BASEPLATES TOTUBE LEGS; PROVIDE2-5/8" DIA X 5" EMBED ANCHOR,SIM TO 'TYP CONDITION' 6/S5.01

NEW CONCRETEAPRON

SALVAGED BIKE RACKS FROMEAST SIDE OF LIBERAL ARTS(7) AT APPROX.10'-6", V.I.F.6"

DATE:

PROJECT #:

ORIGINAL SIZE: 8.5" x 11"

C:\U

sers\

steph

anie\

Docu

ments

\2016

-11-

02 U

MLA1

.1 - C

entra

l_step

hanie

.rvt

32 Campus Drive, University ofMontana

Missoula, MT 59812

UNIVERSITY OF MTLA ENTRY AND

BASEMENT REMODEL

11/16/2016

SKA-131/1

15-21.02

STATE OF MONTANA

NEW RAILINGFROM EXISTING

BIKE RACKSBIDNo. Description Date3 Addendum 3 11/16/2016

1/16" = 1'-0"1

SKA-13 Revision to PartialARCHITECTURAL SITE PLAN

1/4" = 1'-0"2

SKA-13 NEW RAILING FROMEXISTING BIKE RACKS

3

Page 19: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

SEE THE MEP COORDINATION SCHEDULE ON SHEET M0.5 FOR

ADDITIONAL ELECTRICAL INFORMATION. COORDINATE WITH OTHER

TRADES TO ENSURE THAT ALL:

• ELECTRICAL DISCONNECTS

• MOTOR STARTERS

• VARIABLE FREQUENCY DRIVES

• CONTROLS

• ELECTRICAL ACCESSORIES

ARE FURNISHED BY THE APPROPRIATE TRADE AND THAT INSTALLATION

HAS BEEN COORDINATED.

ELECTRICAL COORDINATION FREEZE PROTECTIONTHE HEAT PUMP WATER LOOP SHALL BE FILLED WITH:

• 35% PROPYLENE GLYCOL

• 65% WATER

ALL PROPYLENE GLYCOL SHALL BE SUITABLE FOR USE IN HYDRONIC

SYSTEM AND INCLUDE CORROSION INHIBITORS AND

PROVIDE GLYCOL SUITABLE FOR USE WITH ALUMINUM IF THE INSTALLED

BOILER HAS AN ALUMINUM HEAT EXCHANGER.

AUTOMATIC GLYCOL FEEDER SCHEDULE - BASE BID

MARK MFGR MODEL SERVESSYSTEM STATICPRESSURE (PSI)

CONTAINERVOLUME (GAL)

FLUID

ELECTRICAL DATA

REMARKS

VOLTAGE PHASE AMPS

AGF-1 AXIOM MF300-S HEAT PUMP WATER LOOP 25 1735% PG / 65%

WATER120 1 0.7 SEE NOTES

NOTES: PROVIDE UNIT COMPLETE WITH TANK COVER, STRAINER ON INLET TO PUMP, ADJUSTABLE PRESSURE REGULATING VALVE (25-35 PSIG), PRESSURE GAUGE, CHECK VALVE, AXIOM MODEL RIA10-1-SSA LOW LEVEL ALARMPANEL WITH AUDIBLE ALARM AND DRY CONTACTS FOR CONNECTION TO DDC BUILDING MANAGEMENT SYSTEM AND AXIOM MF200-1430 MOUNTING SHELF.

EXPANSION TANK SCHEDULE - 35% P.G. - BASE BID

MARK MFGR MODEL TOTAL VOLUME (GAL)ACCEPTANCE VOLUME

(GAL)SYSTEM SYSTEM PRESSURE (PSI) SYSTEM VOLUME (GALLONS) REMARKS

ET-1 TACO CA90-125 23 23 HEAT PUMP WATER LOOP 45 350 SEE NOTES

NOTES: THE LISTED SYSTEM PRESSURE IS AN ESTIMATE. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO FIELD VERIFY THE REQUIRED SYSTEM PRESSURE TO ENSURE PROPER SYSTEM OPERATION ANDCHARGE THE TANK AS REQUIRED. AFTER CHARGING RECORD SYSTEM PRESSURE ON SIDE OF TANK.

