01fire rated

Upload: jrvaughn

Post on 07-Apr-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 01fire Rated

    1/22

    H57573 12/05 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 1 of 22

    This section provides an overview of general circuit design considerations and installation

    guidelines for Pyrotenax

    and Raychem

    Fire-Rated Cables. For additional information,

    contact your Tyco Thermal Controls representative or phone Tyco Thermal Controls at

    (800) 545-6258. Also, visit our web site at www.tycothermal.com.

    Contents

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    Typical Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    Pyrotenax System 1850 Fire-Rated Mineral Insulated Cable . . . . . . . . . . . . . . . . . . . . 3

    Cable construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Raychem RHW and Raychem MC Fire-Rated Polymer Insulated Cable . . . . . . . . . . . . . 4

    Raychem RHW Cable Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Raychem MC Cable construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Raychem CI Fire-Rated Polymer Insulated Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Cable construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Approvals and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Pyrotenax System 1850 MI cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Raychem RHW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Raychem MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Raychem CI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Outside North America. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Fire Alarm Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Pyrotenax System 1850 and Raychem CI Fire Alarm Circuit Design Considerations. . . . 8

    Cable sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Equipment bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Cable termination and splices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Supporting fire alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Seismic considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Terminating fire alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Connecting fire alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Critical Power Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Circuit Design Considerations Pyrotenax System 1850 . . . . . . . . . . . . . . . . . . . . . . . 11

    Cable sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Equipment bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Short circuit capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Expansion and vibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Corrosion and MI cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Cable termination and splices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Typical system installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Fire-Rated Fire Alarm and

    Power Cables

  • 8/3/2019 01fire Rated

    2/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    2 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    Supporting System 1850 MI cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Seismic considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Cable layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Terminating System 1850 MI cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Connecting System 1850 MI cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Circuit Design Considerations Raychem RHW and MC cables . . . . . . . . . . . . . . . . . . 19

    Cable sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Equipment bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Cable termination and pull boxes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Supporting Raychem fire-rated cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Supporting Raychem RHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Terminating Raychem RHW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Connecting Raychem RHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Supporting Raychem MC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Terminating Raychem MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Connecting Raychem MC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Seismic considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Cable layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

  • 8/3/2019 01fire Rated

    3/22

    Introduction

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    3 of 22

    Introduction

    Tyco Thermal Controls Pyrotenax

    System 1850 mineral insulated (MI) wiring cables and

    Raychem

    polymer insulated cables (RHW, MC, and CI) meet the relevant requirements of

    the U.S. National Electrical Code (NEC), the National Fire Alarm Code, the Canadian Electrical

    Code (CEC), and the Canadian National Building Code for fire protection of emergency power

    feeders and fire alarm circuits. The codes stipulate that a reliable source of power is requiredto operate all critical life safety circuits necessary to provide time for a safe evacuation of

    building occupants and to allow emergency crews to effectively control the fire. Fire resis-

    tance ratings of 1-hour or 2-hours are required depending on national and local codes, the

    type of circuit, and the environment.

    Typical Applications

    Tyco Thermal Controls fire-rated wiring cables meet the most stringent requirements for

    2-hour fire rating, allowing for the highest degree of fire protection for emergency back-up

    power supply systems, emergency equipment, and fire alarm systems. In the event of a fire,

    electrical power and communication is preserved for critical life safety circuits. These critical

    circuits provide power for: Fire pumps to maintain pressure in the sprinkler system

    Firefighters elevators

    Smoke dampers and pressurization fans to maintain smoke-free areas for egress

    Smoke extraction fans

    Emergency lighting and exit signs

    Fire alarm and voice communication systems

    Typical Locations

    Typical locations requiring emergency power feeders include:

    High-rise buildings

    Hospitals and other institutions

    Historic buildings

    Tunnels and subways

    Airports, stadiums, hotels, banks, etc.

    Pyrotenax System 1850 Fire-Rated Mineral Insulated Cable

    System 1850 2-hour fire-rated MI cable offers a unique combination of dependability,

    versatility, and permanence while withstanding continuous operating temperatures as high

    as 250C (82F) and intermittent exposure temperatures as high as 1010C (1850F).

    Featuring zero smoke, zero flame spread, zero fuel contribution and up to 80% space

    savings compared to conventional conduit and wire systems, System 1850 MI cable is the

    preferred choice for many specifiers. The ease with which this tough cable can be pulled into

    difficult runs with tight corners makes it an ideal choice for many applications. System 1850

    MI cable may be installed in virtually any location: outdoors, submersed or buried with a

    protective over-jacket. The cable can be bent, twisted, or pulled, and can withstand

    mechanical abrasion while remaining fully functional.

    System 1850 MI cable is 2-hour fire-rated to UL 2196 / ULC S139-00, which utilize the ASTM

    E-119 time-temperature curve. The test requires that cables remain operational after

  • 8/3/2019 01fire Rated

    4/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    4 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    exposure to temperatures up to 1010C (1850F) for two hours followed by the full force of a

    firefighters hose stream. System 1850 MI cable passes this rigorous circuit integrity test

    without additional mechanical protection.

    CABLE CONSTRUCTION

    Pyrotenax System 1850 MI cables are manufactured using only inorganic materials, copper

    and magnesium oxide. This construction is inherently tough, yet allows the cable to be bent

    and molded to fit into tight spaces. In addition, the totally inorganic construction of

    unjacketed System 1850 MI cable allows for an environmentally clean electrical cable that

    does not burn, produce smoke, or contribute fuel when exposed to fire conditions.

    Fig. 1 System 1850 MI cable construction

    For superior corrosion protection, an optional polymer jacket is available and is suitable for

    use in temperatures as low as 40C (40F).

