1 lrac – lrah air-cooled water chillers air / water heat pumps 6 – 40kw

68
1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

Upload: anis-armstrong

Post on 28-Dec-2015

239 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

1

LRAC – LRAH

Air-cooled water chillers Air / water heat pumps

6 – 40kW

Page 2: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

2

0

200

400

600

800

1000

1200

1400

1600

kW

Page 3: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

3

Product range

5

10

15

20

25

30

35

40

kW

Page 4: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

4

Local user terminal

Electrical panel

RAL7037 colour

Compressor casing

Fan nozzle

Water tank, pump and expansion tank

EvaporatorCondensing coil

Fans

Page 5: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

5

Options offered by this versionNone (min T = 9°C)

Low environmental temp. (min T = - 20°C)Low water temperature ( - 10°C)

Low environmental temperature + water

Hydronic optionsNonePump

Pump and tank

Operating optionsR410A

-

Options offered by this versionNone (min T = 9°C)Low environmental temperature (min T = - 20°C)Low water temperature ( - 10°C)Low environmental temperature + water

Hydronic options-PumpPump and tank

Operating optionsR410A with EEVR410A with EEV and Hot Gas

VERSIONS

Low noise T. O. P.

Page 6: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

6

ControlUECH

Serial connectionsRS485 (UECH) serial outlet

Local network-

ControlUPCOxs

Serial connectionsRS485 serial outlet (UPCOxs) TCP/IP interface (UPCOxs)LonWoks/FTT10 (UPCOxs)

Local networkLAN connected unit (UPCOxs)

VERSIONS

Low noise T. O. P.

Page 7: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

7

Top Operating Performance

Efficiency, protection, control

electronic thermostatic valve satisfies the requirements of partial loads, guaranteeing excellent results in terms of energy efficiency, and adapting to the outside temperature

special circulation with injection of hot gas permits continuous operation with a constant output temperature even against a 0 to 100% variation in the load

integrated UpCOxs systemenables maintenance of ±1.5°C T with EEV, even with no tank complete management of all the alarmsintelligent defrost management (LRAH) and anti-ice up evaporator LAN connection external BMS connection

Page 8: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

8

Energy efficiency

R410A

Twin compressor above 20 kW

Electronic expansion valve (EEV) available for T.O.P. version

Page 9: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

9

Low environmental impact

R410A- ODP zero- GWP In line- TEWI Inferior (-14% Vs R407C)

extremely low noise levels

Page 10: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

10

Reliability

Scroll compressor

fans manufactured in polymeric material

stainless steel thermostatic valve

evolved control (T.O.P.)

painstaking care taken over detail

Page 11: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

11

Low noise levels

standard modulating control

three blade, scythe-type fans guaranteeing extremely low sound impact

sound absorbent polyurethane nozzle

oversized batteries

compressor in larger framework

insulated compressor opening

Page 12: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

12

Easy installation and maintenance

unit fitted with in-cabin tank and pump

R410A: easy fill up

vertical layout

wall mounted installation (max. 10 kW)

compact

can be set to discharge defrost condensation

Page 13: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

13

Versatility

Low noise version T.O.P. version for industrial/ technological applications

double choice of controls

wide-ranging connectivity to external BMS

max. 10 LAN with T.O.P.

Page 14: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

14

Precision

Low noise version with self-adapting control for basic version with control on return

T.O.P. version with control on chilled water delivery with specific predictive PID-type algorithm

1.5°C tolerance on set-point

T.O.P. version with hot gas by-pass device for constant outgoing temperature against 0 - 100% variations in the load

Page 15: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

15

LRA - LOW NOISE VERSION

Page 16: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

16

UECH 210-211 is a compact device enabling users to control the following types of conditioning units:• air-air• air-water• water-water• condensingsingle circuit, with 1 or 2 compressors (steps).

The speed of the cooling fan can be proportionally controlled for currents of max 2A without using any external device.

