NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables1
Lukas VON LAUE
Technical contact:Lukas von LaueNexans France
41 rue Maurice Gorse
F-18100 Mehun-sur-Yèvre
France
Worldwide Experience with Halogen Free
IEEE 383 Qualified
Nuclear Power Plant Cables
and:Olivier DervoutNexans France
4-10 rue Mozart
F 92587 Clichy
France
NPEC/SC2 meeting
2009/04/08, Knoxville TN
Commercial contact:Antoine MachonNexans Canada
140 Allstate Pkwy
Markham, ON L3R 0Z7
Tel: +1 905 944 4326
Canada
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables2
AbstractHalogen free or FRNC (Fire Retardant Non Corrosive) cables are well adapted
for use in nuclear power plants because they provide increased fire safety. In
contrast to cables containing halogen, they have low smoke, low corrosive
properties and low toxic emissions in case of fire.
Several IEEE 383 nuclear power plant qualifications are available for FRNC
cables, including some for Canadian Projects (i.e. Cernavoda in Rumania and
Qinshan III in China) and a recent US project (Lungmen in Taiwan).
The last part will give details on FRNC qualification using IEEE, ICEA and AEIC
standards performed for the Lungmen Project.
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables3
Introduction
Two different types of cables are used in NPP:
1) Halogenated cablesfrom the beginning and up to now
2) Halogen free cablessince 1991
In USA , Korea , Japan:
EPR/CSP cables
In Europe : XLPE or EPR/PVC
In China, Taiwan, Europe :
halogen free cables,
for AREVA, GE, Westinghouse,
AECL, Atomstroyexport,
Electricité de France,
China Nucl. Power Engineering Comp.
Taiwan Power Company, etc.
Introduction by Nexans of halogen free cables according to IEEE, ICEA, CSA and AEIC standards:
For Lungmen NPP – Taiwan – GE BWR
For Qinshan III – China – AECL Candu
For Cernavoda II – Romania – AECL Candu
Often called FRNC(Fire Retardant Non Corrosive)
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables4
Nexans halogen free NPP cables installed from 1991 to 2009
India2006 Kudankulam
Romania2000 Chernavoda 1
2003-2006 Chernavoda 2
Taiwan
Island 2002-2006
Lungmen
Czech R.1993-2003 Temelin
1995 Dukovany
Slovaquia1995 Bonunice
Russiadiv. rennovations
Ukrainediv. renovations
Mainland China1991-1993 Daya Bay 1+2
1999-2001 Ling Ao 1+2
1999-2002 Qinshan III 1+2
2002-2005 Tianwan 1+2
2007-2009 Ling Ao 3+4
2008-2010 Qinshan II 1+2
Bulgaria1992-1995 Kozloduy
France2009 Flamanville 3
1995 Chooz
> 50 other NPP
with halogenated
cables
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables5
Comparison Key Properties
0
2
4
6
8
10Installation ease
User experience
Industrial experience
EPR/ CSP
Halogen free
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables6
Properties of Halogen free material
Application in since 15 years
Properties compliant with
specifications
Positive experience feedback
Approved by
Westinghouse for Temelin
AECL for Qinshan III
AECL for Cernavoda II
Stone&Webster/GE for Lungmen
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables7
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables8
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables9
7 5 3 165
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables10
Comparison Key Properties
0
2
4
6
8
10Installation ease
User experience
Industrial experience
Mechanical Properties
Oil resistance
Water resistance
EPR/ CSP
Halogen free
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables11
Fire Properties : Non propagation of fire
For Candu (Qinshan III and Cernavoda II)
and GE (Lungmen) projects
type test and inspection tests made with FT4 and IEEE 383
tests
halogen free cables are compliant
IEEE
383
FT4 IEEE
1202
UL 1685
MV Power Cables
LV Power Cables
I&C Cables
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables12
How do these halogenated flame retardants work ?
Halogenated material : HCl or HBr can quench radicals:
HCl/HBr is released when material is heated, then
H• + HCl H2 + Cl•
HO• + HCl H2O + Cl•
Cl• is less reactive than the other radicals flame quenching
good flame retardant, but negative side effect :
SMOKE, TOXICITY, CORROSION
• 1 kg of PVC burnt produces about 2 liter of hydrochloric Acid of “Xi” concentration
• for CSP, “only” ~ 1 liter
i
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables13
How do these halogen free flame retardants work ?
