Siemens 7SS52 TNBGuidebook

Chapter 1.2 - Current Differential Relay (RED670)

Substation: 275/33kV Murum Junction Substation

Bay Name: 275kV Murum A OHL FeederCT Ratio: 2500/1 Class: 5P20VT Ratio: 275000/110References: ABB RED670 Instruction Manual

1. Line Data

DescriptionBakun-Murum JunctionMurum-Murum JunctionSimilajau-Murum Junction

Positive SequenceR1ohm/km0.01900.01900.0190

X1ohm/km0.24630.24630.2463

C1nF/km14.802414.802414.8024

Calculated Xc1Megaohm.km0.21500.21500.2150

Zero SequenceR0ohm/km0.20790.20790.2079

(for single line)X0ohm/km0.77580.77580.7758

C0nF/km8.70318.70318.7031

Calculated Xc0Megaohm.km0.36570.36570.3657

Mutual coupling resistanceR0mohm/km0.18790.18790.1879

Mutual coupling reactanceX0mohm/km0.44050.44050.4405

Line distancekm20.78047.62690.450

2. Protection Scheme

Differential protection is set as a main protection which is have a duplicate protection interface channel (2Mbit/s).

Back up Distance is set for 4 zone quad characteristic for both phase and earth faultsi. Set Zone 1 Forward direction to cover 85% of the total line impedance, zone 1 will trip instantaneous but activate when both Main 1 and Main 2 protection relay fail or total communication channel fail.

ii. Set Zone 2 Forwad direction to cover 120% of the total line impedance. Delay 0.30s.

iii. Set Zone 3 Forward direction to cover 180% of the total line impedance. Delay 0.9s.

iv. Set Zone 4 Reverse direction to cover 40% of the total line impedance. Delay 1.0s.

v. Enable VT supervision blocking of distance protectionvi. Enable power swing blocking (PSB)

vii. Enable distance SOTF to trip fault upon energizing.Note: No carrier for distance protection.

Back up Directional Earth Fault is set to trip on delay 2.00s without carrier, instead of instantaneous trip with carrier received. All backup protection trip such as distance operate, DEF operate, CBF operate, OC operate and BBP operate will initiate direct intertrip send to remote end via signal protection interface Main 1 relay and Main 2 relay.

3. Differential Protection

Description of the restrained and the unrestrained operate characterictics Where;

4. Back Up Distance Protection i. Line Parameter NameLength (km)ImpR ()X ()Z ()Angle(o)Calculated

I c (A)Remarks

Line Murum Junction Murum Hydro

47.626

Z10.904911.730211.7785.5835.187-

Z09.901436.948338.2574.99N/R-

Max arc resistance = N/A pri ohm

Max tower footing resistance = N/A pri ohm

Note:

(R1=0.0190 Ohm/km, X1=0.2463 Ohm/km; R0=0.2079 Ohm/km, X0=0.7758 Ohm/km)

ICharg = U / (3 XC)

= U / (3 / 2fC)

= U (2fC / 3)

= (2/3) UfC

= (3.63) x U x f x C

Where:

U is system voltage

XC is capacitive positive sequence reactance of the line

f is system frequency

C is positive sequence line capacitanceThus,

Ic = (3.63) (275kV) (50Hz) (14.8024 nF/km) (47.626 km) = 35.187 A

Ic (sec) = 35.187 /2500

= 0.014 A

ii. Distance Characteristic

Characteristic for the phase-to-earth measuring loops Characteristic for the phase-to-phase measuring loopsiii. Distance Zone Setting Calculation

The zones are set directly in primary ohms R,X.

