078101610manual trelltent eng 1102

24
TrellTent ® Inflatable shelter system - Instruction manual Trelleborg Protective Products AB Johan Kocksgatan 10, SE-31 81 Trelleborg, Sweden Phone: +46 410 510 00, Fax: +46 410 518 50 E-mail: [email protected], Internet: www.trelleborg.com/protective

Upload: navigator1977

Post on 18-Nov-2015

39 views

Category:

Documents


6 download

DESCRIPTION

for seafarers

TRANSCRIPT

  • TrellTent Inflatable shelter system

    - Instruction manual

    Trelleborg Protective Products AB Johan Kocksgatan 10, SE-31 81 Trelleborg, Sweden

    Phone: +46 410 510 00, Fax: +46 410 518 50 E-mail: [email protected], Internet: www.trelleborg.com/protective

  • Trelleborg Protective Products AB 1102 2 Subject to change without notice

    1. GENERAL ................................................................................................................................................................ 3

    The standard TrellTent system ................................................................................................................................ 3 Ribs ........................................................................................................................................................................... 3 Spacing collars .......................................................................................................................................................... 3 Doors ......................................................................................................................................................................... 3 Windows ................................................................................................................................................................... 3 Connections ............................................................................................................................................................... 3 Support ...................................................................................................................................................................... 4 1.1 TrellTent 3/2 ..................................................................................................................................................... 4 1.2 TrellTent 3/4 ..................................................................................................................................................... 4 1.3 TrellTent 6/2 HD ............................................................................................................................................... 4 1.4 TrellTent TFA ................................................................................................................................................... 4 1.5 Air pressure fan ................................................................................................................................................... 4

    2. TECHNICAL INFORMATION ............................................................................................................................... 5 2.1 TrellTent 3/2 ..................................................................................................................................................... 5 2.2 TrellTent 3/4 ..................................................................................................................................................... 5 2.3 TrellTent 6/2 HD ............................................................................................................................................... 6 2.4 TrellTent TFA ................................................................................................................................................... 6 2.5 Air pressure fan ................................................................................................................................................... 6 2.6 TrellTent 3/2 inner ground sheet ....................................................................................................................... 7 2.7 TrellTent 3/4 inner ground sheet ....................................................................................................................... 7 2.8 TrellTent 6/2 HD inner ground sheet ................................................................................................................ 7 2.9 TrellTent TFA inner ground sheet..................................................................................................................... 7 2.10 TrellTent 3/2 AC Channel ............................................................................................................................... 7 2.11 TrellTent 3/4 AC Channel ............................................................................................................................... 7 2.12 TrellTent 6/2 HD AC Channel ........................................................................................................................ 7 2.13 TrellTent TFA AC Channel ............................................................................................................................ 8 2.14 Tent pegs ........................................................................................................................................................... 8 2.15 Guy ropes .......................................................................................................................................................... 8 2.16 Foot pump ......................................................................................................................................................... 8

    3. HANDLING ............................................................................................................................................................. 8 3.1 General information ............................................................................................................................................ 8 3.2 Erecting tent 3/2, 3/4 and TFA ............................................................................................................................ 9 3.3 Erecting TrellTent 6/2 HD .............................................................................................................................. 12 3.4 Connection alternative ...................................................................................................................................... 12 3.5 Description of specific parts .............................................................................................................................. 15 3.6 Dismantling ....................................................................................................................................................... 18 3.7 Packing .............................................................................................................................................................. 18

    4. MAINTENANCE / REPAIR .................................................................................................................................. 20 4.1 Cleaning ............................................................................................................................................................ 20 4.2 Repair general ................................................................................................................................................ 20 4.3 Repair of tent, floor and window fabric ............................................................................................................ 20

    4.3.1 Repair of minor holes and tears .................................................................................................................. 20 4.3.2 Repair of major holes and tears .................................................................................................................. 20 4.3.3 Repair of large holes and tears ................................................................................................................... 20

