1 03.15 IND1 256 SAN I CONDENS ® Best CDN US FR IMPORTANT DO NOT RETURN ANY MERCHANDISE TO THE VENDOR NE PAS RETOURNER DE MARCHANDISE AU VENDEUR For customer Service, Returns or Technical Questions, please call Saniflo’s Technical support toll-free at 800-571-8191 (USA) or 800-363-5874 (CDN). Pour le service client, les retours ou toute question technique, merci d’appeller le service technique de Saniflo au numéro suivant : 800-571-8191 (USA) or 800-363-5874 (CDN). The user should retain these instructions for future reference • A lire attentivement et à conserver à titre d’information This product must be installed in strict accordance whith local plumbing codes. Product should be installed by a qualified technician. Le produit doit être installé dans le respect des réglements sanitaires locaux. Le produit doit être installé par un technicien qualifié. INSTALLATION AND MAINTENANCE INSTRUCTIONS INSTRUCTIONS D’INSTALLATION ET DE MAINTENANCE

Upload: others

Post on 08-Sep-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IMPORTANTpdf.lowes.com/productdocuments/c91a039e-f20e-4387-91c5-a...SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the

103.15IND1

256

SANICONDENS ® Best

CDNUS FR

IMPORTANT

DO NOT RETURN ANY MERCHANDISE TO THE VENDOR NE PAS RETOURNER DE MARCHANDISE AU VENDEUR

For customer Service, Returns or Technical Questions, please call Saniflo’s Technical support toll-free at 800-571-8191 (USA) or 800-363-5874 (CDN).

Pour le service client, les retours ou toute question technique, merci d’appeller le service technique de Saniflo au numéro suivant : 800-571-8191 (USA) or 800-363-5874 (CDN).

The user should retain these instructions for future reference • A lire attentivement et à conserver à titre d’information This product must be installed in strict accordance whith local plumbing codes.

Product should be installed by a qualified technician.Le produit doit être installé dans le respect des réglements sanitaires locaux.

Le produit doit être installé par un technicien qualifié.

INSTALLATION AND MAINTENANCE INSTRUCTIONS INSTRUCTIONS D’INSTALLATION ET DE MAINTENANCE

Page 2: IMPORTANTpdf.lowes.com/productdocuments/c91a039e-f20e-4387-91c5-a...SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the

2 3

B x 2

C x 2

20 Ft(6m )

A

X

1

D x 3

F x 4

E x 2

G x 1

11 7/8" (301mm)

11" (280.5mm)

10" (

254m

m)

7 1/2" (190mm)

2 1 / 4" (

56m

m)

7" (179mm)

Y

12 Ft (4 m)

9 Ft (3 m)

6 Ft (2 m)

3 Ft (1 m)

1%

1%

1%

1%

1%

1%

max 15 Ft (4.5 m)

150 ft (50 m)

120 ft (40 m)

90 ft (30 m)

60 ft (20 m)

30 ft (10 m)

OK

0 50 100 150 200 250 300 350

0

1

2

3

4

5

0 10 20 30 40 50 60 70 80

Haute

ur

(pie

ds)

•V

ertic

al D

ista

nce (Feet)

Débit (gallons/heure) • Flow rate (gallons/hour)

Haute

ur

(mètres)

• V

ertic

al D

ista

nce (m

ete

rs)

Débit (l/heure) • Flow rate (liters/hour)

0

2

4

6

8

10

12

14

16

Page 3: IMPORTANTpdf.lowes.com/productdocuments/c91a039e-f20e-4387-91c5-a...SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the

DD

DX

7e

7

7b

1

2

7f

X

Y

C

A

B

123

7c

A

7a

F

E

F

G

1

3

2

15Ft (4.5m) max

SANICONDENS®Best

115 V - 60 Hz - 60 W IP20 -1.2 A

8

Page 4: IMPORTANTpdf.lowes.com/productdocuments/c91a039e-f20e-4387-91c5-a...SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the

4

1 CAUTION

SANICONDENS®BEST is a pump for lifting condensate water from an air conditioning system, a condensation boiler or from refrige-ration units.

The pump starts automatically and has a high level of performance, safety and reliability provided that all the installation and maintenance instructions described in this notice are strictly followed.

Please take particular note of the information marked by : « » Indication that a risk of electrical origin exists,

« » Instructions for use only by qualified professionals.

OPERATING PRINCIPLE

SANICONDENS®BEST contains a pump. The tank of the SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the tank, the pump starts up.