Rf/X factor: typically 2/1.5 for long lines and 4-6 for short lines but shall be set less then 8.*Set the Rf/X factor giving the Phf resistive coverage: 2*Set the Rf/X factor giving the EF resistive coverage : 2

Resistive reach for Phase fault (RFPP) is set to Rf/X factor times X1 of each respective Zone resistive reach for earth fault (RFPE) is set to Rf/X factor times (1+KN)X1 of each

respective Zone, where KN = (Z0 Z1)/3Z1iv. Phase selection with Load Enchroachment (PPHS) Setting Calculation

Characteristic of FDPSDIS for phase-to-earth fault Characteristic of FDPSDIS for phase-to-phase fault Characteristic of FDPSDIS for 3 phase fault Characteristic of LOAD encroachment function PHS Setting For the Load Area

Take voltage violation 5%

|ZLmin|=U2min/Smax = (0.95 x 275 kV)2 / (1131.246 MVA) = 60.333

ArgLd = cos-1 (cos min )

= cos-1 0.939 = 20 o

RLdFw = 0.8(0.95x275kV)2 / (3 x 0.95 x 275kV x 2500A x 1) = 48.27 RLdRv = RLdFw = 48.27 RLmin = |ZLmin|.cos (max)

= (60.333) cos (20 o) = 56.69 Safety factor, KL :

For length 60km, KL = 0.8RLdOutFw = (0.8)(56.69 )

= 45.35

RLdOutRv = RLdOutFw = 45.35

RLdInFw = (0.8)(45.35) = 36.28 Limit for resistive reach:

AND

AND

PSB Characteristic

Setting Group N1: Differential Protection (PDIF, 87L) under general settingBasic parameter group settings for the Differential function

(Differential Protection setting (LDIF) under general setting

ParameterRangeStepDefaultProposeUnitDescription

NoOfTerminal23-22-Number of current terminals of the protected circuit

Chan2IsLocalNoYes-NoNo-2-nd local current connected to input channel 2, Yes/No

Ibase50.0-9999.90.13000.002500

ABase (reference) current of the differential protection

Setting Group N1: Differential Protection (PDIF, 87L) under group setting

Basic parameter group settings for the Differential function

(Differential Protection setting (LDIF) under group setting

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OnOn-Operation Off/On

IdMin0.20-2.000.010.30.2IBOper-restr charact., section 1 sensitivity, multiple IBase

IdMinHigh0.20-10.000.010.80.8IBInitial lower sensitivity, as multiple of IBase

tIdMinHigh0.000-60.0000.0011.0001.000sTime interval of initial lower sensitivity, in sec

IdUnre1.00-50.000.0110.0010.00IBUnrestrained differential current limit, multiple of IBase

NegSeqDiffEnOff

On-OnOn-Off/On selection for internal /external fault discriminator

NegSeqROA30.0-120.01.06060DegInternal/external fault discriminator Operate Angle, degrees

IMinNegSeq0.01-0.200.010.040.05IBMin. value of neg. seq. current as multiple of IBase

CrossBlockEnNoYes-NoNo-Off/On selection of the cross-block logic

ChargCurEnableOffOn-OffOff-Off/On selection for compensation of charging currents

AddDelayOff

On-OffOff-Off/On selection for delayed diff.trip command

IMaxAddDelay0.20-5.000.011.001.00IBBelow limit,extra delay can be applied, multiple of IBase

tDefTime0.000-6.0000.0010.0000.000sDefinite time additional delay in seconds

tMinInv0.001-6.0000.0010.0010.01sInverse Delay Minimum Time, in seconds

CurveTypeANSI Ext. inv

ANSI Very inv

ANSI Norm. inv

ANSI Mod.inv.

ANSI Def.Time

L.T.E. inv.

L.T.V. inv

L.T. inv

IEC Norm.inv

IEC Very inv.

IEC Inv

IEC Ext.inv.

