AIR CONDITIONERS XC16 ELITE ® Series R-410A - Two-Stage Compressor Bulletin No. 210743 November 2017 Supersedes August 2017 SEER up to 17.00 2 to 5 Tons Cooling Capacity - 23,200 to 57,500 Btuh X C 16 – 036 - 230 - 5 Series Unit Type C = Air Conditioner Refrigerant Type X = R-410A Nominal Cooling Capacity 024 = 2 tons 036 = 3 tons 048 = 4 tons 060 = 5 tons Minor Revision Number Voltage 230 = 208/230V-1phase-60hz MODEL NUMBER INDENTIFICATION PRODUCT SPECIFICATIONS Regional Standards – (dash) = Southwest Region S = North and South Regions

Upload: lamnguyet

Post on 15-May-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

A I R C O N D I T I O N E R S

XC16ELITE® Series

R-410A - Two-Stage CompressorBulletin No. 210743

November 2017 Supersedes August 2017

SEER up to 17.002 to 5 Tons

Cooling Capacity - 23,200 to 57,500 Btuh

X C 16 – 036 - 230 - 5

Series

Unit Type C = Air Conditioner

Refrigerant Type X = R-410A

Nominal Cooling Capacity 024 = 2 tons 036 = 3 tons 048 = 4 tons 060 = 5 tons

Minor Revision Number

Voltage 230 = 208/230V-1phase-60hz

MODEL NUMBER INDENTIFICATION

P R O D U C T S P E C I F I C AT I O N S

Regional Standards– (dash) = Southwest Region S = North and South Regions

XC16 2-5 TON AIR CONDITIONERS

Page 2: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 2

WARRANTY

Compressor - limited warranty for ten years in residential installations and five years in non-residential installations.

All other covered components - five years in residential installations and one year in non-residential installations.

Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.

APPROVALSAHRI Certified to AHRI Standard 210/240-2008.Sound rated in Lennox reverberant sound test room in accordance with test conditions included in AHRI Standard 270-2008.Tested in the Lennox Research Laboratory environmental test room.Rated according to U.S. Department of Energy (DOE) test procedures.Region specific models meet the minimum efficiency requirements for U.S DOE Federal Regional Standards in that area.Air conditioners and components within bonded for grounding to meet safety standards for servicing required by UL and CEC.Units are ETL certified for the U.S. and Canada.ISO 9001 Registered Manufacturing Quality System.For expanded ratings, see www.LennoxPROs.com.

APPLICATIONSSEER up to 17.20.2 through 5 ton.Single phase power supply.Sound levels as low as 74 dB. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof.Matching add-on furnace indoor coils or air handlers provide a wide range of cooling capacities and applications. See AHRI System Matches.See Indoor Coils and Air Handlers tab sections for data.Units shipped completely factory assembled, piped, and wired. Each unit is test operated at the factory insuring proper operation.Installer must set air conditioner, connect refrigerant lines, and make electrical connections to complete job.

C

D

E

J

B

G

H

I

F

FEATURES

CONTENTSAHRI System Matches - North / South Regions ........ 10AHRI System Matches - Southwest Region .............. 35Dimensions .................................................................. 8Electrical Data.............................................................. 6Features....................................................................... 2Field Wiring .................................................................. 7Installation Clearances ................................................ 7Model Number Indentification ...................................... 1Optional Accessories ................................................... 6Outdoor Sound Data .................................................... 7Specifications............................................................... 6

Page 3: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 3

REFRIGERATION SYSTEMR-410A RefrigerantNon-chlorine, ozone friendly, R-410A. Unit pre-charged with refrigerant. See Specification table.

Outdoor Coil FanDirect drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity. 048 models have a variable-speed outdoor fan motor for quiet operation.Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs.Fan motor has sleeve bearings and is inherently protected.Motor totally enclosed for maximum protection from weather, dust and corrosionFan guard constructed of corrosion-resistant PVC (polyvinyl chloride) coated steel.Fan service access accomplished by removal of fan guard.

Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple-edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area. Flared shoulder tubing connections/silver soldering construction.Coil is factory tested under high pressure to insure leakproof construction.Entire coil is accessible for cleaning.High Pressure SwitchShuts off unit if abnormal operating conditions cause the discharge pressure to rise above setting. Protects compressor from excessive condensing pressure. Auto-reset.

Low Pressure SwitchShuts off unit if suction pressure falls below setting. Provides loss of charge and freeze-up protection. Auto-reset.

Hi-Capacity Liquid Line DrierFactory installed in the liquid line, the drier traps moisture or dirt that could contaminate the refrigerant system.100% molecular-sieve bead type drier.

A

B

C

D

E

F

Optional Accessories

Expansion Valve KitsMust be ordered extra and field installed on certain indoor units. See TXV Usage table.Chatleff style fitting.

FreezestatInstalls on or near the discharge line of the indoor coil or on the suction line.Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint.Opens at 29°F and closes at 58°F.

Refrigerant Line KitsRefrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized, and sealed at factory.Suction line fully insulated.L15 lines are stubbed at both ends.See Specifications table for selection.Not available for -060 model and must be field fabricated.

FEATURES

Page 4: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 4

COMPRESSORCopeland Scroll Ultra Tech™ Two-Stage CompressorCompressor features high efficiency with uniform suction flow, constant discharge flow, high volumetric efficiency and quiet operation. Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. During compression, one scroll remains stationary while the other scroll orbits around it. Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced.When the pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged.During the compression process, there are several pockets in the scroll that are compressing gas. Modulation is achieved by venting a portion of the gas in the first suction pocket back to the low side of the compressor thereby reducing the effective displacement of the compressor.

GA 24-volt DC solenoid valve inside the compressor

controls staging. When the 3-way solenoid is energized it moves the lift ring assembly to block the ports and the compressor operates at full-load or 100% capacity. When the solenoid is de-energized the lift ring assembly moves to unblock the compressor

ports and the compressor operates at part-load or approximately 67% of its full-load capacity.The “loading” and “unloading” of the two stage scroll is done “on the fly” without shutting off the single-speed compressor motor between stages.Low gas pulses during compression reduces operational sound levels.Compressor motor is internally protected from excessive current and temperature.Compressor is installed in the unit on specially formulated, resilient rubber mounts for better sound dampening and vibration free operation.

Crankcase Heater (048-060 models only)Crankcase heater prevents migration of liquid refrigerant into compressor and ensures proper compressor lubrication.

Optional Accessories

Crankcase Heater (Optional for 024-036 models)Crankcase heater prevents migration of liquid refrigerant into compressor and ensures proper compressor lubrication.

Compressor Hard Start KitSingle-phase units are equipped with a PSC compressor motor. This type of motor normally does not need a potential relay and start capacitor.In conditions such as low voltage, kit may be required to increase the compressor starting torque. Hard start kit is required in applications where the supply voltage is less than 230V.

FEATURES

Page 5: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 5

FEATURES

CONTROLS

Optional Accessories

Blower Relay Kit (For Use With EL195E and ML180E Gas Furnaces)Allows furnace blower speed changes when matched with two-stage air conditioners.

ComfortSense® 7500 Touchscreen ThermostatElectronic 7-day, universal, multi-stage, programmable, touchscreen thermostat. 4 Heat/2 Cool. Auto-changeover. Controls dehumidification during cooling mode. Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and equipment maintenance reminders. Easy-to-use, menu driven thermostat with a back-lit, LCD touchscreen. Remote outdoor temperature sensor (optional) allows the thermostat to display outdoor temperature. Required in dual fuel and Humiditrol® applications. See the ComfortSense 7500 Product Specifications bulletin in the Controls section for more information.

Indoor Blower Off Delay RelayDelays the indoor blower-off time during the cooling cycle. Indoor Blower Speed RelayRelay kit provides the option of changing blower speeds on standard permanent split capacitor (PSC) multi-tap blower motors during cooling operation.Provides optimum humidity control conditions by automatically reducing indoor blower speed during continuous fan operation or low stage compressor operation to reduce humidity levels.

Low Ambient KitAir conditioner will operate satisfactorily down to 45°F outdoor air temperature without any additional controls. Kit can be added in the field enabling unit to operate properly down to 30°F. A Freezestat and optional Crankcase Heater (024-036) should be installed on compressors equipped with a Low Ambient Kit. A Compressor Low Ambient Cut-Off Switch should be added to terminate compressor operation below recommended operation conditions.

ThermostatThermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book.

CABINETHeavy-gauge steel construction Pre-painted cabinet finish. Control box is conveniently located with all controls factory wired. Large removable panel provides service access. Drainage holes are provided in base section for moisture removal. High density polyethylene unit support feet raise the unit off of the mounting surface, away from damaging moisture.

PermaGuard™ Unit BaseDurable zinc-coated base section resists rust and corrosion.

SmartHinge™ Louvered Coil ProtectionSteel louvered panels provides complete coil protection. Panels are hinged to allow easy cleaning and servicing of coils. Panels may be completely removed. Interlocking tabs and slots assure tight fit on cabinet.

Refrigerant Line Connections, Electrical Inlets and Service ValvesSuction and liquid lines are located on corner of unit cabinet and are made with sweat connections. See dimension drawing. Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Suction valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. Refrigerant line connections and field wiring inlets are located in one central area of the cabinet. See dimension drawing.

H

I

J

Page 6: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 6

SPECIFICATIONSGeneral Data

Model No. Southwest Region XC16-024 XC16-036 XC16-048 XC16-060North / South Regions XC16S024 XC16S036 XC16S048 XC16S060

Nominal Tonnage 2 3 4 5Connections (sweat)

Liquid line (o.d.) - in. 3/8 3/8 3/8 3/8Suction line (o.d.) - in. 3/4 7/8 7/8 1-1/8

Refrigerant 1 R-410A charge furnished 7 lbs. 5 oz. 8 lbs. 6 oz. 10 lbs. 7 oz. 12 lbs. 1 oz.Outdoor Coil

Net face area - sq. ft. Outer coil 24.50 16.33 21.00 29.09Inner coil - - - 15.76 20.27 28.24

Tube diameter - in. 5/16 5/16 5/16 5/16No. of rows 1 2 2 2

Fins per inch 26 22 22 22Outdoor Fan

Diameter - in. 22 22 22 26No. of blades 4 4 4 3

Motor hp 1/6 1/4 1/3 1/3Cfm - 1st stage 3260 3500 3190 4325

2nd stage - - - - - - 3700 - - -Rpm - 1st stage 840 825 705 865

2nd stage - - - - - - 820 - - -Watts - 1st stage 220 300 165 240

2nd stage - - - - - - 260 - - -Shipping Data - lbs. 1 pkg. 249 243 268 332

ELECTRICAL DATALine voltage data - 60hz 4 230V-1ph 4 230V-1ph 4 230V-1ph 4 230V-1ph2 Maximum overcurrent protection (amps) 25 35 50 603 Minimum circuit ampacity 15.7 20.8 29.2 35.6Compressor Rated load amps 11.66 15.25 21.15 27.1

Locked rotor amps 58.3 83 104 152.9Power factor 0.98 0.99 0.99 0.99

Outdoor Fan Motor

Full load amps 1.0 1.7 2.8 1.8Locked Rotor amps 1.9 3.1 N/A 2.9

OPTIONAL ACCESSORIES - ORDER SEPARATELYBlower Relay Kit (for EL195E and ML180E gas furnaces)

85W66 • • • •

ComfortSense® 7500 Thermostat 13H14 • • • •Outdoor Temperature Sensor - for ComfortSense 7500 Thermostat

X2658 • • • •

Compressor Crankcase Heater 93M04 • •Factory • •

Compressor Hard Start Kit - Required in applications with less than 230V

63W22 •10J42 • •

63W24 •Compressor Low Ambient Cut-Off 45F08 • • • •Compressor Time-Off Control 47J27 • • • •Freezestat 3/8 in. tubing 93G35 • • • •

5/8 in. tubing 50A93 • • • •Indoor Blower Off Delay Relay 58M81 • • • •Indoor Blower Speed Relay Kit 40K58 • • • •5 Low Ambient Kit (Fan Cycling) 34M72 • • •

68M04 •Refrigerant Line Sets

L15-41-20 L15-41-40 L15-41-30 L15-41-50

L15-65-30 L15-65-40 L15-65-50

• •

Field Fabricate •NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the Installation Instructions for information about line set length and

additional refrigerant charge required.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Hard Start Kit is required in applications where the supply voltage is less than 230V.5 Crankcase Heater (if not furnished) and Freezestat are recommended with Low Ambient Kit.

Page 7: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 7

OUTDOOR SOUND DATA

1 Unit Model

Octave Band Linear Sound Power Levels dB, re 10-12 Watts 1Sound Rating

Number (dB)

Center Frequency - HZ

125 250 500 1000 2000 4000 8000

024 66.6 65.5 66.4 62.7 57.9 55.1 55.5 73036 70.6 67.9 66.7 63.1 57.5 54.7 55.4 74048 64.7 64.1 65.8 65.2 60.3 56.1 53.7 74060 68.9 67 66.4 67.4 58.9 57.3 52.5 74NOTE - the octave sound power data does not include tonal correction.1 Tested according to AHRI Standard 270-2008 test conditions.

FIELD WIRING

B

DISCONNECTSWITCH

(By Others)

LENNOXAIR

CONDITIONER

LENNOXHEATING UNIT

ORAIR HANDLER

UNIT

DISCONNECTSWITCH

(By Others)THERMOSTAT

(Optional)

C

DA A - Two Wire Power (not furnished)

B - Two Power (not furnished). See Electrical DataC - Four Wire Low Voltage (not furnished). 18 ga. minimumD - Six Wire Low Voltage (not furnished). 18 ga. minimumAll wiring must conform to NEC or CEC and local electrical codes.

INSTALLATION CLEARANCES - INCHES (MM)

SeeNOTES

See NOTES NOTES:Service clearance of 30 in. (762 mm) must be maintained on oneof the sides adjacent to the control box.

Clearance to one of the other three sides must be 36 in. (914 mm)

Clearance to one of the remaining two sides may be 12 in. (305mm) and the final side may be 6 in. (152 mm).

A clearance of 24 in. (610 mm) must be maintained between twounits.

48 in. (1219 mm) clearance required on top of unit.

SeeNOTES

See NOTES ControlBox

Page 8: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 8

DIMENSIONS - INCHES (MM)

ModelA B C

in. mm in. mm in. mm024 45 1143 30-1/2 775 35 889036 31 787 30-1/2 775 35 889048 39 991 30-1/2 775 35 889060 45 1143 35-1/2 902 39-1/2 1003

ELECTRICALINLETS

SIDE VIEW

DISCHARGE AIR

SUCTION LINECONNECTION

LIQUID LINECONNECTION

A

BC

4−1/4(108)4−3/4(121)

1 (25)

2 (51)

END VIEW

TOP VIEW

SUCTION LINECONNECTION

LIQUID LINECONNECTION

060 BASE SECTION(Large)

024 TO 048 BASE SECTION(Medium)

UNIT SUPPORTFEET

13−7/8(352)

3−5/8(92)

20−5/8(524)

7−3/4(197)

27−1/8(689)

4−1/2(114)

3−1/4(83)

UNIT SUPPORTFEET

16-7/8 (429)

26-7/8(683)

30-3/4 (781)3-1/8(79)

8-3/4(222) 3-3/4 (95)

4-5/8(117)

Page 9: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 9

TXV USAGEUse this table for C33, C35, CH23, CH33, CH35 and CR33 Field Installed TXV/Orifice Match-Ups.Outdoor Unit Model No.

Order No.

XC16(-)(S)024 12J18XC16(-)(S)036 12J19XC16(-)(S)048 12J20XC16(-)(S)060 12J20CX34 and CX35 upflow coils and all Lennox air handlers are shipped with a factory installed TXV. In most cases, no change out of the valve is needed.If a change out is required it will be listed in the “TXV SUBSTITUTIONS” table. The correct TXV must be ordered separately and field installed.C33, C35 and CH33 coils - Use the orifice shipped with the outdoor unit or replace the factory installed orifice with the expansion valve listed .CR33 and CH23 coils - Use the orifice shipped with the outdoor unit or use the expansion valve listed.CH35 coils - Factory installed orifice must be replaced with the expansion valve listed.

MOST POPULAR MATCHESOutdoor Unit Model No.

Indoor Unit Model No

XC16(-)(S)024 CX34-36B with SL280UH090V36BXC16(-)(S)036 CX34-43C with SL280UH090V60CXC16(-)(S)048 CX34-62C with SL280UH090V60CXC16(-)(S)060 CX34-62C with SL280UH090V60C

AHRI STANDARD 210/240

Cooling or heating capacities are net values, including the effects of blower motor heat, and do not include supplementary heat. Power input is the total power input to the compressor(s) and fan(s), plus any controls and other items required as part of the system for normal operation.Units which do not have an indoor air-circulating blower furnished as part of the model, i.e., split system with indoor coil only, is established by subtracting from the total cooling capacity 1250 Btu/h per 1,000 cfm, and by adding the same amount to the heating capacity. Total power input for both heating and cooling is increased by 365 W per 1,000 cfm of indoor air circulated.

*TXV SUBSTITUTIONSUse this table to determine if the factory installed TXV in the indoor unit needs to be replaced.Outdoor Unit Model No. Handler Factory

TXVReplacement TXV

XC16(-)(S)036 CBX25UHV-030 12J18 12J19

XC16(-)(S)036 CBX32MV-024/030 12J18 12J19* Air handlers - The factory installed expansion valve must be replaced with the expansion valve listed (ordered separately). If the combination is not listed above, the factory installed TXV is used.

Page 10: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 10

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S024-230 TXV 24800 16 13 C35-24A SL280UH070V36A 8255899XC16S024-230 TXV 23800 15.5 12.5 C35-24B EL195UH030XE24B 8604030XC16S024-230 TXV 23800 15.5 12.5 C35-24B EL195UH045XE24B 8604001XC16S024-230 TXV 24800 16 13 C35-24B EL296UH045XV36B 8255901XC16S024-230 TXV 24600 15.1 13 C35-24B SL280UH090V36B 8255902XC16S024-230 TXV 24600 16 13 C35-24B SLP98UH070XV36B 8255900XC16S024-230 TXV 24200 14 12 C35-24B 8255898XC16S024-230 TXV 24600 16 13 C35-30/36A SL280UH070V36A 8255911XC16S024-230 TXV 24800 16 13 C35-30/36A SL280UH070XV36A 8255910XC16S024-230 TXV 24600 16 13 C35-30/36B CBWMV-24B-040 8255913XC16S024-230 TXV 23800 15.5 12.5 C35-30/36B EL195UH030XE24B 8604031XC16S024-230 TXV 23800 15.5 12.5 C35-30/36B EL195UH045XE24B 8604002XC16S024-230 TXV 24600 16 13 C35-30/36B EL296UH045XV36B 8255915XC16S024-230 TXV 24400 15.1 13 C35-30/36B SL280UH090V36B 8255912XC16S024-230 TXV 24600 16 13 C35-30/36B SLP98UH070XV36B 8255914XC16S024-230 TXV 24000 14 11.5 C35-30/36B 8255909XC16S024-230 TXV 24600 16 13.5 C35-30/36C SLP98UH090XV36C 8255916XC16S024-230 TXV 25200 17 13 C35-30A SL280UH070V36A 8255905XC16S024-230 TXV 25400 17 13.5 C35-30A SL280UH070XV36A 8255904XC16S024-230 TXV 23800 16 12.5 C35-30B EL195UH030XE24B 8604032XC16S024-230 TXV 23800 16 12.5 C35-30B EL195UH045XE24B 8604003XC16S024-230 TXV 25200 16 13.5 C35-30B EL296UH045XV36B 8255907XC16S024-230 TXV 25000 16 13.5 C35-30B SL280UH090V36B 8255908XC16S024-230 TXV 25200 16 13.5 C35-30B SLP98UH070XV36B 8255906XC16S024-230 TXV 24600 14.5 12 C35-30B 8255903XC16S024-230 TXV 25400 17 13.5 C35-36A SL280UH070V36A 8255919XC16S024-230 TXV 25400 17 13.5 C35-36A SL280UH070XV36A 8255918XC16S024-230 TXV 23800 16 13 C35-36B EL195UH030XE24B 8604033XC16S024-230 TXV 23800 16 13 C35-36B EL195UH045XE24B 8604004XC16S024-230 TXV 25400 16 13.5 C35-36B EL296UH045XV36B 8255922XC16S024-230 TXV 25200 16 13.5 C35-36B SL280UH090V36B 8255920XC16S024-230 TXV 25200 16 13.5 C35-36B SLP98UH070XV36B 8255921XC16S024-230 TXV 24800 14.5 12.2 C35-36B 8255917XC16S024-230 TXV 24000 16 13.5 CBA27UHE-024 10259501XC16S024-230 TXV 24000 17 13.5 CBA27UHE-030 10259502XC16S024-230 TXV 24000 16 13 CBX25UHV-024 7622702XC16S024-230 TXV 25000 16 13.5 CBX27UH-024 7622433XC16S024-230 TXV 25200 17 13.5 CBX27UH-030 7622434XC16S024-230 TXV 24400 14.5 12 CBX32M-018/024 7622436XC16S024-230 TXV 24400 15.5 12.2 CBX32MV-018/024 7622438XC16S024-230 TXV 24600 15.5 12.5 CBX32MV-024/030 7622439XC16S024-230 TXV 24800 16 12.5 CBX40UHV-024 7622595XC16S024-230 TXV 24800 15.5 13 CBX40UHV-030 7622597XC16S024-230 TXV 22800 14.5 11.5 CH23-31 EL195UH030XE24B 8604034XC16S024-230 TXV 22800 14.5 11.5 CH23-31 EL195UH045XE24B 8604005XC16S024-230 TXV 23600 15.5 13 CH23-31 EL296UH070XV36B 7622598XC16S024-230 TXV 23600 15.1 12.5 CH23-31 SL280UH070V36A 7622441XC16S024-230 TXV 23800 16 12.5 CH23-31 SL280UH070XV36A 7622600XC16S024-230 TXV 23400 15 12.5 CH23-31 SL280UH090V36B 7622443XC16S024-230 TXV 23600 15.5 13 CH23-31 SLP98UH070XV36B 7622444XC16S024-230 TXV 23800 15.5 12.5 CH23-41 EL195UH030XE24B 8604035Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 11: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 11

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S024-230 TXV 23800 15.5 12.5 CH23-41 EL195UH045XE24B 8604006XC16S024-230 TXV 24600 16 13 CH23-41 EL296UH070XV36B 7622601XC16S024-230 TXV 24800 16 13 CH23-41 SL280UH070V36A 7622448XC16S024-230 TXV 24800 16 13 CH23-41 SL280UH070XV36A 7622603XC16S024-230 TXV 24600 15.1 13 CH23-41 SL280UH090V36B 7622450XC16S024-230 TXV 24800 15.1 13 CH23-41 SL280UH090V48B 7622605XC16S024-230 TXV 24600 16 13 CH23-41 SLP98UH070XV36B 7622451XC16S024-230 TXV 24200 14 12 CH23-41 7622446XC16S024-230 TXV 24200 16 13 CH33-19 SL280UH070V36A 7622455XC16S024-230 TXV 24400 16 13 CH33-19 SL280UH070XV36A 7622606XC16S024-230 TXV 23600 14 11.5 CH33-19 7622453XC16S024-230 TXV 24200 16 12.5 CH33-24/30 SL280UH070V36A 7622459XC16S024-230 TXV 23600 14 11.5 CH33-24/30 7622457XC16S024-230 TXV 23800 15.5 12.5 CH33-25 EL195UH030XE24B 8604036XC16S024-230 TXV 23800 15.5 12.5 CH33-25 EL195UH045XE24B 8604007XC16S024-230 TXV 24800 16 13 CH33-25A SL280UH070V36A 7622462XC16S024-230 TXV 25000 16 13 CH33-25A SL280UH070XV36A 7622610XC16S024-230 TXV 24200 14.5 12 CH33-25A 7622461XC16S024-230 TXV 24600 16 13 CH33-25B EL296UH045XV36B 7622466XC16S024-230 TXV 24600 16 13 CH33-25B EL296UH070XV36B 7622608XC16S024-230 TXV 24400 15.1 13 CH33-25B SL280UH090V36B 7622468XC16S024-230 TXV 24800 15.1 13 CH33-25B SL280UH090V48B 7622611XC16S024-230 TXV 24600 16 13 CH33-25B SLP98UH070XV36B 7622470XC16S024-230 TXV 24000 14 11.5 CH33-25B 7622464XC16S024-230 TXV 23800 16 12.5 CH33-31 EL195UH030XE24B 8604037XC16S024-230 TXV 23800 16 12.5 CH33-31 EL195UH045XE24B 8604008XC16S024-230 TXV 25200 16 13 CH33-31A SL280UH070V36A 7622473XC16S024-230 TXV 25400 16 13 CH33-31A SL280UH070XV36A 7622615XC16S024-230 TXV 24600 14.5 12 CH33-31A 7622471XC16S024-230 TXV 25200 16 13.5 CH33-31B EL296UH045XV36B 7622477XC16S024-230 TXV 25200 17 13.5 CH33-31B EL296UH070XV36B 7622613XC16S024-230 TXV 25200 16 13.5 CH33-31B SL280UH090V36B 7622479XC16S024-230 TXV 25400 16 13 CH33-31B SL280UH090V48B 7622616XC16S024-230 TXV 25200 16 13.5 CH33-31B SLP98UH070XV36B 7622480XC16S024-230 TXV 24800 14.5 12.2 CH33-31B 7622475XC16S024-230 TXV 23800 15.5 12.5 CH33-36 EL195UH030XE24B 8604038XC16S024-230 TXV 23800 15.5 12.5 CH33-36 EL195UH045XE24B 8604009XC16S024-230 TXV 24600 16 13 CH33-36A SL280UH070V36A 7622484XC16S024-230 TXV 24600 16 13 CH33-36A SL280UH070XV36A 7622619XC16S024-230 TXV 24000 14 11.5 CH33-36A 7622482XC16S024-230 TXV 24600 16 13 CH33-36B EL296UH045XV36B 7622488XC16S024-230 TXV 24600 16 13 CH33-36B EL296UH070XV36B 7622618XC16S024-230 TXV 24400 15.1 13 CH33-36B SL280UH090V36B 7622489XC16S024-230 TXV 24600 16 13 CH33-36B SLP98UH070XV36B 7622491XC16S024-230 TXV 24000 14 11.5 CH33-36B 7622486XC16S024-230 TXV 24800 16 13.5 CH33-36C EL296UH090XV36C 7622621XC16S024-230 TXV 24800 16.5 13.5 CH33-36C SLP98UH090XV36C 7622623XC16S024-230 TXV 24000 16 13 CH35-18A SL280UH070V36A 7623646XC16S024-230 TXV 24000 16 13 CH35-18A SL280UH070XV36A 7623509XC16S024-230 TXV 23800 14 11.5 CH35-18A 7623507XC16S024-230 TXV 24000 16 13 CH35-24A SL280UH070V36A 7623648Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 12: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 12