MECHANICAL PIPING MATERIAL SCHEDULESYSTEM INSTALLATION LOCATION SIZE RANGE MATERIAL FITTING TYPE INSULATION TYPE JACKETING REMARKS

STEAM PIPINGINDOOR ABOVE

GROUND1_2" - 1-1/2" SCH 40 STEEL THREADED

MINERAL FIBER PRE-FORMED 1"THICK

ASJ SEE NOTES

STEAM CONDENSATEINDOOR ABOVE

GROUND1_2" - 1-1/2" SCH 80 STEEL THREADED

MINERAL FIBER PRE-FORMED 1"THICK

ASJ SEE NOTES

HEAT PUMP SUPPLY ANDRETURN

INDOOR ABOVEGROUND

1" - 8" SCH 40 STEELRIGID GROOVED

FITTINGS ANDCOUPLINGS

MINERAL FIBER PRE-FORMED

1" THICK: 1_2" NPS TO 1-1/2" NPS

1-1/2" THICK: 2" NPS AND LARGER

ASJ SEE NOTES

HEAT PUMP SUPPLY ANDRETURN

OUTDOOR ABOVEGROUND

1" - 8" SCH 40 STEELRIGID GROOVED

FITTINGS ANDCOUPLINGS

MINERAL FIBER PRE-FORMED

1" THICK: 1_2" NPS TO 1-1/2" NPS

1-1/2" THICK: 2" NPS AND LARGER

ASJ SEE NOTES

REFRIGERATION PIPING INDOOR 3_8" TO 2" TYPE ACR COPPER BRAZED 3/4" THICK ELASTOMERIC NONE SEE NOTES

REFRIGERATION PIPING OUTDOOR 3_8" TO 2" TYPE ACR COPPER BRAZED 3/4" THICK ELASTOMERIC PVC SEE NOTES

NOTES: INSTALL AND SUPPORT ALL PIPING PER MANUFACTURERS INSTRUCTIONS. INSULATE ALL PIPING IN ACCORDANCE WITH THE INTERNATIONAL ENERGY CONSERVATION CODE. ALL PIPE INSULATION SHALL HAVESMOKE DEVELOPMENT BELOW 50 AND FLAME SPREAD LESS THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.

BUFFER TANK WITH STEAM BUNDLE SCHEDULE - 35% P.G. - BASE BID

MARK MFGR MODELVOLUME

(GAL)HEIGHT

(IN)DIA(IN)

HEAT PUMPWATER

CONNECTIONSIZE (NPS)

STEAM COILCAPACITY(BTH/HR)

STEAMLOAD

(LBS/HR)

STEAMPRESSURE

HEAT PUMPWATER FLOWRATE (GPM)

HEAT PUMPEWT / LWT

ELECTRICAL DATAREMARKS

VOLTAGE PHASE MOP

BT-1 CEMLINE V200SWH624 200 76 30 (QTY 2) 3" 263,200 280.7 5 PSI 61 52.8F / 60F 120 1 15A SEE NOTES

NOTES: PROVIDE JACKETED STORAGE TANK RATED FOR 125PSI WORKING PRESSURE WITH 2" INSULATION AND 20 GA JACKET, SUBMERGED U-BEND STEAM HEATING COIL WITH 3_4" COPPER TUBES AND CAST IRON COIL HEAD,

VENT PORT, TEMPERATURE SENSOR PORT AND DRAIN PORT, STEAM CONTROL VALVE, STEAM TRAP AND INTEGRAL ELECTRONIC CONTROLS. THE INTEGRAL CONTROLS SHALL ALLOW A BMS SYSTEM TO ENABLE/DISABLE THE UNIT,

COMMUNICATE THE TANK TEMPERATURE AND ACCEPT A 4-20mA SIGNAL TO ADJUST THE TANK TEMPERATURE SETPOINT.

DRY COOLER SCHEDULE - 35% P.G. - BASE BID

MARK MFGR MODELTOTAL

CAPACITY(BTU/HR)

FLOWRATE(GPM)

EWT(F)

LWT(F)

FLUIDTYPE

WATERPRESSUREDROP (FT)

OATDB/WB

(F)FANS FAN RPM

VOLTAGE /PHASE

MCA REMARKS

DC-1 LUVANTA LFV8112-4H6-2C 222,043 61.0 112.7 105 35% PG 17.7 93 / 62 2 925 208-230 V / 3PH 13.7 SEE NOTES

NOTES: PROVIDE DRY COOLER WITH ECM FAN MOTORS AND INTEGRAL CONTROL TO VARY FAN SPEED TO MAINTAIN LEAVING WATER SETPOINT.