Main features:• thermoregulation on the input or output sensor depending on the configuration;• condensation control;• input, which can be configured for NTC temperature sensor or 4...20 mA signal;• automatic changeover;• boiler control or integration resistances for heating;• internal fan control for max 3 steps in the air-air application;• dynamic set-point;• parameter setting either using keypad or personal computer;• remote keypad (to max. 100 m) which can be connected directly without serial interfaces;• 4-20 mA or 0-10 V (optional internal card) output;• user interface with menu, 2 different levels of access via password;

EXP200 expansion is only available for the UECH 211 model.

Page 17: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

17

A: alarm outputB: LC filterC: External fan regulatorD: ON/OFF fan relayE: Compressor relayF: Pump relayG: Inversion valve relayH: Heating relay

Page 18: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

18

UECH210 models: analogical optional output which can be used to pilot 4-20mA or 0-10V fans.

UECH211 models: digital, open collector optional output used to pilot the relays of the second compressor.

Page 19: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

19

User InterfaceUser Interface

The interface allows the user to carry out all the operations linked with the use of the unit, and in particular to:• set the operating mode• manage alarm situations• check the state of the resources

The device is able to communicate any kind of information inherent to its state, configuration and alarms by means of a display and the LEDs present on the front.

Select the operating mode:• if heat mode is enabled, the following sequence occurs every time the key is pressed: stand-by > cooling > heating > stand-by• if the heat mode is not enabled, the sequence will be: stand-by > cooling > stand-by

• In menu mode, it becomes the SCROLL UP or UP value (increase in value) key.

Page 20: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

20

• Actuates the alarm reset, as well as switching the instrument on and off.• Pressed once, it will reset all manually reset alarms which are not active;• If the key is pressed for 2 seconds, the instrument will go from ON to OFF or OFF to ON. When OFF, only the decimal point on the display remains lit.• In menu mode, it becomes the SCROLL DOWN or DOWN value (decrease in value) key.

“Mode” and “on-off” keys pressed at the same time:• If both keys are pressed and released within 2 seconds, the visualization menu will drop a level. If both keys are pressed for more than 2 seconds, it will rise up a level.• If the last level of a menu is visualized, pressing and releasing within twosecond will the system will rise by a level anyway.

User InterfaceUser Interface

Page 21: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

21

On the display, the following will be shown during normal visualization:

• Adjustment temperature, in tenths of Celsius degrees with a decimal point or Fahrenheit without a decimal point;

• The alarm code if at least one is active. If more than one alarm is active, the first is visualized according to the Alarm Table (see further).

• If the thermoregulation is not based on analogical inputs and depends on the state of a digital input (AI1 or AI2 configured as digital inputs) the “ON” or “OFF” label is visualized depending on the state of the thermoregulator (active – inactive).

• In menu mode, visualization depends on the position in which it is found. Labels and codes are used to help the user identify the function set.

• Decimal point: when the hours of operation are visualized this indicates that the value must be multiplied x 100.

• If a numerical value is visualized on the display and neither the HEAT nor COOL LEDs are on, the controller is in STAND-BY mode.

User InterfaceUser Interface

Page 22: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

22

User InterfaceUser Interface

Page 23: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

23

Remote KeypadRemote Keypad

• The remote display keypad is a faithful copy of the visualization of the information on the instrument and has the same LEDs.

• The functions are identical to those listed previously.• The only difference is the use of the UP and DOWN keys (value

increase and decrease) separated by the MODE and ON/OFF keys.

The connection is illustrated below:

The clamps of the remote keyboard must be associated with the following colours:• 24 > blue• 25 > red• 26 > black

WARNING! The clamp connections of the remote keyboard are inverted compared with those of the connector.

Page 24: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

24

The unit arrives from the factory on stand-by, i.e. only the reading value of the input sensor will be visualized on the display, but no operating organ is active.

To activate the unit, press the UP key and a LED will light up under the cool symbol.If the unit is enabled for heating too, every time UP is pressed, the following modes will appear in sequence: stand-by>cooling>heating>stand-by.

If, on the other hand, you wish to switch the entire unit off completely, press the DOWN key for 3 seconds (the decimal LED will remain on). To switch on, press the DOWN key for 3 seconds.