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S024-230 TXV 24000 16 13 CH35-24A SL280UH070XV36A 7623513XC16S024-230 TXV 24000 14.5 12 CH35-24A 7623511XC16S024-230 TXV 23800 15.5 12.5 CH35-24B EL195UH030XE24B 8604039XC16S024-230 TXV 23800 15.5 12.5 CH35-24B EL195UH045XE24B 8604010XC16S024-230 TXV 24000 16 13 CH35-24B EL296UH045XV36B 7623516XC16S024-230 TXV 24000 16 13 CH35-24B EL296UH070XV36B 7623518XC16S024-230 TXV 24000 15.1 13 CH35-24B SL280UH090V36B 7623649XC16S024-230 TXV 24000 15.1 13 CH35-24B SL280UH090V48B 7623519XC16S024-230 TXV 24000 16 13 CH35-24B SLP98UH070XV36B 7623651XC16S024-230 TXV 24000 14.25 12 CH35-24B 7623514XC16S024-230 TXV 24000 16 13 CH35-30A SL280UH070V36A 7623653XC16S024-230 TXV 24000 17 13 CH35-30A SL280UH070XV36A 7623523XC16S024-230 TXV 24000 14.5 12.2 CH35-30A 7623521XC16S024-230 TXV 23800 16 12.5 CH35-30B EL195UH030XE24B 8604040XC16S024-230 TXV 23800 16 12.5 CH35-30B EL195UH045XE24B 8604011XC16S024-230 TXV 24000 16 13 CH35-30B EL296UH045XV36B 7623526XC16S024-230 TXV 24000 16 13 CH35-30B EL296UH070XV36B 7623528XC16S024-230 TXV 24000 16 13 CH35-30B SL280UH090V36B 7623655XC16S024-230 TXV 24000 16 13 CH35-30B SL280UH090V48B 7623529XC16S024-230 TXV 24000 16 13 CH35-30B SLP98UH070XV36B 7623656XC16S024-230 TXV 24000 14.5 12.2 CH35-30B 7623524XC16S024-230 TXV 24000 16 13 CH35-36A SL280UH070V36A 7623658XC16S024-230 TXV 24000 16 13 CH35-36A SL280UH070XV36A 7623533XC16S024-230 TXV 24000 14.25 11.5 CH35-36A 7623531XC16S024-230 TXV 23800 15.5 12.5 CH35-36B EL195UH030XE24B 8604041XC16S024-230 TXV 23800 15.5 12.5 CH35-36B EL195UH045XE24B 8604012XC16S024-230 TXV 24000 16 13 CH35-36B EL296UH045XV36B 7623538XC16S024-230 TXV 24000 16 13 CH35-36B EL296UH070XV36B 7623539XC16S024-230 TXV 24000 15.1 13 CH35-36B SL280UH090V36B 7623660XC16S024-230 TXV 24000 16 13 CH35-36B SLP98UH070XV36B 7623662XC16S024-230 TXV 24000 14.25 11.5 CH35-36B 7623534XC16S024-230 TXV 24000 16 13 CH35-36C EL296UH090XV36C 7623541XC16S024-230 TXV 24000 16 13 CH35-36C SLP98UH090XV36C 7623543XC16S024-230 TXV 24000 14.25 11.5 CH35-36C 7623536XC16S024-230 TXV 25200 17 13.5 CR33-30/36 EL296DF045XV36B 7625417XC16S024-230 TXV 25200 16 13 CR33-30/36 EL296DF070XV48B 7622495XC16S024-230 TXV 25200 16 13 CR33-30/36 SL280DF070V36A 7622657XC16S024-230 TXV 24600 16 13.5 CR33-30/36 SLP98DF070XV36B 7622624XC16S024-230 TXV 25000 16 13.5 CR33-30/36 SLP98DF090XV36C 7622626XC16S024-230 TXV 24400 14.5 12 CR33-30/36 7622493XC16S024-230 TXV 23600 15.1 12.5 CX35-18/24A SL280UH070V36A 8255925XC16S024-230 TXV 23800 15.1 12.5 CX35-18/24A SL280UH070XV36A 8255924XC16S024-230 TXV 23600 15 12.5 CX35-18/24B CBWMV-24B-040 10264192XC16S024-230 TXV 23200 15 12.2 CX35-18/24B EL195UH030XE24B 8604019XC16S024-230 TXV 23200 15 12.2 CX35-18/24B EL195UH045XE24B 8603990XC16S024-230 TXV 23600 15 12.5 CX35-18/24B EL296UH045XV36B 8255929XC16S024-230 TXV 23600 15.5 12.5 CX35-18/24B EL296UH070XV36B 8255926XC16S024-230 TXV 23400 14.5 12.5 CX35-18/24B SL280UH090V36B 8255927XC16S024-230 TXV 23600 15 12.5 CX35-18/24B SLP98UH070XV36B 8255928XC16S024-230 TXV 24800 16 13 CX35-24A SL280UH070V36A 8255932XC16S024-230 TXV 24800 16 13 CX35-24A SL280UH070XV36A 8255931Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 13: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 13

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S024-230 TXV 24200 14 12 CX35-24A 10190774XC16S024-230 TXV 23800 15.5 12.5 CX35-24B EL195UH030XE24B 8604020XC16S024-230 TXV 23800 15.5 12.5 CX35-24B EL195UH045XE24B 8603991XC16S024-230 TXV 24800 16 13 CX35-24B EL296UH045XV36B 8255936XC16S024-230 TXV 24800 16 13.5 CX35-24B EL296UH070XV36B 8255934XC16S024-230 TXV 24600 15.1 13 CX35-24B SL280UH090V36B 8255937XC16S024-230 TXV 24800 16 13 CX35-24B SL280UH090V48B 8255933XC16S024-230 TXV 24600 16 13 CX35-24B SLP98UH070XV36B 8255935XC16S024-230 TXV 24200 14 12 CX35-24B 8255930XC16S024-230 TXV 24600 16 13 CX35-30/36A SL280UH070V36A 8255951XC16S024-230 TXV 24800 16 13 CX35-30/36A SL280UH070XV36A 8255948XC16S024-230 TXV 24000 16 13 CX35-30/36B CBWMV-24B-040 9857552XC16S024-230 TXV 23800 15.5 12.5 CX35-30/36B EL195UH030XE24B 8604021XC16S024-230 TXV 23800 15.5 12.5 CX35-30/36B EL195UH045XE24B 8603992XC16S024-230 TXV 24600 16 13 CX35-30/36B EL296UH045XV36B 8255955XC16S024-230 TXV 24600 16 13 CX35-30/36B EL296UH070XV36B 8255953XC16S024-230 TXV 24400 16 13 CX35-30/36B SL280UH090V36B 8255952XC16S024-230 TXV 24600 16 13 CX35-30/36B SLP98UH070XV36B 8255954XC16S024-230 TXV 24000 14 11.5 CX35-30/36B 8255946XC16S024-230 TXV 24600 16 13.5 CX35-30/36C EL296UH090XV36C 10264194XC16S024-230 TXV 24600 16 13.5 CX35-30/36C SLP98UH090XV36C 10264195XC16S024-230 TXV 25200 17 13 CX35-30A SL280UH070V36A 8255940XC16S024-230 TXV 25400 17 13.5 CX35-30A SL280UH070XV36A 8255939XC16S024-230 TXV 23800 16 12.5 CX35-30B EL195UH030XE24B 8604022XC16S024-230 TXV 23800 16 12.5 CX35-30B EL195UH045XE24B 8603993XC16S024-230 TXV 25200 16 13.5 CX35-30B EL296UH045XV36B 8255944XC16S024-230 TXV 25200 16 13.5 CX35-30B EL296UH070XV36B 10264193XC16S024-230 TXV 25000 16 13.5 CX35-30B SL280UH090V36B 8255945XC16S024-230 TXV 25200 16 13 CX35-30B SL280UH090V48B 8255942XC16S024-230 TXV 25200 16 13.5 CX35-30B SLP98UH070XV36B 8255943XC16S024-230 TXV 24600 14.5 12 CX35-30B 8255938XC16S024-230 TXV 25400 17 13.5 CX35-36A SL280UH070V36A 8255958XC16S024-230 TXV 25400 17 13.5 CX35-36A SL280UH070XV36A 8255957XC16S024-230 TXV 23800 16 13 CX35-36B EL195UH030XE24B 8604023XC16S024-230 TXV 23800 16 13 CX35-36B EL195UH045XE24B 8603994XC16S024-230 TXV 25400 16 13.5 CX35-36B EL296UH045XV36B 8255963XC16S024-230 TXV 25200 17 13.5 CX35-36B EL296UH070XV36B 10264196XC16S024-230 TXV 25200 16 13.5 CX35-36B SL280UH090V36B 8255961XC16S024-230 TXV 25400 16 13.5 CX35-36B SL280UH090V48B 8255960XC16S024-230 TXV 25200 16 13.5 CX35-36B SLP98UH070XV36B 8255962XC16S024-230 TXV 24800 14.5 12.2 CX35-36B 8255956XC16S024-230 TXV 24400 16 13 CX38-36B SL280UH090V36B 10559083XC16S036-230 TXV 35000 14.5 11.7 C35-30/36A EL180UH045E36A 8255965XC16S036-230 TXV 35000 15 11.7 C35-30/36A SL280UH070V36A 8255966XC16S036-230 TXV 35000 15 11.7 C35-30/36A SL280UH070XV36A 8255964XC16S036-230 TXV 35000 15 11.7 C35-30/36B EL180UH070E36B 8255970XC16S036-230 TXV 34800 14.5 11 C35-30/36B EL195UH045XE36B 8255973XC16S036-230 TXV 34800 14.5 11.7 C35-30/36B EL195UH070XE36B 8255971XC16S036-230 TXV 34800 14.5 11 C35-30/36B EL296UH045XE36B 8255967XC16S036-230 TXV 34800 15 11.7 C35-30/36B EL296UH045XV36B 8255976XC16S036-230 TXV 34800 14.5 11.7 C35-30/36B EL296UH070XE36B 8255968Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 14: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 14

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 35200 15 12 C35-30/36B SL280UH090V36B 8255974XC16S036-230 TXV 35000 15 12 C35-30/36B SL280UH090V48B 8255975XC16S036-230 TXV 35200 15 12.2 C35-30/36B SL280UH090XV48B 8255969XC16S036-230 TXV 35000 15 11.7 C35-30/36B SLP98UH070XV36B 8255972XC16S036-230 TXV 34800 15 12 C35-30/36C CBWMV-36C-090 8255981XC16S036-230 TXV 34800 15 12 C35-30/36C EL296UH090XV48C 8255980XC16S036-230 TXV 35000 15 12.2 C35-30/36C EL296UH110XV48C 8255988XC16S036-230 TXV 35400 15 12.2 C35-30/36C EL296UH110XV60C 8255978XC16S036-230 TXV 35400 15 12 C35-30/36C SL280UH090V60C 8255987XC16S036-230 TXV 35400 15.1 12 C35-30/36C SL280UH090XV60C 8255979XC16S036-230 TXV 35200 15 12 C35-30/36C SL280UH110V60C 8255986XC16S036-230 TXV 35400 15 12 C35-30/36C SL280UH110XV60C 8255977XC16S036-230 TXV 35000 15 12 C35-30/36C SLP98UH090XV36C 8255984XC16S036-230 TXV 35200 15 12 C35-30/36C SLP98UH090XV48C 8255985XC16S036-230 TXV 35600 15 12 C35-30/36C SLP98UH090XV60C 8255982XC16S036-230 TXV 35400 15 12.2 C35-30/36C SLP98UH110XV60C 8255983XC16S036-230 TXV 36400 15.5 12.2 C35-36A EL180UH045E36A 8255992XC16S036-230 TXV 36400 15.5 12.2 C35-36A EL180UH045XE36A 8255990XC16S036-230 TXV 36400 15.5 12.2 C35-36A SL280UH070V36A 8255993XC16S036-230 TXV 36400 15.5 12.2 C35-36A SL280UH070XV36A 8255991XC16S036-230 TXV 36400 15.5 12.2 C35-36B EL180UH070E36B 8255996XC16S036-230 TXV 36200 15 11.7 C35-36B EL195UH045XE36B 8256004XC16S036-230 TXV 36200 15.5 12.2 C35-36B EL195UH070XE36B 8256001XC16S036-230 TXV 36200 15 11.7 C35-36B EL296UH045XE36B 8255997XC16S036-230 TXV 36200 15.5 12.2 C35-36B EL296UH045XV36B 8256002XC16S036-230 TXV 36200 15.5 12.2 C35-36B EL296UH070XE36B 8255998XC16S036-230 TXV 36400 15.5 12.2 C35-36B EL296UH070XV36B 8255994XC16S036-230 TXV 36600 15.5 12.5 C35-36B SL280UH090V36B 8256003XC16S036-230 TXV 36600 15.5 12.5 C35-36B SL280UH090V48B 8255999XC16S036-230 TXV 36600 15.5 12.5 C35-36B SL280UH090XV48B 8255995XC16S036-230 TXV 36400 15.5 12.2 C35-36B SLP98UH070XV36B 8256000XC16S036-230 TXV 35800 14 11 C35-36B 8255989XC16S036-230 TXV 36600 15.5 12.2 C35-48B EL180UH070E36B 8256116XC16S036-230 TXV 36600 15.5 12.2 C35-48B EL180UH070XE36B 8256111XC16S036-230 TXV 36400 15 11.7 C35-48B EL195UH045XE36B 8256121XC16S036-230 TXV 36400 15.5 12.2 C35-48B EL195UH070XE36B 8256122XC16S036-230 TXV 36400 15 11.7 C35-48B EL296UH045XE36B 8256112XC16S036-230 TXV 36600 15.5 12.2 C35-48B EL296UH045XV36B 8256120XC16S036-230 TXV 36400 15.5 12.2 C35-48B EL296UH070XE36B 8256113XC16S036-230 TXV 36600 15.5 12.2 C35-48B EL296UH070XV36B 8256114XC16S036-230 TXV 37000 16 12.5 C35-48B SL280UH090V36B 8256117XC16S036-230 TXV 36000 16 12.5 C35-48B SL280UH090V48B 8256118XC16S036-230 TXV 36000 16 12.5 C35-48B SL280UH090XV48B 8256115XC16S036-230 TXV 36600 15.5 12.2 C35-48B SLP98UH070XV36B 8256119XC16S036-230 TXV 36600 15.5 12.5 C35-48C CBWMV-36C-090 8256103XC16S036-230 TXV 37000 16 12.5 C35-48C CBWMV-60C-100 8256101XC16S036-230 TXV 36600 16 12.5 C35-48C EL296UH110XV48C 8256109XC16S036-230 TXV 36600 15.1 12.2 C35-48C SL280UH090V60C 8256123XC16S036-230 TXV 37000 15.1 12.5 C35-48C SL280UH090XV60C 8256102XC16S036-230 TXV 36800 15.1 12.5 C35-48C SL280UH110V60C 8256110XC16S036-230 TXV 36800 15.1 12.5 C35-48C SL280UH110XV60C 8256106Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 15: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 15

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 36800 15.5 12.5 C35-48C SLP98UH090XV36C 8256107XC16S036-230 TXV 36800 16 12.5 C35-48C SLP98UH090XV48C 8256108XC16S036-230 TXV 37200 16 12.5 C35-48C SLP98UH090XV60C 8256104XC16S036-230 TXV 37000 15.5 12.5 C35-48C SLP98UH110XV60C 8256105XC16S036-230 TXV 36200 14 11.7 C35-48C 8256100XC16S036-230 TXV 37000 15.5 12.5 C35-49C EL296UH090XV36C 8256008XC16S036-230 TXV 37600 16 12.5 C35-49C SL280UH090V60C 8256012XC16S036-230 TXV 37600 16 12.5 C35-49C SL280UH090XV60C 8256006XC16S036-230 TXV 37200 15.1 12.5 C35-49C SL280UH110V60C 8256013XC16S036-230 TXV 37400 15.1 12.5 C35-49C SL280UH110XV60C 8256007XC16S036-230 TXV 37000 16 12.5 C35-49C SLP98UH090XV36C 8256014XC16S036-230 TXV 37400 16 12.5 C35-49C SLP98UH090XV48C 8256009XC16S036-230 TXV 37600 16 12.5 C35-49C SLP98UH090XV60C 8256010XC16S036-230 TXV 37400 16 12.5 C35-49C SLP98UH110XV60C 8256011XC16S036-230 TXV 36400 14 11.7 C35-49C 8256005XC16S036-230 TXV 36400 16 12.5 C35-50/60C EL296UH110XV48C 8256015XC16S036-230 TXV 36000 15.5 12.2 CBA27UHE-036 10259503XC16S036-230 TXV 36000 16 12.5 CBA27UHE-042 10259504XC16S036-230 TXV 35400 15 12 CBX25UHV-030 7622704XC16S036-230 TXV 36000 15.5 12.2 CBX25UHV-036 7622706XC16S036-230 TXV 37000 16 13 CBX25UHV-042 7622714XC16S036-230 TXV 35800 15 12.2 CBX27UH-036 7621077XC16S036-230 TXV 37000 16 12.5 CBX27UH-042 7621079XC16S036-230 TXV 35200 14.5 11.7 CBX32M-030 7621081XC16S036-230 TXV 35400 14.5 11.7 CBX32M-036 7621082XC16S036-230 TXV 35600 14.5 11.7 CBX32M-042 7621084XC16S036-230 TXV 35600 15 12 CBX32MV-024/030 7621097XC16S036-230 TXV 36000 15.5 12 CBX32MV-036 7621098XC16S036-230 TXV 37000 16 12.5 CBX32MV-048 7621209XC16S036-230 TXV 35400 15 11.7 CBX40UHV-030 7621495XC16S036-230 TXV 35200 15 12 CBX40UHV-036 7621497XC16S036-230 TXV 36600 15.5 12.2 CBX40UHV-042 7621499XC16S036-230 TXV 36600 15 12.5 CBX40UHV-048 7621500XC16S036-230 TXV 35400 15 12 CH23-41 CBWMV-36B-070 9060119XC16S036-230 TXV 35600 15 12 CH23-41 EL180UH070E36B 7621504XC16S036-230 TXV 35600 14.5 11.7 CH23-41 EL195UH045XE36B 7621211XC16S036-230 TXV 35400 15 12 CH23-41 EL195UH070XE36B 7621213XC16S036-230 TXV 35600 14.5 11.7 CH23-41 EL296UH045XE36B 7621505XC16S036-230 TXV 35400 15 12 CH23-41 EL296UH070XE36B 7621507XC16S036-230 TXV 35400 15.5 12 CH23-41 EL296UH070XV36B 7621502XC16S036-230 TXV 35600 15.5 12.2 CH23-41 EL296UH090XV36C 7621508XC16S036-230 TXV 35400 15.5 12.2 CH23-41 EL296UH090XV48C 7621510XC16S036-230 TXV 36000 15.5 12.2 CH23-41 EL296UH090XV60C 7621512XC16S036-230 TXV 35600 15.5 12.5 CH23-41 EL296UH110XV48C 7621214XC16S036-230 TXV 36000 15.5 12.5 CH23-41 EL296UH110XV60C 7621513XC16S036-230 TXV 35400 15.5 12.5 CH23-41 SL280UH090V36B 7621100XC16S036-230 TXV 35600 15 12.5 CH23-41 SL280UH090V48B 7621102XC16S036-230 TXV 36000 15.1 12.5 CH23-41 SL280UH090V60C 7621103XC16S036-230 TXV 35600 15.5 12.5 CH23-41 SL280UH090XV48B 7621515XC16S036-230 TXV 36000 15.1 12.5 CH23-41 SL280UH090XV60C 7621517XC16S036-230 TXV 35800 15.1 12.2 CH23-41 SL280UH110V60C 7621105Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 16: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 16

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 35800 15.1 12.2 CH23-41 SL280UH110XV60C 7621518XC16S036-230 TXV 35400 15.5 12 CH23-41 SLP98UH070XV36B 7621107XC16S036-230 TXV 35600 15.5 12.2 CH23-41 SLP98UH090XV36C 7621108XC16S036-230 TXV 35400 15.5 12.2 CH23-41 SLP98UH090XV48C 7621110XC16S036-230 TXV 36000 15.5 12.2 CH23-41 SLP98UH090XV60C 7621190XC16S036-230 TXV 36000 15.5 12.5 CH23-41 SLP98UH110XV60C 7621192XC16S036-230 TXV 35600 15 12.5 CH23-51 EL180UH070E36B 7621198XC16S036-230 TXV 35600 15 11.7 CH23-51 EL195UH045XE36B 7621193XC16S036-230 TXV 35600 15 12.2 CH23-51 EL195UH070XE36B 7621195XC16S036-230 TXV 35600 15 11.7 CH23-51 EL296UH045XE36B 7621520XC16S036-230 TXV 35600 15 12.2 CH23-51 EL296UH070XE36B 7621522XC16S036-230 TXV 35800 15.5 12.5 CH23-51 EL296UH110XV48C 7621196XC16S036-230 TXV 36000 15.5 12 CH23-65 EL180UH070E36B 7621448XC16S036-230 TXV 36000 15 11.7 CH23-65 EL195UH045XE36B 7621200XC16S036-230 TXV 36000 15 12.2 CH23-65 EL195UH070XE36B 7621201XC16S036-230 TXV 36000 15 11.7 CH23-65 EL296UH045XE36B 7621450XC16S036-230 TXV 36000 15 12.2 CH23-65 EL296UH070XE36B 7620892XC16S036-230 TXV 36200 15.5 12.5 CH23-65 EL296UH090XV36C 7621523XC16S036-230 TXV 36000 15.5 12.5 CH23-65 EL296UH090XV48C 7620894XC16S036-230 TXV 36600 16 12.5 CH23-65 EL296UH090XV60C 7620895XC16S036-230 TXV 36400 16 12.5 CH23-65 EL296UH110XV60C 7620897XC16S036-230 TXV 36600 15.1 12.5 CH23-65 SL280UH090V60C 7621203XC16S036-230 TXV 36600 15.1 12.5 CH23-65 SL280UH090XV60C 7620900XC16S036-230 TXV 36400 15.1 12.5 CH23-65 SL280UH110V60C 7621205XC16S036-230 TXV 36400 15.1 12.5 CH23-65 SL280UH110XV60C 7620898XC16S036-230 TXV 36200 15.5 12.5 CH23-65 SLP98UH090XV36C 7621206XC16S036-230 TXV 36000 15.5 12.5 CH23-65 SLP98UH090XV48C 7621208XC16S036-230 TXV 36600 15.5 12.5 CH23-65 SLP98UH090XV60C 7621058XC16S036-230 TXV 36400 15.5 12.5 CH23-65 SLP98UH110XV60C 7621059XC16S036-230 TXV 36200 15 12 CH33-31B EL296UH045XV36B 7621061XC16S036-230 TXV 35600 15 12.2 CH33-36 EL296UH090XV36C 7620903XC16S036-230 TXV 35400 15.5 12.2 CH33-36 EL296UH090XV48C 7620905XC16S036-230 TXV 36000 15.5 12.2 CH33-36 EL296UH090XV60C 7620906XC16S036-230 TXV 35800 15.5 12.2 CH33-36 EL296UH110XV60C 7620935XC16S036-230 TXV 36000 15.1 12.2 CH33-36 SL280UH090V60C 7620913XC16S036-230 TXV 36000 15.1 12.2 CH33-36 SL280UH090XV60C 7620938XC16S036-230 TXV 35800 15 12 CH33-36 SL280UH110V60C 7620914XC16S036-230 TXV 35800 15.1 12 CH33-36 SL280UH110XV60C 7620973XC16S036-230 TXV 35600 15 12.2 CH33-36 SLP98UH090XV36C 7620916XC16S036-230 TXV 35400 15 12.2 CH33-36 SLP98UH090XV48C 7620918XC16S036-230 TXV 36000 15.5 12.2 CH33-36 SLP98UH090XV60C 7620879XC16S036-230 TXV 35800 15.5 12.2 CH33-36 SLP98UH110XV60C 7620881XC16S036-230 TXV 35400 15 11.7 CH33-36A EL180UH045E36A 7620975XC16S036-230 TXV 34800 14.5 11.7 CH33-36A SL280UH070V36A 7621817XC16S036-230 TXV 34800 14.5 11.7 CH33-36A SL280UH070XV36A 7621819XC16S036-230 TXV 35400 15 11.7 CH33-36B EL180UH070XE36B 7620977XC16S036-230 TXV 34600 14.5 11 CH33-36B EL195UH045XE36B 7621063XC16S036-230 TXV 34800 14.5 11.7 CH33-36B EL195UH070XE36B 7621064XC16S036-230 TXV 34600 14.5 11 CH33-36B EL296UH045XE36B 7620979XC16S036-230 TXV 34800 15 11.7 CH33-36B EL296UH045XV36B 7621066XC16S036-230 TXV 34800 14.5 11.7 CH33-36B EL296UH070XE36B 7620980Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 17: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 17

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 34800 15 11.7 CH33-36B EL296UH070XV36B 7620902XC16S036-230 TXV 35000 15 12 CH33-36B SL280UH090V48B 7620937XC16S036-230 TXV 35000 15 12 CH33-36B SL280UH090XV48B 7620908XC16S036-230 TXV 34800 15 11.7 CH33-36B SLP98UH070XV36B 7620910XC16S036-230 TXV 35600 15.5 12.2 CH33-36C EL296UH110XV48C 7620911XC16S036-230 TXV 36000 15.5 12 CH33-42B EL180UH070E36B 7620984XC16S036-230 TXV 35600 14.5 11.7 CH33-42B EL195UH045XE36B 7620919XC16S036-230 TXV 35600 14.5 11.7 CH33-42B EL195UH070XE36B 7620882XC16S036-230 TXV 35600 14.5 11.7 CH33-42B EL296UH045XE36B 7620985XC16S036-230 TXV 35800 15 11.7 CH33-42B EL296UH045XV36B 7620884XC16S036-230 TXV 35600 14.5 11.7 CH33-42B EL296UH070XE36B 7620987XC16S036-230 TXV 35800 15 12 CH33-42B EL296UH070XV36B 7620989XC16S036-230 TXV 36000 15.5 12.2 CH33-42B SL280UH090V36B 7620885XC16S036-230 TXV 35800 15 12.2 CH33-42B SL280UH090V48B 7620887XC16S036-230 TXV 36000 15 12.2 CH33-42B SL280UH090XV48B 7620982XC16S036-230 TXV 35800 15 12 CH33-42B SLP98UH070XV36B 7620889XC16S036-230 TXV 36800 15.5 12.5 CH33-43 EL296UH090XV36C 7620943XC16S036-230 TXV 36600 16 12.5 CH33-43 EL296UH090XV48C 7620945XC16S036-230 TXV 37200 16 12.5 CH33-43 EL296UH090XV60C 7620946XC16S036-230 TXV 37200 16 12.5 CH33-43 EL296UH110XV60C 7620948XC16S036-230 TXV 37200 15.1 12.5 CH33-43 SL280UH090V60C 7620934XC16S036-230 TXV 37200 16 12.5 CH33-43 SL280UH090XV60C 7621023XC16S036-230 TXV 37000 15.1 12.5 CH33-43 SL280UH110V60C 7620958XC16S036-230 TXV 37000 15.1 12.5 CH33-43 SL280UH110XV60C 7621025XC16S036-230 TXV 36800 15.5 12.5 CH33-43 SLP98UH090XV36C 7620960XC16S036-230 TXV 37000 16 12.5 CH33-43 SLP98UH090XV48C 7620961XC16S036-230 TXV 37200 16 12.5 CH33-43 SLP98UH090XV60C 7620963XC16S036-230 TXV 37200 16 12.5 CH33-43 SLP98UH110XV60C 7620965XC16S036-230 TXV 37200 16 12.5 CH33-43B EL180UH070E36B 7621027XC16S036-230 TXV 37000 15 12 CH33-43B EL195UH045XE36B 7620921XC16S036-230 TXV 37000 15 12.2 CH33-43B EL195UH070XE36B 7620922XC16S036-230 TXV 37000 15 12 CH33-43B EL296UH045XE36B 7621028XC16S036-230 TXV 37000 15.5 12.2 CH33-43B EL296UH045XV36B 7620924XC16S036-230 TXV 37000 15 12.2 CH33-43B EL296UH070XE36B 7620940XC16S036-230 TXV 37000 15.5 12.2 CH33-43B EL296UH070XV36B 7620942XC16S036-230 TXV 37600 16 12.5 CH33-43B SL280UH090V36B 7620925XC16S036-230 TXV 36000 16 12.5 CH33-43B SL280UH090V48B 7620927XC16S036-230 TXV 36000 16 12.5 CH33-43B SL280UH090XV48B 7620950XC16S036-230 TXV 37000 15.5 12.2 CH33-43B SLP98UH070XV36B 7620929XC16S036-230 TXV 36800 14 11.7 CH33-43B 7620890XC16S036-230 TXV 36800 16 12.5 CH33-43C EL296UH110XV48C 7620932XC16S036-230 TXV 36200 14 11.7 CH33-43C 7620930XC16S036-230 TXV 36000 14 11 CH33-44/48 7620967XC16S036-230 TXV 36400 15.5 12.2 CH33-44/48B EL180UH070E36B 7621032XC16S036-230 TXV 36400 15.5 12.2 CH33-44/48B EL180UH070XE36B 7621035XC16S036-230 TXV 36200 14.5 11.7 CH33-44/48B EL195UH045XE36B 7620968XC16S036-230 TXV 36200 15 11.7 CH33-44/48B EL195UH070XE36B 7620970XC16S036-230 TXV 36200 14.5 11.7 CH33-44/48B EL296UH045XE36B 7621034XC16S036-230 TXV 36200 15 12 CH33-44/48B EL296UH045XV36B 7620972XC16S036-230 TXV 36200 15.5 12 CH33-44/48B EL296UH070XV36B 7621037XC16S036-230 TXV 36800 15.5 12.5 CH33-44/48B SL280UH090V36B 7621008Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 18: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 18

