PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANT L&T S&L 31.08.2011 01
EPC CONTRACTOR L&T POWER, VADODARA
CONTRACTORS CONSULTANT DCPL, KOLKATA Prepared by VVG
EBOP CONTRACTOR AREVA T&D INDIA LIMITED Checked by VVG
DOCUMENT NO. 5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 Approved by NAG
REFERENCE DRAWING:
Document No. Revision Document Name
00 245KV CVT Drawing Name Plate Details
INTERCONNECTION CABLE DETAILS FOR
220KV BUS COUPLER (BAY #01)
AREVA T&D INDIA Ltd.
MADHYA PRADESH POWER
GENERATING COMPANY LIMITED
5257PN100-MLW-E-SYD-GAD-1683 00 245KV CVT Drawing Name Plate Details
02 245KV CT Drawing Name Plate Details
02 245KV TARIFF METERING CT Drawing Name Plate Details
00 245KV CT JB TERMINAL DISTRIBUTION
00 245KV CVT JB TERMINAL DISTRIBUTION
02 245KV ISOLATOR Scheme Drawing
02 245KV CIRCUIT BREAKER Scheme Drawing
01 400KV/220KV ICT Scheme Drawing
00 PLCC Drawing (ABB)
02 AC KIOSK Drawing
02 CONTROL ROOM BUILDING PANEL ARRANGEMENT Layout
00 CABLE TRENCH Layout
02 DCDB Drawings
02 ACDB Drawings
5257PN100-MLW-E-SYD-ARR-0010
220KV ANNEXURE-1
5257PN100-MLW-E-SYD-SCH-1586
5257PN100-MLW-E-SYD-SCH-1524
5257PN100-MLW-E-SYD-SCH-3309
5257PN100-MLW-E-SYD-GAD-2501
5257PN100-MLW-E-SYD-CAB-0045
<5257PN100-MLW-E-SYD-SCH-2214>
<5257PN100-MLW-E-SYD-SCH-2214>
5257PN100-MLW-E-SYD-GAD-1683
5257PN100-MLW-E-SYD-GAD-1633
220KV ANNEXURE-1
5257PN100-MLW-E-SYD-GAD-1633
LTSSTPP-AREVA-DWG-E-0011
02 ACDB Drawings
01 BMK Drawings
02 220KV CRP SCHEMATICS OF BUS COUPLER PROTECTION PANEL
01 220KV CRP SCHEMATICS OF BUS COUPLER & ICT#01 CONTROL PANEL
02 220KV CRP SCHEMATICS OF BUS BAR PROTECTION
02 220KV CRP SCHEMATICS OF ISLANDING PROTECTION
CABLE NUMBERING SYSTEM
2 01 1 001
CABLE SL. NO. STARTING FROM 001
AND INCREMENT SUBSEQUENTLY
<5257PN100-MLW-E-SYD-SCH-2103>
5257PN100-MLW-E-SYD-GAD-2396 & SCH-2397
5257PN100-MLW-E-SYD-GAD-2354 & SCH-2355
5257PN100-MLW-E-SYD-GAD-2372 & SCH-2373
5257PN100-MLW-E-SYD-GAD-2370 & SCH-2371
<5257PN100-MLW-E-SYD-SCH-2214>
AND INCREMENT SUBSEQUENTLY
THIS FIELD WILL BE SELECTED ON FOLLOWING CONDITIONS:
1 FOR CABLES WITHIN SWYD EQUIPMENTS.
2 FOR CABLES FROM SWYD EQPT/BMK/JB TO CONTROL & RELAY PANEL
3 FOR CABLES WITHIN CONTROL AND RELAY PANLES
4 AC/DC POWER CABLE FOR CRP/PLCC/RTCC.
BAY NUMBER (01)
SWITCHYARD
7 FOR 765KV SWYD
4 FOR 400KV SWYD
2 FOR 220KV SWYD
Note : 1 FOR 132/110KV SWYD
a) Loop length after glanding shall be sum of width & height of panel/Equipment cubicle. 6 FOR 66KV SWYD a) Loop length after glanding shall be sum of width & height of panel/Equipment cubicle. 6 FOR 66KV SWYD
b) Drum details/actual length shall be filled prior to cable laying at site 3 FOR 33KV SWYD
c) Drum cutting schedule to be prepared by site Engineer prior to cable laying/cutting. 9 FOR 11KV SWYD
5 FOR AUX.SYSTEM
1 OF 18
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
CT -- CT--
1 2 01 1001 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R1S1 TB1-1 2-1 CTA JB-TB1-1 / R1S1 2-1 CTA-R-R1S1 / TB1-1 CORE-1 CPD KN17 SC51 SHT02
3.4 R1S2 TB1-2 2-1 CTA JB-TB1-2 / R1S2 2-1 CTA-R-R1S2 / TB1-2 CPD KN17 SC51 SHT02
5,6 R1S3 TB1-3 2-1 CTA JB-TB1-3 / R1S3 2-1 CTA-R-R1S3 / TB1-3 CPD KN17 SC51 SHT02
7,8 R1S4 TB1-4 2-1 CTA JB-TB1-4 / R1S4 2-1 CTA-R-R1S4 / TB1-4 CPD KN17 SC51 SHT02
9,10 SPARE
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
9,10 SPARE
2 2 01 1002 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R2S1 TB2-1 2-1 CTA JB-TB2-1 / R2S1 2-1 CTA-R-R2S1 / TB2-1 CORE-2 CPD KN17 SC51 SHT02
3.4 R2S2 TB2-2 2-1 CTA JB-TB2-2 / R2S2 2-1 CTA-R-R2S2 / TB2-2 CPD KN17 SC51 SHT02
5,6 R2S3 TB2-3 2-1 CTA JB-TB2-3 / R2S3 2-1 CTA-R-R2S3 / TB2-3 CPD KN17 SC51 SHT02
7,8 R2S4 TB2-4 2-1 CTA JB-TB2-4 / R2S4 2-1 CTA-R-R2S4 / TB2-4 CPD KN17 SC51 SHT02
9,10 SPARE
3 2 01 1003 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R3S1 TB3-1 2-1 CTA JB-TB3-1 / R3S1 2-1 CTA-R-R3S1 / TB3-1 CORE-3 CPD KN17 SC51 SHT02
3.4 R3S2 TB3-2 2-1 CTA JB-TB3-2 / R3S2 2-1 CTA-R-R3S2 / TB3-2 CPD KN17 SC51 SHT02
5,6 R3S3 TB3-3 2-1 CTA JB-TB3-3 / R3S3 2-1 CTA-R-R3S3 / TB3-3 CPD KN17 SC51 SHT02
7,8 R3S4 TB3-4 2-1 CTA JB-TB3-4 / R3S4 2-1 CTA-R-R3S4 / TB3-4 CPD KN17 SC51 SHT02
9,10 SPARE
4 2 01 1004 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R4S1 TB4-1 2-1 CTA JB-TB4-1 / R4S1 2-1 CTA-R-R4S1 / TB4-1 CORE-4 CPD KN17 SC51 SHT02
3.4 R4S2 TB4-2 2-1 CTA JB-TB4-2 / R4S2 2-1 CTA-R-R4S2 / TB4-2 CPD KN17 SC51 SHT02
5,6 R4S4 TB4-3 2-1 CTA JB-TB4-3 / R4S4 2-1 CTA-R-R4S4 / TB4-3 CPD KN17 SC51 SHT02
7,8 R4S4 TB4-4 2-1 CTA JB-TB4-4 / R4S4 2-1 CTA-R-R4S4 / TB4-4 CPD KN17 SC51 SHT02
9,10 SPARE
5 2 01 1005 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R5S1 TB5-1 2-1 CTA JB-TB5-1 / R5S1 2-1 CTA-R-R5S1 / TB5-1 CORE-5 CPD KN17 SC51 SHT02
3.4 R5S2 TB5-2 2-1 CTA JB-TB5-2 / R5S2 2-1 CTA-R-R5S2 / TB5-2 CPD KN17 SC51 SHT02
5,6 R5S5 TB5-3 2-1 CTA JB-TB5-3 / R5S5 2-1 CTA-R-R5S5 / TB5-3 CPD KN17 SC51 SHT025,6 R5S5 TB5-3 2-1 CTA JB-TB5-3 / R5S5 2-1 CTA-R-R5S5 / TB5-3 CPD KN17 SC51 SHT02
7,8 R5S5 TB5-4 2-1 CTA JB-TB5-4 / R5S5 2-1 CTA-R-R5S5 / TB5-4 CPD KN17 SC51 SHT02
9,10 SPARE
6 2 01 1006 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y1S1 TB1-5 2-1 CTA JB-TB1-5 / Y1S1 2-1 CTA-Y-Y1S1 / TB1-5 CORE-1 CPD KN17 SC51 SHT02
3.4 Y1S2 TB1-6 2-1 CTA JB-TB1-6 / Y1S2 2-1 CTA-Y-Y1S2 / TB1-6 CPD KN17 SC51 SHT02
5,6 Y1S3 TB1-7 2-1 CTA JB-TB1-7 / Y1S3 2-1 CTA-Y-Y1S3 / TB1-7 CPD KN17 SC51 SHT02
7,8 Y1S4 TB1-8 2-1 CTA JB-TB1-8 / Y1S4 2-1 CTA-Y-Y1S4 / TB1-8 CPD KN17 SC51 SHT02
9,10 SPARE
7 2 01 1007 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y2S1 TB2-5 2-1 CTA JB-TB2-5 / Y2S1 2-1 CTA-Y-Y2S1 / TB2-5 CORE-2 CPD KN17 SC51 SHT02
3.4 Y2S2 TB2-6 2-1 CTA JB-TB2-6 / Y2S2 2-1 CTA-Y-Y2S2 / TB2-6 CPD KN17 SC51 SHT02
5,6 Y2S3 TB2-7 2-1 CTA JB-TB2-7 / Y2S3 2-1 CTA-Y-Y2S3 / TB2-7 CPD KN17 SC51 SHT02
7,8 Y2S4 TB2-8 2-1 CTA JB-TB2-8 / Y2S4 2-1 CTA-Y-Y2S4 / TB2-8 CPD KN17 SC51 SHT02
9,10 SPARE
8 2 01 1008 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y3S1 TB3-5 2-1 CTA JB-TB3-5 / Y3S1 2-1 CTA-Y-Y3S1 / TB3-5 CORE-3 CPD KN17 SC51 SHT02
3.4 Y3S2 TB3-6 2-1 CTA JB-TB3-6 / Y3S2 2-1 CTA-Y-Y3S2 / TB3-6 CPD KN17 SC51 SHT02
5,6 Y3S3 TB3-7 2-1 CTA JB-TB3-7 / Y3S3 2-1 CTA-Y-Y3S3 / TB3-7 CPD KN17 SC51 SHT02
7,8 Y3S4 TB3-8 2-1 CTA JB-TB3-8 / Y3S4 2-1 CTA-Y-Y3S4 / TB3-8 CPD KN17 SC51 SHT02
9,10 SPARE
9 2 01 1009 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y4S1 TB4-5 2-1 CTA JB-TB4-5 / Y4S1 2-1 CTA-Y-Y4S1 / TB4-5 CORE-4 CPD KN17 SC51 SHT02
3.4 Y4S2 TB4-6 2-1 CTA JB-TB4-6 / Y4S2 2-1 CTA-Y-Y4S2 / TB4-6 CPD KN17 SC51 SHT02
5,6 Y4S3 TB4-7 2-1 CTA JB-TB4-7 / Y4S3 2-1 CTA-Y-Y4S3 / TB4-7 CPD KN17 SC51 SHT02
7,8 Y4S4 TB4-8 2-1 CTA JB-TB4-8 / Y4S4 2-1 CTA-Y-Y4S4 / TB4-8 CPD KN17 SC51 SHT02
9,10 SPARE
10 2 01 1010 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y5S1 TB5-5 2-1 CTA JB-TB5-5 / Y5S1 2-1 CTA-Y-Y5S1 / TB5-5 CORE-5 CPD KN17 SC51 SHT02
3.4 Y5S2 TB5-6 2-1 CTA JB-TB5-6 / Y5S2 2-1 CTA-Y-Y5S2 / TB5-6 CPD KN17 SC51 SHT02
5,6 Y5S3 TB5-7 2-1 CTA JB-TB5-7 / Y5S3 2-1 CTA-Y-Y5S3 / TB5-7 CPD KN17 SC51 SHT02
7,8 Y5S4 TB5-8 2-1 CTA JB-TB5-8 / Y5S4 2-1 CTA-Y-Y5S4 / TB5-8 CPD KN17 SC51 SHT02
9,10 SPARE
11 2 01 1011 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B1S1 TB1-9 2-1 CTA JB-TB1-9 / B1S1 2-1 CTA-B-B1S1 / TB1-9 CORE-1 CPD KN17 SC51 SHT02
3.4 B1S2 TB1-10 2-1 CTA JB-TB1-10 / B1S2 2-1 CTA-B-B1S2 / TB1-10 CPD KN17 SC51 SHT02
5,6 B1S3 TB1-11 2-1 CTA JB-TB1-11 / B1S3 2-1 CTA-B-B1S3 / TB1-11 CPD KN17 SC51 SHT02
7,8 B1S4 TB1-12 2-1 CTA JB-TB1-12 / B1S4 2-1 CTA-B-B1S4 / TB1-12 CPD KN17 SC51 SHT02
9,10 SPARE
12 2 01 1012 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B2S1 TB2-9 2-1 CTA JB-TB2-9 / B2S1 2-1 CTA-B-B2S1 / TB2-9 CORE-2 CPD KN17 SC51 SHT02
3.4 B2S2 TB2-10 2-1 CTA JB-TB2-10 / B2S2 2-1 CTA-B-B2S2 / TB2-10 CPD KN17 SC51 SHT02
5,6 B2S3 TB2-11 2-1 CTA JB-TB2-11 / B2S3 2-1 CTA-B-B2S3 / TB2-11 CPD KN17 SC51 SHT02
7,8 B2S4 TB2-12 2-1 CTA JB-TB2-12 / B2S4 2-1 CTA-B-B2S4 / TB2-12 CPD KN17 SC51 SHT027,8 B2S4 TB2-12 2-1 CTA JB-TB2-12 / B2S4 2-1 CTA-B-B2S4 / TB2-12 CPD KN17 SC51 SHT02
9,10 SPARE
201-BUS COUPLER_05.09.2011 Page 2 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
13 2 01 1013 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B3S1 TB3-9 2-1 CTA JB-TB3-9 / B3S1 2-1 CTA-B-B3S1 / TB3-9 CORE-3 CPD KN17 SC51 SHT02
3.4 B3S2 TB3-10 2-1 CTA JB-TB3-10 / B3S2 2-1 CTA-B-B3S2 / TB3-10 CPD KN17 SC51 SHT02
5,6 B3S3 TB3-11 2-1 CTA JB-TB3-11 / B3S3 2-1 CTA-B-B3S3 / TB3-11 CPD KN17 SC51 SHT02
7,8 B3S4 TB3-12 2-1 CTA JB-TB3-12 / B3S4 2-1 CTA-B-B3S4 / TB3-12 CPD KN17 SC51 SHT02
9,10 SPARE
14 2 01 1014 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B4S1 TB4-9 2-1 CTA JB-TB4-9 / B4S1 2-1 CTA-B-B4S1 / TB4-9 CORE-4 CPD KN17 SC51 SHT02
3.4 B4S2 TB4-10 2-1 CTA JB-TB4-10 / B4S2 2-1 CTA-B-B4S2 / TB4-10 CPD KN17 SC51 SHT02
5,6 B4S3 TB4-11 2-1 CTA JB-TB4-11 / B4S3 2-1 CTA-B-B4S3 / TB4-11 CPD KN17 SC51 SHT02
7,8 B4S4 TB4-12 2-1 CTA JB-TB4-12 / B4S4 2-1 CTA-B-B4S4 / TB4-12 CPD KN17 SC51 SHT02
9,10 SPARE