    CONFIGURATIONS

    System 1850 fire-rated MI cables are available in a range of sizes and conductor

    configurations for power feeders and in twisted pair configurations for fire alarm circuits.

    600 V cables are approved for power feeders; 300 V cables are approved for signal

    applications.

    Raychem RHW and Raychem MC Fire-Rated Polymer Insulated Cable

    Raychem RHW and Raychem MC are 2-hour fire-rated cables capable of withstanding expo-

    sure temperatures up to 1010C (1850F). Raychem RHW achieves its fire rating when

    installed in conduit. Raychem MC is a stand-alone fire-rated system that can be installed in

    cable tray, in conduit, or directly supported. Featuring the familiarity and ease of installation

    and termination of conventional conduit and wire systems, Raychem RHW cable is preferred

    by many installers. Single and multiconductor Raychem MC offers the benefit of single-pull

    installation and ease of pulling into locations with restricted space and runs with tight corners.

    All Raychem fire-rated cables are 2-hour fire-rated to UL 2196 and ULC S139, which utilize

    the ASTM E-119 time-temperature curve. The test requires that cables remain operational

    after exposure to temperatures up to 1010C (1850F) for two hours, followed by the full

    force of a firefighters hose stream. Raychem MC cable passes this rigorous circuit integrity

    test without additional mechanical protection.

    RAYCHEM RHW CABLE CONSTRUCTION

    Raychem RHW cables are NEC Type RHH/RHW constructed to UL 44, and CEC Type R90,

    constructed to CSA C22.2 No.38. Through unique design parameters and the use of highest

    quality materials, this cable may be installed in wet locations and provides a 2-hour fire rat-

    ing when installed in conduit. The conductor material is designed to withstand the tensile

    stresses in a vertical run and is covered with a helically applied tape fire barrier. The silicone

    insulation is a special type that provides electrical protection under fire conditions. The outer

    Solid copperconductors

    Magnesiumoxide (MgO)

    insulation

    Seamlesscopper sheath

  • 8/3/2019 01fire Rated

    5/22

    Introduction

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    5 of 22

    jacket is a cross-linked polyolefin (XLPO) that gives superior abrasion protection and has a

    low coefficient of friction for easy pulling into conduits. Both insulation and jacket are made

    from low smoke zero halogen material and meet the low toxicity index per NES 713 (Naval

    Engineering Standard 713).

    Fig. 2 Raychem RHW cable construction

    CONFIGURATIONS

    Raychem RHW fire-rated cables are available in a range of sizes in single conductorconfiguration only. This cable is 600 V rated and may be used in any application allowed by

    electrical codes for Type RHH or RHW (Type R90 in Canada). For specifications, see the

    product data sheets in the Technical Data section.

    RAYCHEM MC CABLE CONSTRUCTION

    Raychem MC cables are constructed to UL 1569 and are unique in this cable type in

    providing a 2-hour fire rating. This metal-clad cable provides fire resistance without conduit

    protection and the copper armor of Raychem MC cable meets the code requirements of the

    NEC for an equipment grounding conductor.

    For superior corrosion protection, an optional flame retardant polyvinyl chloride (PVC) or

    low smoke, zero halogen polyolefin jacket is available.

    Fig. 3 Raychem MC cable construction

    CONFIGURATIONS

    Raychem MC fire-rated cables are available in a range of single and multiconductor sizes and

    conductor configurations. For specifications, see the product data sheets in the Technical

    Data section.

    Silicone rubber insulation

    Low smoke, zero halogen

    (XLPO) jacket

    Fire barrier tape

    Annealed copper conductor

    Silicone rubber insulation

    Silicone rubber inner jacket

    Continuously welded andcorrugated copper armor

    Annealed copper conductor

  • 8/3/2019 01fire Rated

    6/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    6 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    Raychem CI Fire-Rated Polymer Insulated Cable

    Raychem CI polymeric cable is a line of fire alarm cable that is ideal for twisted pair commu-

    nication wiring and also meets the survivability requirements of NFPA 72. It is a UL Listed

    2-hour fire-rated cable requiring no conduit protection. It is also listed as a 2-hour fire-rated

    Electrical Circuit Protective System when installed within the specified protective conduit.

    CABLE CONSTRUCTION

    Raychem CI meets the requirements for FPL cables to UL 1424, NPLF cables to UL 1425,

    and FAS cables to CSA C22.2 No.208. The conductors for both shielded and unshielded

    cables are insulated with silicone rubber and twisted together to form a single pair. In the

    shielded design, the pair is wrapped with a copper/polyester tape shield and bare copper

    drain wire. In both designs, the assembly is covered with a low smoke, zero halogen polyole-

    fin jacket. The construction of Raychem CI allows the installer to strip the cable with minimal

    effort.

    Fig. 4 Raychem CI cable construction

    CONFIGURATIONS

    Raychem CI fire-resistant cable is a stand-alone 2-hour fire-rated cable, requiring no conduit

    protection to achieve the fire-rating when tested to UL 2196. However, it is also 2-hour

    fire-rated when installed in 1/2" minimum electrical metallic tubing (EMT) or rigid metal

    conduit (RMC) and is ideal for retrofit applications in existing conduit. Raychem CI is fire-

    rated with a utilization voltage of 72 V and is available in shielded and unshielded twisted pair

    configurations, 18 AWG through 12 AWG. For specifications, see the product data sheet in

    the Technical Data section.

    Approvals and Certifications

    PYROTENAX SYSTEM 1850 MI CABLE

    Pyrotenax System 1850 MI cables meet the requirements of the circuit integrity fire test,

    UL 2196 (ULC S139 in Canada), and are UL Listed and CSA Certified in North America.

