WATER TREATMENT PLANT FACILITIES MODIFICATIONS PROJECT
ADDENDUM NO. 4
INVITATION FOR BID: E190015508
QUESTIONS/ANSWERS:
1. Question: Specification 083474, Part 2, Subsection 2.04, Line A on page 083474-4: states,
“Manufacture doors and frames to STC rating of 59…” Subsection 2.01, Line A on page 083747-
3, lists: Basis of Design, Ambico Limited or approved equal.” Per Ambico, an STC-59 rated door
cannot be UL Rated or have a vision light, as specified for these openings on the door schedule.
Please advise if it would be acceptable to either lower the required STC Rating, or remove the
requirements on UL Rating and Vision Lights.
Answer: Specification Section 083474, Part 2, Subsection 2.04, Paragraph A:
DELETE: “59”, and INSERT: “52”.
2. Question: Drawing A-801, shows “Door Schedule,” for Opening 2204. Drawing A-104 does
not list Opening 2204, or Office 2204. Drawing ID-103 shows Office 2204 as an open area accessed
via opening 2205. Please advise how to proceed with Opening 2204.
Answer: Delete Room Tag “Office 2204” from Drawing ID-103.
3. Question: Who will be responsible for moving all furniture, equipment, etc. from spaces to
be renovated?
Answer: The majority of the existing furniture, chemicals, equipment, etc. in the new
work areas on the 2nd floors of Plants 1 and 2 will be removed by the City
prior to the beginning of work in these areas. The existing furniture in all of
the existing offices will remain and will need to be temporarily moved or
relocated to perform the required work. The remaining furniture, items, etc.
left in the new work areas on the 1st floor of Plant 1 and the 2nd floors of Plants
1 and 2 will require temporary relocation and protection as needed to perform
the required work in these areas.
4. Question: There is a specification section 101423 Panel Signage. The drawings do not have
a signage schedule. Can you provide one?
Answer: Contract drawings A-801 and A-802 have been modified accordingly. The
revised contract drawings are included as Attachment A to this Addendum.
5. Question: Drawing A1, shows “Door Schedule,” for Openings B00 and 200. No hardware is
specified for either opening. Please Advise.
Answer: Delete Door B00. Provide 36”X45” rated access door above elevator door per
Key Note 5 on sheet A2. Note: Access door is to be rated 1 HR.
6. Question: Drawing A1, shows “Door Schedule,” for Opening 200 Control Closet. Remarks
are listed as “Door to match those of Facilities Modifications Project,” the facilities modification
project has both Hollow Metal and Wood Doors, please advise which is the intended for this
opening.
Answer: Door 200 is to be a 1 HR rated door. Door material and finish is to match
Door 1212. Provide 3 hinges, door closer, and storeroom lockset, and 3
silencers. All hardware is to match manufacturer, finish, and style of Door
1212.
N:\46499-029\Engineering\5 Bidding\FEB. 2019 REBID\Addendum 4\Addendum 4.docx February 27, 2019 Page 1
Attachment A
Contract Drawings A-801 and A-802
_ :t- X
"<,:
'
s a
<D I
;,,
f 1 EQ 1O" EQ
, !, I, oc8 J
n"'
'
J 1
0
':.
