111207 330-fccmall bms technical description e

Upload: luciana-cristea

Post on 14-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    1/44

    Technical description

    BMS - Mall

    FLOREASCA CITY CENTER

    Bukarest, Calea Floreasca

    05 / 2011

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    2/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 2 of 44

    Table of content

    1. General 31.1. Preliminary remarks 31.2. Prequalification 41.3. Execution- and Installation Planning 41.4. Project communication and project documentation 41.5. Test reports, certificates 51.6. Product sampling 51.7. Inbetriebnahme 51.8. trial operation 51.9. Acceptance / Inventory Documentation / Training 51.10.

    Preservation of evidence 6

    1.11. Standards and regulations 61.12. Interface definition 6

    2. Preliminary remarks BMS 7

    2.1. General 72.2. Guidelines for price information 9

    2.2.1. Installation works 92.2.2. Price building 92.2.3. Construction and secondary workings 102.2.4. Fundamental installation and delivering performances 102.2.5. Measuring 122.2.6. Fire protection - technical requirements 122.2.7. Occupational health and safety standards 122.2.8. Quality Features for the Components and regulations for the execution of Systems 12

    2.3. Performance description BMS 132.3.1. General description BMS 132.3.2. BMS cabinets 162.3.3.

    Description of Basic Functions 19

    2.3.4. Technical description of the crafts 22

    2.4. Manufacturer list 273. General quality description HVAC 28

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    3/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 3 of 44

    1. General

    1.1. PRELIMINARY REMARKS

    All services that are necessary for the erection of the building, in compliance with the constructionstandard as specified, must be taken into account in the calculation.

    The tender documents submitted by the contractor must be in English and / or German. A dimensionsand quantity calculation - suitable for the tender submission requirements - must be compiled by thebidder.

    Minimum requirements for the building physics: the standards and calculation methods applied in thecountry must be observed. The required heat and sound insulation values must be fulfilled on a

    verifiable basis.

    Fire safety: the country standards and the fire safety project must be observed and must be fulfilled ona verifiable basis.

    All implementations and materials must comply as a generally applicable rule with the relevantlegislation and authority regulations in Romania and the Romanian standards and must also be inconformity with generally accepted engineering standards, taking account in each case of the Austrian

    or EU statutory quality standards. In the event of a conflict of content the more stringent regulation isagreed as accepted in each case.

    Alternatives: the bidder is allowed the possibility to develop alternatives in reference to constructionand material, which can verifiably cut costs and / or reduce the construction time. All such suggestionsare to be documented with precise specifications (drawings or plans where required) and they mustalso be compliant on the basis of the submission documents with the specified standards andregulations applicable for this project. Alternatives must be compliant with the legally valid planningpermission and must on no account represent an obstacle to the achievement of the project objectiveand the permission for use. Alternatives must be submitted separately and apart from the basicservices package in the form of complete service packages priced and suitable for checking.

    The bidding company confirms that it has inspected the construction site and is familiar with the local

    conditions.All the components, materials, fittings, devices and facilities described in these TechnicalSpecifications must be a part of the bid and must also have a valid certification for Romania.Furthermore, the content of the available plans as also of the entire tender documents anddescriptions must be observed and must be included in the calculation. All the services described inthese Technical Specifications shall include the material to be delivered including its installation, withthe inclusion of reserve materials for all expendable parts and equipment items relevant for use (e.g.:door stoppers and fittings, clothes hooks, lamps and the like - as described in the TechnicalSpecifications Construction, HVAC and Electric)) as also for all floor coverings and assemblycomponents as described in the Technical Specifications Construction, HVAC and Electrical.

    In the event of differences in the equipment and quality (between the present Technical Specificationsand the plans as also between the present Technical Specifications and the additional fundamentals

    of the tender) the higher quality definition shall apply as valid and must be presented by the contractor.The decision and establishing of which data shall be accepted as having the higher quality definition inthe matter of the above relevant fundamental part of the tender, shall rest with the client.

    The contractor is under the obligation to obtain the permission for use in good time and to organize allthe take overs, tests, test operations and all the documents and permissions in this context, as also tocarry out all subsequent works and services on the basis of authority requirements or conditionsthrough to the permission for use without making claims on the client.

    Any translation of the Technical Specifications that is made into English or the language of the countryis a matter for the contractor and shall not be paid for additionally by the client.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    4/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 4 of 44

    1.2. PREQUALIFICATION

    The bidding company confirms that it has at its disposal the capabilities and resources as listed belowand declares that it is well suited to carry out a sustainable construction project of the kind that isdescribed in these Technical Specifications and in the plans and the descriptions:

    Appropriate experience in carrying out construction projects of the kind.

    Presentation of a reference list of buildings similar in type and size that have already beensuccessfully completed or are currently in construction.

    Appropriately trained and experienced personnel, in the required numbers for the

    implementation of construction projects of this kind.

    Presentation of a list of those employees, who are to work on the current project (with data on

    the age, training and practical experience of the employees).

    Provision of company project manager with excellent written and spoken German and Englishlanguage skills

    Appropriate experience in the commissioning, coordination and management ofsubcontractors, with appropriate suitability and capacity for the deliveries and services

    required in the course of a construction project of the kind.

    Appropriate experience in dealing with the official authorities involved with the constructionprocess.

    The contractor is able to provide a performance guarantee appropriate for the volume of the

    project in the form of a corporate guarantee.

    Internal quality management system

    1.3. EXECUTION- AND INSTALLATION PLANNING

    Essentially, the contractor must, without charging costs, draw up an execution plan appropriate to therelevant overall planning status and be involved with the creation of a detailed time schedule includingcash flow planning. This schedule will be updated at intervals to be agreed and should be regarded aspart of the contract.

    The execution and installation planning for the buildings technology (as per local standard E8390-1and H6010-1) must be carried out according to the status of the last architectural revision on the basisof the submission and tender planning under the leadership and supervision of the client or itsrepresentative, with all documents being signed and/or created in a standard manner.

    The offer price includes all coordination required with all other systems as part of the executionplanning, so that details regarding space requirements, weights, etc. can be factored into theconstruction plans in a coordinated fashion.

    Sound level requirements as defined by the expert report of the building physicist must be taken intoaccount in the plan.

    At the same time as the submission of the execution (installation) drawing, the contractor must alsosubmit an overall circuit diagram that must be confirmed by the regulatory company with regard to the

    correct function of the control and monitoring systems in the context of the overall system. The plansmust be drawn up with the layer structure and block structures specified by the contractor that must besuitable for later processing by the facility management system or for the room specifications book.

    1.4. PROJECT COMMUNICATION AND PROJECT DOCUMENTATION

    The client has the intention of establishing a project - related Internet platform, from which the projectcommunication and all current project documentation (contracts, plans, records, writtencommunications, schedules ...) may be downloaded on demand.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    5/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 5 of 44

    By this means the same information level status shall be assured for all involved in the project, and theentire course of the project shall be made seamlessly traceable. The application and use of theInternet platform referred to is a binding requirement for all involved in the project and is a part of theservice provision for each participant.

    The client shall set up an appropriate training program (workshop or / and written documentation).

    This does not however release the contractor from its obligation to provide information to the partiesinvolved with the project and to the contractor.

    1.5. TEST REPORTS, CERTIFICATES

    Verifications for the building physics, statics, fire prevention and all safety - relevant issues must beprovided before installation.

    All the materials, plant and plant parts for use in this project must have official approval for use inRomania. This official approval must be presented to the client in good time before installation.

    All test reports and certificates required by the local authorities, as also all test protocols required forthe operation of plant parts in compliance with the last applicable national and EN standards must bepresented and submitted to the authorities in good time before the end of construction for the

    obtaining of the building acceptance and permission for use within schedule period.The contractor must have all tests carried out by appropriately authorized testing institutions.

    1.6. PRODUCT SAMPLING

    Models/prototypes/samples of all parts of the plant must be submitted to the contractor and/orarchitect prior to project implementation. The submittal-system of the client must be followed.