IEC S.T.inv

IEC L.T. Inv

IEC Def.Time

Programmable

RI type

RD type-IEC Def.TimeIEC Def.Time-19 curve type. Example: 15 for definite time delay.

k0.05-1.100.011.001.00-Time Multiplier setting(TMS) for inverse delays

IdiffAlarm0.05-1.000.010.150.15IBSustained differential current alarm, factor of Ibase

tAlarmdelay0.000-60.0000.00110.00010.000SDelay for alarm due to sustained differential current, in s

Setting Group N1: Differential Protection (PDIF, 87L) under group setting (advanced)

Basic parameter group settings for the Differential function

(Differential Protection setting (LDIF) under group setting (advanced)

ParameterRangeStepDefaultProposeUnitDescription

EndSection10.20-1.500.011.250.60IBEnd of section 1, as multiple of reference current Ibase

EndSection21.00-10.000.013.002.50IBEnd of section 2, as multiple of reference current Ibase

SlopeSection210.0-50.00.140.050.0%Slope in section 2 of operate-restrain characteristic, in %

SlopeSection330.0-100.00.180.080.0%Slope in section 3 of operate-restrain characteristic, in %

I2/I1Ratio5.0-100.01.010.015%Max. ratio of 2nd harm. To fundamental harm dif.curr.in %

I5/I1Ratio5.0-100.01.025.025%Max. ratio of 5th harm. To fundamental harm dif.curr.in %

p0.01-10000.010.020.02-Settable curve parameter, user-programmable curve type

a0.01-10000.010.140.14-Settable curve parameter, user-programmable curve type

b0.01-10000.011.001.00-Settable curve parameter, user-programmable curve type

c0.01-10000.011.001.00-Settable curve parameter, user-programmable curve type

OpenCTEnableOff

On-OnOn-Open CTEnable Off/On

tOCTAlarmDelay0.100-10.0000.0011.0001.000sOpen CT: time in s to alarm after an open CT is detected

tOCTResetDelay0.100-10.0000.0010.2500.250sReset delay in s. After delay,diff. function is activated

Setting Group N1: Impedance Protection Distance Zones (PDIS, 21)Basic parameter group settings for the ZMQPDIS_21(ZM01-) function

(Distance measuring zones, quadrilateral characteristic (PDIS,21)

ParameterRangeStepDefaultProposeUnitDescription

OperationOffOn-OnOn-Operation Off/On

IBase1-99999130002500ABase current, i.e. rated current

UBase0.05-2000.000.05400.00275

kVBase voltage, i.e. rated voltage

OperationDirOff

Non-directional

Forward

Reserse-ForwardForward-Operation mode of directionality NonDir / Forw / Rev

X10.10-3000.000.0130.009.97

Ohm/pPositive sequence reactance reach

R10.10-1000.000.015.000.77

Ohm/p

Positive seq. resistance for zone characteristic angle

X00.10-9000.000.01100.0031.41Ohm/pZero sequence reactance reach

R00.50-3000.000.0115.008.42

Ohm/pZero seq. resistance for zone characteristic angle

RFPP1.00-3000.000.0130.0019.94Ohm/lFault resistance reach in ohm/loop, Ph-Ph

RFPE1.00-9000.000.01100.0034.50

Ohm/lFault resistance reach in ohm/loop, Ph-E

OperationPPOff

On-OnOn-Operation mode Off/On of Phase-Phase loops

Timer tPPOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-Ph

tPP0.000-60.0000.0010.0000.000

sTime delay of trip, Ph-Ph

Value depends on application

OperationPEOff

On-OnOn-Operation mode Off/On of Phase-Earth loops

Timer tPEOff

On-OnOn

-Operation mode Off/On of Zone timer,Ph-E

tPE0.000-60.0000.0010.0000.000

sTime delay of trip, Ph-E

Value depends on application

IMinOpPP10-3012010%IBMinimum operate delta current for Phase-Phase loops

IMinOpPE10-3012010%IBMinimum operate phase current for Phase-Earth loops

IMinOpIN5-30155%IBMinimum operate residual current for Phase-Earth loops

Basic parameter group settings for the ZMQPDIS_21(ZM02-) function

(Distance measuring zones, quadrilateral characteristic (PDIS,21)

