1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : Simulator Inlet : A 22 foot long, 22 inch diameter inlet duct has been installed to feed the blower Transducer to measure airflow installed hot wire anemometer in duct center line treat inlet flow as "classic" parabolic distribution and derate velocity by 10% to determine mass flow rates calibration curve still being worked out Air flow heating : core heating assembly installed in-line duct heaters are wired locked out, not serviceable incorrect part installed; replacement expected within the week On-going : hot plates ALL hot plate materials on-site assembly for plate #1 completed this week plate #2 expected by the end of October will require testing exterior to the simulator prior to placement (control software and final assembly validation) dry ice; looking to produce on-site Work to date : hot-agent simulant work developing/learning simulator procedures and behavior International Halon Replacement Working Group Ottawa, Canada 13-14October 1999 Douglas Ingerson, Federal Aviation Administration WJ Hughes Technical Center, Fire Safety Section, AAR-422 Atlantic City Int'l Airport, NJ 08405 USA

Upload: kendra-cubberly

Post on 01-Apr-2015

217 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

1

Simulator Status,FAA WJ Hughes Technical Center

• Completed since the April 1999, Seattle meeting :– Simulator Inlet :

• A 22 foot long, 22 inch diameter inlet duct has been installed to feed the blower

• Transducer to measure airflow installed– hot wire anemometer in duct center line– treat inlet flow as "classic" parabolic distribution and

derate velocity by 10% to determine mass flow rates– calibration curve still being worked out

– Air flow heating :• core heating assembly installed• in-line duct heaters are wired

– locked out, not serviceable– incorrect part installed; replacement expected within the

week

• On-going :– hot plates

• ALL hot plate materials on-site• assembly for plate #1 completed this week• plate #2 expected by the end of October• will require testing exterior to the simulator prior to

placement (control software and final assembly validation)

– dry ice; looking to produce on-site• Work to date :

– hot-agent simulant work– developing/learning simulator procedures and behavior

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Page 2: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

2

High Bypass Ratio Turbofan Simulator - Core Heating Impact on ByPass Air Flow

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

0 600 1200 1800 2400 3000 3600 4200 4800 5400

Time (s)

Tem

pera

ture

(°F

)

fwdcor6:00

aftcor6:00

2inair6:00

4inair6:00

fwdcor12:00

aftcor12:00

2inair12:00

4inair12:00

cvr approx 36 ac/minmdot approx 4.3 lbm/s

cvr approx 86 ac/minmdot approx 11 lbm/s

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

0 600 1200 1800 2400 3000 3600 4200 4800 5400

Time (s)

Tem

pera

ture

(°F

)

fwdcor6:00

aftcor6:00

2inair6:00

4inair6:00

fwdcor12:00

aftcor12:00

2inair12:00

4inair12:00

cvr approx 36 ac/minmdot approx 4.3 lbm/s

cvr approx 86 ac/minmdot approx 11 lbm/s

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Page 3: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

3

HFC-125 Distribution Comparison, Simulator Environment, 30Jul99

HFC-125 Distribution Comparison, Average Distribution Comparisons, 30Jul99

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Page 4: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

4

0

2

4

6

8

10

12

14

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

HFC-125 - h125.99.730.02.hot.c

0

2

4

6

8

10

12

14

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

HFC-125 - h125.99.730.05.ambient.c

Bottle volume = 600 in^3Agent weight = 5.44 lbfAgent storage pressure = 650 psigAgent storage temp = 200 °FAir flow temp = 92°FAir flow = 4.3 lbm/s

Bottle volume = 600 in^3Agent weight = 5.44 lbfAgent storage pressure = 650 psigAgent storage temp = 200 °FAir flow temp = 215°FAir flow = 3.5 lbm/s

Page 5: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

5

Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

• 1994-1995. Actions sought to minimize the release of Halon 1301 unnecessarily

• DoD (U.S. Navy) sponsors work through the National Institute of Standards and Technology (NIST) to develop or discover a simulant for Halon 1301 for use in nacelle discharge testing

