0902 electrical design and install - norbuilt.com.au · - certification of conformance with as/nzs...

26
09 ELECTRICAL 0902 Electrical © NATSPEC (Oct 17) 1 28.04.2018 0902 ELECTRICAL 1 ELECTRICAL SYSTEMS 1.1 RESPONSIBILITIES General Requirement: Provide the electrical services, as documented. Variations to the Scope Instructions may be issued throughout the project as a result of final design and coordination. Unless the engineer’s instruction is supported with a formal instruction from the Principal, the engineer’s instruction cannot be used as grounds for a Variation. Where a claim is genuine, additional costs or credits for any such variations must be submitted with a complete breakdown of costs including quantities and rates for all labour, materials and equipment. Variation Claims submitted without breakdowns will be rejected. Substitutions to the Scope Where a substitution to the specification is proposed, the contractor shall submit each substitution, incorporating technical details and a cost breakdown, to the head contractor. The substitution shall be reviewed by the consulting engineer and the client for consideration. Unless approved by the consulting engineer and the client, the substitution will not be acceptable as an equal or approved approach to the specification. Description of the Installation The following works generally describe the Electrical Services installation and shall be carried out under this specification: - Co-ordination with Electricity Supply Authority via the electricity retailer for the provision of a new direct connected revenue meter within the site main switchboard and low voltage electrical pillar on the lot boundary. - Payment of Electricity Supply Authority standard fees and charges. - Provision of new underground consumers mains, and site main switchboard including all switchgear, controlgear and auxiliary panels. - Provision of a power monitoring system including metering, instrumentation and equipment to main switchboard, distribution boards, mains, cabling, terminations and programming. - Multiple submains and distribution boards throughout the installation, including cable trays, cable ladders, supports, conduits, switchgear and controlgear, auxiliary panels and enclosures and all ancillary equipment to complete the installation. - Earthing systems to all accessories, outlets, equipment, luminaires, other services, building structure, switchboards and communications cabling systems including provision of equipotential earthing system to slab reinforcement in all wet areas in accordance with AS3000 and in co- ordination with the Builder. - Underground and underfloor access provisions within and between all buildings on the site including draw wires, pits, sweep bends, locks, floor ducts, cable trays and access panels. - General power installation throughout including access provisions, skirting ducts, supports, cabling and outlets. - RCD protection of all socket outlet circuits, lighting circuits and other circuits and equipment as nominated. - Power supplies to Mechanical, Fire, Hydraulic and specialised services including provision of supplies, outlets or isolators as nominated. - Provision of general and specialised lighting throughout the complex including luminaires, lamps and specialist controls. - Provision and installation of a automated lighting control system where indicated on the accompanying drawings including; motion sensors, photoelectric cell and time clock devices. - Relay contactors provided to all internal lighting circuits connected to the dry contact output from the security system to disable lighting upon arming of the security system.

Upload: trantram

Post on 30-Jul-2018

242 views

Category:

Documents


1 download

TRANSCRIPT

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 1 28.04.2018

0902 ELECTRICAL

1 ELECTRICAL SYSTEMS

1.1 RESPONSIBILITIES

General

Requirement: Provide the electrical services, as documented.

Variations to the Scope

Instructions may be issued throughout the project as a result of final design and coordination. Unless the engineer’s instruction is supported with a formal instruction from the Principal, the engineer’s instruction cannot be used as grounds for a Variation.

Where a claim is genuine, additional costs or credits for any such variations must be submitted with a complete breakdown of costs including quantities and rates for all labour, materials and equipment. Variation Claims submitted without breakdowns will be rejected.

Substitutions to the Scope

Where a substitution to the specification is proposed, the contractor shall submit each substitution, incorporating technical details and a cost breakdown, to the head contractor. The substitution shall be reviewed by the consulting engineer and the client for consideration. Unless approved by the consulting engineer and the client, the substitution will not be acceptable as an equal or approved approach to the specification.

Description of the Installation

The following works generally describe the Electrical Services installation and shall be carried out under this specification:

- Co-ordination with Electricity Supply Authority via the electricity retailer for the provision of a new direct connected revenue meter within the site main switchboard and low voltage electrical pillar on the lot boundary.

- Payment of Electricity Supply Authority standard fees and charges.

- Provision of new underground consumers mains, and site main switchboard including all switchgear, controlgear and auxiliary panels.

- Provision of a power monitoring system including metering, instrumentation and equipment to main switchboard, distribution boards, mains, cabling, terminations and programming.

- Multiple submains and distribution boards throughout the installation, including cable trays, cable ladders, supports, conduits, switchgear and controlgear, auxiliary panels and enclosures and all ancillary equipment to complete the installation.

- Earthing systems to all accessories, outlets, equipment, luminaires, other services, building structure, switchboards and communications cabling systems including provision of equipotential earthing system to slab reinforcement in all wet areas in accordance with AS3000 and in co-ordination with the Builder.

- Underground and underfloor access provisions within and between all buildings on the site including draw wires, pits, sweep bends, locks, floor ducts, cable trays and access panels.

- General power installation throughout including access provisions, skirting ducts, supports, cabling and outlets.

- RCD protection of all socket outlet circuits, lighting circuits and other circuits and equipment as nominated.

- Power supplies to Mechanical, Fire, Hydraulic and specialised services including provision of supplies, outlets or isolators as nominated.

- Provision of general and specialised lighting throughout the complex including luminaires, lamps and specialist controls.

- Provision and installation of a automated lighting control system where indicated on the accompanying drawings including; motion sensors, photoelectric cell and time clock devices.

- Relay contactors provided to all internal lighting circuits connected to the dry contact output from the security system to disable lighting upon arming of the security system.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 2 28.04.2018

- Exit and emergency lighting throughout the installation complying with the requirements of AS 2293.

- Access conduits for communications systems including those for NBN Co and internal voice and data copper, and optical fibre cables, inclusive of pits and draw wires.

- Telecommunications backbone cabling including copper and optical fibre cabling, and terminations.

- Telecommunications facility cabling including support systems, accessories and terminations.

- New wiring and lighting support systems for electrical and communications services including ‘Wyr-Grid’, cable ladder, cable tray, uni-strut suspended support grid, threaded rod supports, fixings, ancillary pieces and other works nominated on the technical drawings.

- Communication cabinet/rack power supplies including outlets.

- Telecommunications racking system including furniture, cable retaining and management equipment, patch panels, outlets, and patch leads.

- Electronic security system including control panel, keypads, detection devices and audio and visual alarms.

- Seismic bracing of electrical installation.

- Provision of all hoisting and access equipment required to install all systems.

- Provision of training of management and maintenance staff for all systems.

- Provision of reticulated MATV system to administration building and transitional dwellings for digital FTA distribution including the ability for high definition digital TV distribution, including backbone cabling, outlet cabling, passive and active equipment, racking, aerial installation, head-end equipment auxiliary equipment and accessories to each apartment to complete the installation.

- Make timely applications and liaise with electrical and telecommunication authorities and utilities for all infrastructure and connections associated with the project on behalf of the Proprietor/Principal to meet the construction program milestones.

- Testing and commissioning of the above systems.

- Maintenance and servicing, defects liability and warranty for 12 months from the date of practical completion.

- Bound volumes of Installation and Operating Manuals, and work-as-executed drawings

1.2 DESIGN

Design for durability and maintainability

Design for durability: Develop the design so the systems achieve the documented performance, reliability, service life, energy efficiency and safety requirements, and are easily maintainable.

Access for maintenance: Develop the design so the systems conform to ACCESS FOR MAINTENANCE in the 0171 General requirements worksection.

Electrical system design

General: Design and provide systems, as documented.

Designer qualifications: Use only appropriately experienced and qualified persons to undertake design work. If requested, provide documents verifying the qualification and experience.

Design parameters: As documented.

Fault protection: Automatic disconnection to AS/NZS 3000 clause 2.4.

Fire-resisting protection: Provide for switchboards and associated electrical conductors to BCA C2.13.

Maximum demand: Calculation method to AS/NZS 3000 Appendix C.

Authority requirements: New PWC LV pillar at lot boundary.

1.3 CROSS REFERENCES

General

Requirement: Conform to the following:

- 0171 General requirements.