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OnOn-Operation Off/On

IBase1-99999130002500ABase current, i.e. rated current

UBase0.05-2000.000.05400.00275

kVBase voltage, i.e. rated voltage

OperationDirOff

Non-directional

Forward

Reserse-ForwardForward-Operation mode of directionality NonDir / Forw / Rev

X10.10-3000.000.0130.0014.08

Ohm/pPositive sequence reactance reach

R10.10-1000.000.015.001.09

Ohm/p

Positive seq. resistance for zone characteristic angle

X00.10-9000.000.01100.0044.34

Ohm/pZero sequence reactance reach

R00.50-3000.000.0115.0011.88

Ohm/pZero seq. resistance for zone characteristic angle

RFPP1.00-3000.000.0130.0028.15

Ohm/lFault resistance reach in ohm/loop, Ph-Ph

RFPE1.00-9000.000.01100.0048.70Ohm/lFault resistance reach in ohm/loop, Ph-E

OperationPPOff

On-OnOn-Operation mode Off/On of Phase-Phase loops

Timer tPPOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-Ph

tPP0.000-60.0000.0010.0000.3

sTime delay of trip, Ph-Ph

OperationPEOff

On-OnOn-Operation mode Off/On of Phase-Earth loops

Timer tPEOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-E

tPE0.000-60.0000.0010.0000.3

sTime delay of trip, Ph-E

IMinOpPP10-3012010%IBMinimum operate delta current for Phase-Phase loops

IMinOpPE10-3012010%IBMinimum operate phase current for Phase-Earth loops

Basic parameter group settings for the ZMQPDIS_21(ZM03-) function

(Distance measuring zones, quadrilateral characteristic (PDIS,21)

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OnOn-Operation Off/On

IBase1-99999130002500ABase current, i.e. rated current

UBase0.05-2000.000.05400.00275

kVBase voltage, i.e. rated voltage

OperationDirOff

Non-directional

Forward

Reserse-ForwardForward-Operation mode of directionality NonDir / Forw / Rev

X10.10-3000.000.0130.0021.11

Ohm/pPositive sequence reactance reach

R10.10-1000.000.015.001.63

Ohm/p

Positive seq. resistance for zone characteristic angle

X00.10-9000.000.01100.0066.51

Ohm/pZero sequence reactance reach

R00.50-3000.000.0115.0017.82

Ohm/pZero seq. resistance for zone characteristic angle

RFPP1.00-3000.000.0130.0042.23

Ohm/lFault resistance reach in ohm/loop, Ph-Ph

RFPE1.00-9000.000.01100.0073.06

Ohm/lFault resistance reach in ohm/loop, Ph-E

OperationPPOff

On-OnOn-Operation mode Off/On of Phase-Phase loops

Timer tPPOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-Ph

tPP0.000-60.0000.0010.0000.900

sTime delay of trip, Ph-Ph

OperationPEOff

On-OnOn-Operation mode Off/On of Phase-Earth loops

Timer tPEOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-E

tPE0.000-60.0000.0010.0000.900

sTime delay of trip, Ph-E

IMinOpPP10-3012010%IBMinimum operate delta current for Phase-Phase loops

IMinOpPE10-3012010%IBMinimum operate phase current for Phase-Earth loops

Basic parameter group settings for the ZMQPDIS_21(ZM04-) function

(Distance measuring zones, quadrilateral characteristic (PDIS,21)