2 SPARE PARTS: see fig.2

3 DIMENSIONS: see fig.3

4 SANICONDENS BEST® AREA OF APPLICATION AND TECHNICAL DATA

Application Air conditioning systems, boilers, refrigeration unitsType condens bestMax. vertical pumping 15 Ft (4.5 m)Maximum flow rate (gal / hour) 86 (326 l/h)Min. pH 2.5

Voltage 110-115 VFrequency 60 HzPower rating 60 WCurrent consumption 1.2 AElectrical class IProtection index IP20Sound level < 45 dBAMaximum allowable temperature 160° F (70° C) S3 15% (1min30 ON, 8min30 OFF)

Net weight 8 lbsTank volume 2 litersSupply cable 6 Ft (2 m)Discharge hose 20 Ft (6 m)Alarm cable (3 core) 6 Ft (2 m)Wall fastening Yes

CAUTION: All applications other than those described in this notice are pro-hibited.

5 PERFORMANCE CURVES: see fig.5

6 VERTICAL PUMPING/HORIZONTAL PUMPING: see fig.6

7 INSTALLATIONSANICONDENS® BEST may be mounted on a wall by using the mounting tabs on the tank..The unit should be easy to access for testing and maintenance.

The unit must be installed leveled. Adjust the installation using a level before mounting the unit.

Make sure that the equipment is protected from damp while ins-talling it.

7b CONNECTION AT THE COVER INLET

The unit has 4 inlets 1” in diameter (2 on each side - see fig. 7b). To connect the water to be drained off, connect the water inlet to one of the inlets and close off any unused inlets with the plug D. If necessary, use the adapter X (3/4”, 1-1/4”, 1-1/2” in diameter).

ELECTRICAL CONNECTION1. The electrical installation should be carried out by a qualified per-

son. The unit should be connected to a fully grounded electrical supply. The SANICONDENS®BEST requires a 120V single phase AC 60 Hz supply.

7e ALARMSANICONDENS ®BEST is fitted with a detection system that can trigger an alarm if the water level rises too high (audible or visual alarm, 1.5V to 120V), see diagram 7e :1 . Brown wire: shared wire2 . Black wire: normally off3 . Blue wire: normally on

To fit the alarm, connect the blue and brown wires of the alarm to the respective terminals on the SANICONDENS ®BEST.

US CDN

INSTRUCTIONS INTENDED SOLELY FOR QUALIFIED PROFESSIONALS

The unit has its own neutralization system that can be used to increase the pH of the acid water from the condensing boiler

Mount the handle E using the 2 screws F. Add the contents of the bag of neutralizing pellets G into the drawer

7a

7c CONNECTING TO THE DISCHARGE HOSEThe SANICONDENS®BEST discharge pipe must be connected to the flexible hose A (supplied : length 20 Ft). This hose should be used to form the vertical section of the discharge pipe.• Place the flexible hose onto the non-return valve of the

SANICONDENS® BEST(see diagram 7c).• Position the flexible hose in the most vertical position

possible to avoid it kinking.• It is advisable to make a smooth bend to avoid the hose from

kinking.• The discharge vinyl tubing (included) can be connected to a

PVC line large in diameter by using the plastic reducer Y that is provided with the system. As shown on the fig. 7f , the plastic fitting connects to the end of the 3/8” vinyl tubing at the top and it increases the diameter to ease the connection to a PVC line. (Reducer is 3/8” barbed x 3/4» male end)

The SANICONDENS ®BEST is fitted with a non-return valve to prevent re-activation.

Page 5: IMPORTANTpdf.lowes.com/productdocuments/c91a039e-f20e-4387-91c5-a...SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the

5

8 STANDARDSThis model is eligible to bear the CSA mark shown with adjacent indicators “C” and “US”. The “C” and “US” indicators adjacent to the CSA mark signify that the product has been tested according to the applicable CSA (CDN) and ANSI/UL standards for use in Canada and the USA. This includes products eligible bear the designation NTRL. NTRL (Nationally Recognized Testing Laboratory) is a desi-gnation awarded by the American Occupational Safety and Health Administration (OSHA) to laboratories authorized to award the certification according to American standards.

11 LIMITED WARRANTY

This SFA appliance bears a 3 year warranty starting from the date of purchase, subject to proper installation and use, in compliance set out in this notice.Warranty issues will be handled by the Technical Department and will be subject to correct installation and usage. If a replacement is to be issued, this will be only extended to the first 180 days starting from the date of purchase and will need to be approved by one of our company’s representative. Warranty repairs will apply after such date up to the warranty’s date of conclusion.Plumber’s invoices for any type of repair, disconnection and reconnection are not covered by the warranty and are the end user’s responsibility. In no event shall the company be liable for any special, incidental or consequential damage, loss or injury of whatsoever nature or kind arising from or in connection with the product or any component thereof.

10 TROUBLESHOOTING

Disconnect the electrical supply before carrying out any work.

FAULT DETECTED

• The pump does not start

• The pump does not lift

PROBABLE CAUSES

• The pump is not connected to the power supply

• The locking pin has not been removed.