METAL STUD
HEAD AT HEAD
II
SEALANT (TYP)
GLAZING TO BE GLASS TYPE #3, LAMINATED GLASS WINDOW TYPES SCALE: 1 / 4"=1'- 0"
fEE SCHEDUf E
SCHEDULED DOO
JAMB ANCHORS (3 PER JAMB)
METAL FRAME
SPOT GROU T L,
AT JAMB - 1
ANCHOR (TYP) N a
I
--"'
w
::, 0w
:r: u V)
w w
JAMB DOUBLE METAL STUDS AT
SEALANT (TYP)
c-- a <DX
c-- V)
JAMB (TYP)
DOOR DETAILS A- 801 SCALE: I " =1'- 0"
I <,:
"A" "B" "c" "D" SINGLE HUNG
"W3"
6'- 0"
2"
a
NOTE: GLAZING TO BE TYPE #2 SAFETY GLAZING AT VISION LITES
DOOR TYPES SCALE: 1/ 4"=1' - Q"
SEE SCHEDULE ,r
w ::, 0w
:u
r:
N
! A- 801 O'
0 0 0
DOORS 2"
WIDTH f
a a
0 0 I I
MASONRY
IN - FILL,
V)
w w V)
SINGLE HUNG "W2"
"SF1"
FRAME TYPES SCALE: 1 / 4''=1 ' - 0"
c--
"Fl"
c--
"F2"
PAINT TO MATCH EXIST
CONSTRUCTION
w ' ::,
NOTE: 4" FRAME HEAD AT MASONRY OPENINGS 0w
:r:
HEAD
5/8" GYPSUM WALL BOARD
r
,-;
u V)
w w V)
BACKER ROD & SEALANT TYP BOTH SIDES
SINGLE HUNG
"W1"
DOOR NOTES: 3 412 J EXISTING STRUCTUR
EXISTING STRUCTUR
I. TYPICAL DOOR HEIGHT: 7'-0" UNLESS NOTED OTHERWISE.
2. TYPICAL DOOR THICKNESS: I 3/ 4" AT STANDARD DOORS, 2 3/ 4" AT ACOUSTICAL STEEL DOORS
3. FIELD VERIFY ALL OPENING SIZES PRIOR TO MANUFACTUREOF FRAMES.
4
ALUMINUM STOREFRONT FRAME
" I4 • SEALANT
HORIZONTAL
I 5/8" STUDS SEALANT
'
EXISTING GLAZED CMU
ir HORIZONTAL
LOUVER BLIND
DOUBLE STUD @ JAMB, TYP.
5/8" GYPSUM WALL BOARD
SCHEDULED DOOR
LOUVER BUN
I
I
I
- SCHEDULED CEILING
- 5/8" GYPBD - PAINT
- 5/8" GYPBD - PAINT
- ALUMINUM WINDOW I
EXISTING GLAZED CMU
-ALUM. WINDOW W/ I" INSUL. GLAZING
.&
Whitman, Requardt & Associates, LLP
9030 Stony Point Parkway, Suite 220, Richmond, Virginia 23235
WINDOW NOTES:
A. * FIELD VERIFY ALL OPENINGS PRIOR TO MANUFACTURE OF
FRAMES
JAMB f
BACKER ROD & SEALANT TYP. BOTH SIDES
I
I
I
I ,,
W/ I" INSU L. GLAZING & MESH SCREEN
-+-- 0
0- ,, & MESH SCREEN
B. GLAZING TO BE TYPE #4 I" LOW E CLEAR INSULATED
GLASS AT EXTERIOR WINDOWS & TYPE #4A AT OFFICES
2203 & 2205
6'-0"
VIF
EXISTING STRUCTU R
SEALANT
SEALANT SCHEDULED 11
DOOR ' SEALANT ,,------,
/ SCHEDULED FRAME
I - SEALANT I
I I " SOLID SURFACE MATERIAL
I I" SSM-2
I 5/8" STUDS '
- SEALANT
.,,...,,,...
CONTINUOUS BOTH SIDES
/ METAL THRESHOLD
- 5/8" GYPBD - PAINT --' +
a
0
EXISTING GLAZED CMU
"11"
LOUVER TYPES SCALE: 1 / 4"=1 ' - 0"
, WALL PARTITION - WHERE OCCURS,
- SINGLE HUNG WINDOW WITH MESH SCREEN
SILL
1 / 4" DIA. STAINLESS SIEEL FLAT HEAD EXP. BOLT @ 24" OC
I
SCHEDULED WALL BASE "'
SCHEDULED FLOORING
' '
EXISTING
FLOORING
N:\ 46499-029\ CADD\ 46499029A8- 01.dwg Feb 18, 2019 - 10:17am
4 PLAN DETAIL @ W INDOW JAMB A- 801 SCALE: 3" =1'- 0"
2 STORE FRONT
DETAILS A- 801 SCALE: 3" =1'- 0"
3 WINDOW DETAIL A- 801 SCALE: 3/4" =1'- 0"
5 WINDOW DETAIL A- 801 SCALE: 3/4'' =1'- 0"
/
2/ A-
SIGNATURE
GRAPHIC SCALES
Q 2' 4' 8' I
SCALE: I / 4" = I' -0"
Q 6" 1' 2' I
SCALE: I " = I ' - 0"