15 2 01 1015 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B5S1 TB5-9 2-1 CTA JB-TB5-9 / B5S1 2-1 CTA-B-B5S1 / TB5-9 CORE-5 CPD KN17 SC51 SHT02
3.4 B5S2 TB5-10 2-1 CTA JB-TB5-10 / B5S2 2-1 CTA-B-B5S2 / TB5-10 CPD KN17 SC51 SHT02
5,6 B5S3 TB5-11 2-1 CTA JB-TB5-11 / B5S3 2-1 CTA-B-B5S3 / TB5-11 CPD KN17 SC51 SHT02
7,8 B5S4 TB5-12 2-1 CTA JB-TB5-12 / B5S4 2-1 CTA-B-B5S4 / TB5-12 CPD KN17 SC51 SHT02
9,10 SPARE
BCVT
16 2 01 1016 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R1a1 TB1-1 2-1 CVT JB-TB1-1 / R1a1 2- B1CVT-R-R1a1 / TB1-1 WDG-1 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 R1n TB1-3 2-1 CVT JB-TB1-3 / R1n 2- B1CVT-R-R1n / TB1-3 CPD KN17 SC51 SHT07
7 SPARE
17 2 01 1017 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R2a1 TB2-1 2-1 CVT JB-TB2-1 / R2a1 2- B1CVT-R-R2a1 / TB2-1 WDG-2 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 R2n TB2-3 2-1 CVT JB-TB2-3 / R2n 2- B1CVT-R-R2n / TB2-3 CPD KN17 SC51 SHT07
7 SPARE
18 2 01 1018 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R3a1 TB3-1 2-1 CVT JB-TB3-1 / R3a1 2- B1CVT-R-R3a1 / TB3-1 WDG-3 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 R3n TB3-3 2-1 CVT JB-TB3-3 / R3n 2- B1CVT-R-R3n / TB3-3 CPD KN17 SC51 SHT07
7 SPARE
19 2 01 1019 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R4a1 TB4-1 2-1 CVT JB-TB4-1 / R4a1 2- B1CVT-R-R4a1 / TB4-1 WDG-4 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 R4n TB4-3 2-1 CVT JB-TB4-3 / R4n 2- B1CVT-R-R4n / TB4-3 CPD KN17 SC51 SHT07
7 SPARE
20 2 01 1020 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y1a1 TB1-4 2-1 CVT JB-TB1-4 / Y1a1 2- B1CVT-Y-Y1a1 / TB1-4 WDG-1 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 Y1n TB1-6 2-1 CVT JB-TB1-6 / Y1n 2- B1CVT-Y-Y1n / TB1-6 CPD KN17 SC51 SHT07
7 SPARE
21 2 01 1021 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y2a1 TB2-4 2-1 CVT JB-TB2-4 / Y2a1 2- B1CVT-Y-Y2a1 / TB2-4 WDG-2 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 Y2n TB2-6 2-1 CVT JB-TB2-6 / Y2n 2- B1CVT-Y-Y2n / TB2-6 CPD KN17 SC51 SHT07
7 SPARE
22 2 01 1022 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y3a1 TB3-4 2-1 CVT JB-TB3-4 / Y3a1 2- B1CVT-Y-Y3a1 / TB3-4 WDG-3 CPD KN17 SC51 SHT0722 2 01 1022 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y3a1 TB3-4 2-1 CVT JB-TB3-4 / Y3a1 2- B1CVT-Y-Y3a1 / TB3-4 WDG-3 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 Y3n TB3-6 2-1 CVT JB-TB3-6 / Y3n 2- B1CVT-Y-Y3n / TB3-6 CPD KN17 SC51 SHT07
7 SPARE
23 2 01 1023 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y4a1 TB4-4 2-1 CVT JB-TB4-4 / Y4a1 2- B1CVT-Y-Y4a1 / TB4-4 WDG-4 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 Y4n TB4-6 2-1 CVT JB-TB4-6 / Y4n 2- B1CVT-Y-Y4n / TB4-6 CPD KN17 SC51 SHT07
7 SPARE
24 2 01 1024 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B1a1 TB1-7 2-1 CVT JB-TB1-7 / B1a1 2- B1CVT-B-B1a1 / TB1-7 WDG-1 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 B1n TB1-9 2-1 CVT JB-TB1-9 / B1n 2- B1CVT-B-B1n / TB1-9 CPD KN17 SC51 SHT07
7 SPARE
25 2 01 1025 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B2a1 TB2-7 2-1 CVT JB-TB2-7 / B2a1 2- B1CVT-B-B2a1 / TB2-7 WDG-2 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 B2n TB2-9 2-1 CVT JB-TB2-9 / B2n 2- B1CVT-B-B2n / TB2-9 CPD KN17 SC51 SHT07
7 SPARE
26 2 01 1026 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B3a1 TB3-7 2-1 CVT JB-TB3-7 / B3a1 2- B1CVT-B-B3a1 / TB3-7 WDG-3 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 B3n TB3-9 2-1 CVT JB-TB3-9 / B3n 2- B1CVT-B-B3n / TB3-9 CPD KN17 SC51 SHT075,6 B3n TB3-9 2-1 CVT JB-TB3-9 / B3n 2- B1CVT-B-B3n / TB3-9 CPD KN17 SC51 SHT07
7 SPARE
201-BUS COUPLER_05.09.2011 Page 3 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
27 2 01 1027 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B4a1 TB4-7 2-1 CVT JB-TB4-7 / B4a1 2- B1CVT-B-B4a1 / TB4-7 WDG-4 CPD KN17 SC51 SHT07
3,4 SPARE CPD KN17 SC51 SHT07
5,6 B4n TB4-9 2-1 CVT JB-TB4-9 / B4n 2- B1CVT-B-B4n / TB4-9 CPD KN17 SC51 SHT07
7 SPARE
28 2 01 1028 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R1a1 TB1-1 2-2 CVT JB-TB1-1 / R1a1 2- B2CVT-R-R1a1 / TB1-1 WDG-1 CPD KN17 SC51 SHT0828 2 01 1028 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R1a1 TB1-1 2-2 CVT JB-TB1-1 / R1a1 2- B2CVT-R-R1a1 / TB1-1 WDG-1 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 R1n TB1-3 2-2 CVT JB-TB1-3 / R1n 2- B2CVT-R-R1n / TB1-3 CPD KN17 SC51 SHT08
7 SPARE
29 2 01 1029 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R2a1 TB2-1 2-2 CVT JB-TB2-1 / R2a1 2- B2CVT-R-R2a1 / TB2-1 WDG-2 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 R2n TB2-3 2-2 CVT JB-TB2-3 / R2n 2- B2CVT-R-R2n / TB2-3 CPD KN17 SC51 SHT08
7 SPARE
30 2 01 1030 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R3a1 TB3-1 2-2 CVT JB-TB3-1 / R3a1 2- B2CVT-R-R3a1 / TB3-1 WDG-3 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 R3n TB3-3 2-2 CVT JB-TB3-3 / R3n 2- B2CVT-R-R3n / TB3-3 CPD KN17 SC51 SHT08
7 SPARE
31 2 01 1031 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R4a1 TB4-1 2-2 CVT JB-TB4-1 / R4a1 2- B2CVT-R-R4a1 / TB4-1 WDG-4 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 R4n TB4-3 2-2 CVT JB-TB4-3 / R4n 2- B2CVT-R-R4n / TB4-3 CPD KN17 SC51 SHT08
7 SPARE
32 2 01 1032 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y1a1 TB1-4 2-2 CVT JB-TB1-4 / Y1a1 2- B2CVT-Y-Y1a1 / TB1-4 WDG-1 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT083,4 SPARE CPD KN17 SC51 SHT08
5,6 Y1n TB1-6 2-2 CVT JB-TB1-6 / Y1n 2- B2CVT-Y-Y1n / TB1-6 CPD KN17 SC51 SHT08
7 SPARE
33 2 01 1033 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y2a1 TB2-4 2-2 CVT JB-TB2-4 / Y2a1 2- B2CVT-Y-Y2a1 / TB2-4 WDG-2 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 Y2n TB2-6 2-2 CVT JB-TB2-6 / Y2n 2- B2CVT-Y-Y2n / TB2-6 CPD KN17 SC51 SHT08
7 SPARE
34 2 01 1034 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y3a1 TB3-4 2-2 CVT JB-TB3-4 / Y3a1 2- B2CVT-Y-Y3a1 / TB3-4 WDG-3 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 Y3n TB3-6 2-2 CVT JB-TB3-6 / Y3n 2- B2CVT-Y-Y3n / TB3-6 CPD KN17 SC51 SHT08
7 SPARE
35 2 01 1035 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y4a1 TB4-4 2-2 CVT JB-TB4-4 / Y4a1 2- B2CVT-Y-Y4a1 / TB4-4 WDG-4 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 Y4n TB4-6 2-2 CVT JB-TB4-6 / Y4n 2- B2CVT-Y-Y4n / TB4-6 CPD KN17 SC51 SHT08
7 SPARE
36 2 01 1036 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B1a1 TB1-7 2-2 CVT JB-TB1-7 / B1a1 2- B2CVT-B-B1a1 / TB1-7 WDG-1 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 B1n TB1-9 2-2 CVT JB-TB1-9 / B1n 2- B2CVT-B-B1n / TB1-9 CPD KN17 SC51 SHT08
7 SPARE7 SPARE
37 2 01 1037 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B2a1 TB2-7 2-2 CVT JB-TB2-7 / B2a1 2- B2CVT-B-B2a1 / TB2-7 WDG-2 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 B2n TB2-9 2-2 CVT JB-TB2-9 / B2n 2- B2CVT-B-B2n / TB2-9 CPD KN17 SC51 SHT08
7 SPARE
38 2 01 1038 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B3a1 TB3-7 2-2 CVT JB-TB3-7 / B3a1 2- B2CVT-B-B3a1 / TB3-7 WDG-3 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 B3n TB3-9 2-2 CVT JB-TB3-9 / B3n 2- B2CVT-B-B3n / TB3-9 CPD KN17 SC51 SHT08
7 SPARE
39 2 01 1039 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B4a1 TB4-7 2-2 CVT JB-TB4-7 / B4a1 2- B2CVT-B-B4a1 / TB4-7 WDG-4 CPD KN17 SC51 SHT08
3,4 SPARE CPD KN17 SC51 SHT08
5,6 B4n TB4-9 2-2 CVT JB-TB4-9 / B4n 2- B2CVT-B-B4n / TB4-9 CPD KN17 SC51 SHT08
7 SPARE
201-BUS COUPLER_05.09.2011 Page 4 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
CB INTERPOLE CABLING
40 2 01 1040 CB-R CBCC 19CX2.5 1 20 1 TB1-10 TB1-10 CBCC-TB1-10 / TB1-10 CB-R-TB1-10 / TB1-10 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03
2 TB1-16 TB1-16 CBCC-TB1-16 / TB1-16 CB-R-TB1-16 / TB1-16 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03
3 TB1-9 TB1-9 CBCC-TB1-9 / TB1-9 CB-R-TB1-9 / TB1-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03
4 TB1-11 TB1-11 CBCC-TB1-11 / TB1-11 CB-R-TB1-11 / TB1-11 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03
5 TB1-14 TB1-14 CBCC-TB1-14 / TB1-14 CB-R-TB1-14 / TB1-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03 5 TB1-14 TB1-14 CBCC-TB1-14 / TB1-14 CB-R-TB1-14 / TB1-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
6 TB1-17 TB1-17 CBCC-TB1-17 / TB1-17 CB-R-TB1-17 / TB1-17 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
7 TB1-19 TB1-19 CBCC-TB1-19 / TB1-19 CB-R-TB1-19 / TB1-19 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
8 TB1-7 TB1-7 CBCC-TB1-7 / TB1-7 CB-R-TB1-7 / TB1-7 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
9 TB1-8 TB1-8 CBCC-TB1-8 / TB1-8 CB-R-TB1-8 / TB1-8 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
10 TB1-18 TB1-18 CBCC-TB1-18 / TB1-18 CB-R-TB1-18 / TB1-18 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
11 TB1-12 TB1-12 CBCC-TB1-12 / TB1-12 CB-R-TB1-12 / TB1-12 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
12 TB1-13 TB1-13 CBCC-TB1-13 / TB1-13 CB-R-TB1-13 / TB1-13 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
