Heating and cooling for exhibition and reception rooms, supermarkets, shopping centres, stores, furniture shops, greenhouses, offices etc. with room heights of approx. 2,5 to 5 m.TRANSCRIPT
Ceiling Air Units FB-A: whisper-quiet, economical, reliableComfort Temperature
Heizung - Lüftung - KlimatechnikHeating - Ventilation - Air Conditioning
… the most beautiful side of air
2* Heating = Cooling =
Air guidance lamellae removable for maintenance
Heating and cooling for exhibition and reception rooms, supermarkets, shopping centres, stores, furniture shops, greenhouses, offices etc. with room heights of approx. 2,5 to 5 m.
in attractive design
Hub motor of the quietly running axial fan with sickle blades
FB-A Ultra Ceiling Air Units for Heating and Cooling
Installation FB-A-K Ultra
Housing cover
Condensate tub with Armaflex insulation
Splash protection
Heater / Radiator
Axial fan
Housing floorSwitching box
Pump
Ceiling Air Units FB-A Ultra
Construction size 600 700 800
Type 623-6 633-6 625-6 635-6 635-6-K 626-6 636-6 723-6 733-6 725-6 735-6 735-6-K 726-6 736-6 823-6 833-6 825-6 835-6 835-6-K 826-6 836-6
Kind of operation*
Air capacity m³/h 1950 1930 1650 1530 1320 1650 1530 2940 2900 2695 2550 2305 2695 2550 3990 3665 3750 3400 2950 3750 3400
Voltage V, 50 Hz 230 400 230 400 230 400
Rotational speed U/min. 1240 900 / 700 910 / 720 1300 900 / 750 890 / 700 890 650 / 490 670 / 500
Motor performance kW 0,22 0,04 / 0,03 0,05 / 0,033 0,45 0,11 / 0,07 0,45 0,17 / 0,10 0,16 / 0,095
Power input A 1,0 0,11 / 0,05 0,11 / 0,05 0,13 / 0,07 1,90 0,27 / 0,13 0,27 / 0,13 0,28 / 0,15 2,10 0,47 / 0,21 0,38 / 0,09
Heat exchanger 2 rows 3 rows 2 rows 3 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 3 rows 2 rows 3 rows
Heating capacity kW 4,8 - 26,9 5,4 - 33,9 2,7 - 26,9 3,2 - 33,9 2,8 - 31,0 2,7 - 26,9 3,2 - 33,9 5,8 - 38,8 7,2 - 51,7 6,6 - 40,8 8,1 - 52,6 5,6 - 49,0 6,6 - 40,8 8,1 - 52,6 6,6 - 50,3 8,0 - 64,3 9,3 - 56,5 10,4 - 72,1 7,5 - 52,3 9,3 - 56,5 10,4 - 72,1
Cooling capacity kW 1,1 - 11,1 2,2 - 17,7 2,7 - 23,0
Sound level in 3 m 57 dB(A) 44 dB(A) 44 dB(A) 45 dB(A) 58 dB(A) 45 dB(A) 45 dB(A) 46 dB(A) 61 dB(A) 46 dB(A) 46 dB(A) 47 dB(A)
Weight 38 kg 40 kg 38 kg 40 kg 56 kg 38 kg 40 kg 44 kg 47 kg 44 kg 47 kg 63 kg 44 kg 47 kg 49 kg 54 kg 49 kg 54 kg 68 kg 49 kg 54 kg
Diameter 945 mm 1030 mm 1290 mm
Height 255 mm 305 mm 255 mm 255 mm 255 mm 305 mm 255 mm 255 mm 305 mm 255 mm
Height with suction flashing 336 mm 386 mm 336 mm 336 mm 336 mm 386 mm 336 mm 336 mm 386 mm 336 mm
3 FB-A Ultra
FB-A Ultra and Ultra plus
FA-A Ultra with recirculating air suction grid
Consistent Heat or Comfortable Coolness Type „Ultra“ is fulfilling technically and optically high demands. It is impressive even in exclusive ambience.
Ultra is blowing out horizontally on six sides with 15° inclination, reaching an especially consistent distribution of the tempered air in the room.
Ceiling air units FB-A Ultra are rated for pure heating operation or for combined heating / cooling operation (FB-A-K).
Units with cooling function are equipped with a condensate tub below the cooling register and a condensate pump.
