1.4 operation of the remote control™s inspection / test ..._[angol]_szervíz... · malfunction...
TRANSCRIPT
Troubleshooting by Remote Control SiEN30-602
150 Troubleshooting
1.4 Operation of the Remote Control�s Inspection / Test Operation Button
Inspection/test operation
Example model
FXCQ25
FXFQ63
Example of capacity code display
Display
028
071
Product classification
VRV system
VRV system
VRV system
VRV system
Display
1
2
F
H
Indoor unit system code
System classification
(VAV indoor unit)
Outdoor air processing unit
Standard indoor unit
New ceilling suspended cassette
Indoor unit type code
Type
VRV System Inverter K Series
R-407C VRV PLUS Series
VRV Heat Recovery Series
High COP type R-407C L Series
VRV II
VRV II Heat Recovery
VRV II Water cooled inverter series
Display
A A 1
A A 3
A 9 2
A A 5
A A A
A 96
A F C
Outdoor (or outside) unit model code
Model
RSXYP
RXYP
RSEYP
RSXYP-L
RXYQ-M
REYQ-M
RWEYQ-M
UnitMalfunction codeInspection
Normal display (No display)
0L 0
Malfunction code blinks when a malfunction occurs.
UnitMalfunction codeInspection
Inspection mode
Push the button.
Inspection/test operation Push the button.
Inspection/test operation Push the button.
Inspection/test operation Push the button.
Inspection/test operation Push the button.
0L 0
Indoor unit model code display
0 7 1F C J
Outdoor or (outside) unit model code display
– – – A A 1
Test operation
Test operation mode
Capacity codeIndoor unit system codeIndoor unit type codeProgression code
0 7 1...F...C...J...
(V2775)
Type
Wall mounted
Double flow
Corner
Multi flow
Ceiling suspended
Built-in
Floor standing
Concealed ceiling duct
Concealed floor standing type
Slim Ceilling mounted duct
Display
A
C
E
F
H
J
L
P
L
3
Model
FXAQ
FXCQ
FXKQ
FXFQ
FXHQ
FXSQ
FXLQ
FXMQ
FXNQ
FXDQ
SiEN30-602 Troubleshooting by Remote Control
Troubleshooting 151
1.5 Remote Control Service ModeHow to Enter the Service Mode
Service Mode Operation Method
1. Select the mode No.Set the desired mode No. with the button.(For Infrared remote control, Mode 43 only can be set.)2. Select the unit No. (For group control only)Select the indoor unit No. to be set with the time mode . (For Infrared remote control,
button.)3. Make the settings required for each mode. (Modes 41, 44, 45)In case of Mode 44, 45, push button to be able to change setting before setting work. (LCD �code� blinks.)For details, refer to the table in next page.4. Define the setting contents. (Modes 44, 45)Define by pushing the timer button.After defining, LCD �code� changes blinking to ON.5. Return to the normal operation mode.Push the button one time.
Normal operation mode
Field set mode
Service mode
Push the button for 4 seconds or longer. Push the button for 4 seconds or longer.
Troubleshooting by Remote Control SiEN30-602
152 Troubleshooting
Mode No
Function Contents and operation method Remote control display example
40 Malfunction hysteresis display
Display malfunction hysteresis.The history No. can be changed with the button.
41 Display of sensor and address data
Display various types of data.Select the data to be displayed with the button. Sensor data0: Thermostat sensor in remote control.1: Suction2: Liquid pipe3: Gas pipe
Address data4: Indoor unit address5: Outside unit address6: BS unit address7: Zone control address8: Cool/heat group address9: Demand / low noise address
43 Forced fan ON Manually turn the fan ON by each unit. (When you want to search for the unit No.)By selecting the unit No. with the button, you can turn the fan of each indoor unit on (forced ON) individually.
44 Individual setting Set the fan speed and air flow direction by each unitSelect the unit No. with the time mode button. Set the fan speed with the button.Set the air flow direction with the button.
45 Unit No. transfer Transfer unit No.Select the unit No. with the button.Set the unit No. after transfer with the button.
46 This function is not used by VRV ll R-410A Heat Pump 50Hz.
47
Hystory No: 1 - 91: Latest
Unit 1
Malfunction code
2-U4
Malfunction code
40
(VE007)
Temperature ºC
41
Sensor data display
Unit No. Sensor type
1 1
2 7
Address
41
Address display
Unit No. Address type
1 8
1
(VE008)
Unit 1
43
(VE009)
Unit 1
Code44
Air flow direction P0 - P4
1 3
(VE010)
Fan speed 1: low 3: High
Unit 1
Code45
Present unit No.
Unit No. after transfer
0 2
(VE011)
SiEN30-602 Troubleshooting by Remote Control
Troubleshooting 153
1.6 Remote control Self-Diagnosis FunctionThe remote control switches are equipped with a self diagnosis function so that more appropriate maintenance can be carried out. If a malfunction occurs during operation, the operation lamp, malfunction code and display of malfunctioning unit No. let you know the contents and location of the malfunction. When there is a stop due to malfunction, the contents of the malfunction given below can be diagnosed by a combination of operation lamp, INSPECTION display of the liquid crystal display and display of malfunction code. It also lets you know the unit No. during group control.
Operation lamp
ON/OFF button
Display of indoor unit for which a malfunction has been detected
Malfunction code
(VL050)
Inspection display
Troubleshooting by Remote Control SiEN30-602
154 Troubleshooting
Malfunction code
Operation lamp
Inspection display
Unit No. Malfunction contents Page Referred
Indoor Unit
A0 9 9 9 Error of external protection device 158A1 9 9 9 PC board defect, E2 PROM defect 159A3 9 9 9 Malfunction of drain level control system (33H) 160A6 9 9 9 Fan motor (MF) lock, overload 162,163A7 8 7 9 Malfunction of swing flap motor (MA) 166A9 9 9 9 Malfunction of moving part of electronic expansion
valve (20E)168
AF 8 7 9 Drain level above limit 170AH 8 7 9 Malfunction of air filter maintenance �AJ 9 9 9 Malfunction of capacity setting 171C4 9 9 9 Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
172
C5 9 9 9 Malfunction of thermistor (R3T) for gas pipes (loose connection, disconnection, short circuit, failure)
173
C9 9 9 9 Malfunction of thermistor (R1T) for air inlet (loose connection, disconnection, short circuit, failure)
174
CJ 8 8 8 Malfunction of thermostat sensor in remote control 175Outside
UnitE1 9 9 9 PC board defect 176E3 9 9 9 Actuation of high pressure switch 177E4 9 9 9 Actuation of low pressure sensor 179E5 9 9 9 Compressor motor lock 181E9 9 9 9 Malfunction of moving part of electronic expansion
valve (Y1E~3E)183
F3 9 9 9 Abnormal discharge pipe temperature 185F6 9 9 9 Refrigerant overcharged 186HJ 9 9 9 Water system defect 188J3 9 9 9 Malfunction of discharge pipe thermistor (R3T)
(loose connection, disconnection, short circuit, failure)
190
J4 9 9 9 Malfunction of heat exchanger gas pipe thermistor (R4T)
191
J5 9 9 9 Malfunction of thermistor (R2T) for suction pipe (loose connection, disconnection, short circuit, failure)
192
J7 9 9 9 Malfunction of liquid pipe thermistor (R6T) 193J9 9 9 9 Malfunction of the evaporating side gas pipe
temperature thermistor on subcooling heat exchanger (R5T)
194
JA 9 9 9 Malfunction of discharge pipe pressure sensor 195JC 9 9 9 Malfunction of suction pipe pressure sensor 196L0 9 9 9 Inverter system error �L4 9 9 9 Malfunction of inverter radiating fin temperature rise 197L5 9 9 9 Inverter compressor motor grounding, short circuit 198L6 9 9 9 Compressor motor coil grounding or short circuit �L8 9 9 9 Inverter current abnormal 199L9 9 9 9 Inverter start up error 200LA 9 9 9 Malfunction of power unit �LC 9 9 9 Malfunction of transmission between inverter and
control PC board201
P1 9 9 9 Inverter over-ripple protection 203P4 9 9 9 Malfunction of inverter radiating fin temperature rise
sensor204
SiEN30-602 Troubleshooting by Remote Control
Troubleshooting 155
System U0 8 7 9 Low pressure drop due to refrigerant shortage or electronic expansion valve failure
205
U1 9 9 9 Reverse phase / open phase 207U2 9 9 9 Power supply insufficient or instantaneous failure 208U3 9 9 9 Check operation is not conducted. 210U4 9 9 9 Malfunction of transmission between indoor and
outside units211
U5 9 9 9 Malfunction of transmission between remote control and indoor unit
213
U5 7 8 7 Failure of remote control PC board or setting during control by remote control
213
U7 9 9 9 Malfunction of transmission between outside units 214U8 9 9 7 Malfunction of transmission between master and
slave remote controls (malfunction of slave remote control)
216
U9 9 9 9 Malfunction of transmission between indoor unit and outside unit in the same system
217
UA 9 9 9 Excessive number of indoor units etc. 219UC 8 8 8 Address duplication of central remote control 220UE 9 9 9 Malfunction of transmission between central remote
control and indoor unit221230
UF 9 9 9 Refrigerant system not set, incompatible wiring / piping
223
UH 9 9 9 Malfunction of system, refrigerant system address undefined
224
Centralized Control
and Schedule
Timer
M1 8 or 7 9 9 PC board defect 225232
M8 8 or 7 9 9 Malfunction of transmission between optional controllers for centralized control
226233
MA 8 or 7 9 9 Improper combination of optional controllers for centralized control
227234
MC 8 or 7 9 9 Address duplication, improper setting 229236
Heat Reclaim
Ventilation
64 8 7 9 Indoor unit�s air thermistor error �65 8 7 9 Outside air thermistor error �68 8 7 9 �6A 8 7 9 Damper system alarm �6A 9 9 9 Damper system + thermistor error �6F 8 7 9 Malfunction of simple remote control �6H 8 7 9 Malfunction of door switch or connector �94 9 9 9 Internal transmission error �
Malfunction code
Operation lamp
Inspection display
Unit No. Malfunction contents Page Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting by Remote Control SiEN30-602
156 Troubleshooting
Malfunction code indication by outdoor unit PCB
<Selection of setting item>
<Confirmation of malfunction 1>
To enter the monitor mode, push the MODE button (BS1) when in “Setting mode 1”.
Push the SET button (BS2) and set the LED display to a setting item.
Push the RETURN button (BS3) once to display "First digit" of malfunction code.
<Confirmation of malfunction 2>
Push the SET button (BS2) once to display "Second digit" of malfunction code.
Push the RETURN button (BS3) and switches to the initial status of “Monitor mode”.
* Push the MODE button (BS1) and returns to “Setting mode 1”.
Contents of malfunction Malfunction code
HPS activated
Abnormal Pe
Detection of INV compressor lock
Instantaneous over current of DC fan motor
Detection of DC fan motor lock
EV1
EV3
Abnormal position signal of DC fan motor
Faulty Ta sensor
Abnormal Td
Refrigerant over charge
Faulty Tdi sensor
Faulty Tg sensor
Faulty Ts sensor
Faulty Tl sensor
Faulty Tsh sensor
Faulty Pc sensor
Faulty Pe sensor
Over heating of inverter radiation fin temperature
Inverter instantaneous over current
Electronic thermal switch 1
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Current increasing)
Stall prevention (Faulty startup)
Abnormal wave form in startup
Out-of-step
Inverter transmission error
Imbalance of inverter power supply voltage
Faulty thermistor of inverter box
Faulty thermistor of inverter fin
Incorrect combination of inverter and fan driver
Gas shortage alarm
Reverse phase error
Insufficient inverter voltage
Inverter open phase (phase T)
Charging error of capacitor in inverter main circuit
I/O transmission error
O/O transmission error
Indoor unit system malfunction in other system or
other unit of own system
Abnormal connection with excessive number of indoor units
Conflict of refrigerant type in indoor units
Incorrect wiring (Auto address error)
Malfunction of multi level converter, abnormality in
conflict check
E3
E4
E5
E7
E9
H7
H9
HJ
F3
F6
J3
J4
J5
J7
J9
JA
JC
L4
L5
L8
L9
LC
P1
P3
P4
PJ
U0
U1
U2
U3
U4
U7
U9
UA
UH
UJ
UF
Abnormal discharge pressure
Abnormal suction pressure
Compressor lock
Over load, over current,
abnormal lock of outdoor unit fan motor
Malfunction of electronic expansion valve
Abnormal position signal of outside unit fan motor
Faulty sensor of outside air temperature
Abnormality in water system
Abnormal discharge pipe temperature
Abnormal heat exchanger temperature
Faulty sensor of discharge pipe temperature
Faulty sensor of heat exchanger gas pipe thermistor
Faulty sensor of suction pipe temperature
Faulty sensor of receiver temperature
Faulty sensor of subcool heat exchanger temperature
Faulty sensor of discharge pressure
Faulty sensor of suction pressure
Inverter radiation fin temperature rising
DC output over current
Electronic thermal switch
Stall prevention (Limit time)
Transmission error between inverter and outdoor unit
Open phase/Power supply imbalance
Faulty temperature sensor inside switch box
Faulty temperature sensor of inverter radiation fin
Incorrect combination of inverter and fan driver
Gas shortage
Reverse phase
Abnormal power supply voltage
No implementation of test-run
Transmission error between indoor and outdoor unit
Transmission error between outdoor units, transmission error
between thermal storage units, duplication of IC address
Transmission error of other system
Erroneous on-site setting
Faulty system function
Transmission error in accessory devices, conflict
in wiring and piping, no setting for system
<Confirmation of malfunction 3>
Push the SET button (BS2) once to display "master or slave1 or slave2" and "malfunction location".
* Refer P.122 for Monitor mode.
* Refer P.122 for Monitor mode.
Detail description on next page.
SiEN30-602 Troubleshooting by Remote Control
Troubleshooting 157
1
Malfunction
code LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED1 LED2 LED3 LED4 LED5 LED6 LED7
Malfunctionlocation
Master
Slave 1
Slave 2
Confirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3
LED1 LED2 LED3 LED4 LED5 LED6 LED7
8 : ON
.: Blink
7 : OFF
8 : ON
.: Blink
7 : OFF
7
7
.
7
.
7
E3
E4
E5
E7
E9
H7
H9
HJ
F3
F6
J3
J4
J5
J7
J9
JA
JC
L4
L5
L8
L9
LC
P1
P3
P4
PJ
U0
U1
U2
U3
U4
U7
U9
UA
UH
UJ
UF
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
.
7
.
.
7
7
7
7
7
7
.
.
.
7
7
.
.
.
7
7
7
.
7
7
7
7
7
7
.
.
.
.
.
7
.
.
.
7
.
7
.
7
.
7
8
.
.
7
7
.
.
.
7
7
.
7
7
.
.
7
7
7
7
.
.
7
7
7
.
.
.
7
7
.
7
.
7
7
.
.
.
7
7
.
7
.
7
7
7
7
7
7
7
.
7
7
7
7
.
.
7
.
7
.
.
7
.
.
7
.
.
.
.
.
.
.
7
.
7
.
.
.
7
7
7
.
7
.
7
.
.
7
.
7
.
7
.
7
.
.
7
.
.
.
7
7
7
7
7
.
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
.
.
.
.
7
7
7
7
.
.
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
.
.
.
.
.
.
7
7
7
7
7
7
8
8
8
8
8
8
7
7
7
7
.
.
7
.
.
.
7
7
.
7
7
.
7
7
.
7
.
7
7
.
Malfunction code 1st digit display section
Malfunction code 2nd digit display section
Troubleshooting by Indication on the Remote Control SiEN30-602
158 Troubleshooting
2. Troubleshooting by Indication on the Remote Control
2.1 �A0� Indoor Unit: Error of External Protection DeviceRemote Control Display
A0
Applicable Models
All indoor unit models
Method of Malfunction Detection
Detect open or short circuit between external input terminals in indoor unit.
Malfunction Decision Conditions
When an open circuit occurs between external input terminals with the remote control set to "external ON/OFF terminal".
Supposed Causes
! Actuation of external protection device! Improper field set! Defect of indoor unit PC board
Troubleshooting
(V2776)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Indoor unit PC board replacement.
Actuation of external protection device.
Change the second code No. to "01" or "02" .
YES
NO
NO
YES
External protection device is
connected to terminals T1 and T2 of the indoor
unit terminal block.
ON/OFF input from
outside (mode No. 12, first code No. 1)
has been set to external protection device input (second code No. 03)
by remotecontrol.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 159
2.2 �A1� Indoor Unit: PC Board DefectRemote Control Display
A1
Applicable Models
All indoor unit models
Method of Malfunction Detection
Check data from E²PROM.
Malfunction Decision Conditions
When data could not be correctly received from the E²PROME²PROM : Type of nonvolatile memory. Maintains memory contents even when the power supply is turned off.
Supposed Causes
! Defect of indoor unit PC board
Troubleshooting
Turn power supply OFF, then power ON again.
Does the system return to normal?
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
External factor other than malfunction (for example, noise etc.).Replace the indoor unit PC board.
(V2777)
NO
Troubleshooting by Indication on the Remote Control SiEN30-602
160 Troubleshooting
2.3 �A3� Indoor Unit: Malfunction of Drain Level Control System (S1L)
Remote Control Display
A3
Applicable Models
FXCQ, FXFQ, FXSQ, FXKQ, FXDQ, FXMQ, FXHQ (Option), FXMQ200·250M (Option), FXAQ (Option)
Method of Malfunction Detection
By float switch OFF detection
Malfunction Decision Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed Causes
! 220~240V power supply is not provided! Defect of float switch or short circuit connector! Defect of drain pump! Drain clogging, upward slope, etc. ! Defect of indoor unit PC board! Loose connection of connector
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 161
Troubleshooting
(V2778)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace float switch.
Modify the float switch's connection and turn on again.
Connect the drain pump and turn on again.
Check the drain piping for clogging or upward slope, etc.
Replace indoor unit PC board.
Replace the drain pump or check for dirt, etc.
Connect either a short circuit connector or float switch and turn on again.
YES
YES
YES
YES
Defect of indoor unit PC board.
Loose connection of connector.
NO NO
NO
YES
YES
NO
NO
YES
NO
YES
NO
NO
NO
A shortcircuit connector is
connected toX8A.
Provide 220~240V power supply.
YES
NO
Becomesnormal when X8A of
the indoor unit PC boardis short circuited
The float switchfunctions normally.
Is power supply 220~240V provided?
Water builds up in the drain pan.
The float switch is
connected to X8A of the indoor unit PC
board.
The drain pump
works when the power supply is reset for the
indoor unit.
The float switch
contact is forming a short circuit (continuity
check with X8A or X15A disconnected)
The voltage of
terminals Y1 and Y2 or X25A is
220~240 V (within 5minutes of resetting the power
supply).
The drain pump is
connected to X25A or terminals Y1 and Y2 of
the indoor unit PC board.
Troubleshooting by Indication on the Remote Control SiEN30-602
162 Troubleshooting
2.4 �A6� Indoor Unit: Fan Motor (M1F) Lock, OverloadRemote Control Display
A6
Applicable Models
FXDQ, FXHQ
Method of Malfunction Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction Decision Conditions
When number of turns can�t be detected even when output voltage to the fan is maximum
Supposed Causes
! Fan motor lock! Disconnected or faulty contact between fan motor and PC board
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Connect the connector correctly.
Check the faulty contact of connector or broken wire etc.
Check for wiring of indoor unit fan motor and motor itself.
Replace the indoor unit PC board.
YES
NO
YES
NO
(V2779)
Disconnect the connectors with power supply and check the voltage between 1 and 3 of connector X4A.
Is the wiring from the fan
motor securely connected to connectors X4A and X27A on the
indoor unit PC board?
Is there APPROX. DC 12
Volt between 1 and 2 pins?
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 163
�A6� Abnormal Indoor Fan MotorRemote Control Display
A6
Applicable Models
FXFQ, FXAQ
Method of Malfunction Detection
Detect abnormal fan rotation with the signal from the fan motor
Malfunction Decision Conditions
When fan rotation does not increase
Supposed Causes
! Disconnected/short-circuited fan motor harnesses or disconnected connectors! Faulty fan motor
(Disconnection and insulation failure)! Abnormal signal from the fan motor
(Circuit breakdown)! Faulty PCB! Instantaneous disturbance of power supply voltage! Fan motor lock
(Caused by the motor or external factors)! Fan does not rotate because foreign particles are trapped in it.! Disconnected connector between PCBs A1P and A2P
Troubleshooting by Indication on the Remote Control SiEN30-602
164 Troubleshooting
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Remove the foreign particles.
Connect properly.
Replace the fan motor.
∗Refer to the figure in following page.
Replace the fan motor.
NO
YES
NO
YES
NO
YES
NO
YES
Turn off the power supply.
Check the fan motor connector. ∗
Connect properly.
Replace the indoor PCB.
YES
NO
Are there foreign particles around the
fan?
Are the harness from the
fan motor and the harness of A1P fan motor (fixed to
X20A) connected properly?
Can the fan be
removed from the junction connector between the fan motor and A1P and
rotated easily with hands?
Does the resistance
between pins satisfy the judgment criteria?
Are heavy current
PCB (A1P) and low current PCB (A2P) connected
properly?
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 165
[Check on connector of fan motor (Power supply cable)](1)Turn off the power supply.Measure the resistance between phases of U,V,W at the motor side connectors (three-core wire) to check that the values are balanced and there is no short circuiting, while connector or relay connector is disconnected.
Red
White
Black
U
V
W
Measure the resistance values between phases U,V,W.
Troubleshooting by Indication on the Remote Control SiEN30-602
166 Troubleshooting
2.5 �A7� Indoor Unit: Malfunction of Swing Flap Motor (MA)Remote Control Display
A7
Applicable Models
FXCQ, FXHQ, FXKQ
Method of Malfunction Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction Decision Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap motor is energized for a specified amount of time (about 30 seconds).
Supposed Causes
! Defect of swing motor! Defect of connection cable (power supply and limit switch)! Defect of air flow direction adjusting flap-cam! Defect of indoor unit PC board
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 167
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Provide 220~240V power supply.
YES
NOIs power supply 220~240V
provided?
Indoor unit is a model equipped
with a swing flap function
The swing motor works
when the power supply is turned off and then
back on.
When the air flow
direction flap's cam mechanism is disconnected
from the swing motor, operation is normal
when turned on again.
After turning the
swing-flap ON and then stopping
with the remote control, the voltage of X6A of the
indoor unit PC board is 220 ~ 240VAC (60 Hz) / 220
VAC(50 Hz) when turnedonagain (within
30 seconds of turning on
again).
The connector is
connected to X9A of the indoor unit PC
board.
The limit switch functions normally.
The connecting cable is short-circuited or
disconnected. Replace the limit switch connecting cable.
Replace indoor unit PC board.
Replace the power supply connecting cable.
Replace swing motor.
Take the cam mechanism apart, reassemble and turn on again.
YES
NO
YES
YES
NO
YES
NO
Connect the connector to X9A and turn on again.
Replace indoor unit PC board.NO
NO
YES NO
YES
NO
YES
YES
NOReplace swing motor.
(V2780)
The connecting cable has no continuity.
Troubleshooting by Indication on the Remote Control SiEN30-602
168 Troubleshooting
2.6 �A9� Indoor Unit: Malfunction of Moving Part of Electronic Expansion Valve (20E)
Remote Control Display
A9
Applicable Models
All indoor unit models
Method of Malfunction Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction Decision Conditions
When number of turns can�t be detected even when output voltage to the fan is maximum
Supposed Causes
! Malfunction of moving part of electronic expansion valve! Defect of indoor unit PC board! Defect of connecting cable
Troubleshooting
(V2781)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
After connecting, turn the power supply off and then back on.
Replace the moving part of the electronic expansion valve.
YES
YES
NO
NO
Replace the connecting cable.
If you turn the power supply off and turn on again, and it still does not help, replace the indoor unit PC board.
NO
YES
The electronic
expansion valve is connected to X7A of the
indoor unit PC board.
Normal when coil
check (∗1) of the moving part of the electronic
expansion valve is checked.
The connecting cable is
short-circuited or disconnected.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 169
∗1: Coil check method for the moving part of the electronic expansion valveDiscount the electronic expansion valve from the PC board and check the continuity between the connector pins.
(Normal)
": Continuity × : No continuity
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown1. White × "
Approx. 300Ω
× "Approx. 150Ω
×
2. Yellow × " Approx.
300Ω
× "Approx. 150Ω
3. Orange × "Approx. 150Ω
×
4. Blue × "Approx. 150Ω
5. Red ×
6. Brown
M
White (1)
Yellow(2)
Blue(4)
Brown(6)
Red (5)
Orange (3)
φ1
φ2 φ4
φ3
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown
Troubleshooting by Indication on the Remote Control SiEN30-602
170 Troubleshooting
2.7 �AF� Indoor Unit: Drain Level above LimitRemote Control Display
AF
Applicable Models
FXCQ, FXFQ, FXSQ, FXKQ, FXMQ, FXDQ
Method of Malfunction Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is in non-operation.
Malfunction Decision Conditions
When the float switch changes from ON to OFF while the compressor is in non-operation.
Supposed Causes
! Humidifier unit (optional accessory) leaking! Defect of drain pipe (upward slope, etc.)! Defect of indoor unit PC board
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Defect of indoor unit PC board.
Modify the drain piping.YES
NO
NO
Check if the humidifier unit isleaking.
YES
(V2782)
Field drain piping has a defect
such as upward sloping.
A humidifier unit
(optional accessory) is installed on the
indoor unit.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 171
2.8 �AJ� Indoor Unit: Malfunction of Capacity Determination Device
Remote Control display
AJ
Applicable Models
All indoor unit models
Method of Malfunction Detection
Capacity is determined according to resistance of the capacity setting adapter and the memory inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal is determined.
Malfunction Decision Conditions
Operation and:1. When the capacity code is not contained in the PC board�s memory, and the capacity setting
adapter is not connected.2. When a capacity that doesn�t exist for that unit is set.
Supposed Causes
! You have forgotten to install the capacity setting adapter.! Defect of indoor unit PC board
Troubleshooting
(V2783)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Install a capacity setting adaptor.
Replace the indoor unit PC board.NO
NO
YES
YES
Replace the indoor unit PC board.
The indoor unit is
a model that requires installation of a capacity
setting adaptor when replacing the PC
board.
The indoor unit PC board was
replaced with a replacementPC board.
Troubleshooting by Indication on the Remote Control SiEN30-602
172 Troubleshooting
2.9 �C4� Indoor Unit: Malfunction of Thermistor (R2T) for Heat Exchanger
Remote Control Display
C4
Applicable Models
All indoor unit models
Method of Malfunction Detection
Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction Decision Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed Causes
! Defect of thermistor (R2T) for liquid pipe ! Defect of indoor unit PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V2784)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace the indoor unit PC board.
Connect the connector and turn on again.
NO
NO
Replace the thermistor (R2T).
YES
YES
Connector is connected to X12A or X18A of
the indoor unit PC board.
Resistance is normal when measured after
disconnecting the thermistor (R2T) from the indoorunit
PC board (3.5kΩ~ 360kΩ)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 173
2.10 �C5� Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes
Remote Control Display
C5
Applicable Models
All indoor unit models
Method of Malfunction Detection
Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction Decision Conditions
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Supposed Causes
! Defect of indoor unit thermistor (R3T) for gas pipe ! Defect of indoor unit PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V2785)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace the indoor unit PC board.
Connect the connector and turn on again.
NO
NO
Replace the thermistor (R3T).
YES
YES
Connector is connected to X11A or
X14A of the indoor unit PC board.
Resistanceis normal whenmeasured after
disconnecting the thermistor (R3T) from the indoor
unit PC board.(0.6kΩ~360kΩ)
Troubleshooting by Indication on the Remote Control SiEN30-602
174 Troubleshooting
2.11 �C9� Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air
Remote Control Display
C9
Applicable Models
AII indoor unit models
Method of Malfunction Detection
Malfunction detection is carried out by temperature detected by suction air temperature thermistor.
Malfunction Decision Conditions
When the suction air temperature thermistor becomes disconnected or shorted while the unit is running.
Supposed Causes
! Defect of indoor unit thermistor (R1T) for air inlet! Defect of indoor unit PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace the indoor unit PC board.
Connect the connector and turn on again.
NO
NO
Replace the thermistor R1T.
YES
YES
Connector is connected to X13A or X19A of
the indoor unit PC board.
Resistance is normal when measured after
disconnecting the thermistor (R1T) from the
indoor unit PC board. (7.2kΩ~112kΩ)
(V2786)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 175
2.12 �CJ� Indoor Unit: Malfunction of Thermostat Sensor in Remote Control
Remote Control Display
CJ
Applicable Models
AII indoor unit models
Method of Malfunction Detection
Malfunction detection is carried out by temperature detected by remote control air temperature thermistor. (Note1)
Malfunction Decision Conditions
When the remote control air temperature thermistor becomes disconnected or shorted while the unit is running.
Supposed Causes
! Defect of remote control thermistor! Defect of remote control PC board
Troubleshooting
Note: In case of remote control thermistor malfunction, unit is still operable by suction air thermistor on indoor unit.
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
Turn power supply OFF, then power ON again.
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is "CJ" displayed on the remote control? Replace remote controller.
External factor other than equipment malfunction.(for example, noise etc.)
(V2787)
NO
Troubleshooting by Indication on the Remote Control SiEN30-602
176 Troubleshooting
2.13 �E1� Outside Unit: PC Board DefectRemote Control Display
E1
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Detect abnormalities by checking communication status of the hard part between the indoor unit and outside unit.