HOT WATER CABINET HEATER SCHEDULE - BASE BID

MARK MFGR MODEL # ARRANGEMENT SERVES

FANPERFORMANCE

HOT WATER HEATING COIL PERFORMANCE - 30% PGELECTRICAL

DATA

REMARKS

CFMESP

(inWC)HP FLUID TYPE

TOTALCAPACITY(BTU/HR)

EWT(F)

LWT(F)

EAT(F)

LAT (F)COIL

ROWS

COILFLOW(GPM)

PRESSUREDROP (FT)

VOLTAGE /PHASE

CH-1 SIGMA SFF-A-08EXPOSED, FLAT TOP

FLOOR MOUNTEDNEW

VESTIBULE800 0 1__

10

35%PROPYLENE

GLYCOL57,500 180 150 60 126 2 4.0 0.52 120V/1

SEENOTES

NOTES: PROVIDE COMPLETE WITH 16 GA FROM PANEL, TOGGLE DISCONNECT SWITCH, UNIT MOUNTED FAN SPEED CONTROLLER, 1" PLEATED MERV-13 FILTERS, SINGLE POINT ELECTRICAL CONNECTION, RETURN GRILLE,EXTENDED PIPING ENCLOSURE AND TAMPER-PROOF ACCESS FASTENERS.

HYDRONIC PUMP SCHEDULE - 35% P.G. - BASE BID

MARK MFGR MODEL MOTOR RPMIMPELLER

DIA (IN)FLOW RATE

(GPM)HEAD (FT) FLUID SERVES

ELECTRICAL DATA

REMARKSVOLTAGE PHASE HP

P-1 ARMSTRONG 4300 1.5x1.5x6 3530 4.74 61 7565% WATER

35% PGHEAT PUMP SYSTEM

PUMP208 3 3 SEE NOTES

P-2 ARMSTRONG 4300 1.5x1.5x6 3530 4.74 61 7565% WATER

35% PGHEAT PUMP SYSTEM

PUMP208 3 3 SEE NOTES

NOTES: PROVIDE WITH SUCTION DIFFUSER, HIGH EFFICIENCY MOTOR AND ALL ACCESSORIES REQUIRED FOR A COMPLETE INSTALLTION.

HOT WATER FINTUBE HEATER SCHEDULE - BASE BID

MARK MFGR MODELENCLOSURE

STYLEENCLOSUREHEIGHT (IN)

NO. OFELEMENTS

ELEMENTLENGTH (FT)

SERVES

HOT WATER HEATING PERFORMANCE

REMARKSOUTPUT / FT(BTU/HR/FT)

TOTAL OUTPUT(BTU/HR)

AWT(F)

EAT(F)

FLOW RATE(GPM)

PRESSUREDROP (FT)

FT-1 SIGMA SWE-S WALL MTD 24 2 20 SEE PLANS 1,608 32,160 170 68 3.25 1.2 SEE NOTES

FT-2 SIGMA SWE-S WALL MTD 24 2 10 SEE PLANS 1,608 16,080 170 68 3.25 0.6 SEE NOTES

NOTES: TOP OUTLET, ARCHITECTURAL ALUMINUM BAR GRILLE, ENCLOSURE WALL SUPPORT, RETURN PIPE HANGER, HANGER STRIP, PROVIDE ENCLOSURE EXTENSION WITH ACCESS DOOR AT EACH END OF ENCLOSURE ASREQUIRED FILL IN ACCORDING TO PLANS, AND ALL ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION. FIELD VERIFY ENCLOSURE LENGTH PRIOR TO ORDERING. FIELD VERIFY ENCLOSURE WIDTH PRIOR TOORDERING.

DETAIL KEY NOTES:

1. ISOLATION VALVE - SEE SPECIFICATIONS FOR TYPE.

2. TEMPERATURE GAUGE

3. PROVIDE 4" CONCRETE HOUSEKEEPING PAD

4. Y-STRAINER

5. DRAIN VALVE - BALL VALVE WITH HOSE THREAD OUTLET AND CAP

6. UNION

7. 50 PSI RELIEF VALVE - PIPE OUTLET TO GYLCOL FEEDER

8. CHECK VALVE - SEE SPECIFICATIONS FOR TYPE

6

3

3/4" CD

2" LPS

T

BT-1

CONNECT TO EXISTING GRAVITYCONDENSATE IN MECH 003

7

DC-1

M

SLEEVE PIPING THROUGH WALLWITH SLEEVE SEAL SYSTEM

HP-1

3"

HP

R

3"

HP

S

5

9

FLOOR

HP-1

CONNEC TO EXISTING 6" STEAM MAININ MECH 003

3" HPS2

" H

PR

2"

HP

R

2"

HP

S

2"

HP

S

(TYP)

M0.3

7

8

2

(TYP)

9. CONCRETE MOUNTING PAD - COORDINATE WITH GENERAL CONTRACTOR

4

5

3

10. PROVIDE 3" GERAND VENTURI FLOW METER MODEL 743 OR EQUAL.PROVIDE REQUIRED STRAIGHT LENGTHS UPSTREAM ANDDOWNSTREAM AS REQUIRED BY THE MFGR.

