wkk-ontmoetingsdag 2021 hydraulic integration of chp
TRANSCRIPT
![Page 1: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/1.jpg)
Ruben VosInt. Key Account Manager
WKK-ontmoetingsdag 2021
Hydraulic integrationof CHP installations
![Page 2: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/2.jpg)
Waarom deze Webinar?
1. Introduction
2. Sizing and optimising CHP/TS
3. Hydraulic integration of CHP’s
4. Case study
![Page 3: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/3.jpg)
Waarom deze Webinar?
Introduction
1. Warmtekrachtkoppeling
2. Hybride stookplaatsen
![Page 4: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/4.jpg)
Why combined heat and power (CHP)?
gas
losses
electricity
heat
45-55%
35-45%
10%
100%
![Page 5: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/5.jpg)
In the Hysopt software…
Stirling
Gas engine
![Page 6: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/6.jpg)
In the Hysopt software…
![Page 7: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/7.jpg)
Controls
Return temperature control with back-end protection valve and shunt pump
The return temperature is taken into account for the modulation of the CHP and disabling of the CHP
Programmable controller which enables the CHP when thermal store is discharged and minimum amount of start-ups for that day or not reached.
![Page 8: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/8.jpg)
Maximimising CHP contribution
• Maintaining optimal working conditions (temperature)
• Provide sufficient flow rates
Return temperature needs to besufficiently low to prevent
modulation and a shutdown
Flow rate needs to besufficiently high to providesufficient load to the CHP
![Page 9: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/9.jpg)
Optimisation of hybrid plantrooms
0
1
2
3
4
5
6
7
8
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
PAYB
AC
K
ENERGY COST SAVING
Payback <1 <2 <3 <5
Project ratio 31% 69% 75% 94%
Energy cost savings / year
>40% >20% >15% >10%
Project ratio 43% 57% 67% 86%
![Page 10: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/10.jpg)
System efficiency vs production efficiency of individual plant
• The system efficiency should always prioritise on the production
efficiency of individual plant → sacrifice production efficiency for the sake
of optimising system efficiency…
η𝑝𝑟𝑜𝑑 =𝑄𝑝𝑟𝑜𝑑𝑢𝑐𝑡𝑖𝑒
𝑄𝑔𝑎𝑠
![Page 11: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/11.jpg)
Waarom deze Webinar? Sizing CHP and thermal store
![Page 12: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/12.jpg)
Consumption data
![Page 13: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/13.jpg)
Energy modelling approach
500 kW
250 kW
![Page 14: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/14.jpg)
Energy modelling approach
500 kW
250 kW
![Page 15: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/15.jpg)
Energy modelling approach
125 kW
250 kW
![Page 16: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/16.jpg)
Energy modelling approach
125 kW
250 kW
• Flow rate?• Return temperature?
But….Hydraulics to be taken into account!
![Page 17: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/17.jpg)
Thermal store
• Avoidance of start/stops (max. 2-6 times a day)
Time
Ther
mal
po
wer
[kW
]
cycle time
Charging time
discharge time
Heat load in
summer day
Lower limit of CHP load
100 kW
125 kW
![Page 18: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/18.jpg)
Thermal store
• Avoidance of start/stops (max. 2-6 times a day)
The CHP is only restartedwhen the thermal store is
discharged
The CHP is disabled whenreturn temperature to
CHP is too high
![Page 19: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/19.jpg)
Thermal store
• Avoidance of
start/stops (max.
2-6 times a day)
max. 6 starts per 24h
Without storage
30 m³
20 m³
![Page 20: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/20.jpg)
Thermal store
• Avoidance of start/stops (max. 2-6 times/day)
• Optimising the CHP production share
• Shifting production share from night to day time (higher electricity tariffs)
Heat networkload
200 kW CHP –no TS
200 kW CHP –20m³ TS
![Page 21: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/21.jpg)
Waarom deze Webinar?
Demo: finding the optimal size
for CHP and thermal store
![Page 22: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/22.jpg)
![Page 24: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/24.jpg)
Waarom deze Webinar?
Hydraulic integration of CHP
installations
![Page 25: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/25.jpg)
Hydraulic integration of CHP installations
70 50
?
CHP at 90/70°C
Back-up boiler
Heating distribution
Thermal store
![Page 26: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/26.jpg)
Hydraulic integration of CHP installations
![Page 27: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/27.jpg)
Hydraulic integration of CHP installations
• Parallel CHP-boiler hybrid• Most common used principle,
similar to boiler cascade
![Page 28: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/28.jpg)
Hydraulic integration of CHP installations
![Page 29: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/29.jpg)
Case study – hydraulic optimisation of existing building
![Page 30: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/30.jpg)
Volume weighted annual return temperature
(VWART):
74°C -> 37°C
Case study – hydraulic optimisation of existing building
![Page 31: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/31.jpg)
BEFORE
AFTER Variable Flow
Constant Flow
1,2 MW
60°C
80°C
650 kW
20°C
Case study – hydraulic optimisation of existing building
Before
After
![Page 32: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/32.jpg)
Waarom deze Webinar?
Optimising the hydraulic integration
of a CHP installation
![Page 33: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/33.jpg)
Design for performance
• Optimised component selection
• Commissioning
• Shareable cloud-based model
Performance at the design
stage
Secure Design
Integrity
Digital Twin
of your P&ID
• Lifecycle management of the installation
• Performance management of the installation
• Gradual integration of low carbon technology
• Design & Calculation too
• Dynamic Simulation tool
• Compare performance of different concepts
![Page 34: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/34.jpg)
What you can expect
30% Energy cost saving
10%capex reduction
75%Payback in under
3 years
>200HVAC optimisation
projects
27%carbon savings
90%reduced design
errors
![Page 35: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/35.jpg)
Waarom deze Webinar? Wrap-up and Q&A
![Page 36: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/36.jpg)
![Page 37: WKK-ontmoetingsdag 2021 Hydraulic integration of CHP](https://reader034.vdocuments.mx/reader034/viewer/2022052106/6287d163502639401f1d955c/html5/thumbnails/37.jpg)
WKK-ontmoetingsdag 2021
Hydraulic integrationof CHP installations
Ruben VosInt. Key Account Manager
Johan BaanAccount Manager BE
Brian VanheelPresales engineer