08_chapter 3.pdf

19
61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this chapter. The system is analyzed under severe disturbance to study the transient behavior by simulating three phase to ground fault at various buses. To enhance the transient stability of the system, STATCOM is inserted and tested to show the effect of the same on the transient stability under severe disturbance. The swing curve in degree, real power in MW, reactive power in MVAr and the voltage in p.u. of 11 kV generator bus(11) and the voltage in p.u. for 11 kV bus(14), 33 kV bus(6) and 110 kV grid bus(1) are taken for analysis. The potential application of STATCOM on the improvement of voltage profile of the various buses and reduction in rotor angle oscillation of the generator is evaluated from the implementation results. 3.2 LITERATURE REVIEW STATCOM includes the GTO and diode valves together with their necessary snubber circuits that make a valuable tool in the power system design process. The STATCOM is given this name because in a steady state operating regime, it replicates the operating characteristics of a rotating synchronous compensator (Gyugyi 1998 and Hingorani and Gyugyi 2000).

Upload: niketsali23

Post on 14-Sep-2015

253 views

Category:

Documents


1 download

TRANSCRIPT

  • 61

    CHAPTER 3

    TRANSIENT STABILITY ENHANCEMENT IN A

    REAL TIME SYSTEM USING STATCOM

    3.1 INTRODUCTION

    The modeling of the real time system with STATCOM using

    MiPower simulation software is presented in this chapter. The system is

    analyzed under severe disturbance to study the transient behavior by

    simulating three phase to ground fault at various buses. To enhance the

    transient stability of the system, STATCOM is inserted and tested to show the

    effect of the same on the transient stability under severe disturbance. The

    swing curve in degree, real power in MW, reactive power in MVAr and the

    voltage in p.u. of 11 kV generator bus(11) and the voltage in p.u. for 11 kV

    bus(14), 33 kV bus(6) and 110 kV grid bus(1) are taken for analysis. The

    potential application of STATCOM on the improvement of voltage profile of

    the various buses and reduction in rotor angle oscillation of the generator is

    evaluated from the implementation results.

    3.2 LITERATURE REVIEW

    STATCOM includes the GTO and diode valves together with their

    necessary snubber circuits that make a valuable tool in the power system

    design process. The STATCOM is given this name because in a steady state

    operating regime, it replicates the operating characteristics of a rotating

    synchronous compensator (Gyugyi 1998 and Hingorani and Gyugyi 2000).

  • 62

    Abido (2005) presented a singular value decomposition (SVD) based

    approach to assess and measure the controllability of the poorly damped

    electromechanical modes by the different control channels of STATCOM. It

    is observed that the electromechanical modes are more controllable via phase

    modulation channel. It is also concluded that the STATCOM-based damping

    stabilizers extend the critical clearing time and enhance greatly the power

    system transient stability. Haque (2004) demonstrated that by the use of

    energy function, the STATCOM is capable to provide additional damping to

    the low frequency oscillations. The damping characteristics of STATCOM

    have also been analyzed and addressed, where different approaches to

    STATCOM-based damping controller design have been adopted, such as

    loop-shaping (Rahim et al 2002), pole placement (Lee and Sun 2002),

    multivariable feedback linearization (Sahoo et al 2002, 2004), H control(Al-Baiyat 2005) and intelligent control (Morris et al 2003).

    3.3 PROBLEM STATEMENT

    Transient stabilization is an important factor in the power system

    control. The key factor in transient stability prediction is the way in which the

    transient swings either converges or diverges. It is important to prevent

    generators from losing synchronism and damping the subsequent oscillations

    quickly. The problem is formulated as the insertion of STATCOM in real

    time system that is to be analyzed using MiPower simulation software for

    enhancing the transient stability.

