Campus
Annual Electricity Maximum Power Max. Chilled Water Annual Thermal Max. Thermal
kWh/gsf/yr W/gsf tons/kgsf therms/gsf/yr therms/hr/kgsf
Includes prorated part of plant use and site lighting
Includes prorated part of small peak (pumping) load at plant Load on plant Includes prorated part of
plant useIncludes prorated part of
plant use
Benchmark 50% Target Benchmark 50% Target Benchmark 50%
Target Benchmark 50% Target Benchmark 80%
Target
Berkeley 36 18.0 7.6 3.8 N/A N/A 1.83 0.92 0.43 0.34
Davis 38 18.9 6.3 3.1 4.7 2.4 1.83 0.91 0.43 0.34
Irvine 38 18.8 5.6 2.8 4.2 2.1 1.78 0.89 0.43 0.34
Los Angeles 37 18.5 5.4 2.7 4.1 2.0 1.79 0.89 0.43 0.34
Merced 39 19.3 6.4 3.2 4.8 2.4 1.82 0.91 0.43 0.34
Riverside 38 19.1 6.3 3.1 4.7 2.4 1.80 0.90 0.43 0.34
San Diego 37 18.4 5.3 2.7 4.0 2.0 1.78 0.90 0.43 0.34
San Francisco Parnassus 36 18.0 5.2 2.6 3.9 1.94 1.84 0.92 0.43 0.34
San Francisco Mission Bay 36 18.1 7.6 3.8 N/A N/A 1.84 0.92 0.43 0.34
Santa Barbara 36 18.1 5.3 2.7 4.0 2.0 1.81 0.91 0.43 0.34
Santa Cruz 36 18.0 7.6 3.8 N/A N/A 1.85 0.93 0.43 0.34
UC Building Energy Benchmarks by Campus Housing Non-complex Space
Campus
Annual Electricity Maximum Power Max. Chilled Water Annual Thermal Max. Thermal
kWh/sf/yr W/sf tons/ksf therms/sf/yr therms/hr/gsf
Includes prorated part of plant use and site lighting
Includes prorated part of small peak (pumping) load at plant Load on plant Includes prorated part of
plant useIncludes prorated part of
plant use
Benchmark 50% Target Benchmark 50% Target Benchmark 50%
Target Benchmark 50% Target Benchmark 80%
Target
Berkeley 7.8 3.9 2.1 1.07 N/A N/A 0.30 0.15 0.18 0.14
Davis 9.3 4.7 2.3 1.16 1.75 0.88 0.29 0.15 0.18 0.14
Irvine 9.1 4.5 1.79 0.90 1.35 0.67 0.23 0.12 0.18 0.14
Los Angeles 8.6 4.3 1.60 0.80 1.20 0.60 0.24 0.12 0.18 0.14
Merced 10.0 5.0 2.4 1.21 1.82 0.91 0.28 0.14 0.18 0.14
Riverside 9.7 4.9 2.3 1.16 1.75 0.88 0.26 0.13 0.18 0.14
San Diego 8.6 4.3 1.55 0.77 1.17 0.58 0.23 0.11 0.18 0.14
San Francisco Parnassus 7.8 3.9 1.40 0.70 1.06 0.53 0.30 0.15 0.18 0.14
San Francisco Mission Bay 8.0 4.0 2.1 1.07 N/A N/A 0.30 0.15 0.18 0.14
Santa Barbara 8.0 4.0 1.55 0.77 1.17 0.58 0.28 0.14 0.18 0.14
Santa Cruz 7.8 3.9 2.2 1.11 N/A N/A 0.32 0.16 0.18 0.14
UC Building Energy Benchmarks by Campus Academic / Administrative Non-complex Space
Campus
Annual Electricity Maximum Power Max. Chilled Water Annual Thermal Max. Thermal
kWh/sf/yr W/sf tons/ksf therms/sf/yr therms/hr/ksf
Includes prorated part of plant use and site lighting
Includes prorated part of small peak (pumping) load at plant Load on plant Includes prorated part of
plant useIncludes prorated part of
plant use
Benchmark 50% Target Benchmark 50% Target Benchmark 50%
Target Benchmark 50% Target Benchmark 80%