11. FACTORY PROVIDED TANK AND HEAT EXCHANGER TRIM AND CONTROLS.SEE MANUFACTURER'S INSTALLATION REQUIREMENTS.

11

12

BYPASS TO ALLOW ISOLATION OF DRY COOLER DURING SYSTEMFLUSHING OR MAINTENANCE.

12.

M0.3

8

P-2

P-1

MANUAL AIR VENT13.

13

3" HPS

3" HPS

3" HPS

DIVERTING VALVE BY T.C.

3" HPR

3" HPR

3" HPR

5M0.3

8

10

3/4" CD

5

1

12

1

(TYP)

AGF-1

ET-1

5

1"

3/4"

M0.3

5

33

AIR SEPARATOR - TACO49025AT-125 OR EQUAL

2ADD #3

2ADD #3

M

ON T A

N

A

PR

OF

ES S IO NA L ENG

INE

ER

ERIK C.RENNA

No. 15652 PE

LICENSED

DA

TE

:

This drawing is not intended nor shall it beused for construction purposes unless thesigned professional stamp of a registeredarchitect employed by Comma-QArchiteture, Inc. is affixed above.

PR

OJE

CT

#:

CONSULTANTS

ORIGINAL DRAWING SIZE: 24" x 36"

C:\U

sers

\ER

enna

\Doc

umen

ts\3

766.

023.

01 U

M L

IBE

RA

L A

RT

S M

EP

CE

NT

RA

L- R

16_e

renn

a.rv

t

UN

IVE

RS

ITY

OF

MO

NT

AN

A -

LIB

ER

AL

AR

TS

BU

ILD

ING

LA

EN

TR

Y &

BA

SE

ME

NT

RE

MO

DE

L

10/2

8/2

016

M0.2

15-2

1

ST

AT

E O

F M

ON

TA

NA

MECHANICAL

SCHEDULES & DETAILS

BID

SE

T13

6 LI

BE

RA

L A

RT

S B

UIL

DIN

G, 3

2 C

AM

PU

S D

RIV

EM

ISS

OU

LA, M

T 5

9812

Not To Scale1

HEATING WATER SYSTEM SCHEMATIC

1ADD #2

# Description Date

1 ADD #2 11-10-14

2 ADD #3 Date 2

Page 20: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

M.E.P. COORDINATION SCHEDULE

MARK DESCRIPTION

ELECTRICAL DATA CONTROL

NOTES

STARTER/DISCONNECT STARTER/DISCONNECT CONTINUED FEEDER

LOAD VOLT-PH TYPE DIV TYPE DIVSIZE

(NEMA)SWITCH(AMPS)

FUSE(AMPS)

ENCLOSURE(NEMA)

COPPERWIRE(AWG)

CONDUIT(INCHES)

AGF-1 AUTOMATIC GLYCOL .9A RCPT 120V/ 1PH INT 23 / 23 1,4 FD/VFD 23 / 26 - - - - #12 3/4"

BT-1 BUFFER TANK WITH PUMP 2.72A 120V/ 1PH INT 23 / 23 1 INT 23 / 26 - - - - #12 3/4"

CH-1 HW CABINET HEATER 1/10 HP 120V/ 1PH INT 23 / 23 1 INT 23 / 26 - - - - #12 3/4"

DC-1 DRY COOLER 13.7MCA 208V/ 3PH INT 23 / 23 FD 26 / 26 - 30 15 3R #12 3/4"

P-1 SYSTEM PUMP 3HP 208V/ 3PH BMS 23 / 23 1 CSFD 26 / 26 - 30 20 1 #12 3/4"

P-2 SYSTEM PUMP 3HP 208V/ 3PH BMS 23 / 23 1 CSFD 26 / 26 - 30 20 1 #12 3/4"

HP-1 HEAT PUMP 36.0+35.0 MCA 208V/3PH INT 23 / 23 (2) FD 26 / 26 - 60 45 1 #8 3/4"

HP-3 HEAT PUMP 32.2MCA 208V/ 1PH INT 23 / 23 FD 26 / 26 - 60 40 3R #8 3/4"

HP-4 HEAT PUMP 27.3MCA 208V/ 1PH INT 23 / 23 FD 26 / 26 - 60 30 3R #8 3/4"

HRV-1 HEAT VENTILLATOR 14.6 MCA 120V/ 1PH INT 23 / 23 FD 26 / 26 - 30 20 3R #12 3/4"

HRV-2 HEAT VENTILLATOR 4.9 MCA 208V/ 1PH INT 23 / 23 INT 23 / 26 - - - 3R #12 3/4"

HWH-1 WATER HEATER 52 A 208/ 3PH INT 22 / 22 FD 26 / 26 - 60 60 1 #4 1"

