    NOTES ON MOTOR APPLICATION, NAMEPLATE RATING &

    DESIGN APPROACH BASE RATING

    The subjectmotorwill be driven by variable voltage variable frequency power

    controllerto

    cater

    to

    the

    Periodically

    Pulsating

    Torque

    requirement

    of

    HCSD

    Pumpcontinuouslyatanyspeedwithinthespeedband(138rpm1697rpm)of

    pumpunderspecifiednormaloperation.

    At rateddutypointoperationofpump [203m3/hr,4650kPa,1379rpm (M)], the

    continuousRMSpower requirement frommotorwillnotbemore than300kW.

    Thepump ishoweverselectedforamaximumdischargeof250m3/hrslurryflow

    againstamaximumdischargepressureexposureup to7000kPawhen theRMS

    Power requirement from motor will be around 519kW @ 1697rpm of motor

    shaft.The

    periodic

    pulsation

    of

    torque

    during

    continuous

    pump

    operation

    will

    be

    Maximum:113.5%,RMS:100.6%,Average:100%&Minimum:77.8%.

    On the basis of above the motor is designed for an Approach Base Rating of

    650kW@[email protected]

    570kW@1493rpmandwillbe suitable for constant torqueoperation through

    690VratedVVVFPowerControllerwithinaspeedbandof138rpm1697rpm.

    REFERENCE DOCUMENT:

    TITLE : TECHNICAL DATA SHEET : HCSD PUMP DCIPS DWG NO. : 10P011ADPH1

    2 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    3/17

    Matrishri Usha Jayswal Mega Power Project

    Phase # I & II (4 X 270 MW), Unit # 1 to 4ASH HANDLING SYSTEM

    DCIPS Doc No :Main Supplier :Consultant :

    10P01-1A-E-604DC Industrial Plant Services Pvt LtdDCPL

    Page 1 of 5

    Cl.NO.

    CONTRACTORS NAMEPROJECT AND PACKAGE

    MOTORS

    1. GENERAL

    a) Manufacturer & Country of origin Marathon Electric/ India

    b) Equiment driven by motor HCSD Pump

    c) Motor type Sq, Cage Induction motor

    d) Quantity 2 Nos ( 1 for PH 1 + 1 for PH II )

    e) Coupling Direct Flexible coupling

    2.DESIGN AND PERFORMANCE DATA

    i) Rated Voltage (volts) 690 V (Base Voltage)

    ii) No. of Phases & Frequency 3 Ph, 56.8 Hz (Base Frequency)

    iii) Permissible variation of

    a) Voltage (volts) 10%

    b) Frequency (Hz) 5%

    c) Combined voltage and frequency 10%

    iv) Minimum permissible starting Voltage (volts) 80%

    v) Rated speed at rated voltage and frequency (rpm) 1698 (Base rpm)

    vi) Direction of rotation as viewed from DE END Bi-Directional

    vii) Derated rating for specified normal condition i.e. 50 deg.C ambient temperature (KW)

    650 KW (Base KW rating)

    viii) At base Voltage and frequency

    a) Full load current Amps

    b) No load current (Approx.) Amps.

    577 Amps

    265 Amps (Max.)

    ix) Power Factor at

    a) 100% load 0.87

    b) 75% Load 0.83

    c) 50% Load 0.72

    d) No load 0.072

    3 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    4/17

    Matrishri Usha Jayswal Mega Power Project

    Phase # I & II (4 X 270 MW), Unit # 1 to 4ASH HANDLING SYSTEM

    DCIPS Doc No :Main Supplier :Consultant :

    10P01-1A-E-604

    DC Industrial Plant Services Pvt Ltd

    DCPL

    Page 2 of 5

    Cl.

    NO.

    CONTRACTORS NAME

    PROJECT AND PACKAGE

    e) Starting 0.22

    f) At duty point 0.86

    x) Efficiency at rated voltage and frequency (%)

    a) 100% load 95.0%

    b) 75% load 94.5%

    c) 50% load 93.5%

    xi) Starting current (Amps) at

    a) 100% voltage 720% FLC (4154.5 A) (Butdepends on VFD)

    b) 85% voltage 610% FLC (3519.7 A) (But depends on VFD)

    c) 80% voltage 575% FLC (3317.8 A) ( But depends on VFD)

    xii) Starting time with minimum permissible voltagea) Without driven equipment coupled 0.8 secs (But depends on VFD)

    b) With driven equipment coupled 5.5 secs (But depends on VFD)

    xiii) Safe stall time with 110% of rated voltage (Sec.)

    a) From hot conditionb) From cold condition

    20 Secs25 Secs

    xiv) Torques ;

    a) Starting torque at min. permissible voltage (kg-mtr.) 90%FLT (But depend on VFD)

    b) Pull up torque at rated voltage (Kgm) 130%FLT (But depend on VFD)

    c) Pull out torque (Kgm) 330%FLTd) Min. accelerating torque (Kgm.) available 35%FLT (But depends on VFD)

    e) Rated Torque (Kg.m) 372.7 KgM

    xv) Stator winding resistance per phase in ohms at 20Deg.c) Approx

    0.00811

    xvi) GD2 value of motor / Load (Kgm) 76 KgM / 16 KgM(max.)

    xvii) No. of permissible successive starts when & motor is in

    a) Hot condition 2

    b) Cold condition 3

    xviii)

    a) Locked rotor KVA input 4965

    b) Locked rotor KVA / KW 7.64

    xix). Bearings

    4 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    5/17

    Matrishri Usha Jayswal Mega Power Project

    Phase # I & II (4 X 270 MW), Unit # 1 to 4ASH HANDLING SYSTEM

    DCIPS Doc No :Main Supplier :Consultant :

    10P01-1A-E-604DC Industrial Plant Services Pvt LtdDCPL

    Page 3 of 5

    Cl.NO.