    The specifications from the GNI criteria 6 and 8 must be taken into account and confirmation mustbe submitted that none of the products from the banned products list are or have been used.

    Safety data sheets and product data sheets must be provided in full and without exception in Germanand English.

    1.7. INBETRIEBNAHME

    Commissioning of all system and process equipment, if necessary on multiple occasions and in stagesas a result of the progress of the construction, rental or for local authority-related reasons. The settingand commissioning work must be carried out in collaboration with all companies involved.

    The commissioning of systems and process equipment is the sole responsibility of the contractor. Thecontractor is obliged to professionally check the cabling and all electrical connections beforecommissioning.

    All checks in accordance with the relevant regulations and provisions must be carried out beforecommissioning by the contractor or the contractor must arrange for these to be carried out. Thecontractor must prepare records of the test results and submit these in good time to the client.

    1.8. TRIAL OPERATIONA standards-compliant pilot operation of all systems and process equipment of the agreed durationmust be carried out. The client must be notified of the pilot operation in good time and in writing. Theproof of performance will only be accepted if this is carried out in the presence of the client. Proof ofperformance for heating systems may only be carried out during the colder seasons, while those forcooling systems may only be carried out during the warmer seasons.

    1.9. ACCEPTANCE / INVENTORY DOCUMENTATION / TRAINING

    The acceptance, inventory documentation and training procedures set down by the client must beobserved.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    6/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 6 of 44

    1.10. PRESERVATION OF EVIDENCE

    Before the start of construction work a preservation of evidence and an inventory of all publicaccesses to the construction site as also to neighbouring buildings and facilities (in all their internaland external areas) and real estate sites must be carried out.

    The contractor must take due care that the construction measures do not cause damage to

    neighbouring buildings and facilities and / or real estate sites.

    1.11. STANDARDS AND REGULATIONS

    EN standards

    Other directives which are listed in the performance specification or to which reference ismade

    The current local standards and regulations (= minimum standard)

    If EN standards are more stringent than the local standards, then the differences between the twomust be highlighted to the client in the context of the execution planning.

    The client shall choose which standards to use.

    1.12. INTERFACE DEFINITION

    Bidding assignment implies development of a completed and ready-to-use building project as perrequested contractual scope of work. Responsibility for the internal coordination of facilities lies withthe contractor.

    Interfaces in terms of the main contractor bidding are those directed outward only, i.e. public utilities.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    7/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 7 of 44

    2. Preliminary remarks BMS

    2.1. GENERAL

    In tendering phase the tenderer has to prove whether required performances can be fulfilled withingiven time.

    All system parts have to correspond with latest standards of technological development and have tobe delivered and mounted at the highest possible quality level.

    In order to ensure permanent and untroubled running, all devices and system parts have to beequipped with all necessary accessories.

    A faultless anti-corrosion protection of all system parts have to be ensured. Rust removal has to be

    carried out before applying the anti-corrosion protection. Derusting to a derusting standard ofminimum 2 must be carried out before the application of any corrosion protection measures.

    All corresponding norms have to be applied to the coatings.

    After installation all damages have to be expertly corrected.

    Constructional components and materials which the contractor has either to deliver or to install into the

    building have to be new and undamaged at the time of take over.All deliveries have to be absolutely suitable for intended use.

    Regarding the usage of installation and other materials all official requirements have to be observed.

    Constructional materials which can badly impact or damage the system parts, so as plaster inconnection with parts made of steel or cast iron or fast adhesive binder containing chlorine, shall notbe used.

    At construction site a special attention have to be paid to careful packaging, delivery and storage ofsystem parts like pumps, oil burners, safety valves, technical control devices, electrical cabinets etc.and other delicate system parts.

    Systems, distributors, equipment etc. have to be protected against pollution and damage until definite

    take-over. During the installation pipes, sockets and openings of system parts have to be protectedagainst pollution. Polluted or damaged system parts wont be accepted. Delicate fittings have to beinstalled as late as possible and protected against pollution.

    Special attention has to be paid to faultless accessibility of the fittings. At mounting no mechanicaltensions may appear.

    All demountable system parts have to be installed in the way that after quite a long time they still canbe solved without destructing them (e.g. blasting of nuts). Demountable connections have to remainaccessible.

    Storing of all mobile parts, axes etc. has to be carried out noiseless and with low-maintenance.

    All accessories made of synthetic materials or synthetic material parts have to be solid- coloured andlightfast (no painting). The colour has to be chosen by the client according to presenting sample cardsand/or sample pieces.

    In accordance with regulations galvanized construction metal parts have to be galvanized all over. Atgalvanized metal parts welding is not allowed. Damages and interfaces shall be galvanized cold.

    If possible, within one coherent construction stage all system parts, facilities and fittings shall be of thesame brand.

    All components at which dew point shortfall is possible have to be provided with devices for draining ofcondensate or suitably isolated.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    8/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 8 of 44

    Before realisation and after client's or architect's request, the samples of every system part (especiallysanitary fixtures and accessories, radiator etc.) have to be presented to them. Client's submittalsystem has to be obligatory realised.

    Simultaneously with construction (installation) documentation sample the contractor also has topresent the complete switching scheme, which has to be confirmed by the regulating companyregarding the exact function of the regulation and control systems in connection with the entire plant.The plans have to be made in accordance with layer and block structures specified by the client andthey must suit for subsequent processing by a facility management system and/or room book.

    System parts have to be coordinated exactly with respect to their definite performance data (fallingpressure of heating and cooling coils etc.) and shall be ordered only after a definite clarification.Wrongly ordered system parts caused by disregarding of this regulation won't be accepted and haveto be exchanged free of charge.

    All devices or plants must have specification plates with engrained data or data attached on a foil.They must be gut accessible and well readable.

    All markings, indicating scales, specification plates etc. even if they originate from a foreign languagecountry have to be translated into Romanian und English language. The same is also valid foroperating and maintenance instructions, technical descriptions etc. Usage of hot stamping foils formarkings is not allowed.

    The entire load cabling and control cabling between the HVAC/ICT control cabinets and the variousequipment are included in the scope of supply or work.

    The connection of all cables at the entrance and exit side of the HVAC/ICT switching and controlcabinets (both on the load and control side), as well as the connection and installation of theperipheral equipment provided, is included in the scope of the contractor's ICT contract. The settingand initial commissioning must be carried out in collaboration with the companies providing the HVACsystems and the regulatory company. All cable support systems (pipework, cable trays and cableducts, etc.) are included in the scope of supply.

    For lifts and escalators, the feed cables connected on both sides and the control cabling required for

    the interfacing of these systems with the DDC alarm system are included in the scope of supply.Integration, even of non-detailed external systems, is included in the scope of supply.

    Should any interfaces problems arise between the systems, the solution of these problems is theresponsibility of the contractor. Contractor obligation of notification.

    The same applies to interfaces to systems that are outside the scope of work if they are required inorder to carry out functions that are described in the tender.

    When devices or materials are included in the scope of services of other suppliers, then the directcoordination, the transfer of data and drawings shall be included in the scope of services, in order topermit other companies who are involved in the implementation of the project to fulfil their contractualobligations. This shall also apply for the production of masonry breaches, openings in furnishings orwoodwork, or the supply of devices that are necessary to maintain the system in operation.

    If data of this type is not handed over in a precise, complete and timely manner, the resulting costs willbe charged to the contractor.

    The contractor must also make available the documentation required for the devices or componentswhich he has delivered.

    The contractor must in dependence on the system, make all consumables that are required at the startof the project available in good time and supply them all before the end of this contract to the extentthat these form a part of the contractor scope of services. The supply of materials and consumables inaccordance with the contract that are required for the test operation shall also be included in the areaof responsibility of the contractor.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    9/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 9 of 44

    The client shall only accept the plant with new and unused additional and auxiliary materials.

    Prior to the technical acceptance of the completed plant, a complete documentation of the installeddevices and the works that have actually been carried out which are in the scope of services of thecontractor must be submitted.