    The details of this system appear in the UL and ULC Fire Resistance Directories, in the UL

    Directory as Electrical Circuit Protective System (FHIT), System No. 10, and are Factory

    Mutual (FM) 2-hour fire rated.

    Factory preterminated MI cable sets are approved for both nonhazardous locations and

    hazardous locations. For specific approval information, see the product data sheets in the

    Technical Data section.

    Copper/polyester tape shield

    Stranded copper drain wire

    Low smoke, zerohalogen polyolefin jacket

    Silicone rubber insulation

    Annealed solid copper conductor

    Low smoke, zerohalogen polyolefin jacket

    Silicone rubber insulation

    Annealed solid copper conductor

    Shielded cableUnshielded cable

  • 8/3/2019 01fire Rated

    7/22

    Introduction

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    7 of 22

    RAYCHEM RHW

    When installed in conduit as specified, Raychem RHW cables meet the requirements of the

    circuit integrity fire test, UL 2196 (ULC S139 in Canada), and are UL Listed and CSA Certified

    in North America. They are listed in the UL and ULC Fire Resistance Directories. For specific

    approval information, see the product data sheets in the Technical Data section.

    RAYCHEM MC

    Raychem MC cables meet the requirements of the circuit integrity fire test, UL 2196, and are

    UL Listed. They are listed in the UL Fire Resistance Directory. Note: 'MC' is not a CEC cable

    type. For specific approval information, see the product data sheets in the Technical Data

    section.

    RAYCHEM CI

    Raychem CI cables are UL Listed as stand-alone fire-rated cables requiring no conduit

    protection when tested to UL Standard No. 2196. However, they are also listed in the UL and

    ULC Fire Resistance Directories as fire-rated systems when provided with conduit protection.

    They are CSA Certified and UL Listed fire alarm cables, NEC Type FPL and NPLF, and CSA

    Type FAS. Cables are also UL listed as Type CL3 (Class 3 cables for remote control, signaling

    and power limited circuits). For specific approval information, see the product data sheets in

    the Technical Data section..

    OUTSIDE NORTH AMERICA

    Pyrotenax fire-rated fire alarm and power cables are also available for use outside North

    America, and are LPCB certified to BS 6387, Categories C, W, and Z, and to BS 5839-1:2002

    for standard and enhanced grades of cable. These products carry the CE Mark, and are

    approved to local standards. Contact Tyco Thermal Controls for information on our range of

    cables certified for use worldwide.

  • 8/3/2019 01fire Rated

    8/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    8 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    Fire Alarm Circuits

    Fire alarm circuits may utilize Pyrotenax System 1850 MI cables or Raychem CI polymeric

    cables. The following general guidelines relate to the design and installation of fire alarm

    circuits using either cable technology.

    Pyrotenax System 1850 and Raychem CI Fire Alarm Circuit Design Considerations

    Fire alarm systems should only be designed by professionals familiar with generally

    accepted design practices. The information provided below relates specifically to designs

    using Tyco Thermal Controls fire alarm cables and must be followed, along with all relevant

    local codes and standards, to ensure that the systems are designed properly. For additional

    information, contact your Tyco Thermal Controls representative or phone Tyco Thermal

    Controls at (800) 545-6258.

    CABLE SIZING

    Primarily data and signal communications, these circuits are low voltage and low current,

    utilizing 18 AWG through 12 AWG conductors.

    Cable sizing should be in accordance with the fire alarm system manufacturers

    recommendations.

    EQUIPMENT BONDING

    The copper sheath of System 1850 cable meets North American code requirements for an

    equipment grounding conductor.

    CABLE TERMINATION AND SPLICES

    When using Raychem CI or Pyrotenax System 1850 shielded cables, the drain wire is

    connected to the metallic foil or shield. At each junction box, the drain wires are connected

    together, but not grounded; the shield drain wire is only grounded at one point in the circuit.

    Raychem CI polymeric cable

    Special terminations are not required for Raychem CI cable. A 2-hour fire-rated slice box

    is available for use with this cable.

    System 1850 MI cable

    System 1850 MI fire alarm cables are approved as a complete system only when used

    with the appropriate Pyrotenax termination and splice kits. The use of nonapproved

    components may compromise the reliability of the system and will invalidate approvals

    and warranties.

    Fig. 5 System 1850 MI cable termination

    Brassgland

    Pot

  • 8/3/2019 01fire Rated

    9/22

    Fire Alarm Circuits

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    9 of 22

    Fig. 6 Typical fire alarm system

    Installation Guidelines

    These installation guidelines apply to Pyrotenax System 1850 MI and Raychem CI polymericcables only. When installing a system, refer to the requirements in the UL/ULC Fire Resis-

    tance Directory and the appropriate System 1850 or Raychem CI data sheets and installation

    instructions (available via the Tyco Thermal Controls web site at www.tycothermal.com).

    SUPPORTING FIRE ALARM CABLE

    It is important that all support components are made of appropriate materials, such as copper,

    steel, stainless steel, and concrete. Materials such as aluminum, brass, plastic, lead, wood,

    etc. are not acceptable.

    Raychem CI polymeric cable

    In fire alarm applications, Raychem CI may be installed without conduit protection, pro-

    vided that it is mounted on noncombustible surfaces such as concrete or masonry, or

    supported by steel hangers from these surfaces. It may also be installed in 1/2" minimum

    EMT, with steel set-screw fittings, or 1/2" RMC. Conduit supports must be spaced 48" on

    center.