1.4 STANDARDS

Comply in all respects with the requirements of the following codes and regulations applicable to the works:

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 3 28.04.2018

- Building Code of Australia

- Local Power, Water & Gas Authority Regulations

- Occupational Health, Welfare and Safety Regulations

- Local and State Government Acts governing the works

Comply in all respects with the requirements of the following Australian Standards applicable to the works (most recent revision unless previous revision is referenced in the current BCA):

AS/NZS 1170.4 Structural design actions - Earthquake actions in Australia

AS/NZS 1345 Identification of the contents of piping, conduits and ducts

AS/NZS 1367

Coaxial cable and optical fibre systems for the RF distribution of digital television, radio and in-house analogue television signals in single and multiple dwelling installations

AS/NZS 1417 Receiving Antennas

AS/NZS 1680 Set Interior Lighting

AS 1882 Earth and bonding clamps

AS/NZS 1939 Set Degrees of protection provided by enclosure for electrical equipment (IP Code)

AS/NZS 2053 Set Conduit and fittings for electrical installations set

AS 2067 Substations and high voltage installations exceeding 1 kV a.c.

AS/NZS 2201 Set Intruder alarm systems set

AS/NZS 2293 Set Emergency escape lighting and exit signs for buildings

AS/NZS 3000 Electrical Installations (known as the Australian/New Zealand Wiring Rules)

AS/NZS 3008 Electrical Installations – Selection of Cables

AS/NZS 3010 Electrical Installations – Generating Sets

AS/NZS 3012 Electrical Installations – Construction and Demolition Sites

AS/NZS 3080 Information technology - Generic cabling for customer premises

AS/NZS 3084

Telecommunications Pathways and Spaces

AS/NZS 3111 Approval and test specification - Miniature overcurrent circuit-breakers

AS 3786 Smoke alarms using scattered light, transmitted light or ionization

AS/NZS 60947 Set Low-voltage switchgear and controlgear

AS/NZS 61000 Set Electromagnetic Compatibility (EMC) set

AS/NZS 61439 Set Low-voltage switchgear and controlgear assemblies

AS/CA S008 Requirements for customer cabling products

AS/CA S009 Installation requirements for customer cabling (Wiring rules)

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 4 28.04.2018

1.5 CONTRACT DOCUMENTS

General

Requirement: Conform to the 0171 General requirements worksection.

1.6 SUBMISSIONS

General

Requirement: Conform to the 0171 General requirements worksection.

Certification

General: Submit the following:

- Certification of conformance with AS/NZS 3000, for electrical services.

- Telecommunications cabling: Submit product and installation certification for the installation.

Samples

Lighting: Submit samples of all luminaires and accessories complete with lamp, control gear and three core flex and plug.

Emergency evacuation lighting: Submit samples of all luminaires and exit signs.

Shop drawings

Lighting: Submit shop drawings for the following:

- Lighting columns.

- Lighting column mounting bases.

- Non-proprietary luminaires.

- Non-standard fixing brackets.

Telecommunications cabling: Submit the following:

- Layouts of equipment racks.

- Cross-connect layout.

- Cabling diagram for complete system.

- Cable management system.

Power: Submit shop drawings for the following:

- Main Switchboards and all Distribution Boards including:

- General plans, elevations and sections, construction and weights.

- Circuit diagrams, busbar and cable sizes

- Current carrying capacity, current and fault ratings

- Equipment types and models, labelling and finishes

- Additionally, provide documentary evidence of fault withstand type tests relevant to the applicable enclosure(s)

Work-As-Executed Drawings

Requirement: Before the Date of Practical Completion and as a pre-condition to Practical Completion supply work-as-executed drawings based on the Contract Drawings.

Include the following minimum information:

- Actual locations of installed equipment

- Interface points with other trades

- Circuit numbers and phase for all final sub-circuits

- Actual cable tray and communication cable routes

- NBN Co cable pathways and supports.

- Location depths of all underground conduits and pits dimensioned from permanent landmarks

Include these drawings once approved in the Electrical Services Installation Manuals.

Provide a laminated copy of the main switchboard single line diagram to the approval of the Principal and Consulting Engineer; mount adjacent the Main Switchboard.

Provide a laminated copy of the voice and data cabling schematic diagram and mount within the Communications Room. Provide a bound set of communication floor plans indicating labelling and wiring routes and locate within the Communications Room.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 5 28.04.2018

Products and materials

Data: Submit technical data for all items of plant and equipment, including the following:

- Assumptions.

- Calculations.

- Model name, designation and number.

- Capacity of all system elements.

- Country of origin and manufacture.

- Materials used in the construction.

- Size, including required clearances for installation.

- Certification of compliance with the applicable code or standard.

- Technical data schedules corresponding to the equipment schedules in the contract documents. If there is a discrepancy between the two, substantiate the change.

- Manufacturers’ technical literature.

- Type-test reports.

- Single line diagram(s), including fault levels at switchboards, cable size and type.

- Switchboard layouts.

Lighting: Submit technical data on the following:

- Luminaires.

- Lamps.

- Ballasts.

- Power factor correction equipment.

- Lighting control systems.

- All accessories.

Telecommunications cabling: Submit technical data including the following:

- System design parameters: Performance.

- Voice and/or data transfer rate.

- Cable type and characteristics.

- Segregation requirements for EMI/EMR.

- Maximum length of cables.

- Cross-connect type and characteristics.

- Cross-connect block.

- Patch cords.

- Fibre optic terminations.

- Patch panel module.

- Cable management for racks.

- Rack.

- Fly leads.

Emergency evacuation lighting: Submit technical data for each type of luminaire and exit sign including the following:

- Maximum luminaire spacing for a given mounting height.

- Luminaire classification to AS 2293.3.

1.7 INSPECTION

Notice

Inspection: Give notice so inspection may be made of the following:

- First Fix Installation

- Second Fix Installation

- Completed Installation, including witnessing commissioned systems compliant with this documentation.

General

Requirement: Conform to the 0171 General requirements worksection.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 6 28.04.2018

2 ASSOCIATED WORKS

The following works related to the Electrical Services installation shall be carried out under other trade packages at the direction of the head contractor unless otherwise indicated.

Coordinate all reticulation, termination locations and connection details. Ensure that information is provided to other trades to facilitate these works.

Mechanical Services Sub-Contractor:

- Wiring and final connection from isolators for air conditioning units and cassette units shall be provided by the Mechanical Services Contractor.

- Flex and plug and final connection from controlled SSOs for toilet exhaust equipment shall be provided by the Mechanical Services Contractor.

- When exhaust fans are being supplied via lighting movement sensors, the Electrical Contractor shall provide power to the fans via the 2nd pole, which will be programmed to run for an additional 10 minutes once the lighting has switched off.

- Electrical contractor to provide 0-30minute adjustable run-on timer for each fan including all cabling and other equipment as required. Run-on timers to be set to 10 minutes initially. Interlock fans to operate with the lighting circuits for each room serviced by the fan such that the operation of any light switch will operate the fan. Provide double pole light switches as required. Co-ordinate exact requirements with mechanical trade prior to first fix.

- Circuit breakers for all air conditioning units (commercial tenancies, apartments and townhouses) shall be provided within local distribution boards by the electrical contractor under this contract. Sub-circuit cabling, weatherproof isolators and final connections to units shall be provided by the Mechanical Contractor.

- For all roof mounted and indoor plant the Electrical Contractor shall provide isolators installed to pedestals located adjacent plant equipment, and labelled to reference plant equipment. No isolators shall be installed directly on plant equipment.

- For all plant located within the ceiling space the Electrical Contractor shall provide isolators/socket outlets securely installed adjacent plant equipment, and labelled to reference plant equipment. No isolators/socket outlets shall be installed directly on plant equipment.

Hydraulics Sub-contractor:

- Wiring and final connections from socket outlets and isolators to all Hydraulic Services Equipment to be provided by the Electrical Contractor under this contact.

- For all roof mounted and indoor plant the Electrical Contractor shall provide isolators installed to pedestals located adjacent plant equipment, and labelled to reference plant equipment. No isolators shall be installed directly on plant equipment.

- For all plant located within the ceiling space the Electrical Contractor shall provide isolators/socket outlets securely installed adjacent plant equipment, and labelled to reference plant equipment. No isolators/socket outlets shall be installed directly on plant equipment.

3 LOW VOLTAGE POWER SYSTEMS

3.1 RESPONSIBILITIES

General

Requirement: Provide low voltage power systems, as documented.