13 TB1-15 TB1-15 CBCC-TB1-15 / TB1-15 CB-R-TB1-15 / TB1-15 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
41 2 01 1041 CB-R CBCC 19CX2.5 1 20 1 TB1-22 TB1-22 CBCC-TB1-22 / TB1-22 CB-R-TB1-22 / TB1-22 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
2 TB1-23 TB1-23 CBCC-TB1-23 / TB1-23 CB-R-TB1-23 / TB1-23 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
3 TB1-26 TB1-26 CBCC-TB1-26 / TB1-26 CB-R-TB1-26 / TB1-26 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
4 TB1-24 TB1-24 CBCC-TB1-24 / TB1-24 CB-R-TB1-24 / TB1-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05
5 TB1-25 TB1-25 CBCC-TB1-25 / TB1-25 CB-R-TB1-25 / TB1-25 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05
6 TB1-29 TB1-29 CBCC-TB1-29 / TB1-29 CB-R-TB1-29 / TB1-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06
7 TB1-30 TB1-30 CBCC-TB1-30 / TB1-30 CB-R-TB1-30 / TB1-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06 7 TB1-30 TB1-30 CBCC-TB1-30 / TB1-30 CB-R-TB1-30 / TB1-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06
8 TB1-31 TB1-31 CBCC-TB1-31 / TB1-31 CB-R-TB1-31 / TB1-31 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06
9 TB1-32 TB1-32 CBCC-TB1-32 / TB1-32 CB-R-TB1-32 / TB1-32 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06
10 TB1-33 TB1-33 CBCC-TB1-33 / TB1-33 CB-R-TB1-33 / TB1-33 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06
11 TB1-34 TB1-34 CBCC-TB1-34 / TB1-34 CB-R-TB1-34 / TB1-34 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06
12 TB1-27 TB1-27 CBCC-TB1-27 / TB1-27 CB-R-TB1-27 / TB1-27 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06
13 TB1-28 TB1-28 CBCC-TB1-28 / TB1-28 CB-R-TB1-28 / TB1-28 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
42 2 01 1042 CB-R CBCC 24CX2.5 1 20 1 TB2-1 TB5-1 CBCC-TB5-1 / TB2-1 CB-R-TB2-1 / TB5-1 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
2 TB2-2 TB5-2 CBCC-TB5-2 / TB2-2 CB-R-TB2-2 / TB5-2 5257PN100-MLW-E-SYD-SCH-1524 SHT08
3 TB2-3 TB5-3 CBCC-TB5-3 / TB2-3 CB-R-TB2-3 / TB5-3 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
4 TB2-4 TB5-4 CBCC-TB5-4 / TB2-4 CB-R-TB2-4 / TB5-4 5257PN100-MLW-E-SYD-SCH-1524 SHT08
5 TB2-5 TB5-5 CBCC-TB5-5 / TB2-5 CB-R-TB2-5 / TB5-5 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
6 TB2-6 TB5-6 CBCC-TB5-6 / TB2-6 CB-R-TB2-6 / TB5-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08
7 TB2-7 TB5-7 CBCC-TB5-7 / TB2-7 CB-R-TB2-7 / TB5-7 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
8 TB2-8 TB5-8 CBCC-TB5-8 / TB2-8 CB-R-TB2-8 / TB5-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08 8 TB2-8 TB5-8 CBCC-TB5-8 / TB2-8 CB-R-TB2-8 / TB5-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08
9 TB2-9 TB5-9 CBCC-TB5-9 / TB2-9 CB-R-TB2-9 / TB5-9 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
10 TB2-10 TB5-10 CBCC-TB5-10 / TB2-10 CB-R-TB2-10 / TB5-10 5257PN100-MLW-E-SYD-SCH-1524 SHT08
11 TB2-11 TB5-11 CBCC-TB5-11 / TB2-11 CB-R-TB2-11 / TB5-11 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
12 TB2-12 TB5-12 CBCC-TB5-12 / TB2-12 CB-R-TB2-12 / TB5-12 5257PN100-MLW-E-SYD-SCH-1524 SHT08
13 TB2-13 TB5-13 CBCC-TB5-13 / TB2-13 CB-R-TB2-13 / TB5-13 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
14 TB2-14 TB5-14 CBCC-TB5-14 / TB2-14 CB-R-TB2-14 / TB5-14 5257PN100-MLW-E-SYD-SCH-1524 SHT08
15 TB2-15 TB5-15 CBCC-TB5-15 / TB2-15 CB-R-TB2-15 / TB5-15 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
16 TB2-16 TB5-16 CBCC-TB5-16 / TB2-16 CB-R-TB2-16 / TB5-16 5257PN100-MLW-E-SYD-SCH-1524 SHT08
17 TB2-33 TB5-33 CBCC-TB5-33 / TB2-33 CB-R-TB2-33 / TB5-33 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
18 TB2-34 TB5-34 CBCC-TB5-34 / TB2-34 CB-R-TB2-34 / TB5-34 5257PN100-MLW-E-SYD-SCH-1524 SHT08
19 TB2-35 TB5-35 CBCC-TB5-35 / TB2-35 CB-R-TB2-35 / TB5-35 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
20 TB2-36 TB5-36 CBCC-TB5-36 / TB2-36 CB-R-TB2-36 / TB5-36
21 SPARE
22 SPARE
23 SPARE
24 SPARE
201-BUS COUPLER_05.09.2011 Page 5 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
43 2 01 1043 CB-R CBCC 24CX2.5 1 20 1 TB2-17 TB5-17 CBCC-TB5-17 / TB2-17 CB-R-TB2-17 / TB5-17 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
2 TB2-18 TB5-18 CBCC-TB5-18 / TB2-18 CB-R-TB2-18 / TB5-18 5257PN100-MLW-E-SYD-SCH-1524 SHT08
3 TB2-19 TB5-19 CBCC-TB5-19 / TB2-19 CB-R-TB2-19 / TB5-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
4 TB2-20 TB5-20 CBCC-TB5-20 / TB2-20 CB-R-TB2-20 / TB5-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08
5 TB2-21 TB5-21 CBCC-TB5-21 / TB2-21 CB-R-TB2-21 / TB5-21 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
6 TB2-22 TB5-22 CBCC-TB5-22 / TB2-22 CB-R-TB2-22 / TB5-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08 6 TB2-22 TB5-22 CBCC-TB5-22 / TB2-22 CB-R-TB2-22 / TB5-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08
7 TB2-23 TB5-23 CBCC-TB5-23 / TB2-23 CB-R-TB2-23 / TB5-23 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
8 TB2-24 TB5-24 CBCC-TB5-24 / TB2-24 CB-R-TB2-24 / TB5-24 5257PN100-MLW-E-SYD-SCH-1524 SHT08
9 TB2-25 TB5-25 CBCC-TB5-25 / TB2-25 CB-R-TB2-25 / TB5-25 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
10 TB2-26 TB5-26 CBCC-TB5-26 / TB2-26 CB-R-TB2-26 / TB5-26 5257PN100-MLW-E-SYD-SCH-1524 SHT08
11 TB2-27 TB5-27 CBCC-TB5-27 / TB2-27 CB-R-TB2-27 / TB5-27 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
12 TB2-28 TB5-28 CBCC-TB5-28 / TB2-28 CB-R-TB2-28 / TB5-28 5257PN100-MLW-E-SYD-SCH-1524 SHT08
13 TB2-29 TB5-29 CBCC-TB5-29 / TB2-29 CB-R-TB2-29 / TB5-29 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
14 TB2-30 TB5-30 CBCC-TB5-30 / TB2-30 CB-R-TB2-30 / TB5-30 5257PN100-MLW-E-SYD-SCH-1524 SHT08
15 TB2-31 TB5-31 CBCC-TB5-31 / TB2-31 CB-R-TB2-31 / TB5-31 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
16 TB2-32 TB5-32 CBCC-TB5-32 / TB2-32 CB-R-TB2-32 / TB5-32 5257PN100-MLW-E-SYD-SCH-1524 SHT08
17 TB2-37 TB5-37 CBCC-TB5-37 / TB2-37 CB-R-TB2-37 / TB5-37 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
18 TB2-38 TB5-38 CBCC-TB5-38 / TB2-38 CB-R-TB2-38 / TB5-38 5257PN100-MLW-E-SYD-SCH-1524 SHT08
19 TB2-39 TB5-39 CBCC-TB5-39 / TB2-39 CB-R-TB2-39 / TB5-39 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
20 TB2-40 TB5-40 CBCC-TB5-40 / TB2-40 CB-R-TB2-40 / TB5-40
21 SPARE
22 SPARE
23 SPARE
24 SPARE
44 2 01 1044 CB-Y CBCC 19CX2.5 1 15 1 TB1-10 TB2-10 CBCC-TB2-10 / TB1-10 CB-Y-TB1-10 / TB2-10 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03
2 TB1-16 TB2-16 CBCC-TB2-16 / TB1-16 CB-Y-TB1-16 / TB2-16 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03
3 TB1-9 TB2-9 CBCC-TB2-9 / TB1-9 CB-Y-TB1-9 / TB2-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03 3 TB1-9 TB2-9 CBCC-TB2-9 / TB1-9 CB-Y-TB1-9 / TB2-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03
4 TB1-11 TB2-11 CBCC-TB2-11 / TB1-11 CB-Y-TB1-11 / TB2-11 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03
5 TB1-14 TB2-14 CBCC-TB2-14 / TB1-14 CB-Y-TB1-14 / TB2-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
6 TB1-17 TB2-17 CBCC-TB2-17 / TB1-17 CB-Y-TB1-17 / TB2-17 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
7 TB1-19 TB2-19 CBCC-TB2-19 / TB1-19 CB-Y-TB1-19 / TB2-19 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
8 TB1-7 TB2-7 CBCC-TB2-7 / TB1-7 CB-Y-TB1-7 / TB2-7 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
9 TB1-8 TB2-8 CBCC-TB2-8 / TB1-8 CB-Y-TB1-8 / TB2-8 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
10 TB1-18 TB2-18 CBCC-TB2-18 / TB1-18 CB-Y-TB1-18 / TB2-18 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
11 TB1-12 TB2-12 CBCC-TB2-12 / TB1-12 CB-Y-TB1-12 / TB2-12 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
12 TB1-13 TB2-13 CBCC-TB2-13 / TB1-13 CB-Y-TB1-13 / TB2-13 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
13 TB1-15 TB2-15 CBCC-TB2-15 / TB1-15 CB-Y-TB1-15 / TB2-15 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
45 2 01 1045 CB-Y CBCC 19CX2.5 1 15 1 TB1-22 TB2-22 CBCC-TB2-22 / TB1-22 CB-Y-TB1-22 / TB2-22 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
2 TB1-23 TB2-23 CBCC-TB2-23 / TB1-23 CB-Y-TB1-23 / TB2-23 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
3 TB1-26 TB2-26 CBCC-TB2-26 / TB1-26 CB-Y-TB1-26 / TB2-26 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
4 TB1-24 TB2-24 CBCC-TB2-24 / TB1-24 CB-Y-TB1-24 / TB2-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05 4 TB1-24 TB2-24 CBCC-TB2-24 / TB1-24 CB-Y-TB1-24 / TB2-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05
5 TB1-25 TB2-25 CBCC-TB2-25 / TB1-25 CB-Y-TB1-25 / TB2-25 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05
6 TB1-29 TB2-29 CBCC-TB2-29 / TB1-29 CB-Y-TB1-29 / TB2-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06
7 TB1-30 TB2-30 CBCC-TB2-30 / TB1-30 CB-Y-TB1-30 / TB2-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06
8 TB1-31 TB2-31 CBCC-TB2-31 / TB1-31 CB-Y-TB1-31 / TB2-31 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06