    4.4 Repair of rib casing ........................................................................................................................................... 20 4.5 Repair of polyurethane inner tubes ................................................................................................................... 20 4.6 Replacement of inner tubes ............................................................................................................................... 21 4.7 Immediate action chart for leaks ....................................................................................................................... 22 4.8 Replacement of door zipper .............................................................................................................................. 23 4.9 Repair of grommets ........................................................................................................................................... 23 4.10 Repair of grommet clamp and loop fastener ................................................................................................... 23 4.11 Submitting for storage ..................................................................................................................................... 24 4.12 Storage ............................................................................................................................................................ 24

  • Trelleborg Protective Products AB 1102 3 Subject to change without notice

    1. GENERAL The standard TrellTent system The TrellTent system was developed in the beginning of the 70s in co-operation with the Medical Board of the Swedish Armed Forces. The serial deliveries started 1980 and up to today, Trelleborg Protective Products has produced some 3500 tents. The TrellTent system was the original inflatable tent with ambient pressure in the tent and inflatable ribs. These features give an erection time of down to 5 minutes. The idea behind the TrellTent system is to offer a lightweight tent, which is quickly erected and easy to handle, but also offers optimal durability and safe operation. This has been achieved by a modular, inflatable tent system with a great variety of sizes, designs, connection units and accessories. The half-cylindrical shape of the tent makes it resistant to wind, snow and rain load. The fixed attached floor gives a clean internal environment and makes the tent easy to handle. The light green colour inside the tent offers a natural colour that meets medical requirements. The ribs are equipped with numerous attachments where equipment can be hanged. Connection parts, which also serve as a barrier for rainwater, are placed around the doors. The fabric is watertight. The durability of the TrellTent system is well proven after many years of use in the most different climatic and environmental circumstances, such as in the Gulf war, the Somalian war, in Cambodia, on the South Pole and during the Swedish Mount Everest expeditions. Ribs The construction with separate ribs and spacing collars of aluminium pipes is chosen of different reasons. The main reason is that this system is much safer than a system with inflatable horizontal tubes. If one rib is damaged, the other ribs will keep the pressure and the tent will still be possible to use. A damaged inner tube can also be exchanged to a new one while the tent is in use. The air valves are of type non-return valves, which are easily manoeuvred by hand. The ribs can be inflated by means of a fan, a foot pump or by air from BA bottles. Spacing collars The spacing collars are made of aluminium pipes with plastic muffs at the ends. The collars are separable into two pieces. They are delivered in bags. Doors The doors are 1,9 m wide and 2,1 m high. They are equipped with heavy-duty metal zippers. When a door is opened, it is rolled together and hangs in three rope loops and pegs. A connection part around the door makes it possible to connect two tents together easily. Windows The windows are made of a loose-woven PVC fabric. The PVC is a bit whitish in order to prevent view from the outside. This also prevents strong direct sunlight. The windows are equipped with hatches that can be rolled together when not used. When used they can be fixed by means of Velcro tapes. The hatches also serve as an extra protection against strong heat. Connections A standard 3/2 tent is equipped with 4 service hoses and a 3/4 tent with 8 service hoses, for electrical cables or hoses. Both tent types have 4 ducts for ventilation.

  • Trelleborg Protective Products AB 1102 4 Subject to change without notice

    Support To secure the tent to the ground, it is equipped with reinforced holes for tent pegs and connection of guy ropes. The tent is also equipped with a 250 mm wide flap along all sides, which can be used for fixation of the tent when tent pegs can not be used. 1.1 TrellTent 3/2 The TrellTent is primarily intended for surgical or other activities that set high demands on the surrounding hygiene and the working environment. The tent is also appropriate for other functions in first-aid stations and hospitals. The 3/2 tents can be connected end-wall to end-wall, which allows unlimited lengthways expansion. 1.2 TrellTent 3/4 The basic design of the 3/4 tent is identical to that of the 3/2 tent. The major difference is that the 3/4 tent has 4 doors, which makes it possible to connect other tents to all four sides of the tent. 1.3 TrellTent 6/2 HD The TrellTent 6/2 HD is a spacious tent designed to be used as an auditorium. It is separated into two sections for easier handling. The sections are connected by means of spring hooks and Velcro tapes. The tent is equipped with 2 standard doors on each gable, and thus it can be connected to the rest of the TrellTent system. 1.4 TrellTent TFA The TFA tent serves as a sluice for a C-protected camp with an internal over-pressure. It has the standard design on one gable and 2 doors on the other. It consists of totally 5 rooms. The airflow is always in the direction from the filtered air to the contaminated outer air. 1.5 Air pressure fan The air pressure fan is a portable 1-phase fan giving a maximal pressure of 18 kPa. It comes in a rigid wooden box for storage and protection.