3.2 PERFORMANCE

Network supply

General: Liaise with the electricity distributor and provide network connection, as documented.

Program: Schedule the works and statutory inspections to suit the construction program.

Prospective fault current: Determine, from the electricity distributor, the prospective fault current and fault protection requirements.

Supply system: 400 V, 3-phase, 4-wire, 50 Hz, multiple earth neutral (MEN) system.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 7 28.04.2018

Distribution system

General: Provide power distribution system elements, as documented.

3.3 SURGE PROTECTION DEVICES (SPD)

General

Requirement: Provide all mode metal oxide varistor based series connected SPD to protect equipment in racks and cabinets, as documented.

Standard: To AS 4262.1 and AS 4262.2.

Surge rating (Imax): ≥ 200 kA (8/20 µs) phase to neutral for MSB and 50kA (8/20 µs) phase to neutral for all other distribution boards.

Voltage protection level (Up):

- < 600 V at 3 kA.

- 700 V at 500 A.

Visual indicator: Provide visual indication of SPD status.

Enclosure and installation: House SPD in an electrical switchboard or panel and protect with a suitable rated circuit breaker equal to or less than the load current rating of the SPD.

3.4 SITE ELECTRICITY SUPPLY

General

Responsibilities: Provide site electricity supplies, as documented. Connect project electrical facilities to the network distributors external site electricity supply.

Consumers mains

Requirement: Provide consumers mains, associated services and all necessary fault and overload current protection equipment to AS/NZS 3000 Section 3, the electricity distributor’s standards and the Service and Installation Rules.

Protected consumers mains: Provide short circuit and overload protection, where required by the electricity distributor.

Metering

Retail: Provide metering to the requirements of the electricity retailer, the electricity distributor and as documented.

Private: Provide private metering, as documented.

Photovoltaic metering: As documented.

3.5 WIRING SYSTEMS

General

Requirement: Provide wiring and site cable reticulation systems appropriate to the installation conditions and the function of the load. Include the following:

- Underground services.

- Above-ground services.

- In-building services.

Type: Re-wireable system.

Neutral conductors: Same size as the corresponding active conductors. Rate the neutral conductor size for the maximum harmonic currents.

3.6 POWER CABLES

Standards

Polymeric insulated cables: To AS/NZS 5000.1.

Aerial cables:

- Copper conductors: To AS 1746.

- Aluminium conductors: To AS 3607 or AS 1531.

Cable selection

Standards: Select cables in accordance with AS/NZS 3000 and AS/NZS 3008.1.

- Ratings: Use AS/NZS 3008.1 for the determination of current ratings, voltage drop and cable size.

- Voltage Drop: The maximum voltage drop to each final sub-circuit is not to exceed 2.5% unless specified otherwise.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 8 28.04.2018

- Conductors: Unless otherwise specified, use multi-stranded copper conductors. Aluminium cabling will not be accepted.

- Minimum Sub-Circuit size: 2.5mm2 for power and lighting circuits.

- Minimum Sub-Main and Consumers Mains size: As shown on the drawings accompanying this specification. In any case, they shall be sized to the maximum circuit protection device rating on the circuit, and shall not be sized any less to those shown on the drawings.

- Sub-Circuit cable types: Unless otherwise specified use cabling with V-90 (PVC) insulation and PVC sheath

Fault loop impedance: Provide final subcircuit cables to satisfy the requirements for automatic disconnection under short circuit and earth fault/touch voltage conditions.

Underground residential distribution (URD) systems: Cables to AS/NZS 4026.

Distribution cables: To AS/NZS 4961.

AS/NZS 4961 provides guidance in the specification and selection of cables used for external distribution.

Colours

Conductor colours: For fixed wiring cables, provide coloured conductor insulation or at least 150 mm of close fitting coloured sleeving at the termination points of each conductor.

Active conductors in single phase circuits: Red.

Active conductors in polyphase circuits:

- A phase: Red.

- B phase: White.

- C phase: Blue.

Sheath: White.

Cable installation

Classifications: To AS/NZS 3000 and 3013.

Handling cables: Report damage to cable insulation, serving or sheathing.

Stress: Do not use installation methods that exceed the cable’s pulling tension. Use cable rollers for cable installed on tray/ladders or in underground enclosures.

Straight-through joints: Unless unavoidable due to length or difficult installation conditions, run cables without intermediate straight-through joints.

Cable joints: Locate in accessible positions in junction boxes and/or in pits.

Individual wiring of extra-low voltage circuits: Tie together at regular intervals.

Manufacturers' recommendations: Unless otherwise specified, install, terminate and joint cables in accordance with manufacturers' recommendations.

Terminations: Terminate each circular multicore cable, and each single core TPS cable of greater cross section than 35mm2, using a nonferrous gland at each end of each cable. Provide non-ferrous gland plates for all single core cables.

Handling cables: Handle cables so as to avoid damage to insulation and serving or sheathing. Report all damage and replace or repair damaged cable as directed.

Installation: Install and adequately support fixed wiring as specified throughout the installation. For cabling routes not specified in detail, submit a proposed route layout and gain approval prior to ordering cables or support equipment. All multi-phase circuits with single conductors shall be installed in trefoil configuration, strictly in accordance with the requirements of AS 3008.

All underground cables that form part of different electrical installations (such as separately metered installations) to be installed in separate conduits.

Should cabling require to be painted for concealment, the cabling shall be installed within a suitably sized conduit, with only the conduit painted in the desired colour. Under no circumstances shall cabling be painted.

Conduits

Minimum sizes: Metallic and non-metallic conduits: 25mm.

Galvanised water pipe: Medium or heavy tube to AS 1074, 25mm nominal minimum bore.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 9 28.04.2018

Fixings: Utilise dual fixing conduit saddles. Single fixing conduit saddles are not acceptable. Maintain fire rating of all wall surfaces.

Do not use explosive-powered or similar fixing equipment unless approved.

To woodwork: Conduit matching saddles and round head plated steel wood screws.

To masonry: Galvanised saddles and round head plated steel screws screwed into approved metallic expansion devices. Wooden plugs, explosive powered fixings and adhesive fastenings are not permitted.

To steelwork: Plated steel metal-thread screws. Drill and tap the steelwork for each saddle.

Support: Unless otherwise specified, fix conduit saddles at a maximum of 1 m intervals in both horizontal and vertical runs. Ensure that installed conduits are fully supported during construction.

Lengths: Up to the commercially obtainable conduit lengths of run, install conduits without joints. Remove all rags, burrs, and sharp edges from each length before completing each conduit joint. Fit moulded plastic screwed bushes to the free ends of metallic conduit runs before installing the conductors.

Inspection fittings: Inspection fittings and the like shall be accessible.

Draw-in boxes: Provide draw-in boxes at suitable intervals not exceeding 30 m in straight runs, and at intervals not exceeding 25 m in other runs including directional changes.

Underground boxes: Fit draw-in boxes installed underground with gasketted covers and seal them against entry of moisture.

Cable trays and ladders

Support system: Bends, connectors, trays, ladders, brackets, and other supports necessary to make a complete cable or conduit support system shall be of the same manufacture, sized to adequately support the installed cabling.

General: All cables greater than 50mm2 cross sectional conductor area, shall be supported via cable tray. All cable runs that require greater than 2 catenaries in a single run shall be supported via cable tray.

Steel trays: Perforated pre-galvanised.

Minimum steel thickness:

- Trays up to 150mm wide: 1.0mm

- Trays from 150mm to 300mm wide: 1.2mm

- Trays over 300mm wide: 1.6mm

Folded edge: Minimum height 20 mm, radiused.

Slotting: Normal or reverse with no burrs or sharp edges on the side to which cables are attached.

Construction: Manufacture cable ladder trays and cable ladder from two folded steel or extruded structural grade aluminium side rails with cable support rungs between the two rails spaced at intervals of not more than 300mm (ladder) and 100mm (ladder trays).

Small cable: Do not run cables smaller than 13mm outside diameter on the cable ladder unless continuously supported.

Cable fixing: Slots or ladder rails shall be suitable for fixing cable ties, strapping or saddles. Communications cabling shall be fixed with Velcro cable ties.

Bend radius: Bends shall have a minimum inside radius of not less than twelve times the outside diameter of the largest diameter cable carried. Bends shall be manufactured by the supplier. The contractor shall not modify trays or ladders to provide bends.

