XCHANGE Energy Recovery XCM–COMPACT MULTIFLOW ERV XCM325C1 Technical Data Technical Specifications Nominal Airflow Supply Air (I/sec) 325 Return Air (I/sec) 325 Controls 240V Controls Included Fan Fault Not available Supply Fan Fan Type Forward Curved Centrifugal Fan Motor Direct Drive Motor Power (Watts) 425 External Static (Pa) 200 Speeds 3 Max Fan Speed (rpm) 1350 Motor Protection Thermal Overload Exhaust Fan Fan Type Forward Curved Centrifugal Fan Motor Direct Drive Motor Power (Watts) 425 External Static (Pa) 200 Speeds 3 Max Fan Speed (rpm) 1350 Motor Protection Thermal Overload Options Internal Drain Tray Available (Model XCM325C1-T) Electrical Supply Fan (A) 3.6 Exhaust Fan (A) 3.6 Nominal Run Current (A) 7.2 Maximum Full Load (A) 8.0 Volt/Phase 240V/1ph Connection Lead & Plug Heat Exchanger *Rated at standard conditions of 35.5° db/24.0° wb Enthalpy Media Standard (Model XCM325C1E) Sensible Media Available (Model XCM325C1S) Corrosion Resistant Media Available Velocity (m/sec) 1.63 Pressure Drop (Pa) 86.6 Kw Recovered (Cooling)* 4.30 Kw Recovered (Heating)* 5.49 Filters Type 45mm V Form Panel - G4 Disposable / Washable Disposable Size L x W x D (mm) 495 x 395 x 45 Number of Filters 2 Cabinet Construction Casing Galvanised Metal Insulation Thickness (mm) 15/25mm Hanging Brackets Included

Upload: others

Post on 30-Apr-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: XCM–COMPACT MULTIFLOW ERV

XCHANGE Energy RecoveryXCM–COMPACT MULTIFLOW ERVXCM325C1 Technical Data

Technical Specifications

Nominal Airflow

Supply Air (I/sec) 325

Return Air (I/sec) 325

Controls

240V Controls Included

Fan Fault Not available

Supply Fan

Fan Type Forward Curved Centrifugal

Fan Motor Direct Drive

Motor Power (Watts) 425

External Static (Pa) 200

Speeds 3

Max Fan Speed (rpm) 1350

Motor Protection Thermal Overload

Exhaust Fan

Fan Type Forward Curved Centrifugal

Fan Motor Direct Drive

Motor Power (Watts) 425

External Static (Pa) 200

Speeds 3

Max Fan Speed (rpm) 1350

Motor Protection Thermal OverloadOptions

Internal Drain Tray Available (Model XCM325C1-T)Electrical

Supply Fan (A) 3.6

Exhaust Fan (A) 3.6

Nominal Run Current (A) 7.2

Maximum Full Load (A) 8.0

Volt/Phase 240V/1ph

Connection Lead & Plug

Heat Exchanger *Rated at standard conditions of 35.5° db/24.0° wb

Enthalpy Media Standard (Model XCM325C1E)

Sensible Media Available (Model XCM325C1S)

Corrosion Resistant Media Available

Velocity (m/sec) 1.63

Pressure Drop (Pa) 86.6

Kw Recovered (Cooling)* 4.30

Kw Recovered (Heating)* 5.49

Filters

Type 45mm V Form Panel - G4

Disposable / Washable Disposable

Size L x W x D (mm) 495 x 395 x 45

Number of Filters 2

Cabinet Construction

Casing Galvanised Metal

Insulation Thickness (mm) 15/25mm

Hanging Brackets Included

Page 2: XCM–COMPACT MULTIFLOW ERV

XCHANGE Energy RecoveryXCM–COMPACT MULTIFLOW ERV – XCM325C1 Technical Data

Technical Drawings – XCM325C1

Dimensions

Height (mm) 440

Width (mm) 830

Length (mm) 1060

Weight (Kg) 90

Access Clearance (mm) 600 (Controls & Filter Access)

Access Clearance (mm) 600 (Filter Access)