In case of a blackout, when the power supply returns, the control will return to the state it was in before the back out. If de-frosting was in progress, the procedure will be annulled. All timings in progress will be annulled and restarted.

Page 25: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

25

Step-by-step procedure for modifying the cooling set-pointa. Press the UP and DOWN keys once together to view the SET codeb. Press UP and DOWN together again to view the COO code. This is the parameter for modifying the cooling set-point. Press the UP and DOWN keys again to view the parameter to modify.c. Press UP to increase the value or DOWN to decrease the value until you reach the value required.d. After setting the value, press the UP and DOWN keys for 5 seconds until the system drops a level.Repeat this procedure until the value of the sensor connected is visualized.

Step-by-step procedure for modifying the heating set-pointa. Press the UP and DOWN keys once together to view the SET codeb. Press UP and DOWN together again to view the COO code. Press the UP or DOWN key to view the HEA parameter.c. Confirm by pressing the UP and DOWN keys, the parameter to modify will be visualisedd. Repeat steps c and d

Note: If no key is pressed for 60 seconds after activation of the procedure, the display will return to the normal operating mode without memorizing any parameters which had been modified.

Page 26: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

26

Reading the temperature sensors connectedThe sensors connected can be read once only, through the following procedure:a. Press the UP and DOWN keys once together – the SET code will be visualisedb. Scroll using the UP or DOWN keys until the TP parameter is visualisedc. Confirm by pressing UP and DOWN, the T01 parameter will be visualisedd. Confirm, again using UP and DOWN, the reading value being carried out at that momentwill be visualisede. To return back a level, press UP and DOWN for 5 secondsf. To visualise the value of the other sensors, scroll using the UP or DOWN keys until youreach the parameter required, then confirm.g. To exit the masks, press UP and DOWN for 5 seconds and repeat until you have exited alllevels.

The table below describes its functions:

Page 27: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

27

Activation of contacts ID4 and ID5Should the user wish to activate the remote on/off (ID4) by means of an external contact, s/he mustsimply remove the pin-strip connected to the unit terminal board (see wiring diagram).Should the user wish to activate the summer/winter exchange contact (ID5) by means of anexternal contact, s/he must remove the pin-strip connected to the unit terminal board (see wiringdiagram), access configuration parameter H27 and modify the parameter.Modify the parameter as follows:a. Press UP and DOWN once together, the SET code will appear on the display;b. Scroll using UP or DOWN until the PASS parameter appears on the display;c. Confirm by pressing UP and DOWN together, and key in the USER 22 password;d. Confirm by pressing UP and DOWN together, scroll to the CNF parameter;e. Confirm by pressing UP and DOWN together, scroll to the H27 parameter;f. Confirm by pressing UP and DOWN together, modify the parameter setting it to 1;g. Confirm by pressing UP and DOWN together;h. Exit the screens by pressing UP and DOWN together for 5 seconds, then repeat untilexiting the system completely.

Page 28: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

28

Configuration for the low temperature versionIn the event that the machines are used in the special low temperature version, you are advised toread the instruction manual which is attached regarding the introduction of the anti-freeze and themodification of some working parameters.In order to change these parameters, it is necessary to enter with the password USER (see theattached envelope). Simultaneously push the two buttons once; when the word PASS is found,insert the code and confirm it by pushing the two buttons once more. Then scroll through thescreens described below:

CNF ParameterH04: Set-point min in cool = -20G01: Set-point cool = -2CP ParameterC08: Accumulated compensation ability = 0 disabledFRO ParameterR10: Set minimum antifreeze resistance = -20ALL ParameterA11: Antifreeze alarm set = -20This type of configuration is carried out to produce water at a temperature of -5°C.

Page 29: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

29

Page 30: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

30

AlarmsAlarms

UECH 210/211 carries out a complete system diagnostics. Alarms are manually resettable by pressing and releasing the ON/OFF key.

The activation of an alarm causes three effects:• the end users involved are blocked;• signalling on the keypad display;• signalling by a solid state output with transistor (12-24V~ with max 500mA current).