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OnOn-Operation Off/On

IBase1-99999130002500ABase current, i.e. rated current

UBase0.05-2000.000.05400.00275.00kVBase voltage, i.e. rated voltage

OperationDirOff

Non-directional

Forward

Reverse-ForwardReverse-Operation mode of directionality NonDir / Forw / Rev

X10.10-3000.000.0130.004.69

Ohm/pPositive sequence reactance reach

R10.10-1000.000.015.000.36

Ohm/p

Positive seq. resistance for zone characteristic angle

X00.10-9000.000.01100.0014.78

Ohm/pZero sequence reactance reach

R00.50-3000.000.0115.003.96

Ohm/pZero seq. resistance for zone characteristic angle

RFPP1.00-3000.000.0130.009.38

Ohm/lFault resistance reach in ohm/loop, Ph-Ph

RFPE1.00-9000.000.01100.0016.23

Ohm/lFault resistance reach in ohm/loop, Ph-E

OperationPPOff

On-OnOn-Operation mode Off/On of Phase-Phase loops

Timer tPPOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-Ph

tPP0.000-60.0000.0010.0001.000sTime delay of trip, Ph-Ph

OperationPEOff

On-OnOn-Operation mode Off/On of Phase-Earth loops

Timer tPEOff

On-OnOn-Operation mode Off/On of Zone timer,Ph-E

tPE0.000-60.0000.0010.0001.000

sTime delay of trip, Ph-E

IMinOpPP10-3012010%IBMinimum operate delta current for Phase-Phase loops

IMinOpPE10-3012010%IBMinimum operate phase current for Phase-Earth loops

Setting Group N1: Impedance Protection Phase Selection (PDIS, 21)- PHS1Basic parameter group settings for the FDPSPDIS_21(PHS--) function

ParameterRangeStepDefaultProposeUnitDescription

IBase1-99999130002500ABase current for current settings

UBase0.05-2000.000.05400.00275

kVBase voltage, i.e. rated voltage

INBlockPP10-10014040

%IPh3I0 limit for blocking phase-to-phase measuring loops

INReleasePE10-10012010

%IPh3I0 limit for releasing phase-to-earth measuring loops

RLdFw1.00-3000.000.0180.0048.27 Ohm/pForward resistive reach within the load impedance area

For load enchroachment Calc the max load imp, R

RLdRv1.00-3000.000.0180.00

48.27

Ohm/pReverse resistive reach within the load impedance area

For load enchroachment

ArgLd5-7013020DegLoad angle determining the load impedance area

For load enchroachment

X10.50-3000.000.0140.0030.40Ohm/pPositive sequence reactance reach 1.44 x Xmax

X00.50-3000.000.01120.0095.77Ohm/pZero sequence reactance reach 1.44 x Xmax

RFFwPP0.50-3000.000.0130.0052.79Ohm/lFault resistance reach Ph-Ph, forward 1.25 x RFPPZmax

RFRvPP0.50-3000.000.0130.0052.79Ohm/lFault resistance reach, Ph-Ph, reverse 1.25 x RFPPZmax

RFFwPE1.00-9000.000.01100.0091.32Ohm/lFault resistance reach, Ph-E, forward 1.25 x RFPEZmax

RFRvPE1.00-9000.000.01100.0091.32Ohm/lFault resistance reach, Ph-E, reverse 1.25 x RFPEZmax

Timer PPOff

On-OnOff-Operation mode Off/On of Zone timer,Ph-Ph

(Not used; For tripping purpose)

tPP0.000-60.0000.0010.0000.000sTime delay of trip, Ph-Ph

Timer PEOff

On-OnOff-Operation mode Off/On of Zone timer,Ph-E

(Not used; For tripping purpose)

tPE0.000-60.0000.0010.0000.000sTime delay of trip, Ph-E

IMinOpPP10-3012010%IBMinimum operate delta current for Phase-Phase loops

IMinOpPE10-301205

%IBMinimum operate phase current for Phase-Earth loops

Setting Group N1: Impedance Protection Directional Impedance (RDIR)- ZD01

Basic parameter group settings for the ZDRDIR (ZD01) function

(Distance measuring zones, quadrilateral characteristic (PDIS,21)

ParameterRangeStepDefaultProposeUnitDescription

ArgNegRes90-1751115115DegAngle to blinder in second quadrant for forward direction