Malfunction Decision Conditions
When communication status of the hard part between the indoor unit and heat source unit is abnormal
Supposed Causes
! Faulty main PCB! Faulty communication part (photo coupler) on the main PCB
Troubleshooting
Turn off the power supply once and then turn it on again.
YES
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Does it return normally?
Foreign particles (electrically
conductive) are attached on the terminal (X1M) of
the main PCB.
Remove the foreign particles (electrically conductive) and restart operation.
Replace the heat source main PCB.
Check the following parts and continue operation• Check noise, etc.• Check whether foreign
particles (electrically conductive) attach to the terminal of the main PCB (X1M).
NO
NO
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 177
2.14 �E3� Outside Unit: Actuation of High Pressure SwitchRemote Control Display
E3
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Detect conductive property of the high pressure switch with the protector circuit.
Malfunction Decision Conditions
When the protector circuit is partially opened(For reference) Working pressure for the high pressure switch
Working pressure: 4.0 MPaReturn pressure: 2.85 MPa
Supposed Causes
! High pressure switch operation! Faulty high pressure switch! Faulty main PCB! Temporal power failure! Faulty high pressure sensor! Insufficient heat source water! Dirty water heat exchanger
Troubleshooting by Indication on the Remote Control SiEN30-602
178 Troubleshooting
Troubleshooting
NO
YES
YES
Replace the HPS.
Improve defects.
Replace the high pressure sensor.
Replace the main PCB.
YES
NO
NO
YES
NO
YES
NO
Red
+5V
Microcomputer A/D input
Black
White
(4)
(3)
(1)
• Set up a pressure gauge in the high pressure service port.• Connect the Service Checker.• Restart operation after resetting operation with a remote
control.
Measure the voltage (DC) between these two points.
• The high pressure sensor is normal and the main PCB pressure detection is also normal.
• In fact, high pressure is rising.
CHECK 1 : Refer to page 243 to eliminate the causes of high pressure rise.
∗1 : Compare the pressure sensor voltage measurements with pressure gauge readings. (For the pressure sensor, voltage is measured at the connector and converted to pressure in accordance with page 288.)
∗2 : Compare “high pressure” checked with the Service Checker with pressure sensor voltage measurements (refer to ∗1).
∗3 : Measure the voltage of the pressure sensor.
(2)
HP
pre
ssur
e se
nsor
Connector for high pressure sensor (red)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Check the following items:1 Is the stop valve open?2 Is the connector for HPS properly connected
to the main PCB?3 Is the high pressure switch electrically
conductive?
Are all of the above conditions
satisfied?
Can the emergency stop (E3)
be repeated?
Is PCB detector pressure
normal? (∗2)
Are high pressure sensor characteristics normal? (∗1)
Is HPS working value (4.0
MPa) normal?
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 179
2.15 �E4� Outside Unit: Actuation of Low Pressure SensorRemote Control Display
E4
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Judge the pressure detected by a low pressure sensor with the main PCB.
Malfunction Decision Conditions
When low pressure drops while the compressor is in operationWorking pressure: 0.07 MPa (Retry: 3 times)
Supposed Causes
! Abnormal low pressure drop! Faulty low pressure sensor! Faulty main PCB! The stop valve left closed! Insufficient heat source water! Dirty water heat exchanger
Troubleshooting by Indication on the Remote Control SiEN30-602
180 Troubleshooting
Troubleshooting
YES
NO
NO
YES
NO
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
1 Set up a pressure gauge in the low pressure service port.
2 Connect the Service Checker.3 Restart operation after resetting operation.
Is the stop valve opened?
• The low pressure sensor is normal and the main PCB pressuredetection is also normal.
• In fact, low pressure is dropping.
Are low pressure sensor characteristics normal? (∗1)
Is PCB detector pressure
normal? (∗2)Replace the main PCB.
Replace the low pressure sensor.
Open the stop valve.
∗1 : Compare the pressure sensor voltage measurements with pressure gauge readings. (For the pressure sensor, voltage is measured at the connector and converted to pressure in accordance with page 288.)
∗2 : Compare “low pressure” measured with the Service Checker with pressure sensor voltage measurements (refer to ∗1).
∗3 : Measure the voltage of the pressure sensor.
: Refer to page 244 to eliminate the causes of low pressure drop.CHECK 2
+5V
(4)
(3)
(1)
(2)Microcomputer A/D input
Measure the voltage (DC) between these two points.
Red
Black
White
LP p
ress
ure
sens
or
Connector for low pressure sensor (Blue)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 181
2.16 �E5� Compressor Motor LockRemote Control Display
E5
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Pick up the location signal using the inverter PCB from the UVWN line connected between the inverter and the compressor and detect location signal pattern.
Malfunction Decision Conditions
In normal operation, location signal for a triple cycle of frequency applied, while in locked operation, it is a double cycle, and they are detected.(Retry twice/60 minutes)
Supposed Causes
! Inverter compressor lock! High differential pressure (0.5 MPa or more)! Incorrect UVWN wire connection ! Faulty inverter PCB! Stop valve left closed
Troubleshooting by Indication on the Remote Control SiEN30-602
182 Troubleshooting
Troubleshooting
YES
NO
NO
YES
YES
NO
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is the UVWN wire connection
proper?
Is it a high differential
pressure at the time of start-up (0.5 MPa or
more)? (∗1)
The inverter compressor operates
normally.
Inverter output voltage
among 3 phases is within ±5V for TL power
supply and ±10V for YL power
supply.
Restart operation after resetting operation.
Disconnect the connection between the compressor and the inverter and turn on power transistor check mode setting using “Setting Mode 2” on the outside unit PCB.
Measure inverter output voltage.Note: Take measurements while
frequency is stable.
Eliminate the causes.The hot gas bypass valve may not be opened. Check it.
NO
YES
Replace the compressor.
NOReplace the inverter PCB.
YESReplace the inverter compressor.
Open the stop valve.
∗1 : Difference in pressure between high and low pressures before start-up∗2 : The quality of the power transistor diode module can be assessed also by means of
measurement of resistance between terminals (page 289, 290).
Is the stop valve opened?
Connect properly.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 183
2.17 �E9� Outside Unit: Malfunction of Moving Part of Electronic Expansion Valve (Y1E, Y3E)
Remote Control Display
E9
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Check disconnection of connectorCheck continuity of expansion valve coil
Malfunction Decision Conditions
Error is generated under no common power supply when the power is on.
Supposed Causes
! Defect of moving part of electronic expansion valve! Defect of outside unit PC board (A1P)! Defect of connecting cable
Troubleshooting
(V3067)
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Return to normal?
Turn power supply off, and turn power supply on again.
Electronic expansion valve is
connected to X26A and X28A of outside unit PC
board (A1P).
Normal when coil check
(∗1) of the moving part of the electronic expansion valve is
checked.
The connecting cable is short-circuited or
disconnected.
Replace the connecting cable.
Replace outside unit PC board A1P.
NO
NO
NO
NO
Replace the moving part of the electronic expansion valve.
External factor other than malfunction (for example, noise etc.).
After connecting, turn the power off and then back on again.
YES
YES
YES
Troubleshooting by Indication on the Remote Control SiEN30-602
184 Troubleshooting
∗1: Coil check method for the moving part of the electronic expansion valveDiscount the electronic expansion valve from the PC board and check the continuity between the connector pins.
(Normal)
": Continuity × : No continuity
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown1. White × "
Approx. 300Ω
× "Approx. 150Ω
×
2. Yellow × " Approx.
300Ω
× "Approx. 150Ω
3. Orange × "Approx. 150Ω
×
4. Blue × "Approx. 150Ω
5. Red ×
6. Brown
M
White (1)
Yellow(2)
Blue(4)
Brown(6)
Red (5)
Orange (3)
φ1
φ2 φ4
φ3
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 185
2.18 �F3� Outside Unit: Abnormal Discharge Pipe TemperatureRemote Control Display
F3
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Abnormality is detected according to the temperature detected by the discharge pipe temperature sensor.
Malfunction Decision Conditions
! When the discharge pipe temperature rises to an abnormally high level (over 135°C)! When the discharge pipe temperature rises suddenly (over 120°C continues 10 min.)
Supposed Causes
! Faulty discharge pipe temperature sensor! Faulty connection of discharge pipe temperature sensor! Faulty outdside unit PC board
Troubleshooting
Connect the Service Checker.Restart operation after resetting operation.
∗1: Compare the resistance values of the discharge pipe thermistor with measurements of a surface thermometer. (For temperature and resistance characteristics of a thermistor, refer to page 286, 287.)
∗2: Compare the discharge pipe temperature checked by the Service Checker with the resistance of the thermistor (refer to ∗1).
• The discharge pipe thermistor is normal and the main PCB temperature detection is also normal.
• In fact, discharge pipe temperature is rising.
: Refer to page 245 to eliminate the causes of overheat operation.
CHECK 3
Is PCB detection
temperature normal?(∗2)
Replace the main PCB.NO
YES
Replace the discharge pipe thermistor.
YES
NO
Are discharge pipe
thermistor characteristics normal? (∗1)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Troubleshooting by Indication on the Remote Control SiEN30-602
186 Troubleshooting
2.19 �F6� Refrigerant OverchargedRemote Control Display
F6
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Detect excessive charging of refrigerant using suction pipe temperature and subcooling heat exchanger outlet temperature during check operation.
Malfunction Decision Conditions
When the suction pipe temperature and the subcooling heat exchanger outlet temperature during check operation drop and become below the evaporation temperature
Supposed Causes
! Excessive refrigerant charging! Suction pipe thermistor removed! Subcooling heat exchanger outlet thermistor removed
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 187
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
YES
YES
YES
NO
NO
NO
∗1: For thermistor temperature and resistance characteristics, refer to page 286, 287.
• There is a possibility that there are other causes of refrigerant overfilling.
: Refer to page 246 to eliminate the causes of wet operation.
CHECK 4
Mount the thermistor properly before operation.
Replace the thermistor if it functions abnormally before operation.
Continue operation.
Check the mounting condition of the suction pipe thermistor and the subcooling heat exchanger outlet thermistor temperature sensor mounted to piping.
Remove the suction pipe thermistor and the subcooling heat exchanger outlet thermistor from the outside unit PCB and measure the resistance with a tester.
Carry out check operation again.
Is the thermistor mounted properly?
Does it function normally? (∗1)
Does the abnormal code (F6) repeat?
Troubleshooting by Indication on the Remote Control SiEN30-602
188 Troubleshooting
2.20 �HJ� Malfunction of Water systemRemote Control Display
HJ
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
! Detect abnormalities using the thermistor on the side of the heat exchanger gas. ! Detect turned off interlock circuit.(When interlock setting is provided.)
Malfunction Decision Conditions
! When temperature on the heat exchanger gas side (R4T) drops remarkably with the smallest operation step (52 Hz) of the compressor
! With interlock setting provided, when interlock circuit is turned off.
Supposed Causes
! Clogged water piping system! Insufficient heat exchanger water! Dirty heat exchanger! Disconnected connector! Faulty thermistor on the heat exchanger gas side! Faulty low pressure sensor
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 189
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace the main PCB.YES
NO
YES
Secure enough water.
Remove the clog.
NO
NOReplace the inverter PCB.
NO Replace the thermistor/sensor if any of its characteristics are abnormal.
YESClean the heat exchanger.
YES
NO
Disconnect the connection between the compressor and the inverter and turn on the power transistor check mode setting using “Setting Mode 2” on the outside PCB.
Measure the output voltage of the inverter.Note: Take measurements while
frequency is stable.
NOConnect the connector properly.
YES
∗1 : For thermistor/sensor characteristics, refer to page 286, 287.∗2 : The quality of the power transistor diode module can be assessed by means of
measurement of resistance between terminals (page 289, 290).
(*2)
Clogged water piping system (mixing in of foreign particles,
solenoid valve for water use)
Is the amount of water of heat exchanger 50
l/minute or more?
Is the heat exchanger dirty?
Is the connection
between the thermistor on the heat exchanger gas side
(R4T) and the low pressure sensor (S1NPL)
proper?
Are characteristics of
the thermistor on the heat exchanger gas side (R4T) and the
low pressure sensor (S1NPL) normal?
(∗1)
The output voltage
among three phases is within ±5V for TL power supply
and ±10V for YL power supply.
Troubleshooting by Indication on the Remote Control SiEN30-602
190 Troubleshooting
2.21 �J3� Outside Unit: Malfunction of Discharge Pipe Thermistor (R3T)
Remote Control Display
J3
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected from the temperature detected by discharge pipe temperature thermistor.
Malfunction Decision Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed Causes
! Defect of thermistor (R3T) for outside unit discharge pipe! Defect of outside unit PC board (A1P)
Troubleshooting
(V3072)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace outside unit PC board A1P.
Connect the connector and turn on again.
NO
NO
Replace the thermistor (R3T)
YES
YES
Connector is connected to X34A of outside unit
PC board (A1P).
Resistance is normal when measured after
disconnecting the thermistor R3T from the outside unit PC board.
(3.5kΩ~400kΩ)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 191
2.22 �J4� Malfunction of Heat Exchanger Gas Pipe Thermistor (R4T)
Remote Control Display
J4
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected according to the temperature detected by heat exchanger gas pipe thermistor.
Malfunction Decision Conditions
When the heat exchanger gas pipe thermistor is short circuited or open.
Supposed Causes
! Faulty heat exchanger gas pipe thermistor (R4T)! Faulty outside unit PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P.286.
(V3075)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace outside unit PC board (A1P).
Connect the connector and operate unit again.
NO
NO
Replace thermistor (R4T).
YES
YES
Is the connector for heat
exchanger gas pipe thermistor connected to
X37A on outside unit PC board (A1P)?
Is the resistance
measured after removing the thermistor
(R4T) from outside unit PC board normal? (3.5 kΩ
to 360 kΩ)
Troubleshooting by Indication on the Remote Control SiEN30-602
192 Troubleshooting
2.23 �J5� Outside Unit: Malfunction of Thermistor (R2T) for Suction Pipe
Remote Control Display
J5
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected from the temperature detected by the suction pipe temperature thermistor.
Malfunction Decision Conditions
When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Supposed Causes
! Defect of thermistor (R2T) for outside unit suction pipe! Defect of outside unit PC board (A1P)
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V3073)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Resistance is normal when measured after
disconnecting the thermistor (R2T) from the outside unit
PC board. (3.5kΩ ~360kΩ)
Replace outside unit PC board (A1P).
Connect the connector and turn on again.
NO
NO
Replace the thermistor R2T.
YES
YES
Connector is connected to X37A, of outside unit PC board.
(A1P)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 193
2.24 �J7� Malfunction of Liquid Pipe Thermistor (R6T)Remote Control Display
J7
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected according to the temperature detected by receiver outlet liquid pipe thermistor.
Malfunction Decision Conditions
When the liquid pipe thermistor is short circuited or open.
Supposed Causes
! Faulty liquid pipe thermistor (R6T)! Faulty outside unit PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V3075)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace outside unit PC board (A1P).
Connect the connector and operate unit again.
NO
NO
Replace thermistor (R6T).
YES
YES
Is the connector for receiver outlet
liquid pipe thermistor connected to X37A on outside unit PC board
(A1P)?
Is the resistance
measured after removing the thermistor
(R6T) from outside unit PC board normal? (3.5 kΩ
to 360 kΩ)
Troubleshooting by Indication on the Remote Control SiEN30-602
194 Troubleshooting
2.25 �J9� Malfunction of Sub Cooling Heat Exchanger Outlet Thermistor (R5T)
Remote Control Display
J9
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected according to the temperature detected by sub cooling heat exchanger outlet thermistor.
Malfunction Decision Conditions
When the sub cooling heat exchanger outlet thermistor is short circuited or open.
Supposed Causes
! Faulty receiver gas pipe thermistor (R5T)! Faulty outside unit PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V3075)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace outside unit PC board (A1P).
Connect the connector and operate unit again.
NO
NO
Replace thermistor (R5T).
YES
YES
Is the connector for
oil equalizing pipe thermistor connected to
X37A on outside unit PC board (A1P)?
Is the resistance
measured after removing the thermistor
(R5T) from outside unit PC board normal? (3.5
kΩ to 360 kΩ)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 195
2.26 �JA� Outside Unit: Malfunction of Discharge Pipe Pressure Sensor
Remote Control Display
JA
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction Decision Conditions
When the discharge pipe pressure sensor is short circuit or open circuit.
Supposed Causes
! Defect of high pressure sensor system! Connection of low pressure sensor with wrong connection. ! Defect of outside unit PC board.
Troubleshooting
∗1: Voltage measurement point
∗2: Refer to pressure sensor, pressure / voltage characteristics table on P288.
(V2806)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace the high pressure sensor.
Connect the high pressure sensor and turn on again.
NO
NO
Replace outside unit PC board A1P.
YES
YES
The high pressure sensor is
connected to X46A of outside unit PC board
(A1P).
The relationship
between the ∗1 VH and high pressure
is normal (see ∗2) when voltage is measured between
X46A pins (1) and (3) of outside unit PC board
(A1P)(see ∗1).
Outside unit PC board A2P+5V
X46A
Red
Black
White
GND
*2 Measure DC voltage here.
Low
pre
ssur
e se
nsor
MicrocomputerA/D input
4
3
2
1
Troubleshooting by Indication on the Remote Control SiEN30-602
196 Troubleshooting
2.27 �JC� Outside Unit: Malfunction of Suction Pipe Pressure Sensor
Remote Control Display
JC
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction Decision Conditions
When the suction pipe pressure sensor is short circuit or open circuit.
Supposed Causes
! Defect of low pressure sensor system! Connection of high pressure sensor with wrong connection. ! Defect of outside unit PC board.
Troubleshooting
∗1: Voltage measurement point
∗2: Refer to pressure sensor, pressure/voltage characteristics table on P288.
(V2808)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
The relationship
between the ∗1 VH and low pressure is
normal (see ∗2) when voltage is measured between X45A pins
(2) and (3) of outside unit PC board (A1P)
(see ∗1).
Replace the low pressure sensor.
Connect low pressure sensor property and restart system.
NO
NO
Replace outside unit PC board A1P.
YES
YES
The low pressure sensor is
connected to X45A (blue) of outside unit PC board
(A1P).
Outside unit PC board A2P+5V
X45A
Red
Black
White
GND
*2 Measure voltage here.
Low
pre
ssur
e se
nsor
MicrocomputerA/D input
Outside unit PC board A2P+5V
X45A
Red
Black
White
GND
*2 Measure DC voltage here.
Low
pre
ssur
e se
nsor
MicrocomputerA/D input
4
3
2
1
(V2809)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 197
2.28 �L4� Outside Unit: Malfunction of Inverter Radiating Fin Temperature Rise (R1T)
Remote Control Display
L4
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction Decision Conditions
When the temperature of the inverter radiation fin increases above 98°C.
Supposed Causes
! Actuation of fin thermal (Actuates above 98°C)! Defect of inverter PC board! Defect of fin thermistor
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V2811)
Defect of power unit radiation.• Intake port is clogged• Radiator fin is dirty• Outdoor temperature is highNO
Replace the thermistor.
YES
Abnormal
Is reset possible?
Reset and operate.
Normal
Replace the inverter PC boardNO
YES
Temperature of the radiator fin rises.
Actuates at min. 98 °C
Resistance check of the radiator fin
thermistor
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Troubleshooting by Indication on the Remote Control SiEN30-602
198 Troubleshooting
2.29 �L5� Outside Unit: Inverter Compressor AbnormalRemote Control Display
L5
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected from current flowing in the power transistor.
Malfunction Decision Conditions
When an excessive current flows in the power transistor.(Instantaneous overcurrent also causes activation.)
Supposed Causes
! Defect of compressor coil (disconnected, defective insulation)! Compressor start-up malfunction (mechanical lock)! Defect of inverter PC board
Troubleshooting Compressor inspection
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
(V2812)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Inverter output
voltage check Inverter output voltage is
not balanced. (Normal if within ±10V for YL power supply and ±5V
for TL power supply ) Must be measured when
frequency is stable.
Replace the compressor.
Compressor inspectionInspect according to the diagnosis procedure for odd noises, vibration and operating status of the compressor.
NO
Replace the inverter unit.
YES
YES
Correct power supply.YES
The compressor's coil
is disconnected or the insulation is defective.
There is instantenious power drop.
NO
NO
Disconnect the connection between the compressor and inverter. Make the power transistor check mode setting ON by service mode.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 199
2.30 �L8� Outside Unit: Inverter Current AbnormalRemote Control Display
L8
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected by current flowing in the power transistor.
Malfunction Decision Conditions
When overload in the compressor is detected.
Supposed Causes
! Compressor overload! Compressor coil disconnected! Defect of inverter PC board
Troubleshooting Output current check
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
(V2813)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Inverter output voltage
check Inverter output voltage is not balanced.
(Normal if within ±10V for YL power supply and ±5V for TL
power supply ) Must be measured when
frequency is stable.
Compressor overloadInspection of the compressor and refrigerant system is required.
Compressor inspectionInspect according to the diagnosis procedure for odd noises, vibration and operating status of the compressor.
NO
Replace the inverter PC board.
YES
NO
Reset and restart.NO
The secondary current
of the inverter is higher than 16.5A (YL power supply) and 25.1 A
(TL power supply) for each phase.
Replace the compressor.
NO
YESCompressor
inspection The compressor's coil is
disconnected.
YES
YES
Disconnect the the connection between the compressor and inverter. Make the power transistor check mode setting ON by service mode.
After turning on again, "L8" blinks
again.
Troubleshooting by Indication on the Remote Control SiEN30-602
200 Troubleshooting
2.31 �L9� Outside Unit: Inverter Start up ErrorRemote Control Display
L9
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Malfunction is detected from current flowing in the power transistor.
Malfunction Decision Conditions
When overload in the compressor is detected during startup
Supposed Causes
! Defect of compressor! Pressure differential start! Defect of inverter PC board
Troubleshooting
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
Inverter output voltage
check Inverter output voltage is not balanced.
(Normal if within ±10V for YL power supply and ±5V for TL
power supply ) Must be measured when
frequency is stable.
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Unsatisfactory pressure equalizationCheck refrigerant system.
Compressor inspectionInspect according to the diagnosis procedure for odd noises, vibration and operating status of the compressor.
YES
Replace the inverter PC board
NO
NO
Reset and restart.NO
The difference
between high and low pressure when starting is
above 0.2MPa.
YES
YES
Disconnect the connection between the compressor and inverter. Make the power transistor check mode ON by service mode.
After turning on again, "L9" blinks
again.
(V2814)
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 201
2.32 �LC� Outside Unit: Malfunction of Transmission Between Inverter and Control PC Board
Remote Control Display
LC
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Check the communication state between inverter PC board and control PC board by micro-computer.
Malfunction Decision Conditions
When the correct communication is not conducted in certain period.
Supposed Causes
! Malfunction of connection between the inverter PC board and outside unit control PC board! Defect of outside unit control PC board (transmission section)! Defect of inverter PC board! Defect of noise filter! External factor (Noise etc.)
Troubleshooting by Indication on the Remote Control SiEN30-602
202 Troubleshooting
Troubleshooting
(V2815)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
The transmission
wiring between the outside unit PC board
inverter unit is disconnected.
YES
Fix the disconnection and turn on again.
Connect transmission wiring and turn on again.
NO
YES
The microcomputer
monitor (green) on the inverter P.C.B is
blinking.
The voltage between
two pins of X1A on the inverter unit is 220 ~
240 V.
Defect of outside unit main PC board or defect of inverter PC board.
Check the noise filter (Z1F) for disconnection, and check the power supply wiring of the inverter PC board.
Replace inverter PC board.
When the LC malfunction occur again, replace control PC board.
YES
NO
NO
YES
NO
Are the connectors
between the main PC board (A1P), and
inverter PC board (A2P) connected securely?
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 203
2.33 �P1� Outside Unit: Inverter Over-Ripple ProtectionRemote Control Display
P1
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Imbalance in supply voltage is detected in PC board.
Malfunction Decision Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited status.! Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
Supposed Causes
! Open phase! Voltage imbalance between phases! Defect of main circuit capacitor! Defect of inverter PC board! Defect of K1M! Improper main circuit wiring
Troubleshooting
(V2816)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is the
voltage imbalance applied to the inverter in
excess of 14 V (YL) and 10V (TL)?
∗2
NO
Part or wiring defectAfter turning the power supply OFF, check and repair the main circuit wiring or parts.(1) Loose or disconnected
wiring between power supply and inverter
(2) K1M contact disposition, fusion or contact is poor.
(3) Loose or disconnected noise filter
Using a device capable of constant recording of power supply voltage record power supply voltage between 3 phases (L1 ~ L2, L2 ~ L3, L3~L1) for about one continuous week.
Open phaseNormalize field cause.
Power supply voltage imbalance
Explanation for users
Fix power supply voltage imbalance.
YES
YES
NO
Imbalance in supplied voltage
is in excess of 14 V (YL) and 10V (TL). ∗1
Open phase?
<When voltage monitoring is possible:>
∗1. Measure voltage at the X1M power supply terminal block.
∗2. Measure voltage at terminals L1, L2 and L3 of the diode module inside the inverter while the compressor is running.
∗In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results"and leave it up to him to improve the imbalance.
Be sure to explain to the user that there is a "power supply imbalance" for which DAIKIN is not responsible.
measure
YES
NO
Troubleshooting by Indication on the Remote Control SiEN30-602
204 Troubleshooting
2.34 �P4� Outside Unit: Malfunction of Inverter Radiating Fin Temperature Sensor
Remote Control Display
P4
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction Decision Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited status.! Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed Causes
! Defect of radiator fin temperature sensor! Defect of inverter PC board
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P286.
(V2818)
After resetting, restart.
YES
YES
Is the resistance of
thermistor correct?
Is the resetting possible?
Replace inverter PC board.(Thermistor can not be removed from inverter PC board)
Measure the resistance of radiation fin thermistor.
NO
Replace inverter PC board.NO
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 205
2.35 �UO� Low Pressure Drop Due to Refrigerant Shortage or Electronic Expansion Valve Failure
Remote Control Display
U0
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Detect insufficient gas using low pressure or difference in temperature between the suction pipe and the heat exchanger.
Malfunction Decision Conditions
In cooling! Low pressure of 0.25 MPa or less continues for 30 minutesIn heating! Suction gas superheated degree of 20°C or more continues for 60 minutes.∗ Abnormality is not confirmed and operation is continued.
Supposed Causes
! Insufficient gas or clogged refrigerant (wrong piping)! Faulty thermistor (R2T, R4T)! Faulty low pressure sensor! Faulty main PCB(A1P)
Troubleshooting by Indication on the Remote Control SiEN30-602
206 Troubleshooting
Troubleshooting
NO
NO
1 Set up a pressure gauge in the service port on the low pressure side.2 Connect the Service Checker.3 Reset operation with a remote controller and restart operation.
Are the low pressure
sensor characteristics normal? (∗1)
Is the PCB
detector pressure normal? (∗2)
Replace the main PCB.
Replace the low pressure sensor.
∗1 : Compare pressure sensor measurements with pressure gauge readings. (For measurements by a pressure sensor, measure voltage between connectors (2) and (3) and convert it to pressure in accordance with page 288.)
∗2 : Compare low pressure measured by the Service Checker with pressure sensor measurements (refer to ∗1).
CHECK 2 : Refer to page 244 to eliminate the causes of low pressure drop.
In cooling
NO
NO
1 Connect the Service Checker.2 After resetting operation with a remote
control, restart operation.
Is PCB detection temperature
normal?(∗4)
Replace the main PCB.
Replace the thermistor.
∗3 : Compare the thermistor resistance with surface thermostat measurements.∗4 : Compare the suction pipe temperature checked by the Service Checker with
measurements obtained in ∗3 above.
In heating
Are characteristics of
the suction pipe thermistor (R2T) and the heat exchanger
thermistor (R4T) normal?
(∗3)
CHECK 3 : Refer to page 245 to eliminate the causes of overheat operation.
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 207
2.36 �U1� Reverse Phase, Open PhaseRemote Control Display
U1
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
The phase of each phase are detected by reverse phase detection circuit and right phase or reverse phase are judged.
Malfunction Decision Conditions
When a significant phase difference is made between phases.
Supposed Causes
! Power supply reverse phase! Power supply open phase! Defect of outside PC board A1P
Troubleshooting
(V2820)
Operation is normal if one
place of power supply line phase is replaced.
Fix the open phase. Requires inspection of field power supply section.
Reverse phaseCounter measure of the problem is completed by phase replacement.
Replace outside unit PC board A1P.
YES
YES
NO
NO
There is an open phase at
the power supply terminal section (X1M) of the
outside unit.
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Troubleshooting by Indication on the Remote Control SiEN30-602
208 Troubleshooting
2.37 �U2� Power Supply Insufficient or Instantaneous FailureRemote Control Display
U2
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction Decision Conditions
When the capacitor above only has a voltage of 360 V or less (YL) and 210V or less (TL).
Supposed Causes
! Power supply insufficient! Instantaneous failure! Open phase! Defect of inverter PC board! Defect of outside control PC board! Defect of K1M. ! Main circuit wiring defect
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 209
Troubleshooting
(V2821)
Replace K1M.
Repair wiring.
NO
NO
NO
Turn on again.
Replace the outside unit PC board (A1P).
YES
YES
YES
Turn K1M ON.YES
NO
Is 220 ~ 240 V of power reaching the
K1M coil?
Is 220 ~ 240 V
at the connector X1A of inverter PC board.
Replace the inverter PC board.
Replace the inverter PC board.