9 TB1-32 TB2-32 CBCC-TB2-32 / TB1-32 CB-Y-TB1-32 / TB2-32 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06
10 TB1-33 TB2-33 CBCC-TB2-33 / TB1-33 CB-Y-TB1-33 / TB2-33 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06
11 TB1-34 TB2-34 CBCC-TB2-34 / TB1-34 CB-Y-TB1-34 / TB2-34 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06
12 TB1-27 TB2-27 CBCC-TB2-27 / TB1-27 CB-Y-TB1-27 / TB2-27 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06
13 TB1-28 TB2-28 CBCC-TB2-28 / TB1-28 CB-Y-TB1-28 / TB2-28 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
201-BUS COUPLER_05.09.2011 Page 6 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
46 2 01 1046 CB-Y CBCC 24CX2.5 1 15 1 TB2-1 TB6-1 CBCC-TB6-1 / TB2-1 CB-Y-TB2-1 / TB6-1 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
2 TB2-2 TB6-2 CBCC-TB6-2 / TB2-2 CB-Y-TB2-2 / TB6-2 5257PN100-MLW-E-SYD-SCH-1524 SHT08
3 TB2-3 TB6-3 CBCC-TB6-3 / TB2-3 CB-Y-TB2-3 / TB6-3 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
4 TB2-4 TB6-4 CBCC-TB6-4 / TB2-4 CB-Y-TB2-4 / TB6-4 5257PN100-MLW-E-SYD-SCH-1524 SHT08
5 TB2-5 TB6-5 CBCC-TB6-5 / TB2-5 CB-Y-TB2-5 / TB6-5 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
6 TB2-6 TB6-6 CBCC-TB6-6 / TB2-6 CB-Y-TB2-6 / TB6-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08 6 TB2-6 TB6-6 CBCC-TB6-6 / TB2-6 CB-Y-TB2-6 / TB6-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08
7 TB2-7 TB6-7 CBCC-TB6-7 / TB2-7 CB-Y-TB2-7 / TB6-7 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
8 TB2-8 TB6-8 CBCC-TB6-8 / TB2-8 CB-Y-TB2-8 / TB6-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08
9 TB2-9 TB6-9 CBCC-TB6-9 / TB2-9 CB-Y-TB2-9 / TB6-9 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
10 TB2-10 TB6-10 CBCC-TB6-10 / TB2-10 CB-Y-TB2-10 / TB6-10 5257PN100-MLW-E-SYD-SCH-1524 SHT08
11 TB2-11 TB6-11 CBCC-TB6-11 / TB2-11 CB-Y-TB2-11 / TB6-11 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
12 TB2-12 TB6-12 CBCC-TB6-12 / TB2-12 CB-Y-TB2-12 / TB6-12 5257PN100-MLW-E-SYD-SCH-1524 SHT08
13 TB2-13 TB6-13 CBCC-TB6-13 / TB2-13 CB-Y-TB2-13 / TB6-13 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
14 TB2-14 TB6-14 CBCC-TB6-14 / TB2-14 CB-Y-TB2-14 / TB6-14 5257PN100-MLW-E-SYD-SCH-1524 SHT08
15 TB2-15 TB6-15 CBCC-TB6-15 / TB2-15 CB-Y-TB2-15 / TB6-15 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
16 TB2-16 TB6-16 CBCC-TB6-16 / TB2-16 CB-Y-TB2-16 / TB6-16 5257PN100-MLW-E-SYD-SCH-1524 SHT08
17 TB2-33 TB6-33 CBCC-TB6-33 / TB2-33 CB-Y-TB2-33 / TB6-33 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
18 TB2-34 TB6-34 CBCC-TB6-34 / TB2-34 CB-Y-TB2-34 / TB6-34 5257PN100-MLW-E-SYD-SCH-1524 SHT08
19 TB2-35 TB6-35 CBCC-TB6-35 / TB2-35 CB-Y-TB2-35 / TB6-35 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
20 TB2-36 TB6-36 CBCC-TB6-36 / TB2-36 CB-Y-TB2-36 / TB6-36
21 SPARE
22 SPARE
23 SPARE
24 SPARE
47 2 01 1047 CB-Y CBCC 24CX2.5 1 15 1 TB2-17 TB6-17 CBCC-TB6-17 / TB2-17 CB-Y-TB2-17 / TB6-17 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
2 TB2-18 TB6-18 CBCC-TB6-18 / TB2-18 CB-Y-TB2-18 / TB6-18 5257PN100-MLW-E-SYD-SCH-1524 SHT08
3 TB2-19 TB6-19 CBCC-TB6-19 / TB2-19 CB-Y-TB2-19 / TB6-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08 3 TB2-19 TB6-19 CBCC-TB6-19 / TB2-19 CB-Y-TB2-19 / TB6-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
4 TB2-20 TB6-20 CBCC-TB6-20 / TB2-20 CB-Y-TB2-20 / TB6-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08
5 TB2-21 TB6-21 CBCC-TB6-21 / TB2-21 CB-Y-TB2-21 / TB6-21 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
6 TB2-22 TB6-22 CBCC-TB6-22 / TB2-22 CB-Y-TB2-22 / TB6-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08
7 TB2-23 TB6-23 CBCC-TB6-23 / TB2-23 CB-Y-TB2-23 / TB6-23 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
8 TB2-24 TB6-24 CBCC-TB6-24 / TB2-24 CB-Y-TB2-24 / TB6-24 5257PN100-MLW-E-SYD-SCH-1524 SHT08
9 TB2-25 TB6-25 CBCC-TB6-25 / TB2-25 CB-Y-TB2-25 / TB6-25 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
10 TB2-26 TB6-26 CBCC-TB6-26 / TB2-26 CB-Y-TB2-26 / TB6-26 5257PN100-MLW-E-SYD-SCH-1524 SHT08
11 TB2-27 TB6-27 CBCC-TB6-27 / TB2-27 CB-Y-TB2-27 / TB6-27 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
12 TB2-28 TB6-28 CBCC-TB6-28 / TB2-28 CB-Y-TB2-28 / TB6-28 5257PN100-MLW-E-SYD-SCH-1524 SHT08
13 TB2-29 TB6-29 CBCC-TB6-29 / TB2-29 CB-Y-TB2-29 / TB6-29 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
14 TB2-30 TB6-30 CBCC-TB6-30 / TB2-30 CB-Y-TB2-30 / TB6-30 5257PN100-MLW-E-SYD-SCH-1524 SHT08
15 TB2-31 TB6-31 CBCC-TB6-31 / TB2-31 CB-Y-TB2-31 / TB6-31 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
16 TB2-32 TB6-32 CBCC-TB6-32 / TB2-32 CB-Y-TB2-32 / TB6-32 5257PN100-MLW-E-SYD-SCH-1524 SHT08
17 TB2-37 TB6-37 CBCC-TB6-37 / TB2-37 CB-Y-TB2-37 / TB6-37 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
18 TB2-38 TB6-38 CBCC-TB6-38 / TB2-38 CB-Y-TB2-38 / TB6-38 5257PN100-MLW-E-SYD-SCH-1524 SHT08
19 TB2-39 TB6-39 CBCC-TB6-39 / TB2-39 CB-Y-TB2-39 / TB6-39 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
20 TB2-40 TB6-40 CBCC-TB6-40 / TB2-40 CB-Y-TB2-40 / TB6-40
21 SPARE
22 SPARE
23 SPARE
24 SPARE 24 SPARE
48 2 01 1048 CB-B CBCC 19CX2.5 1 20 1 TB1-10 TB3-10 CBCC-TB3-10 / TB1-10 CB-B-TB1-10 / TB3-10 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03
2 TB1-16 TB3-16 CBCC-TB3-16 / TB1-16 CB-B-TB1-16 / TB3-16 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03
3 TB1-9 TB3-9 CBCC-TB3-9 / TB1-9 CB-B-TB1-9 / TB3-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03
4 TB1-11 TB3-11 CBCC-TB3-11 / TB1-11 CB-B-TB1-11 / TB3-11 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03
5 TB1-14 TB3-14 CBCC-TB3-14 / TB1-14 CB-B-TB1-14 / TB3-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
6 TB1-17 TB3-17 CBCC-TB3-17 / TB1-17 CB-B-TB1-17 / TB3-17 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
7 TB1-19 TB3-19 CBCC-TB3-19 / TB1-19 CB-B-TB1-19 / TB3-19 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03
8 TB1-7 TB3-7 CBCC-TB3-7 / TB1-7 CB-B-TB1-7 / TB3-7 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
9 TB1-8 TB3-8 CBCC-TB3-8 / TB1-8 CB-B-TB1-8 / TB3-8 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
10 TB1-18 TB3-18 CBCC-TB3-18 / TB1-18 CB-B-TB1-18 / TB3-18 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04
11 TB1-12 TB3-12 CBCC-TB3-12 / TB1-12 CB-B-TB1-12 / TB3-12 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
12 TB1-13 TB3-13 CBCC-TB3-13 / TB1-13 CB-B-TB1-13 / TB3-13 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
13 TB1-15 TB3-15 CBCC-TB3-15 / TB1-15 CB-B-TB1-15 / TB3-15 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
201-BUS COUPLER_05.09.2011 Page 7 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
49 2 01 1049 CB-B CBCC 19CX2.5 1 15 1 TB1-22 TB3-22 CBCC-TB3-22 / TB1-22 CB-B-TB1-22 / TB3-22 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
2 TB1-23 TB3-23 CBCC-TB3-23 / TB1-23 CB-B-TB1-23 / TB3-23 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
3 TB1-26 TB3-26 CBCC-TB3-26 / TB1-26 CB-B-TB1-26 / TB3-26 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05
4 TB1-24 TB3-24 CBCC-TB3-24 / TB1-24 CB-B-TB1-24 / TB3-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05
5 TB1-25 TB3-25 CBCC-TB3-25 / TB1-25 CB-B-TB1-25 / TB3-25 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05
6 TB1-29 TB3-29 CBCC-TB3-29 / TB1-29 CB-B-TB1-29 / TB3-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06 6 TB1-29 TB3-29 CBCC-TB3-29 / TB1-29 CB-B-TB1-29 / TB3-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06
7 TB1-30 TB3-30 CBCC-TB3-30 / TB1-30 CB-B-TB1-30 / TB3-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06
8 TB1-31 TB3-31 CBCC-TB3-31 / TB1-31 CB-B-TB1-31 / TB3-31 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06
9 TB1-32 TB3-32 CBCC-TB3-32 / TB1-32 CB-B-TB1-32 / TB3-32 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06
10 TB1-33 TB3-33 CBCC-TB3-33 / TB1-33 CB-B-TB1-33 / TB3-33 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06
11 TB1-34 TB3-34 CBCC-TB3-34 / TB1-34 CB-B-TB1-34 / TB3-34 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06
12 TB1-27 TB3-27 CBCC-TB3-27 / TB1-27 CB-B-TB1-27 / TB3-27 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06
13 TB1-28 TB3-28 CBCC-TB3-28 / TB1-28 CB-B-TB1-28 / TB3-28 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
50 2 01 1050 CB-B CBCC 24CX2.5 1 15 1 TB2-1 TB7-1 CBCC-TB7-1 / TB2-1 CB-B-TB2-1 / TB7-1 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
2 TB2-2 TB7-2 CBCC-TB7-2 / TB2-2 CB-B-TB2-2 / TB7-2 5257PN100-MLW-E-SYD-SCH-1524 SHT08
3 TB2-3 TB7-3 CBCC-TB7-3 / TB2-3 CB-B-TB2-3 / TB7-3 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
4 TB2-4 TB7-4 CBCC-TB7-4 / TB2-4 CB-B-TB2-4 / TB7-4 5257PN100-MLW-E-SYD-SCH-1524 SHT08
5 TB2-5 TB7-5 CBCC-TB7-5 / TB2-5 CB-B-TB2-5 / TB7-5 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
6 TB2-6 TB7-6 CBCC-TB7-6 / TB2-6 CB-B-TB2-6 / TB7-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08
7 TB2-7 TB7-7 CBCC-TB7-7 / TB2-7 CB-B-TB2-7 / TB7-7 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
