1 Service Information Letter SIL # 014 Agastat To Siemens Timer Conversion Equipment: Agastat timer SSFR90A, Astec P/N 039998 Date Issued: 7-31-2003 Revised: no Additional Reference: none Revision #: 0 By: R. L. Worth Jr. , Service Support Coordinator Astec Service Department PURPOSE: The purpose of this letter is provide instructions for replacing an Agastat SSFR90A, universal timing relay, with a Siemens 3RP1505-1BQ30. This conversion should only be performed by qualified individuals. PARTS REQUIRED (for each replacement): Quantity Astec part number Description 1 054734 Siemens Sirius relay, Siemens item # 3RP1505-1BQ30. 1 054735 3RP1901-QB, Label GETTING STARTED: Before un-wiring and removing the Agastat timer, make sure all wires are labeled. Remove the Agastat timer from the DIN rail. Mount the Siemens in it’s place. Use your current electrical schematics to determine the current configuration you have. The terminal numbers on the new Siemens relay are identified differently than those on the Agastat. Refer to the following examples for wiring instructions. After the conversion is made it will be helpful to note the changes on your electrical schematics. The new Siemens relay will perform the same as the Agastat, once it is configured properly. Please refer to the following examples for configuration instructions. EXAMPLES: RELAY FUNCTION EXAMPLE # PAGE # ON DELAY #1 2 OFF DELAY #2 3 LATCHED #3 4 PULSE SHAPING #4 5-6 For identification of the Siemens relay components, please refer to the figure on page 7.

Upload: sghane5674

Post on 07-Apr-2015

73 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 014 Timer Conversion

1

Service Information Letter SIL # 014 Agastat To Siemens Timer

Conversion

Equipment: Agastat timer SSFR90A, Astec P/N 039998 Date Issued: 7-31-2003 Revised: no

Additional Reference:

none Revision #: 0

By: R. L. Worth Jr. , Service Support Coordinator Astec Service Department PURPOSE: The purpose of this letter is provide instructions for replacing an Agastat SSFR90A, universal timing relay, with a Siemens 3RP1505-1BQ30. This conversion should only be performed by qualified individuals. PARTS REQUIRED (for each replacement): Quantity Astec part number Description 1 054734 Siemens Sirius relay, Siemens item # 3RP1505-1BQ30. 1 054735 3RP1901-QB, Label GETTING STARTED: Before un-wiring and removing the Agastat timer, make sure all wires are labeled. Remove the Agastat timer from the DIN rail. Mount the Siemens in it’s place. Use your current electrical schematics to determine the current configuration you have. The terminal numbers on the new Siemens relay are identified differently than those on the Agastat. Refer to the following examples for wiring instructions. After the conversion is made it will be helpful to note the changes on your electrical schematics. The new Siemens relay will perform the same as the Agastat, once it is configured properly. Please refer to the following examples for configuration instructions. EXAMPLES: RELAY FUNCTION EXAMPLE # PAGE #ON DELAY #1 2 OFF DELAY #2 3 LATCHED #3 4 PULSE SHAPING #4 5-6 For identification of the Siemens relay components, please refer to the figure on page 7.

Page 2: 014 Timer Conversion

2

EXAMPLE # 1, On Delay:

For ON Delay: With power to the relay off. Set the MODE SELECTOR SWITCH to A. This configures the relay as an ON Delay. Then select the desired TIME RANGE SELECTOR to the desired time range. Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL. Turn power back on.

TR3RP1505-1BQ30 3RP1901-QB

A1 A2

15 18 TO LOAD

1 2

TRIGGER

SIEMENS (NEW STYLE TIMER)

TT

TRSSFR90A

10 9

7

1 2 TO LOAD

1 2

TRIGGER

AGASTAT (OLD STYLE TIMER)

TT

ON DELAY TIMER

ON DELAY TIMER

0 – 300 SEC. ON DELAY

Page 3: 014 Timer Conversion

3

EXAMPLE # 2, OFF Delay:

For OFF Delay: With power to the relay off. Set the MODE SELECTOR SWITCH to B. This configures the relay as an OFF Delay. Then select the desired TIME RANGE SELECTOR to the desired time range. Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL. Turn power back on for changes to take place.

AGASTAT (OLD STYLE TIMER)

TRSSFR90A

109

7

1 2 TO LOAD

1 2

TRIGGER

TT 0 – 300 SEC. OFF DELAY

OFF DELAY TIMER

TR3RP1505-1BQ30 3RP1901-QB

A1B1

A2

15 18 TO LOAD

1 2

TRIGGER

SIEMENS (NEW STYLE TIMER)

TT

OFF DELAY TIMER

0 – 300 SEC. OFF DELAY (B)

Page 4: 014 Timer Conversion

4

EXAMPLE # 3, IMPULSE OFF

For IMPULSE OFF TIMER: With power to the relay off. Set the MODE SELECTOR SWITCH to F. This configures the relay as an IMPULSE OFF TIMER. Then select the desired TIME RANGE SELECTOR to the desired time range. Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL. Turn power back on for changes to take place.

AGASTAT (OLD STYLE TIMER)

TRSSFR90A

109

7

1 2 TO LOAD

1 2

TRIGGER

TT .3 - 10 SEC. IMPULSE OFF

IMPULSE OFF TIMER

TR3RP1505-1BQ30 3RP1901-QB

A1B1

A2

15 16 TO LOAD

1 2

TRIGGER

SIEMENS (NEW STYLE TIMER)

TT

IMPULSE OFF TIMER

.3 – 10 SEC. IMPULSE OFF (F)

120 VAC

120 VAC

Page 5: 014 Timer Conversion

5

EXAMPLE # 4, LATCHED INTERVAL / PULSE SHAPING:

TR10

AGASTAT (OLD STYLE TIMER)

SSFR90A

9 7

1 2

1 2

TRIGGER

INTERVAL 45 SEC.

5 6

A SLV

TR3RP1505-1BQ30 3RP1901-QB

A1B1

A2

15 18

1 2

TRIGGER

SIEMENS (NEW STYLE TIMER)

TT 45 SEC. PULSE SHAPING (G)

25 26

A SLV

Page 6: 014 Timer Conversion

6

For PULSE SHAPING (replaces latched interval): With power to the relay off. Set the MODE SELECTOR SWITCH to G. This configures the relay for PULSE SHAPING. Then select the desired TIME RANGE SELECTOR to the desired time range. Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL. Turn power back on for changes to take place. If you have any questions please contact the Astec service department. Please refer to the following figure for a general description of the Siemens relay components.

Page 7: 014 Timer Conversion

7

Siemens relay component identification:

Astec, Inc. 2003

##

##

16NC 18NO A2-

22/26NC 24/28NO

A3+ B3+ 21/25/27C

A1 B1 15/17C

SIEMENS SIRIUS 3R

Top of Relay

Lower Level

Lower Level

AC + (Hot)

AC – (Negative)

TRIGGER COMMON TERMINAL, # 15 & 17, (for NC # 16 and NO # 18)

Power Terminalsfor use with low voltage circuits only … make no connection

COMMON TERMINAL, # 21, 25, & 17, (for NC # 22 & 26, and NO # 24 & 28)

MODE SELECTOR SWITCH (Rotary Dial and Window)

TIME RANGE SELECTOR (Rotary Dial and Window)

PERCENT OF TIME RANGE DIAL