Use default

ArgDir5-4511515DegAngle to blinder in fourth quadrant for forward direction

Use default

IMinOp1-9999911010%IBMinimum operate current in % of IBase

IBase1-99999130002500

ABase current

Use CT primary ratio

UBase0.05-2000.000.05400.00275.00

kVBase voltage

Use VT primary (Ph-Ph) ratio

Setting Group N1: Impedance Protection AutomaticSOTF (PSOF) SFV1

Basic parameter group settings for the ZCVPSOF (SFV1-) function

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OnON-Operation Off/On

IBase1-99999130002500

ABase current (A)

UBase0.05-2000.000.05400.00275.00

kVBase voltage L-L (kV)

ModeImpedance

UlLevel

UlLvl&Imp-UlLevelImpedance-Mode of operation of SOTF Function. Start by zone 2 non-dir. Refer to config ZM02-STND

AutoInitOff

On-OffOff

-Automatic switch onto fault initialization

IPh1 10011010%IBOperate level of phase current in % of

IBase

SealInOff

On -OnOn -Seal in functionality Off/On

USealln1 2500110001000%IBPhase current operate level for step3 in

% of IBase

t30.000 - 60.0000.0010.0000.000sDefinitive time delay of step 3

k30.05 - 999.000.010.050.05 -Time multiplier for the inverse time delay

for step 3

IMin31 - 100001100100%IB

Minimum operate current for step3 in %

of IBase

t3Min0.000 - 60.0000.0010.0000.000sMinimum operate time for inverse curves

for step 3

I3Mult1.0 - 10.00.12.02.0 -Multiplier for current operate level for

step 3

DirMode4Off

Non-directional

Forward

Reverse -Non-directionalNon-directional -Directional mode of step 4 (off, nodir,

forward, reverse)

Characterist4ANSI Ext. inv.

ANSI Very inv.

ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.

IEC Norm. inv.

IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.

IEC Def. Time

Reserved

Programmable

RI type

RD type -ANSI Def. TimeANSI Def. Time -Selection of time delay curve type for

step 4

I4>1 2500110001000%IBPhase current operate level for step4 in

% of IBase

t40.000 - 60.0000.0010.0000.000sDefinitive time delay of step 4

k40.05 - 999.000.010.050.05 -Time multiplier for the inverse time delay

for step 4

IMin41 - 100001100100%IB

Minimum operate current for step4 in %

of IBase

t4Min0.000 - 60.0000.0010.0000.000sMinimum operate time for inverse curves

for step 4

I4Mult1.0 - 10.00.12.02.0 -Multiplier for current operate level for

step 4

Setting Group N1: Current Protection- ResidualOverCurr4Step (PTOC,51N/67N)-TEF1Basic parameter group settings for the EF4PTOC_50N67N (TEF1-) function

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OffOn-Operation Off/On

Only used for DEFC

IBase1 99999130002500 ABase value for current settings

UBase0.05 - 2000.000.05400275kVBase value for voltage settings

AngleRCA-180 18016565DegRelay characteristic angle (RCA)

polMethodVoltage

Current

Dual -VoltageVoltage -Type of polarization

UPolMin1 100111%UBMinimum voltage level for polarization in

% of UBase

IPolMin2 100155%IBMinimum current level for polarization in

% of IBase.Typical 5-10% of I base

RNPol0.50 - 1000.000.015.001000.00ohmReal part of source Z to be used for

current polarisation

XNPol0.50 - 3000.000.0140.003000.00ohmImaginary part of source Z to be used for

current polarisation

IN>Dir1 10011020%IBResidual current level for Direction

release in % of IBase

2ndHarmStab5 - 10012015%Second harmonic restrain operation in %

of IN amplitude

BlkParTransfOff

On -OffOff -Enable blocking at parallel transformers

UseStartValueIN1>

IN2>

IN3>

IN4> -IN4>IN4> -Current level blk at parallel transf (step1,

2, 3 or 4)

SOTFOff

SOTF

UnderTime

SOTF&UnderTime -OffOff -SOTF operation mode (Off/SOTF/

Undertime/ SOTF&Undertime)