  • Trelleborg Protective Products AB 1102 5 Subject to change without notice

    2. TECHNICAL INFORMATION

    2.1 TrellTent 3/2 Length: 7,25 m Width: 5,2 m Maximum height: 2,6 m Floor area: 38 m2 Volume: Approx. 75 m3 Material: PVC coated synthetic fabric Number of doors: 2 Height, door opening: 2150 mm Width, door opening: 1880 mm Number of windows: 4 Number of air ducts: 4 Number of service openings: 4 External colour: Olive green Internal colour: Light green Weight, packed in tarpaulin: 180 kg Weight, packed in box: 223 kg, including pallet and box of 43 kg Volume when packed in tarpaulin: 1,1 m3 Volume when packed in box: L = 1,4 m; B = 1,1 m; H = 1,0 m 2.2 TrellTent 3/4 Length: 7,25 m Width: 5,2 m Maximum height: 2,6 m Floor area: 38 m2 Volume: Approx. 75 m3 Material: PVC coated synthetic fabric Number of doors: 4 Height, door opening: 2150 mm Width, door opening: 1880 mm Number of windows: 4 Number of air ducts: 4 Number of service openings: 8 External colour: Olive green Internal colour: Light green Weight, packed in tarpaulin 200 kg Weight, packed in box 243 kg, including pallet and box of 43 kg Volume when packed in tarpaulin: 1,3 m3 Volume when packed in box: L = 1,4 m; B = 1,1 m; H = 1,0 m

  • Trelleborg Protective Products AB 1102 6 Subject to change without notice

    2.3 TrellTent 6/2 HD Length: 14,5 m Width: 6,8 m Maximum height: 3,3 m Floor area: 98 m2 Volume: Approx. 260 m3 Material: PVC coated synthetic fabric Number of doors: 2 Height, door opening: 2150 mm Width, door opening: 1880 mm Number of windows: 8 Number of air ducts: 8 Number of service openings: 4 External colour: Olive green Internal colour: Light green Weight, packed in tarpaulin: 400 kg Weight, packed in boxes: 485 kg, including pallet and box of 43 kg Volume when packed in boxes: L = 1,4 m; B = 1,1 m; H = 1,0 m. 2 boxes 2.4 TrellTent TFA Length: 7,25 m Width: 5,2 m Maximum height: 2,6 m Floor area: 28 m2 Volume: 38 m3 Material: PVC coated synthetic fabric Number of external doors: 3 Number of internal doors: 4 Number of rooms: 5 Height of external std. door opening: 2150 mm Width of external std. door opening: 1880 mm Number of windows: 6 Number of air ducts: 2 Number of service openings 4 External colour: Olive green Internal colour: Light green Weight when packed: 240 kg (including box and pallet 43 kg) Volume when packed: L = 1,4 m; B = 1,1 m; H = 1,0 m 2.5 Air pressure fan Motor: Electric, 1-phase Power: 900 W, max Voltage: 230 V / 50 Hz alt. 110 V / 60 Hz Fan: 2-step, high pressure fan, direct drive Air flow: 15 l / sec, max Pressure: 18 kPa (1800 mmwg), max Electrical cable: RDOE alt. REOM 3 x 1,5 m2, length 15 m Air hose: Corrugated reinforced rubber hose, length 1,4 m Diameter: 38 mm