    CONTRACTORS NAMEPROJECT AND PACKAGE

    a) Type DE: NU230-C3 / NDE: 6220-C3

    b) Manufacturer SKF/FAG/Equiavalent

    c) Self Lubricated or forced Lubricated Self Lubricated

    d) Recommended Lubricants Sheel Alvania RL 3e) Guaranteed Life in Hours 50,000 Hrs

    xx) Vibration

    a) Velocity (mm/s) 2.8 mm/sec (As per IS:12075)

    b) Displacement (microns) 50 microns (As per IS:12075)

    xxi) Noise Level (DB) 85 dB @ 1.5 meter (As per IS:12065)

    3. CONSTRUCTIONAL FEATURES

    i. Applicable standard to which motor generally conforms IS:325, 1996

    ii. Frame Size FDC450F3

    iii. Type of duty Continious duty / inverter duty

    iv. Type of enclosure and method of cooling, Degree ofprotection.

    TEFC / IC411 / IP55

    v. Type of mounting Horizontal Foot (B3)

    vi. Stator winding Insulation

    a) Class & Type Cl `F with temp. rise limited to Cl B /Mica based resin poor VPI insulation systemb) Tropicalised (Yes / No) Yes

    c) Temperature rise over specified max.

    i) Cold water temperature of 38 deg. C. NA

    ii) Ambient Air 50 deg. C. 70 Deg.C

    d) Method of temperature measurement Winding resistance method

    e) Stator winding connection Delta

    f) Number of terminals brought out 6 Nos.

    vii. Type of terminal box for

    a) Stator leads Std. typeb) Space heater Std. type

    c) Temperature detectors Std. type

    d) Instrument switch etc. NA

    iii. For main terminal box

    a) Location LHS from DE

    5 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    6/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    7/17

    Matrishri Usha Jayswal Mega Power Project

    Phase # I & II (4 X 270 MW), Unit # 1 to 4ASH HANDLING SYSTEM

    DCIPS Doc No :Main Supplier :Consultant :

    10P01-1A-E-604DC Industrial Plant Services Pvt LtdDCPL

    Page 5 of 5

    Cl.NO.

    CONTRACTORS NAMEPROJECT AND PACKAGE

    pads

    xvi. Paint shade RAL 5012

    xvii. Weight of (approx.)

    a) Motor Stator(kg) 3000 Kgb) Motor Rotor (kg) 1500 Kg

    c) Total Weight(kg) 4500 Kg

    4. CHARACTERISTIC CURVES

    i.Torque speed characteristic of the motor Enclosedii. Thermal withstand characteristic Enclosed

    iii. Starting current Vs. Time Not Enclosediv. Starting current Vs. speed Not Enclosedv. Neg. sequence current vs Time Not Enclosedvi. P.F and Efficiency. Vs. Load Enclosedvii. Calibration curves of PTC & BTD Enclosed

    Note:1) All above performance figures are subject to IS tolerance.2) All above performance figures are at base Voltage & Frequency and at base KW rating

    Aux. Motor Detals:

    Rating / Pole : 5.5 KW / 4 Pole

    Supply Voltage : 415V +/-10%Frequency / Phase : 50 Hz +/-5%, 3 Ph.

    Direction of rotation : Clockwise form DE.

    ADDITOINAL FEATURES FOR VFD MOTORS.

    i) Insulated bearing housing at NDE side will be provided.ii) 6 Nos. PTC130 thermistors for windings are providediii) External & Internal earthing facility provided on terminal box.

    iv) Mica based resin poor VPI insulation system provided for windings.

    Details related to VVVF drive :*Suitable for IGBT Drive* Voltage Rise Time > 0.1 sec.* Peak Voltage : 3000 V (Max.)

    7 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    8/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    9/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    10/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    11/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    12/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    13/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    14/17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    15/17

    Marathon Electric

    EFFICIENCY & POWER FACTOR VS % LOAD CURVE

    (without VFD)

    570 KW, 4 POLE, 690 V, FDC450F3 Motor

    Customer : APRL

    85

    85.5

    86

    86.5

    87

    87.5

    88

    88.5

    89

    89.5

    90

    90.5

    91

    91.5

    92

    92.5

    93

    93.5

    94

    94.5

    95

    95.5

    50 75 100

    % LOAD

    %EFFICIENCY

    0.4

    0.42

    0.44

    0.46

    0.48

    0.5

    0.52

    0.54

    0.56

    0.58

    0.6

    0.62

    0.64

    0.66

    0.68

    0.7

    0.72

    0.74

    0.76

    0.78

    0.8

    0.82

    0.84

    0.86

    0.88

    0.9

    0.92

    POWERFACTOR

    EFFICIENCY POWER FACTOR

    15 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    16/17

    Temp. VS Resistance Characteristi c o f PT100 BTD

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    200

    0 50 100 150 200 250

    Temp. ( Deg. C )

    Resistance(Ohm)

    16 of 17

  • 7/28/2019 10P01-1A-E-604-R00_HCSD_PUMP_MOTOR

    17/17