    3.4 GENERAL REPRESENTATION OF STATCOM

    The basic electronic block of a STATCOM is a VSC that converts a

    DC voltage at its input terminal into a three-phase set of AC voltages at

    fundamental frequency with controllable magnitude and phase angle. The

  • 63

    VSC can be made up of three-phase, two-level, six pulse converters

    connected by an appropriate magnetic circuit into a multi-pulse structure to

    meet the practical harmonic, current and voltage rating requirements; or three-

    phase, three-level, twelve-pulse converters in a multi-pulse structure; or

    simply PWM controlled three phase, two-level converters. A STATCOM has

    no inertia and can basically act in a fraction of a second, which is an

    advantage over a synchronous compensator. Furthermore, STATCOM does

    not significantly alter the existing system impedance, which gives it an

    advantage over the SVC. In all STATCOM applications implemented in

    transmission systems so far, only two of these methods have been used; PWM

    are still considered uneconomical due to high switching losses of available

    semiconductor switches with intrinsic turn-off capabilities. A STATCOM can

    be used for voltage regulation in a power system, having as an ultimate goal

    the increase in transmittable power, improvements of steady state

    transmission characteristics and of the overall stability of the system. Under

    light load conditions, the controller is used to minimize or completely

    diminish line overvoltage; on the other hand, it can also be used to maintain

    certain voltage levels under heavy loading conditions. In its simplest form, the

    STATCOM is made up of a coupling transformer, a VSC, and a DC energy

    storage device. The energy storage device is a relatively small DC capacitor,

    and hence, the STATCOM is capable of only reactive power exchange with

    the transmission system. If a DC storage battery or other DC voltage sources

    are used to replace the DC capacitor, the controller can exchange real and

    reactive power with the transmission system, extending its region of operation

    from two to four quadrants. A functional model of a STATCOM is shown in

    Figure 3.1. A STATCOM can support system voltage at extremely low

    voltage conditions as long as the DC capacitor can retain enough energy to

    supply losses. The STATCOM also has increased transient ratings in both

    capacitive and inductive regions.

  • 64

    Figure 3.1 Functional model of a STATCOM

    The overload capability is about 20% for several cycles in both

    regions. It is also worth noticing that the inductive transient current rating is

    slightly larger due to the fact that the GTOs in the inductive region are

    naturally commutated and hence, the amount and duration of this temporary

    overload capability is limited by the maximum current of the free-wheel

    diode. The capacitive transient rating is determined by the maximum current

    turn-off capability of the GTO thyristors.

    3.4.1 Modeling of STATCOM

    STATCOM model shown in Figure 3.2, used to improve the

    transient stability of the real time system (real time system is discussed in

    section 2.6) considered, has been modeled in MiPower6.0. STATCOM is

    modeled using FPB available in MiPower. This FPB is executed to verify the

    correctness of the model. FPB is converted into FPD and this FPD is called as

    a function for the simulation of transient stability.

  • 65

    Figure 3.2 Modeling of STATCOM

    K K

    sT

    K1Vref [1]

    + N[2]

    K=2.23 K=0.9416

    K=0.0584

    T = 0.015

    +

    Max = -0.529

    Min = 0.9959

    STATCOM Q

    Supply

    N[14]N[9]N[6]

    N[7]

    N[5]

    N[3]

    N[16]

    N[17]N[10]

    N[13]

    K = 1 K = 1

    T=0.025 T = 0.01 Terminal Voltage [12]

    N[4]+ N[18]

    sT

    K1sT

    K1

    -

  • 66

    3.5 RESULTS WITH DISCUSSIONS

    The effect of STATCOM on transient stability of power system is

    analyzed by creating three phase to ground fault at 11 kV bus(14) and 33 kV

    bus(6) using MiPower. The transient stability is considered with a fault

    initiated at 1 s and cleared at 1.1 s. i.e., protection system cleared the fault

    within 100 ms. Transient stability is executed upto 10s to view the response.

    By inserting the STATCOM in the 33 kV bus(6) for the fault at 11 kV

    bus(14) and in the 11 kV bus(14) for the fault at 33 kV bus(6), the responses

    are presented. Swing curve and voltages are taken at different conditions like

    normal, at fault and after the insertion of FACTS controllers.

    During the steady state condition (without any disturbance) and

    fault condition (with disturbance) for the fault at 11 kV bus(14), the various

    responses of the system are discussed in sections 2.7.1 and 2.7.2.

    3.5.1 Transient Stability of System with STATCOM at 33 kV Bus(6)

    The STATCOM is placed at 33 kV bus(6) of the system to improve

    the voltage and to enhance the transient stability. Three phase to ground fault

    is simulated for a period of 100 ms in 11 kV bus(14). The swing curve and

    voltage of 11 kV generator bus(11) and voltage of 110 kV grid bus(1) and 33

    kV bus(6) are presented below.

    STATCOM at 33 kV bus(6), for a three phase to ground fault of

    100 ms duration at 11 kV bus(14), leads the generator to oscillate from 3.5 to

    9 degrees (during disturbance its value ranges from 3 to 9.6 degrees) whereas

    at the steady state condition, it is 6.3 degrees with respect to grid. This is

    depicted in Figure 3.3.