Target
Berkeley 11.2 5.6 3.1 1.53 N/A N/A 0.21 0.10 0.12 0.10
Davis 13.3 6.7 3.3 1.66 2.5 1.25 0.20 0.10 0.12 0.10
Irvine 13.0 6.5 2.6 1.28 1.93 0.96 0.16 0.081 0.12 0.10
Los Angeles 12.3 6.2 2.3 1.14 1.72 0.86 0.17 0.085 0.12 0.10
Merced 14.3 7.2 3.5 1.73 2.6 1.3 0.20 0.10 0.12 0.10
Riverside 13.9 6.9 3.3 1.66 2.5 1.25 0.18 0.09 0.12 0.10
San Diego 12.2 6.1 2.2 1.11 1.66 0.83 0.16 0.08 0.12 0.10
San Francisco Parnassus 11.1 5.6 2.0 1.00 1.51 0.75 0.21 0.11 0.12 0.10
San Francisco Mission Bay 11.4 5.7 3.1 1.53 N/A N/A 0.21 0.11 0.12 0.10
Santa Barbara 11.5 5.7 2.2 1.11 1.66 0.83 0.19 0.10 0.12 0.10
Santa Cruz 11.1 5.6 3.2 1.58 N/A N/A 0.23 0.11 0.12 0.10
UCSB 2013 Benchmarks in Relation to UC Benchmarks and Targets
Annual Electricity Peak Electricity Peak Chilled Water
Annual Thermal Peak Thermal0%
40%
80%
120%
160%
200%
Complex (Lab) Housing Non-complex Academic
Perc
ent o
f 199
9 U
C Be
nchm
ark
Target at UC Merced for new buildings – 50% of Benchmark
Basis of Design: gas-fired condensing boiler plantEnergy Conservation Measures:• Ventilation heat recovery from bldg exhaust• Passive solar heat optimization during heating season• Minimization of reheat in labs through application of
chilled beams and dynamic reset of ventilation supply temp.
Heating
Basis of Design: UCSB chilled water loop (.065kW/ton)Energy Conservation Measures:• Specification of low SHGC glazing• External shading• Thermal mass (incl. phase change materials)• Active chilled beams in lab spaces• Operable windows in office and administration areas
Cooling
Energy Conservation Measures:• Demand-controlled ventilation• VAV fume hoods • Air quality sensing in wet labs• Natural ventilation in offices, admin areas, seminar
rooms
Ventilation
Envelope Thermal PropertiesEnvelope Component Non-Res, CZ6 Basis of Design
Roof: low sloped [Btu/h x ft2 x °F] U-0.075 U-0.048
Ext walls: metal framed [Btu/h x ft2 x °F] U-0.098 U-0.069
Floors/soffits [Btu/h x ft2 x °F] U-0.071 U-0.052
Window assembly: north [Btu/h x ft2 x °F]/SHGC U-0.077/0.61 U-0.065/0.25
Window assembly : non-north [Btu/h x ft2 x °F]/SHGC U-0.077/0.34 U-0.065/0.25
Lighting Power Density and Occupancy Values
Equipment Power Densities
Space Type Equipment W/ft2 Natural Ventilation
Break-out 0.0 Yes
Corridor 0.0 Yes
Lecture Hall 1.0 No
MEP Room 0.2 No
Office 1.0 Yes
Restroom 0.0 No
Seminar 1.0 Yes
Stair 0.0 Yes
Based on ASHRAE assumed EPDs.
Lab Type Equipment Peak W/ft2 Natural Ventilation
Wet Labs 5.3 No
Computer Labs 3.7 Yes
Optics 7.5 No
Electronics 7.5 Yes
Equipment Power Densities
Based on metered 120/208v receptacle power demand data from existing laboratories on the UCSB campus.
Power Monitoring - John Bowers Laboratory, UCSB Engineering Science Building
PRED