Air capacity up to 3750 m³/h
Heating capacita up to 40 kW
Cooling capacity up to 19,9 kW
Especially quiet by sickle blades Lateral blow-out Suction possible above or below the ceiling Connection heating medium above Air guiding lamellae individually adjustable Condensate pump Condensate tub Delivery completely wired and piped Recirculating, mixed and outside air operation Control System WOLF-Tronic
Ceiling Air Units FB-A Ultra
Construction size 600 700 800
Type 623-6 633-6 625-6 635-6 635-6-K 626-6 636-6 723-6 733-6 725-6 735-6 735-6-K 726-6 736-6 823-6 833-6 825-6 835-6 835-6-K 826-6 836-6
Kind of operation*
Air capacity m³/h 1950 1930 1650 1530 1320 1650 1530 2940 2900 2695 2550 2305 2695 2550 3990 3665 3750 3400 2950 3750 3400
Voltage V, 50 Hz 230 400 230 400 230 400
Rotational speed U/min. 1240 900 / 700 910 / 720 1300 900 / 750 890 / 700 890 650 / 490 670 / 500
Motor performance kW 0,22 0,04 / 0,03 0,05 / 0,033 0,45 0,11 / 0,07 0,45 0,17 / 0,10 0,16 / 0,095
Power input A 1,0 0,11 / 0,05 0,11 / 0,05 0,13 / 0,07 1,90 0,27 / 0,13 0,27 / 0,13 0,28 / 0,15 2,10 0,47 / 0,21 0,38 / 0,09
Heat exchanger 2 rows 3 rows 2 rows 3 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 3 rows 2 rows 3 rows
Heating capacity kW 4,8 - 26,9 5,4 - 33,9 2,7 - 26,9 3,2 - 33,9 2,8 - 31,0 2,7 - 26,9 3,2 - 33,9 5,8 - 38,8 7,2 - 51,7 6,6 - 40,8 8,1 - 52,6 5,6 - 49,0 6,6 - 40,8 8,1 - 52,6 6,6 - 50,3 8,0 - 64,3 9,3 - 56,5 10,4 - 72,1 7,5 - 52,3 9,3 - 56,5 10,4 - 72,1
Cooling capacity kW 1,1 - 11,1 2,2 - 17,7 2,7 - 23,0
Sound level in 3 m 57 dB(A) 44 dB(A) 44 dB(A) 45 dB(A) 58 dB(A) 45 dB(A) 45 dB(A) 46 dB(A) 61 dB(A) 46 dB(A) 46 dB(A) 47 dB(A)
Weight 38 kg 40 kg 38 kg 40 kg 56 kg 38 kg 40 kg 44 kg 47 kg 44 kg 47 kg 63 kg 44 kg 47 kg 49 kg 54 kg 49 kg 54 kg 68 kg 49 kg 54 kg
Diameter 945 mm 1030 mm 1290 mm
Height 255 mm 305 mm 255 mm 255 mm 255 mm 305 mm 255 mm 255 mm 305 mm 255 mm
Height with suction flashing 336 mm 386 mm 336 mm 336 mm 336 mm 386 mm 336 mm 336 mm 386 mm 336 mm
4
FB-A Ultra plus
FB-A Ultra plus
Ceiling Air Units FB-A de luxe
Construction size 600 700 800
Type 623 633 621 631 626 636 723 733 721 731 726 736 823 833 821 831 826 836
Betriebsart*
Air capacity m³/h 1950 1930 1950 1930 1400 1350 2940 2900 2940 2900 2180 2120 3990 3665 3990 3665 2810 2620
Voltage V, 50 Hz 230 400 400 230 400 400 230 400 400
Rotational speed U/min 1240 1320 / 1000 910 / 720 1300 1330 / 1020 890 / 700 890 890 / 680 670 / 500
Motor performance kW 0,22 0,11 / 0,08 0,05 / 0,033 0,45 0,29 / 0,21 0,11 / 0,07 0,45 0,35 / 0,25 0,16 / 0,095
Power input A 1,0 0,20 / 0,12 0,13 / 0,07 1,90 0,50 / 0,32 0,28 / 0,15 2,10 0,80 / 0,46 0,38 / 0,09
Heat exchanger 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows
Heating capacity kW 3,9 - 27,0 4,8 - 35,9 3,9 - 27,0 4,8 - 35,9 3,0 - 23,0 4,0 - 30,9 5,8 - 38,8 7,2 - 51,7 5,8 - 38,8 7,2 - 51,7 4,7 - 33,2 6,4 - 38,3 8,4 - 52,7 9,6 - 67,3 8,4 - 52,7 9,6 - 67,3 6,3 - 49,3 8,7 - 62,3
Sound level in 3 m 56 dB(A) 48dB(A) 61 dB(A) 54 dB(A) 60 dB(A) 53 dB(A)
Weight Variant H 23 kg 25 kg 23 kg 25 kg 23 kg 25 kg 35 kg 37,5 kg 35 kg 37,5 kg 35 kg 37,5 kg 42 kg 45 kg 42 kg 45 kg 42 kg 45 kg
Weight Variant V 27,5 kg 29,5 kg 27,5 kg 29,5 kg 27,5 kg 29,5 kg 41,5 kg 44 kg 41,5 kg 44 kg 41,5 kg 44 kg 50 kg 53 kg 50 kg 53 kg 50 kg 53 kg
Length by width 600 x 568 mm 750 x 718 mm 850 x 810 mm
Height Variant H1 254 mm 260 mm 266 mm
Height Variant H2 267 mm 273 mm 279 mm
Height Variant V 378 mm 378 mm 378 mm
Enormously powerful Type „Ultra plus“ of series FB-A is extending series Ultra by a diagonal fan unit for hightest air capacities.