    System 1850 MI cable

    System 1850 MI cables may be directly mounted on noncombustible surfaces such as

    concrete or masonry, or supported by steel rod and channel (trapeze) systems.

    Tyco Thermal Controls and UL/ULC listing requirements for fire-rated cables stipulate

    support spacing at certain intervals; refer to the installation instructions shipped with the

    product and available via the Tyco Thermal Controls web site, www.tycothermal.com.

    Emergencysplitter

    Transferswitch

    CPU

    Security console(Central alarm control facility)

    Basement

    BasementGround

    1st floor

    2ndfloor

    3rdfloor

    4thfloor

    5thfloor

    6thfloor

    7thfloor

    8thfloor

    9thfloor

    nthfloor

    Data-gathering panels

    First device on each floor(Pull station, horn, speaker, strobe)

    Other devices

    Roof

    Fire-ratedcable

  • 8/3/2019 01fire Rated

    10/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    10 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    Fig. 7 Typical fire alarm installations for System 1850 MI cable

    SEISMIC CONSIDERATIONS

    In areas where the risk of seismic activity is high, precautions must be taken where Tyco

    Thermal Controls fire-rated cables cross expansion joints and at termination points.

    For more information, see Appendix D.

    TERMINATING FIRE ALARM CABLE

    Raychem CI polymeric cable

    Raychem CI cables are terminated in the same manner as conventional cable and do not

    require special terminations. When terminating shielded cable, the shield is exposed by

    stripping back the outer jacket, then removed and discarded. The shield drain wire is in

    direct contact with the shield throughout the cable, and is used to preserve shield conti-

    nuity at termination and splice points. The drain wire is joined at intermediate splice

    points, but not bonded to ground; single point grounding dictates that it be bonded toground only at one end of a complete circuit.

    Pyrotenax System 1850 MI cable

    Details on terminating Pyrotenax System 1850 MI cables can be found in the installation

    instructions provided with each System 1850 MI fire alarm cable termination kit. Factory

    preterminated System 1850 MI cable sets are available. For details on preterminated

    cable sets, contact your Tyco Thermal Controls representative or phone Tyco

    Thermal Controls at (800) 545-6258.

    CONNECTING FIRE ALARM CABLE

    Raychem CI polymeric cable

    For Raychem CI cable installed in EMT, use only steel set-screw connectors or an all-steel

    compression bushing for coupling the EMT, and for the EMT connection to the enclosure.Zinc or other materials are not acceptable.

    Pyrotenax System 1850 MI cable

    For Pyrotenax System 1850 MI cables, the termination gland is a brass fitting available in

    1/2" and 3/4" NPT sizes, depending on the cable diameter.

    Fig. 8 Brass gland

    Trapeze Method Direct Mounting Method

    Steelrod

    Steelchannel

    Twisted paircables

    Noncombustiblematerial

    Twisted paircables

  • 8/3/2019 01fire Rated

    11/22

    Critical Power Circuits

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    11 of 22

    Gland size information for each specific cable is available from the product data sheets in the

    Technical Data section. When tightened with the recommended torque, this gland simulta-

    neously seals the enclosure and grips the cable through a brass compression sleeve. This

    connection, when installed according to the installation instructions, provides the following

    benefits:

    Hydrostatic withstand pressure up to 6000 lbs/sq in (4.22 kg/sq mm)

    Pull-off force, when tightened to torque settings, as shown in Table 1

    Critical Power Circuits

    Critical power circuits utilize Pyrotenax and Raychem cables. The following general

    guidelines relate to the design and installation of critical power circuits specific to both

    technologies.

    Circuit Design ConsiderationsPyrotenax System 1850

    Critical power circuit systems should only be designed by professionals familiar with gener-

    ally accepted design practices. The information provided below relates specifically to designs

    using Pyrotenax power cables and must be followed, along with all relevant local codes and

    standards, to ensure that the systems are designed properly. For further information, contact

    your Tyco Thermal Controls representative or phone Tyco Thermal Controls at (800) 545-6258.

    CABLE SIZING

    System 1850 MI cable size is based on circuit breaker size, which in turn is based on load

    calculations. Special rules apply for motors, including fire pumps, where cable size is based

    on 125% of full load current. Use the ampacity tables specified in the electrical code to

    determine the cable size. If the calculated voltage drop exceeds the specified limits, a larger

    cable size must be chosen.

    Multiconductor MI cables have the same ampacity ratings as multiconductor polymeric cable

    types. However, the NEC allows full free air ampacity for unjacketed single conductor MI

    cables configured according to Fig. 9 as long as a space of 2.15 cable diameters is

    maintained between bundles.

    In Canada, cable size is determined in accordance with Sections 4 and 8 of the CEC.

    Table 1 Pull-Off Force for Torque Settings

    Gland size (NPT) (in) Recommended torque (lbs-ft) Pull-off force (lbs)

    1/2 25 175

    3/4 42 200

  • 8/3/2019 01fire Rated

    12/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    12 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    Fig. 9 Spacing of bundled conductors

    Although unjacketed single conductor MI cable is unaffected by any temperature increase

    resulting under the installation conditions shown in Fig. 9, the termination may need to be

    sized-up to keep it within its temperature limits in accordance with electrical code require-

    ments. Refer to the installation instructions shipped with the product for details on sizing

    terminations.

    VOLTAGE DROP

    Voltage drop calculations are based on calculated load, not circuit breaker rating.

