Navigating the world of automation

2011 Automation Summit

Orlando, FL

Navigating the world of automation

infoPLC

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 2

2011 Automation Summit

Title: Top Ten S7 Tips and Tricks

Track: NAPR

Topic: S7 PLCs

Presenter: Nick Shea

Company: DMC

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 3

DMC Company Profile

Established in 1996, based in Chicago, IL

Service Companies Nationally & Globally

Siemens Solution Partner

Global Reach: Canada China Georgia Czech Rep. Russia Philippines Mexico India

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 4

Bio

Nick Shea

Senior Project Engineer at DMC

Engineering Physics

(University of Kansas)

With DMC since 2006

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Top Ten S7 Tips and Tricks

You already know the fundamentals of S7 PLC

programming…

And the mistakes to avoid (thanks, Tim)

Now, how do you develop, commission and

troubleshoot most efficiently?

Page 5

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 6

Top Ten S7 Tips and Tricks

If you are an…

External Developer:

How do you work most efficiently to provide the highest

value for your customer while increasing project profitability?

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 7

Top Ten S7 Tips and Tricks

If you are an…

Internal Programmer:

How do you reduce start-up time for new equipment and

decrease production downtime while making modifications

or troubleshooting controls problems?

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 8

Top Ten S7 Tips and Tricks

Now… take your development to the next Level!

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 9

Top Ten S7 Tips and Tricks

Tips and Tricks for:

1. Rapid Diagnostics / Troubleshooting

2. Rapid Development

3. Advanced Tools

Navigating the world of automation

Modular, Object-Oriented

Architecture with FBs and UDTs

#1

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Best Practices for Controls Design – Generally Accepted

• Consistent Design and Documentation

• Mechanical Design

• Electrical Schematics

• P&IDs

• Software

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Best Practices for Controls Design… also includes:

• PLC and HMI Projects

• Naming conventions

• Hardware architecture

• Modular Software Architecture

• Function Blocks

• UDTs

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Line 1

Mixer 1

Agitator VFD

Discharge Valve

Mixer 2

Agitator VFD

Discharge Valve

Mixer 3

Agitator VFD

Discharge Valve

Ventilation

Damper

Blower Motor

Conveying

Pump Motor

Distribution Valve

System Architecture

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

fbMaster

fbMixer_1

fbVFD

fbValve

fbMixer_2

fbVFD

fbValve

fbMixer_3

fbVFD

fbValve

fbVentilation

fbDamper

fbMotor

fbConveying

fbMotor

fbValve

Program Architecture

(similar to system architecture!)

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Example of High-Level Function Block:

fbMixer_1

fbVFD fbValve

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Example of Device Level Function Block utilizing UDTs:

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Variables encapsulated by udtHMI_VFD_Control

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Variables encapsulated by udtErrors_VFD

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Modular, Object-Oriented Architecture with FBs

and UDTs

Page 19

Motor Command

Function Block

Start

Stop

Speed SP

Engage Brake

Reset Error

Acceleration

Motor I/O

Function Block

Start

Stop

Speed SP

Engage Brake

Reset Error

Acceleration

Outputs Inputs

One variable is used

to pass multiple

pieces of information

Start

Stop

Speed SP

Engage Brake

Reset Error

Acceleration

Motor Command

Function BlockCommand

Motor I/O

Function

Block

Command

Navigating the world of automation

Monitoring Instances of Function

Blocks

#2

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Monitoring Instances of Function Blocks

There are two PLC modes and they are toggled in the CPU Properties on the

“Protection” tab: Process Mode and Test Mode.

Page 21

Default is Process mode.

Switch to Test Mode.

Download the hardware configuration.

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Monitoring Instances of Function Blocks

This option is also shown in the Debug -> Operation dropdown menu from the

Ladder Editor

Page 22

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Monitoring Instances of Function Blocks

Right-click on the block and select “Monitor with Call-Up Path”

Process Mode Test Mode

Page 23

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Monitoring Instances of Function Blocks

Note!

As you probably expect, this does slow down the CPU cycle time so this should

only be used when necessary and always leave the final system with “Process

Mode” checked.

Page 24

Navigating the world of automation

Report System Error

#3

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Report System Error

Siemens Support Website

FAQ: How can you report S7 system errors in WinCC?

FAQ: How can you have system error messages from a SIMATIC S7-300 / 400

displayed in WinCC flexible?

Page 26

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Report System Error

End Result:

No (0) programming required!

Page 27

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Report System Error

10 easy steps: (website has screenshots and full instructions)

1. Create S7 and HMI stations.

2. Add languages. Set “English” as default

3. Open the "Report System Error..." dialog in hardware configuration.

4. Activate the entries. Choose the OB blocks that will generate messages

5. Transfer blocks to the CPU. Download the generated blocks to the CPU.

6. Add a connection to the CPU from the WinCC flexible project (if needed)

7. Configure alarm settings. Activate Simatic SFM in the alarm procedure.

8. Configure alarm viewer to include “S7 Alarms”

9. Activate the check boxes in CPU Messages from Simatic Manager

10.Start WinCC flexible and enjoy your diagnostic messages!