FC-1 FAN COIL 1.3 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-2 FAN COIL 1.3 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-3 FAN COIL 1.3 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-4 FAN COIL 1.3 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-5 FAN COIL .2 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-6 FAN COIL .2 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-7 FAN COIL .2 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-8 FAN COIL .2 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-9 FAN COIL .2 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-10 FAN COIL .56 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-11 FAN COIL 1.3 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-12 FAN COIL .16 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-13 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-14 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-15 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-16 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-17 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-18 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-19 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

FC-20 FAN COIL .25 RLA 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

HR-1 BRANCH HEATER .2A 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

HR-2 BRANCH HEATER .2A 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

HR-3 BRANCH HEATER .2A 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

BD-1 BRANCH SELECTOR BOX .16A 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

BD-2 BRANCH SELECTOR BOX .16A 208V/ 1PH INT 23 / 23 MSS (2P) 26 / 26 - - - - #12 3/4"

CONTROL TYPE DIVISION OF RESPONSIBILITIES: ELECTRICAL NOTES:

BASCCO2LPSTUCNATHINT

BUILDING AUTO CONTROLCARBON MONOXIDE DETECTORSCONTINUOUS OPERATIONLIGHT SWITCHPRESSURE SWITCHTIME CLOCKUNIT CONTROLLER - TIED TO B.A.S.NOT APPLICABLETHERMOSTATINTEGRAL

22/2222/2623/2323/2626/26

FURNISHED AND INSTALLED BY DIV. 22, WIRED BY DIV. 22FURNISHED AND INSTALLED BY DIV. 22, WIRED BY DIV. 26FURNISHED AND INSTALLED BY DIV. 23, WIRED BY DIV. 23FURNISHED AND INSTALLED BY DIV. 23, WIRED BY DIV. 26FURNISHED AND INSTALLED BY DIV. 26, WIRED BY DIV. 26

1. UNLESS SPECIFICALLY NOTED, ALL FEEDERS SHALL INCLUDE A FULL

SIZE NEUTRAL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY

WITH THE MANUFACTURER OF THE ACTUAL EQUIPMENT BEING

SUPPLIED WHETHER A NEUTRAL IS REQUIRED PRIOR TO ROUGH-IN.

STARTER/DISCONNECT TYPE NOTES:

FDCSFDRVSSVFDMSSMOCPFWNANFD

FUSED DISCONNECTCOMBINATION STARTER/DISCONNECT - HOAREDUCED VOLTAGE SOLID-STATEVARIABLE FREQUENCY DRIVE - HOAMANUAL STARTER SWITCH (# OF POLES)MOTOR OVER-CURRENT PROTECTIONFACTORY-WIRED SINGLE PT. CONNECTIONNOT APPLICABLENON-FUSED DISCONNECT

1.2.3.4.5.6.7.8.9.10.

INTEGRAL DISCONNECTS AND OVERLOADSINTEGRAL OVERLOADSINTEGRAL OVERLOADS, RECEPTACLERECEPTACLESINGLE POINT CONNECTIONPROVIDE RECEPTACLE AND DATA CONNECTION FOR PANELMOUNT ON UNI-STRUT IN FRONT OF UNITPANEL WITHIN SIGHT AS DISCONNECTDIV 23 TO FURNISH & INSTALL VFD. DIV 26 TO PROVIDE DISCONNECTFEED FROM ROOF TOP CONDENSING UNIT

GENERAL NOTES:

1. ALL DUCT SMOKE DETECTORS FURNISHED BY DIV. 23, INSTALLED BY DIV. 23 AND WIRED BY DIV. 23. DIV 26 SHALL WIRE ALL FANSTO SHUT DOWN WHEN ALARM IS INITIATED BY ANY DUCT SMOKE DETECTOR. DIV 26 TO PROVIDE ADDRESSABLE MODULE FORFIRE ALARM CONNECTION.

LUMINAIRE SCHEDULE

TYPE LAMPS DESCRIPTIONS MANUFACTURER CATALOG NO. OR SERIESMOUNTING/VOLTAGE

NOTES

B1 49W LED VOLUMETRIC 2X2, WITH FROSTED ACRYLIC LENS, AND 0-10V DIMMING. HE WILLIAMS LT-2-2-L43-840-AF-DIM-UNVRECESSED/

120

B1E 49W LEDVOLUMETRIC 2X2, WITH FROSTED ACRYLIC LENS, AND 0-10V DIMMING. WITH INTEGRAL EMBATTERY.