Due to diagonal air flow and favourable sound behaviour, the FB-A Ultra plus ceiling units can used wherever the capa-city of FB-A Ultra units with their low pressure axial fans isn‘t sufficient any more.
Ultra plus will make it even for larger rooms without efforts - and especially quiet.
Moreover, the special scoop shape of the fan wheel is extremely energy-saving.
with High-Performance Fan
Air capacity up to 4255 m³/h
Heating capacity up to 80 kW
Like FB-A Ultra and in addition
with high-performance fan
with especially quietly running external rotor motor with speed control
possible up to double air capacity
high compression possible
with duct connection frame
FB-A Ultra plus
Construction size 800
Type 834-6-D
Kind of operation*
Air capacity m³/h 4255
Voltage V, 50 Hz 400
Rotational speed min-1 890 / 640 U/min
Motor performance kW 0,31 / 0,20
Power input A 0,72 / 0,41
Heat exchanger 3 reihig
Heating capacity kW 37,9
Sound level in 3 m 68 / 59 dB(A)
Weight 68 kg
Diameter 1290 mm
Height 408 mm
Powerful, quietly running radial fan
FB-A Ultra plus
5 FB-A de luxe
FB-A de luxein wide variety
Especially quiet Blow-out possible laterally and below Suction possible above, above or below
intermediate ceiling, laterally and below Air guiding lamellae individually
adjustable Connection heating medium above Alternatively 2- or 3-row heat exchanger
(CuAl) Control system WOLF-tronic or staged by
transformer Delivery completely wired Recirculating, mixed and outside air
operation
Air capacity up to 3990 m³/h
Heating capacity up to 67,9 kW
Removalbe air guiding lamellae frame
Ceiling Air Heater FB-A de luxe, Variant V, for pure Recirculating Air Operation
Ceiling Air Heater FB-A de luxe, Variant H - for recirculating, mixed and outside air operation
Whisper-quiet and variableFB-A de luxe has been approved on the market for many years.
The advance to comparable units is based on the extremely quiet operation and the particular reliability.
FB-A de luxe is available in variants for horizontal and den vertical blow-out.
Especially quietly running fans provide a super-silent operation.
Ceiling Air Units FB-A de luxe
Construction size 600 700 800
Type 623 633 621 631 626 636 723 733 721 731 726 736 823 833 821 831 826 836
Betriebsart*
Air capacity m³/h 1950 1930 1950 1930 1400 1350 2940 2900 2940 2900 2180 2120 3990 3665 3990 3665 2810 2620
Voltage V, 50 Hz 230 400 400 230 400 400 230 400 400
Rotational speed U/min 1240 1320 / 1000 910 / 720 1300 1330 / 1020 890 / 700 890 890 / 680 670 / 500
Motor performance kW 0,22 0,11 / 0,08 0,05 / 0,033 0,45 0,29 / 0,21 0,11 / 0,07 0,45 0,35 / 0,25 0,16 / 0,095
Power input A 1,0 0,20 / 0,12 0,13 / 0,07 1,90 0,50 / 0,32 0,28 / 0,15 2,10 0,80 / 0,46 0,38 / 0,09
Heat exchanger 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows 2 rows 3 rows
Heating capacity kW 3,9 - 27,0 4,8 - 35,9 3,9 - 27,0 4,8 - 35,9 3,0 - 23,0 4,0 - 30,9 5,8 - 38,8 7,2 - 51,7 5,8 - 38,8 7,2 - 51,7 4,7 - 33,2 6,4 - 38,3 8,4 - 52,7 9,6 - 67,3 8,4 - 52,7 9,6 - 67,3 6,3 - 49,3 8,7 - 62,3
Sound level in 3 m 56 dB(A) 48dB(A) 61 dB(A) 54 dB(A) 60 dB(A) 53 dB(A)
Weight Variant H 23 kg 25 kg 23 kg 25 kg 23 kg 25 kg 35 kg 37,5 kg 35 kg 37,5 kg 35 kg 37,5 kg 42 kg 45 kg 42 kg 45 kg 42 kg 45 kg
Weight Variant V 27,5 kg 29,5 kg 27,5 kg 29,5 kg 27,5 kg 29,5 kg 41,5 kg 44 kg 41,5 kg 44 kg 41,5 kg 44 kg 50 kg 53 kg 50 kg 53 kg 50 kg 53 kg
Length by width 600 x 568 mm 750 x 718 mm 850 x 810 mm
Height Variant H1 254 mm 260 mm 266 mm
Height Variant H2 267 mm 273 mm 279 mm
Height Variant V 378 mm 378 mm 378 mm
Quietly running axial fan
6
Air Guidance Ceiling Air UnitsCeiling air unit FB-A UltraPure recirculating air operationSuction laterally, blow-out laterally
