August 14, 2003 Blackout
MAC Meeting
October 8, 2003
Paul Murphy
IMO
2
Thursday, August 14, 2003 at approximately 04:11 PM EDTNortheastern United States and portions of Canada
lost major portions of load, generation and transmission
Effects felt throughout the Eastern Interconnection centered around the Great Lakes
Approximately 61, 800 MW of customer load was lost affecting 50 million people.
The Event
3
The Interconnections
4
4:10:00 – 4:10:38 PM Transmission Lines Disconnect across Michigan and Northern Ohio, Generation
Trips Off Line in Northern Michigan and Northern Ohio, and Northern Ohio Separates from Pennsylvania
1413
15
16
18
Remaining paths into eastern
Michigan
ONTARIO
17
5
Summary of the Situation at 4:10:38
R e m a i n i n g p a t h s i n t o e a s t e r n
M i c h i g a n
O N T A R I O
6
Interface flows 3:10:38 PM EST
7
4:10:42 – 4:10:45 PM Transmission Paths Disconnect in Northern Ontario and New Jersey, Isolating the
Northeast Portion of the Eastern Interconnection
28
27
29(North of Lake
Superior)
30
ONTARIO
8
4:10:50 – 4:11:57 PM Ontario Separates from New York West of Niagara Falls and West of St.
Lawrence. Southwestern Connecticut Separates from New York and Blacks Out.
34
33ONTARIO
35
9
FREQUENCY - Resources
57
57.5
58
58.5
59
59.5
60
60.5
61
61.5
62
62.5
63
15:10:00 15:10:43 15:11:26 15:12:10 15:12:53
August 14, 2003 EST
Freq
uenc
y (H
z)
13000
14000
15000
16000
17000
18000
19000
20000
21000
22000
23000
24000
25000
Gen
erat
ion
+ In
terc
hang
e (M
W)
Beck2 freq Cherrywood freq Generation + interchange
Unstable Island remainsBeginning of collapse
Quickly reduces to ~ 1200 MW
10
S m o k y3 0 M W
4 0 M W L o a d7 2 0 G e n e r a t i o n
D e s J o a c h i m s2 0 M W
8 0 0 M W L o a d4 8 0 M W G e n e r a t i o n
T o N e w Y o r k
11
Restoration Plan Priorities
Restore Class IV AC power to all nuclear sitesRestore power to critical transmission and
generating station, station service loadsRestore critical utility owned telecom facilitiesRestore customer loads only to the extent
necessary to control voltages and secure generating units
Synchronize islands together and/or to adjacent power systems
12
Restoration Paths
13
Complexities of the Restoration Process
Equipment Problems
Communications
Balancing generation/load and maintaining frequency and voltage
Using load to control high voltage during the line restoration process
Assessing available generation to support restoration
Post Contingency conditions
14
15
Nine Days of Emergency Operations
Over the week, assessment of insufficient internal and external generation to meet the normal Ontario demand
August 14
Provincial Government declares a Provincial Emergency August 17
Government requests industrial, commercial and residential customers to reduce load by 50% over peak hours.
Reliable supply maintained at reduced demand level due to: Customer response to requests for curtailment and conservation dispatch of emergency generators emergency purchases from Ontario’s neighbours
16
Nine Days of Emergency Operations
0
5000
10000
15000
20000
25000
14-A
ug-0
3 1:
00
14-A
ug-0
3 13
:00
15-A
ug-0
3 1:
00
15-A
ug-0
3 13
:00
16-A
ug-0
3 1:
00
16-A
ug-0
3 13
:00
17-A
ug-0
3 1:
00
17-A
ug-0
3 13
:00
18-A
ug-0
3 1:
00
18-A
ug-0
3 13
:00
19-A
ug-0
3 1:
00
19-A
ug-0
3 13
:00
20-A
ug-0
3 1:
00
20-A
ug-0
3 13
:00
21-A
ug-0
3 1:
00
21-A
ug-0
3 13
:00
22-A
ug-0
3 1:
00
22-A
ug-0
3 13
:00
Dem
and
(M
W)
NormalForecast
Actual Estimated Demand Response
The IMO remained in an EEA 2 state until August 22, 2003. The emergency lasted for 9Days and was declared over at 1900 EST. The IMO Administered Market resumedoperation at 0:00 EST on August 23, 2003.
17
ObservationsSystem Restoration and Crisis Management Processes
> Equipment protections operated as designed
> Public telephone system was generally availableEfficient and effective assignment of accountabilities within
the control roomGood cooperation from field staff of generators and
transmitters, distributors and customersGood cooperation with neighbouring area operatorsSuccessful restoration plan
Large-scale restoration is inherently complex, and our control room staff adapted to changing circumstances as the restoration proceeded, modifying approaches as necessary to achieve objectives.
The overall restoration and crisis management processes proceeded in an orderly fashion and met their objectives.
18
A Communications Centre was set up to brief media on status of system restoration in Ontario and to provide information as to how customers could assist in the restoration effort. Press conferences, scheduled twice daily, were coordinated with Provincial officials.
Provincial government officials were continuously briefed on power restoration to ensure coordination with other government agencies.
Communication Centre / Provincial Decision Support
19
1. We confirmed that the devices that are in place to protect equipment operated as planned
2. We confirmed that maintaining a well-documented restoration plan, supported by training and rehearsals involving the IMO, market participants and government, was and will continue to be a key investment
3. We confirmed that close cooperation amongst the IMO, the interconnections, and Ontario Transmitters, Generators, market participants and government is essential to achieving an orderly restoration.
Early Lessons Learned
20
4. Effective communications is essential to reliable operation.
5. The extreme speed at which events can cascade across the system increases the significance of timely information.
6. Frequent communication with customers is critical to support their decision making
7. Administered pricing rules need review
Early Lessons Learned
21
1. Maintain and enhance the integration of systems and markets through robust interconnections with our neighbours
Prevention of Future Incidents
2. Reliability standards for the interconnected North American grid should be mandatory.
3. The industry should build on the strong institutional and regulatory foundations already in place
4. The industry should continue to pursue the three part strategy of Prevention, Containment and Minimization of Impact:
22
Ongoing Review
• Internationally:– Canada-U.S. Joint Task Force
• Within Ontario:– Emergency Preparedness Task Force’s (EPTF)
Restoration Working Group– Compliance Assessment
23
Canada-U.S. Joint Task Force• 3 Working Groups to develop recommendations
– Electricity – Nuclear– Security
• IMO is supporting Electricity and Security WGs, through NERC and directly with Joint Task Force– Electricity - sequence of events, event simulation, standards,
operations, and planning– Security - physical and cyber security review
24
The Ongoing Investigation
25
Restoration Working Group• Restoration Working Group (RWG) established by the EPTF Sep 22
Goal:• To improve our level of preparedness
Objectives: • Review the facts regarding the restoration of the IMO-controlled grid• Assess the effectiveness of our restoration efforts• Identify findings and recommend improvements
26
RWG Areas of Interest• Rules and procedures
– restoration priorities– rotational load shedding– curtailment requests
• Auxiliary equipment and tools• Generator re-start• Voice communications• Class IV to nuclear
Focus on items essential to restoring the grid and the supply to consumers (by Nov 26)
27
Compliance
• Examine Compliance With Market Rules:– NPCC criteria– Ontario Power System Restoration Plan– Communication Requirements– Technical Performance Requirements
28
Thanks to all of you for aiding in a successful
restoration of the IMO Controlled Grid and restoring supply to Ontario consumers