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 36400 15 12.2 CH33-44/48B SL280UH090V48B 7621009XC16S036-230 TXV 36400 15.5 12.2 CH33-44/48B SL280UH090XV48B 7621030XC16S036-230 TXV 36400 15.5 12.2 CH33-44/48B SLP98UH070XV36B 7620951XC16S036-230 TXV 36600 15.5 12.5 CH33-48 EL296UH090XV36C 7621143XC16S036-230 TXV 36400 15.5 12.5 CH33-48 EL296UH090XV48C 7621144XC16S036-230 TXV 37000 16 12.5 CH33-48 EL296UH090XV60C 7621146XC16S036-230 TXV 36800 16 12.5 CH33-48 EL296UH110XV60C 7621148XC16S036-230 TXV 37000 15.1 12.5 CH33-48 SL280UH090V60C 7621011XC16S036-230 TXV 37000 15.1 12.5 CH33-48 SL280UH090XV60C 7621141XC16S036-230 TXV 36800 15.1 12.2 CH33-48 SL280UH110V60C 7621013XC16S036-230 TXV 36800 15.1 12.5 CH33-48 SL280UH110XV60C 7621039XC16S036-230 TXV 36600 15.5 12.5 CH33-48 SLP98UH090XV36C 7621015XC16S036-230 TXV 36800 16 12.5 CH33-48 SLP98UH090XV48C 7621016XC16S036-230 TXV 37000 15.5 12.5 CH33-48 SLP98UH090XV60C 7621018XC16S036-230 TXV 36800 15.5 12.5 CH33-48 SLP98UH110XV60C 7621020XC16S036-230 TXV 36000 14 11 CH33-48 7620953XC16S036-230 TXV 36600 16 12.5 CH33-48C EL296UH110XV48C 7620955XC16S036-230 TXV 37000 16 12.5 CH33-50/60C EL296UH110XV48C 7621021XC16S036-230 TXV 36000 15.1 12 CH35-30B EL296UH045XV36B 7623750XC16S036-230 TXV 35000 14.5 11.5 CH35-36A EL180UH045E36A 7623544XC16S036-230 TXV 34800 14.5 11.5 CH35-36A SL280UH070V36A 7623663XC16S036-230 TXV 34800 14.5 11.5 CH35-36A SL280UH070XV36A 7623546XC16S036-230 TXV 35200 15.1 11.5 CH35-36B EL180UH070XE36B 7623547XC16S036-230 TXV 34800 14.5 11.5 CH35-36B EL195UH045XE36B 7623549XC16S036-230 TXV 34800 14.5 11.5 CH35-36B EL195UH070XE36B 7623551XC16S036-230 TXV 34800 14.5 11 CH35-36B EL296UH045XE36B 7623554XC16S036-230 TXV 35000 15.1 11.5 CH35-36B EL296UH045XV36B 7623552XC16S036-230 TXV 34800 14.5 11.5 CH35-36B EL296UH070XE36B 7623556XC16S036-230 TXV 35000 15 11.5 CH35-36B EL296UH070XV36B 7623557XC16S036-230 TXV 35400 15.1 12 CH35-36B SL280UH090V36B 7623665XC16S036-230 TXV 35200 15 12.2 CH35-36B SL280UH090V48B 7623752XC16S036-230 TXV 35200 15.1 12.2 CH35-36B SL280UH090XV48B 7623559XC16S036-230 TXV 35000 15 11.5 CH35-36B SLP98UH070XV36B 7623667XC16S036-230 TXV 35600 15.1 12.2 CH35-36C EL296UH090XV36C 7623560XC16S036-230 TXV 35400 15.5 12.2 CH35-36C EL296UH090XV48C 7623562XC16S036-230 TXV 36000 15.5 12.2 CH35-36C EL296UH090XV60C 7623564XC16S036-230 TXV 35600 15.5 12.2 CH35-36C EL296UH110XV48C 7623565XC16S036-230 TXV 35800 15.5 12.2 CH35-36C EL296UH110XV60C 7623567XC16S036-230 TXV 36000 15.1 12.2 CH35-36C SL280UH090V60C 7623668XC16S036-230 TXV 36000 15.1 12.2 CH35-36C SL280UH090XV60C 7623569XC16S036-230 TXV 35800 15.1 12.2 CH35-36C SL280UH110V60C 7623570XC16S036-230 TXV 35800 15.1 12.2 CH35-36C SL280UH110XV60C 7623572XC16S036-230 TXV 35600 15.1 12.2 CH35-36C SLP98UH090XV36C 7623670XC16S036-230 TXV 35400 15.1 12.2 CH35-36C SLP98UH090XV48C 7623672XC16S036-230 TXV 35800 15.5 12.2 CH35-36C SLP98UH090XV60C 7623674XC16S036-230 TXV 36000 15.5 12.2 CH35-36C SLP98UH110XV60C 7623675XC16S036-230 TXV 36000 16 12.5 CH35-42B EL180UH070E36B 7623575XC16S036-230 TXV 36000 15.1 12 CH35-42B EL195UH045XE36B 7623577XC16S036-230 TXV 36000 15.1 12.2 CH35-42B EL195UH070XE36B 7623578XC16S036-230 TXV 36000 15.1 12 CH35-42B EL296UH045XE36B 7623582XC16S036-230 TXV 36000 15.5 12.2 CH35-42B EL296UH045XV36B 7623580Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 19: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 19

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 36000 15.1 12.2 CH35-42B EL296UH070XE36B 7623583XC16S036-230 TXV 36000 15.5 12.2 CH35-42B EL296UH070XV36B 7623585XC16S036-230 TXV 36000 16 12.5 CH35-42B SL280UH090V36B 7623677XC16S036-230 TXV 36000 15.5 12.5 CH35-42B SL280UH090V48B 7623679XC16S036-230 TXV 36000 15.5 12.5 CH35-42B SL280UH090XV48B 7623587XC16S036-230 TXV 36000 15.5 12.2 CH35-42B SLP98UH070XV36B 7623680XC16S036-230 TXV 36000 14.25 11.5 CH35-42B 7623574XC16S036-230 TXV 36000 15.5 12.5 CH35-42C EL296UH090XV36C 7623590XC16S036-230 TXV 36000 16 12.5 CH35-42C EL296UH090XV48C 7623592XC16S036-230 TXV 36000 16 12.5 CH35-42C EL296UH090XV60C 7623593XC16S036-230 TXV 36000 16 12.5 CH35-42C EL296UH110XV48C 7623595XC16S036-230 TXV 36000 16 12.5 CH35-42C EL296UH110XV60C 7623597XC16S036-230 TXV 36000 16 12.5 CH35-42C SL280UH090V60C 7623682XC16S036-230 TXV 36000 16 12.5 CH35-42C SL280UH090XV60C 7623599XC16S036-230 TXV 36000 15.1 12.5 CH35-42C SL280UH110V60C 7623600XC16S036-230 TXV 36000 15.1 12.5 CH35-42C SL280UH110XV60C 7623602XC16S036-230 TXV 36000 15.5 12.5 CH35-42C SLP98UH090XV36C 7623684XC16S036-230 TXV 36000 16 12.5 CH35-42C SLP98UH090XV48C 7623685XC16S036-230 TXV 36000 16 12.5 CH35-42C SLP98UH090XV60C 7623687XC16S036-230 TXV 36000 16 12.5 CH35-42C SLP98UH110XV60C 7623689XC16S036-230 TXV 36000 14.25 11.5 CH35-42C 7623588XC16S036-230 TXV 36000 15.5 12.2 CH35-48B EL180UH070E36B 7623606XC16S036-230 TXV 36000 15 11.5 CH35-48B EL195UH045XE36B 7623607XC16S036-230 TXV 36000 15 12 CH35-48B EL195UH070XE36B 7623609XC16S036-230 TXV 36000 15 11.5 CH35-48B EL296UH045XE36B 7623613XC16S036-230 TXV 36000 15.5 12 CH35-48B EL296UH045XV36B 7623611XC16S036-230 TXV 36000 15 12 CH35-48B EL296UH070XE36B 7623614XC16S036-230 TXV 36000 15.5 12.2 CH35-48B EL296UH070XV36B 7623616XC16S036-230 TXV 36000 15.5 12.5 CH35-48B SL280UH090V36B 7623690XC16S036-230 TXV 36000 15.1 12.5 CH35-48B SL280UH090V48B 7623692XC16S036-230 TXV 36000 15.5 12.5 CH35-48B SL280UH090XV48B 7623618XC16S036-230 TXV 36000 15.5 12.2 CH35-48B SLP98UH070XV36B 7623693XC16S036-230 TXV 36000 14 11.5 CH35-48B 7623604XC16S036-230 TXV 36000 15.5 12.5 CH35-48C EL296UH090XV36C 7623621XC16S036-230 TXV 36000 16 12.5 CH35-48C EL296UH090XV48C 7623623XC16S036-230 TXV 36000 16 12.5 CH35-48C EL296UH090XV60C 7623625XC16S036-230 TXV 36000 16 12.5 CH35-48C EL296UH110XV48C 7623627XC16S036-230 TXV 36000 16 12.5 CH35-48C EL296UH110XV60C 7623628XC16S036-230 TXV 36000 16 12.5 CH35-48C SL280UH090V60C 7623695XC16S036-230 TXV 36000 16 12.5 CH35-48C SL280UH090XV60C 7623630XC16S036-230 TXV 36000 15.1 12.5 CH35-48C SL280UH110V60C 7623632XC16S036-230 TXV 36000 15.1 12.5 CH35-48C SL280UH110XV60C 7623634XC16S036-230 TXV 36000 15.5 12.5 CH35-48C SLP98UH090XV36C 7623639XC16S036-230 TXV 36000 16 12.5 CH35-48C SLP98UH090XV48C 7623641XC16S036-230 TXV 36000 16 12.5 CH35-48C SLP98UH090XV60C 7623642XC16S036-230 TXV 36000 16 12.5 CH35-48C SLP98UH110XV60C 7623644XC16S036-230 TXV 36000 14 11.5 CH35-48C 7623620XC16S036-230 TXV 36000 16 12.5 CH35-51C EL296UH110XV48C 9977273XC16S036-230 TXV 36000 14.25 11.5 CH35-51C 7623635XC16S036-230 TXV 35600 15 11.7 CR33-30/36 EL180DF070E36B 7621172XC16S036-230 TXV 35200 14.5 11 CR33-30/36 EL195DF045XE36B 7621069Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 20: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 20

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 35200 14.5 11 CR33-30/36 EL296DF045XE36B 7621170XC16S036-230 TXV 35400 15.5 12 CR33-30/36 EL296DF045XV36B 7625419XC16S036-230 TXV 35600 15 12 CR33-30/36 EL296DF070XV48B 7625410XC16S036-230 TXV 35600 15 12 CR33-30/36 EL296DF090XV60C 7621169XC16S036-230 TXV 35600 15 12 CR33-30/36 EL296DF110XV60C 7621167XC16S036-230 TXV 35400 15 11.7 CR33-30/36 SL280DF070V36A 7621068XC16S036-230 TXV 35600 15 12 CR33-30/36 SL280DF090V48B 7621074XC16S036-230 TXV 36000 15.1 12.2 CR33-30/36 SL280DF090V60C 7621071XC16S036-230 TXV 35600 15.1 12.2 CR33-30/36 SL280DF110V60C 7621072XC16S036-230 TXV 35200 15 12 CR33-30/36 SLP98DF070XV36B 7621156XC16S036-230 TXV 35400 15 12 CR33-30/36 SLP98DF090XV36C 7621154XC16S036-230 TXV 35400 15 12 CR33-30/36 SLP98DF090XV48C 7621152XC16S036-230 TXV 35600 15 12 CR33-30/36 SLP98DF090XV60C 7621151XC16S036-230 TXV 35600 15 12 CR33-30/36 SLP98DF110XV60C 7621149XC16S036-230 TXV 36200 15 12 CR33-48 EL180DF070E36B 7621182XC16S036-230 TXV 36000 15 11.7 CR33-48 EL195DF045XE36B 7621085XC16S036-230 TXV 36000 15 12.2 CR33-48 EL195DF070XE48B 7621087XC16S036-230 TXV 35800 14.5 11.7 CR33-48 EL296DF045XE36B 7621183XC16S036-230 TXV 35800 14.5 12.2 CR33-48 EL296DF070XE48B 7621185XC16S036-230 TXV 36000 15 12 CR33-48 EL296DF070XV48B 7625409XC16S036-230 TXV 36200 15.5 12.2 CR33-48 EL296DF090XV60C 7621187XC16S036-230 TXV 36200 15.5 12.2 CR33-48 EL296DF110XV60C 7621188XC16S036-230 TXV 36600 15.1 12.5 CR33-48 SL280DF090V60C 7621089XC16S036-230 TXV 36200 15.1 12.5 CR33-48 SL280DF110V60C 7621090XC16S036-230 TXV 35800 15.5 12.2 CR33-48 SLP98DF070XV36B 7621180XC16S036-230 TXV 36000 15.5 12.2 CR33-48 SLP98DF090XV36C 7621178XC16S036-230 TXV 36000 15.5 12.2 CR33-48 SLP98DF090XV48C 7621177XC16S036-230 TXV 36200 15.5 12.2 CR33-48 SLP98DF090XV60C 7621175XC16S036-230 TXV 36200 15.5 12.2 CR33-48 SLP98DF110XV60C 7621174XC16S036-230 TXV 35800 15.5 12 CR33-48B EL296DF045XV36B 7625418XC16S036-230 TXV 36200 15.5 12.2 CR33-48B SL280DF090V48B 7620956XC16S036-230 TXV 35000 14.5 11.7 CX35-30/36A EL180UH045E36A 8256024XC16S036-230 TXV 35000 15 11.7 CX35-30/36A SL280UH070V36A 8256029XC16S036-230 TXV 35000 15 11.7 CX35-30/36A SL280UH070XV36A 8256022XC16S036-230 TXV 35000 15 11.7 CX35-30/36B EL180UH070E36B 8256035XC16S036-230 TXV 34800 14.5 11 CX35-30/36B EL195UH045XE36B 8256039XC16S036-230 TXV 34800 14.5 11.7 CX35-30/36B EL195UH070XE36B 8256038XC16S036-230 TXV 34800 14.5 11 CX35-30/36B EL296UH045XE36B 8256036XC16S036-230 TXV 34800 15 11.7 CX35-30/36B EL296UH045XV36B 8256043XC16S036-230 TXV 34800 14.5 11.7 CX35-30/36B EL296UH070XE36B 8256037XC16S036-230 TXV 35000 15 11.7 CX35-30/36B EL296UH070XV36B 8256033XC16S036-230 TXV 35200 15 12 CX35-30/36B SL280UH090V36B 8256041XC16S036-230 TXV 35000 15 12 CX35-30/36B SL280UH090V48B 8256042XC16S036-230 TXV 35200 15 12.2 CX35-30/36B SL280UH090XV48B 8256034XC16S036-230 TXV 35000 15 11.7 CX35-30/36B SLP98UH070XV36B 8256040XC16S036-230 TXV 34800 15 12 CX35-30/36C CBWMV-36C-090 8256023XC16S036-230 TXV 35000 15 12 CX35-30/36C EL195UH090XE48C 8256016XC16S036-230 TXV 35000 15 12 CX35-30/36C EL296UH090XV36C 8256019XC16S036-230 TXV 34800 15 12 CX35-30/36C EL296UH090XV48C 8256021XC16S036-230 TXV 35000 15 12.2 CX35-30/36C EL296UH110XV48C 8256032XC16S036-230 TXV 35400 15 12.2 CX35-30/36C EL296UH110XV60C 8256020Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 21: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 21

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 35400 15 12 CX35-30/36C SL280UH090V60C 8256031XC16S036-230 TXV 35400 15.1 12 CX35-30/36C SL280UH090XV60C 8256017XC16S036-230 TXV 35200 15 12 CX35-30/36C SL280UH110V60C 8256030XC16S036-230 TXV 35400 15 12 CX35-30/36C SL280UH110XV60C 8256018XC16S036-230 TXV 35000 15 12 CX35-30/36C SLP98UH090XV36C 8256027XC16S036-230 TXV 35200 15 12 CX35-30/36C SLP98UH090XV48C 8256028XC16S036-230 TXV 35600 15 12 CX35-30/36C SLP98UH090XV60C 8256025XC16S036-230 TXV 35400 15 12.2 CX35-30/36C SLP98UH110XV60C 8256026XC16S036-230 TXV 36400 15.5 12.2 CX35-36A EL180UH045XE36A 8256046XC16S036-230 TXV 36400 15.5 12.2 CX35-36A SL280UH070V36A 8256047XC16S036-230 TXV 36400 15.5 12.2 CX35-36A SL280UH070XV36A 8256045XC16S036-230 TXV 36400 15.5 12.2 CX35-36B EL180UH070E36B 10090929XC16S036-230 TXV 36400 15.5 12.2 CX35-36B EL180UH070XE36B 8256051XC16S036-230 TXV 36200 15 11.7 CX35-36B EL195UH045XE36B 8256058XC16S036-230 TXV 36200 15.5 12.2 CX35-36B EL195UH070XE36B 8256055XC16S036-230 TXV 36000 15 11.7 CX35-36B EL296UH045XE36B 8256052XC16S036-230 TXV 36200 15.5 12.2 CX35-36B EL296UH045XV36B 8256056XC16S036-230 TXV 36200 15.5 12.2 CX35-36B EL296UH070XE36B 8256048XC16S036-230 TXV 36400 15.5 12.2 CX35-36B EL296UH070XV36B 8256050XC16S036-230 TXV 36600 15.5 12.5 CX35-36B SL280UH090V36B 8256057XC16S036-230 TXV 36600 15.5 12.5 CX35-36B SL280UH090V48B 8256053XC16S036-230 TXV 36600 15.5 12.5 CX35-36B SL280UH090XV48B 8256049XC16S036-230 TXV 36400 15.5 12.2 CX35-36B SLP98UH070XV36B 8256054XC16S036-230 TXV 35800 14 11 CX35-36B 8256044XC16S036-230 TXV 36600 15.5 12.2 CX35-48B EL180UH070E36B 8256077XC16S036-230 TXV 36400 15 11.7 CX35-48B EL195UH045XE36B 8256084XC16S036-230 TXV 36400 15.5 12.2 CX35-48B EL195UH070XE36B 8256085XC16S036-230 TXV 36400 15 11.7 CX35-48B EL296UH045XE36B 8256075XC16S036-230 TXV 36600 15.5 12.2 CX35-48B EL296UH045XV36B 8256082XC16S036-230 TXV 36400 15.5 12.2 CX35-48B EL296UH070XE36B 8256079XC16S036-230 TXV 36600 15.5 12.2 CX35-48B EL296UH070XV36B 8256076XC16S036-230 TXV 37000 16 12.5 CX35-48B SL280UH090V36B 8256083XC16S036-230 TXV 36000 16 12.5 CX35-48B SL280UH090V48B 8256080XC16S036-230 TXV 36000 16 12.5 CX35-48B SL280UH090XV48B 8256078XC16S036-230 TXV 36600 15.5 12.2 CX35-48B SLP98UH070XV36B 8256081XC16S036-230 TXV 36600 15.5 12.5 CX35-48C CBWMV-36C-090 8256066XC16S036-230 TXV 37000 16 12.5 CX35-48C CBWMV-60C-100 8256065XC16S036-230 TXV 36600 15.5 12.5 CX35-48C EL296UH090XV36C 8256061XC16S036-230 TXV 36400 15.5 12.5 CX35-48C EL296UH090XV48C 8256062XC16S036-230 TXV 37200 16 12.5 CX35-48C EL296UH090XV60C 8256063XC16S036-230 TXV 36600 16 12.5 CX35-48C EL296UH110XV48C 8256074XC16S036-230 TXV 37000 16 12.5 CX35-48C EL296UH110XV60C 8256064XC16S036-230 TXV 37000 15.1 12.5 CX35-48C SL280UH090V60C 8256060XC16S036-230 TXV 37000 15.1 12.5 CX35-48C SL280UH090XV60C 8256067XC16S036-230 TXV 36800 15.1 12.5 CX35-48C SL280UH110V60C 8256071XC16S036-230 TXV 37000 15.1 12.5 CX35-48C SL280UH110XV60C 8256068XC16S036-230 TXV 36800 15.5 12.5 CX35-48C SLP98UH090XV36C 8256072XC16S036-230 TXV 36800 16 12.5 CX35-48C SLP98UH090XV48C 8256073XC16S036-230 TXV 37200 16 12.5 CX35-48C SLP98UH090XV60C 8256069XC16S036-230 TXV 37000 15.5 12.5 CX35-48C SLP98UH110XV60C 8256070XC16S036-230 TXV 36200 14 11.7 CX35-48C 8256059Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 22: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 22

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S036-230 TXV 37000 15.5 12.5 CX35-49C EL296UH090XV36C 8256089XC16S036-230 TXV 36800 16 12.5 CX35-49C EL296UH090XV48C 8256092XC16S036-230 TXV 37600 16 12.5 CX35-49C EL296UH090XV60C 8256090XC16S036-230 TXV 37400 16 12.5 CX35-49C EL296UH110XV60C 8256088XC16S036-230 TXV 37600 16 12.5 CX35-49C SL280UH090V60C 8256098XC16S036-230 TXV 37600 16 12.5 CX35-49C SL280UH090XV60C 8256087XC16S036-230 TXV 37200 15.1 12.5 CX35-49C SL280UH110V60C 8256095XC16S036-230 TXV 37400 15.1 12.5 CX35-49C SL280UH110XV60C 8256091XC16S036-230 TXV 37000 16 12.5 CX35-49C SLP98UH090XV36C 8256096XC16S036-230 TXV 37400 16 12.5 CX35-49C SLP98UH090XV48C 8256097XC16S036-230 TXV 37600 16 12.5 CX35-49C SLP98UH090XV60C 8256093XC16S036-230 TXV 37400 16 12.5 CX35-49C SLP98UH110XV60C 8256094XC16S036-230 TXV 36400 14 11.7 CX35-49C 8256086XC16S036-230 TXV 36400 16 12.5 CX35-50/60C EL296UH110XV48C 8256099XC16S036-230 TXV 37000 15.1 12.5 CX38-43C SL280UH090V60C 10559281XC16S048-230 TXV 46000 15.5 11.7 C35-48B EL180UH090E48B 8309746XC16S048-230 TXV 46000 15.5 12 C35-48B EL180UH090E60C 8309560XC16S048-230 TXV 45500 15.5 12 C35-48B EL180UH110E60C 8309561XC16S048-230 TXV 45500 15 11.7 C35-48B SL280UH090V48B 9150396XC16S048-230 TXV 45500 14 11 C35-48B 8309562XC16S048-230 TXV 45500 15.5 11.7 C35-48C EL180UH090E60C 8309571XC16S048-230 TXV 46500 15 11.7 C35-48C EL180UH110E60C 8309572XC16S048-230 TXV 45500 15 11.7 C35-48C EL195UH090XE48C 8309563XC16S048-230 TXV 46500 15 11.7 C35-48C EL195UH110XE60C 8309564XC16S048-230 TXV 46000 15.5 11.7 C35-48C EL296UH090XE48C 8309567XC16S048-230 TXV 46000 15.5 11.7 C35-48C EL296UH090XV48C 8309565XC16S048-230 TXV 46000 15 11.7 C35-48C EL296UH090XV60C 8309566XC16S048-230 TXV 46000 15.5 12 C35-48C EL296UH110XE60C 8309570XC16S048-230 TXV 46000 15.5 11.7 C35-48C EL296UH110XV48C 8309568XC16S048-230 TXV 46000 15.5 11.7 C35-48C EL296UH110XV60C 8309569XC16S048-230 TXV 46000 15.5 11.7 C35-48C SL280UH090V60C 8309573XC16S048-230 TXV 46000 15.5 11.7 C35-48C SL280UH090XV60C 8309574XC16S048-230 TXV 46000 15.5 11.7 C35-48C SL280UH110V60C 8309575XC16S048-230 TXV 46000 15.5 12 C35-48C SL280UH110XV60C 8309576XC16S048-230 TXV 46000 15 11.7 C35-48C SLO185B124/141V60 8309577XC16S048-230 TXV 46000 15 11.7 C35-48C SLO185UF124/141V60 8309578XC16S048-230 TXV 46000 15.5 11.7 C35-48C SLP98UH090XV48C 8309579XC16S048-230 TXV 46000 15.5 11.7 C35-48C SLP98UH090XV60C 8309580XC16S048-230 TXV 46000 15.5 11.7 C35-48C SLP98UH110XV60C 8309747XC16S048-230 TXV 45500 14 11 C35-48C 8309581XC16S048-230 TXV 46500 16 12 C35-49C EL180UH090E60C 8309599XC16S048-230 TXV 46500 16 12 C35-49C EL180UH110E60C 8309600XC16S048-230 TXV 46500 15.5 12.2 C35-49C EL195UH090XE48C 8309597XC16S048-230 TXV 46500 16 12 C35-49C EL195UH110XE60C 8309598XC16S048-230 TXV 46500 15.5 12 C35-49C EL296UH090XE48C 8309584XC16S048-230 TXV 46500 16 12 C35-49C EL296UH090XV48C 8309582XC16S048-230 TXV 46500 15.5 12 C35-49C EL296UH090XV60C 8309583XC16S048-230 TXV 46500 16 12 C35-49C EL296UH110XE60C 8309587XC16S048-230 TXV 46500 16 12 C35-49C EL296UH110XV48C 8309585XC16S048-230 TXV 46500 16 12 C35-49C EL296UH110XV60C 8309586XC16S048-230 TXV 47000 16 12 C35-49C SL280UH090V60C 8309588Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 23: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 23