  • Trelleborg Protective Products AB 1102 7 Subject to change without notice

    Hose connection: Bitter Nr SB 9381 Dimensions: 547 x 262 x 386 mm Packing: Wooden box Weight: Approx.18 kg, packing included 2.6 TrellTent 3/2 inner ground sheet Length: 7190 mm Width: 4940 mm Weight: Approx. 30 kg Material: PVC coated synthetic fabric 2.7 TrellTent 3/4 inner ground sheet Length: 7190 mm Width: 4940 mm Weight: Approx. 30 kg Material: PVC coated synthetic fabric 2.8 TrellTent 6/2 HD inner ground sheet Length: 16940 mm Width: 6500 mm Weight: Approx. 73 kg Material: PVC coated synthetic fabric 2.9 TrellTent TFA inner ground sheet Length: 3730 mm 1 pce, 2450 mm 4 pcs Width: 4900 mm 1 pce, 2250 mm 4 pcs Weight: Approx. 27 kg totally Material: PVC coated synthetic fabric 2.10 TrellTent 3/2 AC Channel Number: 1 pce / tent Material: Polyurethane coated synthetic fabric 2.11 TrellTent 3/4 AC Channel Number: 2 pcs / tent Material: Polyurethane coated synthetic fabric 2.12 TrellTent 6/2 HD AC Channel Number: 2 pcs / tent Material: Polyurethane coated synthetic fabric

  • Trelleborg Protective Products AB 1102 8 Subject to change without notice

    2.13 TrellTent TFA AC Channel Number: 1 pce / tent Material: Polyurethane coated synthetic fabric 2.14 Tent pegs Material: Steel Length: 450 mm 2.15 Guy ropes Material: Polypropylene Colour: Black 2.16 Foot pump Material: Fibreglass reinforced polyamide, coated fabric Capacity: 6,5 l Hose length: 1,5 m Hose colour: Black 3. HANDLING 3.1 General information The ribs can be inflated either with the electrical fan, the foot pump or with air from BA bottles. The fan gives the correct pressure, 18 kPa. When using the foot pump, care should be taken that the recommended pressure is not exceeded. With BA bottles, an over pressure valve should be used. The tent pegs can be used also on asphalt, if necessary. Usage of the Air distribution channels is recommended, in order to spread the incoming air evenly. Door seals are to be used when the tents are put under pressure. Two types of seals are available for closed side door and for opened door. In order to keep the tent free from dirt, it is recommended that the inner ground sheets are removed before the tent is dismantled.

  • Trelleborg Protective Products AB 1102 9 Subject to change without notice

    3.2 Erecting tent 3/2, 3/4 and TFA If the tent is to be used for medical purposes, maximum cleanliness must be observed during handling. The tent is packed in tarpaulin as shown in the figure below.

    Place the packed tent where it is to be erected. Check the condition of the ground surface. Open the tarpaulin. Fold in one flap.

    Roll the tent off and remove the tarpaulin. Unroll and unfold the tent. If the tent is to be camouflaged or if a C-fly or a sun net is to be used, place this over the tent before inflating the ribs. Fasten the guy ropes.

  • Trelleborg Protective Products AB 1102 10 Subject to change without notice

    Close the non-return valves.

    Attach the air pressure fan to the valve on one of the ribs. Inflate.

    If the tent is inflated for the first time, the valve should be tightened with air in the ribs in order to avoid leakage. Please see sticker on the valve.

  • Trelleborg Protective Products AB 1102 11 Subject to change without notice

    Lift the ribs from the inside during inflation. Check that the inner tube is correct positioned i.e. not twisted and not folded at the ends, in order to avoid burst of the inner tubes. Avoid bringing in dirt, especially before the inner ground sheet is in place. Fit the spacing collars into place as the other ribs are inflated. Press in the spacing collars between the upper black loop fasteners (about 2 m above the floor) on the sides of the ribs. On the TFA tent special care should be taken that the reinforcements on the inner walls, which correspond to the loop fasteners, are placed over the loop fasteners.

    Place the inner ground sheet with the patterned side facing up. Top off each rib and put on the valve covers. Brace and anchor the tent with the guy ropes and the tent pegs.