HE WILLIAMS LT-2-2-L43-840-AF-DIM-UNV-EM/10WRECESSED/

120

B2 49W LED VOLUMETRIC 2X4, WITH FROSTED ACRYLIC LENS, AND 0-10V DIMMING. HE WILLIAMS LT-2-4-L43-840-AF-DIM-UNVRECESSED/

120

B3 27W 2X2 SEALED RECESSED FIXTURE. ASD LIGHTING EDGE-LIT PANEL-22-D-27-40-HERECESSED/

277

D1 36.5W LED 6" LED DOWNLIGHT, WITH SHALLOW HOUSING, INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. GOTHAM EVO-40-30-6AR-WD-LS-MVOLT-EZ1RECESSED/

120

D1E 36.5W LED 6" LED DOWNLIGHT, WITH SHALLOW HOUSING, INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. GOTHAMEVO-40-30-6AR-WD-LS-MVOLT

-EZ1-ELRECESSED/

120

D2 36.5W LED 6" LED DOWNLIGHT, WITH SHALLOW HOUSING, INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. GOTHAM EVO-40-30-6AR-WD-LS-MVOLT-EZ1RECESSED/

277

D2E 36.5W LED 6" LED DOWNLIGHT, WITH SHALLOW HOUSING, INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. GOTHAMEVO-40-30-6AR-WD-LS-MVOLT

-EZ1-ELRECESSED/

277

D3 22W LED 4" LED DOWNLIGHT, WITH SHALLOW HOUSING, INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. GOTHAMEVO-40-20-4AR-WD-LS-MVOLT

-EZ1-ELRECESSED/

277

E1 36.5W LED 8" LED DOWNLIGHT, WITH INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. GOTHAM EVO-40-30-8AR-WD-LS-MVOLT-EZ1RECESSED/

277

E1E 36.5W LED8" LED DOWNLIGHT, WITH INTEGRAL LED DRIVER, LOW VOLTAGE DIMMING. WITH REMOTEEMERGENCY BATTERY.

GOTHAMEVO-40-30-8AR-WD-LS-MVOLT-EZ1

ELRRECESSED/

277

E2 37W LED ADJUSTABLE SPOT LIGHT. WITH INTEGRAL PHOTOCELL LITHONIADSXF1-LED-2-A530/40K-WFL-MVOLT

-THK-PE-DDBXDGROUND/

120

EL LEDDUAL-HEAD EMERGENCY LUMINAIRE, WITH 90 MINUTE LEAD-ACID BATTERY, ANDSELF-DIAGNOSTICS.

LITHONIA ELM2-LEDWALL/

120

F1 33W LED INDUSTRIAL STRIP FIXTURE. LITHONIAZL1N-48-3000LM-FST-MVOLT-40-80

CRI-WHWALL/

120

P1 11.6W/FT LED12FT LINEAR PENDANT, CABLE-SUSPENDED, WITH FROSTED GLASS. MOUNT WITH BOTTOM OFFIXTURE AT 2' AFF.

COOPER S22DP-2L40-SCST-4-UDD-SI-S92-SCABLE/

1206

P2 8W LED6" DIAMETER CONTEMPORARY CLOSED BOTTOM PENDANT. PROVIDE MANUFACTURERRECOMMENDED TRANSFORMER.

TECH LIGHTING 700-HNK-FJ-B-S-LEDS830SUSPENSION/

2776

P3 11.6W/FT LED12 FT LINEAR PENDANT, CABLE-SUSPENDED, WITH FROSTED GLASS. MOUNT WITH BOTTOM OFFIXTURE AT 2' AFF.

COOPER S22DP-2L40-SCST-4-UDD-SI-S92-SCABLE/

2776

P3A 11.6W/FT LED4FT LINEAR PENDANT, CABLE-SUSPENDED, WITH FROSTED GLASS. MOUNT WITH BOTTOM OFFIXTURE AT 2' AFF.

COOPER S22DP-2L40-SCST-4-UDD-SI-S92-SCABLE/

2776

P4 75W LED 3FT DIAMETER ROUND SUSPENSION MOUNT WITH AIRCRAFT CABLE. HE WILLIAMS RNDP-3-L67-840-DIM-277SUSPENSION/

2776

P5 28W LED 30" DIAMETER HALO TYPE FIXTURE. TECH LIGHTING 700BOD-30-S-LED840SUSPENSION/

2776

P6 125W LED 4FT DIAMETER ROUND SUSPENSION MOUNT WITH AIRCRAFT CABLE. HE WILLIAMS RNDP-4-L136-DIM-277SUSPENSION/

2776

P7 8W LED6" DIAMETER CONTEMPORARY CLOSED BOTTOM PENDANT. PROVIDE MANUFACTURERRECOMMENDED TRANSFORMER.

TECH LIGHTING 700-HNK-FJ-B-S-LEDS830SUSPENSION/

1206

P8 11.6W/FT LED8FT LINEAR PENDANT, CABLE-SUSPENDED, WITH FROSTED GLASS. MOUNT WITH BOTTOM OFFIXTURE AT 2' AFF.

