1Prepared by Dan Sweeney
Energy Use and common sense.Less Air Volume is More Energy savings.
The less amount of air volume that needs to be de-humidified & cooled the less energy is used.
With minimal hot/cold isle isolation 491 Cubic meters of air must be cooled (note entry and closet not included in calculation).
2Prepared by Dan Sweeney
Energy Use and common sense.Less Air Volume is More Energy savings.
With stringent hot/cold isle isolation only 84 Cubic meters of air must be de-humidified & cooled.
This equates to a 83% reduction in the volume of air to be processed.
3Prepared by Dan Sweeney
Energy Use and common sense.Building hot/cold isle isolation into the Data Center.
No hot/cold Isle isolation
4Prepared by Dan Sweeney
Energy Use and common sense.Building hot/cold isle isolation into the Data Center.
Add cold isle cover caps
5Prepared by Dan Sweeney
Energy Use and common sense.Building hot/cold isle isolation into the Data Center.
Add cold isle end of row doors
6Prepared by Dan Sweeney
A brief summary of the specifications on all the equipment for new projects show that with NO EXCEPTION these devices are rated for 30 degrees Celsius operation. The obtuse part is that the REAL requirement actually requires a range of 25-28 degree air at the device inlet.
Device Air inlet25 Celsius
Device Output30 - 32 Celsius
After searching all of Brocade (including Foundry), Cisco, HP, Juniper, Tanberg, Sun (now Oracle) and Cray the only system that did not specifically state operations acceptable at 30 Celsius was the Cray XK6 Supercomputer.
Energy Use and common sense.How cold is “cold enough” ?
7Prepared by Dan Sweeney
75% of cooling cost WASTED 75% of cooling cost utilized
Cover unused cabinet space
Incorrectly isolating Hot Isle from Cold Isle by leaving open blank spaces in cabinets is a major contributor to wasted cooling energy. The combination of installed equipment venting and fans create a large underfloor pressure that pushes the air out the path of lowest resistance. The majority of your cooled air passes un-utilized thru the cabinet and out the hot air return due to the pressure differential created.
Energy Use and common sense.Focus your cooling energy.
8Prepared by Dan Sweeney
Energy Use and common sense.Building hot/cold isle isolation into the Data Center.
9Prepared by Dan Sweeney
Energy Use and common sense.Building hot/cold isle isolation into the Data Center.