  • 67

    Figure 3.3 Swing curve of generator at fault condition (with STATCOM

    at 33 kV bus(6))

    Figure 3.4 110 kV grid bus(1) voltage in p.u. at fault condition

    (with STATCOM at 33 kV bus(6))

  • 68

    STATCOM at 33 kV bus(6), for three phase fault at 11 kV bus(14),

    significantly contributes the reactive power and improves the voltage profile.

    Since 110 kV grid bus(1) is far away from STATCOM at 33 kV bus(6), the

    voltage profile improves from 0.96 p.u. to 0.983 p.u. This is depicted in

    Figure 3.4.

    Figure 3.5 33 kV bus(6) voltage in p.u. at fault condition (with

    STATCOM at 33 kV bus(6))

    STATCOM at 33 kV bus(6), for three phase fault at 11 kV bus(14),

    significantly contributes the reactive power and improves the voltage profile.

    Since the STATCOM is connected in the same bus, the impact on voltage

    profile improvement is high. Even in the steady state, the STATCOM

    increases the voltage profile to 0.995 p.u. and limits the voltage dip to 0.955

    p.u. during fault. This is depicted in Figure 3.5.

  • 69

    Figure 3.6 11 kV generator bus(11) voltage in p.u. at fault condition

    (with STATCOM at 33 kV bus(6))

    STATCOM at 33 kV bus(6), for three phase fault at 11 kV bus(14),

    significantly contributes the reactive power and improves the voltage profile.

    It limits the voltage drop from 0.98 p.u. to 0.99 p.u. This is depicted in

    Figure 3.6.

    Considering the STATCOM at 33 kV bus(6) for the fault at 11 kV

    bus(14), it improves voltage stability to great extent by maintaining the

    voltage profile during steady state and improves the voltage profile

    significantly during fault. However, the impact of STATCOM on angular

    stability is good.

  • 70

    3.5.2 Transient Stability of System with STATCOM at 11 kV bus(14)

    The transient stability is evaluated with the help of swing curve for

    a three phase fault at 33 kV bus(6) for 100 ms duration. It is assumed that

    protection system cleared the fault within 100 ms. Three phase fault at 33 kV

    bus(6) is simulated from 1 s to 1.1 s and the response is plotted up to 10 s.

    The swing curve, real power, reactive power and voltage of 11 kV generator

    bus(11) and voltage of 33 kV bus(6) and 11 kV bus(14) are presented below.

    Figure 3.7 Swing curve of generator at fault condition in 33 kV bus(6)

    A 100 ms three phase to ground fault at 33 kV bus(6) leads the

    generator to oscillate from -2 to 15 degrees whereas at the steady state

    condition, it is 6.3 degrees with respect to grid. This is depicted in Figure 3.7.

    The system is considered stable, for the three phase to ground fault at 33 kV

    bus(6) for 100 ms duration, since the swing is well within the transient limit

    of 180 degrees.

  • 71

    Figure 3.8 Real power generation by generator in MW at fault

    condition in 33 kV bus(6)

    Whenever there is a three phase fault in the network, the real power

    transfer and consumption will come down. However, mechanical input of the

    generator remains constant. This will increase the accelerating torque in the

    generator and in turn leads to unstable condition if not controlled properly.

    Even after the clearance of fault, oscillation will not damp to zero

    immediately. Since the droop characteristics of the generator are slow in

    nature (high time constant), the oscillation takes longer time to damp.

    Figure 3.8 indicates the oscillation of real power of the generator that varies

    from 6.5 MW to 63 MW.

  • 72

    Figure 3.9 Reactive power generation by generator in MVAr at fault

    condition in 33 kV bus(6)

    Whenever there is a three phase fault in the network, the voltage

    will come down to zero at fault point and drastically reduce the voltage

    profile in the vicinity of the fault. The reactive power of the generator

    drastically increases from 14 MVAr to 75 MVAr during the fault without any

    time delay because the exciter characteristics are fast in nature (very low time

    constant). This is depicted in Figure 3.9. Also, after the fault clearance, the

    voltage profile is improved to normal value.

  • 73

    Figure 3.10 33 kV bus(6) voltage in p.u. at fault condition in 33 kV bus(6)

    Since the fault is at this bus, the voltage is zero during fault and

    recovers back to the normal after clearance of the fault. This is depicted in

    Figure 3.10.