Halogen free flame retardants:
Metal Hydrates,
(eg. Aluminium Trihydrate, ATH)
2 Al(OH)3 Al2O3 + 3 H2O
(endotherm reaction)
+ heat
ATH consumes heat and release
water
efficient flame retardant,
without side effect
1 kg of ATH filled compound can produce 216 g = 12 mol
of water, equivalent to 268 liter of water vapor
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables14
Smoke Testing : ASTM E 662 and UL 1685
UL1685 smoke
testing on cables
(results form test similar to
UL1685 :
optically measured in
400mm exhaust duct
above the test chamber)
Very low smoke for halogen free cables
Smoke Production Rate of
3x1,5mm² 0,6/1 kV halogen free cable
0,000
0,050
0,100
0 300 600 900 1200 1500
t [s]
SP
R [
m²/
s]
Total Smoke Production
TSP = 25 m²
Smoke testing
UL 1685
IEEE1202
FT4
requirement
typical result for
FRNC cables
total smoke
production max 95m² 10 to 30m²
peak smoke rate max 0,25m²/s0,05 to
0,15m²/s
ASTM E662classical smoke testing on
material plates
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables15
Halogen free cable in fire means:
No HCl gas production or other halogen gas
Avoid hydrochloric acid formation
Avoid corrosion on metallic
equipment(metallic structures, conducts and pipes,
engines, electronics, … )
Fire Properties : Corrosivity
(Reminder : 1 kG of PVC burnt produces about 2 liter of Hydrochloric Acid of “Xi” concentration)
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables16
fire smoke
corro-
sivity
Halogenated products :
good Fire Retardancy
but releasing heavy smokes
toxic gases
corrosive gases
( HCl, HBr, HF ..)
ok not ok not ok
Halogen Free products :
Good Fire Retardancy
Low Smoke
Zero Halogen release
halogen free FRNC Fire Retardant Non Corrosive
ok ok ok
Fire risk in NPP
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables17
Comparison Key Properties
0
2
4
6
8
10Installation ease
User experience
Industrial experience
Mechanical Properties
Oil resistance
Water resistance
Fire propagationFire propagation of insulation
Smoke production
Corrosivity in case of fire
EPR/CSP
Halogen free
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables18
Lungmen 1&2, Taiwan, BWR from GE (USA)
FRNC Power and control cables from Nexans 2004-2006
Lungmen IEEE 383 Qualification
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables19
1) Thermal Aging
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables20
Method:
Simulate cables qualified life
by
• Arrhenius method -IEEE101
• Complete cable test according
to IEEE 383
Requirement:
Electric evaluation after bending
• 40 years for Lungmen
• 60 years now
1) Thermal Aging
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables21
2) Gamma radiation
radiation
from 60Co
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables22
3) Loss of Coolant Accident Simulation
Lungmen LOCA curve :
max. Temp 340°F
max. Pressure 45 psig
with FRNC cables
0
20
40
60
80
100
120
140
160
180
0 6 12 18 24 30 36 42 48
time [h]
T [
°C]
Temperature
340 °F
320 °F
250 °F
200 °F
2400
0
50
100
150
200
250
300
350
400
450
0 6 12 18 24 30 36 42 48
time [h]
P [
kP
a]
abs. Pressure
2400
45 psig
25 psig
20 psig
Many other LOCA curves are available
Up to 480° F
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables23
Comparison Key Properties
0
2
4
6
8
10
Installation ease
User experience
Industrial experience
Mechanical Properties
Oil resistance
Water resistance
Fire propagationFire propagation of insulation
Smoke production
Corrosivity in case of fire
Ageing resistance
Radiation Resistance
Loca Resistance
EPR/CSP
Halogen free
NPEC/SC2 2009/4/8 Knoxville - L. von Laue (Nexans) : WW experience with Halogen Free IEEE 383 qualified NPP cables24
Conclusion
Halogen Free cables for new US NPP generation
15 years of positive experience
Complete product range IEEE 383 qualified
Important LOCA test range experience
Design compliant to IEEE/ICEA/UL requirements
Improved fire safety
Cost saving solutionThank you for your attention.