    For conventional cables, simple formulas are used to determine if the cable size listed in the

    ampacity tables meets the required voltage drop limits. While these formulas can be applied

    to System 1850 MI cable, voltage drop values specific to the characteristics of MI cable can

    be calculated using any of the following:

    An equation based on the run length, the conductor current, and the circuit voltage is

    provided in Appendix B

    A quick voltage drop calculator is available via the Tyco Thermal Controls web site,

    www.tycothermal.com Pyrosizer MI cable sizing software is available via the Tyco Thermal Controls web site,

    www.tycothermal.com, or through your Tyco Thermal Controls representative

    EQUIPMENT BONDING

    The copper sheath of System 1850 MI cables meets North American code requirements for

    the equipment grounding conductor. The brass gland completes the grounding path from the

    cable sheath to the equipment. For single conductor cables, the ground path includes a non-

    ferrous brass plate, as shown in Fig. 10 (in Canada, brass plates are required only for ampac-

    ities over 200 A).

    Spacing (S) betweenmultiphase paralleledsingle conductor cables(see Fig. 1.16)

    (S)

    (S)

    MulticonductorMI cable

    SingleconductorMI cables

  • 8/3/2019 01fire Rated

    13/22

    Critical Power Circuits

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    13 of 22

    .

    Fig. 10 Equipment bonding using brass plate

    SHORT CIRCUIT CAPABILITY

    The following graphs give the maximum allowable short circuit currents for System 1850 MI

    cables. The first is based on the cable only. The cable will survive if the short circuit currents

    shown are not exceeded; however, the terminations could be damaged. The second graph

    provides the maximum short circuit current to avoid damage to terminations. The cable

    system will tolerate short circuit currents up to this magnitude and survive undamaged.

    Fig. 11 Short circuit currents

    MulticonductorMI cable

    Brass glandBrass plate

    Enclosure wall

    Lock washer

    Details of brass plate

    Steel enclosure cutout(steel must be removed)

    Lock washer

    Single conductorMI cables

    Lock washers

    10

    100

    1000

    Conductor Size

    18

    14

    16

    12

    10

    8 6 4 3 2 1 1 /0

    2/0

    3/0

    4/0

    250kcmil

    350kcmil

    500kcmil

    ConductorCurrent

    ThousandsofAmps

    0.1

    1

    0.1

    1

    10

    100

    1000

    Conductor Size

    1 cycle

    2 cycles

    4 cycles

    8 cycles

    16 cycles30 cycles

    60 cycles90 cycles

    18

    14

    16

    12

    10

    8 6 4 3 2 1 1 /0

    2/0

    3/0

    4/0

    250kcmil

    350kcmil

    500kcmil

    ConductorCurrent

    ThousandsofAmps

    1 cycle

    2 cycles

    4 cycles

    8 cycles

    16 cycles

    30 cycles60 cycles90 cycles

    Maximum short circuit currentsfor Pyrotenax MI cablesexcluding terminations

    Maximum short circuit currentsfor Pyrotenax MI cables

    to avoid damage to terminations

  • 8/3/2019 01fire Rated

    14/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    14 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    EXPANSION AND VIBRATION

    In certain circumstances it may be necessary to take precautions to prevent mechanical

    damage to System 1850 MI cable. See Appendix D for details.

    CORROSION AND MI CABLE

    In most applications, System 1850 MI cables can be used without any additional protection

    against corrosion. However, in applications where the cable may be exposed to corrosives,

    such as when the cable is directly buried or embedded in concrete, additional protection in

    the form of a polymer jacket is required. Refer to Appendix E for more information on corro-

    sion and MI cable.

    CABLE TERMINATION AND SPLICES

    System 1850 MI cables are approved as a complete system only when used with the appro-

    priate Pyrotenax termination and splice kits. The use of nonapproved components will com-

    promise the reliability of the system and will invalidate approvals and warranties.

    Two types of termination kits are available: Pyropak kits for all single and multiconductor

    cables, and Quickterm kits for #6 AWG and larger single conductor cables. The Quickterm

    kits include a special connector to splice the solid MI conductor to a flexible tail (flexible tail

    not supplied).

    Factory preterminated System 1850 MI cable sets are available in a range of sizes and lengths.

    For details on preterminated cable sets, contact your Tyco Thermal Controls representative

    or phone Tyco Thermal Controls at (800) 545-6258.

    Fig. 12 Terminations for System 1850 MI cable

    In cases where the manufactured length is shorter than the required run length, a splice is

    used to join individual lengths of cable. Two options for splicing System 1850 MI cable are

    available:

    Factory fire-rated splice:

    A UL/ULC 2-hour fire-rated, all-welded joint is installed at thefactory.

    Field-installed fire-rated splice:

    A field-installed fire-rated splice, consisting of a splice kit

    and a separate field fire protection kit, is used to extend cable length.

    Cap andsleeveassemblies

    Self-sealingtape

    Brassglands

    Heat-shrinkablesleeving

    Brassglands

    Sealingcompound

    Crimpconnectors

    Brasspots

    Pyropak Quickterm

  • 8/3/2019 01fire Rated

    15/22

    Critical Power Circuits

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    15 of 22

    Fig. 13 Splices for System 1850 MI cable

    TYPICAL SYSTEM INSTALLATION

    A typical critical power circuit installation utilizing System 1850 MI cable is shown in Fig. 14.

    Additionally, components and accessories available for single and multiconductor MI cablesare shown in Table 2. For further information on components and accessories, see the prod-

    uct data sheet in the Technical Data section.

