    WSA/D1381 Rev 0/2003 15075/1 Mechanical Identification

    SECTION 15075

    MECHANICAL IDENTIFICATION

    REVISION HISTORY

    0 18.04.03 Mechanical IdentificationRichard

    Smith

    Steve

    King

    Richard

    Smith

    Rev Date Description Preparedby

    Checkedby

    Authorisedby

  • 8/13/2019 15075 Rev 0

    2/13

    WSA/D1381 Rev 0/2003 15075/2 Mechanical Identification

    1 GENERAL

    1.1 SECTION INCLUDES

    1.1.1 Include the General Conditions of the Contract as part of this section.

    1.1.2 The Contractor shall become familiar with other sections of the Specifications affecting work

    of this trade.

    1.1.3 Furnish all labour, materials, plant, equipment and appliances and perform all necessary

    operations required to execute the work of this section.

    1.1.4 This section describes the requirements for the identification of mechanical services.

    1.2 RELATED SECTIONS

    1.2.1 This schedule is intended to be used as a helpful indication of the related sections within the

    Project Specifications. It is not necessarily comprehensive or complete and it is the

    Contractor's responsibility to ascertain all applicable sections required to understand the fullScope of Works intended.

    15130 Pumps

    15150 Pressure Pipeline

    15720 Air Handling Units and Fan Coil Units

    15830 Fans

    15710 Heat Exchangers

    15815 Ductwork and Accessories

    15910 BEMS

    15300 Fire Suppression and Sprinkler Systems

    15090 Thermal Insulation

    15190 Liquefied Petroleum Gas

    1.3 REFERENCES

    1.3.1 The minimum standards for products specified in this section shall be those standards referred

    to or relevant BSI standards.

    1.4 SUBMITTALS FOR REVIEW

    1.4.1 Section 01300 - Submittals.

    1.4.2 Submit full details of each method of identification and installation method in accordance with

    the Contract Documents. Submissions shall indicate all dimensions, details of constructiondetails of installation, relation and connections with adjoining work.

    1.5 QUALITY ASSURANCE

    1.5.1 Perform Work in accordance with relevant British Standards and industry standard codes.

    1.6 QUALIFICATIONS

    1.6.1 No requirements

    1.7 MOCK-UP

    1.7.1 Provide full size mock up of each type of identification.

  • 8/13/2019 15075 Rev 0

    3/13

    WSA/D1381 Rev 0/2003 15075/3 Mechanical Identification

    1.8 ENVIRONMENTAL REQUIREMENTS

    1.8.1 Identification labels and valve diagrams shall be suitable for the environment in which they

    are installed.

    1.9 WARRANTY

    1.9.1 Section 01740 - Warranties and Bonds.

    2 PRODUCTS

    2.1 APPROVED MANUFACTURER OR PRODUCT

    2.1.1 No particular preference.

    2.2 GENERAL REQUIREMENTS

    2.2.1 All pipe work and ductwork services shall be identified in accordance with BS1710.

    2.2.2 All items of plant, equipment and apparatus shall be allocated and shall bear a unique

    reference number (URN) in accordance with the Engineers site wide referencing system (see

    appendix). If the site wide referencing system is deficient in any way the Contractor shall

    suggest suitable modifications to the Engineer and seek approval for such modifications to be

    used.

    2.2.3 All plant, equipment and apparatus indicated on drawings prepared by the Contractor shall be

    annotated with the URN.

    2.2.4 All methods of identif ication shall be approved by the Engineer.

    2.2.5 All identification shall be permanently applied in a manner approved by the Engineer.

    2.3 ABOVE GROUND SERVICES IDENTIFICATION

    2.3.1 The entire surface area of the liquefied petroleum (LPG), fuel oil, diesel oil, compressed air,

    sprinkler, fire hose reel, cold water service, cooled cold water and condenser water services

    shall be permanently identified with a colour in accordance with BS1710. This shall be

    achieved by painting the entire pipeline with a primer coat (following proper preparation) and

    then two coats of good quality paint or by employing a pipework system with self colour

    properties or an approved sheath such as Yorkshire Kuterlux, in case of copper pipes. Paint,

    self colour properties and sheaths shall be coloured as BS 1710.

    2.3.2 All pipework in services subways or corridors shall have their entire surface area identified as

    required by 2.3.1, above.