YES
NO
NO
Does the voltage
between terminals P2(or P3) and N3 gradually
rise to 556 VDC (YL) or 283 VDC (TL)after
turning on?
Monitor field power supply.
Replace the inverter PC board.
The voltage between
the P2 (or P3) and N3 terminals is 320 VDC (YL) or more and 190 VDC (TL) or
less when the compressor is
running.
Is connection wire
connected between the connector X21A and X6A?
YES
NOIs
220 ~ 240 V at the connector X1A of
outside PC board side?
Check the transmission wiring between the outside unit PC board and inverter unit.
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Troubleshooting by Indication on the Remote Control SiEN30-602
210 Troubleshooting
2.38 �U3� Check Operation not ExecutedRemote Control Display
U3
Applicable Models
RWEYQ10MYL, TL
Method of Malfunction Detection
Check operation is executed or not
Malfunction Decision Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed Causes
! Check operation is not executed.
Troubleshooting
(V3052)
Has the check operation
performed on Outside unit P.C.B?
Press the BS4 on P.C. board on the master outside unit for 5 seconds or more to execute check operation.
Replace the main P.C. board on the outside unit.
NO
YES
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 211
2.39 �U4� Malfunction of Transmission Between Indoor UnitsRemote Control Display
U4
Applicable Models
All model of indoor unitRWEYQ10MYL, TL
Method of Malfunction Detection
Microcomputer checks if transmission between indoor and outside units is normal.
Malfunction Decision Conditions
When transmission is not carried out normally for a certain amount of time
Supposed Causes
! Indoor to outdoor, outside to outside unit transmission wiring F1, F2 disconnection, short circuit or wrong wiring
! Outside unit power supply is OFF! System address doesn�t match! Defect of indoor unit PC board! Defect of outside unit PC board
Troubleshooting by Indication on the Remote Control SiEN30-602
212 Troubleshooting
Troubleshooting
(V2822)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is indoor - outside unit and
outside unit - outside unit transmission wiring
normal?
Supply 220~240 V.
Replace the fuse.
Fix the indoor/outside unit transmission wiring.
Push and hold the RESET button on the outside unit PC board for 5 seconds.
Replace the outside unit PC Board (A1P).
YES
YES
NO
YES
Replace the indoor unit PC Board.
Push and hold the RESET button on the master outside unit PC Board for 5 seconds.∗ The unit will not operate
for up to 12 minutes.
Fix the indoor/outside unit transmission wiring.
YES
NO
NO
YES
Has the indoor
or outside unit PC board been
replaced, or has the indoor - outside or outside - outside
unit transmission wiring been modified?
Allindoor unit
remote controllers of thesame refrigerant system
display"U4."
NOOutside unit
PC board microcomputer monitor (HAP) blinks.
NO
NO
NO Operation ready lamp (H2P) is
blinking.
Lamp does not go off for 12 minutes or
more.
Is indoor - outdoor and outside
-outside unit transmission wiring normal?
YESThe fuse on the outside unit's PC board is
burnt.
Replace the transformer. replacement
Replace outside unit PC board. (A1P)
NOThe secondary voltage of the transformer
is about 22 V.
NO
The voltage between
terminals L1 and N of the outside unit PC board
is 220~240 V.
Reset the power supply.
YES
YESYES
NO
YES
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 213
2.40 �U5� Malfunction of Transmission Between Remote Control and Indoor Unit
Remote Control Display
U5
Applicable Models
All models of indoor units
Method of Malfunction Detection
In case of controlling with 2-remote control, check the system using microcomputer is signal transmission between indoor unit and remote control (main and sub) is normal.
Malfunction Decision Conditions
Normal transmission does not continue for specified period.
Supposed Causes
! Malfunction of indoor unit remote control transmission ! Connection of two main remote controls (when using 2 remote controls)! Defect of indoor unit PC board! Defect of remote control PC board! Malfunction of transmission caused by noise
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2823)
NO
YES YES
NO
Replace indoor unit PC board.
Set one remote controller to "SLAVE"; turn the power supply off once and then back on.
There is possibility of malfunction caused by noise. Check the surrounding area and turn on again.
NO NO
Using 2-remote controls control.
All indoor PC board microcomputer
monitors blink.
YESMulti-core
cable is used for the indoor unit remote controller transmission
wiring.
Operation returns to normal when the power is turned off
momentarily.
YES YESSS1 of both remote controls is set to
"MASTER."
NO
Switch to double-core independent cable. replacement
Defect of remote controller PC board or indoor unit PC board. Replace whichever is defective.
Troubleshooting by Indication on the Remote Control SiEN30-602
214 Troubleshooting
2.41 �U7� Malfunction of Transmission Between Outside UnitsRemote Control Display
U7
Applicable Models
RWEYQ 10MTL/YL
Method of Malfunction Detection
Microcomputer checks if transmission between indoor unit and remote control is normal.
Malfunction Decision Conditions
When transmission is not carried out normally for a certain amount of time
Supposed Causes
! Improper connection of transmission wiring between outside unit and external control adapter for outdoor unit.
! Improper cool/heat selection ! Improper cool/heat unified address (outside unit, external control adapter for outdoor unit)! Defect of outside unit PC board (A1P)! Defect of external control adapter for outdoor unit! Improper connection of transmission wiring between outside units of multi outside unit
connection.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 215
Troubleshooting
(V2824)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
NO
Replace the outside unit PC Board (A1P).
YESC/H SELECT is set to "IND".
Cool / heat selection is unified.
C/H SELECT is set to "MASTER."
NO
C/H SELECT is set to "SLAVE."
YES NOCheck and see if the following items are
normal.
NODoes a
malfunction occur when the cool / heat selector is
set to "IND?"
YES
Set C/H SELECT to "IND."
YES
Fix the outside units multi connection transmission wiring and reset power.
NOIs the outside units multi connection transmission wiring
normal?
Is the indoor /
outside unit transmission wiring normal?
NO
YES
Fix the indior / outside unit transmission wiring.
The cool / heat unified address for outside units in outside - outside unit transmission is duplicated. Set the address correctly.
YES
NO
NO
YES
YES
Replace the outside unit outside control adaptor. replacement
Replace the outside unit PC board (A1P).
External control adaptor for outdoor unit•Is there continuity?•Does the cool/heat unified address match?Outside unit (unified master unit)•Is there continuity?•Does the cool/heat unified address match?
Fix the problem.
Troubleshooting by Indication on the Remote Control SiEN30-602
216 Troubleshooting
2.42 �U8� Malfunction of Transmission Between Master and Slave Remote Controls
Remote Control Display
U8
Applicable Models
All models of indoor units
Method of Malfunction Detection
In case of controlling with 2-remote control, check the system using microcomputer if signal transmission between indoor unit and remote control (main and sub) is normal.
Malfunction Decision Conditions
Normal transmission does not continue for specified period.
Supposed Causes
! Malfunction of transmission between main and sub remote control! Connection between sub remote controls! Defect of remote control PC board
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2825)
SS1 of both remote controllers is set to
"SUB."
Set SS1 to "MAIN"; the power supply off once and then back on.
Set one remote controller to "MAIN"; the power supply off once and then back on.
Turn the power off and then back on. If a malfunction occurs, replace the remote controller PC board.
YES
YESYES
NO
NO
NOUsing 2-remote controls control.
SS1 of remote controller PC boards
is set to "MAIN."
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 217
2.43 �U9� Malfunction of Transmission Between Indoor and Outside Units in the Same System
Remote Control Display
U9
Applicable Models
All models of indoor units
Method of Malfunction Detection
Detect the malfunction signal of any other indoor unit within the system concerned.
Malfunction Decision Conditions
When the malfunction decision is made on any other indoor unit within the system concerned.
Supposed Causes
! Malfunction of transmission within or outside of other system! Malfunction of electronic expansion valve in indoor unit of other system! Defect of PC board of indoor unit in other system! Improper connection of transmission wiring between indoor and outside unit
Troubleshooting by Indication on the Remote Control SiEN30-602
218 Troubleshooting
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2826)
The "U4" display blinks on
the remote controllers of other units within the same
refrigerant system.
Refer to failure diagnosis for "U5" malfunction code.
Re-diagnose by display after passage of 2 minutes or more.
NO
NO
Refer to failure diagnosis for "U4" malfunction code.
YES
YES
"U9" has been displayed for 2 minutes or
more.
NO
Turn on all indoor units.
Refer to failure diagnosis for "A1" malfunction code.
NO
YES
The "A1" display blinks on
the remote controls of other units within the same
refrigerant system.
Refer to failure diagnosis for "UA" malfunction code.
YES
The "UA" display blinks on
the remote controls of other units within the same
refrigerant system.
Refer to failure diagnosis for "A9" malfunction code.
NO
YES
The "A9" display blinks on
the remote controls of other units within the same
refrigerant system.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 219
2.44 �UA� Indoor & Outside Units and Remote Control Combination Failure
Remote Control Display
UA
Applicable Models
All models of indoor unitRWEYQ10MYL, TL
Method of Malfunction Detection
Detect abnormalities in combination of indoor and outside units and the remote control using the outside unit PCB.
Malfunction Decision Conditions
When any of the followings is detected, failure is instantly confirmed.! When there is a problem in the combination of the indoor and outside units ! When there is a problem in the combination of the indoor unit and the remote control
Supposed Causes
! Excess of connected indoor units! Defect of outside unit PC board (A1P)! Mismatching of the refrigerant type of indoor and outside unit.! Setting of outside P.C. board was not conducted after replacing to spare parts P.C. board.
Troubleshooting
∗ The number of indoor units that can be connected to a single outside unit system depends on the type of outside unit.
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2827)
The total of
indoor units displaying "UA" and
indoor units connected to the same refrigerant system is
within connectable number of unit∗
Normal
NO
NO
There are too many indoor units within the same refrigerant system.
Push and hold the RESET button on the outside unit PC board for 5 seconds.
YES
Is the outside
P.C. board replaced to spare parts P.C. board ?
YES The refrigerant classification has not been set yet.
NO
YES
Does a malfunction occur?
Replace outside unit PC board (A1P).
Matches the refrigerant type of indoor and outside unit.
NO
YES
Does the refrigerant type of
indoor and outside unit match?
Troubleshooting by Indication on the Remote Control SiEN30-602
220 Troubleshooting
2.45 �UC� Address Duplication of Centralized ControllerRemote Control Display
UC
Applicable Models
All models of indoor unitCentralized controller
Method of Malfunction Detection
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Malfunction Decision Conditions
The malfunction decision is made as soon as the abnormality aforementioned is detected.
Supposed Causes
! Address duplication of centralized remote control! Defect of indoor unit PC board
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2828)
Replace indoor unit PC board.
Address duplication of central remote controlThe setting must be changed so that the central remote control address is not duplicated.
YES
NO
Optional controllers for
centralized control are connected to the
indoor unit.
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 221
2.46 �UE� Malfunction of Transmission Between Centralized Controller and Indoor Unit
Remote Control Display
UE
Applicable Models
All models of indoor unitsCentralized controller
Method of Malfunction Detection
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction Decision Conditions
When transmission is not carried out normally for a certain amount of time
Supposed Causes
! Malfunction of transmission between optional controllers for centralized control and indoor unit
! Connector for setting master controller is disconnected.! Failure of PC board for central remote controlRemote Control! Defect of indoor unit PC board
Troubleshooting by Indication on the Remote Control SiEN30-602
222 Troubleshooting
TroubleshootingCaution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is the power
supply turned on for indoor units displaying
malfunction?
Is transmission wiring
disconnected or wired incorrectly?
Is the transmission
wiring with the master controller disconnected or
wired incorrectly?
Is the master controller's
connector for setting master controller disconnected?
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector correctly.
Replace the central PC board.
Reset power supply simultaneously for all optional controllers for centralized control.
NO
YES
NO
YES
YES
NO
NO
Turn indoor unit's power supply.
YES
NO
NO
YES
YES
NO
Has an indoor unit once
connected been remove or its address changed?
Is the group No.
of malfunctioning indoor units set?
Is transmission with all indoor units
malfunctioning?
(V2829)
YES
SiEN30-602 Troubleshooting by Indication on the Remote Control
Troubleshooting 223
2.47 �UF� Refrigerant System not Set, Incompatible Wiring/Piping
Remote Control Display
UF
Applicable Models
All models of indoor unitsRWEYQ10MYL, TL
Method of Malfunction Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to that of indoor units that have made changes in temperature.
Malfunction Decision Conditions
The malfunction is determined as soon as the abnormality aforementioned is detected through checking the system for any erroneous connection of units on the check operation.
Supposed Causes
! Improper connection of transmission wiring between outside unit and external control adapter for outdoor unit.
! Failure to execute wiring check operation! Defect of indoor unit PC board
Troubleshooting
Note: Test operation may not be successful if carried out after the outside unit has been off for more than 12 hours, or if it is not carried out after running all connected indoor units in the fan mode for at least an hour.
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2830)
Is indoor -
outside and outside - outside unit transmission
wiring normal?
Replace indoor unit PC board.
Test operation may not have been carried out successfully.
After fixing incorrect wiring, push and hold the RESET button on the master outside unit PC board for 5 seconds.
YES
NOYES
NO
NO
YES
Is the test
operation (Wiring check operation) carried
out?
Is indoor -outside and outside-
outside unit transmission wiring normal?
Open stop valve.
YES
NOAre the stop valves opened?
∗ The unit will not run for up to 12 minutes.
Troubleshooting by Indication on the Remote Control SiEN30-602
224 Troubleshooting
2.48 �UH� Malfunction of System, Refrigerant System Address Undefined
Remote Control Display
UH
Applicable Models
All models of indoor unitsRWEYQ10MYL, TL
Method of Malfunction Detection
Detect an indoor unit with no auto address setting.
Malfunction Decision Conditions
The malfunction decision is made as soon as the abnormality aforementioned is detected.
Supposed Causes
! Improper connection of transmission wiring between outside unit and outside unit outside control adapter
! Defect of indoor unit PC board! Defect of outside unit PC board (A1P)
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2831)
NO
YES
YES
After fixing incorrect wiring, push and hold the RESET button on the master outside unit PC board for 5 seconds.
Normal
NO
Is electricity
being introduce forthe first time after
installation or after an indoor or outside unit PC board has been
replaced?
Is indoor - outside and
outside - outside unit transmission wiring
normal?
YES
NormalNO
Does a malfunction occur?
NODoes a
"UH" malfunction occur for all indoor units
in the system?
YES NO
Does a malfunction
occur even after 12 minutes elapses
from the time when electricity is introduced to indoor
and outside units?
YES
Replace indoor unit PC board.
Replace outside unit PC board (A1P).
After fixing incorrect wiring, push and hold the RESET button on the outside unit PC board for 5 seconds Replace whichever is defective.
* The unit will not run for up to 12 minutes.
SiEN30-602 Troubleshooting (OP: Central Remote Control)
Troubleshooting 225
3. Troubleshooting (OP: Central Remote Control)3.1 �M1� PC Board DefectRemote Control Display
M1
Applicable Models
Central remote control
Method of Malfunction Detection
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction Decision Conditions
When + polarity and - polarity are detected at the same time.
Supposed Causes
! Defect of central remote control PC board
Troubleshooting Replace the central remote control.
Troubleshooting (OP: Central Remote Control) SiEN30-602
226 Troubleshooting
3.2 �M8� Malfunction of Transmission Between Optional Controllers for Centralized Control
Remote Control Display
M8
Applicable Models
Central remote control
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data. (The system will be automatically reset.)
Malfunction Decision Conditions
When no master controller is present at the time of the startup of slave controller.When the centralized controller, which was connected once, shows no response.
Supposed Causes
! Malfunction of transmission between optional controllers for centralized control! Defect of PC board of optional controllers for centralized control
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2833)
Is transmission wiring disconnected or
wired incorrectly?
The PC board of one of the optional controllers for centralized control is defective. Try turning on/off using each optional controllers for centralized control, and replace the PC board of the one that is unable to control the indoor unit.
NO
NO
Fix the wiring correctly.
YES
YES
Has a once connected
optional controller for centralized control been
disconnected or its address
changed?
Turn on power supply for all optional controllers for centralized control.
Reset power supply simultaneously for all optional controllers for centralized control.
YES
NO
Is the power supply
turned on for all optional controllers for centralized
control?
Set reset switch to "normal."
YES
NO
Is the reset switch of all
optional controllers for centralized control set to
''normal?''
SiEN30-602 Troubleshooting (OP: Central Remote Control)
Troubleshooting 227
3.3 �MA� Improper Combination of Optional Controllers for Centralized Control
Remote Control Display
MA
Applicable Models
Central remote control
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
When the schedule timer is set to individual use mode, other central component is present.When multiple master controller are present.When the remote control adapter is present.
Supposed Causes
! Improper combination of optional controllers for centralized control! More than one master controller is connected! Defect of PC board of optional controller for centralized control
Troubleshooting (OP: Central Remote Control) SiEN30-602
228 Troubleshooting
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2834)
NO
NO
Cannot be used in combination with a wiring adaptor for electrical appendices. Remove the wiring adaptor for electrical appendices and reset the power supply for all optional controllers for centralized control simultaneously.
Schedule timer and parallel interface cannot be used in combination. Disconnect either the schedule timer or parallel interface and reset the power supply for all optional controllers for centralized control simultaneously.
Disconnect the schedule timer's individual / combined connector and reset the power supply for all optional controllers for centralized control simultaneously.
Arrange so that the connector for setting master controller is connected to one controller for centralized control and reset the power supply for all optional controllers for centralized control simultaneously.
Disconnect the connector for setting master controller from the master controller, connect to another optional controller for centralized control and simultaneously reset all optional controllers for centralized control again. The controller connected by the connector for setting master controller when the malfunction is cleared is defective and must be replaced.
Reset the power supply forall optional controllers for centralized control simultaneously.
YES
YES
Is the wiring adaptor for
electrical appendices connected?
YESIs a schedule timer connected?
Are there two or more
optional controllers for centralized control connected
with the connector for setting master
controller?
YESIs a parallel interface connected?
NO
YES
Is the schedule timer's
individual/combined connector connected?
NO
NO
If the malfunction is still not cleared:
SiEN30-602 Troubleshooting (OP: Central Remote Control)
Troubleshooting 229
3.4 �MC� Address Duplication, Improper SettingRemote Control Display
MC
Applicable Models
Central remote control
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
Two units are both set to master controller mode or slave controller mode.
Supposed Causes
! Address duplication of centralized remote control
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Are two or more central remote controls connected? Disconnect all central remote
controllers except one and reset the power supply of the central remote control.
Reset power supply of the central remote control.
NO
YES
(V2835)
Troubleshooting (OP: Schedule Timer) SiEN30-602
230 Troubleshooting
4. Troubleshooting (OP: Schedule Timer)4.1 �UE� Malfunction of Transmission Between Centralized
Controller and Indoor UnitRemote Control Display
UE
Applicable Models
Schedule timerAll models of indoor units
Method of Malfunction Detection
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction Decision Conditions
When transmission is not carried out normally for a certain amount of time
Supposed Causes
! Malfunction of transmission between central remote control and indoor unit! Disconnection of connector for setting master controller (or individual/combined switching
connector) ! Defect of schedule timer PC board! Defect of indoor unit PC board
SiEN30-602 Troubleshooting (OP: Schedule Timer)
Troubleshooting 231
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2836)
Is the power
supply turned on for indoor units displaying
malfunction?
Is transmission
wiring disconnected or wired incorrectly?
Is the
transmission wiring with the master
controller disconnected or wired incorrectly?
Is the master
controller's connector for setting master controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector correctly.
Replace the central PC board.
Reset power supply simultaneously for all optional controllers for centralized control.
NO
YES
NO
YES
YES
NO
NO
Turn indoor unit's power supply.
YES
NO
NO
YES
YES
YES
NO
Has an indoor unit once
connected been removed or its address changed?
Is the group No. of malfunctioning
indoor units set?
Is transmission
with all indoor units malfunctioning?
Troubleshooting (OP: Schedule Timer) SiEN30-602
232 Troubleshooting
4.2 �M1� PC Board DefectRemote Control Display
M1
Applicable Models
Schedule timer
Method of Malfunction Detection
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction Decision Conditions
When + polarity and - polarity are detected at the same time.
Supposed Causes
! Defect of schedule timer PC board
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Reset power supply.
Does the system return to normal?
YES
NO
External factor other than equipment malfunction (noise etc.)
Replace the indoor unit PC board.
(V2837)
SiEN30-602 Troubleshooting (OP: Schedule Timer)
Troubleshooting 233
4.3 �M8� Malfunction of Transmission Between Optional Controllers for Centralized Control
Remote Control Display
M8
Applicable Models
Schedule timer
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data. (The system will be automatically reset.)
Malfunction Decision Conditions
When no master controller is present at the time of the startup of slave controller.When the optional controllers for centralized control which was connected once, shows no response.
Supposed Causes
! Malfunction of transmission between optional controllers for centralized control! Defect of PC board of optional controllers for centralized control
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2838)
Is transmission
wiring disconnected or wired incorrectly?
The PC board of one of the optional controllers for centralized control is defective. Try turning on/off using each optional controllers for centralized control, and replace the PC board of the one that is unable to control the indoor unit.
YES
NO
Fix the wiring correctly.
YES
NO
Has a once
connected optional controller for centralized
control been disconnected or its address
changed?
Turn on power supply for all optional controllers for centralized control.
Reset power supply simultaneously for all optional controllers for centralized control.
YES
NOIs the power
supply turned on for all optional controllers for
centralized control?
Set reset switch to "normal."
YES
NO
Is the reset switch of all
optional controllers for centralized control set to
"normal" ?
Troubleshooting (OP: Schedule Timer) SiEN30-602
234 Troubleshooting
4.4 �MA� Improper Combination of Optional Controllers for Centralized Control
Remote Control Display
MA
Applicable Models
Schedule timer
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
When the schedule timer is set to individual use mode, other central component is present.When multiple master controller are present.
Supposed Causes
! Improper combination of optional controllers for centralized control! More than one master controller is connected.! Defect of PC board of optional controller for centralized control
SiEN30-602 Troubleshooting (OP: Schedule Timer)
Troubleshooting 235
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Disconnect the schedule timer's individual / combined connector and reset the power supply for all optional controllers for centralized control simultaneously.
Arrange so that the connector for setting master controller is connected to one controller for centralized control and reset the power supply for all optional controllers for centralized control simultaneously.
Disconnect the connector for setting master controller from the master controller, connect to another optional controller for centralized control and simultaneously reset all optional controllers for centralized control again. The controller connected by the connector for setting master controller when the malfunction is cleared is defective and must be replaced.
Reset the power supply for all optional controllers for centralized control simultaneously.
YES
YES
NO
Is the schedule timer connected?
Are there two
or more optionalcontrollers for
centralized control connected with the
connector for setting master
controller?
YES
Is the schedule timer's
individual/combined connector connected?
NO
NO
Cannot be used in combination with a wiring adaptor for electrical appendices. Remove the wiring adaptor for electrical appendices and reset the power supply for all optional controllers for centralized control simultaneously.
YESIs the
wiring adaptor for electrical appendices
connected?
NO
Schedule timer and parallel interface cannot be used in combination. Disconnect either the schedule timer or parallel interface and reset the power supply for simultaneously centralized control.
YESIs a parallel interface
connected?
NO
If the malfunction is still not cleared:
(V2839)
Troubleshooting (OP: Schedule Timer) SiEN30-602
236 Troubleshooting
4.5 �MC� Address Duplication, Improper SettingRemote Control Display
MC
Applicable Models
All models of indoor units, schedule timer
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
When two or more schedule timers are connected.
Supposed Causes
! Address duplication of optional controller for centralized control
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2840)
Are two or more centralized controller
connected?
Reset the power supply for the centralized controller.
Disconnect all centralized controller except one and reset the centralized controller timer’s power supply.
YES
NO
SiEN30-602 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 237
5. Troubleshooting (OP: Unified ON/OFF Controller)5.1 Operation Lamp BlinksRemote Control Display
Operation lamp blinks
Applicable Models
All models of indoor unitsUnified ON/OFF controller
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
Supposed Causes
! Malfunction of transmission between optional controller and indoor unit! Connector for setting master controller is disconnected! Defect of unified ON/OFF controller! Defect of indoor unit PC board! Malfunction of air conditioner
Troubleshooting (OP: Unified ON/OFF Controller) SiEN30-602
238 Troubleshooting
Troubleshooting
(V2841)
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is the power supply
for the indoor unit displaying a malfunction
turned on?
Is transmission
wiring disconnected or wired incorrectly?
Is the transmission wiring
with the master controller disconnected or wired
incorrectly?
Is the master
controller's connector for setting master controller
disconnected.
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector correctly.
Replace the central PC board.
Reset power supply for all optional controllers for centralized control
NO
YES
NO
YES
YES
NO
YES
Turn the power supply of the indoor unit on.
YES
NO
NO
YES
NO
YES
NO
Has a once connected
indoor unit been removed or its address changed?
Diagnose the cause with the air conditioner's failure diagnosis manual.
NO
YESIs a
malfunction code displayed on the remote
control?
Is the group No.
of malfunctioning indoor units set?
Is transmission
with all indoor units malfunctioning?
SiEN30-602 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 239
5.2 Display �Under Host Computer Integrate Control� Blinks (Repeats Single Blink)
Remote Control Display
�under host computer integrated control� (Repeats single blink)
Applicable Models
Unified ON/OFF controllerCentral remote control, Schedule timer
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
When the centralized controller, which was connected once, shows no response.The control ranges are overlapped.When multiple master central controller are present.When the schedule timer is set to individual use mode, other central controller is present.When the wiring adapter for electrical appendices is present.
Supposed Causes
! Address duplication of central remote control! Improper combination of optional controllers for centralized control! Connection of more than one master controller ! Malfunction of transmission between optional controllers for centralized control! Defect of PC board of optional controllers for centralized control
Troubleshooting (OP: Unified ON/OFF Controller) SiEN30-602
240 Troubleshooting
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2842)
Is the reset
switch of all optional controllers for centralized control set
to "normal"?
Is transmission
wiring disconnected or wired incorrectly?
Correct the setting of the unified ON / OFF controller's switch for setting each address and reset the power supply of the unified ON / OFF controller.
Refer to failure diagnosis for central remote controller or schedule timer.
NO
YES
YES
NO
NO
Fix the wiring correctly.
Set reset switch to "normal."
NO
NO
YES
YES
YES
Is the power
supply turned on for all optional controllers
for centralized control?
Reset power supply simultaneously for all optional controllers for centralized control.
NO
YES
Hasa once
connected optional controller for centralized
control been disconnected or its address changed?
Is the central
remote controller or schedule timer displaying a
malfunction?
Is a central remote
control or schedule timer connected?
Turn on power supply for all optional controllers for centralized control.
NO
YES NO
Is the
setting of the unified ON / OFF
controller's switch for setting each address duplicated?
Are two or more unified ON / OFF controllers
connected?
YES
2A
SiEN30-602 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 241
NO
NO
NO
Cannot be used in combination with a wiring adaptor for electrical appendices. Remove the wiring adaptor for electrical appendices and reset the power supply for all optional controllers for centralized control simultaneously. Schedule timer and data station cannot be used in combination. Disconnect either the schedule timer or data station and reset the power supply for all optional controllers for centralized control simultaneously.
Schedule timer and parallel interface cannot be used in combination. Disconnect either the schedule timer or parallel interface and reset the power supply for all optional controllers for centralized control simultaneously.
Disconnect the schedule timer's individual / combined connector and reset the power supply for all optional controllers for centralized control simultaneously.
Arrange so that the connector for setting master control is connected to one controller for centralized control and reset the power supply for all optional controllers for centralized control simultaneously.
Disconnect the connector for setting master control from the master controller, connect to another optional controller for centralized control and simultaneously reset all optional controllers for centralized control again. The controller connected by the connector for setting master control when the malfunction is cleared is defective and must be replaced.
Reset the power supply for all optional controllers for centralized control simultaneously.
YES
YES
Is the wiring adapter for
electrical appendices connected?
YESIs a schedule timer connected?
Are there two or
more optional controllers for centralized control connected with the
connector for setting master control?
YESIs a parallel interface connected?
NO
YESIs the
schedule timer's individual/combined
connector connected?
YESIs a data station connected?
NO
NO
If the malfunction is still not cleared:
2A
(V2843)
Troubleshooting (OP: Unified ON/OFF Controller) SiEN30-602
242 Troubleshooting
5.3 Display �Under Host Computer Integrate Control� Blinks (Repeats Double Blink)
Remote Control Display
�under host computer integrated control� (Repeats double blink)
Applicable Models
Unified ON/OFF controller
Method of Malfunction Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction Decision Conditions
When no central control addresses are set to indoor units.When no indoor units are connected within the control range.
Supposed Causes
! Central control address (group No.) is not set for indoor unit.! Improper address setting! Improper wiring of transmission wiring
Troubleshooting
CautionBe sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
(V2844)
Is the switch for
setting each address set correctly?
Is the transmission wiring
disconnected or wired incorrectly?
Replace the PC board of the unified ON/OFF controller.
Fix the wiring correctly.
Set by remote controller the central control address for all indoor units connected to the central control line.
YES
YES
Set the switch for setting each address correctly and simultaneously reset the power supply for all optional controllers for centralized control.
NO
NO
NO
YES
Is the central
control address (group No.) set for the
indoor unit?
SiEN30-602 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 243
← Refer to [CHECK 5]← Is the indoor unit too small for the large-sized outside unit?
