VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

ANNEXURE II

TECHNICAL CLARIFICATIONS TO BIDDERS’ QUERIES

JOB Electrical Systems FGUTPP Stage-IV (1X500 MW) TENDERNO NBPPL/MM/FGUTPP/E-41034/14

Sr. No.

Reference clause of tender document

Existing provision Bidder’s query NBPPL’s clarification

I. Volume I - General/ Spec. No. - PE-TS-401-999-E001 1 Clause 2.5,

Quantity Variation Clause/ Page 19 of 1481

VARIATION OF QUANTITIES MAY BE TO THE EXTENT OF +/-30% OF TOTAL CONTRACT VALUE.

Please note that the price shall remain firm for the rating and BOQ specified in tender documents. For any increase or decrease beyond the quantity specified in tender documents, the same shall be subject to price implication as per unit rates specified in Price Schedule.

Please refer GCC Clause No: 6.1

2 Annexure-1 Vendor List/ Page 24 of 1481

2. Medium Voltage Busduct We request to please approve "(i). C&S (ii). Entraco (iii). Powergear (iv). Busbar System (v). Entraco" in the makelist of Medium Voltage Busduct.

Please refer Clause No: 2.3.22 of Scope of Enquiry of Technical specifications Volume-I

Page 3: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

3 Annexure-1 Vendor List/ Page 24 of 1481

6. LT Outdoor Transformer We request to please approve "ABB Make" in the makelist of LT Outdoor Transformers.

Please refer Clause No: 2.3.22 of Scope of Enquiry of Technical specifications Volume-I

4 Annexure-1 Vendor List/ Page 24 of 1481

7. LT Switchgear We request to please approve "ABB Make" in the makelist of LT Switchgear.

Please refer Clause No: 2.3.22 of Scope of Enquiry of Technical specifications Volume-I

5 General Please note that the equipment quoted as a part of complete electrical system are not for Part Ordering and shall be treated under one electrical package as per the BOQ/Quantity estimated by NBPPL. Bidder shall not be responsible for estimation from the given layouts. Quantity provided in BOQ is treated final for ordering during execution.

Follow Technical Specifications

II. Vol II Part-B - TECHNICAL SPECIFICATIONS OF ELECTRICAL SYSTEMS, DOC. NO.: NBPPL-004-201-00-P4E-A 6 General Technical

TECHNICAL SPECIFICATION SECTION - VI PART-C, Cl 5.01.00 & Cl 5.02.00 /Page 2 of 75 OR Page

In addition to the codes and standards specifically mentioned in the relevant technical specifications for the equipment ……………………………...India as well as

Please note that we shall follow equipment specific relevant Indian Standards i.e. IS or IEC/IEEE standards only inline with applicable Statutory regulations if any.

Follow specifications – respective package standards as mentioned in specs shall be followed

Page 4: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

50 of 1481 of the locality where..................

7 General Technical TECHNICAL SPECIFICATION SECTION - VI PART-C, Cl 5.06.00/Page 4 of 75 OR Page 52 of 1481

Two (2) English language copies of all national and international codes and/or standards used in the design of the plant……………….from the date of the Notification of Award.

Please note that Codes and standards cannot be duplicated. However we shall provide the list of the codes / standards related to the equipment supplied by us during detailed engineering. The same can be directly purchased by Client from the relevant governing authorities.

Follow GTR provided by NTPC

MV Busduct - Technical Specification Vol II Part-B, Doc No. - PE-TS-401-505-E002 8 Cl 3.05.02 /Page

220 of 1481 The design of the support structure shall conform to IS:800. the support structure shall also be designed to take care of Employer's cable tray load of 100 kg/ metre.

Please note that It is not recommended to load cable tray on the same support structure of SPBD and cables shall be routed separately.

Bidder to follow the technical specifications

Page 5: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

9 Cl 3.06.01/Page 220 of 1481

A continuous 65 x 8 mm galvanised mild steel earth bar shall be provided along the entire run of each busduct. Each section of the busduct enclosure shall be bonded to this earth bar at least at both ends of the enclosure.