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 46500 16 12 C35-49C SL280UH090XV60C 8309589XC16S048-230 TXV 46500 16 12 C35-49C SL280UH110V60C 8309590XC16S048-230 TXV 46500 16 12 C35-49C SL280UH110XV60C 8309591XC16S048-230 TXV 46500 15.5 12.2 C35-49C SLO185B124/141V60 8309592XC16S048-230 TXV 46500 15.5 12.2 C35-49C SLO185UF124/141V60 8309593XC16S048-230 TXV 46500 16 12 C35-49C SLP98UH090XV48C 8309594XC16S048-230 TXV 46500 16 12 C35-49C SLP98UH090XV60C 8309595XC16S048-230 TXV 46500 16 12 C35-49C SLP98UH110XV60C 8309596XC16S048-230 TXV 46500 14.5 11.7 C35-49C 8309601XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C CBWMV-60C-100 8309602XC16S048-230 TXV 45500 15.5 12 C35-50/60C EL180UH090E60C 8309611XC16S048-230 TXV 45000 15 11.7 C35-50/60C EL180UH110E60C 8309748XC16S048-230 TXV 45000 15 11.7 C35-50/60C EL195UH090XE48C 8309603XC16S048-230 TXV 45500 15 11.7 C35-50/60C EL195UH110XE60C 8309604XC16S048-230 TXV 45500 15 11.7 C35-50/60C EL296UH090XE48C 8309607XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C EL296UH090XV48C 8309605XC16S048-230 TXV 45500 15 11.7 C35-50/60C EL296UH090XV60C 8309606XC16S048-230 TXV 45500 15.5 12 C35-50/60C EL296UH110XE60C 8309610XC16S048-230 TXV 45000 15.5 11.7 C35-50/60C EL296UH110XV48C 8309608XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C EL296UH110XV60C 8309609XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH090V60C 8309612XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH090XV60C 8309613XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH110V60C 8309614XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH110XV60C 8309615XC16S048-230 TXV 45000 15 11.7 C35-50/60C SLO185B124/141V60 8309616XC16S048-230 TXV 45000 15 11.7 C35-50/60C SLO185UF124/141V60 8309617XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SLP98UH090XV48C 8309618XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SLP98UH090XV60C 8309619XC16S048-230 TXV 45500 15.5 11.7 C35-50/60C SLP98UH110XV60C 8309620XC16S048-230 TXV 45000 14 11 C35-50/60C 8309621XC16S048-230 TXV 47000 16 12.5 C35-60C EL180UH090E60C 8309628XC16S048-230 TXV 47000 16 12.5 C35-60C EL180UH110E60C 8309629XC16S048-230 TXV 47000 16 12 C35-60C EL195UH090XE48C 8309630XC16S048-230 TXV 47000 16 12 C35-60C EL195UH110XE60C 8309631XC16S048-230 TXV 47000 16 12 C35-60C EL296UH090XE48C 8309634XC16S048-230 TXV 47000 16 12 C35-60C EL296UH090XV48C 8309632XC16S048-230 TXV 47000 16 12 C35-60C EL296UH090XV60C 8309633XC16S048-230 TXV 47000 16 12 C35-60C EL296UH110XE60C 8309637XC16S048-230 TXV 47000 16 12 C35-60C EL296UH110XV48C 8309635XC16S048-230 TXV 47500 16 12 C35-60C EL296UH110XV60C 8309636XC16S048-230 TXV 47500 16.5 12.2 C35-60C SL280UH090V60C 8309638XC16S048-230 TXV 47000 16 12 C35-60C SL280UH090XV60C 8309639XC16S048-230 TXV 47000 16 12 C35-60C SL280UH110V60C 8309640XC16S048-230 TXV 47000 16 12 C35-60C SL280UH110XV60C 8309641XC16S048-230 TXV 47000 16 12 C35-60C SLO185B124/141V60 8309642XC16S048-230 TXV 47000 16 12 C35-60C SLO185UF124/141V60 8309643XC16S048-230 TXV 47000 16 12 C35-60C SLP98UH090XV48C 8309644XC16S048-230 TXV 47000 16 12 C35-60C SLP98UH090XV60C 8309645XC16S048-230 TXV 47500 16 12 C35-60C SLP98UH110XV60C 8309646XC16S048-230 TXV 47000 14.5 11.7 C35-60C 8309647XC16S048-230 TXV 47000 16 12 C35-60D EL296UH135XV60D 8309622Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 24: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 24

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 47000 16 12 C35-60D SL280UH135V60D 8309623XC16S048-230 TXV 46500 15.5 12.2 C35-60D SLO185B124/141V60 8309624XC16S048-230 TXV 46500 15.5 12.2 C35-60D SLO185UF124/141V60 8309625XC16S048-230 TXV 47000 16 12 C35-60D SLP98UH135XV60D 8309626XC16S048-230 TXV 46500 14.5 11.7 C35-60D 8309627XC16S048-230 TXV 47000 16 12.2 CBA27UHE-048 10259505XC16S048-230 TXV 46500 16 12.2 CBA27UHE-060 10259506XC16S048-230 TXV 46000 14 11.5 CBX25UH-048 7621924XC16S048-230 TXV 47000 16 12 CBX25UHV-048 7622707XC16S048-230 TXV 46000 16 12 CBX27UH-048 7621920XC16S048-230 TXV 46500 16 12 CBX27UH-060 7621922XC16S048-230 TXV 46000 15 12 CBX32M-048 7621925XC16S048-230 TXV 47000 14 12 CBX32M-060 7621927XC16S048-230 TXV 46000 16 12 CBX32MV-048 7621928XC16S048-230 TXV 47000 16 12 CBX32MV-060 7621930XC16S048-230 TXV 47000 16 12 CBX32MV-068 7621932XC16S048-230 TXV 45500 15.5 12 CBX40UHV-048 7622331XC16S048-230 TXV 46000 15.5 12 CBX40UHV-060 7622333XC16S048-230 TXV 44000 14.5 11.5 CH23-51 EL180UH090E48B 7622338XC16S048-230 TXV 44000 15 11.7 CH23-51 EL180UH090E60C 7622339XC16S048-230 TXV 43500 15 11.7 CH23-51 EL180UH110E60C 7622341XC16S048-230 TXV 44000 14.5 11.5 CH23-51 EL195UH090XE48C 7621933XC16S048-230 TXV 44000 15 11.7 CH23-51 EL195UH110XE60C 7621935XC16S048-230 TXV 44000 14.5 11.5 CH23-51 EL296UH090XE48C 7622334XC16S048-230 TXV 44000 15 11.5 CH23-51 EL296UH090XV48C 7621936XC16S048-230 TXV 44000 15 11.5 CH23-51 EL296UH090XV60C 7621938XC16S048-230 TXV 44000 15 11.7 CH23-51 EL296UH110XE60C 7622336XC16S048-230 TXV 44000 15 11.5 CH23-51 EL296UH110XV48C 7621940XC16S048-230 TXV 44000 15 11.5 CH23-51 EL296UH110XV60C 7621941XC16S048-230 TXV 44000 15 11.5 CH23-51 EL296UH135XV60D 7621943XC16S048-230 TXV 44000 15 11.5 CH23-51 SL280UH090V60C 7621945XC16S048-230 TXV 44000 15 11.7 CH23-51 SL280UH090XV60C 7622342XC16S048-230 TXV 44000 15 11.7 CH23-51 SL280UH110V60C 7621946XC16S048-230 TXV 44000 15 11.7 CH23-51 SL280UH110XV60C 7622344XC16S048-230 TXV 44000 15 11.5 CH23-51 SL280UH135V60D 7621948XC16S048-230 TXV 44000 15 11.5 CH23-51 SLP98UH090XV48C 7621949XC16S048-230 TXV 44000 15 11.5 CH23-51 SLP98UH090XV60C 7621951XC16S048-230 TXV 44000 15 11.5 CH23-51 SLP98UH110XV60C 7621953XC16S048-230 TXV 44000 15 11.5 CH23-51 SLP98UH135XV60D 7621954XC16S048-230 TXV 44500 15 11.7 CH23-65 EL180UH090E60C 7622349XC16S048-230 TXV 44500 15 11.7 CH23-65 EL180UH110E60C 7622350XC16S048-230 TXV 44500 15 11.7 CH23-65 EL195UH090XE48C 7621956XC16S048-230 TXV 44500 15 11.7 CH23-65 EL195UH110XE60C 7621957XC16S048-230 TXV 44500 15 11.5 CH23-65 EL296UH090XE48C 7622346XC16S048-230 TXV 44500 15.5 11.7 CH23-65 EL296UH090XV48C 7621959XC16S048-230 TXV 44500 15.5 11.7 CH23-65 EL296UH090XV60C 7621961XC16S048-230 TXV 44500 15 11.7 CH23-65 EL296UH110XE60C 7622347XC16S048-230 TXV 44500 15.5 11.7 CH23-65 EL296UH110XV48C 7621962XC16S048-230 TXV 44500 15.5 11.7 CH23-65 EL296UH110XV60C 7621964XC16S048-230 TXV 45000 15.5 12 CH23-65 EL296UH135XV60D 7621965XC16S048-230 TXV 45000 15.5 12 CH23-65 SL280UH090V60C 7621829Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 25: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 25

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 45000 15.5 12 CH23-65 SL280UH090XV48B 7622415XC16S048-230 TXV 44500 15.5 11.7 CH23-65 SL280UH110V60C 7621830XC16S048-230 TXV 44500 15.5 11.7 CH23-65 SL280UH110XV60C 7622417XC16S048-230 TXV 45000 15.5 12 CH23-65 SL280UH135V60D 7621967XC16S048-230 TXV 44500 15.5 11.7 CH23-65 SLP98UH090XV48C 7621969XC16S048-230 TXV 44500 15.5 11.7 CH23-65 SLP98UH090XV60C 7621970XC16S048-230 TXV 45000 15.5 11.7 CH23-65 SLP98UH110XV60C 7621972XC16S048-230 TXV 45000 15.5 12 CH23-65 SLP98UH135XV60D 7621973XC16S048-230 TXV 46500 15.5 12.2 CH23-68 EL180UH090E60C 7622352XC16S048-230 TXV 46000 15.5 12.2 CH23-68 EL180UH110E60C 7622354XC16S048-230 TXV 46500 15.5 12.2 CH23-68 EL195UH090XE48C 7621975XC16S048-230 TXV 46500 16 12 CH23-68 EL195UH110XE60C 7621977XC16S048-230 TXV 46000 15.5 12 CH23-68 EL296UH090XE48C 7622355XC16S048-230 TXV 46000 15.5 12 CH23-68 EL296UH110XE60C 7622357XC16S048-230 TXV 46500 16 12 CH23-68 EL296UH135XV60D 7621978XC16S048-230 TXV 46500 16 12 CH23-68 SL280UH135V60D 7621980XC16S048-230 TXV 46500 16 12 CH23-68 SLP98UH135XV60D 7621981XC16S048-230 TXV 46000 14 11.5 CH23-68 7621861XC16S048-230 TXV 46500 15.5 12 CH33-43B SL280UH090V48B 7622358XC16S048-230 TXV 46500 15.5 12 CH33-43B SL280UH090XV48B 7622360XC16S048-230 TXV 46000 15.5 12.2 CH33-43C EL180UH090E60C 7621832XC16S048-230 TXV 45500 15.5 12.2 CH33-43C EL180UH110E60C 7621833XC16S048-230 TXV 45500 15 11.7 CH33-43C EL195UH090XE48C 7621983XC16S048-230 TXV 46000 15 11.7 CH33-43C EL195UH110XE60C 7621985XC16S048-230 TXV 45500 15.5 11.7 CH33-43C EL296UH090XE48C 7622362XC16S048-230 TXV 46000 15.5 12 CH33-43C EL296UH110XE60C 7622363XC16S048-230 TXV 45500 15.5 11.7 CH33-43C EL296UH110XV48C 7621986XC16S048-230 TXV 45500 15.5 11.7 CH33-44/48B EL180UH090E48B 7622365XC16S048-230 TXV 45000 15 11.5 CH33-44/48B SL280UH090V48B 7622367XC16S048-230 TXV 45000 15 11.5 CH33-44/48B SL280UH090XV48B 7622368XC16S048-230 TXV 45500 15.5 11.7 CH33-48 EL296UH090XV48C 7621991XC16S048-230 TXV 45500 15 11.7 CH33-48 EL296UH090XV60C 7621993XC16S048-230 TXV 45500 15.5 11.7 CH33-48 EL296UH110XV48C 7621994XC16S048-230 TXV 45500 15.5 11.7 CH33-48 EL296UH110XV60C 7621996XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH090V60C 7621998XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH090XV60C 7622370XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH110V60C 7621999XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH110XV60C 7622371XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SLP98UH090XV48C 7622001XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SLP98UH090XV60C 7622002XC16S048-230 TXV 45500 15.5 11.7 CH33-48 SLP98UH110XV60C 7622004XC16S048-230 TXV 45500 15.5 12 CH33-48C EL180UH090E60C 7622373XC16S048-230 TXV 45500 15.5 12.2 CH33-48C EL180UH110E60C 7622375XC16S048-230 TXV 45000 15 11.7 CH33-48C EL195UH090XE48C 7621988XC16S048-230 TXV 46000 15 11.7 CH33-48C EL195UH110XE60C 7621990XC16S048-230 TXV 45500 15.5 11.7 CH33-48C EL296UH090XE48C 7622376XC16S048-230 TXV 45500 15.5 12 CH33-48C EL296UH110XE60C 7622378XC16S048-230 TXV 45000 14 11 CH33-48C 7621863XC16S048-230 TXV 46500 15.5 12 CH33-49 EL296UH090XV48C 7622006XC16S048-230 TXV 46500 15.5 12 CH33-49 EL296UH090XV60C 7622007XC16S048-230 TXV 46500 15.5 12 CH33-49 EL296UH110XV48C 7622009Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 26: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 26

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 46500 15.5 12 CH33-49 EL296UH110XV60C 7622010XC16S048-230 TXV 46500 16 12 CH33-49 SL280UH090V60C 7622012XC16S048-230 TXV 46500 16 12 CH33-49 SL280UH090XV60C 7622379XC16S048-230 TXV 46500 15.5 12 CH33-49 SL280UH110V60C 7622014XC16S048-230 TXV 46500 15.5 12 CH33-49 SL280UH110XV60C 7622381XC16S048-230 TXV 46500 15.5 12 CH33-49 SLP98UH090XV48C 7622015XC16S048-230 TXV 46500 15.5 12 CH33-49 SLP98UH090XV60C 7622017XC16S048-230 TXV 46500 15.5 12 CH33-49 SLP98UH110XV60C 7622018XC16S048-230 TXV 46000 14.5 11.5 CH33-49 7621904XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C CBWMV-60C-100 7622383XC16S048-230 TXV 46000 16 12 CH33-50/60C EL180UH090E60C 7622384XC16S048-230 TXV 46000 16 12 CH33-50/60C EL180UH110E60C 7622386XC16S048-230 TXV 46000 15.5 12 CH33-50/60C EL195UH090XE48C 7622020XC16S048-230 TXV 46500 15.5 11.7 CH33-50/60C EL195UH110XE60C 7622022XC16S048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH090XE48C 7622418XC16S048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH090XE48C 7621835XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C EL296UH090XV48C 7622023XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C EL296UH090XV60C 7622025XC16S048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH110XE60C 7621837XC16S048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH110XE60C 7622420XC16S048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH110XV48C 7622026XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C EL296UH110XV60C 7622028XC16S048-230 TXV 46500 16 12 CH33-50/60C SL280UH090V60C 7622030XC16S048-230 TXV 46500 15.5 12.2 CH33-50/60C SL280UH090XV60C 7622387XC16S048-230 TXV 46000 15.5 12 CH33-50/60C SL280UH110V60C 7622031XC16S048-230 TXV 46000 15.5 12 CH33-50/60C SL280UH110XV60C 7622389XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C SLP98UH090XV48C 7622033XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C SLP98UH090XV60C 7622035XC16S048-230 TXV 46000 15.5 11.7 CH33-50/60C SLP98UH110XV60C 7622036XC16S048-230 TXV 46000 14.5 11.5 CH33-50/60C 7621864XC16S048-230 TXV 46000 16 12 CH33-60D EL296UH135XV60D 7622038XC16S048-230 TXV 46000 16 12 CH33-60D SL280UH135V60D 7622040XC16S048-230 TXV 46000 15.5 12 CH33-60D SLP98UH135XV60D 7622042XC16S048-230 TXV 45500 14 11.5 CH33-60D 7621866XC16S048-230 TXV 46500 16 12 CH33-62D EL296UH135XV60D 7622043XC16S048-230 TXV 46500 16 12 CH33-62D SL280UH135V60D 7622045XC16S048-230 TXV 46500 16 12 CH33-62D SLP98UH135XV60D 7622047XC16S048-230 TXV 46000 14.5 11.5 CH33-62D 7621868XC16S048-230 TXV 47000 15.5 12 CH35-42B SL280UH090V48B 7624294XC16S048-230 TXV 47000 15.5 12 CH35-42B SL280UH090XV48B 7624296XC16S048-230 TXV 46500 14.5 11.7 CH35-42B 7624291XC16S048-230 TXV 46000 15.5 12 CH35-42C EL180UH090E60C 7624297XC16S048-230 TXV 46000 15.5 12 CH35-42C EL180UH110E60C 7624299XC16S048-230 TXV 45500 15.1 11.7 CH35-42C EL195UH090XE48C 7624301XC16S048-230 TXV 46500 15.1 11.7 CH35-42C EL195UH110XE60C 7624302XC16S048-230 TXV 46000 15.5 12 CH35-42C EL296UH090XE48C 7624304XC16S048-230 TXV 46000 15.5 12 CH35-42C EL296UH110XE60C 7624307XC16S048-230 TXV 46000 15.5 12 CH35-42C EL296UH110XV48C 7624306XC16S048-230 TXV 46000 14.5 11.5 CH35-42C 7624293XC16S048-230 TXV 45500 15.5 11.7 CH35-48B EL180UH090E48B 7624309XC16S048-230 TXV 45500 15.1 11.5 CH35-48B SL280UH090V48B 7624311Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 27: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 27

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 45500 15.1 11.5 CH35-48B SL280UH090XV48B 7624312XC16S048-230 TXV 45500 14.25 11.5 CH35-48B 7624314XC16S048-230 TXV 46000 15.5 12 CH35-48C EL180UH090E60C 7624317XC16S048-230 TXV 45500 15.5 12 CH35-48C EL180UH110E60C 7624319XC16S048-230 TXV 45500 15.1 11.7 CH35-48C EL195UH090XE48C 7624321XC16S048-230 TXV 46000 15.1 11.7 CH35-48C EL195UH110XE60C 7624322XC16S048-230 TXV 45500 15.5 11.7 CH35-48C EL296UH090XV48C 7624324XC16S048-230 TXV 45500 15.1 11.7 CH35-48C EL296UH090XV60C 7624326XC16S048-230 TXV 46000 15.5 12 CH35-48C EL296UH110XE60C 7624330XC16S048-230 TXV 45500 15.5 11.7 CH35-48C EL296UH110XV48C 7624327XC16S048-230 TXV 46000 15.5 11.7 CH35-48C EL296UH110XV60C 7624329XC16S048-230 TXV 46000 15.5 12 CH35-48C SL280UH090V60C 7623697XC16S048-230 TXV 46000 15.5 12 CH35-48C SL280UH090XV60C 7624332XC16S048-230 TXV 45500 15.5 11.7 CH35-48C SL280UH110V60C 7623698XC16S048-230 TXV 45500 15.5 11.7 CH35-48C SL280UH110XV60C 7624333XC16S048-230 TXV 45500 15.5 11.7 CH35-48C SLP98UH090XV48C 7623700XC16S048-230 TXV 45500 15.5 11.7 CH35-48C SLP98UH090XV60C 7623702XC16S048-230 TXV 46000 15.5 11.7 CH35-48C SLP98UH110XV60C 7623703XC16S048-230 TXV 45500 14.25 11.5 CH35-48C 7624316XC16S048-230 TXV 46500 15.5 12 CH35-51C CBWMV-60C-100 7624347XC16S048-230 TXV 46500 16 12 CH35-51C EL180UH090E60C 7624348XC16S048-230 TXV 46500 16 12 CH35-51C EL180UH110E60C 7624350XC16S048-230 TXV 46000 15.5 12 CH35-51C EL195UH090XE48C 7624352XC16S048-230 TXV 47000 15.5 11.7 CH35-51C EL195UH110XE60C 7624353XC16S048-230 TXV 46500 15.5 12 CH35-51C EL296UH090XV48C 7624335XC16S048-230 TXV 46500 15.5 12 CH35-51C EL296UH090XV60C 7624337XC16S048-230 TXV 46500 15.5 11.7 CH35-51C EL296UH110XE60C 7624355XC16S048-230 TXV 46500 15.5 12 CH35-51C EL296UH110XV48C 7624338XC16S048-230 TXV 46500 15.5 12 CH35-51C EL296UH110XV60C 7624340XC16S048-230 TXV 46500 16 12 CH35-51C SL280UH090V60C 7623705XC16S048-230 TXV 46500 16 12 CH35-51C SL280UH090XV60C 7624342XC16S048-230 TXV 46500 15.5 12 CH35-51C SL280UH110V60C 7623706XC16S048-230 TXV 46500 15.5 12 CH35-51C SL280UH110XV60C 7624343XC16S048-230 TXV 46500 15.5 12 CH35-51C SLP98UH090XV48C 7623708XC16S048-230 TXV 46500 15.5 12 CH35-51C SLP98UH090XV60C 7623710XC16S048-230 TXV 46500 15.5 12 CH35-51C SLP98UH110XV60C 7623711XC16S048-230 TXV 46500 14.5 11.7 CH35-51C 7624345XC16S048-230 TXV 47000 16 12 CH35-60D EL296UH135XV60D 7624358XC16S048-230 TXV 46500 16 12 CH35-60D SL280UH135V60D 7623713XC16S048-230 TXV 46500 16 12 CH35-60D SLP98UH135XV60D 7623715XC16S048-230 TXV 46000 14.5 11.5 CH35-60D 7624357XC16S048-230 TXV 44500 15 11.7 CR33-48 EL180DF110E60C 7622054XC16S048-230 TXV 44000 15 11.5 CR33-48 EL195DF090XE48C 7622049XC16S048-230 TXV 44500 15 11 CR33-48 EL195DF110XE60C 7622421XC16S048-230 TXV 44500 15 11.5 CR33-48 EL296DF090XE48C 7622391XC16S048-230 TXV 44500 15 11 CR33-48 EL296DF090XV60C 7622050XC16S048-230 TXV 44500 15 11.7 CR33-48 EL296DF110XE60C 7622392XC16S048-230 TXV 44500 15 11 CR33-48 EL296DF110XV60C 7622052XC16S048-230 TXV 44500 15 11.7 CR33-48 SL280DF090V60C 7622056XC16S048-230 TXV 44500 15.5 11.7 CR33-48 SL280DF110V60C 7622057XC16S048-230 TXV 44500 15 11 CR33-48 SLP98DF090XV48C 7622394Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 28: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 28

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 44500 15 11 CR33-48 SLP98DF090XV60C 7622396XC16S048-230 TXV 44500 15 11.5 CR33-48 SLP98DF110XV60C 7622397XC16S048-230 TXV 44000 14 11 CR33-48 7621907XC16S048-230 TXV 45000 15.5 12 CR33-50/60 EL180DF110E60C 7622399XC16S048-230 TXV 45000 15 11.7 CR33-50/60 EL195DF090XE48C 7622059XC16S048-230 TXV 45000 15 11.7 CR33-50/60 EL195DF110XE60C 7622061XC16S048-230 TXV 45000 15 11.7 CR33-50/60 EL296DF090XE48C 7622400XC16S048-230 TXV 45000 15 11.7 CR33-50/60 EL296DF090XV60C 7622062XC16S048-230 TXV 45000 15 11.7 CR33-50/60 EL296DF110XE60C 7622402XC16S048-230 TXV 45000 15 11.5 CR33-50/60 EL296DF110XV60C 7622064XC16S048-230 TXV 45000 15.5 11.7 CR33-50/60 SL280DF090V60C 7622067XC16S048-230 TXV 45000 15.5 12 CR33-50/60 SL280DF110V60C 7622070XC16S048-230 TXV 45000 15 11.5 CR33-50/60 SLP98DF090XV48C 7622404XC16S048-230 TXV 45000 15 11.7 CR33-50/60 SLP98DF090XV60C 7622405XC16S048-230 TXV 45000 15 11.7 CR33-50/60 SLP98DF110XV60C 7622407XC16S048-230 TXV 44500 14 11 CR33-50/60 7621911XC16S048-230 TXV 44500 14 11 CR33-60 7621914XC16S048-230 TXV 46000 15.5 11.7 CX35-48B EL180UH090E48B 8309650XC16S048-230 TXV 46000 15.5 12 CX35-48B EL180UH090E60C 8309648XC16S048-230 TXV 45500 15.5 12 CX35-48B EL180UH110E60C 8309649XC16S048-230 TXV 45500 15 11.7 CX35-48B SL280UH090V48B 9150397XC16S048-230 TXV 45500 14 11 CX35-48B 8309655XC16S048-230 TXV 45500 15.5 11.7 CX35-48C EL180UH090E60C 8309653XC16S048-230 TXV 46500 15 11.7 CX35-48C EL180UH110E60C 8309654XC16S048-230 TXV 45500 15 11.7 CX35-48C EL195UH090XE48C 8309651XC16S048-230 TXV 46500 15 11.7 CX35-48C EL195UH110XE60C 8309652XC16S048-230 TXV 46000 15.5 11.7 CX35-48C EL296UH090XE48C 8309659XC16S048-230 TXV 46000 15.5 11.7 CX35-48C EL296UH090XV48C 8309657XC16S048-230 TXV 46000 15.5 11.7 CX35-48C EL296UH090XV60C 8309658XC16S048-230 TXV 46000 15.5 12 CX35-48C EL296UH110XE60C 8309662XC16S048-230 TXV 46000 15.5 12 CX35-48C EL296UH110XV48C 8309660XC16S048-230 TXV 46000 15.5 11.7 CX35-48C EL296UH110XV60C 8309661XC16S048-230 TXV 46000 16 12 CX35-48C SL280UH090V60C 8309663XC16S048-230 TXV 46000 15.5 12 CX35-48C SL280UH090XV60C 8309664XC16S048-230 TXV 46000 15.5 12 CX35-48C SL280UH110V60C 8309665XC16S048-230 TXV 46000 15.5 12 CX35-48C SL280UH110XV60C 8309666XC16S048-230 TXV 46000 15.5 12 CX35-48C SLO185B124/141V60 8309667XC16S048-230 TXV 46000 15.5 12 CX35-48C SLO185UF124/141V60 8309668XC16S048-230 TXV 46000 15.5 11.7 CX35-48C SLP98UH090XV48C 8309669XC16S048-230 TXV 46000 15.5 11.7 CX35-48C SLP98UH090XV60C 8309670XC16S048-230 TXV 46000 15.5 11.7 CX35-48C SLP98UH110XV60C 8309671XC16S048-230 TXV 45500 14 11 CX35-48C 8309656XC16S048-230 TXV 46500 16 12 CX35-49C EL180UH090E60C 8309674XC16S048-230 TXV 46500 16 12 CX35-49C EL180UH110E60C 8309675XC16S048-230 TXV 46500 15.5 12.2 CX35-49C EL195UH090XE48C 8309672XC16S048-230 TXV 46500 16 12 CX35-49C EL195UH110XE60C 8309673XC16S048-230 TXV 46500 15.5 12 CX35-49C EL296UH090XE48C 8309679XC16S048-230 TXV 46500 16 12 CX35-49C EL296UH090XV48C 8309677XC16S048-230 TXV 46500 15.5 12 CX35-49C EL296UH090XV60C 8309678XC16S048-230 TXV 46500 16 12 CX35-49C EL296UH110XE60C 8309682XC16S048-230 TXV 46500 16 12 CX35-49C EL296UH110XV48C 8309680Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 29: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 29