[CHECK 1] Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Rise in high pressure
Local pressure rise
Faulty high pressure control
Faulty outside unit electronic expansion valve
Faulty control
Faulty indoor unit electronic expansion valve
Stop valve closed
Faulty high pressure sensor
[In cooling]If the outside unit electronic expansion valve is throttled(∗1)
Dirty water heat exchanger
Decrease in water of the water heat exchanger
Mixing-in of non-condensable gas
Degradation in condensing capacity
Clogged water piping system
[In cooling]
[In heating]
← Check to be sure the stop valve is open.
← Conduct visual checks for pipe conditions.
← Is there any temperature difference around the filter or the branch pipe?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Is the heat exchanger clogged (in cooling)?
← Is air or else mixed in the refrigerant system?
← Is the water temperature at the inlet not more than 45°C?
← Does the water pump function normally?
← Is the strainer or the like clogged?
← Is the suction air temperature not more than 27°C?
← Is air or else mixed in the refrigerant system?
← Is the indoor temperature not more than 27°C?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Can the fan motor be rotated with hands?Are the motor coil resistance and insulation normal?
← If a spare PCB is mounted, is the capacity setting properly made?
← Is the air filter clogged?
← Is there any obstacle in the air passage?
Excessive refrigerant charging
Improper mode selection [In heating]
∗1 : In cooling, the outside unit electronic expansion valve (Y1E) is fully open in normal condition.∗2 : In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(Refer to “Electronic Expansion Valve Control” on page 93)
[In heating]If the indoor unit electronic expansion valve excessively throttled(∗2)
High pipe resistance
A temperature difference in excess of 10°C between the inlet and the outlet is deemed to be abnormal.
Faulty control
Bent and Crush of pipe
Clogging of foreign particles
Faulty valve coil
Faulty valve body
Faulty high pressure sensor
Faulty control PCB
Faulty indoor unit liquid pipe thermistor
Faulty valve coil
Faulty valve body
Faulty control PCB
High water temperature at the water heat exchanger inlet
Faulty water pump
Short circuit
High ambient temperature
Faulty fan motor
Dirty filter
Obstacle
Faulty control PCB (including capacity setting)
Mixing-in of non-condensable gas
High suction air temperature of indoor unit
Decreased fan airflow rate
Decreased fan output
High air passage resistance
Faulty suction air thermistor of indoor unit
Troubleshooting (OP: Unified ON/OFF Controller) SiEN30-602
244 Troubleshooting
Abnormal piping length
Degradation in evaporating capacity
[In cooling]
Short circuit
Low ambient temperature
← Are the coil resistance and insulation normal?
← Can the fan motor be rotated with hands?Are the motor coil resistance and insulation normal?
← If a spare PC board is mounted, is the capacity setting properly made?
← Is the air filter clogged?
← Is there any obstacle in the air passage?
← Is the water temperature at the water heat exchanger inlet not less than 10°C?
← Is the water heat exchanger clogged?
← Is the piping length in the permissible range?
← Conduct visual checks for pipe conditions.
← Is there any temperature difference around the filter or the branch pipe?
← Check to be sure the stop valve is open.
[In heating]
Moisture choke
← Refer to [CHECK 6]
← Eliminate moisture by vacuum break.
∗1 : For details of the compressor capacity control while in cooling, refer to “Compressor Control” on page 69.∗2 : The “low pressure protection control” includes low pressure drop control and hot gas bypass control. For
details, refer to page 75.∗3 : In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (For details,
refer to page 93.)∗4 : In heating, the outdoor unit electronic expansion valve (Y1E) is used for “superheated degree control of
outside unit heat exchanger”. (For details, refer to page 71.)
[CHECK 2] Check for causes of drop in low pressure
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Abnormally low low-pressure (Low evaporating temperature)
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Are the voltage characteristics normal?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Check for the thermistor resistance and connection.
← Check for the thermistor resistance and connection.
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Check for the thermistor resistance and connection.
← Is the suction air temperature not less than 14°C?
← Is the indoor temperature not more than 14°C?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
Less circulation quantity of refrigerant
High pipe resistance
Inadequate refrigerant quantity
Bent or Crush of pipe
Clogging of foreign particles
Stop valve closed
Low water temperature at the water heat exchanger inlet
Dirty water heat exchanger
Faulty low pressure control
[In cooling](∗1)
[In both cooling and heating](∗2)
[In cooling]If the indoor unit electronic expansion valve is excessively throttled (∗3)
Faulty electronic expansion valve control
[In heating]If the outside unit electronic expansion valve is excessively throttled (∗4)
Faulty compressor capacity control
Faulty low pressure protection control
Faulty indoor unit electronic expansion valve
Faulty control
Faulty outside unit electronic expansion valve
Faulty control
Faulty low pressure sensor
Faulty control PCB
Faulty low pressure sensor
Faulty hot gas solenoid valve
Faulty control PCB
Faulty valve coil
Faulty valve body
Faulty gas pipe thermistor of indoor unit
Faulty liquid pipe thermistor of indoor unit
Faulty control PCB
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty control PCB
Low suction air temperature of indoor unit
Faulty suction air thermistor of indoor unit
Decreased fan airflow rate
Decreased fan output
High air passage resistance
Faulty fan motor
Faulty control PCB (including capacity setting)
Dirty filter
Obstacle
SiEN30-602 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 245
(∗1)
Faulty hot gas bypass control
[In cooling only]
(∗2)
Faulty indoor unit electronic expansion valve
Faulty control
Faulty outside unit electronic expansion valve
Clogged hot gas passage
← Are the coil resistance and insulation normal?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Is the temperature of piping connected to the four-way changeover valve normal?
← Are the coil resistance and insulation normal?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Is the connector properly connected? Are the thermistor resistance characteristics normal?
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Refer to [CHECK 6]
← Is the piping length in the permissible range?
← Conduct visual checks for pipe conditions.
← Eliminate moisture by vacuum break.
← Check to be sure the stop valve is open.
∗1 : For hot gas bypass control, refer to “Low Pressure Protection Control” on page 75.∗2 : For subcooling electronic expansion valve, refer to page 71.∗3 : In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (Refer to page 93.)∗4 : In heating, the outside unit electronic expansion valve (Y1E) is used for “superheated degree control.” (Refer to page
71.)∗5 : Reference values for superheated degree to be used in the judgment of overheat operation
1 Suction gas superheated degree: 10°C or more 2 Discharge gas superheated degree: 45°C or more, excluding when it is immediately after startup, under drop control or other specific conditions.(The values above must be used only for reference purposes. Even it is operated within the range above,operation may be normal in other conditions.)
[CHECK 3] Check for causes of overheat operation
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Rise in discharge pipe temperature
Faulty subcooling electronic expansion valve (Y3E) control
Faulty subcooling electronic expansion valve
Faulty control
Faulty four-way changeover valve function
Faulty discharge pipe temperature control
Superheated compressor
[In cooling]If the indoor unit electronic expansion valve excessively throttled (∗3)
Faulty superheated degree control
Inadequate refrigerant quantity
High pipe resistance
[In heating]If the outside unit electronic expansion valve excessively throttled (∗4) Faulty control
Abnormal pipe length
Bent or Crush of pipe
Stop valve closed
(Including moisture choke)
Faulty solenoid valve coil
Faulty solenoid valve body
Faulty control PCB
Faulty valve coil
Faulty control PCB
Faulty valve body
Faulty low pressure sensor
Faulty subcooling heat exchanger outlet thermistor
Four-way changeover valve is located in an intermediate position
Leakage from hot gas bypass valve
Superheat caused by axis damage
Superheat caused by faulty compressor
Faulty valve coil
Faulty valve body
Faulty control PCB
Faulty gas pipe thermistor of indoor unit
Faulty liquid pipe thermistor of indoor unit
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty control PCB
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
Troubleshooting (OP: Unified ON/OFF Controller) SiEN30-602
246 Troubleshooting
∗1 : In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (Refer to page 93.)∗2 : In heating, the outside unit electronic expansion valve (Y1E) is used for “superheated degree control”. (Refer to page
71.)∗3 : Reference values for superheated degree to be used in the judgment of wet operation
1 Suction gas superheated degree: 3°C or less 2 Discharge gas superheated degree: 15°C or less, excluding when it is immediately after startup, under drop control or other specific conditions.(The values above must be used only for reference purposes. Even it is operated within the range above, operation may be normal in other conditions.)
Dwelled refrigerant
Faulty indoor unit electronic expansion valve
Faulty outside unit electronic expansion valve
Faulty crankcase heater
Faulty superheated degree control
Wet operation
[In cooling]
Degradation in evaporation capacity
[In heating]
← Does the water pump function normally?
← Is the strainer or other parts clogged?
← Is the water heat exchanger clogged?
← Is there any obstacle in the air passage?
← Is the air filter clogged?
← Can the fan motor be rotated with hands?Are the motor coil resistance and insulation normal?
← Refer to [CHECK 5]
← Are the coil resistance and insulation normal?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Are the coil resistance and insulation normal?
← Are the voltage characteristics normal?
← Is the connector properly connected?Are the thermistor resistance characteristics normal?
← Does the pressure value of the Service Checker match the reading of the pressure sensor?
← Is the heat exchanger clogged?
[CHECK 4] Check for causes of wet operation
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Excessive refrigerant charging
[In cooling]If the indoor unit electronic expansion valve excessively opened (∗1)
[In heating]If the outside unit electronic expansion valve excessively opened (∗2)
Frequent starts and stops of the compressor
Faulty control
Faulty control
Dirty evaporator
Decreased fan airflow rate
Decreased fan output
High air passage resistance
Faulty valve coil
Faulty valve body
Faulty control PCB
Faulty control PCB
Faulty fan motor
Dirty filter
Obstacle
Clogged water piping system
Faulty water pump
Dirty water heat exchanger
Decrease in water of the water heat exchanger
Faulty control PCB(including capacity setting)
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty gas pipe thermistor of indoor unit
Faulty liquid pipe thermistor of indoor unit
SiEN30-602 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 247
“ªáº
å~áº
Adequate level
(Degree of excessive charging)
Maintains a certain level of high pressure
In order to maintain high pressure, frequency decreases due to capacity control.
Heating
High pressure
Low pressure
Frequency
Cooling
Reaches the lowest frequency
Outside unit electronic expansion valve opens due to overload control
In order to maintain low pressure, frequency rises due to capacity control.
No changes within the range where the receiver is capable of absorbing.
Increase in the degree of excessive charging
High pressure drops immediately after overload control, however high pressure rises again.
Maintains a certain level of low pressure
Gradually rises as the frequency increases.
High pressure step-down control
Subcooling increases(Liquid connecting pipe temperature drops)
No changes within the range where the receiver is capable of absorbing.
Low pressure rises due to decreased compressor output
[CHECK 5] Check for excessive refrigerant charging
In case of the VRV, judgment must be made based on operation conditions in relation to pressure control and electronic expansion valve control. Refer to the following criteria to make such decisions.
Diagnosis of excessive refrigerant charging(1) Since high pressure rises, overload control is carried out and therefore capacity tends to be
insufficient.(2) Since superheated degree of suction gas decreases (or it starts wet operation), the temperature of
the compressor discharge pipe drops too much for pressure applied.(3) Since the subcooling degree of condensate liquid increases, the temperature of air blown through
subcooled part decreases in heating.
Reaches the lowest frequency
High pressure
Low pressure
Frequency
Low pressure rises due to decreased frequency
Low pressure drops because the outside unit electronic expansion valve is closed.Low pressure protection activates hot gas bypass = In fact, low pressure hunting.
Troubleshooting (OP: Unified ON/OFF Controller) SiEN30-602
248 Troubleshooting
In order to maintain low pressure, frequency decreases due to capacity control.
Reaches the lowest frequency
With low outdoor air cooling control, fan is controlled in order to maintain high pressure = Hunting in fact
When frequency reaches the lowest level, low pressure cannot be maintained.
High pressure drops as compressor capacity decreases.
In order to maintain low pressure, frequency decreases due to capacity control.
Low pressure rises due to large open degree of indoor unit electronic expansion valve. Frequency slightly increases due to capacity control.
Frequency decreases due to droop control.
The open degree of the outside unit electronic expansion valve increases.
The outside unit electronic expansion valve opens fully. Frequency increases. Discharges pipe or low
pressure droop control
Any one of electronic expansion valves opens fully.
The open degree of the indoor unit electronic expansion valve increases.
[CHECK 6] Check for inadequate refrigerant quantity
In case of the VRV, judgment must be made based on operation conditions in relation to pressure control and electronic expansion valve control. Refer to the following criteria to make such decisions.
Diagnosis of inadequate refrigerant(1) The superheated degree of suction gas increases and temperature of compressor discharge gas
rises.(2) The superheated degree of suction gas increases and the electronic expansion valve slightly
opens.(3) With low pressure, cooling capacity (heating capacity) is unavailable.
High pressure
Low pressure
Frequency
Cooling
å~áºHeating
High pressure
Low pressure
Frequency
Maintains a certain level of low pressure
Reaches the lowest frequency
Maintains a certain level of high pressure
Adequate level
(Degree of inadequate refrigerant)
Increase in the degree of inadequate refrigerant
SiEN30-602
Procedure for Mounting / Dismounting of Switch Box 249
Part 7Procedure for Mounting /
Dismounting of Switch Box
1. Procedure for Mounting / Dismounting of Switch Box.........................2501.1 Procedure for Dismounting...................................................................2501.2 Procedure for Mounting........................................................................250
Procedure for Mounting / Dismounting of Switch Box SiEN30-602
250 Procedure for Mounting / Dismounting of Switch Box
1. Procedure for Mounting / Dismounting of Switch Box
1.1 Procedure for Dismounting1. Dismount the lid from the switch box.2. Disconnect high voltage and low voltage wirings from the PC board and the terminal blocks,
referring to Figure on the right.3. Unscrew mounting screws from the top plate, the stop valve mounting plate, and the bottom
frame in a total of 6 places.4. With attention paid not to make the switch box support leg into contact with the side panel,
rotate the switch box to pull out it, while referring to Figure on the right.In order to pull out the switch box, check to be sure no wirings get stuck with the switch box.
Procedure for Mounting/Dismounting of Switch Box
1.2 Procedure for Mounting! Mount the switch box, following the procedure for dismounting in reverse.
After the completion of mounting, check to be sure connectors are all properly connected.
Side panel
Switch box support leg
List of Detachable Connectors
A1P
X7A White (WHT) Y1S
X9A Blue (BLU) Y3S
X10A Pink (PNK) Y4S
X12A Gray (GRY) Y6S
X2A Red (RED) S1PH
X17A Gray (GRY) E1HC
X13A Green (GRN) Y25
X15A Blue (BLU) Y5S
X16A Black (BLK) Y7S
U,V,W M1C
X34A Red (RED) R3T
X37A White (WHT) R2T
X37A White (WHT) R4T
X37A White (WHT) R5T
X37A White (WHT) R6T
X46A Red (RED) S1NPH
X45A Blue (BLU) S1NPL
X26A White (WHT)* Y1E
X28A Blue (BLU)* Y3E
X4M
A1P
High voltage wiring
Low voltage wiring
* Attach or detach any connector at the relay connector
SiEN30-602 Procedure for Mounting / Dismounting of Switch Box
Procedure for Mounting / Dismounting of Switch Box 251
Screw/Unscrew the mounting screws
Connect/Disconnect the wirings.
Procedure for Mounting / Dismounting of Switch Box SiEN30-602
252 Procedure for Mounting / Dismounting of Switch Box
SiEN30-602
Appendix 253
Part 8Appendix
1. Piping Diagrams..................................................................................2541.1 Outside Units........................................................................................2541.2 BS Units ...............................................................................................2551.3 Indoor Unit............................................................................................256
2. Wiring Diagrams..................................................................................2582.1 Outside Unit..........................................................................................2582.2 Outside Unit Field Wiring......................................................................2602.3 BS Unit .................................................................................................2642.4 Indoor Unit............................................................................................265
3. List of Electrical and Functional Parts .................................................2793.1 Outside Unit..........................................................................................2793.2 Indoor Side ...........................................................................................280
4. Option List ...........................................................................................2854.1 Optional Accessories............................................................................285
5. Thermistor Resistance / Temperature Characteristics........................2866. Pressure Sensor .................................................................................2887. Method of Checking The Inverter�s Power Transistors
and Diode Modules .............................................................................289
Piping Diagrams SiEN30-602
254 Appendix
1. Piping Diagrams1.1 Outside UnitsRWEYQ10MYL, TL / RWEYQ20MYL, TL / RWEYQ30MYL, TL
FilterSolenoid valve
Solenoid valve
Solenoid valve
Strainer
Solenoid valve
Filter Filter Filter
Filter
Filter
Filter
Stop valve (With service port on on-site piping side Ø7,9mm flare connection)
Solenoid valve
Check valve
Gauge port1/4” flare connection
Gauge port1/4” flare connection
High pressure sensor
High pressure switch
CompressorLow pressure sensor
Check valve
Check valve
Check valve
Fusible plug Electronic
expansion valve
Water inlet
Water outlet
Capillary tube
Capillary tubeCapillary
tube
Capillary tube
Four way valve
Four way valve
Service port
Plate heat exchanger
Pressure regulating valve
Electronic expansion valve
Heat exchanger pipe
Oil
sepa
rato
r
Sub
coo
ling
heat
exc
hang
er
SE
NP
L
Rec
eive
r
SiEN30-602 Piping Diagrams
Appendix 255
1.2 BS UnitsBSVQ36MVJUBSVQ60MVJU
4D045338
Capillary tube
Capillary tube
Check valve
Solenoid valve
Three way valveB
AFilter
Gas piping fitting port
Liquid piping fitting port
Discharge gas piping fitting port
Liquid gas piping fitting port
Liquid piping fitting port
Piping Diagrams SiEN30-602
256 Appendix
1.3 Indoor UnitFXCQ, FXFQ, FXKQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ
DU220-602J
Heat exchanger
(4)
(1)
Gas piping connection port
Liquid piping connection port
(Flare connection)
Flare connection : φ15.9 or lessAttached piping : Above φ19.1
Fan
Filter Filter
(2)
(3)
Electronic expansion valve
Code Name Code Main function
(1) Electronic expansion valve Y1EUsed for gas superheated degree control while in cooling operation or subcooled degree control while in heating operation.
(2) Suction air temperature thermistor R1T Used for thermostat control.
(3) Liquid pipe R2TUsed for gas superheated degree control while in cooling operation or subcooled degree control while in heating operation.
(4) Gas pipe R3T Used for gas superheated degree control while in cooling operation.
(mm)Capacity GAS Liquid
20 / 25 / 32 / 40 / 50M φ12.7 φ6.463 / 80 / 100 / 125M φ15.9 φ9.5
200M φ19.1 φ9.5250M φ22.2 φ9.5
SiEN30-602 Piping Diagrams
Appendix 257
FXDQ
! Refrigerant pipe connection port diameters
4D043864H
Gas side
Liquid side
Filter
Fan
Indoor heat exchanger
Filter
Electronic expansion valve
(mm)Model Gas Liquid
FXDQ20P / 25P / 32PVE(T) φ12.7 φ6.4FXDQ20NA / 25NA / 32NA / 40NA / 50NAVE(T) φ12.7 φ6.4FXDQ63NAVE(T) φ15.9 φ9.5
Wiring Diagrams SiEN30-602
258 Appendix
2. Wiring Diagrams2.1 Outside UnitRWEYQ10MYL / RWEYQ20MYL / RWEYQ30MYL
3D05
1506
A
Pow
er S
uppl
y38
0V 3
N~
60H
z
RED
WHT
BLK
BLU
RED
WHT
BLK
RED
WHT
BLK
RED
WHT
BLK
Det
ail o
f M1C
NO
TES)
WHT
WHT
RE
D
BLU
BLK
GR
N
Ope
ratio
n ou
tput
Not
e) 9
Is c
onne
ctor
col
or fo
r prin
ted
circ
uit b
oard
Is c
onne
ctor
col
or fo
r com
pone
nt.
Is d
iscr
imin
atio
n co
lor f
or c
ompo
nent
lead
wire
.
WHT
WHT
WHT Inte
rlock
Note
) 8
Note
) 5
Note
) 10
Outd
oor (
Q1) (
Q2)
Outd
oor (
F1) (
F2)
Indo
or (F
1) (F
2)
COOL
/HEA
T se
lecto
rIN
-OUT
FAN
COOL
COOL
COOL
/HEA
T se
lecto
r (op
tiona
l acc
esso
ry)
EL. C
ompo
. BOX
HEAT
HEAT
OUT-O
UTOU
T-MUL
TI
ORG
BLU
WHT
BLU
BLU
RED
1. T
his
wiri
ng d
iagr
am is
app
lied
only
to th
e ou
tsid
e un
it.2.
: F
ield
wiri
ng3.
: T
erm
inal
stri
p : C
onne
ctor
: T
erm
inal
: P
rote
ctiv
e ea
rth (s
crew
)4.
Whe
n us
ing
the
optio
n ad
apte
r, re
fer t
ot th
e in
stal
latio
n m
anua
l.5.
Ref
er to
the
inst
alla
tion
man
ual f
or c
onne
ctio
n w
iring
to in
door
-out
door
T
rans
mis
sion
F1
. F2,
out
door
-indo
or tr
ansm
issi
on F
1 . F
2, o
utdo
or-m
ulti
trans
mis
sion
Q1
. Q2
6. R
efer
to “S
ervi
ce P
reca
utio
n” la
bel (
on E
L, C
OM
PO, B
OX
CO
VER
), ho
w to
use
BS1
~BS5
and
DS1
sw
itch.
7. W
hen
oper
atin
g, d
o no
t sho
rt ci
rcui
t for
pro
tect
ion
devi
ce. (
S1PH
)8.
Be
sure
to c
onne
ct a
n in
terlo
ck c
ircui
t bet
wee
n th
e te
rmin
al (3
)-(4)
of t
erm
inal
stri
p (X
3M)
9. In
stal
l a h
eat s
ourc
e w
ater
pum
p op
erat
ion
circ
uit b
etw
een
the
term
inal
(1) -
(2) o
f ter
min
al s
trip
(X2M
), w
hen
inte
rlock
ing
a he
at
sour
ce w
ater
pum
p an
d sy
stem
ope
ratio
n.10
. Coo
l/hea
t sel
ecto
r can
not b
e co
nnec
ted
whe
n op
erat
ing
heat
reco
very
sys
tem
.11
. Col
ors:
BLK
: Bla
ck, R
ED: R
ed, B
lu: B
lue,
WH
T: W
hite
, PN
K: P
ink,
GRY
: Gra
y, O
RG
: Ora
nge
L1-R
ED
L2-W
HT
L3-B
LK
N-B
LUA1
P Pr
inte
d ci
rcui
t boa
rd (M
ain)
K1
0R
Mag
netic
rela
y (O
pera
tion
Out
put)
(A1P
) X1
A, X
3A
Con
nect
or (Y
1E, Y
3E)
A2P
Prin
ted
circ
uit b
oard
(IN
V)
K11R
M
agne
tic re
lay
(Y5S
) (A1
P)
X1M
Te
rmin
al s
trip
(Pow
er s
uppl
y)A3
P Pr
inte
d ci
rcui
t boa
rd (N
oise
filte
r) K1
2R
Mag
netic
rela
y (Y
7S) (
A1P)
X1
M
Term
inal
stri
p (c
ontro
l A1P
)BS
1 ~5
Pu
sh b
utto
n sw
itch
K13R
M
agne
tic re
lay
(E1H
C) (
A1P)
X2
M
Term
inal
stri
p (o
pera
tion
outp
ut)
(M
ode,
Set
, Ret
urn,
Tes
t, R
eset
) L1
R
Rea
ctor
X3
M
Term
inal
stri
p (In
terlo
ck)
C63
, C66
C
apac
itor
M1C
M
otor
(Com
pres
sor)
X4M
Te
rmin
al s
trip
(M1C
)D
S1
Dip
sw
itch
M1F
, M2F
M
otor
(Fan
, Inv
erte
r coo
ling)
Y1
E El
ectro
nic
expa
nsio
n va
lve
(Mai
n)E1
HC
C
rank
case
hea
ter
PS
Switc
hing
pow
er s
uppl
y Y3
E El
ectro
nic
expa
nsio
n va
lve
(Sub
Coo
l)F1
U
Fuse
(250
V, 5
A, �
) (A3
P)
Q1R
P Ph
ase
reve
rsal
det
ect c
ircui
t (A1
P)
Y1S
Sole
noid
val
ve (H
ot G
as B
ypas
s)F1
U, 2
U
Fuse
(250
V, 1
0A, �
) (A
1P)
R50
, R59
R
esis
tor
Y2S
Sole
noid
val
ve (O
il R
ecov
ery)
F3U
Fu
se (2
50V,
5A,
�)
R95
R
esis
tor (
Cur
rent
Lim
iting
) Y3
S So
leno
id v
alve
(Rec
eive
r Pre
ssur
izat
ion)
H1P
~ 8
P Pi
lotla
mp
(Ser
vice
Mon
itor-O
rang
e)(A
1P) R
1T
Ther
mis
tor (
Fin)
(A2P
) Y4
S So
leno
id v
alve
(Rec
eive
r Gas
Pur
ge)
[H
2P] P
repa
re, T
est -
------
-----
Flic
kerin
g R
2T
Ther
mis
tor (
Suct
ion)
Y5
S So
leno
id v
alve
(4 W
ay V
alve
) (M
ain)
Mal
func
tion
Det
ectio
n --
Ligh
t up
R3T
Th
erm
isto
r (M
1C D
isch
arge
) Y6
S So
leno
id v
alve
(Liq
uid
Pipe
)H
AP
Pilo
t lam
p (S
ervi
ce M
onito
r-Gre
en)(A
1P) R
4T
Ther
mis
tor (
Hex
Gas
Pip
e)
Y7S
Solen
oid va
lve (4
Way
valve
)(Hea
t Exc
hang
er)
K1M
M
agne
tic c
onta
ctor
(M1C
) (A2
P)
R5T
Th
erm
isto
r (Su
b co
olin
g he
x)
Z1C
N
oise
filte
r (Fe
rrite
cor
e)K1
R
Mag
netic
rela
y (A
2P)
R6T
Th
erm
isto
r (R
ecei
ver L
iq P
ipe)
Z1
F N
oise
filte
r (W
ith S
urge
Abs
orbe
r)K3
R
Mag
netic
rela
y (Y
1S) (
A1P)
S1
NPH
Pr
essu
re s
enso
r (H
igh)
K5R
M
agne
tic R
elay
(Y3S
) (A1
P)
S1N
PL
Pres
sure
sen
sor (
Low
)K6
R
Mag
netic
Rel
ay (Y
4S) (
A1P)
S4
PH
Pres
sure
sw
itch
(Hig
h)K7
R
Mag
netic
Rel
ay (M
4F, M
2F) (
A1P)
T1
R
Tran
sfor
mer
(220
V/20
V)
Coo
l/Hea
t Sel
ecto
rK8
R
Mag
netic
Rel
ay (Y
6s) (
A1P)
V1
CP
Safe
ty d
evic
es in
put
S1S
Sele
ctor
sw
itch
(Fan
/Coo
l . H
eat)
K9R
M
agne
tic re
lay
(Y2S
) (A1
P)
V1R
, V2R
Po
wer
mod
ule
(A2P
) S2
S Se
lect
or s
witc
h (C
ool/H
eat)
SiEN30-602 Wiring Diagrams
Appendix 259
RWEYQ10MTL / RWEYQ20MTL / RWEYQ30MTL
3D05
1505
A
POW
ER S
UPPL
Y
Detail
of M1
C
EL. C
OMPO
. BOX
Cool/
heat
selec
tor (o
pition
al ac
ceso
ry)
Cool/
heat
selec
torIn/
out
out/o
utou
t/mult
i
note
10
Cool
Cool
Heat
Heat
Fan
Indoo
r (F1)
(F2)
Outdo
or (F1
) (F2)
Outdo
or (Q
1) (Q
2)
Note
7
Is co
nnec
tor co
lor fo
r prin
ted ci
rcuit b
oard.
Is co
nnec
tor co
lor fo
r com
pone
nt.Is d
iscrim
ination
color
for c
ompo
nent
lead w
ire.