Spare capacity: Provide sufficient space on the tray or ladder for not less than 20% more cables or conduits than specified, irrespective of sizes indicated on the drawings. The sizes and quantities nominated on the drawings are indicative, and are to be confirmed by the Electrical Contractor based on final cable quantities, sizes and locations.

Route: Cable tray routes shown on the drawings accompanying this specification are shown indicatively, and are to be confirmed by the Electrical with reference to conditions on site and the Structural Engineers drawings. In any case, cable trays shall be run parallel and perpendicular to the building structure.

Access: Position the support system to give adequate access for inspecting, replacing, or adding cable.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 10 28.04.2018

Support: Provide support brackets of the cantilever type (ie. one side of the bracket left open), cold galvanised after fabrication. Mount brackets to manufacturer's recommendations, with no appreciable sag between supports.

Cable strapping: Fix cable to the support system by proprietary nylon ties, straps or saddles, at 500 mm centres for vertical runs and 1000mm centres for horizontal runs. Use nylon ties for smaller cables (up to 15mm diameter single core cables, 25mm multicore cables), non-magnetic saddles or strapping for larger cables. All data cabling shall be fixed to cable trays with Velcro cable ties.

Cable protection: Provide a slightly curved support surface under cables leaving the tray or cable ladder to protect the cable sheath from impingement by the tray or ladder edge.

Mechanical Protection: Where cables are installed in such a manner that they may be vulnerable to impact provide cable tray lids.

Clearance: Maintain at least 200 mm clearance from hot water pipes 500 mm clearance from boilers or furnaces, and 100 mm clearance (minimum) from all other services.

Segregation: Segregation from electrical, communications, security etc. cabling shall be maintained in accordance with the relevant standards. Cabling can be reticulated on the same cable trays, provided a fixed partition (barrier) is installed to the cable tray.

Earthing: Earth all cable trays, ladder trays and ladders in accordance with the requirements of AS/NZS 3000 and ACMA technical standards.

Catenaries

Construction: Provide commercial manufactured catenaries as follows:

Properly rated for the weight of the cabling to be installed.

Provide uniform support throughout cable length.

Be fixed at each end.

Capable of withstanding any mechanical stresses within the environment installed.

Consist of material equally resistant to corrosion and deterioration.

2.7mm minimum diameter.

1.5kN minimum break force.

Zinc coated.

Cables themselves shall not be used as catenaries.

Installation: Install catenaries as follows:

Provide no more than 3 groups of 5 bundles cables to each catenary.

Provide hangers at 1000mm intervals.

Shall be supported off the Building structure, and not off other plant and/or equipment.

Installed so as to run parallel and/or perpendicular to building structure.

Cable fixing: Nylon cables ties shall be provided for fixing electric cabling, and Velcro cable ties shall be provided for communications cabling at 500mm intervals.

Clearance: Locate cabling 100mm from moving parts of any equipment operating at elevated temperature.

Earthing: Earth all catenaries in accordance with the requirements of AS/NZS 3000 and ACMA technical standards.

Tagging

General: Identify multicore cables and trefoil groups at each end with stamped non-ferrous tags clipped around each cable or trefoil group.

Marking

General: Identify the origin of all wiring by legible indelible marking.

Submains and final sub-circuits

Installation: Provide the following:

- Cables with diameter less than 13 mm: Run in conduit, cable ducts or support on cable trays or ladders.

- Single core cables of 3 phase circuits of diameter greater than 13 mm: Install unenclosed single core cables laid on cable tray or support systems in trefoil (RWBN) groups.

- Cables for lighting systems: Run in conduit, cable ducts, suspend on catenary systems or support on cable trays or ladders.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 11 28.04.2018

- Accessible concealed spaces: Install thermoplastic insulated and sheathed cables.

- Inaccessible concealed spaces: Install cable in PVC-U conduit.

- Roof spaces: Install cable below heat insulation and sarking. If not protected from high ambient roof space temperatures by thermal insulation, derate the cables, to AS/NZS 3008.1.1 Table 27, for an assumed ambient temperature of 55°C.

- Accessible ceiling voids: Support and enclose cables on ceiling surfaces or ceiling suspension systems.

- Plastered or rendered masonry: Install cable in PVC-U conduit.

- Double sided face brick partition: Install cable in PVC-U conduit installed within the brick wall by slotting bricks or using any pathways provided in the brick.

- Stud framed walls with bulk insulation: Install cables in PVC-U conduit.

- Stud framed walls without bulk insulation: Thermoplastic insulated and sheathed cables allowing rewirability.

- Horizontal cable trays or ladders: Fix cables using proprietary nylon cable ties or straps, cable saddles or clips at 2000 mm intervals.

- Vertical cable risers: Fix cables using proprietary nylon cable ties or straps, cable saddles or clips at 1000 mm intervals.

- Plant rooms: Install cable in heavy duty PVC-U conduit or on tray or in duct.

3.7 EARTHING SYSTEMS

Earthing system: The following earthing system is to be provided for each supply in accordance with AS 3000.

- Type: MEN system (New)

- Maximum earth resistance: In accordance with AS 3000.

- Electrodes: Copper Clad Stainless Steel - 2.4m length.

- Pits: Proprietary earthing pit (300 mm x 300 mm).

Earth all metallic structure and equipment where this relates to the Electrical Services or Telecommunications installation.

The location of the earth stake shall be identified at the Main Switchboard.

Connections: For the connection of the main earthing conductor and interconnecting bonding use clamps to AS 1882.

Additional earthing and bonding: Provide additional bonding between the earthing system and all piped services within each building, at the closest practical point to where the piped services enter the building. Include all piped services, including Hot Water, Cold Water and the like, where applicable.

Provide dedicated earthing conductors to each raised floor and bond to the structure at appropriate locations. Insulate support equipment brackets to suit.

Earth all cable supports including by not limited to cable trays, ladders and catenaries.

Telecommunications Earthing: Provide a protective earthing system for the Communications cabling systems in accordance with ACMA regulations. Provide a dedicated 16 mm2 earth cable to each Communications Rack Enclosure, MDF or TPF. The earth cable shall be an uninterrupted link from the nearest Distribution Board. For Communications Racks the earth cable shall be terminated on an earth stud located on a face plate adjacent the enclosure between 900 and 1100 AFFL.

Do not allow the earthing conductor of any rack equipment frame or any earth connection between the communications raised floor and equipment earth. Insulate support equipment brackets to suit.

Showers and Bathrooms: Provide additional bonding to conductive reinforcement within a concrete floors and/or walls forming part of a shower or bathroom construction. The equipotential bonding

conductor shall have a cross sectional area not less than 4mm and shall be bonded to the nearest adjacent earthing system of the electrical installation.

Provide additional earth stakes where required by the Supply Authority or to achieve the earth resistance stated in AS 3000.

Submains: Provide an earth wire with each group of submains sized to meet the minimum requirements outlined in AS/NZS 3000.

Final subcircuits: Provide a separate earth wire to each final subcircuit. Within each respective switchboard connect each earth wire to an earth bar. Ensure that earth bar numbers correspond with circuit breaker and neutral bar numbers.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 12 28.04.2018

3.8 ELECTRICAL ACCESSORIES

General

Style: Provide accessories of the same style and from the same manufacturer, as documented.

Socket outlets - generally

Standards:

- General: To AS/NZS 3112.

- Industrial: To AS/NZS 3123.

Socket outlet properties: Provide sockets conforming to the following or as documented:

- Type: Integral switched socket outlet.

- Material: High impact plastic.

- Size: Standard single gang.

- Current rating: 10 A.

- Pin arrangement: Mount outlets with the earth pins at the 6 o’clock position.

Plastic switched socket outlets

Colour: White electrical.

Mounting configuration: Horizontal.

Ironclad socket outlets

Type: Integral switched socket outlet.

Material: Diecast metal or cast iron.

Colour: Grey.

Weatherproof socket outlets

Colour: Grey.

Combined RCD switched socket outlets

Type: Integral RCD unit with double switched socket outlet.

Colour: White electrical.

RCD trip current: Conform to the following:

- General light and power: 30 mA Type II to AS/NZS 3190.

- Patient treatment areas: 10 mA Type I to AS/NZS 3190, as documented.

Multi-switch socket outlets on grid mounted panels

Type: Separate switch and socket outlets grid mounted on propriety or custom designed panels.