Signalling is formed of an “Enn” type code (nn indicates a 2 figure number which identifies the type of alarm), listed below:

Page 31: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

31

AlarmsAlarms

Page 32: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

32

Alarm RelayAlarm Relay

Page 33: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

33

Alarm RelayAlarm Relay

Page 34: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

34

LRA Low Noise - Refrigerant DrawingLRA Low Noise - Refrigerant Drawing

Page 35: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

35

Page 36: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

36

The microprocessor control independently manages unit operation. The control unit consists of:

a microprocessor control card, installed in the electrical panel;

a graphic user interface installed in the control unit;

the possibility to connect another user terminal with the same functions by means of an RJ11 connector.

The adjustment programme is in the microprocessor control card, on which all the operating parameters are memorised. These parameters can be visualised and set using the user interface. The control system enables the following functions:

temperature control based on the set-points which can be set using the user interface;

setting a double temperature set-point (both during cooling and heating), which is commutable by remote control;

complete alarm detection system;

storage of all alarm events;

Page 37: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

37

• alarm signal contacts, which can be configured using the user interface;

• programming of the automatic restart when the power supply returns;

• remote controlled switching on/off of the unit;

• control of all the compressor operating times and rotation of compressor activation in order to guarantee efficiency and reliability;

• electronic thermostatic valve adjustment and fault signalling;

• passwords for 2 programming levels (settings and service, refer to envelope supplied with manual);

• communication with a supervision system by means of an RS485 serial card (optional);

• counting of operation hours and number of start ups of the most important components;

• display of all of the values read by the sensors connected to the control card;

• management of the clock/calendar (clock card optional);

• differentiated weekly on/off time bands (with optional clock card): Weekday – Pre-holiday – Holiday;

• override function, with which users can manually control the operation of the main components, without excluding the remote control device.

Page 38: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

38

The user interface consists of:

rear-lit 4x20 pixel LCD display;

6 keys for navigating and modifying the parameters.

Page 39: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

39

Before starting up the unit, Uniflair recommends checking that the voltage connected is the one specified on the adhesive label applied to the unit. If the unit is a three-phase unit, check the sequences of the L1 L2 L3 phases since they could cause the control itself not to switch on. Check the electrical connections from other devices external to the unit, as well as the hydraulic connections made. Insert the general switch and check that the incorporated machine control unit display switches on. The unit which has just been switched on will be on stand-by and will display the output water temperature as well as information concerning machine start up. If the clock card has been inserted, the time and day will also be displayed

Local start up using the keypad: Press ENTER once to start up the unit. Press and hold down the ENTER key for 3 seconds to switch the unit off. Automatic start up: the control is configured so that the unit can be switched on/off via: 1. a remote ON/OFF contact; 2. supervision system (only in units equipped with a serial card); 3. programmed automatic time bands (only in units equipped with a clock card).

Page 40: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

40

Press the UP or DOWN keys to display the masks containing the unit operating parameters in reading mode only. To modify the parameters, key in the password contained the envelope enclosed with this manual. There are two passwords, one for the service menu and one for the settings menu.

Page 41: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

41

Depending on the machine configuration, some of these masks may not be displayed. The ―read only‖ masks which do not require a password are: historical alarm I/O state

1. Press UP on the main mask until the 2nd mask is displayed; 2. Press ENTER and select the parameter required using UP or DOWN; 3. Press ENTER to confirm; 4. Once entered scroll using UP or DOWN; 5. Press ESCAPE to exit.

Page 42: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

42

The reading-only and writing masks in the settings level are:

alarm address unit interconnection clock calendar set-point counter

1. Press and hold down the Prg key for 3 seconds from the main mask; 2. Key in the settings password (refer to envelope); 3. Press ENTER and select the mask required using UP or DOWN; 4. Press ENTER to confirm, select the item required using the UP or DOWN keys; 5. Press ENTER to confirm; 6. Once entered scroll using UP or DOWN and select the item required using ENTER again; 7. Press ESCAPE to exit.