0 I ' 2' 3' I I SCALE: 3/ 4" = 1'- 0"
WTPFM - FACILITIES
MODIFICATIONS
CLIENT INFORMATION
CITY OF RICHMOND
900 EAST BROAD ST.
RICHMOND , VA
232 19
3'-0" 2'- 8"
--"'
a
I
t
□
z
0
Cu
c
s
(QQQJj) SAMPLE- SYMBOL DOOR SCHEDU LE
MK
HARDWARE
SET
D O O R S FIRE RATING
-
LABEL
& SIGN TYPE
R E M A R K S
FINISH
WIDTH (NOM) LOCATION TYPE MATL TYPE MATL HEAD JAMB SILL DOOR FRAME
110 1
BYOOOR MANUF. 3'-0" VESTIBULE 11 01 D ALUM. SFI ALUM. 2/A-801 2/ A- 801 2/A-801
LOCATION: PLANT NO. 1 FIRST FLOOR
1115 ETR 3'- 0" CONFERENCE 1115 EXIST. HM EXIST. HM A I SALVAGE & RE- INSTALL EXISTING
DOOR, FRAME & HARDWARE PTO PTD
"" 0 0
c" 0
z0u
w V)
oz
>--
(L
1202 HW- 1 3'-0" OFFICE 1202 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801 A2 STAIN PTD
1203 HW-1 3'- 0" OFFICE 1203 A WO Fl HM 1/ A- 801 1/ A- 801 1 / A- 801
A2
STAIN PTO
1204 HW- 2 3'-0" WOMENS TOILET 1204 C HM Fl HM 1/A-801 1/ A- 801 1 / A- 801
B2
PTO PTD
1205 HW-2 3'- 0" MENS TOILET 1205 C HM Fl HM 1/ A- 801 1/ A- 801 1 / A- 801 Bl
PTD PTD
1206 HW-1 3'-0" LIBRARY 1206 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801 Al
STAIN PTD
1208 HW-3 (2) 3'- 0" FAN ROOM 1208 B STEEL F2 STEEL 1/ A- 801 1/ A- 801 1 / A- 801 45MIN. A
3 NEW ACOUS TICAL STEEL DOOR, REF.
SPEC SECTION 08374 PTD PTD
1209 HW-3 (2) 3'-0" FAN ROOM 1209 B STEEL F2 STEEL 1/A-801 1/ A- 801 1 / A- 801 45MIN. A 3 NEW ACOUSTICAL STEEL DOOR, REF.
SPEC SECTION 08374 PTO PTD
1210 HW-1 3'- 0" CONFERENCE 1210 A WO Fl HM 1/ A- 801 1/ A- 801 1 / A- 801 Al STAIN PTD
1210.1 HW- 1 3'-o" CONFERENCE 1210 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801
A1
STAIN PTD
1212 HW-1 3' - 0" OFFICE 1212 A WO Fl HM 1/ A- 801 1/ A- 801 1 / A- 801
A2
STAIN PTD
1213 HW- 1 3'-0" OFFICE 1213 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801
A2
STAIN PTD
1214 HW-1 3' - 0" HVAC B HM Fl HM 1/ A- 801 1/ A- 801 1 / A- 801 45MIN. A 3 NEW ACOUSTICAL STEEL DOOR, REF.
SPEC SECTION 08374 PTO PTD
1215 HW-1 3'-0" OFFICE 1215 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801 A2 STAIN PTD
1216 HW-1 3' - 0" MECH 1216 B WO Fl HM 1/ A- 801 1/ A- 801 1 / A- 801
A3
STAIN PTD
g§
s
z 0u
w V)
N
0z
z>--
2202
HW-3 (1)3'-0"
( I)2'- 4"
CORRIDOR 2202
B
HM
F2
HM
45MIN.