Material: As documented.

Colour: As documented.

Panel finishes: As documented.

Plugs – 230 volt

Requirement: Insulated type to AS/NZS 3112 with integral pins.

230 volt combination switch and permanently connected cord outlet

Type: Three terminal flush mounted switch and flex-lock insert assembly.

Colour: White electrical.

Neon Indicator: Provide neon indicator to match existing.

Flex-lock assembly: Match and securely grip the size and type of flexible cable used.

Mounting configuration: Horizontal.

Permanently connected equipment

General: Provide final subcircuit to permanently connected equipment, as documented.

Isolating switch: Locate adjacent to equipment.

Mounting:

- Internal installations: Flush mount.

- External installations: Weatherproof surface mounted.

Coordination: Coordinate with equipment supplier.

Wall/ceiling mounted equipment: Conceal final cable connection to equipment.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 13 28.04.2018

Isolating switches

Standard: To AS/NZS 3133.

Emergency stop switches

Standard: To AS/NZS IEC 60947.5.5.

Type: Mushroom head with latch and twist releaser.

3-phase outlets

Standard: To AS/NZS 3123.

Type: Surface mounted Integral switched socket outlet with flap lid on the outlet.

Material: High impact plastic.

IP rating: IP56.

Size: To suit current rating and pin configuration nominated in the project documents.

Colour: Grey.

Current rating: 5 pin, 20 A, 400 V a.c.

Switch mechanism: Rotating type.

Pin arrangement: Five round pins mounted with earth pins at the 6 o’clock position, neutral pins in the centre and the red, white and blue phases in a clockwise sequence when viewed from the front of the outlet.

Plug: Provide a matching plug top for each outlet.

Installation

General: Install accessories and conceal cabling in walls in conformance with the following:

- Rendered masonry partition: Flush wall box, with conduit chased into wall.

- Double sided face brick partition: Vertically mounted flush wall box, with conduit concealed in cut bricks.

- Face brick external cavity wall: Flush wall box, with thermoplastic insulated cables in conduit run in cavity and tied against inner brick surface, or thermoplastic sheathed cables run in cavity.

- Stud partition: Flush plate secured to proprietary support bracket or wall box.

- Fire walls: Flush wall box, with conduit built into wall. Provide additional fire protection around wall boxes, where necessary to maintain fire-resistance rating.

Location: Confirm final location of all outlets and equipment on site, before installation.

Spacing from adjacent horizontal surface: ≥ 75 mm to the centre of accessory socket.

Default mounting heights to centre of accessory plate:

- Outlets: 300 mm.

- Switches and controls: 1100 mm.

Accessories: Flush mounted, except in plant rooms.

Common face plates: Mount adjacent flush mounted accessories under a common faceplate.

Restricted location: Do not install wall boxes across junctions of wall finishes.

Surface mounting: Proprietary mounting blocks.

Installation of ceiling mounted accessories

Connections for appliances: Flush mounted outlets on the ceiling next to support brackets.

Mounting: Mount appliances independent of ceiling tiles and suspended ceiling suspension system. Fix directly to concrete slab or to roof structure above ceiling.

Connections for fixed equipment: Provide concealed permanent connections.

Fixing: For equipment and appliances heavier than 30 kg, provide support through the suspended ceiling to the building structure. Brace appliances that have excessive bending moments, are heavy or vibrate, to prevent horizontal movement, e.g. operating theatre shadowless lights.

4 SWITCHBOARDS – PROPRIETARY

4.1 RESPONSIBILITIES

General

Requirement: Provide proprietary switchboards for the following, as documented:

- Main switchboard.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 14 28.04.2018

- Distribution boards.

4.2 STANDARDS

General

Standards: To AS/NZS 3000, and AS/NZS 3439.3 or AS/NZS 61439.3.

4.3 PRODUCTS

Switchboard connectors

Type: Front connected.

Enclosure

Default material: Metallic-coated sheet steel.

Separation

Default: Form 1.

Metering

Retail: Provide metering to the requirements of the electricity retailer, the electricity distributor and as documented.

Private: Provide private metering, as documented.

Photovoltaic metering: As documented.

Main switchboard main switches

Spare capacity: Provide at least 25% spare capacity in the ratings main switch/isolators.

Busbars

General: Incorporate proprietary insulated busbar systems for the interconnection of isolators, circuit breakers and other circuit protective devices.

Busbar fault rating: Rated to meet the prospective fault current for 1 second or a minimum rating of ≥ 18kA/second, whichever is the greater.

Spare capacity

Default spare poles: ≥ 20%.

Main switchboard incoming busbar: ≥ 25%.

Earthing

General: Make provision for the connection of the communications earth terminal (CET) at switchboard earth bar to AS/CA S009.

Doors

General: Provide lockable doors with a circuit card holder unless enclosed in cupboards or in an area which is not readily accessible to the public.

IP rating

Default rating: IP42 minimum.

Weatherproof: IP56 minimum.

Finishes

External and interior: To the manufacturer’s standard colour.

Supporting structure

Assemblies:

- Wall mounted: ≤ 2 m2.

- Floor mounted: > 2 m2.

Ventilation

General: Required to maintain design operating temperatures at full load.

Cable entries

General: Neatly adapt one or more cable entry plates, if fitted, to accept incoming cable enclosure. Provide the minimum number of entry plates to leave spare capacity for future cable entries. Do not run cables into the top of weatherproof assemblies.

Single core cables: Pass separately through non-ferrous gland plates. Do not provide ferrous metal saddles.

Cable enclosures

Requirement: Continue cable enclosures to or into assemblies and fit cable entry plates so that the IP rating of the assembly and the fire-resistance level of the cable are maintained.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 15 28.04.2018

Cable supports

Requirement: Support or tie mains and submains cables within 200 mm of terminations. Provide cable supports suitable for stresses resulting from short circuit conditions.

5 SWITCHBOARD COMPONENTS

5.1 RESPONSIBILITIES

General

Requirement: Provide switchboard components, as documented.

5.2 DESIGN

Statutory authority’s equipment

General: Liaise with the electricity distributor about the installation and coordinate with their protective and control equipment.

5.3 REQUIREMENTS

General

Selection: To AS/NZS 3000 clause 1.7 and Section 2.

Rated duty: Uninterrupted.

Rated making capacity (peak): ≥ 2.1 x fault level (r.m.s.) at assembly incoming terminals.

Utilization category: To AS/NZS IEC 60947.1 clause 4.4 and the recommendations of Annex A.

- Circuits consisting of motors or other highly inductive loads: At least AC-23.

- Other circuits: At least AC-22.

Coordination: Select and adjust protective devices to discriminate under overload, fault current, and earth fault conditions.

Enclosure: IP4X minimum.

5.4 SWITCH-ISOLATOR AND COMBINATION FUSE-SWITCH UNITS

General

Standard: To AS/NZS IEC 60947.1 and AS/NZS IEC 60947.3.

Operation: Independent manual operation including positive ON/OFF indicator.

Shrouding: Effective over range of switch positions.

Fault make/fault break switch-isolators

Rated breaking capacity: To AS/NZS IEC 60947.3 Table 3.

Rated short-time withstand current: As defined in AS/NZS IEC 60947.1 clause 4.3.6.1 and the manufacturer's recommendation for the prospective fault current conditions.

Rated short-circuit making capacity: As defined in AS/NZS IEC 60947.1 clause 4.3.6.2, to conform to the manufacturer’s recommendation for the prospective fault current conditions.

Rated short-circuit breaking capacity: To AS/NZS IEC 60947.1 clause 4.3.6.3 and the manufacturer’s recommendation for the prospective fault current conditions.

Load make/load break switch-isolators

Rated making and breaking capacity: As defined in AS/NZS IEC 60947.1 clause 4.3.5 to conform to AS/NZS IEC 60947.3 Table 3 and the manufacturer's recommendations for the prospective fault current conditions.

Rated short-time withstand current: As defined in AS/NZS IEC 60947.1 clause 4.3.5, to conform to the manufacturer’s recommendation for the current conditions.

5.5 OVERLOAD AND FAULT PROTECTION GENERALLY

General

Requirement: Provide overload and fault protection devices, including full discrimination and cascade protection, and grade with the electricity distributor’s incoming supply protection system and the downstream site protection devices.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 16 28.04.2018

5.6 FUSE SWITCH UNITS

Fuse links

Requirement: Isolate when switch contacts are open. Provide 3 phase sets of high rupturing capacity (HRC) fuse links.