    When the tent is put under pressure, make sure that it is well anchored to the ground. Use the special seals at the doors in order to minimise the air outlet. Inner ground sheets should always be used together with the seals. The flaps on the lower part of the doors, which are normally turned outwards, should now be turned inwards. The pressure in the tent must not exceed 11 mm water gauge.

  • Trelleborg Protective Products AB 1102 12 Subject to change without notice

    In the TFA tent each internal short wall is equipped with an adjustable opening with a hatch. For optimal ventilation, the hatch should be kept fully open. 3.3 Erecting TrellTent 6/2 HD In general, follow the steps under 3.1. The tent consists of two parts, which are connected by means of spring-hooks and Velcro tape flaps. Follow the same procedure for the HD tent as for the standard tent until the step "Close the non-return valves " (page 10). Then move the two sections together and fasten the spring hooks. Close the Velcro tape flaps. Inflate to some 50 % of the full pressure in all ribs, except for the two centre ribs (the reason for this is to enable to reach to the top to fasten the centre collar). Fasten the spacing collars. Note that the centre collars are secured to the upper grey loop fasteners by means of pegs. Open a part of the Velcro flap to reach the valve. Inflate the two centre ribs to full pressure. Then inflate the other ribs to full pressure. When the tent is put under pressure, make sure that it is well anchored to the ground. On the outer side of each rib, a D-ring is placed, which is to be used in case of need for extra fixation to the ground. Use the special seals at the doors in order to minimise the air outlet. Inner ground sheets should always be used together with the seals. The flaps on the lower part of the doors, which are normally turned outwards, should now be turned inwards. The pressure in the tents must not exceed 11 mm water gauge. 3.4 Connection alternative Once the tents are erected they can easily be moved and connected to each other. Use the handles on the ground flap. The tents are equipped with both grommets and grommet clamps around the doors at the end-walls, which permits several connection alternatives.

  • Trelleborg Protective Products AB 1102 13 Subject to change without notice

    The tents must be placed close enough, in order for the grommet clamps on one tent to be inserted into the grommets on the other tent.

    Fasten the clamps using the connection rope. Finish the clamping with a knot. Connecting end-wall to end-wall using connection section A connection section is primarily used when ground conditions do not allow connection directly end-wall to end-wall.

  • Trelleborg Protective Products AB 1102 14 Subject to change without notice

    Connecting connection tent end-wall to side-wall

    The surplus lining on the side-walls of the connection tent is folded-in and fixed with bands and D-rings. Release this surplus lining and attach it to the surplus lining round the gable door.

  • Trelleborg Protective Products AB 1102 15 Subject to change without notice

    3.5 Description of specific parts The doors shall be rolled up and fixed with rope loops and pegs.

    The rope loops and the pegs serve as an alternative to the door zippers.

    The window flaps are fixed in open position by Velcro strips.

    Place the air heating unit or AC unit close to the air intake, which is to be used. (The other air intakes are then used for ventilation or in a closed position.) Insert the hose into the air intake and fasten by pulling and tying the drawstring. The hose should protrude about 15 cm through the tent roof.

  • Trelleborg Protective Products AB 1102 16 Subject to change without notice

    Fit the distribution channel, starting at the end-wall rib where the air heating or AC unit hose has been inserted. Fasten the centre of the air distribution channel (marked with a black arrow) at the top of the end-wall rib (turn the arrow so it can be seen). Fasten the channel to the rest of the ribs in the black loop fasteners by using S-hooks. The channel should be stretched. The sketch shows channels for heating.

  • Trelleborg Protective Products AB 1102 17 Subject to change without notice

    Draw the connecting end of the AC channel over the hose from the AC unit and pull and tie the drawstring. Close the end, which is not used, by pulling and tying the drawstring. Check that it is tightly sealed.

    Plastic chains for suspending intravenous drip bottles and the like can be mounted in the white loop fasteners by means of the S-hooks. On the outside of each rib there is a spring-loaded non-return valve. The valve is usually opened when the tent is packed. Close the valve before inflating by depressing the button in the middle of the valve and turning it clockwise. The non-return valve is closed when the button is in level with the upper edge of the valve. Important! In case of a temperature change of 20C the valve must be opened for 10 seconds, then connect the blower again and inflate again using the Blower-K 180.

