11kv schemes 24th-25th april 2013
TRANSCRIPT
-
7/27/2019 11kv Schemes 24th-25th April 2013
1/14
Sl.
No:Drawing No. RPCL/Steag Comments BHEL Reply
1 35210078623-Sht 02Correct the CT Neutral formation in the GRP
differential relay connections.
Noted & incorporated.
2 35210078623-Sht 03Correct the CT Neutral formation in the GRP
REF relay connections.
Noted & incorporated.
3 35210078623-Sht 04Clarify the P1 philosophy P1 is always on the breaker side irrespective of power flow
direction.
4 35210078623-Sht 04Output contacts does not match with the
typical functions in relay catalogue.
Noted & incorporated.
5 35210078623-Sht 07Interlocks to other panels to be taken care of
in respective drawings.
Noted & incorporated.
6 35210078623-Sht 08Breaker in test,service,local,remote to ddcmis Noted & incorporated.
7 35210078623-Sht 14Correct the I/O list in all schemes to be revised. Noted & incorporated.
8 35210078624-Sht 08 86X contactor in incomer & Tie Feeder Noted & incorporated.
9 35210078624A-Sht 01
10 35210078625-Sht 01Wherever MCBs are given to be replaced with
fuse.
Noted & incorporated.
11 35210078626-Sht 01
12 35210078627-Sht 01
13 35210078628-Sht 01
14 35210078629-Sht 01
15 35210078630-Sht 01
16 35210078631-Sht 01
17 35210078632-Sht 01
18 35210078633-Sht 01
19 35210078634-Sht 01
20 35210078635-Sht 09
21 35210078636-Sht 09
22 35210078637-Sht 09
23 35210078637A-Sht 09
24 35210078638-Sht 10 Rename 27/27N/2M as 27/27N/2
BHEL REPLY DATED 25/04/2013 RPCL/STEAG COMMENTS ON 11kV SCHMATIC DRAWING REV 02
-
7/27/2019 11kv Schemes 24th-25th April 2013
2/14
reply to be given for output contact rating
-
7/27/2019 11kv Schemes 24th-25th April 2013
3/14
Sl. No: Drawing No. RPCL/Steag Comments BHEL Reply
1 35210078623-Sht 01
Schematic drawing shall be confirmed to logic
diagram of 11Kv switchgear & shall bementioned in the drawing
Drawing revised in line with revised 11kv
Logic diagram. Reference drawing no. of SLD& Logic shall be incorporated in revised/as
manufactured drawings
2 35210078623-Sht 01Furnish legend details Legend of devices submitted.
3 35210078623-Sht 01
Furnish BOM As per MOM Dtd 16-17th Nov'2012 pt 13
BOM shall be furnishede 3 weeks before
inspection.
4 35210078623-Sht 01Panel number mentioned here is not matched
with SLD
Drawing revised to incorporate the comment.
5 35210078623-Sht 01
The closing & tripping logic shall be hardwiredcontrol from ECP & DDCMIS seperately.
Remote closing /tripping shall be wired as
agreed in MOM dtd 4-6th june 2012.
Drawing revised to incorporate the comment.
6 35210078623-Sht 01Furnish CT & PT details in this drawing also for
easy reference.
Drawing revised to incorporate the comment.
7 35210078623-Sht 01
Furnish Numerical Relay connection diagram
for SEL 751A & 2505 indicating P.S , I/O Ports ,
CT/PT connections & communication ports.
Relay catalogue soft copy shall be sent by
15.02.2013.
8 35210078623-Sht 01
Furnish VCB breaker contact development
diagram indicating 94, 52a/b,33SC contact
configuration.
Shall be incorporated in revised/as
manufactured drawings.
9 35210078623-Sht 01Furnish OGA of VCB & details of FEB & BEB OGA of VCB & FEB/BEB Scheme submitted.
BHEL REPLY TO RPCL/STEAG COMMENTS ON 11kV SCHMATIC DRAWING Rev 00
-
7/27/2019 11kv Schemes 24th-25th April 2013
4/14
10 35210078623-Sht 01
Indicate reference drawings Shall be incorporated in revised drawings.
11 35210078623-Sht 02
Since the relay manufacturer is not indicated in
the keydiagram, calculations for the burden &
knee point voltage shall be provided.
Shall be furnished as agreed.
12 35210078623-Sht 02Note: Shorting links are to be removed when
CTs are connected in GRP circuit.
Drawing revised to incorporate the comment.
