    Contractor Logo Contractor name

    Project titleProject titleProject titleProject title

    DOCUMENTDOCUMENTDOCUMENTDOCUMENT

    DESCRIPTION:DESCRIPTION:DESCRIPTION:DESCRIPTION: 

    SLEEPER DESIGNSLEEPER DESIGNSLEEPER DESIGNSLEEPER DESIGN

    INSIDE TANK FARMINSIDE TANK FARMINSIDE TANK FARMINSIDE TANK FARM

    1 Revised as marked xxx xxx  xxx  xxx 

    0 Issued for construction xxx  xxx  xxx  xxx 

    B Revised as marked. xxx  xxx  xxx  xxx 

    A Issued for Client’s Approval. xxx  xxx  xxx  xxx 

    Rev.Rev.Rev.Rev. DateDateDateDate Revision DescriptionRevision DescriptionRevision DescriptionRevision Description PreparedPreparedPreparedPrepared CheckedCheckedCheckedChecked ReviewedReviewedReviewedReviewed ApprovedApprovedApprovedApproved

    DOCUMENT NUMBERDOCUMENT NUMBERDOCUMENT NUMBERDOCUMENT NUMBER

    Type Discp Job SJ Seq Format PAGES

    A4A4A4A4 1111 OF 44444444

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    2/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 2 of 44

    Record of Revisions

    Rev Date Revision Description

    A Issued for Client’s Approval.

    B Revised by changing embedded beam to anchor lugs for sleepers.

    0 Issued for Construction.

    1 Client’s comments incorporated and revised as marked.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    3/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 3 of 44

    TABLE OF CONTENTS

    Sr.

    No.Description

    Page No. 

    1. Introduction 4

    2. Scope 4

    3. Design considerations 4

    4. Design of Steel beam and column. 8

    5. Design of foundation 32

    6. Annexure

    Annexure 1- TANK FARM-6 SLEEPER LOADING DATA 40

    Annexure 2- TANK FARM-7 SLEEPER LOADING DATA 41

    Annexure 3- Beam flange bending check. 42

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    4/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 4 of 44

    1. Introduction: 

    This document is produced to cover the design calculations of sleepers.

    2. Scope: 

    This document presents design calculations of sleepers inside tank farm.

    3. Design considerations:

    a) Seismic load: Seismic load on the sleeper as per Design basis. 

    Seismic load combination and load factor.

    While using UBC force for BS8110 combination shall be divided by 1.4 hence

    Ve= 0.1/1.4 W = 0.0714 W.

    BS code and Client’s design criteria is silent on load combination of thermal (friction force on

    Pipe rack and sleepers so reference is made to shell DEP refer next page.

    Thermal effects shall be taken along with Seismic and wind loads.

    Entire Pipe loading and thermal effects are considered as Imposed load (live load) and factor

    of 1.6 is applied in operational condition. So load combination in operation condition is,

    = (1.4) x Dead load + (1.6) x Pipe vertical load + (1.6) x Pipe lateral load.

    = (1.4) x Dead load + (1.6) x Pipe vertical load + (0.15 x1.6) x vertical load*.

    = (1.4) x Dead load + (1.6) x Pipe vertical load + (0.24) x vertical load*…...a

    Seismic load combination.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    5/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 5 of 44

    = (1.2) x Dead load + (1.2) x Pipe vertical load + (1.2) x Pipe lateral load + (1.2) x Seismic load.

    = (1.2) x Dead load + (1.2) x Pipe vertical load + (1.2 x 0.15) x Pipe vertical load* + (1.2 x 0.0714) x Pipe vertical

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    6/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 6 of 44

    Load*.

    = (1.2) x Dead load + (1.2) x Pipe vertical load + (0.18) x Pipe vertical load* + (0.0857) x Pipe vertical load*.

    = (1.2) x Dead load + (1.2) x Pipe vertical load + (0.18 + 0.0857) x Pipe vertical load*.

    = (1.2) x Dead load + (1.2) x Pipe vertical load + (0.266) x Pipe vertical load*…………………..a

    Comparing combination a and b, the operating load combination with load factor 1.6 found

    more stringent so design of components are done with uniform factor of 1.6.

    Although the thermal forces are not to be transferred to foundation, the foundation stability

    and soil pressures are checked for forces with factor of 1.0. In this case, load component of

    friction (0.15) is higher that the seismic (0.0714) so conservatively foundation are checked for

    friction force of (0.15) vertical load to account for lower seismic force.

    b) Wind load:

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    7/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 7 of 44

    Refer BS 6399 Part -2,

    Wind load on pipe sleeper having width more than 4m and pipes of 32” maximum,

    Wind Load on 4 pipes = 1.2 x 4 x (32 x 0.0254) x 0.971 = 3.8 kN/m

    Pipe operating weight is as follows,

    Seismic load for pipes more than 4 Nos. is = 7.26 x 5 x 0.0714 = 2.6 < 3.8 kN/m is less severe than

    seismic load so seismic load is governing load case over wind and wind load is neglected.

    Also 1.4 DL + 1.6 LL + 1.6 LL (lateral); for superstructure design,

    Is severe than 1.2 DL + 1.2 LL + 1.2 LL (lateral) + 1.2 Seismic; for superstructure design, as 1.2 x

    0.0714 =0.086 W < (1.6 -1.2). For local anchors, seismic lateral force the load factor of LL (lateral)

    (1.6-1.2=0.4) over 0.0714 x 1.2 seismic is governing. So stringent combination of 1.6 factor for

    component design is followed for simplicity in calculations.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    8/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 8 of 44

    4. Design of Steel beam and column.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    9/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 9 of 44

    Notes: (refer table on next page)

    1. Stool height varies from 100mm to 250mm as the pipes are provided at slope of 1:1000.

    2. For each sleeper located 6m apart the level difference is 6mm, towards manifold.

    3. Stools are shown indicative and height is worked out based on piping information i.e. drawing

    number ---------and ---------------. The stools will be provided by piping group.