    2.2. GUIDELINES FOR PRICE INFORMATION

    2.2.1. INSTALLATION WORKS

    The assembly shall be carried out according to the execution planning approved by the client. Ifworkings or outside orders without approval of a principal are executed, the contractor will be chargedfor additional costs resulting from these changes.

    Costs of repeated arrivals and departures of the installation and supervision personnel caused by notcontinuous installation are included in the prices.

    All overtime costs necessary for meeting the deadlines are also included in the prices.

    All components, devices and gadgets (also provided for installation), as well as pipes and junctionboxes have to be kept safe and protected faultlessly until takeover of the building. The contractor ischarged for all damages, thefts and losses until take over.

    All conditions, system parts and performances specified in the technical preliminary notes and

    descriptions have to be taken into account.

    Also remove all pollution and construction waste caused by one's own work, including waste removaland waste disposal.

    Transportation of all materials to the construction site is included in the target price.

    2.2.2. PRICE BUILDING

    Following is understood under the word "material":

    Delivery of every brand new system part which is specified in the respective position. The parts shouldbe the latest type series, as sole components or in composed form, including packaging; freeapplication site including all required descriptions, markings, illustrations, outlines and measuredrawings as well as all required keys, operation tools, etc. and other required accessories whichensure faultless operating, even if this is not specified in the text in particular. The contractor bears therisk of changing surcharges (like copper surcharge).

    Following is understood under the word "work":

    Getting along with, installing and connecting of materials described in respective positions, includingchecking out the functions and protective measurements, making test operations and positioning of allauxiliary means, including paying of labour and additional costs so as travelling expenses etc.

    Prices include also necessary coordination in the course of implementation planning with all othertrades, so that details about space requirements, weights, etc. can be included in detailed projectplanning in coordinated form.

    Costs shall include all labour costs of the staff employed by the tenderer, together with all othersurcharges, ransoms and separation compensations, as well as payments of proportionate costs forsupervision and administration staff, so that the principal and the client as usually doesnt bear anyadditional costs and that planned and assigned performance can be completely realized. Furthermorethe price contains all costs for materials required for the realization of the work; also the costs for toolsand machines supply, scaffoldings etc. including all surcharges. The prices for the system groupsoffered in the supply include also transport, additional costs, construction site cleaning, removal of restmaterial, removal of packing material and rubble, construction site facilities as well as risks,insurances, intermediary transports, intermediary storages and usage failures.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    10/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 10 of 44

    All auxiliary means needed for assembly like ladders, scaffoldings, lifting tools, hydraulic lifts, cranevehicles when required (notwithstanding the height) etc. as well as all required machines and toolsmust be provided by the contractor and are a component of calculation.

    Incidentals of every kind, like screws, angles etc. have to be made of non-ferrous metal or as aprotection the surfaces have to be galvanized or cadmium-plated. All assembly, fixture, smallmaterials, insulation materials etc. and also all special fixture materials (for concrete, tiles, porousstone, light-weight structures in wood and plaster board, metal or steel structures, all suspendedceilings, etc.) shall be included in the target price. No separate remuneration will be provided for anyadditional installation work.

    If possible, all plant components shall be factory assembled and brought inexpensive to theconstruction site in arrangement with the building site supervision.

    The complete documentation of the plant (site technical plans, handbooks, operational guides etc.)shall be included in the target price.

    All offered prices have to include transport costs to the construction site, so as unloading andintermediate storage if needed. Storage on the construction site is permitted. Storage on theconstruction site must be requested in advance and may be provided if installed parts of the systemcan be used.

    Interim storage and storage required outside the construction site is the responsibility of the contractor.

    The capital prices must include all necessary insurance for the workings, materials, equipment andlabour.

    The target price shall include a builders risk insurance taken out by the contractor.

    The target price shall include the following: The contractor must create the implementation planningthat is based on the last planning status released by the client, as also participate in creating adetailed schedule planning including cash flow planning.

    The plan prepared in the way described above still must be updated in time intervals and is regardedas a contract component.

    2.2.3. CONSTRUCTION AND SECONDARY WORKINGS

    Breaking and drilling, core hole drilling or concrete cutting on the construction site shall be carried outonly by approval of the contractor or his representative and under special consideration for the static ofthe building.

    All openings required for the installations must be taken into account in the calculation by thecontractor, provided that these have not been already planed in the outline planning.

    If the contractor creates unnecessarily large gaps or slits (approx. net size plus no more than 10% onall sides) or walls or ceilings are damaged, then the company in charge of the construction work shall

    be authorised to bill the company carrying out the installation work for the costs of repair.

    2.2.4. FUNDAMENTAL INSTALLATION AND DELIVERING PERFORMANCESThe following specified services shall be included in the target price and are to be given attention in

    the design and installation of the plant, when these are a part of the contracted scope of services ofthe contractor.Admission and inspection certificates for plant and parts of the plant, which are subject to a statutoryinspection obligation.

    Checking and compiling of the permission applications as prepared by the client for plant and plantparts, which are subject to an authority specified permission and acceptance procedure for theirimplementation and operation.

    Applications with all documents and drawings in required form and copy shall be made by thecontractor and submitted to responsible authorities.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    11/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 11 of 44

    The contractor provides the assurance of giving the client the best possible support for plant and plantparts, which in accordance with the regulations, rules and directives are subject to a permission andacceptance procedure.

    This shall apply for the acceptance tests as also for the verification of maintenance of the regulations,rules and directives for the implementation and operation of such plant and plant parts by means of:permission issuing, regulatory and inspection authorities and the technical monitoring organization.

    The fees and dues for the specified permissions and acceptance tests by safety monitoringorganization shall be borne by the client.

    The contractor shall provide means of protection during and after assembly to ensure that plant partsare protected until handover to the client. Damaged and dirty coats of paint and plant parts shall berepaired and corrected by the contractor, no matter who caused the damage.

    When stopping the installation works, open plant parts shall be protected by suitable measures -sealing - against penetrating of foreign particles (dirt, dust, etc.).

    Before putting into operation, all required examinations in accordance with prevailing regulations orspecifications shall be carried out by a contractor. The contractor has to make protocols about the testresults and presented them on time to the client.

    Services arising from planning permission requirements and those of local utility supply companies tothe extent that these have been handed over verifiably and on time by the contractor.

    Delivery of details about foundations and block-outs, ceiling openings and inspection openings.

    Self-boring dowel plugs must be used for the applying of fixtures. Elongated bolts are not permissible.When a structure is in a steel construction, no drilling or welding of any kind may be carried out on thestatically bearing parts without the permission of the consultant building physicist.

    Delivery of galvanized steel construction for plating or suspension of carrying systems and sub-constructions for the components of central system.

    All steel parts must at least be treated in compliancy with the standards in Romania - insofar as theyare not already hot galvanized or otherwise corrosion protected.

    Performances and deliveries of the contractor must correspond with demands of the responsible fireprotection authority. Only materials with appropriate fire protection class may be installed.

    Installations which are necessary for fire safeguarding must be clearly indicated in accordance withcorresponding norms and regulations. Information signs must indicate installation places.

    To enable the inspection of all connections to machines, fittings, plants, etc., they must be mount- anddemountable without probability of components destruction. Components which are a subject ofregular maintenance, revision or inspection must be freely accessible.

    Before production and installation all enclosure parts must be provided for sampling inspection. Theseplant parts will be appointed by the client and announced to the contractor; the submittal system of theclient shall be carried out.

    At every wall and ceiling bushing at fire protection walls officially authorized fire protectionconstructions shall be used.

    Configuration of measuring instruments must be carried out in the way that they can be used or readwithout any auxiliary means.

    Every device or every consumer consisting of rotating parts (pumps, ventilators, compressors andsimilar equipment) has to have in their immediate proximity a service/emergency switch, provided thatthe accompanying electrical cabinet is not visible. This emergency switch must switch off all poles.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    12/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 12 of 44

    Putting into operation of a system and system parts is exclusive responsibility of the contractor. He isobliged to check competently all wiring and all electrical connections before putting them intooperation.