13 35210078623-Sht 04
R ,Y B Phase shall be shown It may please be noted that Bus PT voltage is
not required in IF scheme, as it requires only
line voltage, which is provided by Line PT
signals as shown in the scheme.Earlier it was
shown inadvertently & hence it has been
removed.
14 35210078623-Sht 042-50 LBB function shall be indicated Drawing revised to incorporate the comment.
15 35210078623-Sht 05
Indicate what are the parameters shown at
MFTD output.Furnish details of MFTD.
MFTD is Multifunction Transducer which
provides analog signals which can measure
active, reactive power & energy at ECP.
16 35210078623-Sht 05Digital multi function meter Drawing revised to incorporate the comment.
17 35210078623-Sht 05
Watt transducer indicated in SLD to be shown Multifunction transducer provided instead of
watt transducer which provides watt output
alongwith other analog signals.
18 35210078623-Sht 05 Current y phase shall be indicated. To be indicated in revised drawings.
19 35210078623-Sht 06
DC supply supervision 80D aux Contactor used for DC supply
supervision.Description will be indicated in
revised drawings.
-
7/27/2019 11kv Schemes 24th-25th April 2013
5/14
20 35210078623-Sht 06
240VAC shall be derived from 415/240 VAC
aux. transformer of adequate rating so as to
have fault isolation on sec side.
It may be noted that the 415V AC supply is
being fed from AC distribution SWBD. In case
of any short circuit, fuses at the AC
distribution SWBD shall be blown protecting
the bus.Also as the supply is taken from 1
phase & neutral alternately it will prevent theunbalance of current in a single phase.
21 35210078623-Sht 07
What is future interlock for FEB & BEB This future interlock is provided for any
interlock to be used in future at later stage.
22 35210078623-Sht 07Furnish FEB/BEB Scheme Scheme submitted
23 35210078623-Sht 07 Furnish the logic for this where it is derived Drawing revised to incorporate the comment.
24 35210078623-Sht 0786 not operated shall be taken for test closing
circuit
Drawing revised to incorporate the comment.
25 35210078623-Sht 08Furnish the details of planned logic where it is
derived
Planned Logic is derived in numerical relay &
the same has been furnished.
26 35210078623-Sht 0950LBB function of relay shall be indiacted. Drawing revised to incorporate the comment.
27 35210078623-Sht 09
LBB aux relay shall be provided for contact
multiplication & use.
LBB function is part of the numerical relay as
mentioned in SLD. If required numerical relay
contacts can be programmed.
28 35210078623-Sht 11Breaker in Service indication shall be Amber Drawing revised to incorporate the comment.
29 35210078623-Sht 11Provide indicating lamp for closing circuit
healthy indication
Drawing revised to incorporate the comment.
30 35210078623-Sht 1252a/b contacts not shown in sheet 07. Shall be incorporated in revised/as
manufactured drawings.
-
7/27/2019 11kv Schemes 24th-25th April 2013
6/14
31 35210078623-Sht 12Indicate service description of all the contacts
shown
Drawing revised to incorporate the comment.
32 35210078623-Sht 12Closing circuit unhealthy to DDCMIS Drawing will be revised to incorporate the
comment.
33 35210078623-Sht 12Breaker spring charged to DDCMIS Drawing revised to incorporate the comment.
34 35210078623-Sht 12
Feeder/ Bus earthed contacts to DDCMIS. 75FET contacts are given to upstream breaker
circuit for tripping the upstream breaker
during Feeder earthing. However, it is not
possible to provide feeder/Bus earthed
contacts to DDCMIS as no electrical interlocks
can be provided for the same.
35 35210078623-Sht 13
LBB opearted contacts for alarm/ DCS & spare ,
to wire to Bus under voltage master trip relay
& for tie breaker Trip
Drawing will be revised to incorporate the
comment.
36 35210078623-Sht 14Indicate what are the indications provided on
relay front
Shall be incorporated in revised drawings.
37 35210078626-Sht 03
As per SLD time delayed no voltage protection
shall be provided.
Time delayed no voltage protection feature is
present in the numerical relay provided.
38 35210078626-Sht 05Indicate the parameters displayed in MFM Drawing revised to incorporate the comment.
39 35210078626-Sht 05
Ammeter & watt meter transducer shall be
provided to monitor the parameters at ECP
No meters on ECP.Ammeter & Multifunction
transducer provided
40 35210078627-Sht 01Panel number mentioned here is not matched
with SLD
Drawing revised to incorporate the comment.