Opera
tion o
utput
note
9
Interl
ock
L1-R
ED
L2-W
HT
L3-B
LUA1
P Pr
inte
d ci
rcui
t boa
rd (M
ain)
K1
2R
Mag
netic
rela
y (Y
7S) (
A1P)
X1
M
Term
inal
stri
p (P
ower
sup
ply
A2P
Prin
ted
circ
uit b
oard
(IN
V)
K13R
M
agne
tic re
lay
(E1H
C) (
A1P)
X1
M
Term
inal
stri
p (c
ontro
l) (A
1P)
A3P
Prin
ted
circ
uit b
oard
(Noi
se fi
lter)
K84R
M
agne
tic re
lay
(Lim
iting
Res
isto
r) (A
2P)
X2M
Te
rmin
al s
trip
(ope
ratio
n ou
tput
)BS
1 ~5
Pu
sh b
utto
n sw
itch
L1R
R
eact
or
X3M
Te
rmin
al s
trip
(Inte
rlock
)
(Mod
e, S
et, R
etur
n, T
est,
Res
et)
M1C
M
otor
(Com
pres
sor)
X4M
Te
rmin
al s
trip
(M1C
)C
1 C
apac
itor
M1F
, M2F
M
otor
(Fan
, Inv
erte
r coo
ling)
Y1
E El
ectro
nic
expa
nsio
n va
lve
(Mai
n)D
S1
Dip
sw
itch
PS
Switc
hing
pow
er s
uppl
y Y3
E El
ectro
nic
expa
nsio
n va
lve
(Sub
Coo
l)E1
HC
C
rank
case
hea
ter
Q1R
P Ph
ase
reve
rsal
det
ect c
ircui
t (A1
P)
Y1S
Sole
noid
val
ve (H
ot G
as B
ypas
s)F1
U
Fuse
(250
V, 5
A, �
) (A3
P)
R1
Res
isto
r (Li
miti
ng R
esis
tor)
(A2P
) Y2
S So
leno
id v
alve
(Oil
Rec
over
y)F1
U, 2
U
Fuse
(250
V, 1
0A, �
) (A
1P)
R2
Res
isto
r (C
urre
nt S
enso
r) (A
2P)
Y3S
Sole
noid
val
ve (R
ecei
ver P
ress
uriz
atio
n)F3
U
Fuse
(250
V, 5
A, �
) R
1T
Ther
mis
tor (
Fin)
(A2P
) Y4
S So
leno
id v
alve
(Rec
eive
r Gas
Pur
ge)
H1P
~ 8
P Pi
lotla
mp
(Ser
vice
Mon
itor-O
rang
e)(A
1P) R
2T
Ther
mis
tor (
Suct
ion)
Y5
S So
leno
id v
alve
(4 W
ay V
alve
) (M
ain)
[H
2P] P
repa
re, T
est -
------
-----
Flic
kerin
g R
3T
Ther
mis
tor (
M1C
Dis
char
ge)
Y6S
Sole
noid
val
ve (L
iqui
d Pi
pe)
Mal
func
tion
Det
ectio
n --
Ligh
t up
R4T
Th
erm
isto
r (H
ex G
as P
ipe)
Y7
S So
lenoid
valve
(4 W
ay va
lve)(H
eat E
xcha
nger
)H
AP
Pilo
t lam
p (S
ervi
ce M
onito
r-Gre
en)(A
1P) R
5T
Ther
mis
tor (
Sub
cool
ing
hex)
Z1
C
Noi
se fi
lter (
Ferri
te c
ore)
K1M
M
agne
tic c
onta
ctor
(M1C
) (A2
P)
R6T
Th
erm
isto
r (R
ecei
ver L
iq P
ipe)
Z1
F N
oise
filte
r (W
ith S
urge
Abs
orbe
r)K3
R
Mag
netic
Rel
ay (Y
1S) (
A1P)
S1
NPH
Pr
essu
re s
enso
r (H
igh)
K5
R
Mag
netic
Rel
ay (Y
3S) (
A1P)
S1
NPL
Pr
essu
re s
enso
r (Lo
w)
Fi
eld
Supp
lied
Parts
(Not
e 8)
.K6
R
Mag
netic
Rel
ay (Y
4S) (
A1P)
S4
PH
Pres
sure
sw
itch
(Hig
h)
AXP
Inte
rlock
circ
uit
K7R
M
agne
tic R
elay
(M4F
, M2F
) (A1
P)
T1R
Tr
ansf
orm
er (2
20V/
20V)
Con
nect
orfo
r opt
iona
l acc
esso
ry (N
ote
4)K8
R
Mag
netic
Rel
ay (Y
6s) (
A1P)
V1
CP
Safe
ty d
evic
es in
put
X24A
C
onne
ctor
(Ada
pter
)K9
R
Mag
netic
Rel
ay (Y
2S) (
A1P)
V1
R
Pow
er m
odul
e (A
2P)
C
ool/H
eat S
elec
tor
K10R
M
agne
tic R
elay
(Ope
ratio
n O
utpu
t) (A
1P) V
2R
Dio
de b
ridge
(A2P
) S1
S Se
lect
or s
witc
h (F
an/C
ool .
Hea
t)K1
1R
Mag
netic
Rel
ay (Y
5S) (
A1P)
X1
A , X
3A
Con
nect
or (Y
1E, Y
3E)
S2S
Sele
ctor
sw
itch
(Coo
l/Hea
t)
NO
TES)
1. T
his
wiri
ng d
iagr
am is
app
lied
only
to th
e ou
tsid
e un
it.2.
: F
ield
wiri
ng3.
: T
erm
inal
stri
p : C
onne
ctor
: T
erm
inal
: P
rote
ctiv
e ea
rth (s
crew
)4.
Whe
n us
ing
the
optio
n ad
apte
r, re
fer t
ot th
e in
stal
latio
n m
anua
l.5.
Ref
er to
the
inst
alla
tion
man
ual f
or c
onne
ctio
n w
iring
to in
door
-out
door
T
rans
mis
sion
F1
. F2,
out
door
-indo
or tr
ansm
issi
on F
1 . F
2, o
utdo
or-m
ulti
trans
mis
sion
Q1
. Q2
6. R
efer
to “S
ervi
ce P
reca
utio
n” la
bel (
on E
L, C
OM
PO, B
OX
CO
VER
), ho
w to
use
BS1
~BS5
and
DS1
sw
itch.
7. W
hen
oper
atin
g, d
o no
t sho
rt ci
rcui
t for
pro
tect
ion
devi
ce. (
S1PH
)8.
Be
sure
to c
onne
ct a
n in
terlo
ck c
ircui
t bet
wee
n th
e te
rmin
al (3
)-(4)
of t
erm
inal
stri
p (X
3M)
9. In
stal
l a h
eat s
ourc
e w
ater
pum
p op
erat
ion
circ
uit b
etw
een
the
term
inal
(1) -
(2) o
f ter
min
al s
trip
(X2M
), w
hen
inte
rlock
ing
a he
at
sour
ce w
ater
pum
p an
d sy
stem
ope
ratio
n.10
. Coo
l/hea
t sel
ecto
r can
not b
e co
nnec
ted
whe
n op
erat
ing
heat
reco
very
sys
tem
.11
. Col
ors:
BLK
: Bla
ck, R
ED: R
ed, B
lu: B
lue,
WH
T: W
hite
, PN
K: P
ink,
GRY
: Gra
y, O
RG
: Ora
nge
Wiring Diagrams SiEN30-602
260 Appendix
2.2 Outside Unit Field WiringRWEYQ10MYL / RWEYQ20MYL / RWEYQ30MYL
3D04
8823
C
[Ope
ratio
n sy
stem
: Hea
t Rec
over
y]N
otes
1)
All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l co
des.
2) U
se c
oppe
r co
nduc
tors
onl
y.3)
As
for
deta
ils, s
ee w
iring
dia
gram
.4)
Inst
all c
ircui
t bre
aker
for
safe
ty.
5) A
ll fie
ld w
iring
and
com
pone
nts
mus
t be
prov
ided
by
licen
sed
elec
tric
ian.
6) U
nit s
hall
be g
roun
ded
in c
ompl
ianc
e w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
7) W
iring
sho
wn
are
gene
ral p
oint
s-of
-con
nect
ion
guid
es o
nly
and
are
not i
nten
ded
for
or to
incl
ude
all d
etai
ls fo
r a
spec
ific
inst
alla
tion.
8) B
e su
re to
inst
all t
he s
witc
h an
d th
e fu
se to
the
pow
er li
ne o
f eac
h eq
uipm
ent.
9) I
nsta
ll th
e m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner
beca
use
this
sys
tem
cin
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.10
) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lose
pha
se, m
omen
tary
bla
ckou
t or
the
pow
er
goes
on
and
off w
hile
the
prod
uct i
s op
erat
ing,
atta
ch a
rev
erse
d ph
ase
prot
ectio
n ci
rcui
t loc
ally
.R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor
and
othe
r pa
rts.
Whe
n th
e po
wer
sou
rce
is s
uppl
ied
to
each
out
side
uni
t ind
ivid
ually
<>
Whe
n th
e po
wer
sou
rce
is c
onne
cted
in
ser
ies
betw
een
the
units
.<
>O
utsi
de u
nits
Out
side
uni
ts
Pow
er s
uppl
y
Pow
er s
uppl
yP
ower
sup
ply
Pow
er s
uppl
y
Mai
n sw
itch
Mai
n sw
itch
Mai
n sw
itch
Mai
n sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Fus
eF
use
Fus
e
Fus
eF
use
Fus
e
Fus
eF
use
Fus
eF
use
Fus
eF
use
Fus
eF
use
Fus
eF
use
Fus
eF
use
Fus
e
Fus
e
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
eB
S u
nits
Indo
or u
nits
Coo
ling
only
uni
tC
oolin
g on
ly u
nit
BS
uni
ts
Indo
or u
nits
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
][U
NIT
1]
[UN
IT 2
][U
NIT
3]
SiEN30-602 Wiring Diagrams
Appendix 261
RWEYQ10MYL / RWEYQ20MYL / RWEYQ30MYL
3D04
8824
C
[Ope
ratio
n sy
stem
: Hea
t Pum
p]N
otes
1)
All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l co
des.
2) U
se c
oppe
r co
nduc
tors
onl
y.3)
As
for
deta
ils, s
ee w
iring
dia
gram
.4)
Inst
all c
ircui
t bre
aker
for
safe
ty.
5) A
ll fie
ld w
iring
and
com
pone
nts
mus
t be
prov
ided
by
licen
sed
elec
tric
ian.
6) U
nit s
hall
be g
roun
ded
in c
ompl
ianc
e w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
7) W
iring
sho
wn
are
gene
ral p
oint
s-of
-con
nect
ion
guid
es o
nly
and
are
not i
nten
ded
for
or to
incl
ude
all d
etai
ls fo
r a
spec
ific
inst
alla
tion.
8) B
e su
re to
inst
all t
he s
witc
h an
d th
e fu
se to
the
pow
er li
ne o
f eac
h eq
uipm
ent.
9) I
nsta
ll th
e m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner
beca
use
this
sys
tem
cin
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.10
) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lose
pha
se, m
omen
tary
bla
ckou
t or
the
pow
er
goes
on
and
off w
hile
the
prod
uct i
s op
erat
ing,
atta
ch a
rev
erse
d ph
ase
prot
ectio
n ci
rcui
t loc
ally
.R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor
and
othe
r pa
rts.
Whe
n th
e po
wer
sou
rce
is s
uppl
ied
to
each
out
side
uni
t ind
ivid
ually
<>
Whe
n th
e po
wer
sou
rce
is c
onne
cted
in
ser
ies
betw
een
the
units
.<
>O
utsi
de u
nits
Pow
er s
uppl
y
Pow
er s
uppl
y
Mai
n sw
itch
Pow
er s
uppl
y
Mai
n sw
itch
Mai
n sw
itch
Pow
er s
uppl
y
Mai
n sw
itch
Sw
itch
Sw
itch
Sw
itch
Fus
e
Sw
itch
Fus
eF
use
Fus
e
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
]
Out
side
uni
ts
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
]
Indo
or u
nits
Indo
or u
nits
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Fus
eF
use
Fus
eF
use
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
Wiring Diagrams SiEN30-602
262 Appendix
RWEYQ10MTL / RWEYQ20MTL / RWEYQ30MTL
3D05
2074
[Ope
ratio
n sy
stem
: Hea
t Rec
over
y]N
otes
1)
All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l co
des.
2) U
se c
oppe
r co
nduc
tors
onl
y.3)
As
for
deta
ils, s
ee w
iring
dia
gram
.4)
Ins
tall
circ
uit b
reak
er fo
r sa
fety
.5)
All
field
wiri
ng a
nd c
ompo
nent
s m
ust b
e pr
ovid
ed b
y lic
ense
d el
ectr
icia
n.
6) U
nit s
hall
be g
roun
ded
in c
ompl
ianc
e w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
7) W
iring
sho
wn
are
gene
ral p
oint
s-of
-con
nect
ion
guid
es o
nly
and
are
not i
nten
ded
for
or to
incl
ude
all d
etai
ls fo
r a
spec
ific
inst
alla
tion.
8) B
e su
re to
inst
all t
he s
witc
h an
d th
e fu
se to
the
pow
er li
ne o
f eac
h eq
uipm
ent.
9) I
nsta
ll th
e m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner
beca
use
this
sys
tem
cin
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.10
) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lose
pha
se, m
omen
tary
bla
ckou
t or
the
pow
er
goes
on
and
off w
hile
the
prod
uct i
s op
erat
ing,
atta
ch a
rev
erse
d ph
ase
prot
ectio
n ci
rcui
t loc
ally
.R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor
and
othe
r pa
rts.
Whe
n th
e po
wer
sou
rce
is s
uppl
ied
to
each
out
side
uni
t ind
ivid
ually
<>
Whe
n th
e po
wer
sou
rce
is c
onne
cted
in
ser
ies
betw
een
the
units
.<
>O
utsi
de u
nits
Pow
er s
uppl
y
Mai
n sw
itch
Pow
er s
uppl
y
Mai
n sw
itchSw
itch
Sw
itch
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Fus
eF
use
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
]
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
BS
uni
ts
Indo
or u
nits
Coo
ling
only
uni
t
Out
side
uni
ts
Pow
er s
uppl
yPow
er s
uppl
y
Mai
n sw
itch
Mai
n sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Fus
eF
use
Fus
eF
use
Fus
e
Fus
eF
use
Fus
e
Fus
e
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line) Coo
ling
only
uni
t
BS
uni
ts
Indo
or u
nits
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
]
SiEN30-602 Wiring Diagrams
Appendix 263
RWEYQ10MTL / RWEYQ20MTL / RWEYQ30MTL
3D05
2075
[Ope
ratio
n sy
stem
: Hea
t Pum
p]N
otes
1)
All
wiri
ng, c
ompo
nent
s an
d m
ater
ials
to b
e pr
ocur
ed o
n th
e si
te m
ust c
ompl
y w
ith th
e ap
plic
able
loca
l and
nat
iona
l co
des.
2) U
se c
oppe
r co
nduc
tors
onl
y.3)
As
for
deta
ils, s
ee w
iring
dia
gram
.4)
Ins
tall
circ
uit b
reak
er fo
r sa
fety
.5)
All
field
wiri
ng a
nd c
ompo
nent
s m
ust b
e pr
ovid
ed b
y lic
ense
d el
ectr
icia
n.
6) U
nit s
hall
be g
roun
ded
in c
ompl
ianc
e w
ith th
e ap
plic
able
loca
l and
nat
iona
l cod
es.
7) W
iring
sho
wn
are
gene
ral p
oint
s-of
-con
nect
ion
guid
es o
nly
and
are
not i
nten
ded
for
or to
incl
ude
all d
etai
ls fo
r a
spec
ific
inst
alla
tion.
8) B
e su
re to
inst
all t
he s
witc
h an
d th
e fu
se to
the
pow
er li
ne o
f eac
h eq
uipm
ent.
9) I
nsta
ll th
e m
ain
switc
h th
at c
an in
terr
upt a
ll th
e po
wer
sou
rces
in a
n in
tegr
ated
man
ner
beca
use
this
sys
tem
cin
sist
s of
the
equi
pmen
t util
izin
g th
e m
ultip
le p
ower
sou
rces
.10
) If
ther
e ex
ists
the
poss
ibili
ty o
f rev
erse
d ph
ase,
lose
pha
se, m
omen
tary
bla
ckou
t or
the
pow
er
goes
on
and
off w
hile
the
prod
uct i
s op
erat
ing,
atta
ch a
rev
erse
d ph
ase
prot
ectio
n ci
rcui
t loc
ally
.R
unni
ng th
e pr
oduc
t in
reve
rsed
pha
se m
ay b
reak
the
com
pres
sor
and
othe
r pa
rts.
Whe
n th
e po
wer
sou
rce
is s
uppl
ied
to
each
out
side
uni
t ind
ivid
ually
<>
Whe
n th
e po
wer
sou
rce
is c
onne
cted
in
ser
ies
betw
een
the
units
.<
>O
utsi
de u
nits
Out
side
uni
ts
Pow
er s
uppl
y
Pow
er s
uppl
y
Mai
n sw
itch
Pow
er s
uppl
y
Mai
n sw
itch
Mai
n sw
itch
Pow
er s
uppl
y
Mai
n sw
itch
Sw
itch
Sw
itch
Sw
itch
Fus
e
Sw
itch
Fus
eF
use
Fus
e
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
2 W
ires
cabl
e(T
rans
mis
sion
line
)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
]
2 W
ires
cabl
e(T
rans
mis
sion
line
)2
Wire
s ca
ble
(Tra
nsm
issi
on li
ne)
[UN
IT 1
][U
NIT
2]
[UN
IT 3
]
Indo
or u
nits
Indo
or u
nits
Sw
itch
Sw
itch
Sw
itch
Sw
itch
Fus
eF
use
Fus
eF
use
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
Sw
itch
Fus
e
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
2 W
ires
cabl
e(P
ower
line)
Wiring Diagrams SiEN30-602
264 Appendix
2.3 BS UnitBSVQ36MVJUBSVQ60MVJU
PR
INT
ED
CIR
CU
IT B
OA
RD
FU
SE
(
, 2
50V,
A)
LIG
HT
EM
ITT
ING
DIO
DE
(SE
RV
ICE
MO
NIT
OR
-GR
EE
N)
MA
GN
ET
IC R
ELA
YS
ELE
CT
RO
SW
ITC
H(S
ELEC
TION
OF
REM
OTE
CONT
ROLL
ER)
TRA
NS
FOR
ME
R (2
08-2
30V
/23V
)
TE
RM
INA
L S
TR
IP (P
OW
ER
)T
ER
MIN
AL
ST
RIP
(PO
WE
R)
TER
MIN
AL S
TRIP
(C/H
SEL
ECTO
R)
SO
LEN
OID
VA
LVE
(LIQ
UID
LIN
E)
4WAY
VA
LVE
(DIS
CH
AR
GE
LIN
E)
NO
ISE
FIL
TE
R (F
ER
ITE
CO
RE
)C
ON
NE
CT
R F
OR
OP
TIO
NA
L PA
RT
S
L1: R
ED
L1: B
LUE
TE
RM
INA
L,F
IELD
WIR
ING
WH
EN
US
ING
TH
E C
OO
L/H
EAT
SE
LEC
TOR
(OP
TIO
NA
L A
CC
ES
-S
OR
Y),
CO
NN
EC
T IT
TO
TE
RM
INA
LS A
, B A
ND
C O
N X
3M (A
1P).
IN T
HIS
CA
SE
, SE
T T
HE
SE
LEC
TOR
SW
ITC
H S
S1&
SS
2 O
N T
HE
A1P
A
CC
OR
DIN
G T
O B
ELO
W D
RA
WIN
G.
AS
FO
R W
IRIN
G T
O T
HE
IN/D
F1&
F2
AN
D O
UT
/D, B
S F
1&F
2 O
N X
2M, R
EF
ER
TO
INS
TALL
ATIO
N M
AN
UA
L.
BLU
:BLU
E O
RG
:OR
AN
GE
PN
K:P
INK
RE
D:R
ED
W
HT:
WH
ITE
YLW
:YE
LLO
W B
LK:B
LAC
K
TH
IS W
IRIN
G D
IAG
RA
M A
PP
LIE
S T
O T
HE
BS
UN
IT O
NLY
.S
YM
BO
LS S
HO
W A
S F
OLL
OW
S.
US
E C
OP
PE
R C
ON
DU
CTO
RS
ON
LY.
PO
WE
R S
UP
PLY
NO
TE
S:
BS
UN
IT T
OP
NO
TE
3
OUTDOOR UNIT
INDOOR UNIT
CO
NN
EC
TOR
,W
IRE
CLA
MP
CONN
ECTO
R (W
IRIN
G EX
TERN
AL C
ONTR
OL
ADAP
TOR
FOR
OUTD
OOR
UNIT)
ELE
CT
RIC
CO
MP
ON
EN
TS
BO
X
TRAN
SMIS
SION
WIR
ING
TO TH
E IN
DOOR
UNI
T
TRAN
SMIS
SION
WIR
ING
TO TH
E OU
TDOO
R UN
IT
OR O
THER
BS
UNIT
SiEN30-602 Wiring Diagrams
Appendix 265
2.4 Indoor UnitFXCQ20M / 25M / 32M / 63MVE
3D03
9556
A
NO
TE
S:
CONN
ECTO
R,CO
NNEC
TOR,
SYM
BOLS
SHO
WS
AS F
OLL
OW
S.
USE
COPP
ER C
OND
UCTO
RS O
NLY.
PO
WE
R S
UP
PLY
NO
TE-4
ELEC
TRIC
PAR
TS B
OX
WIR
ED R
EMO
TE C
ON
TRO
LLER
(OPT
ION
AL A
CC
ESSO
RY)
NO
TE-5
INP
UT
FRO
M O
UTS
IDE
NO
TE-3
TRA
NS
MIS
SIO
N W
IRIN
G
CE
NTR
AL
RE
MO
TE C
ON
TRO
L
NO
TE-4
REC
EIVE
R/D
ISPL
AY U
NIT
(WIR
ELES
S R
EMO
TE C
ON
TRO
LLER
)
PNK:
PINK
WHT
:WHI
TE Y
LW:Y
ELLO
W O
RG:O
RANG
EBL
U:BL
UE B
LK:B
LACK
RED
:RED
BRN
:BRO
WN
GRN
:GRE
EN
FIEL
D W
IRIN
G,
TERM
INAL
BLO
CK,
PRIN
TED
CIRC
UIT
BOAR
DCA
PACI
TOR
(M1F
)FU
SE (
� , 2
50V,
A)LIG
HT E
MITT
ING
DIOD
E(S
ERVI
CE M
ONITO
R-GR
EEN)
MAGN
ETIC
REL
AY (M
1F)
MAGN
ETIC
REL
AY (M
1S)
MAGN
ETIC
REL
AY (M
1P)
MOTO
R (IN
DOOR
FAN)
MOTO
R (D
RAIN
PUM
P)MO
TOR
(SW
ING
FLAP
)
INDO
OR U
NIT
WIR
ED R
EMOT
E CO
NTRO
LLER
THER
MIS
TOR
(AIR
)SE
LECT
OR
SWIT
CH
(MAI
N/SU
B)
THER
MO S
WIT
CH(M
1F E
MBED
DED)
THER
MIST
OR (A
IR)
THER
MIST
OR (C
OIL)
FLOA
T SW
ITCH
LIMIT
SW
ITCH
(SW
ING
FLAP
)TR
ANSF
ORME
R (22
0-240
V/22
V)TE
RMIN
AL B
LOCK
(POW
ER)
TERM
INAL
BLO
CK (C
ONTR
OL)
ELEC
TRON
ICEX
PANS
ION
VALV
E
RECE
IVER
/DIS
PLAY
UNI
T(A
TTAC
HED
TO W
IREL
ESS
REM
OTE
CONT
ROLL
ER)
CONN
ECTO
R FO
R OP
TION
AL PA
RTS
PRIN
TED
CIRC
UIT
BOAR
DPR
INTE
D CI
RCUI
T BO
ARD
PUSH
BUT
TON
(ON/
OFF)
LIGH
T EM
ITTI
NG D
IODE
(ON-
RED)
LIGH
T EM
ITTI
NG D
IODE
(TIM
ER-G
REEN
)
LIGH
T EM
ITTI
NG D
IODE
(F
ILTER
SIG
N-RE
D)LI
GHT
EMIT
TING
DIO
DE(D
EFRO
ST-O
RANG
E)SE
LECT
OR S
WIT
CH(M
AIN/
SUB)
SELE
CTOR
SW
ITCH
(WIR
ELES
S AD
DRES
S SE
T)
CONN
ECTO
R(W
IRIN
G AD
APTO
R FO
R EL
ECTR
ONIC
AL A
PPEN
DICE
S)CO
NNEC
TOR
(WIR
ELES
S RE
MOTE
CO
NTRO
LLER
)
IN C
ASE
USIN
G C
ENTR
AL R
EMOT
E CO
NTRO
LLER
, CO
NNEC
T IT
TO
THE
UN
IT IN
ACC
ORD
ANCE
WIT
H TH
E AT
TACH
ED IN
STRU
CTIO
N M
ANUA
L.
WHE
N CO
NNEC
TING
THE
INPU
T W
IRES
FRO
M O
UTSI
DE, F
ORC
ED O
FF O
N/O
FF C
ONT
ROL
OPE
RATI
ON
CAN
BE S
ELEC
TED
BY R
EMOT
E CO
NTRO
LLER
.IN
DET
AILS
, REF
ER T
O T
HE IN
STAL
LATI
ON
MAN
UAL
ATTA
CHED
THE
UNI
T.
X23A
IS C
ONN
ECTE
D W
HEN
THE
WIR
ELES
S RE
MOT
E CO
NTRO
LLER
KIT
IS B
EING
USE
D.
Wiring Diagrams SiEN30-602
266 Appendix
FXCQ40M / 50M / 80M/ 125MVE
3D03
9557
A
NO
TE
S:
PO
WE
R S
UP
PLY
NO
TE-4
NO
TE-5
INP
UT
FRO
M O
UTS
IDE
ELE
CTR
IC P
AR
TS B
OX
NO
TE-3
TRA
NS
MIS
SIO
N W
IRIN
GC
EN
TRA
L R
EM
OTE
CO
NTR
OLL
ER
NO
TE-4
RE
CE
IVE
R/D
ISP
LAY
UN
IT(W
IRE
LES
S R
EM
OTE
CO
NTR
OLL
ER
)
WIR
ED R
EMO
TE C
ONT
ROLL
ER(O
PTIO
NAL
ACCE
SSO
RY)
Term
inal
blo
ck,
Fie
ld w
iring
Con
nect
or,
Term
inal
PRIN
TED
CIRC
UIT
BOAR
DCA
PACI
TOR
(M1F
)FU
SE (
� , 5
A, 25
0V)
LIGHT
EMI
TTIN
G DI
ODE
(SER
VICE
MON
ITOR-
GREE
N)MA
GNET
IC R
ELAY
(M1F
)MA
GNET
IC R
ELAY
(M1S
)MA
GNET
IC R
ELAY
(M1P
)MO
TOR
(INDO
OR FA
N)MO
TOR
(DRA
IN P
UMP)
MOTO
R (S
WIN
G FL
AP)
THER
MO S
WIT
CH(M
1F E
MBED
DED)
THER
MIST
OR(A
IR)
THER
MIST
OR(C
OIL)
INDO
OR U
NIT
FLOA
T SW
ITCH
LIMIT
SWITC
H(S
WIN
G FL
AP)
TRAN
SFOR
MER
(220-2
40V/
22V)
TERM
INAL
BLO
CK (P
OWER
)TE
RMIN
AL B
LOCK
(CON
TROL
)EL
ECTR
ONIC
EXPA
NSIO
N VA
LVE
LIGHT
EMI
TTIN
G DI
ODE
(ON-
RED)
LIGHT
EMI
TTIN
G DI
ODE
(TIM
ER-G
REEN
)LIG
HT E
MITT
ING
DIOD
E(F
ILTER
SIG
N-RE
D)LIG
HT E
MITT
ING
DIOD
E(D
EFRO
ST-O
RANG
E)SE
LECT
OR S
WITC
H(M
AIN/
SUB)
SELE
CTOR
SW
ITCH
(WIR
ELES
S AD
RESS
SET
)
CONN
ECTO
R(W
IRIN
G AD
APTO
R FO
R EL
ECTR
ONIC
AL A
PPEN
DICE
S)CO
NNEC
TOR
(WIR
ELES
S RE
MOTE
CO
NTRO
LLER
)
THER
MIST
OR (A
IR)
SELE
CTOR
SW
ITCH
(MAI
N/SU
B)
PRIN
TED
CIRC
UIT B
OARD
PRIN
TED
CIRC
UIT B
OARD
PUSH
BUT
TON
(ON/
OFF)
CONN
ECTO
R FO
R OP
TION
AL PA
RTS
RECE
IVER
/DIS
PLAY
UNI
T(AT
TACH
ED TO
WIR
ELES
S RE
MOT
E CO
NTRO
LLER
)
WIR
ED R
EMOT
E CO
NTRO
LLER
In c
ase
usin
g ce
ntra
l rem
ote
cont
rolle
r, co
nnec
t it to
the
unit i
n ac
cord
ance
with
the
atta
ched
inst
ruct
ion
man
ual.
X23A
is c
onne
cted
whe
n th
e wi
rele
ss re
mot
e co
ntro
ller k
it is
bein
g us
ed.
Whe
n co
nnec
ting
the
inpu
t wire
s fro
m o
utsid
e, fo
rced
off
or o
n/of
f con
trol o
pera
tion
can
be s
elec
ted
by re
mot
e co
ntro
ller.
In d
etai
ls, re
fer t
o th
e in
stal
latio
n m
anua
l atta
ched
the
unit.
Sym
bols
show
s as
follo
ws.
Use
copp
er c
ondu
ctor
s on
ly.
