1 Introduction to Introduction to PREMISES CABLING SYSTEM PREMISES CABLING SYSTEM

Upload: mrirfan

Post on 30-Oct-2014

20 views

Category:

Education


1 download

DESCRIPTION

Introduction to Premises Cabling System

TRANSCRIPT

Page 1: 1 Introduction To Premises Cabling System

1

Introduction toIntroduction toPREMISES CABLING SYSTEMPREMISES CABLING SYSTEM

Page 2: 1 Introduction To Premises Cabling System

2

Standards

TIA/EIATIA/EIA--569569AS 3084AS 3084 CSA T 530CSA T 530

EN50173EN50173 ISO/IEC 11801ISO/IEC 11801 CSA T 529CSA T 529TIA/EIATIA/EIA--568A568AAS/NZS 3080AS/NZS 3080

EIAEIATIATIA

CENELECCENELEC IECIEC CSACSAANSIANSIAS/NZSAS/NZS

ISOISO

TIA/EIATIA/EIA--606606AS/NZS 3085AS/NZS 3085 CSA T 529CSA T 529

TIA/EIATIA/EIA--607607 CSA T 528CSA T 528

Page 3: 1 Introduction To Premises Cabling System

3

Benefits of Standards Compliance

• Assurance that cabling system will support standards-based applications

− Future network applications will most likely be developed based on infrastructure standards

• Simplify administration

− Reduce Total Cost of Ownership (TCO)

• Accommodate future growth

Page 4: 1 Introduction To Premises Cabling System

4

ISO/IEC-11801• Generic cabling for customer premises Standard

− Approved and released in 1995− The de-facto standard that all other organizations model their

standards after

• Purpose− To provide a world standard for the design, installation, and

administration of commercial building telecommunications systems.

Page 5: 1 Introduction To Premises Cabling System

5

TIA/EIA-568A• Commercial Building Telecommunications Cabling

Standard− EIA/TIA-568 - July 1991− TIA/EIA-568A - October 1995− EIA/TIA-568B - 2000

• Purpose− To enable the planning and installation of a structured cabling

system for commercial buildings...− ...specifying a generic telecommunications cabling system that

will support a multi-product, multi-vendor environment

Page 6: 1 Introduction To Premises Cabling System

6

ISO/IEC-11801 and TIA/EIA-568A Overview

Major sections include:• Definitions, Acronyms, Abbreviations• Horizontal and Backbone Cabling• Telecommunications Closets, Equipment Rooms,

Building Entrance Facilities• Unshielded Twisted Pair, Shielded Twisted Pair and

Optical Fiber Cabling and Connecting Hardware• Shielding Practices• Link Specifications and Testing

Page 7: 1 Introduction To Premises Cabling System

7

ISO/IEC-11801 and TIA/EIA-568A Differences

Cable Type:• ISO allows 120Ω cable and 50/125µm optical fiber

Terminology:TIA/EIA-568AMain Cross Connect

Intermediate Cross Connect

Horizontal Cross Connect/Telecommunications Closet

Entrance Facility

Interbuilding Backbone

Intrabuilding Backbone

ISO/IEC 11801Campus Distributor

Building Distributor

Floor Distributor

Building Entrance Facility

Campus Backbone

Building Backbone

Page 8: 1 Introduction To Premises Cabling System

8

TIA/EIA-569A• Commercial Building Standard for Telecommunications

Pathways and Spaces• Purpose

− Standardize specific design and construction practices within and between buildings which are in support of telecommunications media and equipment

• Sections− Horizontal Pathways− Backbone Pathways− Work Area− Telecommunications Closet, Equipment Room, Entrance

Facilities

Page 9: 1 Introduction To Premises Cabling System

9

TIA/EIA-606• Administration Standard for the Telecommunications

Infrastructure of Commercial Buildings• Purpose

− To provide a uniform administration scheme that is independent of applications and establishes guidelines for owners, end users, manufacturers, consultants, contractors, designers, installers, and facilities administrators involved inthe administration of telecommunications infrastructure

• Sections− Administration Concepts− Pathway and Space, and Grounding & Bonding Administration− Labeling and Color Coding

Page 10: 1 Introduction To Premises Cabling System

10

TIA/EIA-607• Commercial Building Grounding and Bonding

Requirements for the Telecommunications Industry• Purpose

− To enable the planning, design, and installation of a telecommunications grounding system that supports a multi-vendor, multi-product environment as well as the grounding practices for various systems

• Sections− Grounding and Bonding Overview− Components of the Grounding and Bonding Infrastructure− Telecommunications Closet, Equipment Room, and Entrance

Facilities

Page 11: 1 Introduction To Premises Cabling System

11

Elements/Sub-Systems

• Work Area• Horizontal Cabling• Telecommunications Closet• Backbone Cabling• Equipment Room• Entrance Facility• Administration