    Coordination with the client and subcontractors in the contractual scope of services must be assuredand a joint commissioning must take place.

    All equipment (sensors, engines, valves etc.) placed outside of the electrical cabinet shall bepermanently labelled with engraved synthetic material signposts (assigned multi-coloured to thedifferent areas). Designation cards shall be installed in the same format just as well for wiring of allother maintenance groups (HVAC-BMS - etc.).

    Labelling analogue to the wiring schematics; all pipelines must be marked at adequate intervals withthe medium carried, the flow-through direction and, when if required by the client, with the pipelinenumber.

    2.2.5. MEASURING

    Measuring instruments equipped with test certificates, performance graphs, calibration curves etc.shall be provided by the contractor. In case of doubt the proper regulation shall decide on themeasuring equipment to be used and the measuring method to be applied.

    Protocols about measurements shall be taken. The client shall be informed on time to take part at themeasuring. The client has the right to carry out measurements even in the absence of the contractor.Furthermore, the efficiency statement can be asked also after the takeover within the warrantyperiod - when data about condition or disturbances at the time of takeover do not exist.

    The contractor has to run function control of all system parts by the means of measuring, beforeputting into operation and takeover of the systems.

    2.2.6. FIRE PROTECTION - TECHNICAL REQUIREMENTS

    Provisions of corresponding NORMS and local regulations have to be observed exactly.

    Particularly fire damper shall be a subject of a sample testing in any case by state-run or stateauthorized testing centre; or only type tested parts shall be used.

    At the installation of fire dampers the absolute attention shall be paid to their best possibleaccessibility. At the release fixture equipment with fusible (glass) link, link changing must be enabledwithout difficulty. Position of the fire damper must be on the spot always recognizable. Should thestructure require that fire dampers in accordance with the required fire protection class, has to be fixedto non-bearing intermediate walls or ceilings with profile bearing structures, threaded rods or similarshould be used in accordance with the regulations.

    A special attention shall be paid to a suitable fire protection on the construction site during theinstallation works, storing, etc; as well as to first aid when extinguishing the fire.

    2.2.7. OCCUPATIONAL HEALTH AND SAFETY STANDARDS

    At the execution of the HVAC plants relevant editions of employees protective provisions and otherlocally relevant regulations must be respected.

    2.2.8. QUALITY FEATURES FOR THE COMPONENTS AND REGULATIONS FOR THEEXECUTION OF SYSTEMS

    All materials must be in an unused and flawless condition.

    Only the agreed quality will be accepted. Lower-quality material will not be acknowledged, even if the

    contractor offers a discount.

    The contractor must ensure that the materials it supplies and installs are in an undamaged condition atacceptance.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    13/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 13 of 44

    Touch-ups of the paintwork applied at the factory must be carried out by a professional in the samecolour and with the same quality of paint. Touch-ups of glazes, stove enamelling or polished surfacesare not permitted.

    Cable conduits may only be installed vertically and horizontally.

    All of the parts that come into contact with the main structure must not be susceptible to any

    aggressive substances that may be contained therein. The installed parts must also not have anydeleterious effect on the main structure.

    All equipment, fittings and installations must be easily locatable and accessible for the purposes ofrepair, maintenance, removal and installation.

    For the connection of installation objects, equipment and fittings provided on site, the contractor mustrequest and comply with the necessary connection devices.

    Painting (minimum requirement):

    Matt paint, surface protection with degreasing, priming and top coat

    Paint type: Synthetic resin paint, plasticiser-resistant (DD paint), switching cabinets, control cabinets,operator stations RAL of choice.

    Labelling:

    In the technical control rooms, coloured electrical diagrams must be secured under glass from whichthe technical installations of the control room in question can be identified or from which theconsumers supplied from this control room, their outputs and rated value can be identified.

    All technical equipment must be permanently labelled in English and Romanian on the base plate andon the component. Warning notices must be ideally created with pictograms, signs with engravedinscriptions or foil in a closed sign, operating and signalling equipment created with labelling fields.

    The nameplates must be made from plastic and the labelling must be defined in collaboration with theclient.

    2.3. PERFORMANCE DESCRIPTION BMS

    2.3.1. GENERAL DESCRIPTION BMS

    A building management system (BMS) for monitoring and control of the plant has to be designed.

    The plant has to be developed in accordance with the planning.

    It will take on the tasks of making possible communication (monitoring, switching, parameterization ofdesired values) between the operator and the building management system (BMS) by means ofschematic graphical representation of the plant systems as also of the plant operational status.

    All devices are to be selected and installed on the basis of control technical and energy efficiencycriteria.

    The time constants of sensors, the control algorithms (and control hierarchies) as also the operatingtimes of actuators are to be aligned to each other in such a manner that a stable control behaviour canbe achieved within the desired tolerances through all disturbance variables. All devices and plant partsare to be equipped with the accessories required for impeccable continuous operation.

    The control centre shall be equipped with an alarm / event printer, a PC colour graphic operatingstation, and an LCD colour monitor of at least 22 dimensions.

    The BMS facility shall be developed on TCP-IP basis.

    Software

    The BMS software shall have a modular structure and implementation, with the result that all actionsand changes of data points, limitations, changes in time switches, evaluation of data, can all be dealt

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    14/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 14 of 44

    with by the user in a simple manner in the operations menu. The software in both the substation and inthe central facilities is secured in a BACKUP medium.

    The basic software for control, operation and monitoring devices, suited for the further processing ofthe data from automation devices, comprises all the functions listed in the following:

    reporting, measuring, counting

    remote control (switching, setting) text output limits monitoring recording operational hours recording of events standard records spontaneous display of messages time-dependent switching protection against unauthorized system access Event memory and long-term trend memory for all system parameters are included in the

    scope of delivery.

    The entire building system plant is represented graphically in colour, whereby a constant display of allrelevant temperatures, variables, faults, operation, rotary speed levels etc. is made.

    The program also has a text level for communication purposes. The change of desired values,variables and the like is made directly by clicking with the mouse on the valve or the consumerdisplayed as also by means of entering a text. The changing of the desired values is made exclusivelyat the own coded access level.

    All the technical installations in the building are linked into the BMS as a matter of principle, and insuch a manner that the operational and fault messages and separate, plant-specific parameters forventilation plant (as also the rotary speed levels, or performance data in % for frequency convertersand volume flow

    regulators) pumps for HVAC and fire protection, de-gassing, refrigerating machines, as also onlyoperational or fault messages for the smallest dimension ventilators (WCs, tea kitchens, elevatormachine rooms), lifting units and sump pumps are displayed.

    All building technical system installations for the HVAC subcontract must be switchable from theregulator switch cabinets. The line circuit breakers are also included in this switch cabinet.

    Separate fields are planned for accommodating the DDC substations in the switch cabinets.

    Menu bar

    The menu bar provides an overview of the possible functions and can be designed on an individualbasis.

    It is possible to navigate simply and quickly through the system with the help of a window. The datacan be displayed either in a user window, or also in a system window and processed by the user.

    Facility graphics (plant viewer)

    Graphics based on practical use must assure a fast and targeted system monitoring and operation

    of the individual plants.

    Alarm viewer

    Rapid troubleshooting for any faults that occur in the building must be possible by using a detailedalarm display. The separate alarms are entered automatically in a list. This list describes the currentalarm status of the system. By using an alarm router it is possible to transfer an alarm report onwardsto a selected receiver.

    Time scheduler

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    15/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 15 of 44

    Central programming of all functions for the technical installations in the building. Simple graphicaloperation of week, holiday and exception programs.

    Trend viewer

    Recording of historic and current data such as temperature, drive positions, frequency converter-operational status etc., for easy analysis of online and offline time for optimizing the system. All actions

    made by users, alarm messages, as also failures are also recorded and can where required, bedisplayed on an overview window for further analysis purposes.

    Access rights

    Access rights are issues to regulate the accesses of user groups.

    The access rights for the user groups comprise among others the right to start or end a program. Theaccess to the graphical representations can be issued on an individual basis. The responsibility for theplant can thus be shared out among several users. Access to the system is by means of a password.