NEW ACOUSTICAL STEEL DOOR, REF. SPEC SECTION 08374
PTO
PTD
2203 HW-1 3'-0" OFFICE 2203 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801 A2 STAIN PTD
2204 HW-1 3'-0" OFFICE 2204 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801
A2
STAIN PTD
2205 HW-1 3'- 0" OFFICE 2205 A WO Fl HM 1/ A- 801 1/ A- 801 1 / A- 801
A2
STAIN PTO
2206 HW-1 3'-0" OFFICE 2206 A WO Fl HM 1/A-801 1/ A- 801 1 / A- 801
A2
STAIN PTD
2207 ETR (2) 3'- 0" MECH 2207 EXIST
EXIST
A 3 SALVAGE & RE- INSTALL EXISTING DOOR, FRAME & HARDWARE PTD PTD
2210 HW- 1 3'-0" ELEC 2210 A HM Fl HM 1/A-801 1/ A- 801 1 / A- 801 A3 PTO PTD
2212 HW- 1 3'-0" 1- C SHOP 2212 A HM F1 HM 1/A-801 1/ A- 801 1 / A- 801
A3
PTO PTD
2213 HW- 2 3'-0" UNISEX 2213 C WO F1 HM 1/A-801 1/ A- 801 1 / A- 801
B3
STAIN PTD
SAMPLE- SYMBOL WI N DOW SCHEDULE
TOTAL NO TYPE NOM WU SIZE
(W X L)
DETAILS LINTEL REMARKS
HEAD JAMB SILL
W1 ALUMINUM 3'- 10" X 6' - 11" VIF 3/A-801 3/ A- 801 3/A-801 EXIST.
32 W2 ALUMINUM 6'- 11" X 6'- 1 I" VIF 3/A-801 3/ A- 801 3/A-801 EXIST. REF. DETAIL 5/ A- 801 FOR PLANT N0.2 FIRST FLOOR CORRIDOR
2 W3 ALUMINUM 3'-8" X 6' - 11" VIF 3/A-801 3/ A- 801 3/A-801 EXIST.
REVISIONS
1 ADDENDUM 1 2/18/19
SCHEDULES & DETAILS
DRAWING NO.
A-801 SCALE:AS SHOWN
DATE:8/ 23/ 2017 SHEET 26 OF 77
DES: KM DRAWN:KM CHECK: KF
5/8"
1/2"
GRAPHIC SCALES
SIGNATURE
PICTOGRAM
DIVIDER STRIP
RAISED LETTERS
BRAILLE
6"
MEN
PICTOGRAM
DIVIDER STRIP
RAISED LETTERS
BRAILLE
6"
WOMEN
PICTOGRAM
DIVIDER STRIP
RAISED LETTERS
BRAILLE
8 1/2"
RESTROOM
Whitman, Requardt & Associates, LLP
9030 Stony Point Parkway, Suite 220, Richmond, Virginia 23235
EDGE OF WALL
EDGE OF WALL
RAISED ROOM NUMBER
BRAILLE ROOM NUMBER
DIVIDER STRIP
RAISED LETTERS
133
11" NUMERIC ROOM
NUMBER
BRAILLE ROOM NUMBER
EXTRUDED ALUMINUM
133
10"
3"
ROOM SIGNAGE
DOOR
HARDWARE
FINISHED FLOOR
3"
ROOM SIGNAGE
DOOR HARDWARE
FINISHED FLOOR
RAISED LETTERS
BRAILLE
CONFERENCE ROOM
8 1/2"
ELECTRICAL
INSERT SLOTS TO ACCEPT PAPER INSERTS
SILK SCREENED LETTERS
EMPLOYEE NAME DEPARTMENT & ACRONYM
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
CLIENT INFORMATION
1/4"
5
3/4"
5/
8"
1/2"
8
1/2"
2 1/
2"
1/4"
4"
6
3/4"
2 1/
2"
1/4"
5
3/4"
8 1/
2"
1/4"
2
1/2"
2
1/2"
5 1/
2"
5/8
1/4
5 3/
4
1/2
8 1/
2"
REVISIONS
1 ADDENDUM 1 2/18/19