8 TB2-8 TB7-8 CBCC-TB7-8 / TB2-8 CB-B-TB2-8 / TB7-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08 8 TB2-8 TB7-8 CBCC-TB7-8 / TB2-8 CB-B-TB2-8 / TB7-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08
9 TB2-9 TB7-9 CBCC-TB7-9 / TB2-9 CB-B-TB2-9 / TB7-9 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
10 TB2-10 TB7-10 CBCC-TB7-10 / TB2-10 CB-B-TB2-10 / TB7-10 5257PN100-MLW-E-SYD-SCH-1524 SHT08
11 TB2-11 TB7-11 CBCC-TB7-11 / TB2-11 CB-B-TB2-11 / TB7-11 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
12 TB2-12 TB7-12 CBCC-TB7-12 / TB2-12 CB-B-TB2-12 / TB7-12 5257PN100-MLW-E-SYD-SCH-1524 SHT08
13 TB2-13 TB7-13 CBCC-TB7-13 / TB2-13 CB-B-TB2-13 / TB7-13 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
14 TB2-14 TB7-14 CBCC-TB7-14 / TB2-14 CB-B-TB2-14 / TB7-14 5257PN100-MLW-E-SYD-SCH-1524 SHT08
15 TB2-15 TB7-15 CBCC-TB7-15 / TB2-15 CB-B-TB2-15 / TB7-15 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
16 TB2-16 TB7-16 CBCC-TB7-16 / TB2-16 CB-B-TB2-16 / TB7-16 5257PN100-MLW-E-SYD-SCH-1524 SHT08
17 TB2-33 TB7-33 CBCC-TB7-33 / TB2-33 CB-B-TB2-33 / TB7-33 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
18 TB2-34 TB7-34 CBCC-TB7-34 / TB2-34 CB-B-TB2-34 / TB7-34 5257PN100-MLW-E-SYD-SCH-1524 SHT08
19 TB2-35 TB7-35 CBCC-TB7-35 / TB2-35 CB-B-TB2-35 / TB7-35 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
20 TB2-36 TB7-36 CBCC-TB7-36 / TB2-36 CB-B-TB2-36 / TB7-36
21 SPARE
22 SPARE
23 SPARE
24 SPARE
51 2 01 1051 CB-B CBCC 24CX2.5 1 15 1 TB2-17 TB7-17 CBCC-TB7-17 / TB2-17 CB-B-TB2-17 / TB7-17 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
2 TB2-18 TB7-18 CBCC-TB7-18 / TB2-18 CB-B-TB2-18 / TB7-18 5257PN100-MLW-E-SYD-SCH-1524 SHT08
3 TB2-19 TB7-19 CBCC-TB7-19 / TB2-19 CB-B-TB2-19 / TB7-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
4 TB2-20 TB7-20 CBCC-TB7-20 / TB2-20 CB-B-TB2-20 / TB7-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08 4 TB2-20 TB7-20 CBCC-TB7-20 / TB2-20 CB-B-TB2-20 / TB7-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08
5 TB2-21 TB7-21 CBCC-TB7-21 / TB2-21 CB-B-TB2-21 / TB7-21 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
6 TB2-22 TB7-22 CBCC-TB7-22 / TB2-22 CB-B-TB2-22 / TB7-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08
7 TB2-23 TB7-23 CBCC-TB7-23 / TB2-23 CB-B-TB2-23 / TB7-23 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
8 TB2-24 TB7-24 CBCC-TB7-24 / TB2-24 CB-B-TB2-24 / TB7-24 5257PN100-MLW-E-SYD-SCH-1524 SHT08
9 TB2-25 TB7-25 CBCC-TB7-25 / TB2-25 CB-B-TB2-25 / TB7-25 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
10 TB2-26 TB7-26 CBCC-TB7-26 / TB2-26 CB-B-TB2-26 / TB7-26 5257PN100-MLW-E-SYD-SCH-1524 SHT08
11 TB2-27 TB7-27 CBCC-TB7-27 / TB2-27 CB-B-TB2-27 / TB7-27 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
12 TB2-28 TB7-28 CBCC-TB7-28 / TB2-28 CB-B-TB2-28 / TB7-28 5257PN100-MLW-E-SYD-SCH-1524 SHT08
13 TB2-29 TB7-29 CBCC-TB7-29 / TB2-29 CB-B-TB2-29 / TB7-29 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
14 TB2-30 TB7-30 CBCC-TB7-30 / TB2-30 CB-B-TB2-30 / TB7-30 5257PN100-MLW-E-SYD-SCH-1524 SHT08
15 TB2-31 TB7-31 CBCC-TB7-31 / TB2-31 CB-B-TB2-31 / TB7-31 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
16 TB2-32 TB7-32 CBCC-TB7-32 / TB2-32 CB-B-TB2-32 / TB7-32 5257PN100-MLW-E-SYD-SCH-1524 SHT08
17 TB2-37 TB7-37 CBCC-TB7-37 / TB2-37 CB-B-TB2-37 / TB7-37 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
18 TB2-38 TB7-38 CBCC-TB7-38 / TB2-38 CB-B-TB2-38 / TB7-38 5257PN100-MLW-E-SYD-SCH-1524 SHT08
19 TB2-39 TB7-39 CBCC-TB7-39 / TB2-39 CB-B-TB2-39 / TB7-39 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08
20 TB2-40 TB7-40 CBCC-TB7-40 / TB2-40 CB-B-TB2-40 / TB7-40
21 SPARE
22 SPARE
23 SPARE
24 SPARE
52 2 01 1052 2-152 2-189BE2 5CX2.5 1 35 1 TB4-19 TB7-19 2-189BE2-TB7-19 / TB4-19 2-152-TB4-19 / TB7-19 CB LOCAL CLOSING I/L CPD KN17 SC51 SHT1252 2 01 1052 2-152 2-189BE2 5CX2.5 1 35 1 TB4-19 TB7-19 2-189BE2-TB7-19 / TB4-19 2-152-TB4-19 / TB7-19 CB LOCAL CLOSING I/L CPD KN17 SC51 SHT12
2 TB4-42 TB7-20 2-189BE2-TB7-20 / TB4-42 2-152-TB4-42 / TB7-20 CPD KN17 SC51 SHT12
3 SPARE
4 SPARE
5 SPARE
201-BUS COUPLER_05.09.2011 Page 8 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
53 2 01 1053 2-152 2-189AE2 5CX2.5 1 65 1 TB4-20 TB7-19 2-189AE2-TB7-19 / TB4-20 2-152-TB4-20 / TB7-19 CB LOCAL CLOSING I/L CPD KN17 SC51 SHT12
2 TB4-42 TB7-20 2-189AE2-TB7-20 / TB4-42 2-152-TB4-42 / TB7-20 CPD KN17 SC51 SHT12
3 SPARE
4 SPARE
5 SPARE 5 SPARE
54 2 01 1054 2-1 89A 2-1 89AE1 5CX2.5 1 14 1 TB3-24 TB1-3 2-1 89AE1-TB1-3 / TB3-24 2-1 89A-TB3-24 / TB1-3 DC, I/L CPD KN17 SC65 SHT10
2 TB3-25 TB1-4 2-1 89AE1-TB1-4 / TB3-25 2-1 89A-TB3-25 / TB1-4 X- spare TB shall be identified at site CPD KN17 SC65 SHT10
3 TB1-1 TB1-1 2-1 89AE1-TB1-1 / TB1-1 2-1 89A-TB1-1 / TB1-1 CPD KN17 SC51 SHT14
4 TB1-2 TB1-2 2-1 89AE1-TB1-2 / TB1-2 2-1 89A-TB1-2 / TB1-2 CPD KN17 SC51 SHT14
5 SPARE
55 2 01 1055 2-1 89B 2-1 89BE1 5CX2.5 1 14 1 TB3-24 TB1-3 2-1 89BE1-TB1-3 / TB3-24 2-1 89B-TB3-24 / TB1-3 DC, I/L CPD KN17 SC65 SHT11
2 TB3-25 TB1-4 2-1 89BE1-TB1-4 / TB3-25 2-1 89B-TB3-25 / TB1-4 CPD KN17 SC65 SHT11
3 TB1-1 TB1-1 2-1 89BE1-TB1-1 / TB1-1 2-1 89B-TB1-1 / TB1-1 CPD KN17 SC65 SHT11
4 TB1-2 TB1-2 2-1 89BE1-TB1-2 / TB1-2 2-1 89B-TB1-2 / TB1-2 CPD KN17 SC51 SHT14
5 SPARE CPD KN17 SC51 SHT14
56 2 01 1056 2-1 89A 2-1 89AE2 5CX2.5 1 14 1 TB4-48 TB1-3 2-1 89AE2-TB1-3 / TB4-48 2-1 89A-TB4-48 / TB1-3 DC, I/L CPD KN17 SC65 SHT10
2 TB4-49 TB1-4 2-1 89AE2-TB1-4 / TB4-49 2-1 89A-TB4-49 / TB1-4 CPD KN17 SC65 SHT10
3 TB1-1 TB1-1 2-1 89AE2-TB1-1 / TB1-1 2-1 89A-TB1-1 / TB1-1 CPD KN17 SC51 SHT14
4 TB1-2 TB1-2 2-1 89AE2-TB1-2 / TB1-2 2-1 89A-TB1-2 / TB1-2 CPD KN17 SC51 SHT14
5 SPARE
57 2 01 1057 2-1 89B 2-1 89BE2 5CX2.5 1 14 1 TB4-48 TB1-3 2-1 89BE2-TB1-3 / TB4-48 2-1 89B-TB4-48 / TB1-3 DC, I/L
2 TB4-49 TB1-4 2-1 89BE2-TB1-4 / TB4-49 2-1 89B-TB4-49 / TB1-4 CPD KN17 SC65 SHT11 2 TB4-49 TB1-4 2-1 89BE2-TB1-4 / TB4-49 2-1 89B-TB4-49 / TB1-4 CPD KN17 SC65 SHT11
3 TB1-1 TB1-1 2-1 89BE2-TB1-1 / TB1-1 2-1 89B-TB1-1 / TB1-1 CPD KN17 SC65 SHT11
4 TB1-2 TB1-2 2-1 89BE2-TB1-2 / TB1-2 2-1 89B-TB1-2 / TB1-2 CPD KN17 SC51 SHT14
5 SPARE X-SPARE TB SHALL BE ARRANGED AT SITE CPD KN17 SC51 SHT14
58 2 01 1058 2-1 89A 2-1 89AE1 5CX2.5 1 14 1 TB3-21 TB6-1 2-1 89AE1-TB6-1 / TB3-21 2-1 89A-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT08
2 TB3-22 TB6-2 2-1 89AE1-TB6-2 / TB3-22 2-1 89A-TB3-22 / TB6-2 CPD KN17 SC65 SHT08
3 TB3-23 TB7-18 2-1 89AE1-TB7-18 / TB3-23 2-1 89A-TB3-23 / TB7-18 CPD KN17 SC65 SHT08
4 SPARE
5 SPARE
59 2 01 1059 2-1 89B 2-1 89BE1 5CX2.5 1 14 1 TB3-21 TB6-1 2-1 89BE1-TB6-1 / TB3-21 2-1 89B-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT08
2 TB3-22 TB6-2 2-1 89BE1-TB6-2 / TB3-22 2-1 89B-TB3-22 / TB6-2 CPD KN17 SC65 SHT08
3 TB3-23 TB7-18 2-1 89BE1-TB7-18 / TB3-23 2-1 89B-TB3-23 / TB7-18 CPD KN17 SC65 SHT08
4 SPARE
5 SPARE
60 2 01 1060 2-1 89A 2-1 89AE2 5CX2.5 1 14 1 TB4-45 TB6-1 2-1 89AE2-TB6-1 / TB4-45 2-1 89A-TB4-45 / TB6-1 DI CPD KN17 SC65 SHT08
2 TB4-46 TB6-2 2-1 89AE2-TB6-2 / TB4-46 2-1 89A-TB4-46 / TB6-2 CPD KN17 SC65 SHT08
3 TB4-47 TB7-18 2-1 89AE2-TB7-18 / TB4-47 2-1 89A-TB4-47 / TB7-18 CPD KN17 SC65 SHT08
4 SPARE
5 SPARE 5 SPARE
61 2 01 1061 2-1 89B 2-1 89BE2 5CX2.5 1 14 1 TB4-45 TB6-1 2-1 89BE2-TB6-1 / TB4-45 2-1 89B-TB4-45 / TB6-1 DI CPD KN17 SC65 SHT08
2 TB4-46 TB6-2 2-1 89BE2-TB6-2 / TB4-46 2-1 89B-TB4-46 / TB6-2 CPD KN17 SC65 SHT08
3 TB4-47 TB7-18 2-1 89BE2-TB7-18 / TB4-47 2-1 89B-TB4-47 / TB7-18 CPD KN17 SC65 SHT08
4 SPARE
5 SPARE
62 2 01 2062 2- B189 2- B189E 5CX2.5 1 14 1 TB4-45 TB1-3 2- B189E-TB1-3 / TB3-21 2- B189-TB3-21 / TB1-3 DC, I/L CPD KN17 SC65 SHT11
2 TB4-46 TB1-4 2- B189E-TB1-4 / TB3-22 2- B189-TB3-22 / TB1-4 CPD KN17 SC65 SHT11
3 TB1-1 TB1-1 2- B189E-TB1-1 / TB3-23 2- B189-TB3-23 / TB1-1 CPD KN17 SC51 CHT15
4 TB1-2 TB1-2 2- B189E-TB1-2 / SPARE 2- B189-SPARE / TB1-2 CPD KN17 SC51 CHT15
5 SPARE
63 2 01 2063 2- B189 2- B189E 5CX2.5 1 14 1 TB3-21 TB6-1 2- B189E-TB6-1 / TB3-21 2- B189-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT09
2 TB3-22 TB6-2 2- B189E-TB6-2 / TB3-22 2- B189-TB3-22 / TB6-2 CPD KN17 SC65 SHT09
3 TB3-23 TB7-18 2- B189E-TB7-18 / TB3-23 2- B189-TB3-23 / TB7-18 CPD KN17 SC65 SHT09
4 SPARE
5 SPARE
64 2 01 2064 2- B289 2- B289E 5CX2.5 1 14 1 TB4-45 TB1-3 2- B289E-TB1-3 / TB4-45 2- B289-TB4-45 / TB1-3 DC, I/L CPD KN17 SC65 SHT12
2 TB4-46 TB1-4 2- B289E-TB1-4 / TB4-46 2- B289-TB4-46 / TB1-4 CPD KN17 SC65 SHT12
3 TB1-1 TB1-1 2- B289E-TB1-1 / TB1-1 2- B289-TB1-1 / TB1-1 CPD KN17 SC51 SHT153 TB1-1 TB1-1 2- B289E-TB1-1 / TB1-1 2- B289-TB1-1 / TB1-1 CPD KN17 SC51 SHT15
4 TB1-2 TB1-2 2- B289E-TB1-2 / TB1-2 2- B289-TB1-2 / TB1-2 CPD KN17 SC51 SHT15
5 SPARE
201-BUS COUPLER_05.09.2011 Page 9 of 18 Cables within SWYD
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES WITHIN SWITCHYARD
AREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
CABLE NO. EQUIPMENT DESIGNATION ESTIMATED
LENGTH
INTERCONNECTION DETAILSSL.