COOPER S22DP-2L40-SCST-4-UDD-SI-S92-SCABLE/

2776

P9 31W LED 2FT DIAMETER ROUND SUSPENSION MOUNT WITH AIRCRAFT CABLE. HE WILLIAMS RNDP-2-L67-840-DIM-277SUSPENSION/

2776

S1 2.2W/FT LEDLED STRIP LIGHT DAMP RATED. PROVIDE WITH CORRESPONDING PLUGABLE POWER SUPPLY.PROVIDE 45° BEZEL. MOUNT ABOVE AND BELOW DISPLAY WINDOW. (2) 2.5FT SECTIONS

LEDI #V4-NS-40-B-BLK-SURFACE/

120

T1 17.2 W LED ADJUSTABLE TRACK LIGHT. COOPER L-805-MED-FL-85-40-MB-120TRACK/

120

X1X2

LED'SEXIT SIGN, WITH THERMOPLASTIC HOUSING, DUAL LED HEADS, HIGH-OUTPUT NI-CAD BATTERYFOR USE WITH REMOTE HEADS (TYPE EL2), GREEN LETTERING, AND SELF-DIAGNOSTICS.

LITHONIA LHQM-LED-R-SD-HOUNIVERSAL/

120

X3 LED EXIT SIGN, WITH CAST ALUMINUM HOUSING AND NI-CAD BATTERY, GREEN LETTERING. SURE-LITES TPX7-1-70-00-R-SDUNIVERSAL/

120

EXEXISTING FIXTURE. TO BE RE-USED WITHIN SPACE. WHERE NEW CEILING TAKE DOWN AND PUTBACK UP.

NOTES:1. PROVIDE FUSING.2. VERIFY FINISH WITH ARCHITECT.3. PROVIDE WITH REMOTE 12V STEP-DOWN TRANSFORMER.4. CIRCUIT VIA TYPE EM INVERTER.5. LAMP DATA IS FOR 4' CROSS-SECTION OF FIXTURE.6. SUBMITTED LUMINAIRE REQUIRES PRIOR APPROVAL.

GENERAL NOTE: THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING TYPES AND PROVIDE ALL REQUIRED MOUNTING ACCESSORIES. FOR FIRE-RATED CEILING ASSEMBLIES, VERIFY ALLRECESSED LUMINAIRE HOUSINGS ARE FIRE-RATED OR PROVIDE FIRE-RATED, DROP-OVER ENCLOSURES OR TENT LUMINAIRE. VERIFY THAT DROP-OVER ENCLOSURES OR TENTS ALLOW FOR AIR SPACEAROUND LUMINAIRE PER MANUFACTURER'S RECOMMENDATIONS.

28342 PEBLOOMFIELD

ARIAN C.

A

S

NO

P

ISS

EF

OR

IGER

NOM

L

EE

R

ENG

I N

DERET

ANAT

DA

TE

:

This drawing is not intended nor shall it beused for construction purposes unless thesigned professional stamp of a registeredarchitect employed by Comma-QArchiteture, Inc. is affixed above.

PR

OJE

CT

#:

CONSULTANTS

ORIGINAL DRAWING SIZE: 24" x 36"

C:\U

sers

\kje

nkin

s\D

eskt

op\L

ocal

Rev

it m

odel

s\37

66.0

23.0

1 U

M L

IBE

RA

L A

RT

S M

EP

CE

NT

RA

L- R

16_k

jenk

ins.

rvt

UN

IVE

RS

ITY

OF

MO

NT

AN

A -

LIB

ER

AL

AR

TS

BU

ILD

ING

LA

EN

TR

Y &

BA

SE

ME

NT

RE

MO

DE

L

10/2

8/2

016

E0.5

15-2

1

ST

AT

E O

F M

ON

TA

NA

MEP SCHEDULE

BID

SE

T13

6 LI

BE

RA

L A

RT

S B

UIL

DIN

G, 3

2 C

AM

PU

S D

RIV

EM

ISS

OU

LA, M

T 5

9812

1ADD #2

1ADD #2

1ADD #2

1ADD #2

# Description Date

1 ADD #2 11-10-14

2 ADD #3 Date 2

2ADD #3

Page 21: 2016-11-16 UMLA1.1 - Addendum 3...Nov 16, 2016  · sure to acknowledge this Addendum on your Bid Proposal. The following information is being issued to all plan holders of record

28342 PEBLOOMFIELD

ARIAN C.