Duct Sizes

Exhaust Air (mm) 300 Ø

Return Air (mm) 300 Ø

Supply Air (mm) 300 Ø

Fresh Air (mm) 300 Ø

Wiring Diagram

Electrical Connections

E Earth Green/Yellow

N Neutral Blue

L Active Brown

H High Speed Brown

M Medium Speed Grey/Orange

L Low Speed White

Page 3: XCM–COMPACT MULTIFLOW ERV

Fan Performance Data

Sound Power Levels*

XCHANGE Energy RecoveryXCM–COMPACT MULTIFLOW ERV – XCM325C1 Technical Data

Filter and Fan Access

Inlet Rating dB Outlet Rating dB

63 Hz 64 63 Hz 66

125 Hz 61 125 Hz 63

250 Hz 70 250 Hz 70

500 Hz 68 500 Hz 70

1k Hz 64 1k Hz 70

2k Hz 63 2k Hz 71

4k Hz 61 4k Hz 67

8k Hz 55 8k Hz 60

LwA 71 LwA 76

* Sound Power Levels Recommended Operating Point.

0

50

100

150

200

250

300

250 275 300 325 350 375 400 425 450 475 500

Exte

rnal

Sta

tic

Pres

sure

[Pa]

Air Flow [l/s]

System Performance Curve

Recommended Duty PointAmp : 2.3A

Page 4: XCM–COMPACT MULTIFLOW ERV

XCHANGE Energy RecoveryXCM–COMPACT MULTIFLOW ERV – XCM325C1 Technical Data

Ductwork Connections

RETURN AIR: Air that is drawn from conditioned areas.

EXHAUST AIR: Ducted to outside the building or into the roof space if adequate ventilation to the outside air is available.

FRESH AIR: Use a fresh air cowl or grill to introduce fresh air.

SUPPLY AIR: Connect to the airconditioning system or directly into the conditioned area.

ENERGY RECOVERY

Exhaust Air

Supply Air

Fresh Air

Return Air

ENERGY RECOVERY

Exhaust Air Fresh Air

Return Air

Supply Air

ENERGY RECOVERY

Exhaust Air

Supply Air

Fresh Air

Return Air

ENERGY RECOVERY

Exhaust Air

Fresh Air

Return Air

Supply Air

ENERGY RECOVERY

Exhaust Air

Fresh Air

Supply Air Return Air

ENERGY RECOVERY

Exhaust Air

Supply Air

Fresh Air

Return Air

ENERGY RECOVERY

Exhaust Air Fresh Air

Supply Air Return Air

ENERGY RECOVERY

Exhaust Air

Supply Air

Fresh Air

Return Air

Page 5: XCM–COMPACT MULTIFLOW ERV

A: 109-111 Northcorp Blvd, Broadmeadows VIC 3047 T: 03 8301 9200 E: [email protected] www.armcor.com.au

© 2021 Armcor Air Solutions reserves the right to alter products and specifications without notice and does not accept responsibility for possible errors and omissions in published documentation.Date: 06/08/2021 | Document: XCM325C1_techspec | Version 2

RETURN AIR: Air that is drawn from conditioned areas.

EXHAUST AIR: Ducted to outside the building or into the roof space if adequate ventilation to the outside air is available.

FRESH AIR: Use a fresh air cowl or grill to introduce fresh air.

SUPPLY AIR: Connect to the airconditioning system or directly into the conditioned area.

XCHANGE Energy RecoveryXCM–COMPACT MULTIFLOW ERV – XCM325C1 Technical Data

ENERGY RECOVERY

Exhaust Air

Supply Air

Fresh Air

Return Air

ENERGY RECOVERY

Exhaust Air Fresh Air

Supply Air Return Air

ENERGY RECOVERY

Exhaust Air

Supply Air

Fresh Air

Return Air

ENERGY RECOVERY

Exhaust Air

Fresh Air

Supply Air Return Air

ENERGY RECOVERY

Exhaust Air

Supply Air Return Air

Fresh Air

ENERGY RECOVERY

Exhaust Air

Return Air

Fresh Air

Supply Air

ENERGY RECOVERY

Exhaust Air

Supply Air Return Air

Fresh Air

ENERGY RECOVERY

Exhaust Air

Return Air

Fresh Air

Supply Air