FB-A
Ult
ra
Ceiling air unit FB-A UltraRecirculating, mixed and outside airSuction above, above intermediate ceiling, Blow-out laterally
Ceiling air unit FB-A Ultra plusRecirculating, mixed and outside airSuction above, by air duct in the intermediate ceiling, Blow-out laterally U
ltra
plu
s
Ceiling air heater FB-A de luxe H 2Pure recirculating air operationSuction below Blow-out laterally
FB-A
de
luxe
Ceiling air heater FB-A de luxe H1Pure recirculating air operationSuction above Blow-out laterally
Ceiling air heater FB-A de luxe VPure recirculating air operationSuction laterallyBlow-out below
Ceiling air heater FB-A de luxe H1Recirculating, mixed and outside airSuction above, above intermediate ceiling, Blow-out laterally
Air Guidance Ceiling Air Units by Suction Duct
Ceiling air unit with recirculating air Air suction by suction grid in intermedi-ate ceilingAir suction by recirculating air suction grid, suitable for grid ceilings 625 x 625.
All
FB-A
uni
ts w
ith
suct
ion
abov
e
Ceiling air unit with mixed air attachment partsOutside air suction through the wallThe recirculating air outside air amount is adjusted by the mixed air part. Outside air suction horizontally through the outside wall. Recirculating air suction by recirculating air suction grid.
Ceiling air unit with mixed air attachment partsOutside air suction through the roofThe recirculating air outside air amount is adjusted by the mixed air part. Outside air suction vertically through the roof. Recirculating air suction by adjustable recircu-lating air suction grid.
Recirculating, Mixed, Outside Air Operation
Out versatile product range - tailor-made for your requirements.
In recirculating air operation, the air is sucked out of the room to be heated and blown back into the same room after being heated.
This procedure causes lowest operating costs.
In mixed air operation, fresh air (fresh air amount variably adjustable) is sucked toge-ther with room air.
This procedure reduces heating costs, using partially already heated air out of the hea-ted room, and on the other hand provides the necessary fresh air.
In outside air operation, the air is sucked directly from outside for heating or cooling.
In suitable circumstances, this procedure guarantees clean and unspoilt air.
Possible Applications FB-A
7
Everything under control
In the far background, coordinated technology takes care of perfectly keeping the selected temperature.
Up to 50 ceiling air units can be connected to one switching device, providing quickly optimally distributed warmth or comfortable coolness.
You don‘t see it, yet feel it …
Maximal Comfort: WOLFtronic
D
Three-phase motor400V
2 stages
Alternating-current motor 230 V
1 stage
Repair switch
2 stages automatic system 2 stages
2 stages StandardIndustry
Wet room
= Number of cores of connection pipe
Day / night-time reduction
Day / night-time reduction 2 stages
Servomotor OPEN / CLOSE
Button OPEN / CLOSE Electronic regulatorPosition indicator
0-100 %
Anti-frost thermostat Servomotor continuous
3 stages 5 stages 5 stages
Mot
ors
Swit
chin
g de
vice
sRo
om T
herm
osta
ts
Printed in Germany
8M12
ND
0 v2
WOLF Anlagen-Technik GmbH & Co. KGGeschäftsbereich Heizung - Lüftung - KlimatechnikMünchener Str. 5485290 Geisenfeld, GERMANYTelefon +49 (0) 8452 99-0Telefax +49 (0) 8452 99-250E-Mail info @ wolf-geisenfeld.de Internet www.wolf-geisenfeld.de
GB
WOLF Anlagen-Technik GmbH & Co. KGDivision Heating - Ventilation - Air-conditioning Münchener Str. 5485290 Geisenfeld, GERMANYTelephone +49 (0) 8452 99-0Telefax +49 (0) 8452 99-250E-Mail info @ wolf-geisenfeld.de Internet www.wolf-geisenfeld.de
Mod
ifica
tions
in d
esig
n an
d fu
nctio
n re
serv
ed.