Page 12: 1 Introduction To Premises Cabling System

12

Campus Cabling Diagram

Page 13: 1 Introduction To Premises Cabling System

13

Campus Cabling Diagram

Page 14: 1 Introduction To Premises Cabling System

14

Hierarchical Star Topology

MDF/CD

IDF/BD

HorizontalCabling

BackboneCabling

TC

H………H

WA

TC

WAH………H

TC

WAH………H

TC

WAH………H

TC

WAH………H

TC

WAH………H

FD

Page 15: 1 Introduction To Premises Cabling System

15

Work Area, Horizontal Cabling, Telecommunications Closet

Page 16: 1 Introduction To Premises Cabling System

16

Backbone Cabling, Equipment Room,Entrance Facilities

Page 17: 1 Introduction To Premises Cabling System

17

Elements/Sub-Systems - Administration

• Work Area• Horizontal Cabling• Telecommunications Closet• Backbone Cabling• Equipment Room• Entrance Facility

• Administration

Page 18: 1 Introduction To Premises Cabling System

18

Twisted Pair Cabling

Page 19: 1 Introduction To Premises Cabling System

19

Cable Classification

Category 3/Class C - 16 MHz

Category 5/Class D - 100 MHz

Category 5e/Class D - 100 MHz

Category 6/Class E - 250 MHz

Category 7/Class F - 600 MHz

Page 20: 1 Introduction To Premises Cabling System

20

Twisted Pair Types

UTP

FTP, SFTP

STP, PiMF

Page 21: 1 Introduction To Premises Cabling System

21

Crosstalk

Page 22: 1 Introduction To Premises Cabling System

22

Near End Crosstalk (NEXT)

Transmit

Receive

• Crosstalk measures the amount of signal interference from one pair to another pair

• NEXT measures crosstalk at the signal source (Near End)

Page 23: 1 Introduction To Premises Cabling System

23

Twisted Pair Construction

22/24 AWG

PVC, LSZH, FEP

22/26 AWG(PiMF = 23 AWG, 4-pair)

Page 24: 1 Introduction To Premises Cabling System

24

Optical Fiber Overview

• Reflection• Refraction• Refractive Index• Core/Cladding • Numerical Aperture• Modes• Wavelength

Page 25: 1 Introduction To Premises Cabling System

25

Advantages of Fiber Optics

• Large Bandwidth

• Low Attenuation

• No Crosstalk

• No Radio Freq. or Electromagnetic Emissions

• No RFI or EMI susceptibility

• No Ground Loops

• Safety, no Shock or Spark Hazards

• High Future Upgrade Capability

• No EMP susceptibility

Page 26: 1 Introduction To Premises Cabling System

26

Reflection vs. Refraction

Source

Refraction

Reflection

Page 27: 1 Introduction To Premises Cabling System

27

Refractive Index

Speed of Light (Vacuum)Speed of Light (Medium)

N =

N2

N1

Page 28: 1 Introduction To Premises Cabling System

28

Internal Reflection in a Fiber

b = sinC

1.461.48

-1 = 80.6°

80.680.6n = 1.461

n = 1.482

n = 1.461

Cladding = n1

Core = n 2

Page 29: 1 Introduction To Premises Cabling System

29

Core/Cladding

CladdingGlass Tube

CoreGlassRod

Hea

t

Hea

tFiber

Cladding

Core

Page 30: 1 Introduction To Premises Cabling System

30

CROSS SECTION OF A TYPICAL FIBER

Core

Cladding125 um

Coating250 um, 400 um or 900 um

Page 31: 1 Introduction To Premises Cabling System

31

Numerical Aperture and Modes

Low Order Modes Axial Mode

Acceptance Cone High Order Modes

Page 32: 1 Introduction To Premises Cabling System

32

Wavelength

ATTENUATION

850 1300/1310 1550

WAVELENGTH

Page 33: 1 Introduction To Premises Cabling System

33

Optical Fiber Review

• Reflection• Refraction• Refractive Index• Core/Cladding • Numerical Aperture• Modes• Wavelength

Page 34: 1 Introduction To Premises Cabling System

34

Optical Fiber Types

• Multi-mode− accepts many modes of light− supports 850 and 1300 nanometer wavelengths

• Singlemode− accepts only one mode of light - the axial mode− supports 1310 and 1550 nanometer wavelengths