• The unit is not level. • Power cut• Float blocked

• Condensates inlet pipe blocked

• Non-return valve blocked

• Discharge pipe blocked

ACTION NEEDED

• Plug in the unit.

• Remove the locking pin.• Please check the unit with a spirit level.• Check the mains voltage.• Clean the SANICONDENS®

tank.• Clean the SANICONDENS®

inlet pipe.•

• Clean the valve.

• Clean the discharge pipe.

INSTRUCTIONS RESERVED SOLELY FOR QUALIFIED PROFESSIONALS

OPTIONAL: if you connect the brown and black wires to the control relays on your boiler, it will be switched off if the water level rises too high in the unit.ATTENTION: The maximum current admissible for our detection system is 0.5A.

To protect the electrical components in the SANICONDENS®BEST

once the alarm has been triggered, any water continuing to fill the tank comes out through the overflow outlets in the cover.

BEFORE TURNING THE DEVICE ON, MAKE SURE YOU REMOVE THE PROTECTIVE LOCKING PIN FROM THE

REAR OF THE DEVICE

7f EXAMPLE OF AN INSTALLATION OF A SANICONDENS®BEST: see fig. 7f

9 DISASSEMBLYIf a breakdown occurs, any service on the unit should be carried out by a qualified technician. In particular the replacement of the power cable.

Disconnect the electrical supply before carrying out work on the unit.

INSTRUCTIONS INTENDED SOLELY FOR QUALIFIED PROFESSIONALS

7e

• Neutralisation drawer is blocked Clean the drawer, replace the pellets

Page 6: IMPORTANTpdf.lowes.com/productdocuments/c91a039e-f20e-4387-91c5-a...SANICONDENS®BEST is fitted with a float which controls the operation of the motor. When the condensate enters the

SA

NIC

ON

DE

NS

® B

est

LIM

ITE

D W

AR

RA

NT

YW

arranty p

eriod

two

-year from

date o

f pu

rchase

Subject to the conditions listed below

, SFA

-SA

NIF

LO IN

C. (hereinafter called the «C

ompany»)

guarantees to repair or at its option replace the product or any component thereof, w

hich, in theopinion of the C

ompany, is faulty or below

standard as a result of inferior workm

anship or materials.

CO

ND

ITIO

NS

The conditions of this guarantee are:

1.The product m

ust not have been subjected to misuse, neglect, accident or dam

agingproducts, in accordance w

ith the paragraph «US

AG

E» of these Installation Instructions.

2.The product m

ust have been connected to a single phase 120V, 60Hz electrical supply.

3.The alleged fault or defect m

ust be notified to the company, w

ithin the warranty period.

PAR

T O

R P

RO

DU

CT

EX

CH

AN

GE

The product w

ill be exchange, free of charge, at the original resellers place of business only, uponthe follow

ings conditions being fullfilled:

1 The custom

er need a «return authorization» number from

the company to authorize and

validate the exchange.

2 The custom

er must supply a copy of their invoice to validate the request for an exchange.

LIM

ITAT

ION

S1.F

ill and flush mechanism

are guaranteed as per OE

M w

arranty only.

2.Cost of disconnection and reconnection (ie labor charges) are not covered by the w

arrantyand are end-users responsability.

3.Cost of m

ail or freight when a part or parts of the system

have to be repaired at thecom

pany are not covered by this warranty.

4.In no event shall the company be reliable for any special, incidental or consequential

damage, loss, or injury of w

hatsoever nature or kind arising from or in connection w

ith theproduct or any com

ponent thereof.

5.The guarantee is transferable only w

hen the product remains at the sam

e premises as

where it w

as installed initialy.

Except as set forth in this Lim

ited Warranty, the com

pany disclaims all other w

arranties, express orim

plied, with respect to the product or any com

ponent thereof including, but not limited to, all im

pliedw

arranties for merchantability and fitness for a particular purpose

For service or for further inquiries, please call or contact any of the following addresses:

United S

tatesC

anadaS

FA-S

AN

IFLO IN

C.

SFA

-SA

NIFLO

INC

.105 N

ewfield A

venue, Suite A

1-685 Speedvale A

venue West

Edison, N

J 08837G

uelph ON

N1K

1E6

Toll Free: 1-800-571-8191

Toll Free: 1-800-363-5874 E

nglishToll Free:

1-800-877-8538 FrenchTelephone:

1-732-225-6070Telephone:

1-519-824-1134Fax:

1-732-225-6072Fax:

1-519-824-1143E

-mail.:

[email protected]

E-m

ail.: sales@

saniflo.comW

eb Site:

ww

w.saniflo.com

Web S

ite: w

ww

.saniflo.ca

8398 224 NOTICE SANISWIFT 02.09.2009 10:16 Page 7