2005 nec ® code changes presenter mark nowak north east specification and project manager

39
2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

Upload: juniper-phillips

Post on 16-Jan-2016

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

2005 NEC® Code Changes

Presenter

Mark NowakNorth East Specification

and Project Manager

Page 3: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

3

This document was compiled through the efforts of the Technical Liaison Department of Thomas & Betts, and is the property of Thomas & Betts.

If you have any questions or require interpretation assistance please contact one of the following:

Tim McNeive 1-800-888-0211 Ext. 5785

Greg Steinman 1-800-888-0211 Ext. 5719

George Dauberger 1-800-888-0211 Ext. 5191

Do not duplicate any part of this publication without the permission of a member of the T&B Technical Liaison Department.

2005 NEC® Changes

Page 4: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

4

General

The phrase “Listed for the purpose” has been removed from the NEC and replaced with “Listed as ____”. This provides users more guidance on the proper application of Listed products. Annex A of the NEC includes a list of Product Safety Standards for reference. An example would be products listed as “grounding and bonding equipment” as opposed to “listed for the purpose”.

Page 5: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

5

Article 100 Definitions

Section 100 (I) GeneralA new definition was added for

Grounding Electrode: A device that establishes an electrical connection to the earth.

Page 6: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

6

Article 200 Use and Identification of Grounded Conductors

Section 200.6(B) Means of Identifying Grounded Conductors - Sizes Larger than 6 AWG.

An insulated grounded conductor larger than 6 AWG shall be identified by one of the following means:

(1) A continuous white or gray outer finish

(2) By three continuous white stripes along its entire length on other than green insulation

(3) At the time of installation, by a distinctive white or gray marking at its terminations. This marking shall encircle the conductor or insulation.

See illustration on the following page.

Page 7: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

7

Gray markings

Article 200 Use and Identification of Grounded Conductors

Page 8: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

8

Article 210 Branch Circuits

GFCI Protection is now required in the following locations:

Section 210.8 (B)(4) (New) Outdoors in public spaces

Section 210.8 (B)(5) (New) HVAC convenience receptacles for other than dwellings

Section 210.8 (C) (New) Boat Hoists

Page 9: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

9

Section 210.52(C)(1) (New Exception) Dwelling Unit Receptacle Outlets; Countertops; Wall Counter Spaces

A new exception and diagrams have been added to clarify how separate wall countertop spaces are determined and to clarify where outlets are and are not required.

See illustrations on the following pages.

Article 210 Branch Circuits

Page 10: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

10

Article 210 Branch Circuits

Page 11: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

11

Article 210 Branch Circuits

Page 12: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

12

Section 210.52(C)(2) Dwelling Unit Receptacle Outlets;

Countertop; Island Counter Spaces

New text has been added to clarify how separate countertop spaces are determined on island countertops. “Where a range top or sink is installed in an island counter, and the width of the counter behind the range top or sink is less than 300 mm (12 in.), the range top or sink is considered to divide the island into two separate countertop spaces as defined in 210.52(C)(4).”

See the following illustration.

Article 210 Branch Circuits

Page 13: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

13

Article 210 Branch Circuits

Page 14: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

14

Article 230 Services

Section 230.44 Cable Trays. ExceptionConductors, other than service-entrance conductors, shall be permitted to be installed in a cable tray with service entrance conductors provided a solid fixed barrier of a material compatible with the cable tray is installed to separate the service entrance conductors from the other conductors installed in the cable tray.

Page 15: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

15

Article 250 Grounding and Bonding

ANALYSIS OF CHANGE: The title of Article 250 has been

changed from “Grounding” to “Grounding and Bonding”. This

article has always included the rules for bonding. There are

differences in these two terms and this is an effort to emphasize

the distinct differences.

Bonded- The permanent joining of metallic parts to form an

electrically conductive path that ensures electrical continuity and

the capacity to conduct safely any current likely to be imposed.

Grounded - Connected to earth or some conducting body thatserves in place of the earth.

Page 16: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

16

Section 250.8 Connection of Grounding and Bonding Equipment

Sheet metal screws shall not be used to connect groundingconductors or connection devices to enclosures.