    The hose of the air pressure fan is equipped with a bayonet attachment, which fits the valve on the rib. The fan cannot supply air pressure exceeding the permitted limit (18 kPa).

  • Trelleborg Protective Products AB 1102 18 Subject to change without notice

    Service openings (2 in each end-wall) are available for insertion of water hoses, electricity cables etc.

    3.6 Dismantling Remove all equipment from the tent. Make sure that all window flaps are closed. Clean the inner ground sheet, fold it and remove it from the tent. Avoid bringing dirt into the tent after this is done. Remove all tent pegs and guy ropes. Loosen all connections that join the tents. Remove the protective covers and open the inflation valves. Do this by depressing the button in the centre of the valve with your thumb and turning the button counter clockwise. Remove the spacing collars. Leave the doors open to let all air out of the tent. Let the air in the ribs flow out for about 5 minutes. 3.7 Packing

    Roll the tent towards the valves in order to press out all remaining air and then roll the tent back. Close the valves. Avoid stepping on the tent cloth. Fold the tent lengthways from both sides towards the centre. Start with the side-wall without a valve.

  • Trelleborg Protective Products AB 1102 19 Subject to change without notice

    Fold the tent lengthways again.

    Place the tarpaulin on the ground. Roll the tent together towards one of the short sides and onto the tarpaulin. Put the inner ground sheet on top. Fold the flaps over and tighten with the rope.

  • Trelleborg Protective Products AB 1102 20 Subject to change without notice

    4. MAINTENANCE / REPAIR 4.1 Cleaning Clean the tent with a solution of water and a synthetic cleanser, such as liquid soap or a detergent. Remove stains of oil or tar with a rag dipped in kerosene. IMPORTANT! The tent should be completely dry before packing. 4.2 Repair general Use Bostik 1818 with 5 % hardener 1-7869 for tent fabric, floor fabric, window fabric and inner tubes of polyurethane. For inner tubes of butyl rubber, a rubber based glue such as Viktoria from Kienzle or art no 5050055 from Tip Top should be used. 4.3 Repair of tent, floor and window fabric 4.3.1 Repair of minor holes and tears Follow the repair instructions below for minor holes and tears (max. 15 cm). a) The repair should be made at room temperature. b) Make sure that the part to be repaired is clean and completely dry. c) Slightly dampen a rag with acetone or industrial petrol and wash the part to be repaired. Engine petrol must not be used. d) Apply the glue to both the repair patch and the cloth. e) Allow to dry until the surfaces are no longer sticky, then press together. f) Allow to dry for a few hours before exposing the repaired part to any stress. 4.3.2 Repair of major holes and tears Major holes and tears up to 50 cm can be repaired by gluing but should be repaired at a workshop for best result. 4.3.3 Repair of large holes and tears Large holes and tears should be repaired by HF-welding in a workshop. 4.4 Repair of rib casing If a rib is damaged, a repair casing can be used for temporary repairs according to the instructions below. NOTE: A permanent repair should be done by HF-welding at a workshop. a) The repair should be made at room temperature. b) Remove the inner tube. c) Place the repair casing on the inside, adjacent to the damaged area. Glue into place if necessary. d) Fit the tube as described in Replacement of inner tubes below. 4.5 Repair of polyurethane inner tubes Urgent repairs can be done according to the instructions below. IMPORTANT! Keep hands free from oil and grease. a) Round off ends of the tear. b) Abrade an area, slightly larger than the patch to be used, around the damaged area with sandpaper, a rasp or nap-liquid. c) Apply a thin layer of glue with hardener or another polyurethane based glue to both surfaces. d) Let dry until the solvent has evaporated, i.e. when the adhesive no longer sticks to the finger but is still tacky. Drying time depends on temperature (normally 3-6 min). e) Apply the patch over the damaged area. Press firmly into place with the thumb working from centre outwards.