NO
Prepared by
ROUTING DETAILS
Approved by
Ferrule Nos.
Checked by
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
65 2 01 2065 2- B289 2- B289E 5CX2.5 1 14 1 TB3-21 TB6-1 2- B289E-TB6-1 / TB3-21 2- B289-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT09
2 TB3-22 TB6-2 2- B289E-TB6-2 / TB3-22 2- B289-TB3-22 / TB6-2 CPD KN17 SC65 SHT09
3 TB3-23 TB7-18 2- B289E-TB7-18 / TB3-23 2- B289-TB3-23 / TB7-18 CPD KN17 SC65 SHT09
4 SPARE
5 SPARE
201-BUS COUPLER_05.09.2011 Page 10 of 18 Cables within SWYD
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES BETWEEN SWITCHYARD TO KIOSK-CR
Protection PANEL -- Protection PANEL--
1 2 01 2001 2-1 B1CVT JB P1 10CX2.5 1 73 1,2 TB1-1 TB1-17 P1-TB1-17 / TB1-1 2-1 B1CVT JB-TB1-1 / TB1-17 WDG-1 CPD KN17 SC51 SH07
3,4 TB1-4 TB1-19 P1-TB1-19 / TB1-4 2-1 B1CVT JB-TB1-4 / TB1-19 CPD KN17 SC51 SH07
5,6 TB1-7 TB1-21 P1-TB1-21 / TB1-7 2-1 B1CVT JB-TB1-7 / TB1-21 CPD KN17 SC51 SH07
7,8 TB1-9 TB1-23 P1-TB1-23 / TB1-9 2-1 B1CVT JB-TB1-9 / TB1-23 CPD KN17 SC51 SH07
9,10 SPARE
EQUIPMENT DESIGNATIONSL.
NO
Prepared by
Checked by
CABLE NO.
Approved byAREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
INTERCONNECTION DETAILSESTIMATED
LENGTHROUTING DETAILS
Ferrule Nos.
9,10 SPARE
2 2 01 2002 2-1 B1CVT JB P1 10CX2.5 1 73 1,2 TB2-1 TB1-25 P1-TB1-25 / TB2-1 2-1 B1CVT JB-TB2-1 / TB1-25 WDG-2 CPD KN17 SC51 SH07
3,4 TB2-4 TB1-27 P1-TB1-27 / TB2-4 2-1 B1CVT JB-TB2-4 / TB1-27 CPD KN17 SC51 SH07
5,6 TB2-7 TB1-29 P1-TB1-29 / TB2-7 2-1 B1CVT JB-TB2-7 / TB1-29 CPD KN17 SC51 SH07
7,8 TB2-9 TB1-31 P1-TB1-31 / TB2-9 2-1 B1CVT JB-TB2-9 / TB1-31 CPD KN17 SC51 SH07
9,10 SPARE
3 2 01 2003 2-1 B1CVT JB P1 10CX2.5 1 73 1,2 TB3-1 TB1-33 P1-TB1-33 / TB3-1 2-1 B1CVT JB-TB3-1 / TB1-33 WDG-3 CPD KN17 SC51 SH07
3,4 TB3-4 TB1-35 P1-TB1-35 / TB3-4 2-1 B1CVT JB-TB3-4 / TB1-35 CPD KN17 SC51 SH07
5,6 TB3-7 TB1-37 P1-TB1-37 / TB3-7 2-1 B1CVT JB-TB3-7 / TB1-37 CPD KN17 SC51 SH07
7,8 TB3-9 TB1-39 P1-TB1-39 / TB3-9 2-1 B1CVT JB-TB3-9 / TB1-39 CPD KN17 SC51 SH07
9,10 SPARE
4 2 01 2004 2-1 B1CVT JB P1 10CX2.5 2 73 1,2 TB4-1 TB1-41 P1-TB1-41 / TB4-1 2-1 B1CVT JB-TB4-1 / TB1-41 WDG-4 TARIFF METERING CPD KN17 SC51 SH07
3,4 TB4-4 TB1-43 P1-TB1-43 / TB4-4 2-1 B1CVT JB-TB4-4 / TB1-43 CPD KN17 SC51 SH07
5,6 TB4-7 TB1-45 P1-TB1-45 / TB4-7 2-1 B1CVT JB-TB4-7 / TB1-45 CPD KN17 SC51 SH07
7,8 TB4-9 TB1-47 P1-TB1-47 / TB4-9 2-1 B1CVT JB-TB4-9 / TB1-47 CPD KN17 SC51 SH07
9,10 SPARE
5 2 01 2005 2-1 B2CVT JB P1 10CX2.5 1 91 1,2 TB1-1 TB2-1 P1-TB2-1 / TB1-1 2-1 B2CVT JB-TB1-1 / TB2-1 WDG-1 CPD KN17 SC51 SH08
3,4 TB1-4 TB2-3 P1-TB2-3 / TB1-4 2-1 B2CVT JB-TB1-4 / TB2-3 CPD KN17 SC51 SH08
5,6 TB1-7 TB2-5 P1-TB2-5 / TB1-7 2-1 B2CVT JB-TB1-7 / TB2-5 CPD KN17 SC51 SH085,6 TB1-7 TB2-5 P1-TB2-5 / TB1-7 2-1 B2CVT JB-TB1-7 / TB2-5 CPD KN17 SC51 SH08
7,8 TB1-9 TB2-7 P1-TB2-7 / TB1-9 2-1 B2CVT JB-TB1-9 / TB2-7 CPD KN17 SC51 SH08
9,10 SPARE
6 2 01 2006 2-1 B2CVT JB P1 10CX2.5 1 91 1,2 TB2-1 TB2-9 P1-TB2-9 / TB2-1 2-1 B2CVT JB-TB2-1 / TB2-9 WDG-2 CPD KN17 SC51 SH08
3,4 TB2-4 TB2-11 P1-TB2-11 / TB2-4 2-1 B2CVT JB-TB2-4 / TB2-11 CPD KN17 SC51 SH08
5,6 TB2-7 TB2-13 P1-TB2-13 / TB2-7 2-1 B2CVT JB-TB2-7 / TB2-13 CPD KN17 SC51 SH08
7,8 TB2-9 TB2-15 P1-TB2-15 / TB2-9 2-1 B2CVT JB-TB2-9 / TB2-15 CPD KN17 SC51 SH08
9,10 SPARE
7 2 01 2007 2-1 B2CVT JB P1 10CX2.5 1 91 1,2 TB3-1 TB2-17 P1-TB2-17 / TB3-1 2-1 B2CVT JB-TB3-1 / TB2-17 WDG-3 CPD KN17 SC51 SH08
3,4 TB3-4 TB2-19 P1-TB2-19 / TB3-4 2-1 B2CVT JB-TB3-4 / TB2-19 CPD KN17 SC51 SH08
5,6 TB3-7 TB2-21 P1-TB2-21 / TB3-7 2-1 B2CVT JB-TB3-7 / TB2-21 CPD KN17 SC51 SH08
7,8 TB3-9 TB2-23 P1-TB2-23 / TB3-9 2-1 B2CVT JB-TB3-9 / TB2-23 CPD KN17 SC51 SH08
9,10 SPARE
8 2 01 2008 2-1 B2CVT JB P1 10CX2.5 2 91 1,2 TB4-1 TB2-25 P1-TB2-25 / TB4-1 2-1 B2CVT JB-TB4-1 / TB2-25 WDG-4 TARIFF METERING CPD KN17 SC51 SH08
3,4 TB4-4 TB2-27 P1-TB2-27 / TB4-4 2-1 B2CVT JB-TB4-4 / TB2-27 CPD KN17 SC51 SH08
5,6 TB4-7 TB2-29 P1-TB2-29 / TB4-7 2-1 B2CVT JB-TB4-7 / TB2-29 CPD KN17 SC51 SH08
7,8 TB4-9 TB2-31 P1-TB2-31 / TB4-9 2-1 B2CVT JB-TB4-9 / TB2-31 CPD KN17 SC51 SH08
9,10 SPARE
9 2 01 2009 2-1 CTA JB P1 10CX2.5 1 25 1,2 TB2-1 TB1-9 P1-TB1-9 / TB2-1 2-1 CTA JB-TB2-1 / TB1-9 BACK UP CPD KN17 SC51 SH099 2 01 2009 2-1 CTA JB P1 10CX2.5 1 25 1,2 TB2-1 TB1-9 P1-TB1-9 / TB2-1 2-1 CTA JB-TB2-1 / TB1-9 BACK UP CPD KN17 SC51 SH09
3,4 TB2-5 TB1-11 P1-TB1-11 / TB2-5 2-1 CTA JB-TB2-5 / TB1-11 CPD KN17 SC51 SH09
5,6 TB2-9 TB1-13 P1-TB1-13 / TB2-9 2-1 CTA JB-TB2-9 / TB1-13 CPD KN17 SC51 SH09
7,8 TB2-12 TB1-15 P1-TB1-15 / TB2-12 2-1 CTA JB-TB2-12 / TB1-15 CPD KN17 SC51 SH09
9,10
10 2 01 2010 P1 2-1 CB 24CX2.5 1 45 1,2 TB3-8 TB4-13 2-1 CB-TB4-13 / TB3-8 P1-TB3-8 / TB4-13 DC-1, TRIP-1, TCS CB CPD KN17 SC51 SH12
3,4 TB3-9 TB4-14 2-1 CB-TB4-14 / TB3-9 P1-TB3-9 / TB4-14 CPD KN17 SC51 SH12
5,6 TB3-10 TB4-22 2-1 CB-TB4-22 / TB3-10 P1-TB3-10 / TB4-22 CPD KN17 SC51 SH12
7,8 TB3-11 TB1-5 2-1 CB-TB1-5 / TB3-11 P1-TB3-11 / TB1-5 CPD KN17 SC51 SH12
9,10 TB3-12 TB2-5 2-1 CB-TB2-5 / TB3-12 P1-TB3-12 / TB2-5 CPD KN17 SC51 SH12
11,12 TB3-13 TB3-5 2-1 CB-TB3-5 / TB3-13 P1-TB3-13 / TB3-5 CPD KN17 SC51 SH12
13 TB3-14 TB1-6 2-1 CB-TB1-6 / TB3-14 P1-TB3-14 / TB1-6 CPD KN17 SC51 SH12
14 TB3-15 TB1-8 2-1 CB-TB1-8 / TB3-15 P1-TB3-15 / TB1-8 CPD KN17 SC51 SH12
15 TB3-16 TB2-6 2-1 CB-TB2-6 / TB3-16 P1-TB3-16 / TB2-6 CPD KN17 SC51 SH12
16 TB3-17 TB2-8 2-1 CB-TB2-8 / TB3-17 P1-TB3-17 / TB2-8 CPD KN17 SC51 SH12
17 TB3-18 TB3-6 2-1 CB-TB3-6 / TB3-18 P1-TB3-18 / TB3-6 CPD KN17 SC51 SH12
18 TB3-19 TB3-8 2-1 CB-TB3-8 / TB3-19 P1-TB3-19 / TB3-8 CPD KN17 SC51 SH12
19-24 SPARE
201-BUS COUPLER_05.09.2011 Page 11 of 18 Cables between SWYD to Kiosk-CR
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES BETWEEN SWITCHYARD TO KIOSK-CR
EQUIPMENT DESIGNATIONSL.
NO
Prepared by
Checked by
CABLE NO.
Approved byAREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
INTERCONNECTION DETAILSESTIMATED
LENGTHROUTING DETAILS
Ferrule Nos.