PNK:
Pink
WHT
:Whi
te Y
LW:Y
ello
w O
RG:O
rang
e BL
U:Bl
ue B
LK: B
lack
RED
:Red
BRN
:Bro
wn G
RN:G
reen
SiEN30-602 Wiring Diagrams
Appendix 267
FXFQ25M / 32M / 40M / 50M / 63M / 80M / 100M / 125MVE
3D03
9600
A
IND
OO
R U
NIT
PRIN
TED
CIRC
UIT
BOAR
D
(POW
ER S
UPPL
Y)
PRIN
TED
CIRC
UIT
BOAR
D
(CON
TROL
)
PRIN
TED
CIRC
UIT
BOAR
D
(TEM
PERA
TURE
SEN
SOR
UNIT
)
FUSE
(�, 5
A, 2
50V)
LIGH
T EM
ITTI
NG D
IODE
(SER
VICE
MON
ITOR
GRE
EN)
MAG
NETI
C RE
LAY
(M1P
)
MOT
OR (I
NDOO
R FA
N)
MOT
OR (D
RAIN
PUM
P)
MOT
OR (S
WIN
G FL
AP)
THER
MIS
TOR
(AIR
)
THER
MIS
TOR
(COI
L LI
QUID
)
THER
MIS
TOR
(COI
L GA
S)
FLOA
T SW
ITCH
TERM
INAL
BLO
CK
TERM
INAL
BLO
CK
ELEC
TRON
IC E
XPAN
SION
VALB
E
NOIS
E FI
LTER
POW
ER C
IRCU
IT
PRIN
TED
CIRC
UIT
BOAR
D
PRIN
TED
CIRC
UIT
BOAR
D
PUSH
BUT
TON
(ON/
OFF)
LIGH
T EM
ITTI
NG D
IODE
(ON-
RED)
LIGH
T EM
ITTI
NG D
IODE
(TIM
ER-G
REEN
)
LIGH
T EM
ITTI
NG D
IODE
(FILT
ER S
IGN-
RED)
LIGH
T EM
ITTI
NG D
IODE
(DEF
ROST
-ORA
NGE)
SELE
CTOR
SW
ITCH
(MAI
N/SU
B)
SELE
CTOR
SW
ITCH
(WIR
ELES
S AD
DRES
S SE
T)
CONN
ECTO
R
(WIR
ELES
S RE
MOTE
CON
TROL
LER)
CONN
ECTO
R
(ADA
PTOR
FOR
WIR
ING)
CONN
ECTO
R (G
ROUP
CON
TROL
ADAP
TOR)
THER
MIST
OR (A
IR)
SELE
CTOR
SW
ITCH
(MAI
N/SU
B)
RECE
IVER
/DIS
PLAY
UNI
T (A
TTAC
HED
TO W
IREL
ESS
REM
OTE
CONT
ROLL
ER)
CONN
ECTO
R FO
R OP
TION
AL PA
RTS
WIR
ED R
EMOT
E CO
NTRO
LLER
NOTE
S:
POW
ER S
UPPL
Y
SWIT
CH B
OX(IN
DOOR
UNI
T)
TRAN
SMIS
SION
WIR
ING
CENT
RAL
REM
OTE
CONT
ROLL
ER
RECE
IVER
/DIS
PLAY
UNI
T(W
IREL
ESS
REM
OTE
CONT
ROLL
ER)
INPU
T FR
OM O
UTSI
DE NOTE
2
NOTE
4
NOTE
3
Term
inal
blo
ckC
onne
ctor
Fie
ld w
iring
In c
ase
usin
g ce
ntra
l rem
ote
cont
rolle
r, co
nnec
t it t
o th
e un
it in
acc
orda
nce
with
the
atta
ched
inst
alla
tion
man
ual.
X24
A is
con
nect
ed w
hen
the
wire
less
rem
ote
cont
rolle
r ki
t is
bein
g us
ed.
Whe
n co
nnec
ting
the
inpu
t wire
s fr
om o
utsi
de, f
orce
d of
f or
on/
off c
ontr
ol o
pera
tion
can
be s
elec
ted
by r
emot
e co
ntro
ller.
In d
etai
ls, r
efer
to th
e in
stal
latio
n m
anua
l at
ache
d th
e un
it.
Rem
ote
cont
rolle
r m
odel
var
ies
acco
rdin
g to
the
com
bina
tion
syst
em, c
onfir
m e
ngin
eerin
g da
ta a
nd
cata
logs
, etc
, bef
ore
conn
ectin
g.C
onfir
m th
e m
etho
d of
set
ting
the
sele
ctor
sw
itch
(SS
1, S
S2)
of
wire
d re
mot
e co
ntro
ller
and
wire
less
rem
ote
cont
rolle
r by
in
stal
latio
n m
anua
l and
eng
inee
ring
data
, etc
.
Sym
bols
sho
ws
as fo
llow
s:R
ED
:Red
BLK
: Bla
ck W
HT
:Whi
te Y
LW:Y
ello
w G
RN
:Gre
enO
RG
:Ora
nge
BR
N:B
row
n P
NK
:Pin
k G
RY
:Gra
y B
LU:B
lue
Wiring Diagrams SiEN30-602
268 Appendix
FXKQ25MA / 32MA / 40MA / 63MAVE
Pow
er s
uppl
yE
lect
ric p
arts
box
Not
e 4
Inpu
t fro
m o
utsi
deN
ote
3Tr
ansm
issi
on w
iring
Not
e 5
Not
es
Cen
tral
rem
ote
cont
rol
wire
d re
mot
e co
ntro
l(O
ptio
nal A
cces
sory
)
1.
Term
inal
blo
ck,
Con
nect
or,
Term
inal
2.
Fie
ld w
iring
3. I
n ca
se u
sing
cen
tral
rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith
the
atta
ched
inst
ruct
ion
man
ual.
4. W
hen
conn
ectin
g th
e in
put w
ires
from
out
side
, fro
ced
OF
F o
r O
N/O
FF
con
trol
op
erat
ion
can
be s
elec
ted
by r
emot
e co
ntro
l.In
det
ails
, ref
er to
the
inst
alla
tion
man
ual a
ttach
ed th
e un
it.5.
In
case
hig
h E
.S.P
. ope
ratio
n, c
hang
e ov
er th
e w
iring
con
nect
ion
from
X2A
to X
3A.
6. S
ymbo
ls s
how
as
follo
ws.
(P
NK
: Pin
k, W
HT:
Whi
te, Y
LW: Y
ello
w, O
RG
: Ora
nge,
B
LU: B
lue,
BLK
: Bla
ck, R
ED
: RE
D, B
RN
: Bro
wn,
GR
Y: G
ray)
7. U
se c
oppe
r co
nduc
tors
onl
y.
Indo
or u
nit
Prin
ted
circ
uit b
oard
Term
inal
boa
rd
Cap
acito
r (M
1F)
Fus
e (
� ,
5A, 2
50V
)
Ligh
t em
ittin
g di
ode
(Ser
vice
Mon
itor-
Gre
en)
Mag
netic
rel
ay (
M1F
)
Mag
netic
rel
ay (
M1S
)
Mag
netic
rel
ay (
M1P
)
Mot
or (
Indo
or F
an)
Mot
or (
Dra
in P
ump)
Mot
or (
Sw
ing
Fla
p)
The
rmo
Sw
itch
(M1F
Em
bedd
ed)
The
rmis
tor
(Air)
The
rmis
tor
(Coi
l)
Flo
at s
witc
h
Lim
it sw
itch
(Sw
ing
Flap
)
Tran
sform
er (2
20-2
40V/
22V)
Term
inal
blo
ck (P
ower
)
Term
inal
blo
ck (C
ontro
l)
Ele
ctro
nic
expa
nsio
n
valv
e
Wire
d R
emot
e C
ontr
ol
The
rmis
tor
(Air)
Sele
ctor
Swi
tch
(Mai
n/Su
b)
Con
nect
or F
or O
ptio
nal P
arts
Conn
ector
(Ada
pter F
or W
iring)
Conn
ecto
r (W
iring
Ada
pter
)
For E
lect
orica
l App
endi
ces)
3D03
9564
C
SiEN30-602 Wiring Diagrams
Appendix 269
FXDQ20P / 25P / 32PVE (with Drain Pump)
3D04
5500
C
TE
RM
INA
L
FIE
LD W
IRIN
G
NO
TE
S:
Con
trol B
ox
Pow
er
supp
ly
Prin
ted
circ
uit b
oard
Cap
acito
r (M
1F)
Fus
e (F
5A/2
50V
)Li
ght e
mitt
ing
diod
e(S
ervi
ce M
onito
r Gre
en)
Mag
netic
rela
y (M
1P)
Mot
or (I
ndoo
r Fan
)M
otor
(Dra
in P
ump)
Ther
mal
pro
tect
or (M
1F E
mbe
dded
)T
herm
isto
r (A
ir)T
herm
isto
r (C
oil-1
)T
herm
isto
r (C
oil-2
)F
loat
sw
itch
Tran
sfor
mer
(220
V/2
2V)
Pha
se c
ontro
l circ
uit
Term
inal
blo
ckTe
rmin
al b
lock
Ele
ctro
nic
expa
nsio
n va
lve
Noi
se fi
lter (
Ferr
ite C
ore)
Wire
d R
emot
e C
ontro
lT
herm
isto
r (A
ir)S
elec
tor S
witc
h (M
ain/
Sub
)C
onne
ctor
For
Opt
iona
l Par
tsC
onne
ctor
(Ada
ptor
For
Wiri
ng)
Con
nect
or (W
iring
Ada
ptor
Fo
r Ele
ctric
al A
pend
ices
)
Not
e 5
Inpu
t fro
m
outs
ide
trans
mis
sion
w
iring
cen
tral
rem
ote
cont
rol
Not
e 3
Wire
d re
mot
e co
ntro
l
CO
NN
EC
TOR
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith th
e at
tach
ed in
stal
latio
n m
anua
l.R
emot
e co
ntro
l mod
el v
arie
s ac
cord
ing
to th
e co
mbi
natio
n sy
stem
, con
firm
eni
neer
ing
mat
eria
ls a
nd c
atal
ogs,
etc
. bef
ore
conn
ectin
g.W
hen
conn
ectin
g th
e in
put w
ires
from
out
side
, for
ced
OF
F o
r ON
/OF
F c
ontro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
cont
rol.
In d
etai
ls, r
efer
to th
e in
stal
latio
n m
anua
l atta
ched
the
unit.
Sym
bols
sho
w a
s fo
llow
s:
Red
: Red
B
LK: B
lack
W
HT:
Whi
te
YLW
: Yel
low
P
RP
: Pur
ple
GR
Y: G
ray
Blu
: Blu
e P
NK
: Pin
k O
rg: O
rang
e G
RN
: Gre
en
Wiring Diagrams SiEN30-602
270 Appendix
FXDQ20P / 25P / 32PVET (without Drain Pump)
3D04
9604
A
TE
RM
INA
L
FIE
LD W
IRIN
G
NO
TE
S:
Con
trol B
ox
Pow
er
supp
ly
Prin
ted
circ
uit b
oard
Cap
acito
r (M
1F)
Fus
e (F
5A/2
50V
)Li
ght e
mitt
ing
diod
e(S
ervi
ce M
onito
r Gre
en)
Mot
or (I
ndoo
r Fan
)Th
erm
al p
rote
ctor
(M1F
Em
bedd
ed)
The
rmis
tor (
Air)
The
rmis
tor (
Coi
l-1)
The
rmis
tor (
Coi
l-2)
Tran
sfor
mer
(220
V/2
2V)
Pha
se c
ontro
l circ
uit
Term
inal
blo
ckTe
rmin
al b
lock
Ele
ctro
nic
expa
nsio
n va
lve
Noi
se fi
lter (
Ferr
ite C
ore)
Wire
d R
emot
e C
ontro
lT
herm
isto
r (A
ir)S
elec
tor S
witc
h (M
ain/
Sub
)C
onne
ctor
For
Opt
iona
l Par
tsC
onne
ctor
(Ada
ptor
For
Wiri
ng)
Con
nect
or (W
iring
Ada
ptor
Fo
r Ele
ctric
al A
pend
ices
)
Not
e 5
Inpu
t fro
m
outs
ide
trans
mis
sion
w
iring
cen
tral
rem
ote
cont
rol
Not
e 3
Wire
d re
mot
e co
ntro
l
CO
NN
EC
TOR
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith th
e at
tach
ed in
stal
latio
n m
anua
l.R
emot
e co
ntro
l mod
el v
arie
s ac
cord
ing
to th
e co
mbi
natio
n sy
stem
, con
firm
eni
neer
ing
mat
eria
ls a
nd c
atal
ogs,
etc
. bef
ore
conn
ectin
g.W
hen
conn
ectin
g th
e in
put w
ires
from
out
side
, for
ced
OF
F o
r ON
/OF
F c
ontro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
cont
rol.
In d
etai
ls, r
efer
to th
e in
stal
latio
n m
anua
l atta
ched
the
unit.
Sym
bols
sho
w a
s fo
llow
s:
Red
: Red
B
LK: B
lack
W
HT:
Whi
te
YLW
: Yel
low
P
RP
: Pur
ple
GR
Y: G
ray
Blu
: Blu
e P
NK
: Pin
k O
rg: O
rang
e G
RN
: Gre
en
SiEN30-602 Wiring Diagrams
Appendix 271
FXDQ20NA / 25NA / 32NA / 40NA / 50NA / 63NAVE (with Drain Pump)
3D04
5500
C
TE
RM
INA
L
FIE
LD W
IRIN
G
NO
TE
S:
Con
trol B
ox
Pow
er
supp
ly
Prin
ted
circ
uit b
oard
Cap
acito
r (M
1F)
Fus
e (F
5A/2
50V
)Li
ght e
mitt
ing
diod
e(S
ervi
ce M
onito
r Gre
en)
Mag
netic
rela
y (M
1P)
Mot
or (I
ndoo
r Fan
)M
otor
(Dra
in P
ump)
Ther
mal
pro
tect
or (M
1F E
mbe
dded
)T
herm
isto
r (A
ir)T
herm
isto
r (C
oil-1
)T
herm
isto
r (C
oil-2
)F
loat
sw
itch
Tran
sfor
mer
(220
V/2
2V)
Pha
se c
ontro
l circ
uit
Term
inal
blo
ckTe
rmin
al b
lock
Ele
ctro
nic
expa
nsio
n va
lve
Noi
se fi
lter (
Ferr
ite C
ore)
Wire
d R
emot
e C
ontro
lT
herm
isto
r (A
ir)S
elec
tor S
witc
h (M
ain/
Sub
)C
onne
ctor
For
Opt
iona
l Par
tsC
onne
ctor
(Ada
ptor
For
Wiri
ng)
Con
nect
or (W
iring
Ada
ptor
Fo
r Ele
ctric
al A
pend
ices
)
Not
e 5
Inpu
t fro
m
outs
ide
trans
mis
sion
w
iring
cen
tral
rem
ote
cont
rol
Not
e 3
Wire
d re
mot
e co
ntro
l
CO
NN
EC
TOR
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith th
e at
tach
ed in
stal
latio
n m
anua
l.R
emot
e co
ntro
l mod
el v
arie
s ac
cord
ing
to th
e co
mbi
natio
n sy
stem
, con
firm
eni
neer
ing
mat
eria
ls a
nd c
atal
ogs,
etc
. bef
ore
conn
ectin
g.W
hen
conn
ectin
g th
e in
put w
ires
from
out
side
, for
ced
OF
F o
r ON
/OF
F c
ontro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
cont
rol.
In d
etai
ls, r
efer
to th
e in
stal
latio
n m
anua
l atta
ched
the
unit.
Sym
bols
sho
w a
s fo
llow
s:
Red
: Red
B
LK: B
lack
W
HT:
Whi
te
YLW
: Yel
low
P
RP
: Pur
ple
GR
Y: G
ray
Blu
: Blu
e P
NK
: Pin
k O
rg: O
rang
e G
RN
: Gre
en
Wiring Diagrams SiEN30-602
272 Appendix
FXDQ20N / 25N / 32N / 40N / 50N / 63NVET (without Drain Pump)
3D04
9604
A
TE
RM
INA
L
FIE
LD W
IRIN
G
NO
TE
S:
Con
trol B
ox
Pow
er
supp
ly
Prin
ted
circ
uit b
oard
Cap
acito
r (M
1F)
Fus
e (F
5A/2
50V
)Li
ght e
mitt
ing
diod
e(S
ervi
ce M
onito
r Gre
en)
Mot
or (I
ndoo
r Fan
)Th
erm
al p
rote
ctor
(M1F
Em
bedd
ed)
The
rmis
tor (
Air)
The
rmis
tor (
Coi
l-1)
The
rmis
tor (
Coi
l-2)
Tran
sfor
mer
(220
V/2
2V)
Pha
se c
ontro
l circ
uit
The
rmin
al b
lock
Term
inal
blo
ckE
lect
roni
c ex
pans
ion
valv
eN
oise
filte
r (Fe
rrite
Cor
e)W
ired
Rem
ote
Con
trolle
rT
herm
isto
r (A
ir)S
elec
tor S
witc
h (M
ain/
Sub
)C
onne
ctor
For
Opt
iona
l Par
tsC
onne
ctor
(Ada
ptor
For
Wiri
ng)
Con
nect
or (W
iring
Ada
ptor
Fo
r Ele
ctric
al A
pend
ices
)
Not
e 5
Inpu
t fro
m
outs
ide
trans
mis
sion
w
iring
cen
tral
rem
ote
cont
rol
Not
e 3
Wire
d re
mot
e co
ntro
l
CO
NN
EC
TOR
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith th
e at
tach
ed in
stal
latio
n m
anua
l.R
emot
e co
ntro
l mod
el v
arie
s ac
cord
ing
to th
e co
mbi
natio
n sy
stem
, con
firm
eni
neer
ing
mat
eria
ls a
nd c
atal
ogs,
etc
. bef
ore
conn
ectin
g.W
hen
conn
ectin
g th
e in
put w
ires
from
out
side
, for
ced
OF
F o
r ON
/OF
F c
ontro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
cont
rol.
In d
etai
ls, r
efer
to th
e in
stal
latio
n m
anua
l atta
ched
the
unit.
Sym
bols
sho
w a
s fo
llow
s:
Red
: Red
B
LK: B
lack
W
HT:
Whi
te
YLW
: Yel
low
P
RP
: Pur
ple
GR
Y: G
ray
Blu
: Blu
e P
NK
: Pin
k O
rg: O
rang
e G
RN
: Gre
en
SiEN30-602 Wiring Diagrams
Appendix 273
FXSQ20M / 25M / 32M / 40M / 50M / 63M / 80M / 100M / 125MVE
3D03
9561
A
Indo
or u
nit
Prin
ted
circ
uit b
oard
Term
inal
boa
rdC
apac
itor
(M1F
)F
use
( �
,5A
, 250
V)
Ligh
t em
ittin
g di
ode
(ser
vice
mon
itor g
reen
)
Mag
netic
rela
y (M
1F)
Mag
netic
rela
y (M
1P)
Mot
or (i
ndoo
r fan
)M
otor
(dra
in p
ump)
Ther
mo
switc
h(M
1F e
mbe
dded
)
Mot
or (d
rain
pum
p)Th
erm
isto
r (co
il)Fl
oat s
witc
hTr
anso
rmer
220
-240
/22V
)Te
rmin
al b
lock
(pow
er)
Term
inal
blo
ck (c
ontro
l)El
ectrp
nic
expa
nsio
n va
lve
Opt
iona
l par
tsE
lect
ric h
eate
rFu
se (
� ,1
5A, 2
50V
)H
umid
ifier
Mag
nect
ic re
lay
(E1H
)H
umid
ifier
Term
inal
blo
ck (E
1H)
Wire
d re
mot
e co
ntro
lTh
erm
isto
r (ai
r)Se
lecto
r swi
tch (m
ain/su
b)A
dapt
er fo
r w
iring
Fuse
( �
,5A
, 250
V)
Mag
netic
rela
yM
agne
tic re
lay
Mag
netic
rela
y (E
1H)
Mag
netic
rela
y (H
u)C
onne
ctor
for o
ptio
nal p
arts
Conn
ector
(ada
pter fo
r wirin
g)Co
nnec
tor (w
iring a
dapte
r for
electo
rical
appe
ndice
s)
A1P
A2P
C1R
F1U
HA
P
K1R-K
3RK
PR
M1F
M1P
Q1M
R1T
R2T·R
3TR
1T
T1R
X1M
X2M
Y1E
E1H
F1U-F
3UH
uK
1MS
1HX
3M
R1T
SS
1
F1U·
F2U
KC
RK
FR
KH
RKH
uR
X16
AX
18A
Not
es:
Term
inal
blo
ckC
onne
ctor
Term
inal
Fie
ld w
iring
In c
ase
of u
sing
a c
entr
al r
emot
e co
ntro
l, co
nnec
t it t
o th
e un
it in
ac
cord
ance
with
the
atta
ched
inst
ruct
ion
man
ual.
Whe
n co
nnec
ting
the
inpu
t wire
s fr
om o
utsi
de, f
orce
d of
f or
on/ o
ff co
ntro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
conr
ol, i
n de
tails
, ref
er to
the
inst
alla
tion
man
ual a
ttach
ed to
the
unit.
.In
cas
e in
stal
ling
the
elec
tric
hea
ter,
exec
ute
the
addi
tiona
l wiri
ng fo
r he
ater
circ
uit (
K1M
, E1H
). In
this
cas
e, th
e m
ain
pow
er s
uppl
y ha
s to
be
supp
lied
inde
pend
ently
.In
cas
e of
hig
h or
lpw
E.S
.P. o
pera
tion,
cha
nge
over
the
wiri
ng c
onne
ctio
n fr
om X
4A(o
f A2P
) to
X3A
or
X5A
.S
ymbo
ls s
how
as
follo
ws.
(P
NK
:Pin
k W
HT
: Whi
te Y
LW: Y
ello
w G
RY
: Gra
y O
RG
: Ora
nge
BLU
: Blu
e B
LK: B
lack
RE
D: R
ed
BR
N: B
row
n G
RN
: Gre
en)
Use
cop
per
cond
ucto
rs o
nly.
Pow
er s
uppl
y
Not
e-5
Sep
arat
e po
wer
sup
ply
Terminals for operation indicator
Com
pres
sor
adap
ter
for
wiri
ng o
pera
tion
(opt
iona
l acc
esso
ry)
Fan
oper
atio
n
Not
e-4
Inpu
t fro
m o
utsi
de
Not
e-3
Tran
smis
sion
wiri
ng c
entr
al
rem
ote
cont
rol
Ele
ctric
par
ts b
ox
Wire
d re
mot
e co
ntro
l (op
tiona
l ac
cess
ory)
Not
e-6
Low
E. S
. P o
pera
tion
Hig
h E
.S.P
ope
ratio
n
Hig
h E
.S.P
ope
ratio
n(2
0 · 2
5 · 3
2 ty
pe)
(40
· 50
· 63
· 80
· 10
0 · 1
25 t
ype)
(80
· 100
·125
typ
e)
(20
· 25
· 32
· 40
· 50
typ
e)
Wiring Diagrams SiEN30-602
274 Appendix
FXMQ40MA / 50MA / 63MA / 80MA / 100MA / 125MAVE
3D03
9620
B
Prin
ted
circ
uit b
oard
A2P
Term
inal
boa
rd
C1R
Cap
acito
r(M
1F)
F1U
Fus
e (�
, 5A
, 250
V)
40 ·
50 ·
63 ·
80 t
ype
Fus
e (�
, 10A
, 25
0V)
100
· 125
typ
eF
1U
HA
PLi
ght e
mitt
ing
diod
e (s
ervi
ce m
onito
r-gr
een)
Mag
netic
rel
ay(M
1F)
Mag
netic
rel
ay(M
1P)
K1R·
K3R
KP
R
Mot
or (
indo
or fa
n)M
1F
Q1M
The
rmo
switc
h(M
1F e
mbe
dded
)
Opt
iona
l par
ts
The
rmis
tor
(air)
Ther
mis
tor(
coil)
Flo
at s
witc
h
Tran
sfor
mer
(220
-240
V/2V
)
Term
inal
blo
ck(p
ower
)
Term
inal
blo
ck (c
ontro
l)
Ele
ctro
nic
expa
nsio
n va
lve
Mot
or (d
rain
pum
p)
Wire
d re
mot
e co
ntro
l
Sel
ecto
r sw
itch
(mai
n/su
b)
Mag
netic
rela
y
Con
nect
or fo
r opt
iona
l par
ts
Conn
ector
(wirin
g ada
pter fo
r ele
ctoric
al ap
pend
ices)
R1T
R2T-R
3T
S1L
T1R
X
1M
X2M
Y1E
M1P
SS
1
KF
R
X18
A
Not
es:
Term
inal
blo
ckC
onne
ctor
Fie
ld w
iring
In c
ase
of u
sing
a c
entr
al r
emot
e co
ntro
l, co
nnec
t it t
o th
e un
it in
ac
cord
ance
with
the
atta
ched
inst
ruct
ion
man
ual.
Whe
n co
nnec
ting
the
inpu
t wire
s fr
om o
utsi
de, f
orce
d of
f or
on/ o
ff co
ntro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
conr
ol, i
n de
tails
, ref
er to
the
inst
alla
tion
man
ual a
ttach
ed to
the
unit.
.In
cas
e in
stal
ling
the
elec
tric
hea
ter,
exec
ute
the
addi
tiona
l wiri
ng fo
r he
ater
circ
uit (
K1M
, E1H
). In
this
cas
e, th
e m
ain
pow
er s
uppl
y ha
s to
be
supp
lied
inde
pend
ently
.In
cas
e of
hig
h or
lpw
E.S
.P. o
pera
tion,
cha
nge
over
the
wiri
ng c
onne
ctio
n fr
om X
2A a
s sh
own
on u
pper
figu
re.
Sym
bols
sho
w a
s fo
llow
s. (
PN
K:P
ink
WH
T: W
hite
YLW
: Yel
low
OR
G: O
rang
e B
LU: B
lue
BLK
: Bla
ck R
ED
: Red
BR
N: B
row
n)U
se c
oppe
r co
nduc
tors
onl
y.
Term
inal
Not
es-5
Indo
or u
nit
A1P
The
rmis
tor
(air)
Ele
ctric
par
ts b
ox
Not
es-4
Inpu
t fro
m o
utsi
deN
otes
-3Ta
nsm
issi
on w
iring
Cen
tral
rem
ote
cont
rol
Wire
d re
mot
e co
ntro
l (o
ptio
nal a
cces
sory
)
SiEN30-602 Wiring Diagrams
Appendix 275
FXMQ200MA / 250MAVE
3D03
9621
B
WIR
ED
RE
MO
TE C
ON
TRO
L(O
PTI
ON
AL
AC
CE
SS
OR
Y)
PO
WE
R S
UP
PLY
NO
TE-4
INP
UT
FRO
M O
UTS
IDE
NO
TE-3
TRA
NS
MIS
SIO
N W
IRIN
G C
ER
EM
OTE
CO
NTR
OL
Prin
ted
circ
uit b
oard
Cap
acito
r (M
1F, 2
F)
Fus
e (
� ,5
A, 2
50V
)Li
ght e
mitt
ing
diod
e(s
ervi
ce m
onito
r-gr
een)
Mag
netic
con
tact
or (M
1F, 2
F)M
agne
tic c
onta
ctor
(M1F
, 2F)
Mag
netic
con
tact
or (M
1F, 2
F)M
agne
tic r
elay
(M
1F, 2
F)
Mag
netic
rel
ay (
M1P
)M
otor
(in
door
fan)
The
rmo
switc
h(M
1F e
mbe
dded
)
The
rmis
tor
(Air)
The
rmis
tor
(Coi
l)S
elec
tor
Sw
itch
(Sta
tic P
ress
ure)
Tr
ansf
orm
er (2
20-2
40V
/22V
)Te
rmin
al b
lock
(P
ower
)Te
rmin
al b
lock
Term
inal
blo
ck (
Con
trol
)E
lect
roni
c ex
pans
ion
valv
eO
ptio
nal P
arts
Mot
or (
Dra
in p
ump)
Wire
d re
mot
e co
ntro
lT
herm
isto
r (A
ir)S
elec
tor
switc
h (M
ain/
Sub
)C
onne
ctor
for
optio
nal p
arts
Con
nect
or (
Flo
at S
witc
h)C
onne
ctor
(W
iring
Ada
pter
F
or E
lect
oric
al A
ppen
dice
s)
Indo
or u
nit
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith th
e at
tach
ed in
stru
ctio
n m
anua
l.W
hen
conn
ectin
g th
e in
put w
ires
from
out
side
, for
ced
off o
r on
/off
cont
rol o
pera
tion
can
be s
elec
ted
by r
emot
e co
ntro
l, in
de
tails
, ref
er to
the
inst
alla
tion
man
ual a
ttach
ed th
e un
it.
Sym
bols
sho
w a
s fo
llow
s. (P
NK
: Pin
k W
HT:
Whi
te Y
LW: Y
ello
w
OR
G: O
rang
e B
LU:B
lue
BLK
: Bla
ck R
ED
: Red
BR
N: B
row
n)
In c
ase
inst
allin
g th
e dr
ain
pum
p, re
mov
e th
e sh
ort c
ircui
t con
nect
or o
f X
8A a
nd e
xecu
te th
e ad
ditio
nal w
iring
for f
loat
sw
itch
and
drai
n pu
mp.
Use
cop
per
cond
ucto
rs o
nly.
In c
ase
high
E.S
.P. o
pera
tion,
cha
nge
the
switc
h (S
S)
for
“H”.