A

S

NO

P

ISS

EF

OR

IGER

NOM

L

EE

R

ENG

I N

DERET

ANAT

Da

OS

OS

Db

Dc

OS

Db

Da

OS

OS

De Dd

PP

f

c

OS

OS

Db

Da

P

c

EL

EL

D2 D2E D2

E1E1EE1

P2

P2

P2

P2

X3

2.6

2.7

2.8

2.E

2.F

2.H

1

b

a

a

a

a

a

2

P3

P3

NEWENTRY

104

ENTRYVESTIBULE

104A

REMOTE EMERGENCYBATTERY PACK

Room

13

STUDENTLOUNGE

206STUDENTLOUNGE

206

CLASSROOM

205

P5

P4

P6

P5P2

P2

P2

2.6

2.7

2.8

2.E 2.F 2.H

11

P2

b

ff

b

2

P4

P4

b

b

f

a

a

a

f

c

c

L1A- 17FAN CONTROLLER

B3

B3

B3

B3

B3

P8

P8

P8

1

d

d

d

d

d

DAYLIGHTING ZONE

P2e

P2e

P2e

P2e

P2e

1ADD #2

S1

3

b

b

P9

P94

44

4

dD34

2ADD #3

2ADD #3

6 2ADD #3

6 2ADD #3

6 2ADD #3

P2

P2

P2

P2

2.6

2.7

2.8

2.E

2.F

2.H

1

P3AP3A

P3

P3

L1A- 19

b

b

b

cc

a

a

a

FAN CONTROLLER

DAYLIGHTING ZONE

52ADD #3

GENERAL NOTES:1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE

WITH EACH OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATIONOF DUCTS, CONDUITS, DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUTTHIS PROJECT BEFORE FINAL PLACEMENT OF MATERIALS.

2. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK DEPICTED INTHESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL PATCHINGOF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.

KEY NOTES:

DA

TE

:

This drawing is not intended nor shall it beused for construction purposes unless thesigned professional stamp of a registeredarchitect employed by Comma-QArchiteture, Inc. is affixed above.

PR

OJE

CT

#:

CONSULTANTS

ORIGINAL DRAWING SIZE: 24" x 36"

C:\U

sers

\kje

nkin

s\D

eskt

op\L

ocal

Rev

it m

odel

s\37

66.0

23.0

1 U

M L

IBE

RA

L A

RT

S M

EP

CE

NT

RA

L- R

16_k

jenk

ins.

rvt

UN

IVE

RS

ITY

OF

MO

NT

AN

A -

LIB

ER

AL

AR

TS

BU

ILD

ING

LA

EN

TR

Y &

BA

SE

ME

NT

RE

MO

DE

L

10/2

8/2

016

E1.1

15-2

1

ST

AT

E O

F M

ON

TA

NA

RENOVATION MAIN

FLOORS LIGHTING PLAN

BID

SE

T13

6 LI

BE

RA

L A

RT

S B

UIL

DIN

G, 3

2 C

AM

PU

S D

RIV

EM

ISS

OU

LA, M

T 5

9812

1/8" = 1'-0"1

LEVEL 1 LIGHTING PLAN

1/8" = 1'-0"2

LEVEL 2 LIGHTING PLAN

1/8" = 1'-0"3

LEVEL 3 LIGHTING PLAN

1. RE-USE EXISTING 277V LIGHTING CIRCUIT WITHIN THIS SPACE FOR NEWLIGHTING.

2. ALL FIXTURES DENOTED AS 'a' TO BE CONTROLLED BY OCC SENSOR ANDDIMMER SWITCH. FIXTURES DENOTED WITH 'b' TO BE CONTROLLED BY DIMMERSWITCH ONLY.

3. POWER FIXTURE 'S1' WITH NEAREST RCPT. SEE POWER PLAN SHEET E2.1.MOUNT STRIPS ON 45° BEZEL ABOVE AND BELOW DISPLAY WINDOW. FIXTURESTO BE SUSPENDED FROM BUILDING STRUCTURE. ADJUST SUSPENSION LENGTHTO PLACE FIXTURE AS CLOSE TO BOTTOM OF LOWERED CEILING AS POSSIBLE.

4. PROVIDE MACROAIR AVD 370 OR APPROVED EQUAL WITH A 10’ RADIUS. WITH ADIGITAL TOUCHPAD CONTROLLER.

5. PROVIDE MACROAIR AVD 370 OR APPROVED EQUAL WITH A 6’ RADIUS. WITH ADIGITAL TOUCHPAD CONTROLLER.

6. BASE BID PROVIDE P3 FIXTURES AND LOCATE ALL THE LIGHT SWITCHES ON THEWEST WALL OF THE STUDENT LOUNGE AREA. COFFEE SHOP IS ALTERNATE.

1ADD #2

1ADD #2

# Description Date

1 ADD #2 11-10-14

2 ADD #3 Date 2

2ADD #3