    Fig. 14 Typical System 1850 power circuit system

    Factory splice

    Field-installed splice

    Emergencysplitter

    Emergencysplitter

    Splice

    Generator

    GFire

    pump

    Transferswitch

    Mainelectrical

    switchgear

    Transferswitch

    Flexibletails

    Quickterm

    Brassplate

    Gearclamp

    Clamp

    System 1850 fire-rated MI cable

    Table 2 Component and Accessory Availability

    Catalog number Single conductor MI Multiconductor MI

    Pyropak

    Quickterm

    Field and factory splices

    Brass plates

  • 8/3/2019 01fire Rated

    16/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    16 of 22

    Tyco Thermal Controls

    www.tycothermal.com (800) 545-6258

    H57573 12/05

    Installation Guidelines

    These installation guidelines apply to System 1850 MI cables only. When installing a system,

    refer to the requirements in the UL/ ULC Fire Resistance Directory and appropriate System

    1850 data manuals and installation instructions shipped with the product, and available via

    the Tyco Thermal Controls web site at www.tycothermal.com. Refer to national and local

    electrical codes for additional details. For further information, contact your Tyco ThermalControls representative or phone Tyco Thermal Controls at (800) 545-6258.

    SUPPORTING SYSTEM 1850 MI CABLE

    It is important that all support components are made of appropriate materials, such as copper,

    steel, stainless steel, and concrete. Materials such as aluminum, brass, plastic, lead, wood,

    etc. are not acceptable.

    System 1850 MI cable may be directly mounted on noncombustible surfaces such as

    concrete or masonry, or supported by steel rod and channel (trapeze) systems. To achieve

    free air rating, spacing must be maintained between the cable bundles and also between the

    bundles and the mounting surface; refer to Fig. 15. Tyco Thermal Controls and UL/ULC

    listing requirements for fire-rated cables stipulate support spacing at certain intervals; refer

    to the installation instructions shipped with the product and available via the Tyco ThermalControls web site, www.tycothermal.com.

    System 1850 MI cable should not be installed in conduit, other than when transitioning

    through a wall, floor, or ceiling,

    Fig. 15 Supporting System 1850 MI cable

    It is important to keep the overall loading on the rod and channel system within limits.

    Table 3 shows the recommended loading guidelines based on the minimum channel depth

    of 1-1/2 inch. Note that the cable load calculations as shown in Table 3 take into account

    only the load represented by the MI cable.

    Steelrod

    1-1/2" channel(to maintain NEC

    free air rating)Multiconductor

    cable

    Free air rated installation Free air rated installation Non-free air rated installation

    Singleconductor

    cables Steelchannel

    Noncombustiblematerial

    Noncombustiblematerial

    Singleconductorcables

    Table 3 Loading Guidelines

    Cable load* Support method

    Up to 150 lbs 3/8" threaded rod

    Between 150 lbs and 200 lbs 1/2" threaded rod

    Between 200 lbs and 300 lbs 1/2" threaded rod, double channel

    * Cable load = lbs/ft cable x total number of runs x 4

    Note:

    Maximum width of 1-1/2" channel: 36"

  • 8/3/2019 01fire Rated

    17/22

    Critical Power Circuits

    H57573 12/05

    (800) 545-6258 www.tycothermal.com

    Tyco Thermal Controls

    17 of 22

    SEISMIC CONSIDERATIONS

    In areas where the risk of seismic activity is high, precautions must be taken where the cable

    crosses expansion joints and at termination points. For more information, see Appendix D.

    CABLE LAYOUT

    In multiconductor cables, the magnetic effects of the phase conductors cancel each other

    out, allowing for cable installation in any configuration. However, single conductor cables

    should be bundled in groups containing one conductor from each phase to minimize the

    resulting magnetic field in each grouping. The grouped single conductor cables are then

    fastened tightly together, ensuring that the gland connectors at each end of the cable run are

    connected to the metal enclosure, either directly or through a brass plate. Typical single

    conductor cable configurations are shown in Fig. 16. The neutral conductor may be located

    within or outside the cable group.

    Fig. 16 Recommended installation configurations

    Electrical codes generally limit paralleling cable configurations to cable sizes 1/0 AWG and

    larger. The codes address the balancing of resistance by stipulating:

    All conductors must be the same length

    All conductors must be the same size and the same material

    All conductors must have the same type of insulation

    All conductors must be terminated in the same manner

    A current measurement should be taken immediately after the cables begin to carry load.

    Load imbalances between conductors of up to 10% are tolerable and expected. Deviations

    above 10% must be investigated and corrected.

    When installing single conductor cables through a ferrous enclosure, precautions must be

    taken to prevent induction heating in the steel. This is accomplished by removing a section of

    the enclosure and installing a nonferrous brass plate (in Canada, this is only required above

    200 amperes). Brass plates with pretapped holes are available for the gland connectors.

    Single circuit(preferred)

    Single circuit(alternative)

    Two cables inparallel per phase

    (preferred)

    Two cables inparallel per phase

    (alternative)

    Three or more cablesin parallel per phase

    (preferred)

    Three or more cablesin parallel per phase

    (alternative)

    Note: The spacing S between bundles, not including neutral, should be a minimum of 2.15 cable diameters in the U.S. (NEC), or 2 cable diameters in Canada (CEC).Neutral may be located as shown, or outside groups in the most convenient location.

    NAB

    NBA

    NAB

    NAB

    NAB

    NAB

    ABN

    ABN ABC ABCNBA ABCNNCBA

    ABC ABCN

    ABC BC

    AN

    S

    S

    ABN ABNS

    ABNS

    ABC ABCS

    ABCS

    ABCNS

    ABCNS

    ABCN

    ABC

    ABC

    S

    ABC

    ABC

    S ABC

    S

    BCBCANAN S

    BCBCANAN S

    BCANSS S

    Single Phase 3 Phase 3 Wire 3 Phase 4 Wire

  • 8/3/2019 01fire Rated

    18/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    18 of 22 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57573 12/05

    Fig. 17 Enclosure with cutout and brass plate

    TERMINATING SYSTEM 1850 MI CABLE

    Details on terminating System 1850 MI cables can be found in the installation instructionsprovided with each System 1850 MI cable termination kit.