• The cumulative effort also involves Boeing, Walter Kidde Aerospace (WKA), and Shorts Brothers, PLC

• NIST reviewed existing material data bases for materials having :

– characteristics commensurate with the application of nacelle discharge testing

– characteristics comparable to Halon 1301 during discharge in this application

• Jakob number• Saturated vapor pressure• Experimental history• Atmospheric lifetime (ODP and ALT)

• 3 candidates selected :– CHClF2

– SF6

– C2HF5 (HFC-125, pentafluoroethane)

Page 6: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

6

Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125

• Field Work :– NIST– USN, WKA on the F-18– Boeing on the Pratt and Whitney PW 4084 on the B777

airframe– Shorts Brothers, PLC on the Allied Signal TFE731-40

on the IAI Astra SPX airframe• Conclusions :

– HFC-125 most effectively simulates a Halon 1301 discharge in these applications

– US military specification Mil-E-22285 edited to reflect such procedures

• Additional field work, April 1998.– FAA personnel assisting USN on agent distribution

within the F-18 nacelle– As courtesy to the FAA, a simulant test pair is run– Results reflect previous results– Historical review indicates overdesign far outweighs the

delta found between agents in the simulation– FAA publishes technical note on the concept

• Qualitative discussion regarding limitations :– the simulation appears to be sensitive to the ventilation

rate of the compartment; compare cargo and nacelle environments (forced vs. natural/gravitationally driven ventilation)

– recent work at the FAATC indicates agent temperature likely plays a role in the simulation effectiveness

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Page 7: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

7

Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125

• Procedures.– Agent Storage :

• Calculate/determine required weight of Halon 1301 for application

• multiply desired Halon 1301 weight by 0.77 to determine the required weight of HFC-125 for the simulation

• load and superpresurize with N2 as would be done for the design Halon 1301 bottle

• cold soak the bottle• perform test

– Halonyzer operation :• the analyzer is configured for HFC-125• capture the simulant test with the HFC-125 calibration

curve as the analyzer reference• compare results to the certification criteria of Halon 1301• determine success or failure

• NOTE : This procedure is not intended to provide a method to determine a weight of HFC-125 for fire suppression purposes. This process delineates a method to use HFC-125 in a manner which would reasonably simulate the discharge of Halon 1301 in an aircraft engine nacelle from a gaseous distribution perspective.

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Page 8: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

8

Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125

• References.• Kaufmann, K. J., Miller, M. P., Wozniak, G., and Mitchell, M.D., 1995,

"Results of Halon 1301 and HFC-125 Concentration Tests on a Large Commercial Aircraft Engine Installation," International Halon Replacement Working Group Minutes, United States Department of Transportation, Federal Aviation Administration, W.J. Hughes Technical Center, Atlantic City, NJ.

• Ingerson, D. A., "Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125," DOT/FAA/AR-TN99/64, United States Department of Transportation, Federal Aviation Administration, W.J. Hughes Technical Center, Atlantic City International Airport, NJ.

• Military Specification MIL-E-22285(AS), Amendment 3, 1996, "Extinguishing System, Fire, Aircraft, High-Rate-Discharge Type. Installation and Test of," United States Department of Defense, Department of the Navy, Naval Air Systems Command, Washington, D.C.

• Mitchell, M. D., 1994, "Methodology for Halon 1301 Simulant Testing and Concentration Equivalence Verification," Report No. R-5102, Kidde Technologies, Wilson, NC.

• Mitchell, M. D., 1995, "Full Scale Halon Simulant Testing of F-18D Aircraft Using Bromotrifluoromethane and Pentafluoroethane," Report No. R-5127, Kidde Technologies, Wilson, NC.

• Riordan, D., 1995, "Engine Fire Extinguisher Agent Concentration Testing," International Halon Replacement Working Group Minutes, United States Department of Transportation, Federal Aviation Administration, W.J. Hughes Technical Center, Atlantic City, NJ.