    2.3.3 In addition to those referred to in 2.3.1 and 2.3.2 above, all other pipework and ductwork

    services that are concealed in risers and ceiling voids shall have their entire surface area

    finished as required by the thermal insulation standard specification using standard materials /

    colours, as specified.

    2.3.4 In addition to those referred to in 2.3.1 and 2.3.2 above, all other pipework and ductwork

    services that are exposed to view shall have their entire surface area finished as required by

    the thermal insulation standard specification using the standard materials / colours, as

    specified.

  • 8/13/2019 15075 Rev 0

    4/13

    WSA/D1381 Rev 0/2003 15075/4 Mechanical Identification

    2.3.5 All services, whether concealed or exposed to view shall be identified with identification

    bands. These bands shall be coloured as BS1710 and shall also bear direction of flow arrows

    and an abbreviation to identify the service.

    2.3.6 Identification bands shall be applied in each riser section, at 15m centres in ceiling voids /

    subways / service corridors and in locations in plantroom and laundry spaces where it is

    possible to see an ID band for any service from any vantage point.

    2.3.7 Standard abbreviations to be used on services identification bands shall include:

    ChW Chilled water

    HRChW Heat recovery chilled water

    CW Condenser water

    LTHW Low temperature hot water

    HRLTHW Heat recovery low temperature hot water

    HWS Hot water service

    CWS Cold water service

    CCWS Cooled cold water service

    RUHWS Reuse hot water service

    THWS Tempered hot water service

    WHWS Waste water hot water service.

    LPG Liquefied petroleum gas

    CA Compressed air

    St(10) 10 bar(g) steam

    St(7.5) 7.5 bar(g) steam

    St(5.5) 5.5 bar(g) steam

    Cond Condensate (steam system)

    Con Condensate (a-c system)

    GS Gravity sewage

    PS Pumped sewage

    FHR Fire hose reel Sprinkler Sprinkler

    SD Sprinkler drain

    F Flow (liquid circulation systems)

    R Return (liquid circulation systems)

    CF Cold feed

    Exp Expansion

    PSA Primary supply air

    PEA Primary extract air

    SA Supply air

    RA Recirculation air

    EA Extract air

    KEA Kitchen extract air

    Exh Exhaust air IA Intake air

    [D] Dirty

    [C] Clean

    2.4 BELOW GROUND SERVICES IDENTIFICATION

    2.4.1 All below ground services shall be identified by a unique colour per service.

    2.4.2 Refer to particular specification for details.

    2.5 PLANT AND EQUIPMENT TALLY PLATES

    2.5.1 All items of plant and equipment shall have a permanently fixed tally plate that shall include

  • 8/13/2019 15075 Rev 0

    5/13

    WSA/D1381 Rev 0/2003 15075/5 Mechanical Identification

    the following information as a minimum:

    Makers name and contact details;

    Date of manufacture;

    Makers reference number that will allow item to be traced in future.

    Working pressure (liquid items)

    Test pressure (liquid items) Basic duty parameters;

    Dry weight (if in excess of 1 tonne)

    2.5.2 Where plant and equipment is insulated the tally plate shall be extended so that insulation can

    be placed behind the plate.

    2.6 VALVE, STRAINER, COCK AND STEAM TRAP IDENTIFICATION

    2.6.1 Every valve, strainer, cock and steam trap shall be identified with a unique reference number

    (URN) in accordance with the sitewide referencing system (see appendix)

    2.6.2 Valve, strainer, cock and steam trap URNs shall be indicated on as built drawings and in O&Mmanuals.

    2.6.3 Valve, strainer, cock and steam traps shall be identif ied with a brass or approved plastic fob

    which shall be permanently engraved (10mm Arial font) with the URN. The fob shall be

    permanently attached with a chain.

    2.6.4 In addition to the URN, commissioning sets and metering stations shall have commissioned

    flow rate (kg/s) and signal pressure (mm w.g.) engraved on the fob in 6mm Arial font.

    2.6.5 In addition to the URN, differential pressure valves shall have the commissioned differential

    pressure set point engraved onto the fob in 6mm Arial font.

    2.6.6 All motorised and solenoid valves shall have a URN identification fob as described above. In

    addition the fob shall have the valve flow rate (kg/s) permanently engraved onto it in 6mm

    Arial font.

    2.6.7 Valve diagrams shall be sited on walls in locations agreed with the Engineer. These valve

    diagrams shall provide an isometric or general arrangement layout of the services in the

    vicinity of the chart and shall clearly indicate each valve, strainer, cock and steam trap URN.