    Factory preterminated System 1850 MI cable sets are available in a range of sizes and lengths.

    For details on preterminated cable sets, contact your Tyco Thermal Controls representative

    or phone Tyco Thermal Controls at (800) 545-6258.

    Fig. 18 Preterminated cable set

    CONNECTING SYSTEM 1850 MI CABLE

    The termination gland is a brass fitting available in standard NPT sizes. The glands are sup-

    plied in 1/2", 3/4", 1", or 1-1/4" sizes, depending on the cable diameter.

    Fig. 19 Brass gland

    Gland size information for each MI cable is available from the product data sheets in the

    Technical Data section. When tightened with the recommended torque, this gland simulta-

    neously seals the enclosure and grips the cable through a brass compression sleeve. This

    connection, when installed according to the installation instructions, provides the following

    benefits:

    Brassplate

  • 8/3/2019 01fire Rated

    19/22

    Critical Power Circuits

    H57573 12/05 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 19 of 22

    Hydrostatic withstand pressure up to 6000 lbs/sq in (4.22 kg/sq mm)

    Pull-off force when tightened to torque settings as shown in Table 4

    Note: Terminations are not required to be fire-rated since the emergency equipment they

    serve is in a fire-rated room.

    Circuit Design ConsiderationsRaychem RHW and MC cables

    Critical power circuit systems should only be designed by professionals familiar with

    generally accepted design practices. The information provided below relates specifically to

    designs using Raychem RHW and MC power cables and must be followed, along with allrelevant local codes and standards, to ensure that the systems are designed properly. For

    further information, contact your Tyco Thermal Controls representative or phone Tyco

    Thermal Controls at (800) 545-6258.

    CABLE SIZING

    Cable size is based on circuit breaker size, which in turn is based on load calculations.

    Special rules apply for motors, including fire pumps, where cable size is based on 125% of

    full load current. Use the ampacity tables specified in the electrical code to determine the

    cable size. If the calculated voltage drop exceeds the specified limits, a larger cable size must

    be chosen.

    Ampacity for Raychem RHW cables is based on cable in conduit rules in the NEC and CEC.

    Higher ampacity is allowed for single conductor Raychem MC, in accordance with NEC Table310.20, when bundled and configured for free air as shown in Fig.1.15 as long as a space of

    2.15 cable diameters is maintained between bundles.

    VOLTAGE DROP

    Standard voltage drop calculations apply to Raychem RHW and MC cables.

    EQUIPMENT BONDING

    Normal equipment bonding rules apply to Raychem RHW in conduit; a properly sized equip-

    ment grounding conductor is required. For further information on Raychem fire-rated

    grounding conductors, contact your Tyco Thermal Controls representative or phone Tyco

    Thermal Controls at (800) 545-6258.

    Raychem MC cables are designed so that the copper sheath meets the NEC requirement for

    an equipment grounding conductor; no separate grounding conductor is required. For single

    conductor cables, the ground path includes a nonferrous (brass) plate.

    CABLE TERMINATION AND PULL BOXES

    Raychem RHW cables are terminated in the same manner as conventional cable in conduit

    and do not require special terminations. Pullboxes are approved for use with Raychem RHW.

    Raychem MC is terminated using readily available brass fittings and simple tools. Details of

    terminating procedures can be found in the installation instructions provided with each cable

    shipment.

    Table 4 Pull-Off Force for Torque Settings

    Gland size (NPT) (in) Recommended torque (lbs-ft) Pull-off force (lbs)

    1/2 25 175

    3/4 42 200

    1 58 250

    1-1/4 75 300

  • 8/3/2019 01fire Rated

    20/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    20 of 22 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57573 12/05

    Installation Guidelines

    These installation guidelines apply to Raychem fire-rated cables only. When installing a

    system, refer to the requirements in the UL/ ULC Fire Resistance Directory and appropriate

    Raychem RHW or Raychem MC installation instructions shipped with the product and

    available via the Tyco Thermal Controls web site at www.tycothermal.com. Refer to national

    and local electrical codes for additional details. For further information, contact your TycoThermal Controls representative or phone Tyco Thermal Controls at (800) 545-6258.

    SUPPORTING RAYCHEM FIRE-RATED CABLES

    It is important that all support components are made of appropriate materials, such as

    copper, steel, stainless steel, and concrete. Materials such as aluminum, brass, plastic, lead,

    wood, etc. are not acceptable.

    SUPPORTING RAYCHEM RHW

    Raychem RHW fire-rated cable in conduit may be mounted in any environment suitable for

    conventional RHW cable in conduit. The conduit may be directly mounted on noncombusti-

    ble surfaces such as concrete or masonry, or supported by steel rod and channel (trapeze)

    systems. In a vertical run, the conductors must be supported inside the conduit in the rec-

    ommended manner described in the installation instructions shipped with the product andavailable via the Tyco Thermal Controls web site at www.tycothermal.com.

    Fig. 20 Supporting Raychem RHW cable

    It is important to keep the overall loading on the rod and channel system within limits.

    Following are the recommended loading guidelines based on a minimum channel depth of

    1-1/2 inch.