Not
es:
Term
inal
blo
ckC
onne
ctor
Sho
rt c
ircui
t con
nect
orTe
rmin
alF
ield
wiri
ng
Wiring Diagrams SiEN30-602
276 Appendix
FXHQ32MA / 63MA / 100MAVE
3D03
9801
D
Indo
or u
nit
Opt
iona
l par
ts
Prin
ted
circu
it bo
ard
Capa
citor
(M1F
)Fu
se (�
, 5A,
250
V)Li
ght e
mitt
ing
diod
e(s
ervic
e m
onito
r-gre
en)
Mag
netic
relay
(M1S
)M
agne
tic re
lay (M
1P)
Mot
or (i
ndoo
r fan
)M
otor
(swi
ng fl
ap)
Ther
mo
switc
h (M
1F e
mbe
dded
)Th
erm
istor
(AIR
)Th
erm
istor
(coi
l liqu
id)
Ther
mist
or (c
oil g
as)
Lim
it sw
itch
(swi
ng fl
ap)
Tran
sform
er (2
20-2
40V/
22V)
Term
inal
blo
ck (p
ower
)Te
rmin
al b
lock
(con
trol)
Elec
troni
c ex
pans
ion
valve
Phas
e co
ntro
l circ
uit
Mot
or (d
rain
pum
p)
Ther
mist
or (A
IR)
Sele
ctor
switc
h (m
ain/
sub)
Prin
ted
circu
it bo
ard
Prin
ted
circu
it bo
ard
Push
but
ton
(on/
off)
Ligh
t em
ittin
g di
ode
(on-
red)
Ligh
t em
ittin
g di
ode
(tim
er-g
reen
)
Wire
d re
mot
e co
ntro
l
Wire
d re
mot
e co
ntro
l
NOTE
SNo
te 5
Note
4
Note
6
Inpu
t fro
m
outs
ide
Tran
smiss
ion
wirin
g ce
ntra
l rem
ote
cont
rol
Rece
iver/d
isplay
uni
t (w
irele
ss re
mot
e co
ntro
ller)
Note
3
POW
ER S
UPPL
Y
Term
inal
blo
ckCo
nnec
tor
Elec
tric
parts
box
Wire
d re
mot
e co
ntro
ller
(opt
iona
l acc
esso
ry)
In c
ase
usin
g ce
ntra
l rem
ote
cont
rolle
r, co
nnec
t it
to th
e un
it in
acc
orda
nce
with
the
atta
ched
in
stru
ctio
n m
anua
l.X2
3A is
con
nect
ed w
hen
the
wire
less
rem
ote
cont
rol k
it is
bein
g us
ed.
Whe
n co
nnec
ting
the
inpu
t wire
s fro
m o
utsid
e, fo
rced
off
or o
n/of
f con
trol
oper
atio
n ca
n be
sel
ecte
d by
rem
ote
cont
rolle
r. In
det
ails,
refe
r to
the
inst
alla
tion
man
ual a
ttach
ed th
e un
it.
In c
ase
inst
allin
g th
e dr
ain
pum
p, re
mov
e th
e sh
ort c
ircui
t con
nect
or o
f X8A
an
d ex
ecut
e th
e ad
ditio
nal w
iring
for f
loat
switc
h an
d dr
ain
pum
p.
Use
copp
er c
ondu
ctor
s on
ly.
PNK:
Pin
k WHT
: Whi
te Y
LW: Y
ellow
ORG
: Ora
nge
BLU:
Blu
e BL
K: B
lack
RED
: Red
Sym
bols
show
as
follo
ws.
Fiel
d wi
ring
Rece
iver/d
isplay
uni
t (at
tach
ed to
wi
rele
ss re
mot
e co
ntro
l)
Ligh
t em
ittin
g di
ode
(filte
r sig
n-re
d)Li
ght e
mitt
ing
diod
e(d
efro
st-o
rang
e)Se
lect
or sw
itch
(mai
n/su
b)Se
lect
or sw
itch
(wire
less
add
ress
set
)
Conn
ecto
r (flo
at sw
itch)
Conn
ecto
r (wi
ring
adap
tor f
or
elec
trica
l app
endi
ces
Conn
ecto
r (wi
rele
ss re
mot
e co
ntro
ller)
Show
s sho
rt cir
cuit c
onne
ctor.
SiEN30-602 Wiring Diagrams
Appendix 277
FXAQ20MA / 25MA / 32MA / 40MA / 50MA / 63MAVE
3D03
4206
C
Indo
or u
nit
PO
WE
R S
UP
PLY
Prin
ted
circ
uit b
oard
Fus
e (
� ,5
A, 2
50V
)
Ligh
t em
ittin
g di
ode
(ser
vice
mon
itor
gree
n)
Mot
or (
Indo
or F
an)
Mot
or (
Sw
ing
Fla
p)
The
rmis
tor
(AIR
)
The
rmis
tor
(Coi
l Liq
uid
Pip
e)
The
rmis
tor
(Coi
l Gas
Pip
e)
Term
inal
Blo
ck (
cont
rol)
Term
inal
Blo
ck (
Pow
er)
Ele
ctro
nic
expa
nsio
n va
lve
Pow
er c
ircui
t
Prin
ted
circ
uit b
oard
Prin
ted
circ
uit b
oard
Pus
h bu
tton
(ON
/OF
F)
Ligh
t em
ittin
g di
ode
(ON
-RE
D)
Ligh
t em
ittin
g di
ode
(tim
er-g
reen
)
Ligh
t em
ittin
g di
ode
(Filt
er s
ign-
red)
Ligh
t em
ittin
g di
ode
(Def
rost
-ore
nge)
Sel
ecto
r sw
itch
(MA
IN/S
UB
)
Sel
ecto
r sw
itch
(wire
less
add
ress
set
)T
herm
isto
r (A
IR)
Sel
ecto
r sw
itch
(MA
IN/S
UB
)
Con
nect
or (
float
sw
itch)
Con
nect
or (
grou
p co
ntro
l ada
ptor
)
Rec
eive
r/di
spla
y un
it (a
ttach
ed to
wire
less
rem
ote
cont
rolle
r)
Wire
rem
ot c
ontr
olC
onne
ctor
for
optio
nal p
arts
Not
es:
Term
inal
Fie
ld w
iring
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in a
ccor
danc
e w
ith th
e at
tach
ed in
stal
latio
n m
anua
l.
Sym
bols
sho
ws
as fo
llow
s: R
ED
:Red
WH
T:W
hite
GR
N:G
reen
P
NK
:Pin
k Y
LW: Y
ello
w B
LK:B
lack
OR
G: O
rang
e B
RN
:Bro
wn
BLU
:Blu
e
Whe
n co
nnec
ting
the
inpu
t wire
s fr
om
outs
ide,
forc
ed o
ff or
on/
off c
ontr
ol
oper
atio
n ca
n be
sel
ecte
d by
rem
ote
cont
rol,
in d
etai
ls, r
efer
to th
e in
stal
la-
tion
man
ual a
tach
ed th
e un
it.
Rem
ote
cont
rol m
odel
var
ies
acco
rdin
g to
the
com
bina
tion
syst
em, c
onfir
m
engi
neer
ing
data
and
cat
alog
s, e
tc,
befo
re c
onne
ctin
g.C
onfir
m th
e m
etho
d of
set
ting
the
sele
ctor
sw
itch
(SS
1, S
S2)
of w
ired
rem
ote
cont
rol a
nd w
irele
ss r
emot
e co
ntro
l by
inst
alla
tion
man
ual a
nd
engi
neer
ing
data
, ET
C.
X24
A is
con
nect
ed w
hen
the
wire
less
re
mot
e co
ntro
ller
kit i
s be
ing
used
.
Sho
ws
shor
t circ
uit c
onne
ctor
.
Con
nect
or
Con
trol
box
Sid
eFr
ont
Not
e 8
Not
e 8
Not
e 5
Not
e 2
Rec
eive
r/di
spla
y un
it(w
irele
ss r
emot
e co
ntro
l)
Inpu
t fro
m o
utsi
de
Tran
smis
sion
wiri
ng
cent
ral r
emot
e co
ntro
l
Wire
d re
mot
e co
ntro
l
(Ind
oor
unit)
Con
nect
or
Wiring Diagrams SiEN30-602
278 Appendix
FXLQ20 · 25 · 32 · 40 · 50 · 63MAVEFXNQ20 · 25 · 32 · 40 · 50 · 63MAVE
3D03
9826
D
Indo
or u
nit
In c
ase
usin
g ce
ntra
l rem
ote
cont
rol,
conn
ect i
t to
the
unit
in
acco
rdan
ce w
ith th
e at
tach
ed in
stru
ctio
n m
anua
l.
PO
WE
R S
UP
PLY
WIR
ED
RE
MO
TE C
ON
TRO
L(O
PTI
ON
AL
AC
CE
SS
OR
Y)
CO
NTR
OL
BO
X
NO
TE-4
INP
UT
FRO
M O
UTS
IDE
NO
TE-3
TRA
NS
MIS
SIO
N W
IRIN
G
CE
NTR
AL
RE
MO
TE C
ON
TRO
L
Whe
n co
nnec
ting
the
inpu
t wire
s fr
om o
utsi
de, f
orce
d of
f or
on/o
ff co
ntro
l ope
ratio
n ca
n be
sel
ecte
d by
rem
ote
cont
rolle
r, in
det
ails
, ref
er to
the
inst
alla
tion
man
ual a
ttach
ed th
e un
it.
Sym
bols
sho
w a
s fo
llow
s. (
PN
K: P
ink
WH
T:
Whi
te Y
LW: Y
ello
w
OR
G: O
rang
e B
LU:B
lue
BLK
: Bla
ck R
ED
: Red
BR
N: B
row
n)
Use
cop
per
cond
ucto
rs o
nly.
Prin
ted
circ
uit b
oard
Cap
acito
r (M
1F)
Fus
e (
� ,5
A, 2
50V
)Li
ght e
mitt
ing
diod
e(s
ervi
ce m
onito
r-gr
een)
Mag
netic
rel
ay (
M1F
)M
otor
(in
door
fan)
The
rmo
switc
h(M
1F e
mbe
dded
)T
herm
isto
r (A
IR)
The
rmis
tor
(CO
IL)
Tran
sfor
mer
(22
0-24
0V/2
2V)
Term
inal
blo
ck (
pow
er)
Term
inal
blo
ck (
cont
rol)
Ele
ctro
nic
expa
nsio
n va
lve
The
rmis
tor
(AIR
)S
elec
tor
switc
h (M
AIN
/SU
B)
Con
nect
or (
wiri
ng a
dapt
or fo
r el
ectr
onic
al a
ppen
dice
s)
Wire
d re
mot
e co
ntro
l
Con
nect
or fo
r op
tiona
l par
ts
Not
es:
Term
inal
blo
ckC
onne
ctor
Term
inal
Fie
ld w
iring
SiEN30-602 List of Electrical and Functional Parts
Appendix 279
3. List of Electrical and Functional Parts3.1 Outside Unit3.1.1 RWEYQ10MYL
3.1.2 RWEYQ10MTL
Item Name SymbolModel
RWEYQ10MYL
Compressor InverterType
M1CJT1G-VDKYR@T
OC protection device 13.5A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 2000plsElectronic expansion valve (Subcool) Y2E Fully closed: 0pls Fully open: 2000pls
Pressure protection
High pressure switch For M1C HPS OFF: 4.0 MPa ON: 3.0±0.15MPa
Low pressure sensor S1NPL OFF: 0.07MPaFusible plug � Open: 70~75°C
Temperature protection
Discharge gas temperature protection(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature protection(Radiator fin thermistor)
R1T OFF: 98°C
Others Fuse
For main PC board
F1U 250V AC 10A Class BF2U 250V AC 10A Class B
For Noise filter PC board F1U 250V AC 5A Class B
+0−0.12
Item Name SymbolModel
RWEYQ10MTL
Compressor InverterType
M1CJT100G-VDK@S3
OC protection device 24.0A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 2000plsElectronic expansion valve (Subcool) Y2E Fully closed: 0pls Fully open: 2000pls
Pressure protection
High pressure switch For M1C HPS OFF: 4.0 MPa ON: 3.0±0.15MPa
Low pressure sensor S1NPL OFF: 0.07MPaFusible plug � Open: 70~75°C
Temperature protection
Discharge gas temperature protection(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature protection(Radiator fin thermistor)
R1T OFF: 98°C
Others Fuse
For main PC board
F1U 250V AC 10A Class BF2U 250V AC 10A Class B
For Noise filter PC board F1U 250V AC 5A Class B
+0−0.12
List of Electrical and Functional Parts SiEN30-602
280 Appendix
3.2 Indoor Side3.2.1 Indoor Unit
Parts Name SymbolModel
RemarkFXFQ25MVE
FXFQ32MVE
FXFQ40MVE
FXFQ50MVE
FXFQ63MVE
FXFQ80MVE
FXFQ100MVE
FXFQ125MVE
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC7E61W
Motors
Fan Motor M1F DC380V 30W 8P DC 380V 120W 8P
Drain Pump M1PAC220-240V (50Hz) AC220V (60Hz)
PLD-12230DMThermal Fuse 145°C
Swing Motor M1S MP35HCA[3P007482-1]Stepping Motor DC16V
Thermistors
Thermistor (Suction Air) R1T In PC board A4P or wired remote controlThermistor (for Heat Exchanger High Temp.) R3T ST8605-5 φ8 L1000
20kΩ (25°C)Thermistor (Heat Exchanger) R2T ST8602A-5 φ6 L1000
20kΩ (25°C)
Others
Float Switch S1L FS-0211BFuse F1U 250V 5A φ5.2Thermal Fuse TFu �Transformer T1R �
Parts Name SymbolModel
RemarkFXCQ20MVE
FXCQ25MVE
FXCQ32MVE
FXCQ40MVE
FXCQ50MVE
FXCQ63MVE
FXCQ80MVE
FXCQ125MVE
RemoteController
Wired Remote Control BRC1A61OptionInfrared Remote
Control BRC7C62
Motors
Fan Motor M1F
AC 220~240V 50Hz1φ10W 1φ15W 1φ20W 1φ30W 1φ50W 1φ85W
Thermal Fuse 152°C � Thermal protector 135°C : OFF 87°C : ON
Drain Pump M1PAC220-240V (50Hz) AC220V (60Hz)
PLD-12230DMThermal Fuse 145°C
Swing Motor M1S MT8-L[3PA07509-1]AC200~240V
Thermistors
Thermistor (Suction Air) R1T ST8601-6 φ4 L125020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-6 φ8 L1250
20kΩ (25°C)Thermistor (Heat Exchanger) R2T ST8602A-5 φ6 L1000
20kΩ (25°C)
OthersFloat Switch S1L FS-0211BFuse F1U 250V 5A φ5.2Transformer T1R TR22H21R8
SiEN30-602 List of Electrical and Functional Parts
Appendix 281
∗only for FXDQ20~63N(A)VE, FXDQ20~32PVE (with Drain Pump Type)
Parts Name SymbolModel
RemarkFXKQ25MAVE
FXKQ32MAVE
FXKQ40MAVE
FXKQ63MAVE
RemoteController
Wired Remote Control BRC1C62 OptionInfrared Remote Control BRC4C61
Motors
Fan Motor M1F
AC 220~240V 50Hz1φ15W 4P 1φ20W 4P 1φ45W 4P
Thermal Fuse 146°C Thermal protector 120°C : OFF 105°C : ON
Drain Pump M1PAC 220-240V (50Hz)
PLD-12200DMThermal Fuse 145°C
Swing Motor M1S MP35HCA [3P080801-1]AC200~240V
Thermistors
Thermistor (Suction Air) R1T ST8601-13 φ4 L63020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-7 φ8 L1600
20kΩ (25°C)Thermistor (Heat Exchanger) R2T ST8602A-7 φ6 L1600
20kΩ (25°C)
OthersFloat Switch S1L FS-0211BFuse F1U 250V 5A φ5.2Transformer T1R TR22H21R8
Parts Name Symbol
Model
RemarkFXDQ20N(A)VE(T),
PVE(T)
FXDQ25N(A)VE(T),
PVE(T)
FXDQ32N(A)VE(T),
PVE(T)FXDQ
40N(A)VE(T)FXDQ
50N(A)VE(T)FXDQ
63N(A)VE(T)
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC4C62
Motors
Fan Motor M1F
AC 220~240V 50Hz1φ62W 1φ130W
Thermal protector130°C: OFF, 83°C: ON
Drain Pump M1PAC220-240V (50Hz)
PLD-12230DMThermal Fuse 145°C
*
Thermistors
Thermistor (Suction Air) R1T ST8601-1 φ4 L=25020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-4 φ8 L=800
20kΩ (25°C)Thermistor (Heat Exchanger) R2T ST8602A-4 φ6 L=800
20kΩ (25°C)
OthersFloat Switch S1L FS-0211E *Fuse F1U 250V 5A φ5.2Transformer T1R TR22H21R8
List of Electrical and Functional Parts SiEN30-602
282 Appendix
Parts Name SymbolModel
RemarkFXSQ20MVE
FXSQ25MVE
FXSQ32MVE
FXSQ40MVE
FXSQ50MVE
FXSQ63MVE
FXSQ80MVE
FXSQ100MVE
FXSQ125MVE
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC4C62
Motors
Fan Motor M1F
AC 220~240V 50Hz
1φ50W 1φ65W 1φ85W 1φ125W 1φ225W
Thermal Fuse 152°C Thermal protector 135°C : OFF 87°C : ON
Drain Pump M1PAC220-240V (50Hz)
PLD-12230DMThermal Fuse 145°C
Thermistors
Thermistor (Suction Air) R1T ST8601-4 φ4 L80020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-7 φ8 L1600
20kΩ (25°C)Thermistor (Heat Exchanger) R2T ST8602A-6 φ6 L1250
20kΩ (25°C)
OthersFloat Switch S1L FS-0211BFuse F1U 250V 5A φ5.2Transformer T1R TR22H21R8
Parts Name SymbolModel
RemarkFXMQ40MAVE
FXMQ50MAVE
FXMQ63MAVE
FXMQ80MAVE
FXMQ100MAVE
FXMQ125MAVE
FXMQ200MAVE
FXMQ250MAVE
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC4C62
MotorsFan Motor M1F
AC 220~240V 50Hz1φ100W 1φ160W 1φ270W 1φ430W 1φ380W×2
Thermal protector 135°C : OFF 87°C : ON
Capacitor for Fan Motor C1R 5μ F-400V 7μ F 400V
10μ F400V
8μ F400V
10μ F400V
12μ F400V
Thermistors
Thermistor (Suction Air) R1T ST8601A-5 φ4 L100020kΩ (25°C)
ST8601A-13φ4 L630
Thermistor (for Heat Exchanger High Temp.) R3T ST8605A-4 φ8 L800
20kΩ (25°C)ST8605A-5 φ8 L1000
Thermistor (Heat Exchanger) R2T ST8602A-4 φ6 L800
20kΩ (25°C)ST8602A-6 φ6 L1250
OthersFloat switch S1L FS-0211Fuse F1U 250V 5A φ5.2 250V 10A φ5.2 250V 10ATransformer T1R TR22H21R8
SiEN30-602 List of Electrical and Functional Parts
Appendix 283
Parts Name SymbolModel
RemarkFXHQ32MAVE
FXHQ63MAVE
FXHQ100MAVE
RemoteController
Wired Remote Control BRC1C62 OptionInfrared Controller BRC7E63W
Motors
Fan Motor M1FAC 220~240V/220V 50Hz/60Hz
1φ63W 1φ130WThermal protector 130°C : OFF 80°C : ON
Capacitor for Fan Motor C1R 3.0μF-400V 9.0μF-400V
Swing Motor M1S MT8-L[3P058751-1]AC200~240V
Thermistors
Thermistor (Suction Air) R1T ST8601A-1 φ4 L25020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-6 φ8 L = 1250
20kΩ (25°C)ST8605-6 φ8 L = 1250
20kΩ (25°C)Thermistor (Heat Exchanger) R2T ST8602A-6 φ6 L = 1250
20kΩ (25°C)ST8602A-6 φ6 L = 1250
20kΩ (25°C)
OthersFuse F1U 250V 5A φ5.2Transformer T1R TR22H21R8
Parts Name SymbolModel
RemarkFXAQ20MAVE
FXAQ25MAVE
FXAQ32MAVE
FXAQ40MAVE
FXAQ50MAVE
FXAQ63MAVE
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC7E618
MotorsFan Motor M1F
AC 220~240V 50Hz1φ40W 1φ43W
Thermal protector 130°C : OFF 80°C : ON
Swing Motor M1S MP24 [3SB40333-1]AC200~240V
MSFBC20C21 [3SB40550-1]AC200~240V
Thermistors
Thermistor (Suction Air) R1T ST8601-2 φ4 L40020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-2 φ8 L400
20kΩ (25°C)Thermistor (for Heat Exchanger) R2T ST8602-2 φ6 L400
20kΩ (25°C)
OthersFloat Switch S1L OPTION
Fuse F1U 250V 5A φ5.2
List of Electrical and Functional Parts SiEN30-602
284 Appendix
Parts Name SymbolModel
RemarkFXLQ20MAVE
FXLQ25MAVE
FXLQ32MAVE
FXLQ40MAVE
FXLQ50MAVE
FXLQ63MAVE
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC4C62
MotorsFan Motor M1F
AC 220~240V 50Hz1φ15W 1φ25W 1φ35W
Thermal protector 135°C : OFF 120°C : ONCapacitor for Fan Motor C1R 1.0μF-400V 0.5μF-400V 1.0μF-400V 1.5μF-400V 2.0μF-400V
Thermistors
Thermistor (Suction Air) R1T ST8601-6 φ4 L125020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-9 φ8 L2500
20kΩ (25°C)Thermistor (for Heat Exchanger) R2T ST8602A-9 φ6 L2500
20kΩ (25°C)
OthersFuse F1U AC250V 5ATransformer T1R TR22H21R8
Parts Name SymbolModel
RemarkFXNQ20MAVE
FXNQ25MAVE
FXNQ32MAVE
FXNQ40MAVE
FXNQ50MAVE
FXNQ63MAVE
RemoteController
Wired Remote Control BRC1C62OptionInfrared Remote
Control BRC4C62
MotorsFan Motor M1F
AC 220~240V 50Hz1φ15W 1φ25W 1φ35W
Thermal protector 135°C : OFF 120°C : ONCapacitor for Fan Motor C1R 1.0μF-400V 0.5μF-400V 1.0μF-400V 1.5μF-400V 2.0μF-400V
Thermistors
Thermistor (Suction Air) R1T ST8601-6 φ4 L125020kΩ (25°C)
Thermistor (for Heat Exchanger High Temp.) R3T ST8605-9 φ8 L2500
20kΩ (25°C)Thermistor (for Heat Exchanger) R2T ST8602A-9 φ6 L2500
20kΩ (25°C)
OthersFuse F1U AC250V 5ATransformer T1R TR22H21R8
SiEN30-602 Option List
Appendix 285
4. Option List4.1 Optional Accessories
NOTE)1. Refer to the latest drawing.2. In the case of heat recovery system, COOL/HEAT Selector cannot be connected.
3D052730
Models
KRC19-26AKJB111A
DTA104A62
Optional accessories
Refnet header
Refnet joint
Outside unit multi connection piping kit
COOL/HEAT SelectorFixing box
External control adaptor for outdoor unit
Dis
trib
utiv
e pi
ping
RWEYQ10MYLRWEYQ10MTL
RWEYQ20MYLRWEYQ20MTL
RWEYQ30MYLRWEYQ30MTL
KHRP25M33H(Max. 8 branch)
KHRP26M22H, KHRP26M33H(Max. 4 branch) (Max. 8 branch)
KHRP25M22T, KHRP25M33T, KHRP26M22T, KHRP26M33T
KHRP25M22T, KHRP25M33T, KHRP25M72T, KHRP26M22T, KHRP26M33T, KHRP26M72T
BHFP22MA56,BHFP26MA56
BHFP22MA84BHFP26MA84
KHRP25M22T, KHRP25M33T, KHRP25M72T, KHRP25M73T, KHRP26M22T, KHRP26M33T, KHRP26M72T, KHRP26M73T
KHRP25M33H, KHRP25M72H(Max. 8 branch) (Max. 8 branch)
KHRP26M22H, KHRP26M33H, KHRP26M72H(Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
KHRP25M33H, KHRP25M72H, KHRP25M73H(Max. 8 branch), (Max. 8 branch) (Max. 8 branch)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Thermistor Resistance / Temperature Characteristics SiEN30-602
286 Appendix
5. Thermistor Resistance / Temperature Characteristics
Indoor unit For air suction R1TFor liquid pipe R2TFor gas pipe R3T
Outdoor unit For outdoor air R1TFor coil R2TFor suction pipe R4TFor Receiver gas pipe R5T
(kΩ)T°C 0.0 0.5 T°C 0.0 0.5-20 197.81 192.08 30 16.10 15.76-19 186.53 181.16 31 15.43 15.10-18 175.97 170.94 32 14.79 14.48-17 166.07 161.36 33 14.18 13.88-16 156.80 152.38 34 13.59 13.31-15 148.10 143.96 35 13.04 12.77-14 139.94 136.05 36 12.51 12.25-13 132.28 128.63 37 12.01 11.76-12 125.09 121.66 38 11.52 11.29-11 118.34 115.12 39 11.06 10.84-10 111.99 108.96 40 10.63 10.41-9 106.03 103.18 41 10.21 10.00-8 100.41 97.73 42 9.81 9.61-7 95.14 92.61 43 9.42 9.24-6 90.17 87.79 44 9.06 8.88-5 85.49 83.25 45 8.71 8.54-4 81.08 78.97 46 8.37 8.21-3 76.93 74.94 47 8.05 7.90-2 73.01 71.14 48 7.75 7.60-1 69.32 67.56 49 7.46 7.310 65.84 64.17 50 7.18 7.041 62.54 60.96 51 6.91 6.782 59.43 57.94 52 6.65 6.533 56.49 55.08 53 6.41 6.534 53.71 52.38 54 6.65 6.535 51.09 49.83 55 6.41 6.536 48.61 47.42 56 6.18 6.067 46.26 45.14 57 5.95 5.848 44.05 42.98 58 5.74 5.439 41.95 40.94 59 5.14 5.05
10 39.96 39.01 60 4.96 4.8711 38.08 37.18 61 4.79 4.7012 36.30 35.45 62 4.62 4.5413 34.62 33.81 63 4.46 4.3814 33.02 32.25 64 4.30 4.2315 31.50 30.77 65 4.16 4.0816 30.06 29.37 66 4.01 3.9417 28.70 28.05 67 3.88 3.8118 27.41 26.78 68 3.75 3.6819 26.18 25.59 69 3.62 3.5620 25.01 24.45 70 3.50 3.4421 23.91 23.37 71 3.38 3.3222 22.85 22.35 72 3.27 3.2123 21.85 21.37 73 3.16 3.1124 20.90 20.45 74 3.06 3.0125 20.00 19.56 75 2.96 2.9126 19.14 18.73 76 2.86 2.8227 18.32 17.93 77 2.77 2.7228 17.54 17.17 78 2.68 2.6429 16.80 16.45 79 2.60 2.5530 16.10 15.76 80 2.51 2.47
SiEN30-602 Thermistor Resistance / Temperature Characteristics
Appendix 287
Outside Unit Thermistors for Discharge Pipe (R3T)
(kΩ)T°C 0.0 0.5 T°C 0.0 0.5 T°C 0.0 0.5
0 640.44 624.65 50 72.32 70.96 100 13.35 13.151 609.31 594.43 51 69.64 68.34 101 12.95 12.762 579.96 565.78 52 67.06 65.82 102 12.57 12.383 552.00 538.63 53 64.60 63.41 103 12.20 12.014 525.63 512.97 54 62.24 61.09 104 11.84 11.665 500.66 488.67 55 59.97 58.87 105 11.49 11.326 477.01 465.65 56 57.80 56.75 106 11.15 10.997 454.60 443.84 57 55.72 54.70 107 10.83 10.678 433.37 423.17 58 53.72 52.84 108 10.52 10.369 413.24 403.57 59 51.98 50.96 109 10.21 10.06
10 394.16 384.98 60 49.96 49.06 110 9.92 9.7811 376.05 367.35 61 48.19 47.33 111 9.64 9.5012 358.88 350.62 62 46.49 45.67 112 9.36 9.2313 342.58 334.74 63 44.86 44.07 113 9.10 8.9714 327.10 319.66 64 43.30 42.54 114 8.84 8.7115 312.41 305.33 65 41.79 41.06 115 8.59 8.4716 298.45 291.73 66 40.35 39.65 116 8.35 8.2317 285.18 278.80 67 38.96 38.29 117 8.12 8.0118 272.58 266.51 68 37.63 36.98 118 7.89 7.7819 260.60 254.72 69 36.34 35.72 119 7.68 7.5720 249.00 243.61 70 35.11 34.51 120 7.47 7.3621 238.36 233.14 71 33.92 33.35 121 7.26 7.1622 228.05 223.08 72 32.78 32.23 122 7.06 6.9723 218.24 213.51 73 31.69 31.15 123 6.87 6.7824 208.90 204.39 74 30.63 30.12 124 6.69 6.5925 200.00 195.71 75 29.61 29.12 125 6.51 6.4226 191.53 187.44 76 28.64 28.16 126 6.33 6.2527 183.46 179.57 77 27.69 27.24 127 6.16 6.0828 175.77 172.06 78 26.79 26.35 128 6.00 5.9229 168.44 164.90 79 25.91 25.49 129 5.84 5.7630 161.45 158.08 80 25.07 24.66 130 5.69 5.6131 154.79 151.57 81 24.26 23.87 131 5.54 5.4632 148.43 145.37 82 23.48 23.10 132 5.39 5.3233 142.37 139.44 83 22.73 22.36 133 5.25 5.1834 136.59 133.79 84 22.01 21.65 134 5.12 5.0535 131.06 128.39 85 21.31 20.97 135 4.98 4.9236 125.79 123.24 86 20.63 20.31 136 4.86 4.7937 120.76 118.32 87 19.98 19.67 137 4.73 4.6738 115.95 113.62 88 19.36 19.05 138 4.61 4.5539 111.35 109.13 89 18.75 18.46 139 4.49 4.4440 106.96 104.84 90 18.17 17.89 140 4.38 4.3241 102.76 100.73 91 17.61 17.34 141 4.27 4.2242 98.75 96.81 92 17.07 16.80 142 4.16 4.1143 94.92 93.06 93 16.54 16.29 143 4.06 4.0144 91.25 89.47 94 16.04 15.79 144 3.96 3.9145 87.74 86.04 95 15.55 15.31 145 3.86 3.8146 84.38 82.75 96 15.08 14.85 146 3.76 3.7247 81.16 79.61 97 14.62 14.40 147 3.67 3.6248 78.09 76.60 98 14.18 13.97 148 3.58 3.5449 75.14 73.71 99 13.76 13.55 149 3.49 3.4550 72.32 70.96 100 13.35 13.15 150 3.41 3.37
Pressure Sensor SiEN30-602
288 Appendix
6. Pressure Sensor
High Pressure (PH)
Low Pressure (PL)
PH = 1.38V-0.69PL = 0.57V-0.28PH : High pressure (MPa)VL : Low pressure (MPa)V : Voltage (V)
PH : Detected Pressure [High Side] MPaPL : Detected Pressure [Low Side] MPaVH : Output Voltage [High Side] VDC
VL : Output Voltage [Low Side] VDC
Output Voltage (VH, VL)
Detected Pressure
(V3053)
SiEN30-602 Method of Checking The Inverter�s Power Transistors and Diode Modules
Appendix 289
7. Method of Checking The Inverter�s Power Transistors and Diode Modules
[In case of YL (3ph, 380V, 60Hz) power supply]Please conduct followings before checking (1) Make the outside unit power off.(2) Disconnect the electric wiring connected to the power transistor and diode module.