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 46500 16 12 CX35-49C EL296UH110XV60C 8309681XC16S048-230 TXV 47000 16 12 CX35-49C SL280UH090V60C 8309683XC16S048-230 TXV 46500 16 12 CX35-49C SL280UH090XV60C 8309684XC16S048-230 TXV 46500 16 12 CX35-49C SL280UH110V60C 8309685XC16S048-230 TXV 46500 16 12 CX35-49C SL280UH110XV60C 8309686XC16S048-230 TXV 46500 15.5 12.2 CX35-49C SLO185B124/141V60 8309687XC16S048-230 TXV 46500 15.5 12.2 CX35-49C SLO185UF124/141V60 8309688XC16S048-230 TXV 46500 16 12 CX35-49C SLP98UH090XV48C 8309689XC16S048-230 TXV 46500 16 12 CX35-49C SLP98UH090XV60C 8309690XC16S048-230 TXV 46500 16 12 CX35-49C SLP98UH110XV60C 8309691XC16S048-230 TXV 46500 14.5 11.7 CX35-49C 8309676XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C CBWMV-60C-100 8309693XC16S048-230 TXV 45500 15.5 12 CX35-50/60C EL180UH090E60C 8309702XC16S048-230 TXV 45000 15 11.7 CX35-50/60C EL180UH110E60C 8309749XC16S048-230 TXV 45000 15 11.7 CX35-50/60C EL195UH090XE48C 8309694XC16S048-230 TXV 45500 15 11.7 CX35-50/60C EL195UH110XE60C 8309695XC16S048-230 TXV 45500 15 11.7 CX35-50/60C EL296UH090XE48C 8309698XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C EL296UH090XV48C 8309696XC16S048-230 TXV 45500 15 11.7 CX35-50/60C EL296UH090XV60C 8309697XC16S048-230 TXV 45500 15.5 12 CX35-50/60C EL296UH110XE60C 8309701XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C EL296UH110XV48C 8309699XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C EL296UH110XV60C 8309700XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH090V60C 8309703XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH090XV60C 8309704XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH110V60C 8309705XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH110XV60C 8309706XC16S048-230 TXV 45000 15 11.7 CX35-50/60C SLO185B124/141V60 8309707XC16S048-230 TXV 45000 15 11.7 CX35-50/60C SLO185UF124/141V60 8309708XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SLP98UH090XV48C 8309709XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SLP98UH090XV60C 8309710XC16S048-230 TXV 45500 15.5 11.7 CX35-50/60C SLP98UH110XV60C 8309711XC16S048-230 TXV 45000 14 11 CX35-50/60C 8309692XC16S048-230 TXV 47000 16 12.5 CX35-60C EL180UH090E60C 8309719XC16S048-230 TXV 47000 16 12.5 CX35-60C EL180UH110E60C 8309720XC16S048-230 TXV 47000 16 12 CX35-60C EL195UH090XE48C 8309721XC16S048-230 TXV 47000 16 12 CX35-60C EL195UH110XE60C 8309722XC16S048-230 TXV 47000 16 12 CX35-60C EL296UH090XE48C 8309725XC16S048-230 TXV 47000 16 12 CX35-60C EL296UH090XV48C 8309723XC16S048-230 TXV 47000 16 12 CX35-60C EL296UH090XV60C 8309724XC16S048-230 TXV 47000 16 12 CX35-60C EL296UH110XE60C 8309729XC16S048-230 TXV 47000 16 12 CX35-60C EL296UH110XV48C 8309726XC16S048-230 TXV 47500 16 12 CX35-60C EL296UH110XV60C 8309727XC16S048-230 TXV 47500 16.5 12.2 CX35-60C SL280UH090V60C 8309731XC16S048-230 TXV 47000 16 12 CX35-60C SL280UH090XV60C 8309733XC16S048-230 TXV 47000 16 12 CX35-60C SL280UH110V60C 8309734XC16S048-230 TXV 47000 16 12 CX35-60C SL280UH110XV60C 8309736XC16S048-230 TXV 47000 16 12 CX35-60C SLO185B124/141V60 8309737XC16S048-230 TXV 47000 16 12 CX35-60C SLO185UF124/141V60 8309738XC16S048-230 TXV 47000 16 12 CX35-60C SLP98UH090XV48C 8309739XC16S048-230 TXV 47000 16 12 CX35-60C SLP98UH090XV60C 8309740XC16S048-230 TXV 47500 16 12 CX35-60C SLP98UH110XV60C 8309741Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 30: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 30

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S048-230 TXV 47000 14.5 11.7 CX35-60C 8309718XC16S048-230 TXV 47000 16 12 CX35-60D EL296UH135XV60D 8309713XC16S048-230 TXV 47000 16 12 CX35-60D SL280UH135V60D 8309714XC16S048-230 TXV 46500 15.5 12.2 CX35-60D SLO185B124/141V60 8309715XC16S048-230 TXV 46500 15.5 12.2 CX35-60D SLO185UF124/141V60 8309716XC16S048-230 TXV 47000 16 12 CX35-60D SLP98UH135XV60D 8309717XC16S048-230 TXV 46500 14.5 11.7 CX35-60D 8309712XC16S048-230 TXV 47500 16.5 12.2 CX38-62C SL280UH090V60C 10559505XC16S060-230 TXV 56000 15 11.7 C35-48C EL180UH090E60C 8309317XC16S060-230 TXV 55500 15 11.7 C35-48C EL180UH110E60C 8309318XC16S060-230 TXV 55500 15 11.7 C35-48C EL195UH110XE60C 8309319XC16S060-230 TXV 55500 15 11 C35-48C EL296UH090XV60C 8309320XC16S060-230 TXV 55500 15 11.7 C35-48C EL296UH110XE60C 8309322XC16S060-230 TXV 55500 15 11 C35-48C EL296UH110XV60C 8309321XC16S060-230 TXV 56000 15 11.7 C35-48C SL280UH090V60C 8309323XC16S060-230 TXV 56000 15 11.7 C35-48C SL280UH090XV60C 8309324XC16S060-230 TXV 55500 15 11 C35-48C SL280UH110V60C 8309325XC16S060-230 TXV 55500 15 11 C35-48C SL280UH110XV60C 8309326XC16S060-230 TXV 55500 15 11 C35-48C SLP98UH090XV60C 8309327XC16S060-230 TXV 55500 15 11 C35-48C SLP98UH110XV60C 8309328XC16S060-230 TXV 55500 14 11 C35-48C 8309329XC16S060-230 TXV 56500 15 12 C35-49C EL180UH090E60C 8309330XC16S060-230 TXV 56500 15 12 C35-49C EL180UH110E60C 8309331XC16S060-230 TXV 56500 15 12 C35-49C EL195UH110XE60C 8309332XC16S060-230 TXV 56500 15 11 C35-49C EL296UH090XV60C 8309333XC16S060-230 TXV 56500 15 12 C35-49C EL296UH110XE60C 8309335XC16S060-230 TXV 56500 15 11.7 C35-49C EL296UH110XV60C 8309334XC16S060-230 TXV 56500 15 11.7 C35-49C SL280UH090V60C 8309336XC16S060-230 TXV 56500 15 11.7 C35-49C SL280UH090XV60C 8309337XC16S060-230 TXV 56500 15 11.7 C35-49C SL280UH110V60C 8309338XC16S060-230 TXV 56500 15 11.7 C35-49C SL280UH110XV60C 8309339XC16S060-230 TXV 56500 15 11 C35-49C SLP98UH090XV60C 8309340XC16S060-230 TXV 56000 15 11 C35-49C SLP98UH110XV60C 8309341XC16S060-230 TXV 56500 14 11 C35-49C 8309342XC16S060-230 TXV 54000 14.5 11 C35-50/60C CBWMV-60C-120 8309343XC16S060-230 TXV 55000 15 11.7 C35-50/60C EL180UH090E60C 8309344XC16S060-230 TXV 55000 14.5 11.7 C35-50/60C EL180UH110E60C 8309345XC16S060-230 TXV 55000 14.5 11.7 C35-50/60C EL180UH110XE60C 8309346XC16S060-230 TXV 55000 15 11.7 C35-50/60C EL195UH110XE60C 8309347XC16S060-230 TXV 55000 14.5 11 C35-50/60C EL296UH090XV60C 8309348XC16S060-230 TXV 55000 15 11.7 C35-50/60C EL296UH110XE60C 8309350XC16S060-230 TXV 55000 14.5 11 C35-50/60C EL296UH110XV60C 8309349XC16S060-230 TXV 55000 14.5 11 C35-50/60C SL280UH090V60C 8309352XC16S060-230 TXV 55000 15 11 C35-50/60C SL280UH090XV60C 8309351XC16S060-230 TXV 55000 14.5 11 C35-50/60C SL280UH110V60C 8309353XC16S060-230 TXV 54500 14.5 11 C35-50/60C SL280UH110XV60C 8309354XC16S060-230 TXV 55000 14.5 11 C35-50/60C SLP98UH090XV60C 8309355XC16S060-230 TXV 55000 14.5 11 C35-50/60C SLP98UH110XV60C 8309356XC16S060-230 TXV 55000 14 11 C35-50/60C 8309357XC16S060-230 TXV 57500 15.5 12.2 C35-60C EL180UH090E60C 8309358XC16S060-230 TXV 57500 15.5 12.2 C35-60C EL180UH110E60C 8309359Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 31: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 31

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S060-230 TXV 57500 15.5 12.2 C35-60C EL180UH110XE60C 8309360XC16S060-230 TXV 57500 15.5 12.2 C35-60C EL195UH110XE60C 8309361XC16S060-230 TXV 56500 15 11.7 C35-60C EL296UH090XV60C 8309362XC16S060-230 TXV 57500 15.5 12.2 C35-60C EL296UH110XE60C 8309364XC16S060-230 TXV 56500 15 11.7 C35-60C EL296UH110XV60C 8309363XC16S060-230 TXV 57500 16 12 C35-60C SL280UH090V60C 8309365XC16S060-230 TXV 57500 15.5 12 C35-60C SL280UH090XV60C 8309366XC16S060-230 TXV 57500 15.5 11.7 C35-60C SL280UH110V60C 8309367XC16S060-230 TXV 57500 15.5 11.7 C35-60C SL280UH110XV60C 8309368XC16S060-230 TXV 57000 15 11.7 C35-60C SLO185UF124/141V60 8309369XC16S060-230 TXV 57500 15.5 11.7 C35-60C SLP98UH090XV60C 8309473XC16S060-230 TXV 57000 15.5 11.7 C35-60C SLP98UH110XV60C 8309370XC16S060-230 TXV 57500 14.5 11.7 C35-60C 8309371XC16S060-230 TXV 57000 15.5 12 C35-60D EL180UH135E60D 8309372XC16S060-230 TXV 57000 15 11.7 C35-60D EL195UH135XE60D 8309373XC16S060-230 TXV 56500 15 11.7 C35-60D EL296UH135XE60D 8309375XC16S060-230 TXV 57000 15.5 11.7 C35-60D EL296UH135XV60D 8309374XC16S060-230 TXV 57000 15.5 12 C35-60D SL280UH135V60D 8309376XC16S060-230 TXV 57000 15 11.7 C35-60D SLO185B124/141V60 8309377XC16S060-230 TXV 56000 15 11.7 C35-60D SLO185UF124/141V60 8309378XC16S060-230 TXV 57000 15.5 12 C35-60D SLP98UH135XV60D 8309379XC16S060-230 TXV 56500 14 11 C35-60D 8309380XC16S060-230 TXV 56000 15.1 11.7 CBA27UHE-060 10259507XC16S060-230 TXV 56500 14.5 11.7 CBX25UH-060 7621782XC16S060-230 TXV 56500 16 12 CBX25UHV-060 7622709XC16S060-230 TXV 56500 15.5 12 CBX27UH-060 7621579XC16S060-230 TXV 56500 14.5 11.7 CBX32M-060 7621581XC16S060-230 TXV 56000 15.5 11.7 CBX32MV-048 7621583XC16S060-230 TXV 56500 15.5 11.7 CBX32MV-060 7621584XC16S060-230 TXV 56500 15.5 12.2 CBX32MV-068 7621586XC16S060-230 TXV 55000 15 11.7 CBX40UHV-048 7621783XC16S060-230 TXV 55500 15 11.7 CBX40UHV-060 7621785XC16S060-230 TXV 54000 14.5 11 CH23-65 EL180UH090E60C 7621787XC16S060-230 TXV 54000 14.5 11 CH23-65 EL180UH110E60C 7621788XC16S060-230 TXV 54000 14.5 11 CH23-65 EL195UH110XE60C 7621587XC16S060-230 TXV 54000 14.5 11 CH23-65 EL296UH090XV60C 7621589XC16S060-230 TXV 54000 14.5 11 CH23-65 EL296UH110XE60C 7621790XC16S060-230 TXV 54000 14.5 11 CH23-65 EL296UH110XV60C 7621591XC16S060-230 TXV 54500 15 11 CH23-65 EL296UH135XV60D 7621592XC16S060-230 TXV 54500 15 11 CH23-65 SL280UH090V60C 7621594XC16S060-230 TXV 54000 14.5 11 CH23-65 SL280UH110XV60C 7621596XC16S060-230 TXV 54500 15 11 CH23-65 SL280UH135V60D 9150366XC16S060-230 TXV 54000 14.5 11 CH23-65 SLP98UH090XV60C 7621599XC16S060-230 TXV 54000 14.5 11 CH23-65 SLP98UH110XV60C 7621601XC16S060-230 TXV 54500 15 11 CH23-65 SLP98UH135XV60D 7621602XC16S060-230 TXV 54500 15 11 CH23-68 EL180UH135E60D 7621793XC16S060-230 TXV 57000 15 11.7 CH23-68 EL195UH135XE60D 7621606XC16S060-230 TXV 54500 14.5 11 CH23-68 EL296UH135XE60D 7621792XC16S060-230 TXV 57500 15.5 12 CH23-68 EL296UH135XV60D 7621607XC16S060-230 TXV 57000 15 11.7 CH23-68 SL280UH110V60C 8703411XC16S060-230 TXV 57000 15 11.7 CH23-68 SL280UH110XV60C 8703412Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 32: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 32

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S060-230 TXV 57500 15.5 12 CH23-68 SL280UH135V60D 7621609XC16S060-230 TXV 57000 15.5 12 CH23-68 SLP98UH135XV60D 7621610XC16S060-230 TXV 57500 14.5 11.7 CH23-68 7621604XC16S060-230 TXV 56000 15 11.7 CH33-50/60C EL180UH090E60C 7621798XC16S060-230 TXV 56000 15 11.7 CH33-50/60C EL180UH110E60C 7621800XC16S060-230 TXV 56000 15 11.7 CH33-50/60C EL180UH110XE60C 7621801XC16S060-230 TXV 56000 15 11.7 CH33-50/60C EL195UH110XE60C 7621616XC16S060-230 TXV 56000 15 11 CH33-50/60C EL296UH090XV60C 7621617XC16S060-230 TXV 56000 15 11.7 CH33-50/60C EL296UH110XE60C 7621803XC16S060-230 TXV 56000 15 11 CH33-50/60C EL296UH110XV60C 7621619XC16S060-230 TXV 56000 15 11 CH33-50/60C SL280UH090V60C 7621620XC16S060-230 TXV 56000 15 11 CH33-50/60C SL280UH090XV60C 7621796XC16S060-230 TXV 56000 14.5 11 CH33-50/60C SL280UH110V60C 7621622XC16S060-230 TXV 55500 15 11.7 CH33-50/60C SL280UH110XV60C 7621795XC16S060-230 TXV 56000 15 11 CH33-50/60C SLP98UH090XV60C 7621624XC16S060-230 TXV 56000 15 11 CH33-50/60C SLP98UH110XV60C 7621625XC16S060-230 TXV 56000 14 11 CH33-50/60C 7621612XC16S060-230 TXV 56000 15 11.7 CH33-60D CBWMV-60C-100 7621629XC16S060-230 TXV 56000 15 11 CH33-60D EL195UH135XE60D 7621631XC16S060-230 TXV 56000 15 11.7 CH33-60D EL296UH135XV60D 7621632XC16S060-230 TXV 56000 15 11.7 CH33-60D SL280UH135V60D 7621634XC16S060-230 TXV 56000 15.5 11.7 CH33-60D SLP98UH135XV60D 7621636XC16S060-230 TXV 55500 14 11 CH33-60D 7621627XC16S060-230 TXV 56500 15.5 11.7 CH33-62D EL180UH135E60D 7621806XC16S060-230 TXV 56500 15 11.7 CH33-62D EL195UH135XE60D 7621639XC16S060-230 TXV 56500 15 11.7 CH33-62D EL296UH135XE60D 7621804XC16S060-230 TXV 56500 15 11.7 CH33-62D EL296UH135XV60D 7621641XC16S060-230 TXV 56000 15 12 CH33-62D SL280UH090V60C 7621643XC16S060-230 TXV 56500 15.5 11.7 CH33-62D SL280UH090XV60C 7621808XC16S060-230 TXV 56000 15 12 CH33-62D SL280UH110V60C 7621645XC16S060-230 TXV 56500 15.5 11.7 CH33-62D SL280UH135V60D 7621646XC16S060-230 TXV 56500 15.5 11.7 CH33-62D SLP98UH135XV60D 7621648XC16S060-230 TXV 56000 14 11 CH33-62D 7621638XC16S060-230 TXV 57000 15.5 12 CH35-51C CBWMV-60C-100 7623755XC16S060-230 TXV 56500 15 11.5 CH35-51C CBWMV-60C-120 7623716XC16S060-230 TXV 57000 15.5 12 CH35-51C EL180UH090E60C 7623718XC16S060-230 TXV 56500 15.25 12 CH35-51C EL180UH110E60C 7623719XC16S060-230 TXV 56500 15.25 12 CH35-51C EL180UH110XE60C 7623721XC16S060-230 TXV 56500 15.25 12 CH35-51C EL195UH110XE60C 7623723XC16S060-230 TXV 56500 15 11 CH35-51C EL296UH090XV60C 7623724XC16S060-230 TXV 56500 15.25 12 CH35-51C EL296UH110XE60C 7623728XC16S060-230 TXV 56500 15.25 11.5 CH35-51C EL296UH110XV60C 7623726XC16S060-230 TXV 57000 15.25 11.7 CH35-51C SL280UH090V60C 7623729XC16S060-230 TXV 57000 15.25 11.7 CH35-51C SL280UH090XV60C 7623731XC16S060-230 TXV 56500 15 11.5 CH35-51C SL280UH110V60C 7623732XC16S060-230 TXV 56000 15.25 11.7 CH35-51C SL280UH110XV60C 7623734XC16S060-230 TXV 56500 15.25 11 CH35-51C SLP98UH090XV60C 7623736XC16S060-230 TXV 56500 15.25 11.5 CH35-51C SLP98UH110XV60C 7623737XC16S060-230 TXV 56500 14.5 11.5 CH35-51C 7623754XC16S060-230 TXV 56500 15.5 11.7 CH35-60D EL180UH135E60D 7623741XC16S060-230 TXV 56500 15 11.7 CH35-60D EL195UH135XE60D 7623742Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 33: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 33

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S060-230 TXV 56500 15 11.7 CH35-60D EL296UH135XE60D 7623746XC16S060-230 TXV 56500 15.5 11.7 CH35-60D EL296UH135XV60D 7623744XC16S060-230 TXV 56500 15.5 11.7 CH35-60D SL280UH135V60D 7623747XC16S060-230 TXV 56500 15.5 11.7 CH35-60D SLP98UH135XV60D 7623749XC16S060-230 TXV 56000 14.25 11.5 CH35-60D 7623739XC16S060-230 TXV 54000 14.5 11 CR33-50/60 EL296DF110XV60C 9114303XC16S060-230 TXV 55000 14.5 11 CR33-50/60 SL280DF090V60C 9105523XC16S060-230 TXV 55000 14.5 11 CR33-50/60 SL280DF110V60C 9105524XC16S060-230 TXV 54000 14.5 11 CR33-50/60 SLP98DF090XV60C 7621809XC16S060-230 TXV 54000 14.5 11 CR33-50/60 SLP98DF110XV60C 7621812XC16S060-230 TXV 54500 14.5 11.5 CR33-60 EL195DF110XE60C 7622671XC16S060-230 TXV 54500 14.5 11 CR33-60 EL296DF090XV60C 7621652XC16S060-230 TXV 54500 14.5 11 CR33-60 EL296DF110XV60C 7621653XC16S060-230 TXV 55000 14.5 11 CR33-60 SL280DF090V60C 9105525XC16S060-230 TXV 55000 14.5 11 CR33-60 SL280DF110V60C 9105526XC16S060-230 TXV 54000 14.5 11 CR33-60 SLP98DF090XV60C 7621811XC16S060-230 TXV 54000 14.5 11 CR33-60 SLP98DF110XV60C 7621814XC16S060-230 TXV 55000 14 11 CR33-60 7621650XC16S060-230 TXV 56000 15 11.7 CX35-48C EL180UH090E60C 8309475XC16S060-230 TXV 55500 15 11.7 CX35-48C EL180UH110E60C 8309476XC16S060-230 TXV 55500 15 11.7 CX35-48C EL180UH110XE60C 8309477XC16S060-230 TXV 55500 15 11.7 CX35-48C EL195UH110XE60C 8309478XC16S060-230 TXV 55500 15 11 CX35-48C EL296UH090XV60C 8309479XC16S060-230 TXV 55500 15 11.7 CX35-48C EL296UH110XE60C 8309481XC16S060-230 TXV 55500 15 11 CX35-48C EL296UH110XV60C 8309480XC16S060-230 TXV 56000 15 11.5 CX35-48C SL280UH090V60C 8309482XC16S060-230 TXV 56000 15 11.5 CX35-48C SL280UH090XV60C 8309483XC16S060-230 TXV 55500 15 11 CX35-48C SL280UH110V60C 8309484XC16S060-230 TXV 55500 15 11 CX35-48C SL280UH110XV60C 8309485XC16S060-230 TXV 55500 15 11 CX35-48C SLP98UH090XV60C 8309486XC16S060-230 TXV 55500 15 11 CX35-48C SLP98UH110XV60C 8309487XC16S060-230 TXV 55500 14 11 CX35-48C 8309474XC16S060-230 TXV 56500 15 12 CX35-49C EL180UH090E60C 8309489XC16S060-230 TXV 56500 15 12 CX35-49C EL180UH110E60C 8309490XC16S060-230 TXV 56500 15 12 CX35-49C EL180UH110XE60C 8309491XC16S060-230 TXV 56500 15 12 CX35-49C EL195UH110XE60C 8309492XC16S060-230 TXV 56500 15 11 CX35-49C EL296UH090XV60C 8309493XC16S060-230 TXV 56500 15 12 CX35-49C EL296UH110XE60C 8309495XC16S060-230 TXV 56000 15 11 CX35-49C EL296UH110XV60C 8309494XC16S060-230 TXV 56500 15 11.7 CX35-49C SL280UH090V60C 8309496XC16S060-230 TXV 56500 15 11.7 CX35-49C SL280UH090XV60C 8309497XC16S060-230 TXV 56500 15 11.7 CX35-49C SL280UH110V60C 8309498XC16S060-230 TXV 56500 15 11.7 CX35-49C SL280UH110XV60C 8309499XC16S060-230 TXV 56500 15 11 CX35-49C SLP98UH090XV60C 8309500XC16S060-230 TXV 56000 15 11 CX35-49C SLP98UH110XV60C 8309501XC16S060-230 TXV 56500 14 11 CX35-49C 8309488XC16S060-230 TXV 54000 14.5 11 CX35-50/60C CBWMV-60C-120 8309502XC16S060-230 TXV 55000 15 11.7 CX35-50/60C EL180UH090E60C 8309503XC16S060-230 TXV 55000 14.5 11.7 CX35-50/60C EL180UH110E60C 8309504XC16S060-230 TXV 55000 14.5 11.7 CX35-50/60C EL180UH110XE60C 8309505XC16S060-230 TXV 55000 15 11.7 CX35-50/60C EL195UH110XE60C 8309506Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 34: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 34

AHRI SYSTEM MATCHES - NORTH / SOUTH REGIONSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16S060-230 TXV 55000 14.5 11 CX35-50/60C EL296UH090XV60C 8309507XC16S060-230 TXV 55000 15 11.7 CX35-50/60C EL296UH110XE60C 8309509XC16S060-230 TXV 55000 14.5 11 CX35-50/60C EL296UH110XV60C 8309508XC16S060-230 TXV 55000 14.5 11 CX35-50/60C SL280UH090V60C 8309511XC16S060-230 TXV 55000 15 11 CX35-50/60C SL280UH090XV60C 8309510XC16S060-230 TXV 55000 14.5 11 CX35-50/60C SL280UH110V60C 8309512XC16S060-230 TXV 54500 14.5 11 CX35-50/60C SL280UH110XV60C 8309513XC16S060-230 TXV 55000 14.5 11 CX35-50/60C SLP98UH090XV60C 8309514XC16S060-230 TXV 55000 14.5 11 CX35-50/60C SLP98UH110XV60C 8309515XC16S060-230 TXV 57500 15.5 12.2 CX35-60C EL180UH090E60C 8309517XC16S060-230 TXV 57500 15.5 12.2 CX35-60C EL180UH110E60C 8309518XC16S060-230 TXV 57500 15.5 12.2 CX35-60C EL180UH110XE60C 8309519XC16S060-230 TXV 57500 15.5 12.2 CX35-60C EL195UH110XE60C 8309520XC16S060-230 TXV 57500 15.5 11.7 CX35-60C EL296UH090XV60C 8309521XC16S060-230 TXV 57500 15.5 12.2 CX35-60C EL296UH110XE60C 8309523XC16S060-230 TXV 57000 15.5 11.7 CX35-60C EL296UH110XV60C 8309522XC16S060-230 TXV 57500 16 12 CX35-60C SL280UH090V60C 8309524XC16S060-230 TXV 57500 15.5 12 CX35-60C SL280UH090XV60C 8309525XC16S060-230 TXV 57500 15.5 11.7 CX35-60C SL280UH110V60C 8309526XC16S060-230 TXV 57500 15 11.7 CX35-60C SL280UH110XV60C 8309527XC16S060-230 TXV 57000 15 11.7 CX35-60C SLO185UF124/141V60 8309528XC16S060-230 TXV 57500 15.5 11.7 CX35-60C SLP98UH090XV60C 8309529XC16S060-230 TXV 57000 15.5 11.7 CX35-60C SLP98UH110XV60C 8309530XC16S060-230 TXV 57500 14.5 11.7 CX35-60C 8309516XC16S060-230 TXV 57000 15.5 12 CX35-60D EL180UH135E60D 8309532XC16S060-230 TXV 57000 15 11.7 CX35-60D EL195UH135XE60D 8309533XC16S060-230 TXV 57000 15 11.7 CX35-60D EL296UH135XE60D 8309535XC16S060-230 TXV 57000 15.5 11.7 CX35-60D EL296UH135XV60D 8309534XC16S060-230 TXV 57000 15.5 12 CX35-60D SL280UH135V60D 8309536XC16S060-230 TXV 57000 15 11.7 CX35-60D SLO185B124/141V60 8309537XC16S060-230 TXV 56000 15 11.7 CX35-60D SLO185UF124/141V60 8309538XC16S060-230 TXV 57000 15.5 12 CX35-60D SLP98UH135XV60D 8309539XC16S060-230 TXV 56500 14 11 CX35-60D 8309531XC16S060-230 TXV 57500 16 12 CX38-62C SL280UH090V60C 10559616Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 35: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 35