    DDC substations

    The DDC substations consist of the process device and the Input and output modules.

    The Process device monitors the technical installations in the building plant and is integrated in the

    appropriate BMS switching cabinet. The Input and output modules are linked to the process device byprocess bus and form the interface to the peripheral devices. The separate modules are pluggableand can be taken out or replaced for service purposes.

    Process device

    The process device can operate autonomously as a standalone, or also peer-to-peer with otherdevices that have equal rights or also as a master device (e.g. for floor level networks). The separateprocess devices are linked to the building management system (BMS) via a bus cable.

    The unit is fitted with an integrated display. The current values and data points of the relevantcomponents can be either read or set at the site.

    The basic device functions include:

    carrying out of the unit specific processes in the program inserts Data traffic between input and output modules via the process bus Self monitoring of the connected devices controlling information available on display

    System security

    The following functions will be maintained by a UPS system (uninterrupted power supply) for at least60 days:

    date and time microprocessor monitoring (Watchdog) user programs, configuration and process data

    The service life of the battery is to be at least 4 years. The battery status will be displayed and

    monitored by the process device.

    The system carries out a controlled abort function on under voltage or power cuts (reset). The processbus and all communication lines are then passive, i.e. their transmission functions are switched off. Assoon as mains operational current is available again a defined re-start begins to ensure that the plantcan operate again on a functionally correct basis.

    All connected input and output modules are passive on a process device failure.

    I / O Modules

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    16/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 16 of 44

    The I / O module system is the link between the process device and a plant with all its elements.I / O modules are changed by the signals passing through the process bus to the form required for thereceiving devices or elements and their functions.

    The I / O modules are pluggable and can be newly loaded, removed or plugged without the need foradditional terminal connections or software.

    The basic functions of the I / O modules are:

    Reporting, measuring, counting, switching and setting. The switching, reporting and setting modules have an integrated status display.

    Room temperature control

    Reference thermostats are installed in the separate areas.

    Room temperature controls with use of a turning knob for pre-selecting the temperature or equivalentand operational wafer switch.

    Fan coil devices with temperature control and speed selection switch are the equipment in principle.

    Standard operation:

    The temperature controls compare the room temperature on the reference thermostat with the setdesired temperature value. When there is a deviation heating or cooling valves are opened onrequirement and the ventilation system ventilators are switched to the pre-selected rotary speedlevels. When the desired room temperature has been reached the hot or cold valve is closed and theventilator is actuated.

    The defined sinking of normal operation must also be possible outside of the usual operating times.

    Frost protected operation - building:

    The frost protection operation is effective when the operational pre-selection switch is at off. In thecourse of this the room temperature is et to a desired value of 8C.

    2.3.2. BMS CABINETS

    The DDC - substations, controls and power supply for the HVAC components such as the ventilators,pumps, etc. are installed in the BMS switch cabinets.

    The switch cabinet implementation must comply with generally applicable regulations and withgenerally accepted engineering standards. All components must have the locally applicable test mark.In addition the regulations of the energy supply companies and the building authorities in the localarea must be followed.

    When mask distributors are planned, it must be ensured in the mounting and cabling work that the

    mounting is on a rail frame in cable channels, whereby all voltage-carrying parts must be fully covered.

    Implementation of the door panels:

    All voltage-carrying devices in the door are to be protected against being touched with door panelcoverings. The widths of the doors which are to open depending on specification to right or left, must

    be a maximum of approximately 0.8 m. For door widths above 0.42 m surround strengthening profilesor U-shaped door edging is to be provided. The door must close with a locking handle T-type andprovided with a cylinder lock. The housing must be provided either with integrated or with removablepedestals at least 10 cm in height.

    Each cabinet must contain:

    1 pc. plan case per field 1 pc. reserve fuse switch for 10 fuse cartridges 10 pcs. reserve fuses cartridges for assembly.

    The exceptions to this are small wall cabinets or panels.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    17/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 17 of 44

    A reserve space of at least 20% must be maintained.

    The cable insertion must be either top or bottom depending on requirements. For a top cableinsertion a removable flange plate with drilled or punched holes in appropriate size must be provided.The number and diameters of the holes are to be established in dependence on the cable outlets. Theattachment screw connections are included in the scope of delivery for the switch cabinet.

    For cable insertions top a cross-bonding space for the connecting cables and a shunting space of atleast 20 cm above the entire length of the terminal strip is to be kept free. Brass-nickel attachmentscrew connections apply as strain relief.

    In case of cables or floor lines (bottom), the relevant relieving facilities in form of series clips oranchor brackets are to be planned for. When using anchor brackets except for EYY cables, trunkingmade of insulating material placed against the cable shall be used before and behind the cable.Switch cabinet shall be provided with cabling fully ready to connection on connecting terminals.

    Cabling shall be made using cable wires, connectors shall be provided with terminal bushing orterminal plugs depending on set requirements, and each terminal bushing or terminal plug shall crimponly one wire.

    For turning doors and panels flexible cable materials YF or YSF shall be used. The cabling in turn

    zone shall be additionally protected from mechanical damage.

    For phases L1, L2 and L3 black cable wire shall be used, for fourth wire blue cable wire shall be used,and for the wire of protective connection PE yellow and green cable wire shall be used inaccordance with instructions.

    All other cables under voltage can be of random colour. Block wire clamps shall be excluded as a rule.

    Necessary protection measures shall be taken.

    For instrumental terminals there are maximal 2 wires per nipping point, for connecting blocks or fourthwires maximum 1 wire per nipping point shall be used.

    If the mnemonic diagram (linear circuit) is used, it shall be painted, engraved in colour, painted incolour, depicted with colour trace or made as black and white photo (Colours according to the

    standard requirement).

    All mnemonic diagrams shall be engraved on the substrate material, for example aluminium. Thediagram shall be placed on the door using FIL bolts. In the nomenclature of the device for working andemergency alarm, if possible, provide signal lamp in form of two-colour LED.

    If the mnemonic diagram (linear circuit) is present switchers or also indication components (forexample, working hour timers) shall be integrated in the mnemonic diagram.

    The description of switcher shall be made on the switcher in the separate positions of switcher.

    The removable devices in distribution cabinet shall be marked as both the device and its base.

    Safety circuits, automatic circuit breakers, differential protection switchers etc as well as the amplifiers0f regulation system with the possibility of tuning and all the control elements inside shall be marked

    using non-encrypted text on thermo resistant stickers with typewriter type. Contactors or supportingcontactors and terminals are equipped with inserted labels with definitions. The list of safety circuits,made in non-encrypted text, with full list of safety circuits (automatic circuit breakers) in distributioncabinet are placed on the door panels (pressure-sensitive type).

    All the optic signal lamps in the doors must be made as LEDs.

    Multiple stage loads

    If multiple staged loads are present (for example, 2-staged fans or heat pumps) working and alertalarm shall be provided for each stage in form of two-coloured LED. The socket with protective contacton 230 V shall be installed inside the distribution cabinet (second control level).

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    18/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 18 of 44

    Frequency converter

    When necessary and when theres functional need the relevant to the technical level frequency-regulated drives. Necessary frequency converter units with integrated pressure control circuit shall beinstalled.

    Operation and alarm indication

    Main switch

    Main switch is placed in the door of switch cabinet and is used for emergency shutdown of all pumps,fans etc powered from this cabinet.

    Check back button

    The button is placed in the door of switch cabinet. After the failures such as freezing alert, enginefailure etc are fixed, the button needs to be pressed. Then the equipment relaunches automatically.

    Output manual switches:

    Manual switches are placed on the door of switch cabinet and are protected with Plexiglas window.

    Using those switchers you can deactivate program control function for all the elements of the

    installation, such as fans, pumps etc. Those switchers are made for emergency mode only and shallalways stay in AUTO position when in normal working mode. Switching position of every single outputmanual switcher is regulated by DDC substation and is displayed accordingly on central control board.