• Womeldorf, C. A., Grosshandler, W. L., 1995, "Selection of a CF3Br Simulant for Use in Engine Nacelle Certification Tests," Fire Suppression System Performance of Alternative Agents in Aircraft Engine and Dry Bay Laboratory Simulations, SP890, Vol. 2, p.591-621, National Institutes of Standards and Technology, Gaithersburg, MD.

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Page 9: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

9

Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125, Historical

Example of Overdesign

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Lockheed C-140 Jet Star Concentration Profile at N1 = 78%

(Sommers, 1970, p. 34)

Page 10: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

10

Simulating the Distribution of Halon 1301 in an Aircraft Engine Nacelle with HFC-125, Historical

Example of Overdesign

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

General Dynamics F/EF-111 Agent Concentration Profile for Test 1301-8 (Chamberlain and Boris, 1988, p.57)

Page 11: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

11

Halon 1301 - h1301.99.923.01.c

0

2

4

6

8

10

12

14

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

alon

130

1

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

HFC-125 - h125.99.927.01.c

0

2

4

6

8

10

12

14

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Bottle volume = 600 in^3Agent weight = 7.59 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 71°FAir flow = 2.3 lbm/s

Bottle volume = 600 in^3Agent weight = 5.89 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 75°FAir flow = 2.3 lbm/s

Page 12: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

12

HFC-125 - h125.99.930.03.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

Halon 1301 - h1301.99.930.02.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

alon

130

1

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Bottle volume = 400 in^3Agent weight = 3.54 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 72°FAir flow = 2.3 lbm/s

Bottle volume = 400 in^3Agent weight = 4.58 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 73°FAir flow = 2.3 lbm/s

Page 13: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

13

Halon 1301 - h1301.99.a07.01.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

alon

130

1

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Bottle volume = 300 in^3Agent weight = 4.25 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 63°FAir flow = 2.3 lbm/s

HFC-125 - h125.99.a07.02.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

Bottle volume = 300 in^3Agent weight = 3.28 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 64°FAir flow = 2.3 lbm/s

Page 14: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

14

Halon 1301 - h1301.99.a07.04.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

alon

130

1

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Bottle volume = 300 in^3Agent weight = 4.40 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 64°FAir flow = 2.3 lbm/s

HFC-125 - h125.99.a07.03.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

Bottle volume = 300 in^3Agent weight = 3.39 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 64°FAir flow = 2.3 lbm/s

Page 15: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

15

HFC-125 - h125.99.a06.02.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

Halon 1301 - h1301.99.a06.04.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

alon

130

1

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Bottle volume = 300 in^3Agent weight = 3.08 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 70°FAir flow = 2.3 lbm/s

Bottle volume = 300 in^3Agent weight = 4.00 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 70°FAir flow = 2.3 lbm/s

Page 16: 1 Simulator Status, FAA WJ Hughes Technical Center Completed since the April 1999, Seattle meeting : –Simulator Inlet : A 22 foot long, 22 inch diameter

16

HFC-125 - h125.99.a06.03.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

HFC-125 - h125.99.a06.01.c

0

1

2

3

4

5

6

7

8

9

10

0 2000 4000 6000 8000 10000 12000 14000

Time (ms)

%V

/V H

FC

-125

11

9

8

4

1

7

5

2

10

12

6

3

Halonyzer Channel Designations - FAA WJH Technical Center - Nacelle SimulatorForward Ring Mid Ring Aft Ring

12:00 11 1:00 1 12:00 103:00 9 4:30 7 3:00 126:00 8 7:30 5 6:00 69:00 4 11:00 2 9:00 3

International Halon Replacement Working GroupOttawa, Canada 13-14October 1999

Douglas Ingerson, Federal Aviation AdministrationWJ Hughes Technical Center, Fire Safety Section, AAR-422

Atlantic City Int'l Airport, NJ 08405 USA

Bottle volume = 300 in^3Agent weight = 3.08 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 70°FAir flow = 2.3 lbm/s

Bottle volume = 300 in^3Agent weight = 3.08 lbfAgent storage pressure = 400 psigAgent storage temp = 100 °FAir flow temp = 66°FAir flow = 2.3 lbm/s