Page 35: 1 Introduction To Premises Cabling System

35

Optical Fiber Types

SinglemodeMultimode

Graded Index Preform

Page 36: 1 Introduction To Premises Cabling System

36

Multi-mode Step Index

Source

Dispersion

Output Pulse

Input Pulse

Page 37: 1 Introduction To Premises Cabling System

37

Multi-mode Graded Index

Dispersion

Source

Output Pulse

Input Pulse

Page 38: 1 Introduction To Premises Cabling System

38

Multi-mode Optical Fiber Sizes

50/12562.5/125

Page 39: 1 Introduction To Premises Cabling System

39

Singlemode Fiber

Source

Output PulseInput Pulse

125 m Cladding Diameter

8.3 to 10 m Core Diameter

Page 40: 1 Introduction To Premises Cabling System

40

FIBER TYPES

Multimode step index fiber

Singlemode step index fiber

Multimode graded index fiber

Low Order Mode

Input Pulse

Output Pulse

Input Pulse Output Pulse

Input Pulse

Output Pulse

Refractive Index Profile

Refractive Index Profile

Refractive Index Profile

Only one mode, No mode dispersion

High Order Mode

Page 41: 1 Introduction To Premises Cabling System

41

Optical Fiber from a preform

Preform

Muffle furnace

Fiber

Page 42: 1 Introduction To Premises Cabling System

42

Optical Fiber Components

Fiber Coating ProtectiveBuffer

StrengthMembers

OuterJacket

Page 43: 1 Introduction To Premises Cabling System

43

CABLE CONSTRUCTIONCABLE CONSTRUCTION

PVC Outer Jacket

Kevlar Strength MembersHytrel Buffer

Optical Fiber

Simplex, Tight Buffer Cable

Page 44: 1 Introduction To Premises Cabling System

44

Coatings and Buffers

Loose Tube

Tight Tube

Page 45: 1 Introduction To Premises Cabling System

45

Strength Members and Outer Jackets

KevlarPVC, LSZH, FEP (Plenum)

Steel/Fiberglass

PE

Page 46: 1 Introduction To Premises Cabling System

46

Optical Fiber Cable

Page 47: 1 Introduction To Premises Cabling System

47

Cable ConstructionInterconnect Cables

Pigtail, Patchcords, IntrabuildingInternal equipment connectionsPatch panels - Wall outlet to desktopUser friendly

Distribution CablesBackbones CablingVertical/Horizontal CablingFor cabling behind the wall and patch panels.Less fiber protection at connectorized level.

Page 48: 1 Introduction To Premises Cabling System

48

Cable Construction

Breakout Cables Backbones - Campus - Zone cablingVertical Cabling - Horizontal CablingFiber very well protected at connectorized levelEssentially simplex cables in common jacket

Long distanceBuried - Aerial - Building EntranceGenerally no flame rating - limited distance

in buildingGel filled to eliminate moistureLoose tube for expansion/contraction/movementNo fiber protection at connector level

Outdoor Cables

Page 49: 1 Introduction To Premises Cabling System

49

Cable Ratings

Defined by National Electrical Code. Tested by UL, etc. Cables must meetspecific requirements for flammability and smoke generation.

OFN : General use, less than 50´

OFNR : Riser rated, Can be used in vertical passages.

OFNP : Plenum rated, Can be installed in air plenums without conduit.

LSZH : Low Smoke, Zero halogen, No specific flame requirements

Page 50: 1 Introduction To Premises Cabling System

50

CABLE APPLICATIONSCABLE APPLICATIONS

• Outside Plant (OSP), Loose Tube

− Use: All Outside Applications

− Aerial

− Gel-filled

− Ultra-violet Resistant

− Self-supporting or Lashed

− Direct Burial (Trenched)

− Rodent Protected

− Gel-filled

− Strong Central Strength Member

− Burial (Conduit)

− Gel-filled, Not as Rugged

Page 51: 1 Introduction To Premises Cabling System

51

Cabling Media Types

MediaType Bandwidth Connector

Type

up to300 MHz

4-PositionData

up to600 MHz

up to16/100/200 MHz

8-PositionIDC

up to500 MHz-km

up to500 MHz-km +

SinglemodeFiber

62.5/125µmMulti-mode

Duplex568SC

100ΩCAT 7 STP

150Ω STP-A

8-PositionIDC

Duplex568SC

50/125µmMulti-mode

100Ω/120ΩCAT 3/5/5e/6 UTP

SC-Dup to

500 MHz-km

Page 52: 1 Introduction To Premises Cabling System

52

CONNECTING IT ALL TOGETHERCONNECTING IT ALL TOGETHER

Page 53: 1 Introduction To Premises Cabling System

53

Horizontal Cabling Distance

90 m 3 m6 m

Page 54: 1 Introduction To Premises Cabling System

54

Backbone Cabling Distances

HC/FD

HC/FD IC/BD

MC/CD EP

B

C

A

MEDIA A B C

UTP voice

UTP data

STP-A

Multimode Fiber

Singlemode Fiber

90 m/295ft

800 m/2624ft

90 m/295ft

500 m/1640ft 300 m/984ft

500 m/1640ft

500 m/1640ft3000 m/9840ft

2000 m/6560ft 1500 m/4920ft

2500 m/8200ft

Page 55: 1 Introduction To Premises Cabling System

55

Summary

• Premises Cabling System• ISO and TIA/EIA Standards• Elements of Telecommunications

Infrastructure• Cable/Fiber Types, Categories, Classes and

Performance • Cable Construction• Cable, Connectors and Cabling Distances