Article 250 Grounding and Bonding

Page 17: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

17

Section 250.30 Grounding Separately Derived AlternatingCurrent SystemsThe section was completely rewritten.250.30 (A)(4)(c) Connections. All tap connections to thecommon grounding electrode conductor shall be made at anaccessible location by one of the following methods:

1)a listed connector

2)listed connections to aluminum or copper busbars not lessthan 6 mm x 50 mm (b in. x 2 in.). Where aluminum

busbars are used, the installation shall comply with 250.64(A).

3)by the exothermic welding process

Article 250 Grounding and Bonding

Page 18: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

18

Section 250.50 Grounding Electrode SystemThe term “if available” was replaced with “are present” to describethe existing grounding electrodes that must be bonded together. In addition, an exception was added for concrete encasedelectrodes at existing buildings or structures. These electrodes donot have to be bonded where the re-enforcing bars or rods are not accessible for use without disturbing the concrete.

Exception: Concrete-encased electrodes of existing buildings orstructures shall not be required to be part of the groundingelectrode system where the steel reinforcing bars or rods are notaccessible for use without disturbing the concrete.

Article 250 Grounding and Bonding

Page 19: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

19

Section 250.126 Identification of Wiring Device Terminals FPN:

Section 406.9(B)(4) and Figure Grounding-

The Grounding Symbol was changed to a fine print note.

Article 250 Grounding and BondingArticle 406 Receptacles, Cord Connectors and Attachment Plugs (Caps)

Page 20: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

20

Section 250.146(A) Connecting Receptacle Grounding Terminal to Box; Surface Mounted BoxAt least one of the insulating washers shall be removed from receptacles that do not have a contact yoke or device that complies with 250.146(B) to ensure metal to metal contact.

Article 250 Grounding and Bonding

Page 21: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

21

Article 300 Wiring Methods

Section 300.4Several changes have been made to the section covering “Protection Against Physical Damage”.

1. Installations where cables are run parallel to furring strips are required to utilize cable protection.

2. Protection for cables can be supplied by a steel plate less than 1/16 inch thick as long as it provides equal or better protection.

3. Cables run in notches must comply with the protection requirement.

Page 22: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

22

Section 300.18(A) Exception (New) Raceway Installations; Complete Runs

Add the following exception: “Short sections of raceways used to contain conductors or cable assemblies for protection from physical damage shall not be required to be installed complete between outlet, junction, or splicing points.”

Article 300 Wiring Methods

Page 23: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

23

Article 300 Wiring Methods

Section 300.22(B) Wiring in Ducts Plenums, and other Air-Handling Spaces; Ducts or Plenums Used for Environment Air

The term “Liquidtight Flexible Metal Conduit” was removed from the list of approved wiring methods permitted to be used in ducts or plenums specifically used to transport environmental air.

Page 24: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

24

Section 312.2(A) Damp, Wet, or Hazardous (Classified) Locations; Damp and Wet Locations.

The following sentence will be added to the end of the section.

“For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts shall use fittings listed for wet locations.”

Article 300 Wiring Methods

Page 25: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

25

Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies; Fittings; and Handhole Enclosures

Section 314.16(B)(1) Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies, Box Fill Calculations, Conductor Fill.

A new second sentence was added to the section and reads as follows: A looped, unbroken conductor not less than twice the minimum length required for free conductors in 300.14 shall be counted twice.

Page 26: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

26

combustible non-combustible

Section 314.20 In Wall or Ceiling

This section was revised to add plaster rings, domed covers,

extension rings and listed extenders to the installation

requirements relative to the surface of the wall or ceiling.

Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies; Fittings; and Handhole Enclosures

Page 27: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

27

Section 314.23(B)(1) Supports; Structural Mounting; Nails and Screws.This change adds the following sentence to the end of the requirement, “Screws shall not be permitted to pass through the box unless exposed threads in the box are protected using approved means to avoid abrasion of conductor insulation.”

Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies; Fittings; and Handhole Enclosures

Page 28: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

28

Articles 342, 344, 348, 350, 352, 356, 358, 362

Bends - How made

This change moves the table that specifies the radius of the curve for bends to Table 2, Chapter 9.