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-024-230 TXV 23200 15 12.2 C35-18/24B EL195UH030XE24B 8604043XC16-024-230 TXV 23200 15 12.2 C35-18/24B EL195UH045XE24B 8604042XC16-024-230 TXV 24800 16 13 C35-24A SL280UH070V36A 8256126XC16-024-230 TXV 23800 15.5 12.5 C35-24B EL195UH030XE24B 8595376XC16-024-230 TXV 23800 15.5 12.5 C35-24B EL195UH045XE24B 8595321XC16-024-230 TXV 24800 16 13 C35-24B EL296UH045XV36B 8256125XC16-024-230 TXV 24600 15.1 13 C35-24B SL280UH090V36B 8256127XC16-024-230 TXV 24600 16 13 C35-24B SLP98UH070XV36B 8256124XC16-024-230 TXV 24600 16 13 C35-30/36A SL280UH070V36A 8256138XC16-024-230 TXV 24800 16 13 C35-30/36A SL280UH070XV36A 8256134XC16-024-230 TXV 24600 16 13 C35-30/36B CBWMV-24B-040 8256136XC16-024-230 TXV 23800 15.5 12.5 C35-30/36B EL195UH030XE24B 8595377XC16-024-230 TXV 23800 15.5 12.5 C35-30/36B EL195UH045XE24B 8595322XC16-024-230 TXV 24600 16 13 C35-30/36B EL296UH045XV36B 8256139XC16-024-230 TXV 24400 15.1 13 C35-30/36B SL280UH090V36B 8256133XC16-024-230 TXV 24600 16 13 C35-30/36B SLP98UH070XV36B 8256137XC16-024-230 TXV 24600 16 13.5 C35-30/36C SLP98UH090XV36C 8256135XC16-024-230 TXV 25200 17 13 C35-30A SL280UH070V36A 8256130XC16-024-230 TXV 25400 17 13.5 C35-30A SL280UH070XV36A 8256128XC16-024-230 TXV 23800 16 12.5 C35-30B EL195UH030XE24B 8595380XC16-024-230 TXV 23800 16 12.5 C35-30B EL195UH045XE24B 8595325XC16-024-230 TXV 25200 16 13.5 C35-30B EL296UH045XV36B 8256131XC16-024-230 TXV 25000 16 13.5 C35-30B SL280UH090V36B 8256132XC16-024-230 TXV 25200 16 13.5 C35-30B SLP98UH070XV36B 8256129XC16-024-230 TXV 25400 17 13.5 C35-36A SL280UH070V36A 8256145XC16-024-230 TXV 25400 17 13.5 C35-36A SL280UH070XV36A 8256142XC16-024-230 TXV 24800 14.5 12.2 C35-36A 8256140XC16-024-230 TXV 23800 16 13 C35-36B EL195UH030XE24B 8595381XC16-024-230 TXV 23800 16 13 C35-36B EL195UH045XE24B 8595326XC16-024-230 TXV 25400 16 13.5 C35-36B EL296UH045XV36B 8256146XC16-024-230 TXV 25200 16 13.5 C35-36B SL280UH090V36B 8256143XC16-024-230 TXV 25200 16 13.5 C35-36B SLP98UH070XV36B 8256144XC16-024-230 TXV 24800 14.5 12.2 C35-36B 8256141XC16-024-230 TXV 24000 16 13 CBA27UHE-024 10259508XC16-024-230 TXV 24000 17 13 CBA27UHE-030 10259495XC16-024-230 TXV 24000 16 13 CBX25UHV-024 6970136XC16-024-230 TXV 25000 16 13.5 CBX27UH-024 6742502XC16-024-230 TXV 25200 17 13.5 CBX27UH-030 6742503XC16-024-230 TXV 24400 15.5 12.2 CBX32MV-018/024 6742505XC16-024-230 TXV 24600 15.5 12.5 CBX32MV-024/030 6742506XC16-024-230 TXV 24800 16 12.5 CBX40UHV-024 6742599XC16-024-230 TXV 24800 15.5 13 CBX40UHV-030 6742600XC16-024-230 TXV 23600 15.5 13 CH23-31 EL296UH070XV36B 6742601XC16-024-230 TXV 23600 15.1 12.5 CH23-31 SL280UH070V36A 6742508XC16-024-230 TXV 23800 16 12.5 CH23-31 SL280UH070XV36A 6742602XC16-024-230 TXV 23400 15 12.5 CH23-31 SL280UH090V36B 6742509XC16-024-230 TXV 23600 15.5 13 CH23-31 SLP98UH070XV36B 6742510XC16-024-230 TXV 23800 15.5 12.5 CH23-41 EL195UH030XE24B 8595382XC16-024-230 TXV 23800 15.5 12.5 CH23-41 EL195UH045XE24B 8595329XC16-024-230 TXV 24600 16 13 CH23-41 EL296UH070XV36B 6742603XC16-024-230 TXV 24800 16 13 CH23-41 SL280UH070V36A 6742512Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 36: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 36

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-024-230 TXV 24800 16 13 CH23-41 SL280UH070XV36A 6742604XC16-024-230 TXV 24600 15.1 13 CH23-41 SL280UH090V36B 6742513XC16-024-230 TXV 24800 15.1 13 CH23-41 SL280UH090V48B 6742605XC16-024-230 TXV 24600 16 13 CH23-41 SLP98UH070XV36B 6742514XC16-024-230 TXV 24200 16 13 CH33-19 SL280UH070V36A 6742516XC16-024-230 TXV 24400 16 13 CH33-19 SL280UH070XV36A 6742606XC16-024-230 TXV 24200 16 12.5 CH33-24/30 SL280UH070V36A 6742518XC16-024-230 TXV 23800 15.5 12.5 CH33-25 EL195UH030XE24B 8595385XC16-024-230 TXV 23800 15.5 12.5 CH33-25 EL195UH045XE24B 8595330XC16-024-230 TXV 24600 16 13 CH33-25 EL296UH045XV36B 6742522XC16-024-230 TXV 24600 16 13 CH33-25 EL296UH070XV36B 6742607XC16-024-230 TXV 24800 16 13 CH33-25 SL280UH070V36A 6742520XC16-024-230 TXV 25000 16 13 CH33-25 SL280UH070XV36A 6742608XC16-024-230 TXV 24400 15.1 13 CH33-25 SL280UH090V36B 6742523XC16-024-230 TXV 24800 15.1 13 CH33-25 SL280UH090V48B 6742609XC16-024-230 TXV 24600 16 13 CH33-25 SLP98UH070XV36B 6742524XC16-024-230 TXV 23800 16 12.5 CH33-31 EL195UH030XE24B 8595386XC16-024-230 TXV 23800 16 12.5 CH33-31 EL195UH045XE24B 8595332XC16-024-230 TXV 25200 16 13.5 CH33-31 EL296UH045XV36B 6742528XC16-024-230 TXV 25200 17 13.5 CH33-31 EL296UH070XV36B 6742610XC16-024-230 TXV 25200 16 13 CH33-31 SL280UH070V36A 6742526XC16-024-230 TXV 25400 16 13 CH33-31 SL280UH070XV36A 6742611XC16-024-230 TXV 25200 16 13.5 CH33-31 SL280UH090V36B 6742529XC16-024-230 TXV 25400 16 13 CH33-31 SL280UH090V48B 6742612XC16-024-230 TXV 25200 16 13.5 CH33-31 SLP98UH070XV36B 6742530XC16-024-230 TXV 24800 14.5 12.2 CH33-31B 6742527XC16-024-230 TXV 23800 15.5 12.5 CH33-36 EL195UH030XE24B 8595389XC16-024-230 TXV 23800 15.5 12.5 CH33-36 EL195UH045XE24B 8595333XC16-024-230 TXV 24600 16 13 CH33-36 EL296UH045XV36B 6742534XC16-024-230 TXV 24600 16 13 CH33-36 EL296UH070XV36B 6742613XC16-024-230 TXV 24600 16 13 CH33-36 SL280UH070V36A 6742532XC16-024-230 TXV 24600 16 13 CH33-36 SL280UH070XV36A 6742614XC16-024-230 TXV 24400 15.1 13 CH33-36 SL280UH090V36B 6742535XC16-024-230 TXV 24600 16 13 CH33-36 SLP98UH070XV36B 6742536XC16-024-230 TXV 24800 16 13.5 CH33-36C EL296UH090XV36C 6742615XC16-024-230 TXV 24800 16.5 13.5 CH33-36C SLP98UH090XV36C 6742616XC16-024-230 TXV 24000 16 13 CH35-18A SL280UH070V36A 7165584XC16-024-230 TXV 24000 16 13 CH35-18A SL280UH070XV36A 7165458XC16-024-230 TXV 24000 16 13 CH35-24A SL280UH070V36A 7165585XC16-024-230 TXV 24000 16 13 CH35-24A SL280UH070XV36A 7165460XC16-024-230 TXV 23800 15.5 12.5 CH35-24B EL195UH030XE24B 8595390XC16-024-230 TXV 23800 15.5 12.5 CH35-24B EL195UH045XE24B 8595334XC16-024-230 TXV 24000 16 13 CH35-24B EL296UH045XV36B 7165462XC16-024-230 TXV 24000 16 13 CH35-24B EL296UH070XV36B 7165463XC16-024-230 TXV 24000 15.1 13 CH35-24B SL280UH090V36B 7165586XC16-024-230 TXV 24000 15.1 13 CH35-24B SL280UH090V48B 7165464XC16-024-230 TXV 24000 16 13 CH35-24B SLP98UH070XV36B 7165587XC16-024-230 TXV 24000 16 13 CH35-30A SL280UH070V36A 7165588XC16-024-230 TXV 24000 17 13 CH35-30A SL280UH070XV36A 7165466XC16-024-230 TXV 24000 14.5 12.2 CH35-30A 7165465XC16-024-230 TXV 23800 16 12.5 CH35-30B EL195UH030XE24B 8595393Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 37: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 37

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-024-230 TXV 23800 16 12.5 CH35-30B EL195UH045XE24B 8595337XC16-024-230 TXV 24000 16 13 CH35-30B EL296UH045XV36B 7165468XC16-024-230 TXV 24000 17 13 CH35-30B EL296UH070XV36B 7165469XC16-024-230 TXV 24000 16 13 CH35-30B SL280UH090V36B 7165589XC16-024-230 TXV 24000 16 13 CH35-30B SL280UH090V48B 7165470XC16-024-230 TXV 24000 16 13 CH35-30B SLP98UH070XV36B 7165590XC16-024-230 TXV 24000 14.5 12.2 CH35-30B 7165467XC16-024-230 TXV 24000 16 13 CH35-36A SL280UH070V36A 7165591XC16-024-230 TXV 24000 16 13 CH35-36A SL280UH070XV36A 7165472XC16-024-230 TXV 23800 15.5 12.5 CH35-36B EL195UH030XE24B 8595394XC16-024-230 TXV 23800 15.5 12.5 CH35-36B EL195UH045XE24B 8595338XC16-024-230 TXV 24000 16 13 CH35-36B EL296UH045XV36B 7165475XC16-024-230 TXV 24000 16 13 CH35-36B EL296UH070XV36B 7165476XC16-024-230 TXV 24000 15.1 13 CH35-36B SL280UH090V36B 7165592XC16-024-230 TXV 24000 16 13 CH35-36B SLP98UH070XV36B 7165593XC16-024-230 TXV 24000 16 13 CH35-36C EL296UH090XV36C 7165477XC16-024-230 TXV 24000 16 13 CH35-36C SLP98UH090XV36C 7165478XC16-024-230 TXV 25200 17 13.5 CR33-30/36 EL296DF045XV36B 7505729XC16-024-230 TXV 25200 16 13 CR33-30/36 EL296DF070XV48B 6742539XC16-024-230 TXV 25200 16 13 CR33-30/36 SL280DF070V36A 6742830XC16-024-230 TXV 24600 16 13.5 CR33-30/36 SLP98DF070XV36B 6742617XC16-024-230 TXV 25000 16 13.5 CR33-30/36 SLP98DF090XV36C 6742618XC16-024-230 TXV 23600 15.1 12.5 CX35-18/24A SL280UH070V36A 8256153XC16-024-230 TXV 23800 15.1 12.5 CX35-18/24A SL280UH070XV36A 8256148XC16-024-230 TXV 23600 15 12.5 CX35-18/24B CBWMV-24B-040 8256149XC16-024-230 TXV 23200 15 12.2 CX35-18/24B EL195UH030XE24B 8595353XC16-024-230 TXV 23200 15 12.2 CX35-18/24B EL195UH045XE24B 8595298XC16-024-230 TXV 23600 15 12.5 CX35-18/24B EL296UH045XV36B 8256152XC16-024-230 TXV 23600 15.5 12.5 CX35-18/24B EL296UH070XV36B 8256147XC16-024-230 TXV 23400 14.5 12.5 CX35-18/24B SL280UH090V36B 8256150XC16-024-230 TXV 23600 15 12.5 CX35-18/24B SLP98UH070XV36B 8256151XC16-024-230 TXV 24800 16 13 CX35-24A SL280UH070V36A 8256158XC16-024-230 TXV 24800 16 13 CX35-24A SL280UH070XV36A 8256155XC16-024-230 TXV 23800 15.5 12.5 CX35-24B EL195UH030XE24B 8595354XC16-024-230 TXV 23800 15.5 12.5 CX35-24B EL195UH045XE24B 8595299XC16-024-230 TXV 24800 16 13 CX35-24B EL296UH045XV36B 8256157XC16-024-230 TXV 24800 16 13.5 CX35-24B EL296UH070XV36B 8256154XC16-024-230 TXV 24600 15.1 13 CX35-24B SL280UH090V36B 8256159XC16-024-230 TXV 24800 16 13 CX35-24B SL280UH090V48B 8256156XC16-024-230 TXV 24600 16 13 CX35-24B SLP98UH070XV36B 8256160XC16-024-230 TXV 24600 16 13 CX35-30/36A SL280UH070V36A 8256174XC16-024-230 TXV 24800 16 13 CX35-30/36A SL280UH070XV36A 8256169XC16-024-230 TXV 24000 16 13 CX35-30/36B CBWMV-24B-040 8256171XC16-024-230 TXV 23800 15.5 12.5 CX35-30/36B EL195UH030XE24B 8595357XC16-024-230 TXV 23800 15.5 12.5 CX35-30/36B EL195UH045XE24B 8595302XC16-024-230 TXV 24600 16 13 CX35-30/36B EL296UH045XV36B 8256175XC16-024-230 TXV 24600 16 13 CX35-30/36B EL296UH070XV36B 8256172XC16-024-230 TXV 24400 16 13 CX35-30/36B SL280UH090V36B 8256168XC16-024-230 TXV 24600 16 13 CX35-30/36B SLP98UH070XV36B 8256176XC16-024-230 TXV 24600 16 13.5 CX35-30/36C EL296UH090XV36C 8256173XC16-024-230 TXV 24600 16 13.5 CX35-30/36C SLP98UH090XV36C 8256170Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 38: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 38

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-024-230 TXV 25200 17 13 CX35-30A SL280UH070V36A 8256167XC16-024-230 TXV 25400 17 13.5 CX35-30A SL280UH070XV36A 8256162XC16-024-230 TXV 23800 16 12.5 CX35-30B EL195UH030XE24B 8595358XC16-024-230 TXV 23800 16 12.5 CX35-30B EL195UH045XE24B 8595303XC16-024-230 TXV 25200 16 13.5 CX35-30B EL296UH045XV36B 8256164XC16-024-230 TXV 25200 16 13.5 CX35-30B EL296UH070XV36B 8256161XC16-024-230 TXV 25000 16 13.5 CX35-30B SL280UH090V36B 8256165XC16-024-230 TXV 25200 16 13 CX35-30B SL280UH090V48B 8256163XC16-024-230 TXV 25200 16 13.5 CX35-30B SLP98UH070XV36B 8256166XC16-024-230 TXV 25400 17 13.5 CX35-36A SL280UH070V36A 8256183XC16-024-230 TXV 25400 17 13.5 CX35-36A SL280UH070XV36A 8256180XC16-024-230 TXV 24800 14.5 12.2 CX35-36A 8256177XC16-024-230 TXV 23800 16 13 CX35-36B EL195UH030XE24B 8595361XC16-024-230 TXV 23800 16 13 CX35-36B EL195UH045XE24B 8595306XC16-024-230 TXV 25400 16 13.5 CX35-36B EL296UH045XV36B 8256184XC16-024-230 TXV 25200 17 13.5 CX35-36B EL296UH070XV36B 8256179XC16-024-230 TXV 25200 16 13.5 CX35-36B SL280UH090V36B 8256185XC16-024-230 TXV 25400 16 13.5 CX35-36B SL280UH090V48B 8256181XC16-024-230 TXV 25200 16 13.5 CX35-36B SLP98UH070XV36B 8256182XC16-024-230 TXV 24800 14.5 12.2 CX35-36B 8256178XC16-024-230 TXV 24400 16 13 CX38-36B SL280UH090V36B 10558790XC16-036-230 TXV 35200 15 12.2 C35-30/36B SL280UH090XV48B 8256187XC16-036-230 TXV 35000 15 12.2 C35-30/36C EL296UH110XV48C 8256189XC16-036-230 TXV 35400 15 12.2 C35-30/36C EL296UH110XV60C 8256186XC16-036-230 TXV 35400 15 12.2 C35-30/36C SLP98UH110XV60C 8256188XC16-036-230 TXV 36400 15.5 12.2 C35-36A EL180UH045E36A 8256195XC16-036-230 TXV 36400 15.5 12.2 C35-36A EL180UH045XE36A 8256191XC16-036-230 TXV 36400 15.5 12.2 C35-36A SL280UH070V36A 8256201XC16-036-230 TXV 36400 15.5 12.2 C35-36A SL280UH070XV36A 8256193XC16-036-230 TXV 36400 15.5 12.2 C35-36B EL180UH070E36B 8256192XC16-036-230 TXV 36200 15.5 12.2 C35-36B EL195UH070XE36B 8256198XC16-036-230 TXV 36200 15.5 12.2 C35-36B EL296UH045XV36B 8256199XC16-036-230 TXV 36400 15.5 12.2 C35-36B EL296UH070XV36B 8256190XC16-036-230 TXV 36600 15.5 12.5 C35-36B SL280UH090V36B 8256200XC16-036-230 TXV 36400 15.5 12.5 C35-36B SL280UH090V48B 8256196XC16-036-230 TXV 36600 15.5 12.5 C35-36B SL280UH090XV48B 8256194XC16-036-230 TXV 36400 15.5 12.2 C35-36B SLP98UH070XV36B 8256197XC16-036-230 TXV 36600 15.5 12.2 C35-48B EL180UH070XE36B 8256203XC16-036-230 TXV 36400 15.5 12.2 C35-48B EL195UH070XE36B 8256217XC16-036-230 TXV 36600 15.5 12.2 C35-48B EL296UH045XV36B 8256218XC16-036-230 TXV 36600 15.5 12.2 C35-48B EL296UH070XV36B 8256205XC16-036-230 TXV 36000 16 12.5 C35-48B SL280UH090V48B 8256213XC16-036-230 TXV 36000 16 12.5 C35-48B SL280UH090XV48B 8256208XC16-036-230 TXV 36600 15.5 12.2 C35-48B SLP98UH070XV36B 8256214XC16-036-230 TXV 36600 15.5 12.5 C35-48C CBWMV-36C-090 8256207XC16-036-230 TXV 37000 16 12.5 C35-48C CBWMV-60C-100 8256204XC16-036-230 TXV 36600 16 12.5 C35-48C EL296UH110XV48C 8256215XC16-036-230 TXV 37000 15.1 12.5 C35-48C SL280UH090XV60C 8256206XC16-036-230 TXV 36800 15.1 12.5 C35-48C SL280UH110V60C 8256202XC16-036-230 TXV 36800 15.1 12.5 C35-48C SL280UH110XV60C 8256216XC16-036-230 TXV 36800 15.5 12.5 C35-48C SLP98UH090XV36C 8256210Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 39: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 39

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-036-230 TXV 36800 16 12.5 C35-48C SLP98UH090XV48C 8256211XC16-036-230 TXV 37200 16 12.5 C35-48C SLP98UH090XV60C 8256212XC16-036-230 TXV 37000 15.5 12.5 C35-48C SLP98UH110XV60C 8256209XC16-036-230 TXV 36000 15.5 12.5 C35-49C EL296UH090XE48C 8256219XC16-036-230 TXV 37000 15.5 12.5 C35-49C EL296UH090XV36C 8256222XC16-036-230 TXV 37600 16 12.5 C35-49C SL280UH090V60C 8256227XC16-036-230 TXV 37600 16 12.5 C35-49C SL280UH090XV60C 8256220XC16-036-230 TXV 37200 15.1 12.5 C35-49C SL280UH110V60C 8256228XC16-036-230 TXV 37400 15.1 12.5 C35-49C SL280UH110XV60C 8256221XC16-036-230 TXV 37000 16 12.5 C35-49C SLP98UH090XV36C 8256224XC16-036-230 TXV 37400 16 12.5 C35-49C SLP98UH090XV48C 8256225XC16-036-230 TXV 37600 16 12.5 C35-49C SLP98UH090XV60C 8256226XC16-036-230 TXV 37400 16 12.5 C35-49C SLP98UH110XV60C 8256223XC16-036-230 TXV 36400 16 12.5 C35-50/60C EL296UH110XV48C 8256229XC16-036-230 TXV 36000 15 12.2 CBA27UHE-036 10259496XC16-036-230 TXV 36000 16 12.5 CBA27UHE-042 10259497XC16-036-230 TXV 36000 15.5 12.2 CBX25UHV-036 6970138XC16-036-230 TXV 37000 16 13 CBX25UHV-042 7040824XC16-036-230 TXV 35800 15 12.2 CBX27UH-036 6507591XC16-036-230 TXV 37000 16 12.5 CBX27UH-042 6507593XC16-036-230 TXV 37000 16 12.5 CBX32MV-048 6507605XC16-036-230 TXV 36600 15.5 12.2 CBX40UHV-042 6508725XC16-036-230 TXV 36600 15 12.5 CBX40UHV-048 6508727XC16-036-230 TXV 35600 15.5 12.2 CH23-41 EL296UH090XV36C 6508742XC16-036-230 TXV 35400 15.5 12.2 CH23-41 EL296UH090XV48C 6508745XC16-036-230 TXV 36000 15.5 12.2 CH23-41 EL296UH090XV60C 6508748XC16-036-230 TXV 35600 15.5 12.5 CH23-41 EL296UH110XV48C 6507618XC16-036-230 TXV 36000 15.5 12.5 CH23-41 EL296UH110XV60C 6508750XC16-036-230 TXV 35400 15.5 12.5 CH23-41 SL280UH090V36B 6507624XC16-036-230 TXV 35600 15 12.5 CH23-41 SL280UH090V48B 6507626XC16-036-230 TXV 36000 15.1 12.5 CH23-41 SL280UH090V60C 6507629XC16-036-230 TXV 35600 15.5 12.5 CH23-41 SL280UH090XV48B 6508754XC16-036-230 TXV 36000 15.1 12.5 CH23-41 SL280UH090XV60C 6508756XC16-036-230 TXV 35800 15.1 12.2 CH23-41 SL280UH110V60C 6507633XC16-036-230 TXV 35800 15.1 12.2 CH23-41 SL280UH110XV60C 6508759XC16-036-230 TXV 35600 15.5 12.2 CH23-41 SLP98UH090XV36C 6507641XC16-036-230 TXV 35400 15.5 12.2 CH23-41 SLP98UH090XV48C 6507644XC16-036-230 TXV 36000 15.5 12.2 CH23-41 SLP98UH090XV60C 6507650XC16-036-230 TXV 36000 15.5 12.5 CH23-41 SLP98UH110XV60C 6507653XC16-036-230 TXV 35600 15 12.5 CH23-51 EL180UH070E36B 6507667XC16-036-230 TXV 35600 15 12.2 CH23-51 EL195UH070XE36B 6507659XC16-036-230 TXV 35800 15.5 12.5 CH23-51 EL296UH110XV48C 6507664XC16-036-230 TXV 36000 15 12.2 CH23-65 EL195UH070XE36B 6507678XC16-036-230 TXV 36200 15.5 12.5 CH23-65 EL296UH090XV36C 6508772XC16-036-230 TXV 36000 15.5 12.5 CH23-65 EL296UH090XV48C 6508784XC16-036-230 TXV 36600 16 12.5 CH23-65 EL296UH090XV60C 6508787XC16-036-230 TXV 36400 16 12.5 CH23-65 EL296UH110XV60C 6508789XC16-036-230 TXV 36600 15.1 12.5 CH23-65 SL280UH090V60C 6507687XC16-036-230 TXV 36600 15.1 12.5 CH23-65 SL280UH090XV60C 6508795XC16-036-230 TXV 36400 15.1 12.5 CH23-65 SL280UH110V60C 6507691XC16-036-230 TXV 36400 15.1 12.5 CH23-65 SL280UH110XV60C 6508792Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 40: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 40