    The writings shall be done in English and Romanian languages.

    The following manual bypath switchers are used:

    Switch for 1-staged devices (i.e. pumps, fans)

    AUTO: DDC control system is active, the device is controlled by the program O: DDC control system is inactive, the device is turned off 1: DDC control system is inactive, the device is controlled manually

    Switch for 2-staged devices (for example, 2-staged fans):

    AUTO: DDC control system is active, the fans are controlled by the program O: DDC control system is inactive, the fans are turned off 1: DDC control system is inactive, the fans are controlled manually for stage 1 2: DDC control system is inactive, the fans are controlled manually for stage 2

    Switch for double pumps

    AUTO: DDC control system is active, the pumps are controlled by the program O: DDC control system is inactive, the pumps are turned off 1: DDC control system is inactive, pump 1 is controlled manually 2: DDC control system is inactive, pump 2 is controlled manually

    The control of executive devices (actuators) in emergency mode (manual control function) is

    performed on the substations.

    Revision switch

    When performing the operations on fans, revision switch is provided on the spot for each engine that isused to shutdown the voltage on all the poles of the engine. Activation and deactivation of revisionswitch shall be performed only after the facility shutdown. The OFF position of the switch is integratedin the alarm system of the relevant device and is registered by the DDC system as failure.

    If the access to relevant distribution cabinet is available, the switches can be excluded.

    Signaling

    The indication of separate operating and notice of malfunction is made by LEDs.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    19/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 19 of 44

    The writing shall be done in the language of the using country.

    2.3.3. DESCRIPTION OF BASIC FUNCTIONS

    General functions

    Control in case of fire

    In case of fire the system of fire alarm shuts down all the ventilation systems that arent used for fireextinguishing and smoke exhaust. BMS building control systems receives relevant no-voltage contactsfrom the fire alarm system to turn the fans on and off in accordance with the fire protection system.Fire protection screens are controlled by proximity switches. Closed signal is displayed individuallyfor each screen in graphical form on control station of BMS system.

    Smoke exhaust

    BMS System will monitor the ventilators and domed rooflights.

    Shops and Mall

    The smoke-exhaust fans are switched on and off via the fire alarm system, while safeguards andsupply must be linked into the emergency network and must be fire-resistant. The smoke in the mall isdischarged via openable domed rooflights.

    The fire-prevention (fire-resistant) smoke flaps are to be actuated in accordance with the fire-prevention plan via the fire-alarm centre.

    Stairwells, corridors or airlocks

    Staircases, corridors or airlocks are kept free of smoke via their own pressure ventilation fans whichare activated only in the event of fire. In the event of fire, the corresponding fans will be called upindividually from the fire alarm system in accordance with the relevant fire safety plan via voltage-freecontact. The switching is done by the respective ICA (instrumentation, control and automation)cabinet. The smoke is vented through openable skylights by a smoke extraction fan.

    Garage

    Smoke in stairwells, corridors, or airlocks is extracted by forced draft via ventilators. The smoke is

    vented by a smoke extraction fan.

    The garage is divided into eight CO-extraction zones and into as many fire-smoke extraction zones.Both CO2 and smoke are extracted by means of the Jet System and by fire-gas exhaust fans. In bothcases, air is replenished naturally via fire-smoke dampers. Only that zone that has either an excessive

    CO-concentration or where there is a fire alarm is ventilated and replenished. To vent CO thededicated fan is switched on, thus reducing the through-flow of air.

    Protective functions

    Protection against freeze over the air

    Freezing relay protects the heating register of water heating from freezing.

    Freezing relay sends the freezing alert signal to the controller when the temperature on the heating

    register is lowered beyond the threshold value of freezing relay.

    DDC regulation block then performs the following operations in the system:

    EMERGENCY ACTIVATION opening of heating register valve and activation of heatingregister pump

    EMERGENCY SHUTDOWN of forced-air and exhaust ventilation Closing of screens of outside air/out coming air with engine drive. Emergency shutdown of the system

    Freezing alert is displayed in the BMS system and in the instrumentation and control system cabinet(BMS) using LED.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    20/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 20 of 44

    The function of protection against the freeze is active even after the facility shutdown.

    Protection from the freeze over the water

    Theres the immersion sensor built into recirculating circuit of heating register that measures thetemperature of working environment. If the temperature is lowered below set minimal value, forexample, 15C the heating register valve is opened in the relevant way by the DDC control block and

    stays in such position before the minimal value is reached.Control functions

    Filter control:

    Differential pressure relay controls the degree of filter clogging. The more clogged the filter is, thestronger is the air resistance when passing through the air filter. If the air resistance in the filtersurpasses maximal allowed value, the differential pressure relay activates service alert signal Thefilter is clogged.

    Filter clogging is displayed in the BMS system and in the instrumentation and control systemcabinet (BMS) using LED.

    Pumps monitoring

    The absence of working feedback signal or the engine failure signal initiates the emergency shutdownof the facility.

    However, it happens only during low outside air temperature, when it is impossible to provide facilitywith the necessary amount of heat without heat recuperator. When the outside temperatures arehigher, only the signal of pump failure is displayed.

    Engine protection failure signal is displayed in the BMS system and in the instrumentation and controlsystem cabinet using LED.

    Fans monitoring:

    The absence of working feedback signal through differential pressure relay or the engine failure signalinitiates the emergency shutdown of the facility.

    Engine protection failure signal is displayed in the BMS system and in the instrumentation and controlsystem cabinet using LED.

    For fans with V-belt drives, all-pole service switches are provided directly with the drives.

    Control Functions

    Program of time-based control

    The aim of program of time-based control is to regulate the performance of the systems of heating,ventilation and air conditioning in accordance with the periods of use of the building and its premises,as well as the other needs with time based regulation both during the day and the whole year.

    Time-based switching functions, included in time-based control program, provide:

    Time-dependent activation and deactivation of heating system, ventilation and air conditioningor alteration of its stages, Increase or decrease of set values of heating system, ventilation and air conditioning and

    correspondingly the setting of daily pro archives of temperature and humidity.

    Restoration of mains supply

    The system of restoration of the power supply after mains supply shutdown guarantees organizedstaged and load dependent activation of electric load of maintenance engineering devices after mainssupply shutdown.

    Intensive night ventilation

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    21/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 21 of 44

    In summer intensive night ventilation allows the economy of cooling energy, for this purpose in nighttime the premises are cooled by cold outside air before the next day.

    Terms of intensive night ventilation activation:

    System stage Intense night ventilation is activated if the following conditions are performedsimultaneously:

    intensive night ventilation is activated by time-based control program; outside temperature surpasses set threshold value; inside temperature surpasses set threshold value; the temperature difference between outside and inside temperatures surpasses set

    temperature differences.

    Intensive night ventilation turns off:

    by time-based control program, if one of abovementioned conditions is not fulfilled but no earlier than after set minimal

    operating time.

    Peak load program

    The goal of peak load program is to regulate the energy consumption in such a way that maximal level

    of energy consumption during measurement period that usually equates 15 minutes does not surpassfixed threshold value. To do that program connects and disconnects relevant number of loads. Theaim of the program is to prevent the appearance of current peaks and to use received electric energyin rational way. The energy received above threshold norm shall be paid for at higher rate inaccordance with local regulations on energy consumption.

    That program regulates not only maximal power consumption but energy consumption in general(including heat). That allows for energy saving as power is supplied not voluntary but according to theplan and with set limits.

    Fire dampers with or without electric drive

    Fire dampers are closed during the fire using thermal trigger. In normal situation the dampers arealways opened.

    The closing of fire dampers indicates that theres fire in the building. Signal of closed damper isprocessed in accordance with fire protection scheme.

    Ventilating dampers with spring-based retraction

    During de-energization the dampers are closed by themselves using spring-based retractionmechanism. Ventilation system works with supply and exhaust dampers that regulate the air volume orstop the air supply. If the ventilation system is active, the dampers are opened. They close during thesystem shutdown. The position of the dampers is regulated using the switching commands.