Page 29: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

29

Articles 342(IMC), 344(RMC), 358(EMT)

Section 342.42(A)

Section 344.42(A)

Section 358.42

The reference “raintight type” was changed to “...comply with

314.15(A)”.

Page 30: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

30

Articles 342(IMC) and 344(RMC)

Section 342.30(B)(3) Securing and Supporting; SupportsSection 344.30(B)(3) Securing and Supporting; SupportsThe phrase “firmly supported” did not adequately secure the raceway, so the term was changed to “securely fastened” so the section reads, “Exposed vertical risers from industrial machinery or fixed equipment shall be permitted to be supported at intervals not exceeding 6 m (20 ft.), if the conduit is made up with threaded couplings, the conduit is securely fastened at the top and bottom of the riser, and no other means of intermediate support is readily available.

Page 31: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

31

Article 356 - Liquidtight Flexible Nonmetallic Conduit

Section 356.42 Couplings and Connectors

The Section was revised as follows:

“356.42 Connectors and Couplings. Only fittings listed for use with LFNC shall be used. Angle connectors shall not be used for concealed raceway installations.”

Page 32: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

32

Articles 386, 388 Surface Raceways

Section 386.56 Splices and TapsSection 388.56 Splices and Taps

The word “junction” was removed from the following requirement: “Splices and taps in surface nonmetallic raceways without removable covers shall be made only in boxes.

Page 33: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

33

Section 386.70 Combination RacewaysSection 388.70 Combination RacewaysThis change revises the means for identifying data and powercompartments in surface nonmetallic raceway. Previously, the compartments had to be marked with sharply contrasting colors. This change permits stamping, imprinting or color-coding as a means of identification.

Articles 386, 388 Surface Raceways

Page 34: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

34

Article 390 Underfloor Raceways

Section 390.17 Ampacity of Conductors (New)

The following new Section was added:

“390.17 Ampacity of Conductors. The ampacity adjustment factors in 310.15(B)(2) shall apply to conductors installed in underfloor raceways.”

Page 35: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

35

Article 392 Cable Tray

Section 392.11(B)(3) Ampacity of Cables, Rated 2000 Volts orLess, in Cable Trays; Single-Conductor Cables; Exception (New)

The exception was added to 392.11(B)(3) so it reads:

“(3) Where single conductors are installed in a single layer in uncovered cable trays, with a maintained space of not less than one cable diameter between individual conductors, the ampacity of 1/0 AWG and larger cables shall not exceed the allowable ampacities in Tables 310.17 and 310.19.

Exception: For solid bottom cable trays the ampacity of singleconductor cables shall be determined by 310.15(C).

Page 36: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

36

Article 406 Receptacles, Cord Connectors and Attachment Plugs (Caps)

Section 406.8(B)(1) Receptacles in Damp or Wet Locations; Wet Locations; 15 and 20 Ampere Receptacles.

This Section was revised by deleting “outdoor” to read as follows: 15 and 20 ampere, 125 and 250 volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the plug cap is inserted.

Page 37: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

37

Article 409 Industrial Control Panels

Entire Article is new

This article was added to the NEC® to provide guidance to AHJ’s for the proper installation of industrial control panels. Locating the requirements in one article makes it easier to locate the needed information.

Page 38: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

38

Article 430 - Motors, Motor Circuits, and Controllers

Section 430.102(B) Location; Motor; Exception

This second sentence of the exception was revised to read as follows: The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed.

Page 39: 2005 NEC ® Code Changes Presenter Mark Nowak North East Specification and Project Manager

39

Article 518 Assembly Occupancies

Section 518.4(C) Wiring Methods; Spaces with Finish Rating

The title of the article was changed from “Places of Assembly” to

“Assembly Occupancies”. College and university classrooms,

drinking establishments, passenger stations and terminals of air,

surface, underground, and marine public transportation facilities

have all been removed from the list of locations where electrical

nonmetallic tubing and rigid nonmetallic conduit may be used in

spaces with finish rating.