    4. The total height for working out moment at foundation base level is = depth of foundation

    below ground + height of steel beam top above FGL + stool height + half of pipe diameter.

    5. Maximum size of pipe is considered for working out the moment in each sleeper in the above

    expression.

    6. Orientation of sleeper in table is 1 when the sleeper is along North-South and 0 when it is

    Along East-West.

    7. Two groups are identified in sleeper for further design, up-to lateral load of 31kN and 32kN to

    63 kN.

    8. Sleeper SL-053 is located on middle of culvert so only superstructure design is applicable.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    10/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 10 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    11/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 11 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    12/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 12 of 44

     S L - 0  5  3 R E  S T I  N  G ON 

    P I  P E  C  U L V E R T -F  O U N D A T I   ON I   S D E  S I   GN 

    E D WI  T H P I  P E  C  U L V E R T 

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    13/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 13 of 44

    Beam stress check: (detailed calculation done for SL-117A and all other sleeper tabulated in table).

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    14/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 14 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    15/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 15 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    16/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 16 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    17/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 17 of 44

    Factored forces on beam for anchor bolt design:

    SL-117A Anchor design:

    Resultant shear force = √1002+11.8 - 78.68 x µ (where µ co-eff of friction between steel

    and concrete (ACI 318 Design guide).

    =53.48 kN (to be used for anchor bar design)

    Vertical force P= 78.68kN and moment M =18.8 kN-m (for base plate and anchor pullout

    design), (minimum vertical load and max. moment is more stringent combination so adopted)

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    18/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 18 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    19/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 19 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    20/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 20 of 44

    Tensile force on Anchor P= 74.9 kN = 16.83 kips.

    Shear force on Anchor S= 53.48 kN = 12.02 kips.

    Supplimentry reinforcement for tension:

    Ast = Pu/0.9 x Fy = 74.9 x 1000 / (0.9 x 460 ) = 180mm2 .

    Top 4-Nos T12 bars having area of 452mm2 

    Supplimentry reinforcement for shear:

    Ast = Su/0.9 x Fy = 53.48 x 1000 / (0.9 x 460 ) = 129 mm 2 .

    Top 4-Nos T8 bars having area of 200mm2 

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    21/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 21 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    22/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 22 of 44

    All other sleeper anchor design. (SL-0116)

    Maximum moment and corresponding axial load is considered.

    Shear force is considered maximum of both tank farms.

    Resultant shear force = √54.462+27.72 - 92.35 x µ (where µ co-eff of friction between steel

    and concrete. =5.69 kN (to be used for anchor bar design).

    Vertical force P= 72.62kN and moment M =10.23 kN-m (for base plate and anchor pullout

    design), (minimum vertical load and max. moment is more stringent combination so adopted).

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    23/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 23 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    24/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 24 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    25/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 25 of 44

    Supplimentry reinforcement for tension:

    Ast = Pu/0.9 x Fy = 32.44 x 1000 / (0.9 x 460 ) = 78.4mm 2 .

    Top 4-Nos T12 bars having area of 452mm2

     Supplimentry reinforcement for shear:

    Ast = Su/0.9 x Fy = 5.7 x 1000 / (0.9 x 460 ) = 13.8 mm2 .

    Top 4-Nos T8 bars having area of 200mm2 

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    26/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 26 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    27/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 27 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    28/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 28 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    29/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 29 of 44

    Beam Flange and web check for local bending/Bucking load:

    Maximum load from page No of 37 of this document is 139kN/m and stiffners are provided at

    750mm c/c. Weight of 8m long pipe filled with product of density is worked out on next page

    and beam is checked for the same.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    30/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 30 of 44

    With load factor of 1.6, shear force is132.8 kN.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    31/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 31 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    32/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 32 of 44

    5. Design of foundation

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    33/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 33 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    34/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 34 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    35/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 35 of 44

    Moment due to eccentricity = Fy x e = 37.5 x 0.5 = 18.75 kNm (for SL019B)

    1

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    36/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 36 of 44

    Note-2

    Note-1

    1

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    37/44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    38/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 38 of 44

    Notes:1) Note-1: sleeper shifted on pipe culvert, Note 2: Sleeper deleted.

    Note-1

    1

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    39/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 39 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    40/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 40 of 44

    Annexure 1- TANK FARM-6 SLEEPER LOADING DATA

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    41/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 41 of 44

    Annexure 2- TANK FARM-7 SLEEPER LOADING DATA

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    42/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 42 of 44

    Annexure 3- Beam flange bending check.

    C/c distances of biggest pipes (32”) are 1000mm for TF6 and TF7 respectively as shown.

    Shoe support as per PDMS snapshot.

    Beam size 203 x 133 x 25.

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    43/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    XX-X-XXXX-XX-XXXX-1Rev xx-Tank-farm Sleeper design.doc

    Page 43 of 44

  • 8/16/2019 XX X XXXX XX XXXX 1Rev Xx Tank Farm Sleeper Design

    44/44

     

    Client Logo SLEEPER

    DESIGN

    INSIDE TANK

    FARM

    Contractor Logo

    Contractor NameContractor NameContractor NameContractor Name 

    Job No: Doc. Revision : Date:1

    Notes:1. As the pipe is very stiff it is not possible that it will bend with respect to beam flange and bear on the

    corner of flange. Due to any other reason it bears then it wil l get self adjusted by a small deflection.

    2. Beam is considered as rigidly held between support point (anchor bolts) but which is not a real case It

    will follow a small rotation (twisting) along with stool bottom surface to bring in one level.