    Additional switching contacts are used to ensure that the fans are turned on only when the dampersare partially or fully opened. Release time-dependent activation scheme.

    Retraction spring

    During de-energization the return spring puts the dampers in the emergency position.

    Heating register (Double pump)

    For the heating of outside or mixed air the air heater with pump-based water heating is provided.

    The heater is integrated in the system of sequential regulation of the temperature of the room orincoming air, and the resulting output signal of controller acts as the executive command on therelevant heater valve.

    A recirculating pump is integrated in the control circuit of air heater with pump-based water heating.

    Recirculating pump is activated when necessary i.e. depending on the state of servo valve output (Y

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    22/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 22 of 44

    >= 4 %) without delay. If theres the necessity of deactivation with delay, with the absence of necessityin its work (Y

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    23/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 23 of 44

    With increasing demand for heat, the supply air temperature regulation operates in the followingmanner and sequence on the existing heat exchanger:

    Increase the power of heat recuperators, * Increase the power of the pre air heater,** Increase the power of the post air heater,*/** Close the constant dampers up to 20 % circulating position.**

    Cooling (Summer):

    With increasing demand for cooling, the supply air temperature regulation operates in the followingmanner and sequence on the existing heat exchanger:

    Increase the power of heat recuperators, * increase the power of air coolers

    *: if possible/available

    **: among themselves synchronized process (matrix)

    Room temperature or exhaust air temperature regulation (shops> 1000 m; Mall; systems 2nd floor):

    Heating (Winter):

    When thermal load increases, the system of out coming air temperature regulation affects the existingheat exchanging machinery in the following way and order:

    the dampers of permanent action closed in minimal position according air quality sensor(always)

    Increase the power of heat recuperators, * power of air heaters is increased, ** power of secondary air heaters is increased,*/** Increase the performance of the FU,** the dampers of permanent action are closed in air recirculation position (super limitation),**

    Cooling (Summer):

    At the increase of cooling load the system of out coming air temperature regulation affects the existing

    heat exchanging machinery in the following way and order: open the dampers of permanent action according air quality sensor (always) Increase the power of heat recuperators, * increase the power of air coolers

    Cooling (Winter):

    With increasing demand for cooling, the discharge air temperature regulation operates in the followingmanner and sequence on the existing heat exchanger:

    Min. supply air temperature Open constant dampers according air quality sensor (always), (FU to min) Dampers opened

    *: if possible/available

    **: among themselves synchronized process (matrix)

    Limitation of supply air temperature:

    Incoming air temperature is limited to its minimal and maximal value. When theres the significantamount of outside heat in the premise, it prevents the temperature of incoming air from being loweredtoo much. Without this limitation low temperature of incoming air would have caused drafts.

    Summer compensation (in cooling mode)

    During the temperature regulation the set value is controlled depending on the outside temperature.During the change of outside temperature in the range between 22C and 32C, for example, set

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    24/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 24 of 44

    value of room temperature gradually increases from 22C to 26C. It allows to avoid too largetemperature gradients between outside and inside temperatures and thus allows for more comfortmode. Besides, that measure allows to save the energy spent for cooling.

    Heating

    General information

    The unblocking of the system for heating systems is activated depending on demand (e.g. via outsidetemperature, outside temperature curve, opening of heating valves, etc.), by seasonal switchingprogrammes or, if run, by optimisation programmes. An individual switching programme is definableand configurable for each system.

    Energy is supplied via three gas boilers, all equipped with a dual burner (oil, gas) feature, whichprovides for limited emergency operation in the event that gas supply is interrupted. The boilers areengaged, based on performance, by the temperature level in the hydraulic separator.

    In consumer closed-loop controls the temperature is managed via the associated control valve, where,as shown in the schemata, there is a slide of the set-point as a function of outside temperature.

    For floor heating a maximum limit is provided for.

    DDC functions such as weather-driven flow temperature control, room correction, standby,optimisation, pump protection and limiting, etc., serve as the basis for system programming.

    The FM area (1st basement) will be regulated by a reference room thermostat (activation of thethermoelectric actuators).

    Cooling

    General information

    Cold production is performed by chillers and cooling towers.

    The higher-level release of the cooling systems is actuated based on demand (e.g. outdoortemperature or outdoor temperature curve) or by a seasonal scheduling programme. The release ofthe chillers is a function of storage temperature. If one chiller fails, the second network will be supplied

    by the other remaining chiller.Increasing the chilled water temperature as a function of outside temperature (e.g.> 35C)

    Inlet temperature regulation in the condenser circuit to the chillers.

    Chiller regulation including filling, draining and frost protection

    DDC functions such as flow temperature control, set-point slide, low limit, maximum limit, pumpprotection, etc. serve as the basis for system programming.

    Sanitary

    Hot water

    Boilers that work on electricity are installed.

    Temperature is regulated by built-in thermostat independently of DCC.

    Distribution

    Water distribution is performed using separate system and is not the part of BMS.

    Signals of cut-off and water consumption are transferred and displayed in BMS system.

    Sewage pumping stations

    Sewage pumping stations are a separate system and are not included in BMS. Breakdowns and errorsare displayed in BMS system.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    25/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 25 of 44

    Pressure increase stations

    Separate system, not a part of BMS. Breakdowns, errors, tank volume (min/max) are displayed inBMS system.

    Separator stations

    Separator stations are a separate system and are not included in BMS. Breakdowns and errors are

    displayed in BMS system.

    Fire-extinguishing systems

    Sprinklers, hydrants and gas extinguishing systems are a separate system that is not included in BMS.Breakdowns and errors are displayed in BMS system.

    Rainwater / grey water usage

    Level gauges, ON-OFF-AUTO mode and fault-standby alarm are provided.

    Electrical Engineering

    Control system functions:

    Sectional door systems (per door)

    Well installations (per well)

    Lighting circuit

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    26/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 26 of 44

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    27/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 27 of 44

    Monitoring functions:

    From the following parts of the plant (depending on the design), operating and malfunction alarms, aswell as stand-by and release signals, will be taken up and transmitted to the DDC system.

    These messages will be archived as trend logs. Alarms will be passed on as such.

    Medium-voltage switchgear (position of the main switch) Transformers Low-voltage main distribution board (position of the main switch, failures, ...) UPS Diesel generators Central battery system Gully heaters Trace heating CO-warning system

    Counting:

    For energy analysis, performance meters for electricity, heating and cooling energy are switched ontothe DDC system.

    DDC functions such as pulse counting, heat measurement, limit values, etc. serve as the basis forsystem programming.

    2.4. MANUFACTURER LIST

    The products and types listed are understood as quality and design specifications by the client. Thechoice of product is essentially free, provided the client's quality, functional and design specificationsas well as the specified technical parameters are met.

    Honeywell Sauter Johnson-Control

    Siemens

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    28/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 28 of 44

    3. General quality description HVAC

    00 Quality description

    00.05 Special regulations for the individual case

    00.05.14 Fire protection

    Notwithstanding all the existing legal obligations for the contractor he takesfollowing fire protection measures without separate reimbursement:

    According to Romanian directives and regulations, fire protection on theconstruction site

    00.06 Technical requirements

    00.06.01 Security, legal verification

    By legal rule of evidence the fulfilment of the security requirements for theproposed electrical operation means is proved in form of test or conformity signand/or through conformity declaration as written in respective official documentsto the electrical technique law or through a certification, issued abroad andacknowledged by the prescription or certificate of the federal office of economicaffairs.

    00.06.03

    Following regulations for the range of a certain orderer are to be followed in aframe, which was valid at the moment of the end of the offer deadline; in casethere is now deadline, the date of the offer is valid.

    00.06.03B Special regulations Water

    Regulations of the responsible water supply company. The relevant Romanianguidelines have to be followed.

    00.06.03D Special regulations Gas

    Regulations of the responsible gas supply company. The relevant Romanianguidelines from Gas net have to be followed.

    00.06.50 Products containing PVC and halogen

    Products or packaging materials containing the PVC, other synthetic materialscontaining PVC or halogen hydrocarbons are undesired and possibly should not beoffered.