5.7 MOULDED CASE AND MINIATURE CIRCUIT BREAKERS

General

Moulded case breakers: To AS/NZS IEC 60947.1 and AS/NZS IEC 60947.2.

Miniature circuit breakers: Interrupting capacity classification to AS/NZS 60898.1 or AS/NZS 3111.

- For general building services: Type C.

- For motor protection: Type D.

Operation: Independent manual operation including positive ON/OFF indicator.

Trip type: Conform to the following:

- Moulded case breakers: Adjustable electronic.

- Miniature circuit breakers: Fixed thermal and fixed magnetic.

Mounting: Mount circuit breakers so that the ON/OFF and current rating indications are clearly visible with covers or escutcheons in position. Align operating toggles of each circuit breaker in the same plane.

Clip tray chassis: For miniature overcurrent circuit breakers, provide clip tray assemblies capable of accepting single, double or triple circuit breakers and related busbars. Provide moulded clip-on pole fillers for unused portions.

Trip settings: Set as documented, seal, and label.

Interchangeable trip units: Connect trip units so that trip units are not live when circuit breaker contacts are open.

Fault current limiting circuit breakers: Select breaker frame sizes from one manufacturer’s tested range of breakers to give cascade and discrimination protection within the switchboard and downstream switchboards as required.

5.8 ELECTRICITY DISTRIBUTOR’S SERVICE PROTECTIVE DEVICES

General

Low voltage service protective devices: To AS/NZS 3000, the electricity distributor’s requirements and the Service and Installation Rules.

Service protective devices > 100 A: Provide fault current limiting circuit breakers with adjustable overload and short circuit current facilities with full discrimination and cascade protection between the incoming supply protection systems and the downstream protection systems.

5.9 RESIDUAL CURRENT OPERATED CIRCUIT BREAKERS (RCBO)

General

Standard: To AS/NZS 3190.

Integral non-overload protection type: To AS/NZS 61008.1.

Integral overload protection type: To AS/NZS 61009.1.

Modular type: To AS/NZS IEC 60947.2.

- Type II.

. Default tripping current: 30 mA.

5.10 FUSES WITH ENCLOSED FUSE LINKS

General

Standards: To IEC 60269-1.

Fuses with fuse links for the protection of semiconductor devices: To IEC 60269-4.

Fuses with fuse links used as fault current limiters: Coordinate fuse type and rating with the protection switchgear manufacturer’s recommendation if used downstream of the fault current limiters. Provide labels adjacent to the fuse holder stating FAULT CURRENT LIMITER and fuse size.

Fuse links: Enclosed, high rupturing capacity type mounted in a fuse carrier.

Breaking range and utilisation category:

- Distribution/general purpose: gG.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 17 28.04.2018

- Motors: gM.

5.11 CONTACTORS

General

Standard: To AS/NZS IEC 60947.4.1.

Type: Enclosed, block type, air break, electromagnetic.

Poles: 3.

Rated operational current: The greater of:

- Full load current of the load controlled.

- ≥ 16 A.

Mechanical durability: 10 million cycles to AS/NZS IEC 60947.4.1.

Electric durability: ≥ 1 million operations at AC-22 to AS/NZS IEC 60947.4.1.

Mounting: Mount with sufficient clearance to allow full access for maintenance, removal and replacement of coils and contacts, without the need to disconnect wiring or remove other equipment.

Auxiliary contacts: Provide auxiliary contacts with at least one normally-open and one normally-closed separate contacts with rating of 6 A at 230 V a.c., utilization category AC-1.

6 LIGHTING

6.1 RESPONSIBILITIES

General

Requirement: Provide lighting and control systems, as documented.

6.2 STANDARDS

AS 2293: Emergency escape lighting and exit signs for buildings

AS 2293.1:- System design, installation and operation

AS/NZS 2293.2: - Inspection and maintenance

AS 2293.3: - Emergency escape luminaires and exit signs

AS/NZS 60269: Low-voltage fuses

AS/NZS 60269.1:- General requirements

AS/NZS 60269.2.0- Supplementary requirements for fuses for use by authorized persons (fuses mainly for industrial application)

AS/NZS 60269.2.1 - Supplementary requirements for fuses for use by authorized persons (fuses mainly for industrial application) – Section I to VI: Example of types of standardized fuses

AS/NZS 61048: Auxiliaries for lamps – Capacitors for use in tubular fluorescent and other discharge lamp circuits – General safety requirements

6.3 PROPRIETARY LUMINAIRES

General

Requirement: Provide proprietary luminaires complete with lamps, luminaire control equipment, lighting control equipment, and accessories as documented. Provide lamps of the same type from the same brand and country of manufacture.

Self-ballasted lamps: To AS/NZS 60968 and AS/NZS 60969.

6.4 LIGHT-EMITTING DIODES (LEDS) LUMINAIRES

The luminaire must be supported by an LM-79 photometric test from a certified test laboratory.

The operating Tc temperature of the LED board and control gear must be tested in accordance to

AS/NZS 60598.1 2003.

The lumen maintenance life projection must be provided for the luminaire, not just the LED board.

The colour rendering of the LED must be Ra80 or greater.

The LED must have an initial McAdams ellipse rating of 4 McAdams SDCM’s or lower.

The luminaire must conform to Australian Standards:

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 18 28.04.2018

- AS/NZS 60598.1 2003 Luminaires Part 1: General requirements and tests.

- AS/NZS CISPR 15:201 1 Limits and methods of measurement of radio disturbance characteristics of electrical lighting.

- IEC/PAS 62722-2-1 Luminaire performance Part 2-1: Particular requirements for LED luminaires.

The luminaire's control gear must have a Certificate of Approval for prescribed items (in the case of remote drivers) or a Certificate of Suitability

6.5 CONTROL GEAR ENCLOSURE

General

Requirement: Provide controlgear support enclosure within the body of the luminaire, except where remotely mounted controlgear is documented or required by the manufacturer.

Enclosures and controlgear mounting assemblies: Provide heat dissipation facilities to dissipate heat from the luminaire.

Controlgear enclosure: Form a barrier against direct contact with live parts of the controlgear and the area of the luminaire containing the lamp and lamp support holders.

Separate controlgear enclosures: lf separate controlgear enclosures external to the luminaire are required, conform to the above requirements.

Fixing: Screw fixed.

6.6 WIRING

External flexible cords

Recessed luminaires: Provide flexible cord in conformance with the following:

- Length: ≥ 1.5 m.

- Cross sectional area: 0.75 mm2.

- Type: 3-core V75 (minimum) PVC/PVC, connected to a 10 A 3-pin moulded plug to AS/NZS 3112 or multi-pin plug, as documented.

6.7 LIGHTING CONTROL

General

Requirement: Provide the following as documented:

- Lighting switches.

- Dimmers.

- Automatic control systems.

Digital control system

General: Provide a proprietary, microprocessor-based system to control lighting under automatic and user interface control, as documented.

6.8 SUPPORTS

General

Requirement: Install luminaires on proprietary supports by means of battens, trims, noggings, roses and packing material.

Suspended luminaires

Rods: Steel pipe suspension rods fitted with gimbal joints.

Chains: Electroplated welded link chain.

Levelling wire: Stainless steel.

Levelling: Adjust the suspension system length so that the lighting system is level and even.

Horizontal tolerance: ± 3 mm between luminaires within the same area.

Surface mounted luminaires

General: Fit packing pieces to level luminaires and prevent distortion of luminaire bodies. Provide packing strips to align end to end luminaires.

Fixing: Conform to the following:

- Generally: Provide 2 fixings at each end of fluorescent luminaires.

- Luminaires less than 150 mm: A single fixing at each end in conjunction with 1.6 mm backing plates may be used.

- Provide battens and support for the fitting.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 19 28.04.2018

- Do not direct fix into plasterboard.

Recessed luminaires

General: Install recessed luminaires in trimmed openings in the suspended ceiling.

6.9 COMPLETION

General

Requirement: Before the date of practical completion carry out the following:

- Verify the operation of all luminaires.

- Adjust aiming and controls for all luminaires under night time conditions.

- Replace lamps which have been in service for a period greater than 50% of the lamp life as published by the lamp manufacturer.

