2009-034 e v1 - nrcan.gc.ca€¦ · toxicity no high no global warming potential gwp 3260 - 1...
TRANSCRIPT
-
1
1
Daniel Giguère, ASHRAE, Ste-Foy, February 2, 2009
Refrigeration
Technologies under development
2
Themes
BackgroundFundamental principlesSecondary fluids Carbon dioxide refrigerantEjectors
-
2
3
BackgroundFor the past 20 years, the refrigeration industry has been hit hard by the environmental impacts of synthetic refrigerants.
4
Schedule for the Gradual Phase-Out of HCFCs
HCFC Production100.0%
65.0%
35.0%
10.0%0.5% 0.0%
0%
20%
40%
60%
80%
100%
1989 2004 2010 2015 2020 2030
In 2010, demand for HCFCs in the USA will exceed supply by 12.5 million kilograms in the refrigeration sector.
(U.S. Environmental Protection Agency)
No new R22 equipment
2,000,000 kg
-
3
5
PRESERVATION OF THE OZONE LAYER AND THE EARTH’S CLIMATE SYSTEMQuestions about hydrofluorocarbons and perfluorocarbonsIPCC/TEAP, 2005 http://www.ipcc.ch/ipccreports/special-reports.htm
Refrigerant leaks projected using a bottom-up approach suggest an annual global emission rate of 30% of the stored load.
6
GWP (PRG) of HFC Refrigerants
R404a = R125/143a/134aR410a = R32/125R507a = R125/143a
-
4
77
Fundamental PrinciplesRefrigeration cycle
8
Refrigeration Cycle
Pre
ssur
e
Enthalpy
-
5
9
Definition of COP
Qf + W = 4 kW
Qf = 3 kW
W= 1 kW
Pre
ssur
e
Enthalpy
COP = Qf = 3W
1010
Secondary Fluids Indirect Refrigeration Systems
-
6
11
Secondary Fluid
-25oF-20oF
-20oF
HFCs
12
Secondary Fluid
-20oF
Secondary fluid
Secondary fluid
Refrigerant limited to the mechanical room
Mechanical room
-
7
13
Advantages of Indirect Systems
1. Much less synthetic refrigerant
2. Better functioning
3. Much less complex
4. Lower maintenance costs
5. Increase in the quality and longevity of food products (for systems in supermarkets)
14
Significant Reduction in Refrigerant
75 to 90% less synthetic refrigerant;
At about $10/lb, could correspond to over $25,000 for an average supermarket;
Dramatic reduction in the potential for refrigerant leaks.
-
8
15
Better Operation
Less overheating of the compressor and therefore improved efficiency
Better possibility of installing sub-cooling; again, improved efficiency
More stable condensation pressure
Better controllability
No oil return problems
16
Less Complex
Only one evaporator with two expansion valves, located in the mechanical room rather than 50 evaporators with as many expansion valves several dozens of metres away from itNo pressure regulators to adjust or control. Secondary fluid balancing valves adjusted at start-upLow-pressure piping (often pre-isolated in synthetic material)
-
9
17
Less Expensive to Maintain
Refrigerant leaks are limited to the mechanical room and therefore easier to detect and less expensive
Overall maintenance costs can be reduced by almost 50% compared to a conventional direct expansion (DX) system (FMI Energy)
18
Product Quality
Less product loss
A more stable product temperature (1oF rather than 2.5oF for DX)
Shorter defrost cycle
-
10
19
The Disadvantages of Indirect Systems
Change
Expected loss of efficiency
Cost
20
Change
Not common practiceNew design and assessment criteria to learn and applyMaking these changes must be planned far in advance (who is doing what?)Tenders from contractors do not reflect the anticipated benefitsThis job is added to the many tasks and responsibilities for all stakeholders in the construction project
-
11
21
Expected Loss of Efficiency
Evaporation and condensation temperatures for secondary fluid systems are equal if not better than those for direct expansion (DX) systemsOverheating of compressors during suction is reduced to a minimumSub-cooling is very easy to integrate and it increases the refrigeration system’s efficiency by 10 to 25%The thermal inertia of the secondary fluid contributes to stabilizing the operation of the systemHeat recovery is more effective and can meet the heating load of a building
22
Cost
There are several hundred installations in North AmericaThe design criteria and choice of materials are increasingly being masteredThe cost is still higher than that of a DX system, but the difference is decreasing with time and will soon become a standard in the refrigeration industryOperating costs are less than or equal to those of DX systems
-
12
23
DX vs. Secondary Fluid
24
Types of Secondary Fluids
Without phase changeEthylene glycol (heat rejection in the condenser)Propylene glycol (10 to 32oF)Potassium formate (-30 to 0oF)Other antifreezes