Page 43: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

43

The read-only and writing masks in the service level are:

service menu

1. From the main mask press UP until the 1st mask is displayed;

2. Press ENTER and select the item required using UP or DOWN;

3. Press ENTER to confirm;

4. Press and hold down the Prg key for 3 seconds and key in the configuration menu password; (refer to envelope). Press ENTER to confirm;

5. Once entered, scroll using UP or DOWN, confirm the item to modify, press UP or DOWN and reconfirm to save the parameter;

6. Press ESCAPE to exit.

Page 44: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

44

Service menu: this mask provides access to the machine configuration. After introducing the password, the user will access the mask below:

HARDWARE CONFIGURATION The unit adjustment programme must be ―configured‖, that is, adapted to the machine in which it is to be installed. All of the elements which the unit is equipped with and which the microprocessor must control, have to be defined during this phase. This work is usually only necessary when the control is installed on the machine, and therefore carried out at the factory during final testing. It may, however, be necessary to intervene if subsequent modifications have been made to the machine. The masks regarding configuration are in English and reserved for assistance technicians, who can modify the data memorised in the microprocessor from the mask below.

Page 45: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

45

Program Set-up This operation is carried out automatically should the programme be replaced. It may be useful if data (set-points, configurations, etc.) become ―dirty‖ as it permits the user to clear the memory (including those data relating to the unit HARDWARE configuration). All set-points are automatically reset to the factory set values (refer to “DEFAULT VALUES"). The control must be reconfigured after this operation, and any set-points which are different to the default values readjusted. N.B. Even when only one configuration parameter is modified (therefore also when the programme has to be replaced), the RAM memory must also be zeroed. This is done by cutting off the power supply to the control for a few seconds.

Al.Page Clear-up The Historical alarm clear up enables the user to delete all of the alarm events stored in the memory.

Hardware Set-up Enables the user to recognise the devices connected to the control automatically. This operation is useful if the user wishes to add an option to the card, replace a sensor or when the display shows "NC" instead of reading a temperature sensor.

Page 46: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

46

DELAY SETTINGS This mask concerns the behaviour in the initial transients and makes it possible to set:

- the machine switch on delay after a power cut (‗POWER ON DELAY‘). It is used to prevent contemporary start up in multiple installations. In LAN units there is automatically a progressive start up sequence (unit 1, unit 2, …) with 5 second intervals between one unit and the next. - the initial period – from compressor start up – during which the low pressure switch reading is ignored (‗LPSTAT DELAY‘). This permits compressor start up even in extremely cold weather. -the time which elapses between the start-up of the unit and the adjustment start (‗START TRANS.‘) is the period considered necessary to obtain control system stability. During this period, the reading of the FS air flow switch is also ignored. - The delay in the water temperature alarm signal from unit start up (‗Temp Al. Delay‘). -The anti-hunting time constant (‗ANTI HUNTING CONSTANT OF ROOM TEMP. CONTROL‘) which prevents excessive heat ranges. This value must be higher than the heat inertia in the air-conditioned environment. - the delay of the water flow alarm during start up and operation. - the compressor operating time during start up, re-start up and the minimum switch on time.

Page 47: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

47

MANUAL CONTROL During normal operation, all of the components which the unit is equipped with are managed automatically. Nevertheless, in order to facilitate maintenance and adjustment work and during emergencies, it is possible to override manually the following (independently from the switch on adjustment process of the single components):

the unit circulation pump (Unit start-Up); compressor 1/2 (Compressor 1/2); the condenser fan speed in % 000 Y1 and Y3 output activation in % 000

The safety devices are active even during manual operation.

EXV The operating parameters of the electronic thermostatic valve are found in this mask:

type of valve operating temperatures and pressures LOP and MOP timings for any alarm activations.

Page 48: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

48

Historical Alarms: this mask displays the alarm sequence stored. The microprocessor stores the last 100 events in its memory. All memorised alarms can be read in series by pressing the UP or DOWN keys. The counter threshold overrun is not memorised and therefore not read. The first event shown in the sequence corresponds to the last alarm which has triggered. In controls equipped with clock cards (optional) the date and hour is associated with every alarm which triggers.