11 2 01 2011 P1 2-1 CB 24CX2.5 1 45 1,2 TB3-32 TB4-15 2-1 CB-TB4-15 / TB3-32 P1-TB3-32 / TB4-15 DC-2, TRIP-2, TCS, Manual Trip-2 CPD KN17 SC51 SH13
3,4 TB3-33 TB4-16 2-1 CB-TB4-16 / TB3-33 P1-TB3-33 / TB4-16 CPD KN17 SC51 SH13
5,6 TB3-34 TB4-24 2-1 CB-TB4-24 / TB3-34 P1-TB3-34 / TB4-24 CPD KN17 SC51 SH13
7,8 TB3-35 TB1-20 2-1 CB-TB1-20 / TB3-35 P1-TB3-35 / TB1-20 CPD KN17 SC51 SH13
9,10 TB3-36 TB2-20 2-1 CB-TB2-20 / TB3-36 P1-TB3-36 / TB2-20 CPD KN17 SC51 SH13
11,12 TB3-37 TB3-20 2-1 CB-TB3-20 / TB3-37 P1-TB3-37 / TB3-20 CPD KN17 SC51 SH1311,12 TB3-37 TB3-20 2-1 CB-TB3-20 / TB3-37 P1-TB3-37 / TB3-20 CPD KN17 SC51 SH13
13 TB3-38 TB1-21 2-1 CB-TB1-21 / TB3-38 P1-TB3-38 / TB1-21 CPD KN17 SC51 SH13
14 TB3-39 TB1-23 2-1 CB-TB1-23 / TB3-39 P1-TB3-39 / TB1-23 CPD KN17 SC51 SH13
15 TB3-40 TB2-21 2-1 CB-TB2-21 / TB3-40 P1-TB3-40 / TB2-21 CPD KN17 SC51 SH13
16 TB3-41 TB2-23 2-1 CB-TB2-23 / TB3-41 P1-TB3-41 / TB2-23 CPD KN17 SC51 SH13
17 TB3-42 TB3-21 2-1 CB-TB3-21 / TB3-42 P1-TB3-42 / TB3-21 CPD KN17 SC51 SH13
18 TB3-43 TB3-23 2-1 CB-TB3-23 / TB3-43 P1-TB3-43 / TB3-23 CPD KN17 SC51 SH13
19-24 SPARE CPD KN17 SC51 SH13
12 2 01 2012 P1 2-1 CB 7CX2.5 1 45 1,2 TB3-20 TB4-21 2-1 CB-TB4-21 / TB3-20 P1-TB3-20 / TB4-21 REMOTE CLOSING, MANL TRIP-1 CPD KN17 SC51 SH12
3,4 TB3-22 TB4-22 2-1 CB-TB4-22 / TB3-22 P1-TB3-22 / TB4-22 CPD KN17 SC51 SH12
5,6 TB3-23 TB4-18 2-1 CB-TB4-18 / TB3-23 P1-TB3-23 / TB4-18 CPD KN17 SC51 SH12
7 SPARE
13 2 01 2013 P1 2-1 CB 5CX2.5 1 45 1,2 TB3-44 TB4-24 2-1 CB-TB4-24 / TB3-44 P1-TB3-44 / TB4-24 TRIP-2 CPD KN17 SC51 SH13
3,4 TB3-45 TB4-23 2-1 CB-TB4-23 / TB3-45 P1-TB3-45 / TB4-23 CPD KN17 SC51 SH13
5 SPARE
14 2 01 2014 2-1 CTA JB P1 10CX2.5 1 25 1,2 TB5-1 TB1-1 P1-TB1-1 / TB5-1 2-1 CTA JB-TB5-1 / TB1-1 BUS BAR PROTECTION CPD KN17 SC51 SH19
3,4 TB5-5 TB1-3 P1-TB1-3 / TB5-5 2-1 CTA JB-TB5-5 / TB1-3 CPD KN17 SC51 SH193,4 TB5-5 TB1-3 P1-TB1-3 / TB5-5 2-1 CTA JB-TB5-5 / TB1-3 CPD KN17 SC51 SH19
5,6 TB5-9 TB1-5 P1-TB1-5 / TB5-9 2-1 CTA JB-TB5-9 / TB1-5 CPD KN17 SC51 SH19
7,8 TB5-11 TB1-7 P1-TB1-7 / TB5-11 2-1 CTA JB-TB5-11 / TB1-7 CPD KN17 SC51 SH19
9,10 SPARE
15 2 01 2015 2-1 CB P1 5CX2.5 1 45 1 TB5-3 TB5-13 P1-TB5-13 / TB5-3 2-1 CB-TB5-3 / TB5-13 DI FOR BB PROTECTION CPD KN17 SC51 SH20
2 TB7-4 TB5-14 P1-TB5-14 / TB7-4 2-1 CB-TB7-4 / TB5-14 CPD KN17 SC51 SH20
3 TB7-12 TB5-15 P1-TB5-15 / TB7-12 2-1 CB-TB7-12 / TB5-15 CPD KN17 SC51 SH20
4 SPARE
5 SPARE
16 2 01 2016 2-189A P1 5CX2.5 1 80 1 TB4-27 TB5-16 P1-TB5-16 / TB4-27 2-189A-TB4-27 / TB5-16 DI FOR BB PROTECTION CPD KN17 SC51 SH20
2 TB4-28 TB5-17 P1-TB5-17 / TB4-28 2-189A-TB4-28 / TB5-17 CPD KN17 SC51 SH20
3 TB3-4 TB5-18 P1-TB5-18 / TB3-4 2-189A-TB3-4 / TB5-18 CPD KN17 SC51 SH20
4 SPARE
5 SPARE
17 2 01 2017 2-189B P1 5CX2.5 1 55 1 TB4-27 TB5-19 P1-TB5-19 / TB4-27 2-189B-TB4-27 / TB5-19 DI FOR BB PROTECTION CPD KN17 SC51 SH20
2 TB4-28 TB5-20 P1-TB5-20 / TB4-28 2-189B-TB4-28 / TB5-20 CPD KN17 SC51 SH20
3 TB3-4 TB5-21 P1-TB5-21 / TB3-4 2-189B-TB3-4 / TB5-21 CPD KN17 SC51 SH20
4 SPARE
5 SPARE5 SPARE
18 2 01 2018 BB2 P1 5CX2.5 1 100 1,2 TB1-13 TB5-11 P1-TB5-11 / TB1-13 BB2-TB1-13 / TB5-11 DC SUPPLY CPD KN17 SC59 SH04
3,4 TB1-14 TB5-12 P1-TB5-12 / TB1-14 BB2-TB1-14 / TB5-12 CPD KN17 SC51 SH20
5 SPARE
CONTROL PANEL
19 2 01 2019 2-1 CTA JB C1 10CX2.5 1 25 1,2 TB3-4 TB1-1 C1-TB1-1 / TB3-4 2-1 CTA JB-TB3-4 / TB1-1 METERING CPD KN17 SC65 SHT07
3,4 TB3-8 TB1-3 C1-TB1-3 / TB3-8 2-1 CTA JB-TB3-8 / TB1-3 CPD KN17 SC65 SHT07
5,6 TB3-12 TB1-5 C1-TB1-5 / TB3-12 2-1 CTA JB-TB3-12 / TB1-5 CPD KN17 SC65 SHT07
7,8 TB3-9 TB1-7 C1-TB1-7 / TB3-9 2-1 CTA JB-TB3-9 / TB1-7 CPD KN17 SC65 SHT07
9,10 SPARE
201-BUS COUPLER_05.09.2011 Page 12 of 18 Cables between SWYD to Kiosk-CR
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES BETWEEN SWITCHYARD TO KIOSK-CR
EQUIPMENT DESIGNATIONSL.
NO
Prepared by
Checked by
CABLE NO.
Approved byAREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
INTERCONNECTION DETAILSESTIMATED
LENGTHROUTING DETAILS
Ferrule Nos.
20 2 01 2020 C1 2-1 CB 19CX2.5 1 45 1 TB1C-7 TB5-9 2-1 CB-TB5-9 / TB1C-7 C1-TB1C-7 / TB5-9 DI OF CB & TROUBLES CPD KN17 SC65 SHT08
2 TB1P1-1 TB5-10 2-1 CB-TB5-10 / TB1P1-1 C1-TB1P1-1 / TB5-10 CPD KN17 SC65 SHT08
3 TB1P1-2 TB5-2 2-1 CB-TB5-2 / TB1P1-2 C1-TB1P1-2 / TB5-2 CPD KN17 SC65 SHT08
4 TB1P1-4 TB6-10 2-1 CB-TB6-10 / TB1P1-4 C1-TB1P1-4 / TB6-10 CPD KN17 SC65 SHT08
5 TB1P1-5 TB6-2 2-1 CB-TB6-2 / TB1P1-5 C1-TB1P1-5 / TB6-2 CPD KN17 SC65 SHT08
6 TB1P1-7 TB7-10 2-1 CB-TB7-10 / TB1P1-7 C1-TB1P1-7 / TB7-10 CPD KN17 SC65 SHT086 TB1P1-7 TB7-10 2-1 CB-TB7-10 / TB1P1-7 C1-TB1P1-7 / TB7-10 CPD KN17 SC65 SHT08
7 TB1P1-8 TB7-2 2-1 CB-TB7-2 / TB1P1-8 C1-TB1P1-8 / TB7-2 CPD KN17 SC65 SHT08
8 TB1P1-10 TB3-28 2-1 CB-TB3-28 / TB1P1-10 C1-TB1P1-10 / TB3-28 CPD KN17 SC65 SHT08
9 TB1P1-11 TB4-26 2-1 CB-TB4-26 / TB1P1-11 C1-TB1P1-11 / TB4-26 CPD KN17 SC65 SHT08
10 TB1P1-13 TB4-28 2-1 CB-TB4-28 / TB1P1-13 C1-TB1P1-13 / TB4-28 CPD KN17 SC65 SHT08
11 TB1P1-14 TB4-32 2-1 CB-TB4-32 / TB1P1-14 C1-TB1P1-14 / TB4-32 CPD KN17 SC65 SHT08
12 TB1P1-16 TB4-43 2-1 CB-TB4-43 / TB1P1-16 C1-TB1P1-16 / TB4-43 CPD KN17 SC65 SHT08
13 TB1P1-17 TB4-34 2-1 CB-TB4-34 / TB1P1-17 C1-TB1P1-17 / TB4-34 CPD KN17 SC65 SHT08
14 TB1P1-19 TB4-33 2-1 CB-TB4-33 / TB1P1-19 C1-TB1P1-19 / TB4-33 CPD KN17 SC65 SHT08
15-19 SPARE
21 2 01 2021 2-1 89A C1 14CX2.5 1 80 1 TB1-9 TBOD1-9 C1-TBOD1-9 / TB1-9 2-1 89A-TB1-9 / TBOD1-9 DC, CONTROL, I/L CPD KN17 SC65 SHT10
2 TB1-10 TBOD1-10 C1-TBOD1-10 / TB1-10 2-1 89A-TB1-10 / TBOD1-10 CPD KN17 SC65 SHT10
3 TB1-11 TBOD1-12 C1-TBOD1-12 / TB1-11 2-1 89A-TB1-11 / TBOD1-12 CPD KN17 SC65 SHT10
4 TB1-3 TBOD1-14 C1-TBOD1-14 / TB1-3 2-1 89A-TB1-3 / TBOD1-14 CPD KN17 SC65 SHT10
5 TB1-6 TBOD1-13 C1-TBOD1-13 / TB1-6 2-1 89A-TB1-6 / TBOD1-13 CPD KN17 SC65 SHT10
6 TB3-24 TBOD1-16 C1-TBOD1-16 / TB3-24 2-1 89A-TB3-24 / TBOD1-16 CPD KN17 SC65 SHT10
7 TB3-25 TBOD1-15 C1-TBOD1-15 / TB3-25 2-1 89A-TB3-25 / TBOD1-15 CPD KN17 SC65 SHT10
8 TB4-48 TBOD1-19 C1-TBOD1-19 / TB4-48 2-1 89A-TB4-48 / TBOD1-19 CPD KN17 SC65 SHT10
9 TB4-49 TBOD1-21 C1-TBOD1-21 / TB4-49 2-1 89A-TB4-49 / TBOD1-21 CPD KN17 SC65 SHT10
10 TB1-1 TB10-1 C1-TB10-1 / TB1-1 2-1 89A-TB1-1 / TB10-1 CPD KN17 SC51 SHT14
11 TB1-2 TB10-2 C1-TB10-2 / TB1-2 2-1 89A-TB1-2 / TB10-2 CPD KN17 SC51 SHT14
12-14 SPARE X-SPARE TB SHALL BE ARRANGED AT SITE
CB
DC SUPPLY TO BE
WIRED FROM P1
PANEL
12-14 SPARE X-SPARE TB SHALL BE ARRANGED AT SITE
22 2 01 2022 2-1 89B C1 14CX2.5 1 55 1 TB1-9 TBOE1-1 C1-TBOE1-1 / TB1-9 2-1 89B-TB1-9 / TBOE1-1 DC, CONTROL, I/L CPD KN17 SC65 SHT11
2 TB1-10 TBOE1-2 C1-TBOE1-2 / TB1-10 2-1 89B-TB1-10 / TBOE1-2 CPD KN17 SC65 SHT11
3 TB1-11 TBOE1-4 C1-TBOE1-4 / TB1-11 2-1 89B-TB1-11 / TBOE1-4 CPD KN17 SC65 SHT11
4 TB1-3 TBOE1-6 C1-TBOE1-6 / TB1-3 2-1 89B-TB1-3 / TBOE1-6 CPD KN17 SC65 SHT11
5 TB1-6 TBOE1-5 C1-TBOE1-5 / TB1-6 2-1 89B-TB1-6 / TBOE1-5 CPD KN17 SC65 SHT11