7 TELECOMMUNICATIONS CABLING

7.1 RESPONSIBILITIES

General

Requirement: Provide a passive telecommunications cabling network system as documented and as follows:

- Network connection.

- Campus distributor.

- Campus cabling.

- Building distributor.

- Backbone cabling.

- Floor distributors.

- Consolidation points.

- Telecommunications outlets.

- Patching.

System performance

System warranty: 25 years minimum.

Surge protection devices (SPD)

General: Provide surge protection devices to protect equipment in racks and cabinets to LOW VOLTAGE SYSTEMS, SURGE PROTECTION DEVICES.

7.2 STANDARDS

General

AS/NZS 3080: Telecommunications installations – Generic cabling for commercial premises (ISO/IEC 11801:2002, MOD)

AS/NZS 3084: Telecommunications installations – Telecommunications pathways and spaces for commercial buildings

AS/NZS 3085.1: Telecommunication installations – Administration of communications cabling systems – Basic requirements

AS/NZS 3086: Telecommunications Cabling Systems for Small Office/Home Office Premises

AS/NZS 3087: Testing of Balanced Communications Cabling

AS/NZS 4117: Surge Protection Devices for Telecommunications Cabling

AS/ACIF S009: Installation requirements for customer cabling (Wiring Rules)

SAA HB 29: Telecommunications cabling handbook

SAA HB 252: Communications cabling manual, module 3: Residential communications cabling handbook

7.3 NETWORK CONNECTION

External network

Requirement: Liaise with each external communications carrier and determine the services and site access requirements for the network connection.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 20 28.04.2018

7.4 BUILDING ENTRANCE FACILITIES

Campus distributor (CD)

Standard: To AS/NZS 3080.

Network termination device

Requirement: Provide network termination device for the termination of external carrier cables and facilities. Provide separate frames as required for each external communications’ carrier and for copper and optical fibre cables.

Degree of protection for external BD/CDs: To AS 60529.

7.5 DISTRIBUTORS

General

Requirement: Provide the Building Distributors (BD) for voice and data to AS/NZS 3080 and as documented for the termination of campus and building backbone cable systems and the horizontal cable distribution systems.

Equipment requirements: Provide cable termination racks, patch panels, equipment mounting racks for servers and routers complete with power outlets as documented.

Copper cable termination distributors

General: Provide Krone termination frames for the termination of copper backbone and horizontal cable services.

Certification: Provide vendor certification (including the warranty period) for the integrated voice/data copper cabling systems.

Equipment racks

Dimension and type: Conform to the following:

- Equipment racks: 19 inch wide industrial type, or 600 mm or 800 mm wide RUs:

. ≤ 18 RU: Wall mounted, 600 mm depth.

. > 18 RU: Floor mounted, 800 mm or 1000 mm depth.

- Patch panels – Copper CAT 6 cables: 800 mm wide and 800 mm deep.

- Patch panels – Optical fibre cables: 800 mm wide and 800 mm deep. Nominate height of units.

- Server racks: 600 mm wide and 1000 mm deep. Nominate height of units.

Access location: Front, sides or rear.

Cable tray: Locate within outer cabinet void.

Doors: Provide transparent safety glass, lockable doors.

Power provision: Minimum 1 socket outlet for every 3 rack units on vertical rail.

Cable management: Provide as follows:

- 1 module for every 2 patch panels.

- 1 module for each fibre termination panel.

- Location: Vertically, on both sides of the panel.

Provisions for active equipment: 25% minimum, 1 fixed shelf for every 4RU of active equipment space.

Ventilation: Fan assisted.

Earthing: CES earth bar required.

Fixing: Conform to the following:

- Floor mounted: Firmly fix to floor, bolt together multiple racks using standard kit accessories.

- Floor/Wall mounted: Firmly fix to floor and wall.

Cross connect patch panels (copper cables)

General: Provide cross connect patch panels as documented.

Terminations: Terminate directly to the modular connector.

Fixed terminations:

- Rear terminals: Connect to 45° IDC punch down type.

- Front terminals: Connect to RJ45 modular connector.

Patch cords: Terminate cord ends with appropriate registered jacks.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 21 28.04.2018

Optical fibre termination panels

Requirement: Provide rack mounted termination frames for the termination of optical fibre backbone and horizontal cable services.

Certification: Provide vendor certification, including the warranty period, for the optical fibre cabling systems.

Break out trays: Provide fibre optic cable break out trays at each group of fibre optic cable terminations.

Loom cables: Neatly loom cables and lay stripped cables into the break out tray.

Secure cables: Make sure that cables are secured by the sheath and that there is no stress on the fibre optic cores.

Cross connect patch panels (optical fibre cables)

Requirement: Provide optical fibre cross connect patch panels as documented for both single and multicore optical fibre cables.

Cable management

Record book: Provide a record book at each cross-connect.

Location: Secure log books in each distribution frame records holder.

Identification, labelling, and record documentation: To AS/NZS 3085.1.

7.6 CABLES

Copper

Standard: To AS/CA S008, AS/CA S009, AS/NZS 3080 and AS/NZS ISO/IEC 14763.2. Amend spare capacity as necessary to suit future requirements.

Horizontal cabling voice and data: CAT 6 UTP cabling to each floor outlet.

Balanced system cables: UTP.

Cable end length: Provide a 5 m cable loop at each end of the cable.

Optical fibre

Standard: To IEC 60793-2-10.

Campus and building backbone cables:

- Default multimode type: 12 core multi-mode OM4 50/125 mµ.

Length: Provide not less than 1000 mm spare at each end.

Component type: SC.

Safe practices: To AS/NZS 2967.

External

Standard: Water penetration resistance to IEC 60794-1-2.

7.7 TELECOMMUNICATIONS OUTLETS

General

Outlets: Provide RJ45 8 way modular jacks, mounted on 6-way faceplate. Provide for up to three modular voice or data outlets on the each faceplate with three spaces for identification inserts.

Pinouts: T568A to AS/NZS 3080.

7.8 FLY LEADS

General

Type: Stranded.

Length: 1200 mm.

Quantity: Provide fly leads to 50% of outlets installed.

7.9 PATCH CORDS

General

Type: Stranded.

Length: 900 mm.

Quantity: 100% of outlets installed.

Termination: Registered jacks.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 22 28.04.2018

7.10 WIRELESS ACCESS POINT (WAP)

General

Requirement: Provide WAPs as documented, cabled to patch panels in the nearest FD.

Compatibility: ISO/IEC 8802-11 and IEEE 802.11.

LAN port: 100 Mbps.

Modes: Wireless access point, point-to-point bridge, point-to-multi-point wireless bridge, wireless client and wireless repeater.

Power over ethernet: Required.

Location: Install in ceiling voids distributed around the site buildings and determine the number and location by a site survey using the wireless network to confirm full site coverage.

7.11 ENGINEERING SERVICES

General

Requirement: Provide cabling systems, as documented.

7.12 CABLE INSTALLATION

Installation

Requirement: To the manufacturers' recommendations.

Crossover: Install cables neatly and without crossovers between cables.

Loom size: Loom cables into groups not exceeding 50 cables, and hold looms in place using reusable cable ties at least 20 mm wide. Do not exert compressive force on the cables when installing cable straps.

Cable separation

Separation for safety: To AS/CA S009, and by at least 150 mm.

Fluorescent luminaires: Maintain a clearance of more than 300 mm.

External cables

Requirement: To ACIF C524.

7.13 TELECOMMUNICATIONS OUTLET INSTALLATION

Installation

Mounting: Flush mount.

Flushplate layout: Provide 6-way standard flushplate capable of accepting the installation of three individual modular sockets along the top horizontal axis and three identification inserts on the bottom horizontal axis. Unused socket positions to be filled with blank inserts. Arrange the modular sockets with the locking latch in the bottom position, i.e. pins at the top.

Horizontal cabling termination: Terminate Category 6 cabling to the rear of the outlet modular jack with insulation displacement connections forming a gas tight joint. Arrange cable pairs at each jack conforming to AS/NZS 3080 Fig 15.

7.14 EARTHING SYSTEM

General

Standard: To AS/CA S009 Section 20.

Communication earth system (CES)

Requirement: Provide a communications earth terminal (CET) adjacent to each electrical switchboard. Connect the CET to the local protective earth (PE) system at the switchboard.

Distributor: Provide an earth bar within each distributor and connect to the local CET.