41 35210078627-Sht 01Also refer comments marked in IF type 1 from
unit incomer
Drawing revised to incorporate the comment.
42 35210078628-Sht 01Also refer comments marked in IF type 1 from
unit incomer
Drawing revised to incorporate the comment.
43 35210078629-Sht 01Also refer comments marked in IF type 1 from
unit incomer
Drawing revised to incorporate the comment.
-
7/27/2019 11kv Schemes 24th-25th April 2013
7/14
44 35210078629-Sht 01Panel number mentioned here is not matched
with SLD
Drawing revised to incorporate the comment.
45 35210078629-Sht 01Indicate services of OG Feeder Drawing revised to incorporate the comment.
46 35210078630-Sht 01Comments same as on 629 Drawing revised to incorporate the comment.
47 35210078630-Sht 02
Relay should be communicated to DDCMIS All numerical relays will be connected through
RS 485 port to the DDCMIS.Drawing will be
revised to incorporate the comment.
48 35210078630-Sht 03Relay should cover sensitive earth fault
protection by using CBCT as input
Function 50G will be shown in drawing
49 35210078630-Sht 04 Ammeter & transducer to be provided Already shown in drawing as TDI.
50 Indicate services Shall be incorporated in revised drawings.
51 Indicate logic diagram reference Shall be incorporated in revised drawings.
52Panel number mentioned here is not matched
with SLD
Drawing revised to incorporate the comment.
53Also refer comments marked in IF type 1 from
unit incomer
Drawing revised to incorporate the comment.
54 35210078632,33-Sht 02Relay should have sensitive earth fault
protection
Function 50G will be shown in drawing
55 35210078633-Sht 03Current to be displayed at ECP, necessary
transducer to be provided.
Ammeter transducer already provided in Y
phase.
56 35210078634-Sht 02Provide technical manual Technical manual to be sent by 15th feb 2013.
57 35210078634-Sht 03Ammeter transducer to be provided Ammeter transducer already provided in Y
phase.
58Panel number mentioned here is not matched
with SLD
Drawing revised to incorporate the comment.
59Also refer comments marked in IF type 1 from
unit incomer
Drawing revised to incorporate the comment.
35210078631,32,33,34-
Sht 01
35210078635,36,37,38-
-
7/27/2019 11kv Schemes 24th-25th April 2013
8/14
60
As per SLD time delayed no voltage protection
shall be provided.
Time delayed no voltage protection feature is
present in the numerical relay provided.
RPCL STEAG BHEL
-
7/27/2019 11kv Schemes 24th-25th April 2013
9/14
RPCL/Steag Comments
Noted
RPCL/Steag will review & furnish
comments, if any.
Noted
Noted
Discussed on Rev 01 drawings.
Noted
BHEL to include the numerical
relay diagram in the respective
schemes indicating all itscontacts & ports. BHEL agreed to
incorporate the same.
Same shall be indicated in the
revised drawings.BHEL agreed.
RPCL/Steag will review & furnish
comments/approval.
-
7/27/2019 11kv Schemes 24th-25th April 2013
10/14
Same shall be indicated in the
revised drawings.BHEL agreed.
Not yet furnished.BHEL to furnish
the same.
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
-
7/27/2019 11kv Schemes 24th-25th April 2013
11/14
Noted
RPCL/Steag requested BHEL to
furnish the write up on interlock
& functioning of FEB & BEB.
BHEL has agreed to furnish the
same.
RPCL/Steag will review & furnish
comments/approval.
RPCL/Steag will review & furnishcomments, if any.
Noted
RPCL/Steag will review & furnish
comments, if any.
Noted.
Noted.
Noted.
Noted.
Noted.
-
7/27/2019 11kv Schemes 24th-25th April 2013
12/14
Noted.
Noted.
Noted.
Noted
Noted
Same to be indicated in the
drawing
Noted
Noted
Noted
Same as in Drg No: 35210078623
Same as in Drg No: 35210078623
Same as in Drg No: 35210078623
-
7/27/2019 11kv Schemes 24th-25th April 2013
13/14
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Not recieved. BHEL furnished
soft copy.
Noted
RPCL/Steag will review & furnish
comments/approval.
RPCL/Steag will review & furnish
comments/approval.
-
7/27/2019 11kv Schemes 24th-25th April 2013
14/14
RPCL/Steag will review & furnish
comments/approval.