6 TB3-24 TBOE1-8 C1-TBOE1-8 / TB3-24 2-1 89B-TB3-24 / TBOE1-8 CPD KN17 SC65 SHT11
7 TB3-25 TBOE1-7 C1-TBOE1-7 / TB3-25 2-1 89B-TB3-25 / TBOE1-7 CPD KN17 SC65 SHT11
8 TB4-48 TBOE1-10 C1-TBOE1-10 / TB4-48 2-1 89B-TB4-48 / TBOE1-10 CPD KN17 SC65 SHT11
9 TB4-49 TBOE1-9 C1-TBOE1-9 / TB4-49 2-1 89B-TB4-49 / TBOE1-9 CPD KN17 SC65 SHT11
10 TB1-1 TB10-3 C1-TB10-3 / TB1-1 2-1 89B-TB1-1 / TB10-3 CPD KN17 SC51 SHT14
11 TB1-2 TB10-4 C1-TB10-4 / TB1-2 2-1 89B-TB1-2 / TB10-4 CPD KN17 SC51 SHT14
12-14 SPARE
23 2 01 2023 2-1 89A C1 14CX2.5 1 80 1 TB3-1 TB1C-9 C1-TB1C-9 / TB3-1 2-1 89A-TB3-1 / TB1C-9 DI OF ISO & E/S CPD KN17 SC65 SHT08
2 TB3-2 TB1P1-20 C1-TB1P1-20 / TB3-2 2-1 89A-TB3-2 / TB1P1-20 CPD KN17 SC65 SHT08
3 TB4-26 TB1P1-22 C1-TB1P1-22 / TB4-26 2-1 89A-TB4-26 / TB1P1-22 CPD KN17 SC65 SHT08
DC SUPPLY TO BE
WIRED FROM P1
PANEL
4 TB1-14 TB1O1-1 C1-TB1O1-1 / TB1-14 2-1 89A-TB1-14 / TB1O1-1 CPD KN17 SC65 SHT08
5 TB1-13 TB1O1-2 C1-TB1O1-2 / TB1-13 2-1 89A-TB1-13 / TB1O1-2 CPD KN17 SC65 SHT08
6 TB3-21 TB1C-10 C1-TB1C-10 / TB3-21 2-1 89A-TB3-21 / TB1C-10 CPD KN17 SC65 SHT08
7 TB3-22 TB1O1-4 C1-TB1O1-4 / TB3-22 2-1 89A-TB3-22 / TB1O1-4 CPD KN17 SC65 SHT08
8 TB3-23 TB1O1-5 C1-TB1O1-5 / TB3-23 2-1 89A-TB3-23 / TB1O1-5 CPD KN17 SC65 SHT08
9 TB4-45 TB1C-11 C1-TB1C-11 / TB4-45 2-1 89A-TB4-45 / TB1C-11 CPD KN17 SC65 SHT08
10 TB4-46 TB1O1-7 C1-TB1O1-7 / TB4-46 2-1 89A-TB4-46 / TB1O1-7 CPD KN17 SC65 SHT08
11 TB4-47 TB1O1-8 C1-TB1O1-8 / TB4-47 2-1 89A-TB4-47 / TB1O1-8 CPD KN17 SC65 SHT08
12-14 SPARE
24 2 01 2024 2-1 89B C1 14CX2.5 1 55 1 TB3-1 TB1C-12 C1-TB1C-12 / TB3-1 2-1 89B-TB3-1 / TB1C-12 DI OF ISO & E/S CPD KN17 SC65 SHT08
2 TB3-2 TB1O1-10 C1-TB1O1-10 / TB3-2 2-1 89B-TB3-2 / TB1O1-10 CPD KN17 SC65 SHT08
3 TB4-26 TB1O1-11 C1-TB1O1-11 / TB4-26 2-1 89B-TB4-26 / TB1O1-11 CPD KN17 SC65 SHT08
4 TB1-14 TB1O1-13 C1-TB1O1-13 / TB1-14 2-1 89B-TB1-14 / TB1O1-13 CPD KN17 SC65 SHT08
5 TB1-13 TB1O1-14 C1-TB1O1-14 / TB1-13 2-1 89B-TB1-13 / TB1O1-14 CPD KN17 SC65 SHT08
6 TB3-21 TB1C-13 C1-TB1C-13 / TB3-21 2-1 89B-TB3-21 / TB1C-13 CPD KN17 SC65 SHT08
7 TB3-22 TB1O1-16 C1-TB1O1-16 / TB3-22 2-1 89B-TB3-22 / TB1O1-16 CPD KN17 SC65 SHT08
8 TB3-23 TB1O1-17 C1-TB1O1-17 / TB3-23 2-1 89B-TB3-23 / TB1O1-17 CPD KN17 SC65 SHT08
9 TB4-45 TB1C-14 C1-TB1C-14 / TB4-45 2-1 89B-TB4-45 / TB1C-14 CPD KN17 SC65 SHT08
10 TB4-46 TB1O1-19 C1-TB1O1-19 / TB4-46 2-1 89B-TB4-46 / TB1O1-19 CPD KN17 SC65 SHT08
11 TB4-47 TB1O1-20 C1-TB1O1-20 / TB4-47 2-1 89B-TB4-47 / TB1O1-20 CPD KN17 SC65 SHT0811 TB4-47 TB1O1-20 C1-TB1O1-20 / TB4-47 2-1 89B-TB4-47 / TB1O1-20 CPD KN17 SC65 SHT08
12-14 SPARE
201-BUS COUPLER_05.09.2011 Page 13 of 18 Cables between SWYD to Kiosk-CR
INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)
VVG
PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision
OWNERS CONSULTANTL&T S&L 31.08.2011 01
EPC CONTRACTORL&T POWER, VADODARA VVG
CONTRACTORS CONSULTANTDCPL, KOLKATA
EBOP CONTRACTORAREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG
ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :
FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.
CABLES BETWEEN SWITCHYARD TO KIOSK-CR
EQUIPMENT DESIGNATIONSL.
NO
Prepared by
Checked by
CABLE NO.
Approved byAREVA T&D INDIA LTD.
NO. OF
RUNSSIZE
INTERCONNECTION DETAILSESTIMATED
LENGTHROUTING DETAILS
Ferrule Nos.
25 2 01 2025 2- B189 C1 14CX2.5 1 70 1 TB1-9 TBOE1-11 C1-TBOE1-11 / TB1-9 2- B189-TB1-9 / TBOE1-11 DC, CONTROL, I/L CPD KN17 SC65 SHT11
2 TB1-10 TB0E1-12 C1-TB0E1-12 / TB1-10 2- B189-TB1-10 / TB0E1-12 CPD KN17 SC65 SHT11
3 TB1-11 TB0E1-14 C1-TB0E1-14 / TB1-11 2- B189-TB1-11 / TB0E1-14 CPD KN17 SC65 SHT11
4 TB1-3 TB0E1-15 C1-TB0E1-15 / TB1-3 2- B189-TB1-3 / TB0E1-15 CPD KN17 SC65 SHT11
5 TB1-6 TB0E1-16 C1-TB0E1-16 / TB1-6 2- B189-TB1-6 / TB0E1-16 CPD KN17 SC65 SHT11
6 TB4-45 TB0E1-19 C1-TB0E1-19 / TB4-45 2- B189-TB4-45 / TB0E1-19 CPD KN17 SC65 SHT116 TB4-45 TB0E1-19 C1-TB0E1-19 / TB4-45 2- B189-TB4-45 / TB0E1-19 CPD KN17 SC65 SHT11
7 TB4-46 TB0E1-21 C1-TB0E1-21 / TB4-46 2- B189-TB4-46 / TB0E1-21 CPD KN17 SC65 SHT11
8 TB1-1 TB10-5 C1-TB10-5 / TB1-1 2- B189-TB1-1 / TB10-5 CPD KN17 SC51 SHT15
9 TB1-2 TB10-6 C1-TB10-6 / TB1-2 2- B189-TB1-2 / TB10-6 CPD KN17 SC51 SHT15
10 SPARE
11 SPARE
12 SPARE
13 SPARE
14 SPARE
26 2 01 2026 2-B189 C1 10CX2.5 1 70 1 TB3-1 TB1C-18 C1-TB1C-18 / TB3-1 2-B189-TB3-1 / TB1C-18 DI OF ISO & E/S CPD KN17 SC65 SHT09
2 TB3-2 TB1N1-1 C1-TB1N1-1 / TB3-2 2-B189-TB3-2 / TB1N1-1 CPD KN17 SC65 SHT09
3 TB4-26 TB1N1-2 C1-TB1N1-2 / TB4-26 2-B189-TB4-26 / TB1N1-2 CPD KN17 SC65 SHT09
4 TB1-14 TB1N1-4 C1-TB1N1-4 / TB1-14 2-B189-TB1-14 / TB1N1-4 CPD KN17 SC65 SHT09
5 TB1-13 TB1N1-5 C1-TB1N1-5 / TB1-13 2-B189-TB1-13 / TB1N1-5 CPD KN17 SC65 SHT09
6 TB3-21 TB1C-19 C1-TB6-1 / TB3-21 2-B189-TB3-21 / TB6-1 CPD KN17 SC65 SHT09
7 TB3-22 TB1N1-7 C1-TB6-2 / TB3-22 2-B189-TB3-22 / TB6-2 CPD KN17 SC65 SHT09
8 TB3-23 TB1N1-8 C1-TB7-18 / TB3-23 2-B189-TB3-23 / TB7-18 CPD KN17 SC65 SHT09
9-10 SPARE
27 2 01 2027 2- B289 C1 14CX2.5 1 85 1 TB1-10 TBOF1-2 C1-TBOF1-2 / TB1-10 2- B289-TB1-10 / TBOF1-2 DC, CONTROL, I/L CPD KN17 SC65 SHT12
2 TB1-9 TBOF1-1 C1-TBOF1-1 / TB1-9 2- B289-TB1-9 / TBOF1-1 CPD KN17 SC65 SHT12
3 TB1-11 TBOF1-4 C1-TBOF1-4 / TB1-11 2- B289-TB1-11 / TBOF1-4 CPD KN17 SC65 SHT123 TB1-11 TBOF1-4 C1-TBOF1-4 / TB1-11 2- B289-TB1-11 / TBOF1-4 CPD KN17 SC65 SHT12
4 TB1-3 TBOF1-6 C1-TBOF1-6 / TB1-3 2- B289-TB1-3 / TBOF1-6 CPD KN17 SC65 SHT12
5 TB1-6 TBOF1-5 C1-TBOF1-5 / TB1-6 2- B289-TB1-6 / TBOF1-5 CPD KN17 SC65 SHT12
6 TB4-45 TBOF1-8 C1-TBOF1-8 / TB4-45 2- B289-TB4-45 / TBOF1-8 CPD KN17 SC65 SHT12
7 TB4-46 TBOF1-7 C1-TBOF1-7 / TB4-46 2- B289-TB4-46 / TBOF1-7 CPD KN17 SC65 SHT12
8 TB1-1 TB10-7 C1-TB10-7 / TB1-1 2- B289-TB1-1 / TB10-7 CPD KN17 SC51 SHT15
9 TB1-2 TB10-8 C1-TB10-8 / TB1-2 2- B289-TB1-2 / TB10-8 CPD KN17 SC51 SHT15
10 SPARE
11 SPARE
12 SPARE
13 SPARE
14 SPARE
28 2 01 2028 2- B289 C1 10CX2.5 1 85 1 TB3-1 TB1C-20 C1-TB1C-20 / TB3-1 2- B289-TB3-1 / TB1C-20 DI OF ISO & E/S CPD KN17 SC65 SHT09
2 TB3-2 TBIN1-10 C1-TBIN1-10 / TB3-2 2- B289-TB3-2 / TBIN1-10 CPD KN17 SC65 SHT09
3 TB4-26 TB1N1-11 C1-TB1N1-11 / TB4-26 2- B289-TB4-26 / TB1N1-11 CPD KN17 SC65 SHT09
4 TB1-14 TB1N1-13 C1-TB1N1-13 / TB1-14 2- B289-TB1-14 / TB1N1-13 CPD KN17 SC65 SHT09
5 TB1-13 TB1N1-14 C1-TB1N1-14 / TB1-13 2- B289-TB1-13 / TB1N1-14 CPD KN17 SC65 SHT09
6 TB3-21 TB1C-21 C1-TB1C-21 / TB3-21 2- B289-TB3-21 / TB1C-21 CPD KN17 SC65 SHT09
7 TB3-22 TB1N1-16 C1-TB1N1-16 / TB3-22 2- B289-TB3-22 / TB1N1-16 CPD KN17 SC65 SHT09
8 TB3-23 TB1N1-17 C1-TB1N1-17 / TB3-23 2- B289-TB3-23 / TB1N1-17 CPD KN17 SC65 SHT09
9-10 SPARE
Note: In isolator Panel following terminals to be added. 1. TB3:25-29 and TB4:49-53
Note: DC supply for iso and ISO/E/S shall be wired from P1 to C1, in the panel at site.(BUS WIRED AT SITE),TB10-spare TBs shall be arranged
201-BUS COUPLER_05.09.2011 Page 14 of 18 Cables between SWYD to Kiosk-CR