Interconnections: Verify that there are no interconnections between the lightning protective earthing system and the telecommunications earthing system.

7.15 COMPLETION

Cable management

General: Before the date for practical completion, submit log books for each distribution frame with details of cable terminations and provisions for recording cable, line and jumper information.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 23 28.04.2018

8 TELEVISION DISTRIBUTION SYSTEMS

8.1 RESPONSIBILITIES

General

Requirement: Provide a system suitable for the reception and distribution of analog and digital television, video, radio and sound signals, as documented.

Network connection: Arrange with the network operator(s) for the connection of their network. Conform to the network operators' requirements.

Designer: Network operator’s Approved Design Partner.

Survey: Confirm location and height of Free-to-air (FTA) antenna by on-site measurements.

8.2 SYSTEM DESCRIPTION

System type

Type: As documented.

Performance requirements

General: To AS/NZS 1367.

Capacity: Provide the distribution system with the installed capacity to accommodate 30% additional outlets.

Signal sources

Free-to-air (FTA) antennae system: Provide FTA antennae system terminating at the premises cabling interface.

Network operator: Provide for the connection of the network operator’s system terminating at the premises cabling interface as documented.

Local signal source: Provide television input sockets at the premises cabling head-end for the distribution of in-house television channels on separate channels of the network.

Service entry

General: Provide service entry facilities to suit signal sources, head end equipment and distribution systems.

Location: As documented.

Head end equipment

General: Provide head end equipment to suit signal sources, distribution systems and documented performance.

Location: As documented.

Surge protection devices (SPD)

General: Provide surge protection devices to protect final equipment in racks and cabinets to LOW VOLTAGE POWER SYSTEMS, SURGE PROTECTION DEVICES.

Distribution system

General: Provide a cabling distribution network from the head end equipment to each network distribution tap.

FTA distribution taps: Provide FTA distribution taps.

Network distribution taps: For systems designed for more than one network operator provide individual distribution taps for each network operator. Co-locate the taps with FTA taps in groups to facilitate selected connection or changes to outlet feeders.

Location: Group all equipment as documented.

Outlets

General: Provide outlets and feeders from distribution tap(s) as documented.

Quantity: Provide separate sockets for each source and service.

8.3 STANDARDS

General

Electromagnetic compatibility: To AS/NZS 1367.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 24 28.04.2018

9 EMERGENCY EVACUATION LIGHTING

9.1 RESPONSIBILITIES

General

Requirement: Provide single point monitored emergency lighting and exit signs, as documented.

9.2 SINGLE-POINT SYSTEM LUMINAIRES

General

Visual indicator lights: Provide a red indicator, readily visible when the luminaire is in its operating location, which indicates that the battery is being charged.

Inverter system: Provide protection of the inverter system against damage in the event of failure, removal or replacement of the lamp, while in normal operation.

Local test switches: Provide a momentary action test switch, accessible from below the ceiling, on each luminaire to temporarily disconnect the mains supply and connect the battery to the lamp.

Common test switches: Provide a common test switch on the local distribution board which disconnects main supply to the luminaires and tests for discharge performance and automatically reverts to normal operating mode after testing.

Monitored system

Data connection: Provide internal monitoring facilities and provision for the connection of data cabling to a central monitoring computer.

Batteries

Type: Lead-acid or nickel-cadmium batteries capable of operating each lamp at its rated output continuously for at least 2 hours during commissioning tests and 1.5 hours during subsequent tests.

Battery life: At least 3 years when operating under normal conditions at an ambient temperature of between 10oC and 40°C and subject to charging and discharging at 6 monthly intervals.

Marking: Indelibly mark each battery with its date of manufacture.

9.3 SINGLE POINT SYSTEM

Power supply

General: Provide an unswitched active supply to each luminaire and exit sign, originating from the test switch control panel.

Data monitoring

General: If a monitoring system is documented, provide a data cable system from each single-point luminaire and connect to the monitoring computer.

10 ELECTRONIC SECURITY AND ACCESS CONTROL

10.1 RESPONSIBILITIES

General

Requirement: Provide electronic security systems, as documented.

System components

Requirement: Provide the following components:

- Remote monitoring system.

- Access control system.

- Intercom system.

Security classification: As documented.

System communications: As documented.

10.2 STANDARDS

Intruder alarm systems

General: To AS/NZS 2201.1.

Alarm transmission system: To AS/NZS 2201.5.

Internal detection devices: To AS 2201.3.

Wireless systems: To AS 2201.4.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 25 28.04.2018

10.3 SECURITY SYSTEMS

Alarm system panels or processors

Capacity: Provide separate sectors for each nominated internal zone, and for normally-closed and normally-open perimeter zones.

Sector time delay: Provide adjustable time delay entry/exit for each sector, with adjustment range 0 to 30 s.

Batteries and chargers:

- Sealed battery: Provide a sealed battery and charger system contained within each control panel with capacity as documented.

Uninterruptible power supply

General: Provide a dedicated uninterruptible power supply and connect to the security systems.

Capacity: At least 15 minutes, for the complete system in normal operation.

Activation

Activation devices: Provide keypads, cards, card readers and other activation devices for access control and intruder alarm systems as documented.

External: Provide weatherproof (IP56) hoods or housings for external units.

Default mounting height: 1100 mm from floor level.

External audible and visual alarms

General: Provide a corrosion-resistant weatherproof metal enclosures containing sirens and blue strobe lights. Fix in locations not readily accessible without a ladder.

Anti-tamper devices

Requirement: Provide anti-tamper devices to control panels, external equipment, control and activating devices, and access control devices.

Function: To register an instantaneous alarm if covers are removed or vital wiring is disconnected.

Remote monitoring

Monitoring system: Provide a monitoring system in the alarm panel or processor for transmission of alarms and monitoring of the system by parties responsible for attending to alarms.

10.4 ACCESS CONTROL

Access control processors or panels

Capacity: Provide separate entry/exit control modules for each designated access point.

Users: Program the system to match the number of authorised users with unique access codes.

Time zones: At least 4 per day, with provision for weekends and public holidays.

Door control devices

Requirement: Provide door control devices as set out in DOOR CONTROL DEVICES and as documented.

Vehicle control

Vehicle access control: Provide vehicle access control system combining connection to vehicular doors and boom gates, and interconnection to the main access control system.

Exit loop detection: Provide a buried loop detection system adjacent to the exit point to activate boom gates or vehicular doors on approach by a vehicle. Connect so that doors or gates close after a pre-set time.

Interlock: Provide a photoelectric beam safety interlock.

Interlock function: To prevent door or gate from closing until the vehicle has cleared the exit point.

Mounting of entry access equipment: Where practicable, provide direct wall mounted push-buttons or readers; otherwise provide a robust mounting bollard and extension arm.

Default mounting height: 1000 mm from floor level.

Reed switches: Provide heavy duty reed switches on both sides of vehicle doors to generate a door closed indication at the control panel, where documented.

Intercom

Base station: Provide intercom base station, interconnected with the individual local stations. Include speakers and microphones.

Entry station construction: Wall mounted flush stainless steel panel.

Weatherproofing: IP56.

09 ELECTRICAL 0902 Electrical

© NATSPEC (Oct 17) 26 28.04.2018

Dial: Digital push-button type.

Schedule: Provide a weatherproof (IP56) schedule holder and card identifying individual local stations. Locate next to the base station intercom panel.

Local station: Provide wall mounted intercom local stations, interconnected with the base stations and external entry points.

Internal station type: Surface mounted, removable handset type.

Operation: Provide an audible tone device to indicate that the individual station is being called, and a press-to-talk switch so that the entry station can communicate with the internal station only when the switch is held down.

Door control: Provide integral momentary action door release switches to operate the door release or opening mechanisms at each external entry point.

10.5 EQUIPMENT POWER SUPPLY

Mains supplies

Permanent power supply: Provide permanent power supply to the following:

- Intruder alarm panels and access control panels including sub panels.

- Electric door strike local panels or control equipment.

- Intercom stations.

Marking: Label the switchboard circuit breaker from which power for the security systems is obtained as follows:

SECURITY SYSTEM - Do not switch off.

Interconnection to other services

General: Provide functions and equipment to allow the interconnection to other systems. Provide and connect wiring to the designated services.

Lifts: Arrange for installation and connection of lift readers and associated equipment.