With phase changeCarbon dioxide (CO2) (-50 to +20oF)Slurry (water, methanol, glycol, etc.) (0 to 32oF)
-
13
25
CO2: the Ideal Secondary FluidLiquid CO2 cools a fluid by evaporating in a
heat exchanger. A simple liquid pump is used to circulate the CO2
No corrosion Negligible pumping powerNo oil management problemsMinimal pipe diameterExceptional heat transfer features
26
CO2: Breadboard Model-30°C, CO2 Test chamber
Air coil
-
14
27
Slurries: the Secondary Fluid that Stores Energy
Slurry?Fine ice crystals (
-
15
2929
CO2: The Indispensable Refrigerant
http://www.r744.com/articles/2009-01-29-ashrae-winter-conference-r744-seminar.php
30
Carbon Dioxide
Is present in the atmosphere in a proportion of 375 ppmv (parts per million in volume) The concentration is increasing rapidly, by about 2 ppmv/yearR744 is a natural refrigerant, like water, air, ammonia and hydrocarbons
-
16
31
1850 199319601920 ----------1930
Golden age of CO2
Reinvention of CO2 in refrigeration
(G. Lorentzen) of NorwayInitial concept of CO2as a refrigerant (Alexander Twining, British patent)
Danfoss, Niels P Vestergaard Niels P Vestergaard Ver 2004-04-SI+US
First CO2 refrigeration system: Carle Linde
J&E Hall: first two-stage CO2 refrigeration system
CO2 transcritical cycle
CFCs invented, 1928
History of CO2
Montreal protocol
1Jan. 1, 1989
CO2 compressor
Around 1900
32
88°F
1070
145
400
-
17
33
0.33.42.1Saturated ΔT / ΔP = 1 psi at -40 [oF]2262436BTU/cubic foot at -40 [oF]16144137Boiling point at 400 psig [oF]
NOhighNOToxicity
1-3260Global Warming Potential GWP
1067/881640/270541/162Critical condition [psi/ oF]-69-28-51 Boiling point at 15 psig [oF]
NO(slightly)NOFlammability
000Ozone Depletion Potential ODPYESYESNONatural refrigerantCO2NH3R404ARefrigerant
Properties
34
+86oF
Enthalpy
717- CO2 Cascade System
CO2
-4oF
+5oF
Pres
sure
Enthalpy
Pres
sure
CO2
R717
-40oF
-40oF (135 psi)
+5oF (333 psi)
+86oF (171 psi)
-4oF (28 psi)
-40oF
Danfoss, Niels P Vestergaard Niels P Vestergaard Ver 2004-04-SI+US
R717
-
18
35
HFC - CO2 Cascade Systems
CO2
-4oF
+5oF
-40oF
-40oF
HFCs
-20oF
10oF20oF
20oF
HFCs
CO2
36
CO2 as a Secondary Fluid
-25oF-20oF
-20oF
HFCs
NO OIL
-
19
37
Transcritical CycleP
ress
ure
Enthalpy
The Eco-Cute hot water HP produces hot water at 180oF with a COP of 4 to 8!
38
IndustrialCommercialStrong arguments
Why CO2?
EnvironmentGradual elimination of substances that have an impact on the environment (HCFCs, HFCs):(ODP (Ozone Depletion Potential), GWP (Global Warming Potential) )
SafetyToxicity and flammability for systems using large quantities of ammonia
Costs• Lower operating costs• More efficient systems • Lower refrigerant costs• Lower component volume
�
�
��
-
20
39
ConclusionsIn the last 10 years, products available for applications using CO2 have become increasingly abundant. These applications cover all sectors.
Low-temperature refrigeration and heat pumps are especially appealing.
Operating pressures can be high, but the equipment is more compact and often more efficient.
It is a natural refrigerant that is safe and inexpensive.
Every refrigeration equipment manufacturer around the world is interested in CO2 as a refrigerant.
4040
Ejectors
-
21
41
What is an Ejector?
Primary nozzle Secondary nozzle
Actuating or primary fluid
Entrained,or secondary fluid
Diffuser
No moving parts
Mixing zone
Ejectors convert kinetic energy into pressure and quantity of movement. It is a thermocompressor.
42
Why Ejectors?
They are simple
They have no moving parts
They use no oil
There is a large variety of materials for building one
They can use any gas or refrigerant
-
22
43
Weaknesses
Operation is not a very flexible
Low apparent efficiency
Not well known; used primarily for recompressing vapour
Complex design (supersonic flow)
44
Applications
Using effluent as a source of energy for cooling
Or to recover heat through heat pumping
Trigeneration
-
23
45
Trithermal Combined Cycle
TC
Generator
Evaporator
Condenser
Qevap
Free Qgen !
W
46
Ejector Cycle Output
TC
wtwc
Qevap
Free Qgen !
W
Qgen
TC
Generator
Evaporator
Condenser
Qevap
W
ηeject = Qevap ≈ 0.5Qgen
Pre
ssur
e
Enthalpy
-
24
47
Applications
Integration into the refrigeration cycle to recover the expansion energy and increase the COP
48
Ejector Regulator
20oF
0oF
COP 26% higher
Pre
ssur
e
Enthalpy
-
25
49
Applications
Integration into the refrigeration cycle to recover the condensation energy to increase the thermal discharge temperature, thereby making it useful for heat recovery or increasing the COP of the refrigeration system.
50
Ejector Condenser
0oF
COP 20% higher
-
26
5151
Thank you