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-036-230 TXV 36200 15.5 12.5 CH23-65 SLP98UH090XV36C 6507695XC16-036-230 TXV 36000 15.5 12.5 CH23-65 SLP98UH090XV48C 6507699XC16-036-230 TXV 36600 15.5 12.5 CH23-65 SLP98UH090XV60C 6507702XC16-036-230 TXV 36400 15.5 12.5 CH23-65 SLP98UH110XV60C 6507706XC16-036-230 TXV 35600 15 12.2 CH33-36 EL296UH090XV36C 6508801XC16-036-230 TXV 35400 15.5 12.2 CH33-36 EL296UH090XV48C 6508804XC16-036-230 TXV 36000 15.5 12.2 CH33-36 EL296UH090XV60C 6508807XC16-036-230 TXV 35800 15.5 12.2 CH33-36 EL296UH110XV60C 6508810XC16-036-230 TXV 36000 15.1 12.2 CH33-36 SL280UH090V60C 6507766XC16-036-230 TXV 36000 15.1 12.2 CH33-36 SL280UH090XV60C 6508817XC16-036-230 TXV 35600 15 12.2 CH33-36 SLP98UH090XV36C 6507774XC16-036-230 TXV 35400 15 12.2 CH33-36 SLP98UH090XV48C 6507777XC16-036-230 TXV 36000 15.5 12.2 CH33-36 SLP98UH090XV60C 6507783XC16-036-230 TXV 35800 15.5 12.2 CH33-36 SLP98UH110XV60C 6507786XC16-036-230 TXV 35600 15.5 12.2 CH33-36C EL296UH110XV48C 6507762XC16-036-230 TXV 36000 15.5 12.2 CH33-42 SL280UH090V36B 6507810XC16-036-230 TXV 35800 15 12.2 CH33-42 SL280UH090V48B 6507814XC16-036-230 TXV 36000 15 12.2 CH33-42 SL280UH090XV48B 6508834XC16-036-230 TXV 37200 16 12.5 CH33-43 EL180UH070E36B 6508853XC16-036-230 TXV 37000 15 12.2 CH33-43 EL195UH070XE36B 6507832XC16-036-230 TXV 37000 15.5 12.2 CH33-43 EL296UH045XV36B 6507835XC16-036-230 TXV 37000 15 12.2 CH33-43 EL296UH070XE36B 6508859XC16-036-230 TXV 37000 15.5 12.2 CH33-43 EL296UH070XV36B 6508862XC16-036-230 TXV 36800 15.5 12.5 CH33-43 EL296UH090XV36C 6508864XC16-036-230 TXV 36600 16 12.5 CH33-43 EL296UH090XV48C 6508868XC16-036-230 TXV 37200 16 12.5 CH33-43 EL296UH090XV60C 6508870XC16-036-230 TXV 37200 16 12.5 CH33-43 EL296UH110XV60C 6508873XC16-036-230 TXV 37600 16 12.5 CH33-43 SL280UH090V36B 6507842XC16-036-230 TXV 36000 16 12.5 CH33-43 SL280UH090V48B 6507846XC16-036-230 TXV 37200 15.1 12.5 CH33-43 SL280UH090V60C 6507862XC16-036-230 TXV 36000 16 12.5 CH33-43 SL280UH090XV48B 6508878XC16-036-230 TXV 37200 16 12.5 CH33-43 SL280UH090XV60C 6508848XC16-036-230 TXV 37000 15.1 12.5 CH33-43 SL280UH110V60C 6507866XC16-036-230 TXV 37000 15.1 12.5 CH33-43 SL280UH110XV60C 6508851XC16-036-230 TXV 37000 15.5 12.2 CH33-43 SLP98UH070XV36B 6507850XC16-036-230 TXV 36800 15.5 12.5 CH33-43 SLP98UH090XV36C 6507869XC16-036-230 TXV 37000 16 12.5 CH33-43 SLP98UH090XV48C 6507873XC16-036-230 TXV 37200 16 12.5 CH33-43 SLP98UH090XV60C 6507876XC16-036-230 TXV 37200 16 12.5 CH33-43 SLP98UH110XV60C 6507879XC16-036-230 TXV 36800 16 12.5 CH33-43C EL296UH110XV48C 6507857XC16-036-230 TXV 36400 15.5 12.2 CH33-44/48 EL180UH070E36B 6508883XC16-036-230 TXV 36800 15.5 12.5 CH33-44/48 SL280UH090V36B 6507904XC16-036-230 TXV 36400 15 12.2 CH33-44/48 SL280UH090V48B 6507912XC16-036-230 TXV 36400 15.5 12.2 CH33-44/48 SL280UH090XV48B 6508879XC16-036-230 TXV 36400 15.5 12.2 CH33-44/48 SLP98UH070XV36B 6507914XC16-036-230 TXV 36600 15.5 12.5 CH33-48 EL296UH090XV36C 6508901XC16-036-230 TXV 36400 15.5 12.5 CH33-48 EL296UH090XV48C 6508903XC16-036-230 TXV 37000 16 12.5 CH33-48 EL296UH090XV60C 6508907XC16-036-230 TXV 36800 16 12.5 CH33-48 EL296UH110XV60C 6508909XC16-036-230 TXV 37000 15.1 12.5 CH33-48 SL280UH090V60C 6507926XC16-036-230 TXV 37000 15.1 12.5 CH33-48 SL280UH090XV60C 6508898Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 41: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 41

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-036-230 TXV 36800 15.1 12.2 CH33-48 SL280UH110V60C 6507930XC16-036-230 TXV 36800 15.1 12.5 CH33-48 SL280UH110XV60C 6508895XC16-036-230 TXV 36600 15.5 12.5 CH33-48 SLP98UH090XV36C 6507934XC16-036-230 TXV 36800 16 12.5 CH33-48 SLP98UH090XV48C 6507938XC16-036-230 TXV 37000 15.5 12.5 CH33-48 SLP98UH090XV60C 6507942XC16-036-230 TXV 36800 15.5 12.5 CH33-48 SLP98UH110XV60C 6507945XC16-036-230 TXV 36600 16 12.5 CH33-48C EL296UH110XV48C 6507922XC16-036-230 TXV 37000 16 12.5 CH33-50/60C EL296UH110XV48C 6507949XC16-036-230 TXV 35200 15 12.2 CH35-36B SL280UH090V48B 7165648XC16-036-230 TXV 35200 15.1 12.2 CH35-36B SL280UH090XV48B 7165491XC16-036-230 TXV 35600 15.1 12.2 CH35-36C EL296UH090XV36C 7165493XC16-036-230 TXV 35400 15.5 12.2 CH35-36C EL296UH090XV48C 7165494XC16-036-230 TXV 36000 15.5 12.2 CH35-36C EL296UH090XV60C 7165495XC16-036-230 TXV 35600 15.5 12.2 CH35-36C EL296UH110XV48C 7165496XC16-036-230 TXV 36000 15.5 12.2 CH35-36C EL296UH110XV60C 7165497XC16-036-230 TXV 36000 15.1 12.2 CH35-36C SL280UH090V60C 7165597XC16-036-230 TXV 36000 15.1 12.2 CH35-36C SL280UH090XV60C 7165498XC16-036-230 TXV 35800 15.1 12.2 CH35-36C SL280UH110V60C 7165499XC16-036-230 TXV 35800 15.1 12.2 CH35-36C SL280UH110XV60C 7165500XC16-036-230 TXV 35600 15.1 12.2 CH35-36C SLP98UH090XV36C 7165598XC16-036-230 TXV 35400 15.1 12.2 CH35-36C SLP98UH090XV48C 7165599XC16-036-230 TXV 36000 15.5 12.2 CH35-36C SLP98UH090XV60C 7165600XC16-036-230 TXV 36000 15.5 12.2 CH35-36C SLP98UH110XV60C 7165601XC16-036-230 TXV 36000 16 12.5 CH35-42B EL180UH070E36B 7165502XC16-036-230 TXV 36000 15.1 12.2 CH35-42B EL195UH070XE36B 7165504XC16-036-230 TXV 36000 15.5 12.2 CH35-42B EL296UH045XV36B 7165505XC16-036-230 TXV 36000 15.1 12.2 CH35-42B EL296UH070XE36B 7165507XC16-036-230 TXV 36000 15.5 12.2 CH35-42B EL296UH070XV36B 7165508XC16-036-230 TXV 36000 16 12.5 CH35-42B SL280UH090V36B 7165602XC16-036-230 TXV 36000 15.5 12.5 CH35-42B SL280UH090V48B 7165603XC16-036-230 TXV 36000 15.5 12.5 CH35-42B SL280UH090XV48B 7165509XC16-036-230 TXV 36000 15.5 12.2 CH35-42B SLP98UH070XV36B 7165604XC16-036-230 TXV 36000 15.5 12.5 CH35-42C EL296UH090XV36C 7165511XC16-036-230 TXV 36000 16 12.5 CH35-42C EL296UH090XV48C 7165512XC16-036-230 TXV 36000 16 12.5 CH35-42C EL296UH090XV60C 7165513XC16-036-230 TXV 36000 16 12.5 CH35-42C EL296UH110XV48C 7165514XC16-036-230 TXV 36000 16 12.5 CH35-42C EL296UH110XV60C 7165515XC16-036-230 TXV 36000 16 12.5 CH35-42C SL280UH090V60C 7165605XC16-036-230 TXV 36000 16 12.5 CH35-42C SL280UH090XV60C 7165516XC16-036-230 TXV 36000 15.1 12.5 CH35-42C SL280UH110V60C 7165517XC16-036-230 TXV 36000 15.1 12.5 CH35-42C SL280UH110XV60C 7165518XC16-036-230 TXV 36000 16 12.5 CH35-42C SLP98UH090XV36C 7165606XC16-036-230 TXV 36000 16 12.5 CH35-42C SLP98UH090XV48C 7165607XC16-036-230 TXV 36000 16 12.5 CH35-42C SLP98UH090XV60C 7165608XC16-036-230 TXV 36000 16 12.5 CH35-42C SLP98UH110XV60C 7165609XC16-036-230 TXV 36000 15.5 12.2 CH35-48B EL180UH070E36B 7165520XC16-036-230 TXV 36000 15.5 12.2 CH35-48B EL296UH070XV36B 7165526XC16-036-230 TXV 36000 15.5 12.5 CH35-48B SL280UH090V36B 7165610XC16-036-230 TXV 36000 15.1 12.5 CH35-48B SL280UH090V48B 7165611XC16-036-230 TXV 36000 15.5 12.5 CH35-48B SL280UH090XV48B 7165527XC16-036-230 TXV 36000 15.5 12.2 CH35-48B SLP98UH070XV36B 7165612Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 42: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 42

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-036-230 TXV 36000 15.5 12.5 CH35-48C EL296UH090XV36C 7165529XC16-036-230 TXV 36000 16 12.5 CH35-48C EL296UH090XV48C 7165530XC16-036-230 TXV 36000 16 12.5 CH35-48C EL296UH090XV60C 7165531XC16-036-230 TXV 36000 16 12.5 CH35-48C EL296UH110XV48C 7165532XC16-036-230 TXV 36000 16 12.5 CH35-48C EL296UH110XV60C 7165533XC16-036-230 TXV 36000 15.1 12.5 CH35-48C SL280UH090V60C 7165613XC16-036-230 TXV 36000 16 12.5 CH35-48C SL280UH090XV60C 7165534XC16-036-230 TXV 36000 15.1 12.5 CH35-48C SL280UH110V60C 7165535XC16-036-230 TXV 36000 15.1 12.5 CH35-48C SL280UH110XV60C 7165536XC16-036-230 TXV 36000 15.5 12.5 CH35-48C SLP98UH090XV36C 7165580XC16-036-230 TXV 36000 16 12.5 CH35-48C SLP98UH090XV48C 7165581XC16-036-230 TXV 36000 16 12.5 CH35-48C SLP98UH090XV60C 7165582XC16-036-230 TXV 36000 16 12.5 CH35-48C SLP98UH110XV60C 7165583XC16-036-230 TXV 36000 16 12.5 CH35-51C EL296UH110XV48C 9977275XC16-036-230 TXV 36000 15.1 12.2 CR33-30/36 SL280DF090V60C 6507984XC16-036-230 TXV 35600 15.1 12.2 CR33-30/36 SL280DF110V60C 6507987XC16-036-230 TXV 36000 15 12.2 CR33-48 EL195DF070XE48B 6508008XC16-036-230 TXV 35800 14.5 12.2 CR33-48 EL296DF070XE48B 6508962XC16-036-230 TXV 36200 15.5 12.2 CR33-48 EL296DF090XV60C 6508964XC16-036-230 TXV 36200 15.5 12.2 CR33-48 EL296DF110XV60C 6508966XC16-036-230 TXV 36200 15.5 12.2 CR33-48 SL280DF090V48B 6507999XC16-036-230 TXV 36600 15.1 12.5 CR33-48 SL280DF090V60C 6508013XC16-036-230 TXV 36200 15.1 12.5 CR33-48 SL280DF110V60C 6508016XC16-036-230 TXV 35800 15.5 12.2 CR33-48 SLP98DF070XV36B 6508953XC16-036-230 TXV 36000 15.5 12.2 CR33-48 SLP98DF090XV36C 6508951XC16-036-230 TXV 36000 15.5 12.2 CR33-48 SLP98DF090XV48C 6508949XC16-036-230 TXV 36200 15.5 12.2 CR33-48 SLP98DF090XV60C 6508945XC16-036-230 TXV 36200 15.5 12.2 CR33-48 SLP98DF110XV60C 6508942XC16-036-230 TXV 35200 15 12.2 CX35-30/36B SL280UH090XV48B 8256231XC16-036-230 TXV 35000 15 12.2 CX35-30/36C EL296UH110XV48C 8256233XC16-036-230 TXV 35400 15 12.2 CX35-30/36C EL296UH110XV60C 8256230XC16-036-230 TXV 35400 15 12.2 CX35-30/36C SLP98UH110XV60C 8256232XC16-036-230 TXV 36400 15.5 12.2 CX35-36A EL180UH045XE36A 8256237XC16-036-230 TXV 36400 15.5 12.2 CX35-36A SL280UH070V36A 8256244XC16-036-230 TXV 36400 15.5 12.2 CX35-36A SL280UH070XV36A 8256234XC16-036-230 TXV 36400 15.5 12.2 CX35-36B EL180UH070XE36B 8256238XC16-036-230 TXV 36200 15.5 12.2 CX35-36B EL195UH070XE36B 8256241XC16-036-230 TXV 36200 15.5 12.2 CX35-36B EL296UH045XV36B 8256242XC16-036-230 TXV 36400 15.5 12.2 CX35-36B EL296UH070XV36B 8256236XC16-036-230 TXV 36600 15.5 12.5 CX35-36B SL280UH090V36B 8256243XC16-036-230 TXV 36400 15.5 12.5 CX35-36B SL280UH090V48B 8256239XC16-036-230 TXV 36400 15.5 12.5 CX35-36B SL280UH090XV48B 8256235XC16-036-230 TXV 36400 15.5 12.2 CX35-36B SLP98UH070XV36B 8256240XC16-036-230 TXV 36600 15.5 12.2 CX35-48B EL180UH070E36B 8256253XC16-036-230 TXV 36400 15.5 12.2 CX35-48B EL195UH070XE36B 8256267XC16-036-230 TXV 36600 15.5 12.2 CX35-48B EL296UH045XV36B 8256263XC16-036-230 TXV 36600 15.5 12.2 CX35-48B EL296UH070XV36B 8256249XC16-036-230 TXV 37000 16 12.5 CX35-48B SL280UH090V36B 8256264XC16-036-230 TXV 36000 16 12.5 CX35-48B SL280UH090V48B 8256265XC16-036-230 TXV 36000 16 12.5 CX35-48B SL280UH090XV48B 8256254XC16-036-230 TXV 36600 15.5 12.2 CX35-48B SLP98UH070XV36B 8256261Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 43: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 43

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-036-230 TXV 36600 15.5 12.5 CX35-48C CBWMV-36C-090 8256252XC16-036-230 TXV 37000 16 12.5 CX35-48C CBWMV-60C-100 8256248XC16-036-230 TXV 36600 15.5 12.5 CX35-48C EL296UH090XV36C 8256250XC16-036-230 TXV 36400 15.5 12.5 CX35-48C EL296UH090XV48C 8256251XC16-036-230 TXV 37200 16 12.5 CX35-48C EL296UH090XV60C 8256246XC16-036-230 TXV 36600 16 12.5 CX35-48C EL296UH110XV48C 8256266XC16-036-230 TXV 37000 16 12.5 CX35-48C EL296UH110XV60C 8256247XC16-036-230 TXV 36800 16 12.5 CX35-48C SL280UH090V60C 8256245XC16-036-230 TXV 37000 15.1 12.5 CX35-48C SL280UH090XV60C 8256255XC16-036-230 TXV 36800 15.1 12.5 CX35-48C SL280UH110V60C 8256262XC16-036-230 TXV 37000 15.1 12.5 CX35-48C SL280UH110XV60C 8256256XC16-036-230 TXV 36800 15.5 12.5 CX35-48C SLP98UH090XV36C 8256258XC16-036-230 TXV 36800 16 12.5 CX35-48C SLP98UH090XV48C 8256259XC16-036-230 TXV 37200 16 12.5 CX35-48C SLP98UH090XV60C 8256260XC16-036-230 TXV 37000 15.5 12.5 CX35-48C SLP98UH110XV60C 8256257XC16-036-230 TXV 36000 15.5 12.5 CX35-49C EL296UH090XE48C 8256268XC16-036-230 TXV 37000 15.5 12.5 CX35-49C EL296UH090XV36C 8256273XC16-036-230 TXV 36800 16 12.5 CX35-49C EL296UH090XV48C 8256270XC16-036-230 TXV 37600 16 12.5 CX35-49C EL296UH090XV60C 8256274XC16-036-230 TXV 37400 16 12.5 CX35-49C EL296UH110XV60C 8256272XC16-036-230 TXV 37600 16 12.5 CX35-49C SL280UH090V60C 8256280XC16-036-230 TXV 37600 16 12.5 CX35-49C SL280UH090XV60C 8256271XC16-036-230 TXV 37200 15.1 12.5 CX35-49C SL280UH110V60C 8256278XC16-036-230 TXV 37400 15.1 12.5 CX35-49C SL280UH110XV60C 8256269XC16-036-230 TXV 37000 16 12.5 CX35-49C SLP98UH090XV36C 8256279XC16-036-230 TXV 37400 16 12.5 CX35-49C SLP98UH090XV48C 8256276XC16-036-230 TXV 37600 16 12.5 CX35-49C SLP98UH090XV60C 8256277XC16-036-230 TXV 37400 16 12.5 CX35-49C SLP98UH110XV60C 8256275XC16-036-230 TXV 36400 16 12.5 CX35-50/60C EL296UH110XV48C 8256281XC16-036-230 TXV 37000 15.1 12.5 CX38-43C SL280UH090V60C 10558837XC16-048-230 TXV 46000 15.5 12 C35-48B EL180UH090E48B 8256282XC16-048-230 TXV 46500 16 12 C35-49C EL180UH090E60C 8256290XC16-048-230 TXV 46500 16 12 C35-49C EL180UH110E60C 8256291XC16-048-230 TXV 46500 15.5 12.2 C35-49C EL195UH090XE48C 8256302XC16-048-230 TXV 46500 16 12 C35-49C EL195UH110XE60C 8256299XC16-048-230 TXV 46500 15.5 12 C35-49C EL296UH090XE48C 8256287XC16-048-230 TXV 46500 16 12 C35-49C EL296UH090XV48C 8256300XC16-048-230 TXV 46500 15.5 12 C35-49C EL296UH090XV60C 8256301XC16-048-230 TXV 46500 16 12 C35-49C EL296UH110XE60C 8256288XC16-048-230 TXV 46500 16 12 C35-49C EL296UH110XV48C 8256296XC16-048-230 TXV 46500 16 12 C35-49C EL296UH110XV60C 8256297XC16-048-230 TXV 47000 16 12 C35-49C SL280UH090V60C 8256298XC16-048-230 TXV 46500 16 12 C35-49C SL280UH090XV60C 8256289XC16-048-230 TXV 46500 16 12 C35-49C SL280UH110V60C 8256292XC16-048-230 TXV 46500 16 12 C35-49C SL280UH110XV60C 8256286XC16-048-230 TXV 46500 15.5 12.2 C35-49C SLO185B124/141V60 8256285XC16-048-230 TXV 46500 15.5 12.2 C35-49C SLO185UF124/141V60 8256284XC16-048-230 TXV 46500 16 12 C35-49C SLP98UH090XV48C 8256293XC16-048-230 TXV 46500 16 12 C35-49C SLP98UH090XV60C 8256294XC16-048-230 TXV 46500 16 12 C35-49C SLP98UH110XV60C 8256295XC16-048-230 TXV 46500 14.5 11.7 C35-49C 8256283Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 44: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 44

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C CBWMV-60C-100 8256308XC16-048-230 TXV 45500 15.5 12 C35-50/60C EL180UH090E60C 8256309XC16-048-230 TXV 45000 15.5 12 C35-50/60C EL180UH110E60C 8256305XC16-048-230 TXV 45000 15 11.7 C35-50/60C EL195UH090XE48C 8256317XC16-048-230 TXV 45500 15 11.7 C35-50/60C EL296UH090XE48C 8256306XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C EL296UH090XV48C 8256318XC16-048-230 TXV 45500 15 11.7 C35-50/60C EL296UH090XV60C 8256319XC16-048-230 TXV 45500 15.5 12 C35-50/60C EL296UH110XE60C 8256307XC16-048-230 TXV 45000 15.5 11.7 C35-50/60C EL296UH110XV48C 8256314XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C EL296UH110XV60C 8256315XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH090V60C 8256316XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH090XV60C 8256303XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH110V60C 8256311XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SL280UH110XV60C 8256304XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SLP98UH090XV48C 8256312XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SLP98UH090XV60C 8256313XC16-048-230 TXV 45500 15.5 11.7 C35-50/60C SLP98UH110XV60C 8256310XC16-048-230 TXV 47000 16 12.5 C35-60C EL180UH090E60C 8256366XC16-048-230 TXV 47000 16 12.5 C35-60C EL180UH110E60C 8256363XC16-048-230 TXV 47000 16 12 C35-60C EL195UH090XE48C 8256375XC16-048-230 TXV 47000 16 12 C35-60C EL195UH110XE60C 8256376XC16-048-230 TXV 47000 16 12 C35-60C EL296UH090XE48C 8256364XC16-048-230 TXV 47000 16 12 C35-60C EL296UH090XV48C 8256372XC16-048-230 TXV 47000 16 12 C35-60C EL296UH090XV60C 8256373XC16-048-230 TXV 47000 16 12 C35-60C EL296UH110XE60C 8256365XC16-048-230 TXV 47000 16 12 C35-60C EL296UH110XV48C 8256374XC16-048-230 TXV 47500 16 12 C35-60C EL296UH110XV60C 8256369XC16-048-230 TXV 47500 16 12 C35-60C SL280UH090V60C 8256377XC16-048-230 TXV 47000 16 12 C35-60C SL280UH090XV60C 8256361XC16-048-230 TXV 47000 16 12 C35-60C SL280UH110V60C 8256370XC16-048-230 TXV 47000 16 12 C35-60C SL280UH110XV60C 8256362XC16-048-230 TXV 47000 16 12 C35-60C SLO185B124/141V60 8256359XC16-048-230 TXV 47000 16 12 C35-60C SLO185UF124/141V60 8256360XC16-048-230 TXV 47000 16 12 C35-60C SLP98UH090XV48C 8256371XC16-048-230 TXV 47000 16 12 C35-60C SLP98UH090XV60C 8256367XC16-048-230 TXV 47500 16 12 C35-60C SLP98UH110XV60C 8256368XC16-048-230 TXV 47000 14.5 11.7 C35-60C 8256358XC16-048-230 TXV 47000 16 12 C35-60D EL296UH135XV60D 8256383XC16-048-230 TXV 47000 16 12 C35-60D SL280UH135V60D 8256381XC16-048-230 TXV 46500 15.5 12.2 C35-60D SLO185B124/141V60 8256380XC16-048-230 TXV 46500 15.5 12.2 C35-60D SLO185UF124/141V60 8256379XC16-048-230 TXV 47000 16 12 C35-60D SLP98UH135XV60D 8256382XC16-048-230 TXV 46500 14.5 11.7 C35-60D 8256378XC16-048-230 TXV 47000 16 12.2 CBA27UHE-048 10259498XC16-048-230 TXV 46500 16 12.2 CBA27UHE-060 10259499XC16-048-230 TXV 47000 16 12 CBX25UHV-048 6970139XC16-048-230 TXV 46000 16 12 CBX27UH-048 6685156XC16-048-230 TXV 46500 16 12 CBX27UH-060 6685157XC16-048-230 TXV 46000 15 12 CBX32M-048 6685162XC16-048-230 TXV 47000 14 12 CBX32M-060 6685163XC16-048-230 TXV 46000 16 12 CBX32MV-048 6685164Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 45: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 45

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-048-230 TXV 47000 16 12 CBX32MV-060 6685165XC16-048-230 TXV 47000 16 12 CBX32MV-068 6685166XC16-048-230 TXV 45500 15.5 12 CBX40UHV-048 6685441XC16-048-230 TXV 46000 15.5 12 CBX40UHV-060 6685442XC16-048-230 TXV 45000 15.5 12 CH23-65 EL296UH135XV60D 6685188XC16-048-230 TXV 45000 15.5 12 CH23-65 SL280UH090V60C 6677936XC16-048-230 TXV 45000 15.5 12 CH23-65 SL280UH090XV48B 6685494XC16-048-230 TXV 45000 15.5 12 CH23-65 SL280UH135V60D 6685189XC16-048-230 TXV 45000 15.5 11.7 CH23-65 SLP98UH110XV60C 6685192XC16-048-230 TXV 45000 15.5 12 CH23-65 SLP98UH135XV60D 6685193XC16-048-230 TXV 46500 15.5 12.2 CH23-68 EL180UH090E60C 6685454XC16-048-230 TXV 46000 15.5 12.2 CH23-68 EL180UH110E60C 6685455XC16-048-230 TXV 46500 15.5 12.2 CH23-68 EL195UH090XE48C 6685194XC16-048-230 TXV 46500 16 12 CH23-68 EL195UH110XE60C 6685195XC16-048-230 TXV 46000 15.5 12 CH23-68 EL296UH090XE48C 6685456XC16-048-230 TXV 46000 15.5 12 CH23-68 EL296UH110XE60C 6685457XC16-048-230 TXV 46500 16 12 CH23-68 EL296UH135XV60D 6685196XC16-048-230 TXV 46500 16 12 CH23-68 SL280UH135V60D 6685197XC16-048-230 TXV 46500 16 12 CH23-68 SLP98UH135XV60D 6685198XC16-048-230 TXV 46500 15.5 12 CH33-43 SL280UH090V48B 6685458XC16-048-230 TXV 46500 15.5 12 CH33-43 SL280UH090XV48B 6685459XC16-048-230 TXV 46000 15.5 12.2 CH33-43C EL180UH090E60C 6677938XC16-048-230 TXV 45500 15.5 12.2 CH33-43C EL180UH110E60C 6677939XC16-048-230 TXV 45500 15 11.7 CH33-43C EL195UH090XE48C 6685199XC16-048-230 TXV 46000 15 11.7 CH33-43C EL195UH110XE60C 6685200XC16-048-230 TXV 45500 15.5 11.7 CH33-43C EL296UH090XE48C 6685460XC16-048-230 TXV 46000 15.5 12 CH33-43C EL296UH110XE60C 6685461XC16-048-230 TXV 45500 15.5 11.7 CH33-43C EL296UH110XV48C 6685201XC16-048-230 TXV 45500 15.5 11.7 CH33-44/48 EL180UH090E48B 6685462XC16-048-230 TXV 45500 15.5 11.7 CH33-48 EL296UH090XV48C 6685205XC16-048-230 TXV 45500 15 11.7 CH33-48 EL296UH090XV60C 6685206XC16-048-230 TXV 45500 15.5 11.7 CH33-48 EL296UH110XV48C 6685207XC16-048-230 TXV 45500 15.5 11.7 CH33-48 EL296UH110XV60C 6685208XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH090V60C 6685209XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH090XV60C 6685465XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH110V60C 6685210XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SL280UH110XV60C 6685466XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SLP98UH090XV48C 6685211XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SLP98UH090XV60C 6685212XC16-048-230 TXV 45500 15.5 11.7 CH33-48 SLP98UH110XV60C 6685213XC16-048-230 TXV 45500 15.5 12 CH33-48C EL180UH090E60C 6685467XC16-048-230 TXV 45500 15.5 12.2 CH33-48C EL180UH110E60C 6685468XC16-048-230 TXV 45000 15 11.7 CH33-48C EL195UH090XE48C 6685203XC16-048-230 TXV 46000 15 11.7 CH33-48C EL195UH110XE60C 6685204XC16-048-230 TXV 45500 15.5 11.7 CH33-48C EL296UH090XE48C 6685469XC16-048-230 TXV 45500 15.5 12 CH33-48C EL296UH110XE60C 6685470XC16-048-230 TXV 46500 15.5 12 CH33-49 EL296UH090XV48C 6685214XC16-048-230 TXV 46500 15.5 12 CH33-49 EL296UH090XV60C 6685215XC16-048-230 TXV 46500 15.5 12 CH33-49 EL296UH110XV48C 6685216XC16-048-230 TXV 46500 15.5 12 CH33-49 EL296UH110XV60C 6685217XC16-048-230 TXV 46500 16 12 CH33-49 SL280UH090V60C 6685218Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 46: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 46