    Valve diagrams shall be heat sealed onto moisture resistant MDF with edges sealed with two

    coats of matt black paint. Valve URNs, types and services shall also be indicated in tabular

    format on the diagram.

    2.7 AIR HANDLING UNIT, PRIMARY AIR HANDLER A ND FAN IDENTIFICATION

    2.7.1 This section applies to all type of air handling unit (e.g PAH, AH) and fans (eg KEF, EF)

    2.7.2 Each air handling unit and fan shall be identified with its URN using a permanent traffolite

    label that shall be fixed to the casing of the unit in a prominent location. The label shall have

    black 25mm Arial font on a white background.

    2.7.3 A permanent engraved traffolite label shall be fixed onto the air handling unit/fan casing in a

    location that corresponds with the each component inside. The label shall contain the

    following information and shall have 6mm black Arial font on a white background:

    Dampers

    - Fixed or motorised- Number

  • 8/13/2019 15075 Rev 0

    6/13

    WSA/D1381 Rev 0/2003 15075/6 Mechanical Identification

    - Mixing or ON/Off

    Filter

    - Type (bag or panel)

    - Grade (G2, G3.F7, F8, etc)

    - Clean resistance (Pa)

    - Max Dirty resistance (Pa)

    Heating or Cooling Coils

    - Duty (kW)

    - Liquid temperatures (C)

    - Airside resistance (Pa)

    - Waterside resistance (kPa)

    Fans

    - Type

    - Duty (m3/s)

    - Fan static pressure (Pa)

    - External total resistance to unit (Pa)- Motor rating (kW)

    - Full load current (A)

    Heat recovery device

    - Type

    - Duty (kW)

    - Air side resistance (Pa)

    - Electrical rating (kW)

    2.8 VOLUME CONTROL DAMPERS

    2.8.1 Volume control dampers shall be permanently marked with their setting. A permanent label

    shall be affixed to the damper to indicate the flow rate that has been achieved during

    commissioning.

    2.9 PUMP IDENTIFICATION

    2.9.1 All pumps shall bear a permanent label that shall identify their URN, design flow rate, design

    head, no flow head, electrical motor rating and full load current.

    2.9.2 Labels shall be as 2.7.2, above but in addition shall include the pump duty in kg/s and kPa

    using 6mm Arial font.

    2.10 FIRE EQUIPMENT IDENTIFICATION

    2.10.1 Fire hose reel cabinets, dry riser stations and fire tender connection points shall be identified

    in accordance with ROP Civil Defense requirements.

    2.10.2 In addition, each fire hose reel shall be marked with a sequential reference number. A

    separate numbering system shall be adopted for each building or building group. This number

    shall be indicated on the door (bottom right hand corner) of each fire hose reel cabinet and

    shall be prefixed FHR This identication shall be sign written or created with proprietary self

    adhesive letters using a 20mm black Arial font.

    2.10.3 Similarly, dry riser outlets shall be identified in the same way as fire hose reels but the prefix

    shall be dry riser inlets shall leave prefix DR.

  • 8/13/2019 15075 Rev 0

    7/13

    WSA/D1381 Rev 0/2003 15075/7 Mechanical Identification

    2.10.4 Sprinkler zone valves shall be identified in the same way as fire hose reels but the prefix shall

    be SZV

    2.11 BUILDING ENERGY MANA GEMENT SYSTEM (BEMS) IDENTIFICATION

    2.11.1 All MCCs, outstations, starters, variable speed drives, sensors, detectors, switches,

    thermostats, actuators and items of head end equipment shall be clearly identified inaccordance with the site wide identification system. Where specific references are not

    included in the site wide identification system the Contractor shall devise suitable references,

    as required.

    2.11.2 Identification shall be achieved by engraving of the item of equipment / apparatus of by

    affixing (glue and screwed) engraved or proprietary, permanent, printed self-adhesive labels

    (not as Dymo).

    2.11.3 BEMS identification references shall be reflected in the Contractors material submittals,

    working drawings, points schedules, as built documents and operating and maintenance

    documents.

    2.12 HEAT EXCHANGERS (SEE OVER)

    2.12.1 All heat exchangers shall bear a URN identification label as described for air handling units in

    2.7.2 above. In addition the label shall provide the following information in 6mm Arial font.