ActivationSOTFOpen

Closed

CloseCommand -OpenOpen -Select signal that shall activate SOTF

StepForSOTFStep 2

Step 3 -Step 2Step 2 -Selection of step used for SOTF

HarmResSOTFOff

On -OffOff -Enable harmonic restrain function in

SOTF

tSOTF0.000 - 60.0000.0010.2000.200sTime delay for SOTF

t4U0.000 - 60.0000.0011.0001.000sSwitch-onto-fault active time

DirMode1Off

Non-directional

Forward

Reverse-Non-directionalForward

-Directional mode of step1 (off, nodir, forward, reverse)

Characterist1ANSI Ext. inv.

ANSI Very inv.

ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.

IEC Norm. inv.

IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.

IEC Def. Time

Reserved

Programmable

RI type

RD type -ANSI Def. Time IEC Def. Time

-Time delay curve type for step 1

IN1>1 2500110010%IBOperate residual current level for step 1

in % of IBase

t10.000 - 60.0000.0010.0002.000sIndependent (defenite) time delay of step

1

k10.05 - 999.000.010.051.00 -Time multiplier for the dependent time

delay for step 1

t1Min0.000 - 60.0000.0010.00060.000sMinimum operate time for inverse curves

for step 1

IN1Mult1.0 - 10.00.12.010.0 -Multiplier for scaling the current setting

value for step 1

HarmRestrain1Off

On -OnOn -Enable block of step 1 from harmonic

Restrain

DirMode2Off

Non-directional

Forward

Reverse-Non-directionalOff

-Directional mode of step2 (off, nodir, forward, reverse)

Characterist2ANSI Ext. inv.

ANSI Very inv.

ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.

IEC Norm. inv.

IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.

IEC Def. Time

Reserved

Programmable

RI type

RD type -ANSI Def. Time IEC Def. Time

-Time delay curve type for step 2

IN2>1 2500110010%IBOperate residual current level for step 2

in % of IBase

t20.000 - 60.0000.0010.0002.000sIndependent (defenite) time delay of step

2

k20.05 - 999.000.010.05999.00 -Time multiplier for the dependent time

delay for step 2

t2Min0.000 - 60.0000.0010.00060.000sMinimum operate time for inverse curves

for step 2

IN2Mult1.0 - 10.00.12.010.0 -Multiplier for scaling the current setting

value for step 2

HarmRestrain2Off

On -OnOn -Enable block of step 2 from harmonic

Restrain

DirMode3Off

Non-directional

Forward

Reverse-Non-directionalOff

-Directional mode of step3 (off, nodir, forward, reverse)

Characterist3ANSI Ext. inv.

ANSI Very inv.

ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.

IEC Norm. inv.

IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.

IEC Def. Time

Reserved

Programmable

RI type

RD type -ANSI Def. Time ANSI Def. Time

-Time delay curve type for step 3

IN3>1 2500110033%IBOperate residual current level for step 3

in % of IBase

t30.000 - 60.0000.0010.0000.800SIndependent (defenite) time delay of step

3

k30.05 - 999.000.010.050.05 -Time multiplier for the dependent time

delay for step 3

t3Min0.000 - 60.0000.0010.0002.000SMinimum operate time for inverse curves

for step 3

IN3Mult1.0 - 10.00.12.02.0 -Multiplier for scaling the current setting

value for step 3

HarmRestrain3Off

On -OnOn -Enable block of step 3 from harmonic

Restrain

DirMode4Off

Non-directional

Forward

Reverse-Non-directionalOff

-Directional mode of step4 (off, nodir, forward, reverse)

Characterist4ANSI Ext. inv.

ANSI Very inv.

ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.

IEC Norm. inv.

IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.