Inverter PC board (A2P)
X11A
U
P1
Electronic circuit
Inverter P.C.Board
P2IGBT
X11A
U V W
L1
L2
L3
X10A
DM
N3
Fasten TabK2
K2
P3 V W
PC0409
Pin
P2
J1
P1
P3
N3
(V2895)
J2
J3
J1
J2
J3
Method of Checking The Inverter�s Power Transistors and Diode Modules SiEN30-602
290 Appendix
Power Transistor IGBT (On Inverter PC Board)
(Decision) If other than given above, the power unit is defective and must be replaced.
Note: Above figures are measured by analogue tester. Make sure to set �Tester Range� to �x 1k�.
Diode Module
(Decision)If other than given above, the diode module is defective and must be replaced.
Note: Above figures are measured by analogue tester. Make sure to set �Tester Range� to �x 1k�.
[In case of TL (3ph, 220V, 60Hz) power supply]Please conduct following before checking
(1) Make the outside unit power off.(2) Disconnect the electric wiring connected to the power transistor and diode module.
++
++
Resistance
P3 U 9±6Ω x 1k N3 U 17±12Ω x 1k
“ V 9±6Ω x 1k “ V 17±12Ω x 1k
“ W 9±6Ω x 1k “ W 17±12Ω x 1kU P3 17±12Ω x 1k U N3 9±6Ω x 1kV “ 17±12Ω x 1k V “ 9±6Ω x 1kW “ 17±12Ω x 1k W “ 9±6Ω x 1k
Tester Range Resistance Tester Range
(V2896)
++
++
ResistanceP1 J1 9±6Ω x 1k N3 J1 � x 1kP1 J3 9±6Ω x 1k “ J3 � x 1kP1 J2 9±6Ω x 1k “ J2 � x 1kJ1 P1 � x 1k L1 N3 9±6Ω x 1kJ3 P1 � x 1k L2 N3 9±6Ω x 1kJ2 P1 � x 1k L3 N3 9±6Ω x 1k
Tester Range Resistance Tester Range
(V2897)
SiEN30-602 Method of Checking The Inverter�s Power Transistors and Diode Modules
Appendix 291
[In case of TL (3ph, 220V, 60Hz) power supply]Please conduct followings before checking. (1) Make the outside unit power off.(2) Disconnect the electric wiring connected to the power transistor and diode module.
P3P3P3UVWN3N3N3UVW
UVWP3P3P3UVWN3N3N3
10~20(∗1)10~20(∗1)10~20(∗1)
100~300k→∞ (∗2)100~300k→∞ (∗2)100~300k→∞ (∗2)100~300k→∞ (∗2)100~300k→∞ (∗2)100~300k→∞ (∗2)
10~20(∗1)10~20(∗1)10~20(∗1)
×1K×1K×1K×1M×1M×1M×1M×1M×1M×1K×1K×1K
Tester electrode + Tester electrode – Tester rangeResistance ΩP1P1P1
HSRBHSSBHSTB
N3N3N3
HSRBHSSBHSTB
HSRBHSSBHSTB
P1P1P1
HSRBHSSBHSTB
N3N3N3
10~20(∗1)10~20(∗1)10~20(∗1)
∞ (∗2)∞ (∗2)∞ (∗2)∞ (∗2)∞ (∗2)∞ (∗2)
10~20(∗1)10~20(∗1)10~20(∗1)
×1K×1K×1K×1K×1K×1K×1K×1K×1K×1K×1K×1K
Tester electrode + Tester electrode – Tester rangeResistance Ω
WVU
L1
L2
L3
N3
P3IGBT
P2P1DM
HSRB
HSSB
HSTB
[Checking procedure]
�Power transistor[Judgment criteria]Values for each phase in ∗1 and ∗2 in the following table must be the same.
<The conditions that must be judged as the same value>1 The difference in resistance among each phase in ∗1 is 10Ω or less.2 The difference in resistance among each phase in ∗2 is 200Ω or less.
�Diode module[Judgment criteria]Values for each phase in ∗1 and ∗2 in the following table must be the same.
<The conditions that must be judged as the same value>1 The difference in resistance among each phase in ∗1 is 10Ω or less.2 All of the resistances of each phase in ∗2 is ∞Ω.
Printed Circuit Board Circuit Diagram
∗ When a digital tester is used, “∞” and “continuity” may be switched.
SiEN30-602
Precautions for New Refrigerant (R-410A) 293
Part 9Precautions for NewRefrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................2941.1 Outline ..................................................................................................2941.2 Refrigerant Cylinders............................................................................2961.3 Service Tools........................................................................................297
Precautions for New Refrigerant (R-410A) SiEN30-602
294 Precautions for New Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A)1.1 Outline1.1.1 About Refrigerant R-410A
! Characteristics of new refrigerant, R-410A1. Performance
Almost the same performance as R-22 and R-407C2. Pressure
Working pressure is approx. 1.4 times more than R-22 and R-407C.3. Refrigerant composition
Few problems in composition control, since it is a Quasi-azeotropic mixture refrigerant.
H1. Non-azeotropic mixture refrigerant: mixture of two or more refrigerants having different boiling points.
H2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar boiling points.
H3. The design pressure is different at each product. Please refer to the installation manual for each product.
(Reference) 1 MPa 10.19716 kgf / cm2
HFC units (Units using new refrigerants) HCFC unitsRefrigerant name R-407C R-410A R-22
Composing substances
Non-azeotropic mixture of HFC32, HFC125 and HFC134a (*1)
Quasi-azeotropic mixture of HFC32 and JFC125 (*1)
Single-component refrigerant
Design pressure3.2 MPa (gauge pressure) = 32.6 kgf/cm2
4.0 MPa (gauge pressure) = 40.78 kgf/cm2
2.75MPa (gauge pressure) = 28.0 kgf/cm2
Refrigerant oil Synthetic oil (Ether) Mineral oil (Suniso)Ozone destruction
factor (ODP) 0 0 0.05
Combustibility None None NoneToxicity None None None
Pressure-Enthalpy curves of HFC-32/125 (50/50wt%)
SiEN30-602 Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 295
! Thermodynamic characteristic of R-410A
Temperature(°C)
Steam pressure (kPa)
Liquid Vapor
Density (kg/m3 )
Liquid Vapor
Specific heat at constant pressure (kJ/kgK)Liquid Vapor
Specific enthalpy (kJ/kg)
Liquid Vapor
Specific entropy(kJ/KgK)
Liquid Vapor
Precautions for New Refrigerant (R-410A) SiEN30-602
296 Precautions for New Refrigerant (R-410A)
1.2 Refrigerant Cylinders! Cylinder specifications2 The cylinder is painted refrigerant color (pink).2 The cylinder valve is equipped with a siphon tube.
! Handling of cylinders(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in handling them. Before using, refer to the High-Pressure Gas Safety Law.The Law stipulates standards and regulations that must be followed to prevent accidents with high-pressure gases. Be sure to follow the regulations.
(2) Handing of vesselsSince R-410A is high-pressure gas, it is contained in high-pressure vessels.Although those vessels are durable and strong, careless handling can cause damage that can lead to unexpected accidents. Do not drop vessels, let them fall, apply impact or roll them on the ground.
(3) StorageAlthough R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark place in the same way as any other high-pressure gases.It should also be noted that high-pressure vessels are equipped with safety devices that releases gas when the ambient temperature reaches more than a certain level (fusible plug melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
Refrigerant can be charged in liquid state with cylinder in upright position.
Caution: Do not lay cylinder on its side during charging, since it cause refrigerant in gas state to enter the system.
Sip
hon
tube
Cylinder
SiEN30-602 Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 297
1.3 Service ToolsR-410A is used under higher working pressure, compared to previous refrigerants (R-22,R-407C). Furthermore, the refrigerating machine oil has been changed from Suniso oil to Ether oil, and if oil mixing is occurred, sludge results in the refrigerants and causes other problems. Therefore, gauge manifolds and charge hoses that are used with a previous refrigerant (R-22,R-407C) can not be used for products that use new refrigerants.Be sure to use dedicated tools and devices.
! Tool compatibility
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of charge hose.
! Copper tube material and thickness
* O: Soft (Annealed)H: Hard (Drawn)
ToolCompatibility
Reasons for changeHFC HCFCR-410A R-407C R-22
Gauge manifoldCharge hose 5
2Do not use the same tools for R-22 and R-410A.
2Thread specification differs for R-410A and R-407C.
Charging cylinder 5 " 2Weighting instrument used for HFCs.Gas detector " 5 2The same tool can be used for HFCs.Vacuum pump(pump with reverse flow preventive function)
"2To use existing pump for HFCs,
vacuum pump adapter must be installed.
Weighting instrument "
Charge mouthpiece 5
2Seal material is different between R-22 and HFCs.
2Thread specification is different between R-410A and others.
Flaring tool (Clutch type) " 2For R-410A, flare gauge is necessary.Torque wrench " 2Torque-up for 1/2 and 5/8Pipe cutter "
Pipe expander "
Pipe bender "
Pipe assembling oil 5 2Due to refrigerating machine oil change. (No Suniso oil can be used.)
Refrigerant recovery device Check your recovery device.
Refrigerant piping See the chart below. 2Only φ19.1 is changed to 1/2H material while the previous material is "O".
Pipe size
φ6.4φ9.5
φ12.7φ15.9φ19.1φ22.2φ25.4φ28.6φ31.8φ38.1φ44.5
Ve-upR-407C
Material
OOOOO
1/2H1/2H1/2H1/2H1/2H1/2H
Ve-upIIR-410A
Material
OOOO
1/2H1/2H1/2H1/2H1/2H1/2H1/2H
Thickness t (mm)
0.80.80.81.01.01.01.01.01.21.41.6
Thickness t (mm)
0.80.80.81.01.01.01.01.01.11.41.6
Precautions for New Refrigerant (R-410A) SiEN30-602
298 Precautions for New Refrigerant (R-410A)
1. Flaring tool
! Specifications2 Dimension A
! Differences2 Change of dimension A
Conventional flaring tools can be used when the work process is changed. (change of work process) Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.(For clutch type only) Conventional tool with pipe extension margin adjustment can be used.
Flare gauge
Nominal size
1/4
3/8
1/2
5/8
3/4
Tube O.D.
Do
6.35
9.52
12.70
15.88
19.05
Class-2 (R-410A)
9.1
13.2
16.6
19.7
24.0
Class-1 (Conventional)
9.0
13.0
16.2
19.4
23.3
+0-0.4
Unit:mm
A
Dimension A
For class-1: R-407CFor class-2: R-410A
SiEN30-602 Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 299
2. Torque wrench
! Specifications2 Dimension B Unit:mm
No change in tightening torqueNo change in pipes of other sizes
! Differences2 Change of dimension B
Only 1/2", 5/8" are extended
3. Vacuum pump with check valve
! Specifications2 Discharge speed ) Maximum degree of vacuum
50 l/min (50Hz) Select a vacuum pump which is able to keep60 l/min (60Hz) the vacuum degree of the system in excess of
2 Suction port UNF7/16-20(1/4 Flare) �100.7 kPa (5 torr � 755 mmHg).UNF1/2-20(5/16 Flare) with adapter
! Differences2 Equipped with function to prevent reverse oil flow2 Previous vacuum pump can be used by installing adapter.
Nominal size Class-1 Class-2 Previous1/2 24 26 245/8 27 29 27
Dimension B
For class-1: R-407CFor class-2: R-410A
Vacuum pump adapterReverse flow preventive vacuum adapter
Precautions for New Refrigerant (R-410A) SiEN30-602
300 Precautions for New Refrigerant (R-410A)
4. Leak tester
! Specifications2 Hydrogen detecting type, etc.2 Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
! Differences2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
5. Refrigerant oil (Air compal)
! Specifications2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.2 Offers high rust resistance and stability over long period of time.
! Differences2 Can be used for R-410A and R-22 units.
6. Gauge manifold for R-410A
! Specifications2 High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)2 Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)2 1/4" → 5/16" (2min → 2.5min)2 No oil is used in pressure test of gauges.
→ For prevention of contamination
SiEN30-602 Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 301
2 Temperature scale indicates the relationship between pressure and temperature in gas saturated state.
! Differences2 Change in pressure2 Change in service port diameter
7. Charge hose for R-410A
! Specifications2 Working pressure 5.08 MPa (51.8 kg/cm2)2 Rupture pressure 25.4 MPa (259 kg/cm2)2 Available with and without hand-operate valve that prevents refrigerant from outflow.
! Differences2 Pressure proof hose2 Change in service port diameter2 Use of nylon coated material for HFC resistance
8. Charging cylinder
! Specifications2 Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
! Differences2 The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is generated inside charging cylinder.
(Hose with ball valve)
Can not be used
SiEN30-602
Drawings & Flow Charts 303
Drawings & Flow ChartsAAbnormal Discharge Pipe Temperature ...............185Actuation of High Pressure Switch .......................177Actuation of Low Pressure Sensor .......................179Address Duplication of Centralized
Controller ......................................................220Address Duplication, Improper Setting ........ 229, 236
BBRC4C type .........................................................104BRC7E type .........................................................104BSVQ36, 60M ........................................................44
CCentralized Control Group No. Setting .................111
BRC1A Type ..................................................111BRC7C Type .................................................112Group No. Setting Example ...........................112
Check Operation not executed ............................210Compressor Motor Lock .......................................181Contents of Control Modes ..................................113
DDisplay �Under Host Computer Integrate Control�
Blinks (Repeats Double Blink) ......................242Display �Under Host Computer Integrate Control�
Blinks (Repeats Single Blink) ........................239Drain Level above Limit .......................................170Drain Pump Control ...............................................87
When the Float Switch is Tripped and �AF� is Displayed on the Remote Control .......88
When the Float Switch is Tripped During Cooling OFF by Thermostat ............................87
When the Float Switch is Tripped During Heating Operation ............................................88
When the Float Switch is Tripped While the Cooling Thermostat is ON ..................87
EElectronic expansion Valve Control .......................93Error of External Protection Device ......................158
FFan Motor (M1F) Lock, Overload .........................162Field Setting from Outside Unit ............................115
Mode changing procedure .............................116Setting by dip switches ..................................115
Freeze Prevention ..................................................96Functional Parts Layout .........................................45
HHeater Control ........................................................94Hot Start Control (In Heating Operation Only) .......93
IImproper Combination of Optional Controllers for
Centralized Control .............................. 227, 234Inverter Compressor Abnormal ........................... 198Inverter Current Abnormal ................................... 199Inverter Over-Ripple Protection ........................... 203Inverter Start up Error ......................................... 200
LList of Swing Flap Operations ............................... 95Louver Control for Preventing Ceiling Dirt ............. 89Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure ............. 205
MMalfunction of Capacity
Determination Device ................................... 171Malfunction of Discharge
Pipe Pressure Sensor .................................. 195Malfunction of Discharge
Pipe Thermistor (R3T) ................................. 190Malfunction of Drain Level
Control System (S1L) ................................... 160Malfunction of Heat Exchanger
Gas Pipe Thermistor (R4T) .......................... 191Malfunction of Inverter Radiating Fin
Temperature Rise (R1T) .............................. 197Malfunction of Inverter Radiating Fin
Temperature Sensor .................................... 204Malfunction of Liquid Pipe Thermistor (R6T) ....... 193Malfunction of Moving Part of
Electronic Expansion Valve (20E) ................ 168Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y3E) ...... 183Malfunction of Sub Cooling Heat Exchanger
Outlet Thermistor (R5T) ............................... 194Malfunction of Suction
Pipe Pressure Sensor .................................. 196Malfunction of Swing Flap Motor (MA) ................ 166Malfunction of System, Refrigerant System
Address Undefined ...................................... 224Malfunction of Thermistor
(R1T) for Suction Air .................................... 174Malfunction of Thermistor
(R2T) for Heat Exchanger ............................ 172Malfunction of Thermistor
(R2T) for Suction Pipe ................................. 192Malfunction of Thermistor
(R3T) for Gas Pipes ..................................... 173Malfunction of Thermostat Sensor in Remote Control
175Malfunction of Transmission Between Centralized
Controller and Indoor Unit .................... 221, 230Malfunction of Transmission Between Indoor and
Outside Units in the Same System .............. 217
SiEN30-602
304 Drawings & Flow Charts
Malfunction of TransmissionBetween Indoor Units ....................................211
Malfunction of Transmission Between Inverter and Control PC Board ..........................................201
Malfunction of Transmission Between Master and Slave Remote Controls .................................216
Malfunction of Transmission BetweenOptional Controllers forCentralized Control .............................. 226, 233
Malfunction of Transmission BetweenOutside Units ................................................214
Malfunction of Transmission Between Remote Control and Indoor Unit .................................213
Malfunction of Water system ................................188Method of Checking The Inverter�s Power Transistors
and Diode Modules .......................................289
OOperation Lamp Blinks .........................................237Operation of the Remote Control�s Inspection / Test
Operation Button ...........................................150Outside Unit PC Board Layout .............................102Outside Unit Rotation .............................................86
PPC Board Defect ......................... 159, 176, 225, 232Piping Diagrams ...................................................254
BS Units .........................................................255Indoor Unit .....................................................256Outside Units .................................................254
Power Supply Insufficient orInstantaneous Failure ...................................208
Pressure Sensor ..................................................288Procedure for Mounting / Dismounting of
Switch Box ....................................................250Procedure for Dismounting ............................250Procedure for Mounting .................................250
RRefrigerant Overcharged .....................................186Refrigerant System not Set, Incompatible
Wiring/Piping .................................................223Remote Control Self-Diagnosis Function .............153Remote Control Service Mode .............................151Reverse Phase, Open Phase ..............................207RWEYQ10MYL, TL ................................................45
SSelf-diagnosis by Wired Remote Control .............146Self-diagnosis by Infrared Remote Control ..........147Setting of Demand Operation ..............................130
Image of operation in the case of A ...............132Image of operation in the case of A and B ....132Image of operation in the case of B ...............132
Setting of Refrigerant Additional Charging Operation ......................................................134Check Operation ............................................139In the Case of Multi-Outside-Unit System .....140
Simplified Remote Control ...................................105BRC2A51 .......................................................105BRC2C51 ......................................................105
TTest Operation ...................................................... 98Thermostat Control in Dry Operation .................... 92Thermostat Control While in Normal Operation .... 92Thermostat Sensor in Remote Control .................. 90
Cooling ............................................................ 90Heating ........................................................... 91
Troubleshooting (OP:Central Remote Control) ............................... 225Schedule Timer) ........................................... 230Unified ON/OFF Controller) .......................... 237
Troubleshooting by Remote Control ................... 145
WWired Remote Control ......................................... 103Infrared Remote Control - Indoor Unit ................. 104
BRC7C type .................................................. 104Wiring Diagrams .................................................. 258
BS Unit .......................................................... 264Indoor Unit .................................................... 265Outside Unit .................................................. 258Outside Unit Field Wiring .............................. 260
SiEN30-602
Index i
IndexAA0 .........................................................................158A1 .........................................................................159A3 .........................................................................160A6 .................................................................162, 163A7 .........................................................................166A9 .........................................................................168Abnormal Discharge Pipe Temperature ...............185Abnormal Indoor Fan Motor .................................163About Refrigerant R-410A ....................................294Actuation of High Pressure Switch .......................177Actuation of Low Pressure Sensor .......................179Address Duplication of Centralized
Controller ......................................................220Address Duplication, Improper Setting .........229, 236AF .........................................................................170AJ .........................................................................171Auto restart after power failure reset ....................108
BBSVQ36, 60M ........................................................44
CC4 .........................................................................172C5 .........................................................................173C9 .........................................................................174Centralized Control Group No. Setting .................111Check Operation ..................................................100Check Operation not executed .............................210CJ .........................................................................175Compressor Motor Lock .......................................181Contents of Control Modes ..................................113Cool / Heat Mode Switching
(In case of heat pump connection) ................125Cool / Heat Mode Switching (In case of heating
and simultaneous cooling / heating) operation connection .....................................................124
DDetailed Explanation of Setting Modes ................108Discharge Pipe Protection Control .........................77Display �Under Host Computer Integrate Control�
Blinks (Repeats Double Blink) ......................242Display �Under Host Computer Integrate Control�
Blinks (Repeats Single Blink) ........................239Drain Level above Limit ........................................170Drain Pump Control ................................................87
EE1 .........................................................................176E3 .........................................................................177E4 .........................................................................179E5 .........................................................................181E9 .........................................................................183Error of External Protection Device ......................158
FF3 ........................................................................ 185F6 ........................................................................ 186Fan Motor (M1F) Lock, Overload ........................ 162Field Setting ........................................................ 103Field Setting from Outside Unit ........................... 115
Setting by dip switches ................................. 115Setting by pushbutton switches .................... 116
Field Setting from Remote Control ...................... 103Filter Sign Setting ................................................ 108Freeze Prevention ................................................. 96Functional Parts Layout ........................................ 45
HHigh Pressure Protection Control .......................... 74HJ ........................................................................ 188
IImproper Combination of Optional Controllers for
Centralized Control .............................. 227, 234Inverter Compressor Abnormal ........................... 198Inverter Current Abnormal ................................... 199Inverter Over-Ripple Protection ........................... 203Inverter Protection Control .................................... 78Inverter Start up Error ......................................... 200
JJ3 ........................................................................ 190J4 ........................................................................ 191J5 ........................................................................ 192J7 ........................................................................ 193J9 ........................................................................ 194JA ........................................................................ 195JC ........................................................................ 196
LL4 ........................................................................ 197L5 ........................................................................ 198L8 ........................................................................ 199L9 ........................................................................ 200LC ........................................................................ 201List of Electrical and Functional Parts ................. 279
Indoor Unit .................................................... 280Outside Unit .................................................. 279
Louver Control for Preventing Ceiling Dirt ............. 89Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure .............. 205Low Pressure Protection Control .......................... 75
MM1 ............................................................... 225, 232M8 ............................................................... 226, 233MA ............................................................... 227, 234Malfunction code indication by
outside unit PCB .......................................... 156
SiEN30-602
ii Index
Malfunction of CapacityDetermination Device ....................................171
Malfunction of DischargePipe Pressure Sensor ...................................195
Malfunction of Discharge PipeThermistor (R3T) ...........................................190
Malfunction of Drain LevelControl System (S1L) ....................................160
Malfunction of Heat Exchanger Gas PipeThermistor (R4T) ...........................................191
Malfunction of Inverter Radiating Fin Temperature Rise (R1T) .....................................................197
Malfunction of Inverter Radiating Fin Temperature Sensor ...........................................................204
Malfunction of Liquid Pipe Thermistor (R6T) ........193Malfunction of Moving Part of Electronic Expansion
Valve (20E) ...................................................168Malfunction of Moving Part of Electronic Expansion
Valve (Y1E, Y2E) ..........................................183Malfunction of Sub Cooling Heat Exchanger Outlet
Thermistor (R5T) ...........................................194Malfunction of Suction Pipe Pressure Sensor ......196Malfunction of Swing Flap Motor (MA) .................166Malfunction of System, Refrigerant System Address
Undefined ......................................................224Malfunction of Thermistor (R1T) for
Suction Air .....................................................174Malfunction of Thermistor (R2T) for
Heat Exchanger ............................................172Malfunction of Thermistor (R2T) for
Suction Pipe ..................................................192Malfunction of Thermistor (R3T) for
Gas Pipes .....................................................173Malfunction of Thermostat Sensor in Remote Control
175Malfunction of Transmission Between
Centralized Controller andIndoor Unit ............................................221, 230
Malfunction of Transmission Between Indoor and Outside Units in the Same System ...............217
Malfunction of Transmission BetweenIndoor Units ...................................................211
Malfunction of Transmission Between Inverter and Control PC Board ..........................................201
Malfunction of Transmission Between Master and Slave Remote Controls .................................216
Malfunction of Transmission Between Optional Controllers for Centralized Control ........226, 233
Malfunction of Transmission BetweenOutside Units ................................................214
Malfunction of Transmission Between Remote Control and Indoor Unit .................................213
Malfunction of Water system ................................188MC ................................................................229, 236Method of Checking The Inverter�s
Power Transistors and Diode Modules .........289
NNormal Control .......................................................69Normal Operation ...................................................60
OOperation Lamp Blinks ........................................ 237Operation Mode .................................................... 59Option List ........................................................... 285Outside Unit PC Board Layout ............................ 102
PP1 ........................................................................ 203P4 ........................................................................ 204PC Board Defect ......................... 159, 176, 225, 232Power Supply Insufficient or
Instantaneous Failure ................................... 208Precautions for New Refrigerant (R-410A) .......... 294Pressure Sensor ................................................. 288Protection Control ................................................. 74
RRefrigerant Circuit ................................................. 42
BSVQ36, 60M ................................................. 44RWEYQ10MYL, TL ......................................... 42
Refrigerant Cylinders .......................................... 296Refrigerant Flow for Each Operation Mode ........... 47
In Case of Heat Pump Connection ................. 47In Case of Heat Recovery Connection
(3 Outside units Connection.) ............ 53In Case of Heat Recovery Connection
(One Outside Unit Installation) ........... 49Refrigerant Overcharged ..................................... 186Refrigerant System not Set, Incompatible Wiring/
Piping ........................................................... 223Reverse Phase, Open Phase .............................. 207RWEYQ10MYL, TL ............................................... 45
SService Tools ...................................................... 297Setting Contents and Code No. .......................... 106Setting of Demand Operation .............................. 130Setting of Refrigerant Additional
Charging Operation ...................................... 134Special Operation .................................................. 80Specifications ........................................................ 16
BS Units .......................................................... 17Indoor Units .................................................... 18Outside Units .................................................. 16
Standby ................................................................. 65Startup Control ...................................................... 66Stop ....................................................................... 62
TTest Operation ...................................................... 98
Procedure and Outline .................................... 98Thermistor Resistance / Temperature
Characteristics ............................................. 286Thermostat Sensor in Remote Control .................. 90Troubleshooting (OP:
Central Remote Control) ............................... 225Schedule Timer) ........................................... 230Unified ON/OFF Controller) .......................... 237
UU0 ........................................................................ 205
SiEN30-602
Index iii
U1 .........................................................................207U2 .........................................................................208U3 .........................................................................210U4 .........................................................................211U5 .........................................................................213U7 .........................................................................214U8 .........................................................................216U9 .........................................................................217UA ........................................................................219UC ........................................................................220UE ................................................................221, 230UF ........................................................................223UH ........................................................................224
ÉSiEN30-602GËÍ
ISO14001 assures an effective environmentalmanagement system in order to help protect human healthand the environment from the potential impact of ouractivities, products and services and to assist inmaintaining and improving the quality of the environment.
Daikin Europe N.V. is approved by LRQA for its QualityManagement System in accordance with the ISO9001standard. ISO9001 pertains to quality assurance regardingdesign, development, manufacturing as well as to servicesrelated to the product.
Daikin units comply with the European regulations thatguarantee the safety of the product.
SiEN
30-6
02 �
12/20
07 �
Copy
right
© D
aikin
Prep
ared
in B
elgium
by La
nnoo
(ww
w.lan
noop
rint.b
e), a
comp
any w
hose
conc
ern f
orthe
envir
onmo
nt is
set in
the E
MAS
and I
SO 14
001 s
ystem
s. Re
spon
sible
Edito
r: Da
ikin E
urop
e N.V
., Zan
dvoo
rdes
traat
300,
B- 84
00 O
osten
de
The present publication is drawn up by way of information only and does notconstitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. hascompiled the content of this publication to the best of its knowledge. Noexpress or implied warranty is given for the completeness, accuracy,reliability or fitness for particular purpose of its content and the products andservices presented therein. Specifications are subject to change withoutprior notice. Daikin Europe N.V. explicitly rejects any liability for any direct orindirect damage, in the broadest sense, arising from or related to the useand/or interpretation of this publication. All content is copyrighted by DaikinEurope N.V..
Daikin�s unique position as a manufacturer of airconditioning equipment, compressors andrefrigerants has led to its close involvement inenvironmental issues. For several years Daikin hashad the intension to become a leader in the provisionof products that have limited impact on theenvironment. This challenge demands the eco designand development of a wide range of products and anenergy management system, resulting in energyconservation and a reduction of waste.
VRV products are not within the scope of the Euroventcertification programme.
Naamloze VennootschapZandvoordestraat 300B-8400 Oostende - Belgiumwww.daikin.euBTW: BE 0412 120 336RPR Oostende