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-048-230 TXV 46500 16 12 CH33-49 SL280UH090XV60C 6685471XC16-048-230 TXV 46500 15.5 12 CH33-49 SL280UH110V60C 6685219XC16-048-230 TXV 46500 15.5 12 CH33-49 SL280UH110XV60C 6685472XC16-048-230 TXV 46500 15.5 12 CH33-49 SLP98UH090XV48C 6685220XC16-048-230 TXV 46500 15.5 12 CH33-49 SLP98UH090XV60C 6685221XC16-048-230 TXV 46500 15.5 12 CH33-49 SLP98UH110XV60C 6685222XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C CBWMV-60C-100 6685473XC16-048-230 TXV 46000 16 12 CH33-50/60C EL180UH090E60C 6685474XC16-048-230 TXV 46000 16 12 CH33-50/60C EL180UH110E60C 6685475XC16-048-230 TXV 46000 15.5 12 CH33-50/60C EL195UH090XE48C 6685223XC16-048-230 TXV 46500 15.5 11.7 CH33-50/60C EL195UH110XE60C 6685224XC16-048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH090XE48C 6685496XC16-048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH090XE48C 6677940XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C EL296UH090XV48C 6685225XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C EL296UH090XV60C 6685226XC16-048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH110XE60C 6685497XC16-048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH110XE60C 6677941XC16-048-230 TXV 46000 15.5 12 CH33-50/60C EL296UH110XV48C 6685227XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C EL296UH110XV60C 6685228XC16-048-230 TXV 46500 16 12 CH33-50/60C SL280UH090V60C 6685229XC16-048-230 TXV 46500 15.5 12.2 CH33-50/60C SL280UH090XV60C 6685476XC16-048-230 TXV 46000 15.5 12 CH33-50/60C SL280UH110V60C 6685230XC16-048-230 TXV 46000 15.5 12 CH33-50/60C SL280UH110XV60C 6685477XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C SLP98UH090XV48C 6685231XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C SLP98UH090XV60C 6685232XC16-048-230 TXV 46000 15.5 11.7 CH33-50/60C SLP98UH110XV60C 6685233XC16-048-230 TXV 46000 16 12 CH33-60D EL296UH135XV60D 6685234XC16-048-230 TXV 46000 16 12 CH33-60D SL280UH135V60D 6685235XC16-048-230 TXV 46000 15.5 12 CH33-60D SLP98UH135XV60D 6685236XC16-048-230 TXV 46500 16 12 CH33-62D EL296UH135XV60D 6685237XC16-048-230 TXV 46500 16 12 CH33-62D SL280UH135V60D 6685238XC16-048-230 TXV 46500 16 12 CH33-62D SLP98UH135XV60D 6685239XC16-048-230 TXV 47000 15.5 12 CH35-42B SL280UH090V48B 7166465XC16-048-230 TXV 47000 15.5 12 CH35-42B SL280UH090XV48B 7166466XC16-048-230 TXV 46500 14.5 11.7 CH35-42B 7166463XC16-048-230 TXV 46000 15.5 12 CH35-42C EL180UH090E60C 7166467XC16-048-230 TXV 46000 15.5 12 CH35-42C EL180UH110E60C 7166468XC16-048-230 TXV 45500 15.1 11.7 CH35-42C EL195UH090XE48C 7166469XC16-048-230 TXV 46500 15.1 11.7 CH35-42C EL195UH110XE60C 7166470XC16-048-230 TXV 46000 15.5 12 CH35-42C EL296UH090XE48C 7166471XC16-048-230 TXV 46000 15.5 12 CH35-42C EL296UH110XE60C 7166473XC16-048-230 TXV 46000 15.5 12 CH35-42C EL296UH110XV48C 7166472XC16-048-230 TXV 45500 15.5 11.7 CH35-48B EL180UH090E48B 7166474XC16-048-230 TXV 46000 15.5 12 CH35-48C EL180UH090E60C 7166479XC16-048-230 TXV 45500 15.5 12 CH35-48C EL180UH110E60C 7166480XC16-048-230 TXV 45500 15.1 11.7 CH35-48C EL195UH090XE48C 7166481XC16-048-230 TXV 46000 15.1 11.7 CH35-48C EL195UH110XE60C 7166482XC16-048-230 TXV 45500 15.5 11.7 CH35-48C EL296UH090XV48C 7166483XC16-048-230 TXV 45500 15.1 11.7 CH35-48C EL296UH090XV60C 7166484XC16-048-230 TXV 46000 15.5 12 CH35-48C EL296UH110XE60C 7166487XC16-048-230 TXV 45500 15.5 11.7 CH35-48C EL296UH110XV48C 7166485Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 47: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 47

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-048-230 TXV 46000 15.5 11.7 CH35-48C EL296UH110XV60C 7166486XC16-048-230 TXV 46000 15.5 12 CH35-48C SL280UH090V60C 7165614XC16-048-230 TXV 46000 15.5 12 CH35-48C SL280UH090XV60C 7166488XC16-048-230 TXV 45500 15.5 11.7 CH35-48C SL280UH110V60C 7165615XC16-048-230 TXV 45500 15.5 11.7 CH35-48C SL280UH110XV60C 7166489XC16-048-230 TXV 45500 15.5 11.7 CH35-48C SLP98UH090XV48C 7165616XC16-048-230 TXV 45500 15.5 11.7 CH35-48C SLP98UH090XV60C 7165617XC16-048-230 TXV 46000 15.5 11.7 CH35-48C SLP98UH110XV60C 7165618XC16-048-230 TXV 46500 15.5 12 CH35-51C CBWMV-60C-100 7166497XC16-048-230 TXV 46500 16 12 CH35-51C EL180UH090E60C 7166498XC16-048-230 TXV 46500 16 12 CH35-51C EL180UH110E60C 7166499XC16-048-230 TXV 46000 15.5 12 CH35-51C EL195UH090XE48C 7166500XC16-048-230 TXV 47000 15.5 11.7 CH35-51C EL195UH110XE60C 7166501XC16-048-230 TXV 46500 15.5 12 CH35-51C EL296UH090XV48C 7166490XC16-048-230 TXV 46500 15.5 12 CH35-51C EL296UH090XV60C 7166491XC16-048-230 TXV 46500 16 12 CH35-51C EL296UH110XE60C 7166502XC16-048-230 TXV 46500 15.5 12 CH35-51C EL296UH110XV48C 7166492XC16-048-230 TXV 46500 15.5 12 CH35-51C EL296UH110XV60C 7166493XC16-048-230 TXV 46500 16 12 CH35-51C SL280UH090V60C 7165619XC16-048-230 TXV 46500 16 12 CH35-51C SL280UH090XV60C 7166494XC16-048-230 TXV 46500 15.5 12 CH35-51C SL280UH110V60C 7165620XC16-048-230 TXV 46500 15.5 12 CH35-51C SL280UH110XV60C 7166495XC16-048-230 TXV 46500 15.5 12 CH35-51C SLP98UH090XV48C 7165621XC16-048-230 TXV 46500 15.5 12 CH35-51C SLP98UH090XV60C 7165622XC16-048-230 TXV 46500 15.5 12 CH35-51C SLP98UH110XV60C 7165623XC16-048-230 TXV 46500 14.5 11.7 CH35-51C 7166496XC16-048-230 TXV 47000 16 12 CH35-60D EL296UH135XV60D 7166504XC16-048-230 TXV 46500 16 12 CH35-60D SL280UH135V60D 7165624XC16-048-230 TXV 46500 16 12 CH35-60D SLP98UH135XV60D 7165625XC16-048-230 TXV 45000 15.5 12 CR33-50/60 EL180DF110E60C 6685484XC16-048-230 TXV 45000 15 11.7 CR33-50/60 EL195DF090XE48C 6685246XC16-048-230 TXV 45000 15 11.7 CR33-50/60 EL195DF110XE60C 6685247XC16-048-230 TXV 45000 15 11.7 CR33-50/60 EL296DF090XE48C 6685485XC16-048-230 TXV 45000 15 11.7 CR33-50/60 EL296DF090XV60C 6685248XC16-048-230 TXV 45000 15 11.7 CR33-50/60 EL296DF110XE60C 6685486XC16-048-230 TXV 45000 15.5 11.7 CR33-50/60 SL280DF090V60C 6685251XC16-048-230 TXV 45000 15.5 12 CR33-50/60 SL280DF110V60C 6685252XC16-048-230 TXV 45000 15 11.7 CR33-50/60 SLP98DF090XV60C 6685488XC16-048-230 TXV 45000 15 11.7 CR33-50/60 SLP98DF110XV60C 6685489XC16-048-230 TXV 46000 15.5 12 CX35-48B EL180UH090E48B 8256320XC16-048-230 TXV 45500 15 11.7 CX35-48B SL280UH090V48B 10514225XC16-048-230 TXV 46500 16 12 CX35-49C EL180UH090E60C 8256328XC16-048-230 TXV 46500 16 12 CX35-49C EL180UH110E60C 8256329XC16-048-230 TXV 46500 15.5 12.2 CX35-49C EL195UH090XE48C 8256338XC16-048-230 TXV 46500 16 12 CX35-49C EL195UH110XE60C 8256339XC16-048-230 TXV 46500 15.5 12 CX35-49C EL296UH090XE48C 8256325XC16-048-230 TXV 46500 16 12 CX35-49C EL296UH090XV48C 8256335XC16-048-230 TXV 46500 15.5 12 CX35-49C EL296UH090XV60C 8256336XC16-048-230 TXV 46500 16 12 CX35-49C EL296UH110XE60C 8256326XC16-048-230 TXV 46500 16 12 CX35-49C EL296UH110XV48C 8256337XC16-048-230 TXV 46500 16 12 CX35-49C EL296UH110XV60C 8256332Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 48: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 48

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-048-230 TXV 47000 16 12 CX35-49C SL280UH090V60C 8256333XC16-048-230 TXV 46500 16 12 CX35-49C SL280UH090XV60C 8256327XC16-048-230 TXV 46500 16 12 CX35-49C SL280UH110V60C 8256334XC16-048-230 TXV 46500 16 12 CX35-49C SL280UH110XV60C 8256324XC16-048-230 TXV 46500 15.5 12.2 CX35-49C SLO185B124/141V60 8256321XC16-048-230 TXV 46500 15.5 12.2 CX35-49C SLO185UF124/141V60 8256322XC16-048-230 TXV 46500 16 12 CX35-49C SLP98UH090XV48C 8256330XC16-048-230 TXV 46500 16 12 CX35-49C SLP98UH090XV60C 8256331XC16-048-230 TXV 46500 16 12 CX35-49C SLP98UH110XV60C 8256340XC16-048-230 TXV 46500 14.5 11.7 CX35-49C 8256323XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C CBWMV-60C-100 8256346XC16-048-230 TXV 45500 15.5 12 CX35-50/60C EL180UH090E60C 8256347XC16-048-230 TXV 45000 15.5 12 CX35-50/60C EL180UH110E60C 8256343XC16-048-230 TXV 45000 15 11.7 CX35-50/60C EL195UH090XE48C 8256355XC16-048-230 TXV 45500 15 11.7 CX35-50/60C EL296UH090XE48C 8256344XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C EL296UH090XV48C 8256356XC16-048-230 TXV 45500 15 11.7 CX35-50/60C EL296UH090XV60C 8256357XC16-048-230 TXV 45500 15.5 12 CX35-50/60C EL296UH110XE60C 8256345XC16-048-230 TXV 45000 15.5 11.7 CX35-50/60C EL296UH110XV48C 8256352XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C EL296UH110XV60C 8256353XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH090V60C 8256354XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH090XV60C 8256341XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH110V60C 8256349XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SL280UH110XV60C 8256342XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SLP98UH090XV48C 8256350XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SLP98UH090XV60C 8256351XC16-048-230 TXV 45500 15.5 11.7 CX35-50/60C SLP98UH110XV60C 8256348XC16-048-230 TXV 47000 16 12.5 CX35-60C EL180UH090E60C 8256392XC16-048-230 TXV 47000 16 12.5 CX35-60C EL180UH110E60C 8256389XC16-048-230 TXV 47000 16 12 CX35-60C EL195UH090XE48C 8256401XC16-048-230 TXV 47000 16 12 CX35-60C EL195UH110XE60C 8256402XC16-048-230 TXV 47000 16 12 CX35-60C EL296UH090XE48C 8256390XC16-048-230 TXV 47000 16 12 CX35-60C EL296UH090XV48C 8256398XC16-048-230 TXV 47000 16 12 CX35-60C EL296UH090XV60C 8256399XC16-048-230 TXV 47000 16 12 CX35-60C EL296UH110XE60C 8256391XC16-048-230 TXV 47000 16 12 CX35-60C EL296UH110XV48C 8256400XC16-048-230 TXV 47500 16 12 CX35-60C EL296UH110XV60C 8256395XC16-048-230 TXV 47500 16.5 12.2 CX35-60C SL280UH090V60C 8256403XC16-048-230 TXV 47000 16 12 CX35-60C SL280UH090XV60C 8256387XC16-048-230 TXV 47000 16 12 CX35-60C SL280UH110V60C 8256396XC16-048-230 TXV 47000 16 12 CX35-60C SL280UH110XV60C 8256388XC16-048-230 TXV 47000 16 12 CX35-60C SLO185B124/141V60 8256385XC16-048-230 TXV 47000 16 12 CX35-60C SLO185UF124/141V60 8256384XC16-048-230 TXV 47000 16 12 CX35-60C SLP98UH090XV48C 8256397XC16-048-230 TXV 47000 16 12 CX35-60C SLP98UH090XV60C 8256393XC16-048-230 TXV 47500 16 12 CX35-60C SLP98UH110XV60C 8256394XC16-048-230 TXV 47000 14.5 11.7 CX35-60C 8256386XC16-048-230 TXV 47000 16 12 CX35-60D EL296UH135XV60D 8256409XC16-048-230 TXV 47000 16 12 CX35-60D SL280UH135V60D 8256407XC16-048-230 TXV 46500 15.5 12.2 CX35-60D SLO185B124/141V60 8256404XC16-048-230 TXV 46500 15.5 12.2 CX35-60D SLO185UF124/141V60 8256405Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 49: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 49

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-048-230 TXV 47000 16 12 CX35-60D SLP98UH135XV60D 8256408XC16-048-230 TXV 46500 14.5 11.7 CX35-60D 8256406XC16-048-230 TXV 47500 16.5 12.2 CX38-62C SL280UH090V60C 10558938XC16-060-230 TXV 56500 15 12 C35-49C EL180UH090E60C 8256413XC16-060-230 TXV 56500 15 12 C35-49C EL180UH110E60C 8256414XC16-060-230 TXV 56500 15 12 C35-49C EL195UH110XE60C 8256415XC16-060-230 TXV 56500 15 12 C35-49C EL296UH110XE60C 8256410XC16-060-230 TXV 56500 15 11.7 C35-49C SL280UH090V60C 8256416XC16-060-230 TXV 56500 15 11.7 C35-49C SL280UH090XV60C 8256411XC16-060-230 TXV 56500 15 11.7 C35-49C SL280UH110V60C 8256417XC16-060-230 TXV 56500 15 11.7 C35-49C SL280UH110XV60C 8256412XC16-060-230 TXV 55000 15 11.7 C35-50/60C EL180UH090E60C 8256418XC16-060-230 TXV 55000 14.5 11.7 C35-50/60C EL180UH110E60C 8256419XC16-060-230 TXV 55000 14.5 11.7 C35-50/60C EL180UH110XE60C 8256420XC16-060-230 TXV 55000 15 11.7 C35-50/60C EL195UH110XE60C 8256422XC16-060-230 TXV 55000 15 11.7 C35-50/60C EL296UH110XE60C 8256421XC16-060-230 TXV 57500 15.5 12.2 C35-60C EL180UH090E60C 8256431XC16-060-230 TXV 57500 15.5 12.2 C35-60C EL180UH110E60C 8256428XC16-060-230 TXV 57500 15.5 12.2 C35-60C EL195UH110XE60C 8256432XC16-060-230 TXV 57500 15.5 11.7 C35-60C EL296UH090XV60C 8256433XC16-060-230 TXV 57500 15.5 12.2 C35-60C EL296UH110XE60C 8256429XC16-060-230 TXV 57000 15.5 11.7 C35-60C EL296UH110XV60C 8256435XC16-060-230 TXV 57500 16 12 C35-60C SL280UH090V60C 8256426XC16-060-230 TXV 57500 15.5 12 C35-60C SL280UH090XV60C 8256430XC16-060-230 TXV 57500 15.5 11.7 C35-60C SL280UH110V60C 8256436XC16-060-230 TXV 57500 15 11.7 C35-60C SL280UH110XV60C 8256427XC16-060-230 TXV 57000 15 12 C35-60C SLO185UF124/141V60 8256425XC16-060-230 TXV 57500 15.5 11.7 C35-60C SLP98UH090XV60C 8256437XC16-060-230 TXV 57000 15.5 11.7 C35-60C SLP98UH110XV60C 8256434XC16-060-230 TXV 57500 14.5 11.7 C35-60C 8256423XC16-060-230 TXV 57000 15.5 12 C35-60D EL180UH135E60D 8256438XC16-060-230 TXV 57000 15 11.7 C35-60D EL195UH135XE60D 8256442XC16-060-230 TXV 57000 15 11.7 C35-60D EL296UH135XE60D 8256439XC16-060-230 TXV 57000 15.5 11.7 C35-60D EL296UH135XV60D 8256443XC16-060-230 TXV 57000 15.5 12 C35-60D SL280UH135V60D 8256441XC16-060-230 TXV 57000 15.5 12 C35-60D SLP98UH135XV60D 8256440XC16-060-230 TXV 57500 14.5 11.7 C35-60D 8256424XC16-060-230 TXV 56000 15.1 11.7 CBA27UHE-060 10259500XC16-060-230 TXV 56500 14.5 11.7 CBX25UH-060 6564156XC16-060-230 TXV 56500 16 12 CBX25UHV-060 6970140XC16-060-230 TXV 56500 15.5 12 CBX27UH-060 6563962XC16-060-230 TXV 56500 14.5 11.7 CBX32M-060 6563963XC16-060-230 TXV 56000 15.5 11.7 CBX32MV-048 6563964XC16-060-230 TXV 56500 15.5 11.7 CBX32MV-060 6563965XC16-060-230 TXV 56500 15.5 12.2 CBX32MV-068 6563966XC16-060-230 TXV 55000 15 11.7 CBX40UHV-048 6564157XC16-060-230 TXV 55500 15 11.7 CBX40UHV-060 6564158XC16-060-230 TXV 57000 15 11.7 CH23-68 EL195UH135XE60D 6563981XC16-060-230 TXV 57500 15.5 12 CH23-68 EL296UH135XV60D 6563982XC16-060-230 TXV 57500 15.5 12 CH23-68 SL280UH135V60D 6563984XC16-060-230 TXV 57000 15.5 12 CH23-68 SLP98UH135XV60D 6563985Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 50: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 50

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-060-230 TXV 57500 14.5 11.7 CH23-68 6563980XC16-060-230 TXV 56000 15 11.7 CH33-50/60C EL180UH090E60C 6564167XC16-060-230 TXV 56000 15 11.7 CH33-50/60C EL180UH110E60C 6564168XC16-060-230 TXV 56000 15 11.7 CH33-50/60C EL180UH110XE60C 6564169XC16-060-230 TXV 56000 15 11.7 CH33-50/60C EL195UH110XE60C 6563988XC16-060-230 TXV 56000 15 11.7 CH33-50/60C EL296UH110XE60C 6564170XC16-060-230 TXV 55500 15 11.7 CH33-50/60C SL280UH110XV60C 6564165XC16-060-230 TXV 56000 15 11.7 CH33-60D CBWMV-60C-100 6563998XC16-060-230 TXV 56000 15 11.7 CH33-60D EL296UH135XV60D 6564000XC16-060-230 TXV 56000 15 11.7 CH33-60D SL280UH135V60D 6564002XC16-060-230 TXV 56000 15.5 11.7 CH33-60D SLP98UH135XV60D 6564003XC16-060-230 TXV 56500 15.5 11.7 CH33-62D EL180UH135E60D 6564172XC16-060-230 TXV 56500 15 11.7 CH33-62D EL195UH135XE60D 6564005XC16-060-230 TXV 56500 15 11.7 CH33-62D EL296UH135XE60D 6564171XC16-060-230 TXV 56500 15 11.7 CH33-62D EL296UH135XV60D 6564006XC16-060-230 TXV 56000 15 12 CH33-62D SL280UH090V60C 6564008XC16-060-230 TXV 56500 15.5 11.7 CH33-62D SL280UH090XV60C 6564173XC16-060-230 TXV 56000 15 12 CH33-62D SL280UH110V60C 6564009XC16-060-230 TXV 56500 15.5 11.7 CH33-62D SL280UH135V60D 6564010XC16-060-230 TXV 56500 15.5 11.7 CH33-62D SLP98UH135XV60D 6564011XC16-060-230 TXV 57000 15.5 12 CH35-51C CBWMV-60C-100 7165650XC16-060-230 TXV 57000 15.5 12 CH35-51C EL180UH090E60C 7165627XC16-060-230 TXV 56500 15.25 12 CH35-51C EL180UH110E60C 7165628XC16-060-230 TXV 56500 15.25 12 CH35-51C EL180UH110XE60C 7165629XC16-060-230 TXV 56500 15.25 12 CH35-51C EL195UH110XE60C 7165630XC16-060-230 TXV 56500 15.25 12 CH35-51C EL296UH110XE60C 7165633XC16-060-230 TXV 57000 15.25 11.7 CH35-51C SL280UH090V60C 7165634XC16-060-230 TXV 57000 15.75 12 CH35-51C SL280UH090XV60C 7165635XC16-060-230 TXV 56000 15.25 11.7 CH35-51C SL280UH110XV60C 7165637XC16-060-230 TXV 56500 15.5 11.7 CH35-60D EL180UH135E60D 7165641XC16-060-230 TXV 56500 15 11.7 CH35-60D EL195UH135XE60D 7165642XC16-060-230 TXV 56500 15 11.7 CH35-60D EL296UH135XE60D 7165644XC16-060-230 TXV 56500 15.5 11.7 CH35-60D EL296UH135XV60D 7165643XC16-060-230 TXV 56500 15.5 11.7 CH35-60D SL280UH135V60D 7165645XC16-060-230 TXV 56500 15.5 11.7 CH35-60D SLP98UH135XV60D 7165646XC16-060-230 TXV 56500 15 12 CX35-49C EL180UH090E60C 8256446XC16-060-230 TXV 56500 15 12 CX35-49C EL180UH110XE60C 8256447XC16-060-230 TXV 56500 15 12 CX35-49C EL195UH110XE60C 8256450XC16-060-230 TXV 56500 15 11.7 CX35-49C SL280UH090V60C 8256448XC16-060-230 TXV 56500 15 11.7 CX35-49C SL280UH090XV60C 8256444XC16-060-230 TXV 56500 15 11.7 CX35-49C SL280UH110V60C 8256449XC16-060-230 TXV 56500 15 11.7 CX35-49C SL280UH110XV60C 8256445XC16-060-230 TXV 55000 15 11.7 CX35-50/60C EL180UH090E60C 8256451XC16-060-230 TXV 55000 14.5 11.7 CX35-50/60C EL180UH110E60C 8256452XC16-060-230 TXV 55000 14.5 11.7 CX35-50/60C EL180UH110XE60C 8256453XC16-060-230 TXV 55000 15 11.7 CX35-50/60C EL195UH110XE60C 8256455XC16-060-230 TXV 56500 15 12 CX35-50/60C EL296UH110XE60C 8256454XC16-060-230 TXV 57500 15.5 12.2 CX35-60C EL180UH090E60C 8256464XC16-060-230 TXV 57500 15.5 12.2 CX35-60C EL180UH110E60C 8256461XC16-060-230 TXV 57500 15.5 12.2 CX35-60C EL195UH110XE60C 8256465XC16-060-230 TXV 57500 15.5 12.2 CX35-60C EL296UH110XE60C 8256463Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 51: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

XC16 - 2 to 5 Ton Air Conditioner / Page 51

AHRI SYSTEM MATCHES - SOUTHWEST REGIONNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.orgModel No.

Expansion Device Capacity SEER EER Coil or

Air Handler Furnace AHRI Reference

XC16-060-230 TXV 57500 16 12 CX35-60C SL280UH090V60C 8256459XC16-060-230 TXV 57500 15.5 12 CX35-60C SL280UH090XV60C 8256460XC16-060-230 TXV 57500 15.5 11.7 CX35-60C SL280UH110V60C 8256466XC16-060-230 TXV 57500 15.5 12.2 CX35-60C SL280UH110XV60C 8256462XC16-060-230 TXV 57000 15 12 CX35-60C SLO185UF124/141V60 8256456XC16-060-230 TXV 57500 15.5 11.7 CX35-60C SLP98UH090XV60C 8256467XC16-060-230 TXV 57000 15.5 11.7 CX35-60C SLP98UH110XV60C 8256468XC16-060-230 TXV 57500 14.5 11.7 CX35-60C 8256457XC16-060-230 TXV 57000 15.5 12 CX35-60D EL180UH135E60D 8256469XC16-060-230 TXV 57000 15 11.7 CX35-60D EL195UH135XE60D 8256472XC16-060-230 TXV 56500 15 11.7 CX35-60D EL296UH135XE60D 8256470XC16-060-230 TXV 57000 15.5 11.7 CX35-60D EL296UH135XV60D 8256473XC16-060-230 TXV 57000 15.5 12 CX35-60D SL280UH135V60D 8256474XC16-060-230 TXV 57000 15.5 12 CX35-60D SLP98UH135XV60D 8256471XC16-060-230 TXV 57500 14.5 11.7 CX35-60D 8256458XC16-060-230 TXV 57500 16 12 CX38-62C SL280UH090V60C 10558974Ratings AHRI Certified to AHRI Standard 210/240 (with 25 ft. of connecting refrigerant lines); 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.Also see Expansion Valve Kit Usage Table.

Page 52: XC16 2-5 TON AIR CONDITIONERS AIR CONDITIONERS … · AIR CONDITIONERS XC16 ... Single-phase units are equipped with a PSC compressor motor. This type of motor normally does not need

REVISIONS

REVISIONS

Sections Description of Change

AHRI System Matches Updated

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2017 Lennox Industries, Inc.