wesave box
DESCRIPTION
Box of WeSave (Wellness Telecom)TRANSCRIPT
Option 3F 3 Measurement of power in three- phase circuits
Option 9M Measurement of power in 9 single phase circuits
Option 3FD Measurement of power in 6 three-phase circuits
Option 9MD Measurement of power in 18 single phase circuits
Parameters measured Voltage (V). Current (A). Active Power (kW). Reactive Power (kVAr). Power factor. Active Energy consumption (kWh). Reactive Energy Consumption (kVArh)
Operating Voltage Range 40 - 400 VACOvervoltage Tolerance (OVT) 800V / 30s
Current measurement Depending on CT usedFrequency 45 / 60 HzSupply 85 / 265 VACAccuracy Class Current 0.5s
Voltage 0.5sPower 0.5sEnergy 1.0s
Power Consumption < 3VAResistance >100MΩIsolation Power input/output AC 2kV / 1min 50Hz
TemperatureRange
Operating -15°C /+55°CStorage -25°C /+70°CHumidity < 93%
Option 3F9M Measurement of power in 9 single phase circuits and 3
three-phase circuits
FeaturesThis option includes a RJ45 jack for direct connection to a LAN network
Ethernet connection 10/100 Base-T. RJ45 jack. IP Addressing: DHCP, static IP address.
FeaturesThis option allows connecting to a Wi-Fi stan-dard network to access information
Compatible with standard IEEE802.11a/b/gCompatible with WEP, WPA, WPA2, PSK
FeaturesThis option allows direct communication with WeSave servers through the mobile phone network, which makes network confi-guration unnecessary.
Quad-band module GSM 850/900/1800/1900 MHz
Virtual APN private and secured
Fully Automatic Setup