IEC Def. Time

Reserved

Programmable

RI type

RD type -ANSI Def. Time ANSI Def. Time

-Time delay curve type for step 4

IN4>1 2500110013%IBOperate residual current level for step 4

in % of IBase

t40.000 - 60.0000.0010.0001.200SIndependent (defenite) time delay of step

4

k40.05 - 999.000.010.050.50 -Time multiplier for the dependent time

delay for step 4

t4Min0.000 - 60.0000.0010.0000.000SMinimum operate time for inverse curves

for step 4

IN4Mult1.0 - 10.00.12.02.0 -Multiplier for scaling the current setting

value for step 4

HarmRestrain4Off

On -OnOn -Enable block of step 4 from harmonic

Restrain

Setting Group N1: Current Protection- ThermalOverload1TimerConst(PTTR,26)

Basic parameter group settings for the LPTTR_26(THL1-) function

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OffOff-Operation Off/On

Not used.

IBase0 99999130002500ABase current in A

TRef0 60019090DegEnd temperature rise above ambient of

the line when loaded with IRef

IRef0 4001100100%IBThe load current (in %of IBase) leading

to TRef temperature

IMult1 5111 -Current multiplier when function is used

for two or more lines

Tau0 10001145MinTime constant of the line in minutes.

AlarmTemp0 20018080DegTemperature level for start (alarm)

TripTemp0 60019090DegTemperature level for trip

ReclTemp0 60017575DegTemperature for reset of lockout after trip

tPulse0.05 - 0.300.010.10.1sOperate pulse length. Minimum one

execution cycle

AmbiSensOff

On -OffOff -External temperature sensor availiable

DefaultAmbTemp-50 25012020DegAmbient temperature used when

AmbiSens is set to Off.

DefaultTemp-50 60015050DegTemperature raise above ambient

temperature at startup

Setting Group N1: Scheme communication-EFSchemeCommunication (PSCH,85)

Accelerated scheme for full distance with DEFC application

Basic parameter group settings for the ECPSCH_85(EFC1-) function

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OffOn

-Operation Off/On

Not used.

Scheme TypeOff

Intertrip

Permissive UR

Permissive OR

Blocking -Permissive URPermissive OR -Scheme type, Mode of Operation

tCoord0.000 - 60.0000.0010.0350.050sCommunication scheme coordination

time

tSendMin0.000 - 60.0000.0010.1000.100sMinimum duration of a carrier send signal

Setting Group N1: Logic-TripLogic(PTRC,94)

Basic parameter group settings for the SMPPTRC_94 (TRP1-)Function

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

On-OnOn-Operation Off / On

Program3 phase

1ph/3ph

1Ph/2Ph/3Ph-1ph/3ph1ph/3ph

Three ph; single or three

ph; single, two or three

ph trip

tTripMin0.000 - 60.0000.0010.1500.060

sMinimum duration of trip

output signal.

Use recommended

Setting Group N1: Logic-TripMatrix(GGIO)TR01

Basic parameter group settings for the TMAGGIO (TR01-) function

ParameterRangeStepDefaultProposeUnitDescription

OperationOff

ON-ONOn-Operation Off / On

PulseTime0.050 - 60.0000.0010.0000.150

sOutput pulse time

OnDelay0.000 - 60.0000.0010.0000.000sOutput on delay time

OffDelay0.000 - 60.0000.0010.0000.000sOutput off delay time

ModeOutput1Steady

Pulsed

-SteadySteady-Mode for output ,1 steady

or pulsed

ModeOutput2Steady

Pulsed

-SteadySteady-Mode for output 2, steady

or pulsed

ModeOutput3Steady

Pulsed

-SteadySteady-Mode for output 3, steady

or pulsed

EMBED Excel.Sheet.12

Page 1 of 30

Sheet1

%R1X1RFPP (2 x X1)R0X0RFPE [2x(1+KN) X1]Remarks

Line 0.904911.7302-9.9036.95-

Zone 1850.76929.970719.94138.4231.4134.4985

Zone 21201.085914.076228.152511.8844.3448.7038

Zone 31801.628821.114442.228717.8266.5173.0557

Zone 4400.36204.69219.38423.9614.7816.2346