    Heat exchanger rating (kW)

    Hot liquid inlet and outlet temperatures (oC)

    Cold liquid inlet and outlet temperatures (oC)

    3 EXECUTION

    3.1 EXAMINATION

    3.1.1 Verify site conditions under provisions of Section 01400.

    3.1.2 Before ordering any materials/commencing work verify that building structure associated with

    the system is within tolerance and take full account of shape configuration and material

    properties of the structure.

    3.2 HANDLING AND STORAGE

    3.2.1 Deliver component parts to site, completely identified in accordance with shop and certified

    drawings prepared for this work. Store in accordance with manufacturer's instructions, above

    ground, properly protected from the weather and construction activities.

    3.3 INSTALLATION

    3.3.1 Before beginning installation in any area, examine all parts of the adjoining work into which

    applicable work is to be placed. Should any conditions be found which will prevent the proper

    execution of the work, installation shall not proceed in that area until such conditions are

    corrected by the contractor.

    3.4 FIELD QUALITY CONTROL

    3.4.1 Provide field quality control under provisions of Section 01400 - Quality Control.

  • 8/13/2019 15075 Rev 0

    8/13

    WSA/D1381 Rev 0/2003 15075/8 Mechanical Identification

    3.5 CLEANING

    3.5.1 Section 01710 - Cleaning installed work.

    3.5.2 Remove any paint or concrete splatters after work is complete.

    3.6 PROTECTION OF FINISHED WORK

    3.6.1 Protect work under provisions of Section 01710.

    3.7 STANDARD SPECIFICATION

    3.7.1 This standard specification is intended to be used as a helpful indication of work within this

    section. It is not necessarily comprehensive or complete and it is the Contractor's

    responsibility to ascertain and complete the full works intended and as shown within the

    drawings, specification and Contract or thereby implied.

  • 8/13/2019 15075 Rev 0

    9/13

    WSA/D1381 Rev 0/2003 15075/9 Mechanical Identification

    SITEWIDE REFERENCING SYSTEM - BUILDING SERVICES

    Unique Identification Number (URN)

    V 01 P 5 B URN presentation format :

    V-01-P5(B)

    BuildingComplexletter

    (seeschedule1)

    Subareacode

    (seeschedule2)

    Plant/equipmentcode

    (seeschedule3)

    Plantequipmenttype

    sequentialnumber

    Standbyplantdesignation

    (A=

    duty;B=

    standby)

    SCHEDULE 1 - BUILDING COMPLEX LETTER

    V Village Hotel

    T Town Hotel

    C Castle Hotel

    X Externals + Utility Compound

    SCHEDULE 2 - SUB AREA CODE LETTER

    B1 BasementG Ground floor

    01 First floor

    02 Second floor

    03 Third floor

    04 Fourth floor

    R Roof

    S Subway duct

    STP Sewage Treatment Plant Compound

    RO Reverse Osmosis Plant Hall

  • 8/13/2019 15075 Rev 0

    10/13

    WSA/D1381 Rev 0/2003 15075/10 Mechanical Identification

    SCHEDULE 3M - MECHANICAL BUILDING SERVICES LETTER CODES

    2MV 2 port motorised valve

    3MV 3 port motorised valve

    A Duct mounted attenuatorPAH1 100% freshaire AHU with only supply fan

    PAH2 100% fresh air with cooling and reheat and supply fan

    PAH3 100% fresh air AHU with S&E fans and heat recovery

    PAH4 100% freshaire AHU with S&E fans and double heat recovery

    AH1 Recirculating AHU with 2 way mixing box and supply fan

    AH2 Recirculating AHU with 3 way mixing box and S&E fans

    AH3 Recirculating AHU with 3 way mixing box and S&E fans and heat recovery

    AV Pressure accumulator vessel

    AVV Anti vacuum valve

    B Boiler

    BS Booster setCA Duct mounted cross talk attenuator

    CCE Cold room evaporator unit

    CCU Cold room condensing unit

    CDC Cold room door curtain

    CDH Cold room door heater

    CH Chiller

    CHM Cold room heater mat

    CPV Cold room pressure valve

    CS Commissioning set

    CT Cooling Tower

    CVU Contant air volume unitDPV Differential pressure valve

    EG Extract grille

    ENM LTHW or ChW energy meter

    EV Extract valve

    FCUS Surface mounted, exposed to view fan coil unit

    FCUV Void mounted fan coil unit

    FH External fire hydrant

    FS Fume scrubber

    GCP Emergency gas control panel

    GD Gas detector

    GM Gas meterHDH Ductwork mounted humidity detector

    HR Hose reel

    HWC Hot water cylinder

    HWD Wall mounted humidity detector

    KC Kitchen canopy

    LPGT Liquefied petroleum gas tank

    MD Motorised damper

    MGV Motorised gas valve (emergency)