Page 28

Navigating the world of automation

RAM Disk

#4

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

RAM Disk

• When compiling an S7 project, many small files are read and written.

• RAM Disk is RAM that is used as a disk drive – via 3rd party software.

• RAM Disk is orders of magnitude faster than other forms of storage media.

• We’ve reduced >10 min compile times to <3 min.

Page 30

Navigating the world of automation

Auto-Generate Symbol Table

#5

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Auto-Generate Symbol Table

Page 32

The S7 PLC symbol table allows copy/paste directly from a spreadsheet such as

MS Excel.

• If possible, develop your IO list in a compatible format

• Alternatively, build a tool to convert it to a compatible format

• For example, thousands of IO can be added into the symbol list in a few

minutes.

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Auto-Generate Symbol Table

Page 33

Navigating the world of automation

Using Local Memory to Parse

Data

#6

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Using Local Memory to Parse Data

Split data types into smaller pieces without using ST or SCL.

1. Assign a variable to TEMP memory.

2. Move data into the TEMP memory variable.

Page 35

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Using Local Memory to Parse Data

Split data types into smaller pieces without using ST or SCL.

3. Access the TEMP or Local memory using the “L” prefix.

Page 36

Navigating the world of automation

Network Node Activating,

Deactivating, and Monitoring

#7

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Network Node Activating, Deactivating, and

Monitoring

Dynamically activate and Deactivate

Profibus and Profinet Nodes

Using “D_ACT_DP” SFC12

Examples:

• Modular Machines

• Alternate Machine Configurations

Page 38

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Network Node Activating, Deactivating, and

Monitoring

Monitoring Ethernet Nodes using “RDSYSST” SFC51

Page 39

Navigating the world of automation

Safety Programming

#8

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Safety Programming

• Leverage Siemens safety blocks

Page 41

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Safety Programming

• Safety program can be really simple or really complicated depending on the

application.

• Example of implementing simple E-Stop safety functionality:

Page 42

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Safety Programming

• Always ON and OFF variables available inside “F_GLOBDB” datablock.

Page 43

Navigating the world of automation

Backup DB Data by Generating

Source

#9

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Backup DB Data by Generating Source

A simple yet common problem when programming a Siemens Simatic S7-300

PLC is losing the data already stored in the PLC after downloading an updated

data block.

Page 45

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Backup DB Data by Generating Source

In the normal case:

If you are simply adding items to the end of a flat data block (not adding items to

a user-defined type (udt) within the data block, for example) then to retain the

values of the data block follow these quick steps.

1. Go online with all of the blocks in Simatic Manager.

2. Copy the online version of the data block whose values you would like to

retain into your offline project.

3. Add the items to end of the data block.

4. Download - your values will be retained.

Page 46

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Backup DB Data by Generating Source

A more complicated change to the data block such as adding items to a udt

used with the data block requires extra steps. Even if you have first saved a copy

of your online values prior to making the change, the values will be lost after you

save the change. Therefore, follow these extra steps.

1. Follow steps 1 and 2 above.

2. Open the datablock and Generate Source for the data block.

File -> Generate Source. This will save a version of your data block;

and the values in a file in the Sources folder.

Page 47

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Backup DB Data by Generating Source

3. Make all changes that you need to the data block (not source code)

then Save and Close the data block.

4. Open the Source file you created and compile it. This will set all values in the

data block equal to the values you see in the Source file.

5. Download - your values have been retained.

Page 48

Navigating the world of automation

Keyboard Shortcuts

#10

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Keyboard Shortcuts

Navigating / Searching

Cross Reference: Ctrl-Alt-Q

Find: Ctrl-F

Find Variables within a FC or FB: Ctrl-Shift-F (search forward)

or

Ctrl-Shift-B (search backward)

Jump to Network: Ctrl-E

Reference Data Interface: Ctrl-R

Open an FC or FB: Ctrl-Alt-O

Page 50

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Keyboard Shortcuts

Development Shortcuts

New Empty Rung / Network: Ctrl-R

Normally open contact: F2

Normally closed contact: F3

Coil: F7

Empty Box: Alt-F9

Page 51

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Keyboard Shortcuts

Monitoring / Diagnostics / Other Shortcuts

Monitor: Ctrl-F7

Module Information: Ctrl-D

Page 52

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Keyboard Shortcuts

Monitoring / Diagnostics / Other Shortcuts

Operating Mode: Ctrl-I

Download: Ctrl-L

Page 53

Navigating the world of automation

Summary

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Page 55

Summary – Top Ten S7 Tips and Tricks

1. Modular, Object-Oriented Architecture with FBs and UDTs

2. Monitoring Instances of Function Blocks

3. Report System Error

4. RAM Disk

5. Auto-Generate Symbol Table

6. Network Node Activating, Deactivating, and Monitoring

7. Safety Programming Basics

8. Using Local Memory to Parse Data

9. Backup DB Data by Generating Source

10. Keyboard Shortcuts

Navigating the world of automation

Copyright © Siemens Industry, Inc. 2011. All rights reserved.

Thank You

Nick Shea

[email protected]

www.dmcinfo.com

Page 56