    Figure 3.11 11 kV generator bus(11) voltage in p.u. at fault condition in

    33 kV bus(6)

  • 74

    Though the 11 kV generator bus(11) is far away from the faulty 33

    kV bus(6) and two transformer impedances exist between the two buses, the

    generator connected to the 11 kV generator bus(11) limits the voltage drop to

    small value (from 1 p.u. to 0.97 p.u.) during fault and recovers back to normal

    after clearance of the fault. This is depicted in Figure 3.11.

    Figure 3.12 11 kV bus(14) voltage in p.u. at fault condition in 33 kV

    bus(6)

    Since the 11 kV bus(14) is far away from the faulty 33 kV bus(6)

    and two transformer impedances exist between the two buses, the voltage

    reduction is severe (from 1 p.u. to 0.95 p.u.) during fault and recovers back to

    normal after clearance of the fault. This is depicted in Figure 3.12.

  • 75

    The effect of STATCOM on transient stability of power system is

    analyzed by simulating three phase to ground fault at 33 kV bus(6) using

    MiPower, by inserting the STATCOM in the 11 kV bus(14). The swing curve

    and voltage of 11 kV generator bus(11) and voltage of 11 kV bus(14) are

    presented below.

    Figure 3.13 Swing curve of generator at fault condition in 33 kV bus(6)

    (with STATCOM at 11 kV bus(14))

    STATCOM at 11 kV bus(14), for a three phase to ground fault of

    100 ms duration at 33 kV bus(6), leads the generator to oscillate from -1 to 14

    degrees (during disturbance its value ranges from -2 to 15 degrees) whereas at

    the steady state condition it is 6.3 degrees with respect to grid. This is

    depicted in Figure 3.13.

  • 76

    Figure 3.14 11 kV generator bus(11) voltage in p.u. at fault condition in

    33 kV bus(6) (with STATCOM at 11 kV bus(14))

    STATCOM at 11 kV bus(14), for three phase fault at 33 kV bus(6),

    significantly contributes the reactive power and improves the voltage profile.

    It limits the voltage drop from 0.97 p.u. to 0.985 p.u. This is depicted in

    Figure 3.14.

    STATCOM at 11 kV bus(14), for three phase fault at 33 kV bus(6),

    significantly contributes the reactive power and improves the voltage profile.

    Since the STATCOM is connected in the same bus, the impact on voltage

    profile improvement is higher and maintained at 1 p.u. This is depicted in

    Figure 3.15.

  • 77

    Figure 3.15 11 kV bus(14) voltage in p.u. at fault condition in 33 kV

    bus(6) (with STATCOM at 11 kV bus(14))

    Considering the STATCOM at 11 kV bus(14), it improves voltage

    stability to great extent by maintaining the voltage profile during steady state

    and improves the voltage profile significantly during fault. However, the

    impact of STATCOM on angular stability is good.

    The reactive power supplied by STATCOM at 11 kV bus(14) to

    nearby buses 13 and 15 is depicted in the Figures 3.16 and 3.17 respectively.

  • 78

    Figure 3.16 Reactive power Q supplied to bus13 (with STATCOM at

    11 kV bus(14))

    Figure 3.17 Reactive power Q supplied to bus15 (with STATCOM at

    11 kV bus(14))

  • 79

    The ability of the STATCOM to supply the reactive power during

    voltage dip / drop improves the voltage profile of buses, which in turn

    prevents the large motors connected to those buses to stall.

    3.6 CONCLUSION

    Modeling of real time system with the STATCOM using MiPower

    simulation software is presented. STATCOM is modeled using MiPower for

    enhancing the transient stability of the system. From the transient stability

    analysis, it is observed that STATCOM improves the voltage profile of the

    system for the following conditions:

    i) STATCOM at 33 kV bus(6), three phase to ground fault at

    11 kV bus(14)

    ii) STATCOM at 11 kV bus(14), three phase to ground fault at

    33 kV bus(6)

    Also, the impact of STATCOM on damping the rotor angle

    oscillation of generator is effective in the system considered.

    Compared with the performance of SVC discussed in chapter 2, the

    STATCOM provides much better control in damping the rotor angle

    oscillation of the generator in addition to the improvement of voltage profile.

    The damping of the rotor angle oscillation of the generator may

    further be improved by increasing the inertia of the generator by means of

    adding additional weight or flywheel.