    MS Metering station

    OG Ozone generator

    P PumpPDD Ductwork pressure detector

  • 8/13/2019 15075 Rev 0

    11/13

    WSA/D1381 Rev 0/2003 15075/11 Mechanical Identification

    SCHEDULE 3M - MECHANICAL BUILDING SERVICES LETTER CODES

    PDDD Ductwork differential pressure detector

    PDPD Pipeline differential pressure detector

    PDS Ductwork pressure switch

    PHEX Plate heat exchanger

    PPD Pipeline pressure detectorPPS Pipeline pressure switch

    PRV Pressure reducing valve

    PU Pressurisation / fill unit

    PWC Chilled potable water cylinder

    RO Reverse osmosis stream

    SD Smoke damper

    SD Supply diffuser

    SF Sand filter

    SG Steam generator

    SPTP Sprinkler test point

    SPV Sprinkler valveSV Safety valve

    T Tank

    TCD Tank contents detector

    TDD Ductwork temperature detector

    TG Transfer grille

    TPD Pipeline temperature detector

    TPS Pipeline mounted thermostat

    TPSH Pipeline mounted thermostat (high limit)

    TS Textile sock range

    TWD Wall mounted temperature detector

    TWT Wall mounted thermostatWM Water meter

    WMS Water manifold set

    WTP Water treatment plant

    FL Fusible link (cable mounted)

    OV Emergency oil shut off valve (gravity operated)

  • 8/13/2019 15075 Rev 0

    12/13

    WSA/D1381 Rev 0/2003 15075/12 Mechanical Identification

    SCHEDULE 3E - ELECTRICAL BUILDING SERVICES LETTER CODES

    MCC Motor control centre

    MSB Main switchpanel

    SMDB Sub main distribution boardSG Standby generator

    ERG Earthing rod group

    EM Earthing mat

    TR Transformer

    RMU Ring main unit

    DB Distribution board

    FCPM Master fire alarm control panel

    FCPR Repeater fire alarm control panel

    FAHE Fire alarm head end

    GLRU Guestroom lighting relay unit

    ELSS Emergency lighting sub battery / control unitELHE Emergency lighting head end

    UPS Passive uninterrupted power supply and battery unit

    EM Sub electrical meter

    PABXM Master PABX

    PABXS Slave PABX

    OFH Optic fibre hub

    CPP Communication cable patch panel

    DPP Data cable patch panel

    TOS Telephone operator's station

    TVSE TV Satellite dish farm and head end

    TVHE TV system head end and primary amplification equipmentTVPPV TV system pay per view equipment

    TVSD TV system sub distribution equipment

    PMSHE PMS / POS head end equipment

    PMSSE PMS / POS satellite equipment

    LOCC Local optic fibre / copper converter

    CCTVHE CCTV head end equipment

    CCTVSE CCTV satellite equipment

    BEMSHE Main BEMS human interface consule

    BEMSIE Local BEMS human interface consule

    BEMSLP BEMS laptop connection point

    BEMSOS BEMS outstationDDB Distribution board with full scene dimming facility

    MS Microphone station

    AS Amplifier station

    BGMS Background music sources

    ICP Islamic clock and call to prayer unit

  • 8/13/2019 15075 Rev 0

    13/13

    WSA/D1381 Rev 0/2003 15075/13 Mechanical Identification

    SCHEDULE 3P - PUBLIC HEALTH BUILDING SERVICES LETTER CODES

    BD Bidet

    BTH BathFCT Faucet set

    GI Grease interceptor

    RV Anti shock reflux valve

    SC Standard connection assembly type

    SHT Sewage holding tank

    SHV Shower valve

    SP Sump pump

    ST Shower tray

    STP Sewage treatment plant

    SVP Soil and vent pipe stack

    SWP Sewage pumpU Urinal stall

    WC Water closet pan

    WCC Flushing cistern

    WHB Wash hand basin

    END OF SECTION