  • Trelleborg Protective Products AB 1102 21 Subject to change without notice

    67

    5

    3

    21

    2

    Valve

    f) Press the surfaces firmly together with a hand roller. Work from centre outwards in order to press out any air. Please also refer to the instructions given on the glue packing. 4.6 Replacement of inner tubes Remove the damaged inner tube. A separate rib can be temporarily installed during the replacement. 1) Remove the valve from the damaged inner tube and install it on the new tube as follows: a) Unscrew the valve-nut (6) fig.1, and the washer (5) fig.1. b) Pull up the inner tube cover in order to make the valve opening in the PU tube visible. c) Press the valve house (1) fig.1, through the opening in the PU tube (3) fig.1. d) Place the valve house (1) fig.1, in the protection-cover (2) fig.1 and fig. 2., found inside the new PU tube. e) Pull down and straighten the inner tube cover. Place the valve into the PVC reinforced valve-hole in the sleeve. f) Screw the valve-nut, (6) fig.1, on to the valve house. Do not mount the washer (5) fig.1.

    Fig. 1 Fig. 2 2) Fold the tube twice length-wise over the valve. See sketch fig. 3 below. Fig. 3

  • Trelleborg Protective Products AB 1102 22 Subject to change without notice

    4

    3 2

    1Openings

    Valve

    3) Insert the inner tube, starting at the end with the valve, through opening 3, fig. 4, and push it towards the valve-hole in the casing. Push and pull the other end of the inner tube towards the other side by means of openings 2 and 1. Fig. 4 2) Look through the openings to make sure that the inner tube is not twisted. Unscrew the valve-nut (6) fig.1, and place the valve house through the opening in the tent. 3) Mount the washer (5) fig.1, and replace the valve-nut on the outside. NOTE: Do not tighten the valve-nut yet! 4) Push the inner tube in the bottom ends of the casing and make sure that the tube goes all the way down to the floor of the casing. IMPORTANT! If the inner tube does not have support from the casing all the way down to the bottom, the inner tube may explode. 8) Fill the rib to the half and tighten the valve-nut with the valve spanner. 9) Check that: - the inner tube is correctly placed without any twists - the inner tube fills the casing completely - there are no wrinkles or settlings on the rib If any of the above problems occur, let the air out and adjust the inner tube. IMPORTANT! If the inner tube is twisted or wrinkled, it may explode. 10) When you are satisfied with the result, fill the inner tube completely. 11) Tighten the valve with the valve spanner. 12) Check that there is no leakage around the valve by using soap water. If a leak occurs, check for wrinkles around the valve and tighten again with the valve spanner. 4.7 Immediate action chart for leaks Valve not screwed tightly Inflate the inner tube to maximum pressure and tighten the nut with the valve spanner. Dirt in the valve Remove dirt by pressing the button in the non-return valve a few times. Damaged rubber membrane in the valve Erect an extra rib from the repair kit. Release the air from the rib with the faulty valve. Remove the nut and the washer on the outside of the tent. Open the hatch that is placed closest to the valve on the rib. Pull out a part of the inner tube and replace the valve.