    In case no equally appropriate substitute products are available, it has to bereported and reasoned. The suitability of the substitute products is checked everytime by the appointing office under the aspect of economic viability and assessmentof the ecological and technical advantages and disadvantages. Goods cannot bepackaged with materials containing PVC. Exceptions have to be mentionedseparately and the use has to be reasoned. On demand the bidder is obliged toprovide the appointing office on his own expense with a certificate, that confirmsthat all the product positions that are not mentioned separately contain no PVCproducts, no synthetic materials containing halogen as well as no products,produced with usage of halogen hydrocarbons.

    00.06.64 Safety requirements on electrical equipment

    All electrical equipment, control cabinets, electrical installations and similar mustcomply with the applicable elements of the Act on Electrical Engineering or therelevant provisions and requirements of the local energy supply company. Theproof of this must be provided by the contractor either via an approved test markapplied to the device or via a statement from a state-approved testing centre.

    The contractor must be prepared, following completion of the work and withoutprompting, to draw up an inspection report (in triplicate) for the systems or systemparts he has installed and hand this to the client.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    29/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 29 of 44

    All required proof must be provided by the contractor without prompting and at hisown expense.

    00.06.80

    Following products have to be calculated into the offer. The delivery takes placetimely before the execution of the contract and independently from the deliveryof the documentation.

    00.06.80B Schemes and assembly schedules

    Delivery of all assembly schedules and basic schemes as determined before inconsistent CAD (computer-aided design)-

    -Specifications by principal

    00.06.80C Calculation and design documentation

    Delivery of all Calculation and design documentations

    00.06.80D Setting values of plant components

    Delivery of compilation containing the setting values of all mechanical andelectrical devices

    00.06.80F Tutorial for emergency operations

    Delivery of tutorials and details in triplicate for maintenance of emergencyoperations in case of breakdown of particular plant components

    00.06.80G Plant schemes rearward glass

    Delivery and mounting of plant basic schemes broken according to asset groups,executed as standardized coloured plan prints rearward glass including frame(laminated on aluminium plate). In these plant schemes all products and types ofthe mounting parts have to be registered.

    00.06.80H List of products and types

    Delivery of a quadripartite list of products and types of all mounted devicesincluding the declaration of supplying companies. All required replacement andspare parts (filter cartridges, v-belt dimensions and suchlike) have to be

    specified in this list. Installations and contents will be coordinated with localbuilding inspection immediately after contract award.

    00.06.80K Construction documentation

    Continuative planning, based on the assigned project, including the consulting ofall parties concerned (architect, structural engineer, other relevant contractors, etcetera), inclusion of possible local authority regulations and change requests bythe principal, realisation of the required calculations, writing of functional andtechnical descriptions, submission of all documents in quadruplicate to bereleased by the local building inspection and the principal, inclusion of the resultsof approval process in the continuous planning, compilation of construction andelectrical specifications and all other tasks and services relevant to theconstruction documentation including the verification of all assembly schedulesaccording to Romanian prescriptions.

    00.06.80O Side construction regulations

    All additional disbursement and expenses associated with compliance of theenclosed side construction regulations.

    85 BMS (measurement, control and regulation) programmablecontrollers

    Controllers:

    Controllers are represented by freely programmable control and adjustment unitswith microprocessor control (DDC equipment) and they can function off-line andindepently from other possible controllers and/or control and service devices.

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    30/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 30 of 44

    Controllers perform all monitoring functions, such as measurement, control,regulation, calculation, alarm, limit value monitoring, time and event switching,optimization, as well as self-control which shut out the necessity of usingstandard components for certain tasks. If controllers operate together with othercontrollers and/or control and service devices, in case of shutdown or failure ofone of these devices or connection, a controller continues to operate in an off-line mode. When the voltage switches off, controller outputs are swithced over tothe specified position. Unless specified otherwise, the controller may be replacedwith a previously adjusted DDC regulation and control unit, in case it meets allrequirements, imposed on the controller, and is eqipped with required interfacesfor remote control and remote adjustment of basic parameters or data entrancepoints.

    Accuracy:

    Time of reaction and regulating algorithms are co-ordinated with each other orwith the regulation line by means of monitoring hardware and software (forexample, with the help of temporary and fixed-time sensors, servo driveoperation time) in such a manner that will help to ensure regulation processstable characteristic within the range of required statistical accuracy in terms ofthe whole interval of disturbing effect.

    Central station is equipped with an alert message/event printing device, a PC-based multicolor graphic control station, as well as with a color picture monitor17.

    Software

    The range of obligations regarding controller software development includesperipheral device interface definition, selection and adjustment of configurationof the required functional modules, calculation of all required parameters,programm and data entry and storage in the controller, testing of softwarewithout peripheral devices and development of documentation that includes thelist of connected peripheral devices, program configuration and parameters,program modules description.

    Message categories:

    Danger messages: result in mechanism(-s) shutdown, even if the mechanism orits parts are in manual operation mode. Danger messges have to beacknowledged,

    a program, called in by a danger message, remains active till the moment ofacknowledgement.

    Sensors are connected on the principle of closed current.

    Failure messages: result in defective device shutdown, but not in the wholemechanism shutdown.

    Failure messages neednt to be acknowledged. Sensors are connected on theprinciple of closed current.

    Operation messages: inform about switching state of a device. Sensors areconnected on the principle of operating current.

    Controller, SW: hereinafter software is referred to as the abbreviation SW.

    85.01 Monitoring system

    Unless specified otherwise, integrated system is offered for measuring sensors,controllers and regulating devices, including software.

    85.02 Scope of performance group

    This group includes all controller components required for automatic operation ofthe HAVS technological equipment (heating, air conditioning, ventilation and

  • 7/30/2019 111207 330-FCCMall BMS Technical Description E

    31/44

    Raiffeisen evolution

    Floreasca City Center Mall BMS

    23.05.2011 Page 31 of 44

    sanitary). Automatic and off-line regulation and control of technologicalequipment may be implemented by using them without the help of upper levelcentral control system (ZLT).

    85.11 20 V emergency power supply mode software

    Emergency power supply mode: application software (SW) used for loadshutdown of consumers for which emergency power supply is not provided. Theprogram is suitable for connection of the specified amount of consumers.Consumers are connected in accordance with the equipment layout.

    85.11.21 SW of general failure alarm with warning horn

    Application software (SW) for general failure alarm with acknowledgementperformed through control unit or digital input is used for activation of externaloptical signal indicator by means of producing a flicker effect upon danger,failure or service signal entry. The external alarm sounder is activated uponsignal entry prior to its acknowledgement.

    85.12 Controller software, system functions

    Application software for controler system functions:

    Safety functions have priority over other functions. System automation programshave priority over automation functions of system components or devices,however they can affect only those system elements and devices which areregulated and controlled not in manual mode or by safety function. Input signalsrequired for system function are provided by corresponding controller input or itsconnection interface. Expenditures for development of SW used for signaltransfer to one or several other controllers are taken into account in positions ofthe subgroup Controller SW, signal transfer.

    85.12.02 Application software for protecting shutdown

    System shutdown program (OFF) depending on a specified condition.

    85.12.04 Application software (SW) for system control

    through specified command device or program address.

    85.12.10 SW, time switching

    Application software for time switching with daily, weekly and yearly curves,minimal switching interval is 1 minute.

    85.12.21 SW, tracking mode

    Application software for ventilation and air conditioning system control in trackingmode. Control is carried out depending on minimal and maximal limit value.

    85.12.22 SW, night cooling mode

    Application software for ventilation and air conditioning system control in nightcooling mode with a 100-percent outside air supply, activation is carried outupon exceeding the temperature limit value that is adjusted in parameters,

    switching on takes place regardless of difference between room and otside airtemperatures which is adjuxted in parameters.

    85.12.50 SW, supply temperature regulation depending on outside temperature

    Application software for supply temperature regulation depending on outsidetemperature with a possibility of emergency parameter connection