Set-point: this mask displays the set-points and other factory pre-set adjustment parameters, to enable the control to operate correctly, maintaining the water temperature at standard conditions.

o Cooling set-point

o Heating set-point

o Temperature alarm set-point

Page 49: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

49

Counter: this mask displays and enables the user to establish the intervals of maintenance for the unit components. When the device involved exceeds the operating hours threshold indicated, the microprocessor signals the request for maintenance by triggering the alarm. The number of hours accumulated, the trigger threshold and number of compressor start ups are shown on the masks. The user can access the mask to modify the limits and/or reset the counter by keying in the password in settings mode.

I/O state: this and the successive masks enable the user to check the state of the card inputs and outputs. The abbreviations displayed on the display are identical to those used to identify the components both inside the unit and on the relative documents (wiring diagrams).

o IDx = digital inputs

o Bx = analogical inputs

o Cx = digital outputs

o Yx = analogical outputs

Page 50: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

50

Mask no. 3

Programme version: this mask displays the version of the programme, the bios and the boot which are contained in the control and the LAN address of the board.

Mask no. 4

Mode: this mask displays the possibility of choosing between the summer and winter work season by using the keypad and typing in the settings password. The keypad command will be ignored if a remote contact is inserted (refer to Mask 1: unit interconn.).

Page 51: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

51

Mask no. 5

Pressure sensor reading: this mask displays the reading of the pressure and temperature sensors of the machine in operation.

Masks no. 6 and 7

Temperature sensor reading: these masks display the reading of the external sensor, water input sensor, water output sensor and condenser fan speed percentage.

Page 52: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

52

If an alarm triggers, the alarm description will be displayed. If the reason for the alarm has been removed, the last alarm message can be reset by pressing and holding down the ALARM key for a few seconds. If the reason for the alarm has not been removed, the signal will be displayed again. All of the possible alarm messages which may be shown on the display of the user terminal are listed below. Indications for resolving the problem are only supplied for the alarms which are still active (and therefore for those memorized in the history sequence) in the last two lines of the display.

Water temperature limit over the maximum: these alarms are activated when the thermohygrometric limits which are set on the set point mask are exceeded.

High and low temperature inlet water alarm. May be delayed during the start up of the unit. The delay is 15 minutes by default.

Page 53: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

53

Unit functional alarms: these alarms concern the unit components and are caused by the intervention of a protection device.

Loss of water flow alarm from the flow switch.

Loss of water flow alarm from the pump flow switch.

Water flow switch failure alarm. Every time the unit is switched on the unit checks the operation of the control contact.

Low circuit pressure pre-alarm. It resets automatically after 60 seconds. If it is triggered four times in a row within an hour the alarm is activated. (with reserve: it is necessary to reset using the keyboard)

Page 54: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

54

Low pressure alarm

High circuit pressure alarm from the high pressure switch with manual reset.

Compressor 1 thermal pre-alarm. It automatically resets when the contact is closed. If it is triggered three times in a row within a period of three hours, the alarm is activated (with reserve: it is necessary to reset using the keyboard). This is the same for compressor 2.

Compressor 1 thermal alarm. This is the same for compressor 2.

Evaporator antifreeze alarm. When there is ice present, in the case of the 2 compressors, the call is partialised. If the situation is repeated 4 times in a row in the space of one hour, the antifreeze alarm is activated and both compressors are blocked (with reserve: it is necessary to reset using the keyboard).

Evaporator antifreeze alarm. The alarm is activated also when the delta between the evaporation temperature and the saturation temperature is 12°C or more.

Page 55: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

55

EVX400 Driver alarms: these alarms concern the electronic expansion valve which is connected to the Pcoxs control by means of the tLAN.

tLAN communication alarm between the EXV driver and the Pcoxs control. Check the connection.

tLAN communication alarm between the EXV driver and the Pcoxs control. Check the connection.

This alarm is activated by a signal from the NTC low pressure temperature sensor for the superheating reading.

This alarm is activated if there is an excess in evaporation pressure, or when the MOP is higher than the threshold which has been set, for a period of time longer than the MOP Alarms Delay.

Page 56: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

56

This alarm is activated if there is a lack of evaporation pressure, or when the LOP is lower than the threshold which has been set, for a period of time longer than the LOP Alarms Delay.