  • Trelleborg Protective Products AB 1102 23 Subject to change without notice

    The valve's flanges have slipped out of the inner tube Erect an extra rib from the repair kit. Release the air from the tent rib. Loosen the nut on the valve. Replace the valve in correct position and screw it into place. Inflate the rib. Tighten the nut on the valve. Minor hole in the tube Erect an extra rib. Open the hatches and remove the valve. Pull out the inner tube through the opening on the opposite side from the valve in order to let remaining air pass through the valve opening. When repairing, follow the instructions in the repair kit for inner tubes. Fit the inner tube as described in Replacement of inner tubes above. Major hole in the tube Proceed as stated above where relevant. Also replace the inner tube as described above. 4.8 Replacement of door zipper Replacement of the door zipper is to be performed by Trelleborg Protective Products AB. If a zipper is broken, the door can be closed temporarily with the pegs and the rope loops. 4.9 Repair of grommets An oval grommet can be repaired easily by placing a new grommet on the reverse side of the broken one. Repairs should take place at room temperature. a) Make sure that the surface of the cloth, where the grommet is to be placed, is clean and completely dry. b) Slightly dampen a rag with acetone or industrial petrol. Wash the part to be repaired and the grommet. Do not use engine petrol. c) Apply Bostik 1818 with hardener to both the grommet and the cloth. d) Allow to dry until the surfaces are no longer sticky, and then press together. e) Allow to dry for a few hours before exposing the grommet to stress. If the damaged grommet has to be removed, do so by loosening one edge of the grommet with a knife. Then pull off the grommet using pliers. Be careful to avoid damaging the fabric. a) Make sure that the surface of the cloth, where the grommet is to be placed, is clean and completely dry. b) Slightly dampen a rag with acetone or industrial petrol. Wash the part to be repaired and the grommet. Do not use engine petrol. c) Apply Bostik 1818 with hardener to the fabric. Allow to dry. Repeat three times. Apply the glue to the grommet and allow to dry. d) Press together. e) Allow to dry for a few hours before exposing the grommet to stress. 4.10 Repair of grommet clamp and loop fastener Repairs should take place at room temperature. a) Remove the damaged part by loosening one edge with a knife. Remove the damaged part using pliers. Be careful to avoid damaging the cloth. b) Make sure that the surface of the fabric, where the spare part is to be fitted, is clean and completely dry. c) Slightly dampen a rag with acetone or industrial petrol. Wash the tent part to be repaired and the spare part. Do not use engine petrol. d) Apply Bostik 1818 with hardener to the fabric. Allow to dry. Repeat three times. Apply the glue to the spare part and allow to dry. e) Press together.

  • Trelleborg Protective Products AB 1102 24 Subject to change without notice

    f) If the loop fastener is to be glued onto an inflated rib, it must first either be heated with hot air or heated carefully above an open flame in order to bend it into the shape of the rib. Apply the glue and allow to dry. g) Allow to dry for a few hours before exposing to stress. 4.11 Submitting for storage Erect the inflatable components. Examine. Be especially observant of any holes, rips, tears and leaks in the inner tubes (leave the tent inflated for 3-4 hours when checking). Examine the connection sections. Clean as described in "Cleaning" above. Repair as described in Repair above. Check that all equipment is present in accordance with the equipment and accessory lists. Close the non-return valves on the ribs. 4.12 Storage The valve springs shall not be subjected to pressure during long-term storage. Tents should be stored separately on shelves.

    1. GENERALThe standard TrellTent systemRibsSpacing collarsDoorsWindowsConnectionsSupport1.1 TrellTent 3/21.2 TrellTent 3/41.3 TrellTent 6/2 HD1.4 TrellTent TFA1.5 Air pressure fan

    2. TECHNICAL INFORMATION2.1 TrellTent 3/22.2 TrellTent 3/42.3 TrellTent 6/2 HD2.4 TrellTent TFA2.5 Air pressure fan2.6 TrellTent 3/2 inner ground sheet2.7 TrellTent 3/4 inner ground sheet2.8 TrellTent 6/2 HD inner ground sheet2.9 TrellTent TFA inner ground sheet2.10 TrellTent 3/2 AC Channel2.11 TrellTent 3/4 AC Channel2.12 TrellTent 6/2 HD AC Channel2.13 TrellTent TFA AC Channel2.14 Tent pegs2.15 Guy ropes2.16 Foot pump

    3. HANDLING3.1 General information3.2 Erecting tent 3/2, 3/4 and TFA3.3 Erecting TrellTent 6/2 HD3.4 Connection alternative3.5 Description of specific parts3.6 Dismantling3.7 Packing

    4. MAINTENANCE / REPAIR4.1 Cleaning4.2 Repair general4.3 Repair of tent, floor and window fabric4.3.1 Repair of minor holes and tears4.3.2 Repair of major holes and tears4.3.3 Repair of large holes and tears

    4.4 Repair of rib casing4.5 Repair of polyurethane inner tubes4.6 Replacement of inner tubesFig. 1 Fig. 2Fig. 3Fig. 4

    4.7 Immediate action chart for leaks4.8 Replacement of door zipper4.9 Repair of grommets4.10 Repair of grommet clamp and loop fastener4.11 Submitting for storage4.12 Storage