    Trapeze support Two piece clamp

    Wall or floorassembly

    (noncombustiblematerial)

    ConduitSteelchannel

    Clamp

    Conduit

    Steel channel

    Clamp

    Table 5 Loading Guidelines

    Cable load* Support method

    Up to 150 lbs 3/8" threaded rodBetween 150 lbs and 200 lbs 1/2" threaded rod

    Between 200 lbs and 300 lbs 1/2" threaded rod, double channel

    * Cable load = (lbs/ft of conduit x total number of conduits + lbs/ft cable x total number of runs) x 5

    Note: Maximum width of 1-1/2" channel: 36"

  • 8/3/2019 01fire Rated

    21/22

    Critical Power Circuits

    H57573 12/05 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 21 of 22

    TERMINATING RAYCHEM RHW

    In critical circuits, Tyco Thermal Controls requires installation of an intermediate box to

    prevent ingress of gases into critical equipment enclosures, as described in the installation

    instructions shipped with the product, and available via the Tyco Thermal Controls web site

    at www.tycothermal.com.

    CONNECTING RAYCHEM RHW

    No special accessories or tools are required for connecting Raychem RHW.

    SUPPORTING RAYCHEM MC

    Raychem MC may be directly mounted on noncombustible surfaces such as concrete or

    masonry, or supported by steel rod and channel (trapeze) systems (see Figure 1.21). Free air

    rating may be achieved when using bundled single conductor cables providing the proper

    spacing is maintained between bundles and also between bundles and the mounting surface;

    refer to Fig. 1.15. Tyco Thermal Controls and UL/ULC listing requirements for fire-rated

    cables stipulate support spacing at certain intervals; refer to the installation instructions

    shipped with the product and available via the Tyco Thermal Controls web site,

    www.tycothermal.com.

    Fig. 21 Supporting Raychem MC cable

    It is important to keep the overall loading on the rod and channel system within limits.

    Following are the recommended loading guidelines based on a minimum channel depth of

    1-1/2 inch. Note that the cable load calculat ions as shown in Table 6 take into account only

    the load represented by the MI cable.

    TERMINATING RAYCHEM MC

    In critical circuits, Tyco Thermal Controls requires installation of an intermediate box to

    prevent ingress of gases into critical equipment enclosures, as described in the installation

    instructions shipped with the product, and available via the Tyco Thermal Controls web site

    at www.tycothermal.com.

    Trapeze support Kindorf clamp Two piece clamp

    Wall or floorassembly

    (noncombustible

    material)

    Steelchannel

    Steelchannel

    Wall or floorassembly

    (noncombustible

    material)

    ClampClamp

    Armor

    Steel channel

    Clamp

    ArmorArmor

    Table 6 Loading Guidelines

    Cable load* Support method

    Up to 150 lbs 3/8" threaded rod

    Between 150 lbs and 200 lbs 1/2" threaded rod

    Between 200 lbs and 300 lbs 1/2" threaded rod, double channel* Cable load = lbs/ft cable x total number of runs x 4

    Note: Maximum width of 1-1/2" channel: 36"

  • 8/3/2019 01fire Rated

    22/22

    FIRE-RATED FIRE ALARM AND POWER CABLES

    CONNECTING RAYCHEM MC

    Removal of the copper sheath and insulation from the conductors is accomplished with stan-

    dard tools in a few simple steps. For details, refer to the installation instructions shipped with

    the product, and available via the Tyco Thermal Controls web site at www.tycothermal.com.

    SEISMIC CONSIDERATIONS

    In areas where the risk of seismic activity is high, precautions must be taken where the cable

    crosses expansion joints and at termination points. For more information, see Appendix D.

    CABLE LAYOUT

    In multiconductor cables, the magnetic effects of the phase conductors cancel each other

    out, allowing for cable installation in any configuration. However, single conductor cables

    should be bundled in groups containing one conductor from each phase to minimize the

    resulting magnetic field in each grouping. The grouped single conductor cables are then

    fastened tightly together, ensuring that the gland connectors at each end of the cable run are

    connected to the metal enclosure, either directly or through a brass plate. Typical single

    conductor cable configurations are shown in Fig. 22. The neutral conductor may be located

    within or outside the cable group.

    Fig. 22 Recommended installation configurations

    Electrical codes generally limit paralleling cable configurations to cable sizes 1/0 AWG and

    larger. The codes address the balancing of resistance by stipulating:

    All conductors must be the same length

    All conductors must be the same size and the same material

    All conductors must have the same type of insulation

    All conductors must be terminated in the same manner

    A current measurement should be taken immediately after the cables begin to carry load.

    Load imbalances between conductors of up to 10% are tolerable and expected. Deviations

    above 10% must be investigated and corrected.

    When installing single conductor cables through a ferrous enclosure, precautions must be

    taken to prevent induction heating in the steel. This is accomplished by removing a section of

    the enclosure and installing a brass plate, or by cutting slots in the enclosure between the

    cable entries.

    Single circuit(preferred)

    Single circuit(alternative)

    Two cables inparallel per phase

    (preferred)

    Two cables inparallel per phase

    (alternative)

    Three or more cablesin parallel per phase

    (preferred)

    Three or more cables

    in parallel per phase(alternative)

    Note: The spacing S between bundles, not including neutral, should be a minimum of 2.15 cable diameters in the U.S. (NEC), or 2 cable diameters in Canada (CEC).Neutral may be located as shown, or outside groups in the most convenient location.

    NAB

    NBA

    NAB

    NAB

    NAB

    NAB

    ABN

    ABN ABC ABCNBA ABCNNCBA

    ABC ABCN

    ABC BC

    AN

    S

    S

    ABN ABN

    S

    ABN

    S

    ABC ABC

    S

    ABC

    S

    ABCN

    S

    ABCN

    S

    ABCN

    ABC

    ABC

    S

    ABC

    ABC

    S ABC

    S

    BCBCANAN S

    BCBCANAN S

    BCANSS S

    Single Phase 3 Phase 3 Wire 3 Phase 4 Wire