This alarm is activated following an error in the memory of the EEPROM del Driver.

The alarm is activated if there is low superheating, for a period longer than the Low SH Alarms Delay.

The alarm is activated if the suction temperature taken by the EVD400 sensor, is higher than the threshold set for the High SH.

This is shown only in the alarm history, when the compressors are operating and when the driver remains without power for more than 5 seconds

Page 57: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

57

Sensor alarms: these alarms refer to a malfunction or an error regarding the sensors on the Pcoxs control board. If one of these alarms is activated, check the exact configuration which has been set, the presence of the sensor and its connection and operation.

Inlet water temperature sensor failure alarm

Outlet water temperature sensor failure alarm

External air temperature sensor failure alarm

Condensing pressure sensor failure alarm of the condensing fan speed control

Page 58: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

58

Note: these alarm are activated when the operating hours limit for the component concerned is exceeded. The alarm remains activated until the counter is reset and will not be memorised in the alarm history sequence.

Only a signal. It can also refer to the compressors. The counter needs to be zeroed in order to reset the alarm. NOTE: The mask used to set the alarm threshold and zero the counter can be found on the second counter mask. If the threshold is set at 0 hours, the alarm will not be activated.

Interrupted “LAN” alarm: these alarm are activated when the operating hours limit for the component concerned is exceeded. The alarm remains activated until the counter is reset and will not be memorised in the alarm history sequence.

This alarm indicates a communication problem between the units in the LAN and specifies which units are not connected. This can be due to a lack of power supply, a malfunction in the serial cards or an interruption in the electrical connections between the units. The alarm appears in the units with the lowest address in the network, both up and downstream from the interruption.

Page 59: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

59

This alarm indicates an error in the EEPROM memory, probably due to the cancellation/writing cycle being exceeded. It is necessary to replace the Pcoxs control board.

This refers to an attempt at accessing the setting masks or configurations by inserting the wrong password 3 consecutive times. NOTE: To reset the alarm, carry out the following procedure:

7. Press UP on the main mask until the first mask is shown. 8. Press ENTER and using UP or DOWN select the desired item. 9. Confirm by pressing ENTER. 10. Press Prg for 3 seconds and then enter the configuration menu password (see envelope) and confirm using ENTER. 11. Exit the menu using the ESC button until the main screen is reached 12. Press the ALARM button again to reset the cycle and then keep it pressed for another three seconds to reset the whole alarm.

When the power supply returns following a break in the power supply in the system, the control memorizes the mask which is shown here in the alarm history sequence.

Page 60: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

60

HEAT PUMPCHILLER

Page 61: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

61

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

The purpose of LRA TOP is to perfectly match the cooling power requirements, also in case of partial loads.

In order to do that, it is possible to adjust the cooling capacity of the compressor by using an inverter.

On these units, in place of the inverter, other strategies are used:

1.Increasing of the condensing temperature;2.Flooding of the evaporator;3.Opening of the hot gas by-pass (option).

Page 62: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

62

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

Page 63: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

63

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

Increasing of the condensing temperature

The condensing temperature is brought to a value as

higher as possible

The cooling capacity lowers

The power consumption

increases

Page 64: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

64

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

Flooding of the evaporator

The expansion valve opens till to complete fill the evaporator with liquid phase

The liquid separator safely protects the compressor from the liquid phase

Page 65: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

65

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

Flooding of the evaporator

The condensing temperature is kept

as higher as possible

The expansion valve opens till to

complete fill the evaporator with

liquid phase

The liquid separator safely protects the

compressor from the liquid phase

Page 66: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

66

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

Opening of the hot gas by-pass

The hot gas by-pass provides a sudden expansion and equilibration of pressures between

the high and the low sides.

The compressed gas enters the liquid separator and hence the compressor’s suction, providing a

cooling capacity closed to zero.

Page 67: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

67

LRA TOP - Refrigerant DrawingLRA TOP - Refrigerant Drawing

Opening of the hot gas by-pass

Page 68: 1 LRAC – LRAH Air-cooled water chillers Air / water heat pumps 6 – 40kW

68