Earthing busbar size shall be capable of system fault current & duration. Continuous earth busbar shall be provided only on one side of enclosure. Other side provision of earth busbar shall be given.

Bidder to follow the technical specifications

10 Cl 3.09.02/Page 221 of 1481

The paints shall consist of one coat of primer followed by one anti-corrosive coat for steel structures. Finally two coast of finishing paint shall be given. The final colour shade shall be BLUE RAL: 5012.

Please note that all the steel structures shall be hot dip galvanized only. Painting is not applicable for the structures. Painting procedure shall be manufacturer specific only. Color coding mentioned will be followed as per specification.

Bidder to follow the technical specifications

11 Cl 4.02.00 Page 223 of 1481

Type test to be conducted on Medium Voltage Busduct (Each rating)…………….

Please note that we shall submit only relevant type test reports conducted within last ten years from date of bid opening and no conduction of type test is envisaged by us.

Bidder to follow the technical specifications

Page 6: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

12 Cl 4.03.00 Page 215 of 1474/Cl 5.00.00 (f) Page 223 of 1481

Radiography Test (RT) shall be conducted as follow: 1. 2% on Enclosure (Circumferential and Longitudinal Butt weld joints) 2. 10% on Flexible conductor 10% radiography and 100% DP test on all site welded joints of busbar and enclosure.

Please note that Radiography Test is not applicable for MV Busduct. Hence the same shall not be conducted.

Bidder to follow the technical specifications

13 Annexure-A Sl. No.18 (e)/Page 225 of 1481

Material of insulator : Porcelain / Cast resin.

Please note that Insulator material shall be porcelain / cast resin / FRP type.

Bidder to follow the technical specifications

MV SWITCHGEAR - Technical Specification Vol II Part-B, Section - VI Part-B, Subsection-B-07(A) 33kV/11kV/6.kV6/3.3kV (HT Switchgear) 14 Cl 3.00.00(b)(2)

Page 253 of 1481 Temperature rise allowed for busbars shall be 40 deg.C for plain joints and 55 deg.C for silver plated joints.

Please note that Aluminium busbar with tempraure rise above ambient as per IEC 62271-200 i..e end temp of 115 deg C for Silver plated joint shalle be considered as per type tested OEM design.

Bidder to follow the technical specifications

15 Cl 4.01.00 (e)/Page 256 of 1481

The VT/relay compartments shall have degree of protection not less than IP 5X in

Please note that entire enclosure including relay / VT compartment will be IP 4X protection.

Bidder to follow the technical specifications

Page 7: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

accordance with…………………………

16 Cl 4.01.00 (f)/Page 257 of 1481

The Switchgear shall have an Internal Arc Classification………………….

Please note that inline with this clause we have already carried out Internal arc test. Test report for same shall be submitted during Detail engineering, we do not envisage any repetiiton of type tests

Bidder to follow the technical specifications

17 Cl 4.01.00 (o) /Page 258 of 1481

Suitable base frames made out of steel channels shall be supplied

Please note that Foundation frames shall be as per manufacturer standard shall be supplied.

Bidder to follow the technical specifications

18 Cl 4.06.00 (d)/Page 262 of 1481

Busbars and Insulators - All busbars shall be color coded

Please note that Busbars are HT sleeved and hence can not be color coded however stickers will be provided on rear cover for phase identification

Bidder to follow the technical specifications; colored HT sleeves shall be provided by the bidder.

19 Cl 4.08.00 (d)/Page 263of 1481

Painting Painting : We have offered panels made up of special material called "Alu Zinc". Alu Zinc is light in weight, has more strength, and extremely corrosion resistant compared to normal CRCA sheets and this does not require any surface treatment like powder coating. Panels shall be made up of Alu Zinc material except front doors & end covers which shall be painted sheet steel. We

Bidder to follow the technical specifications

Page 8: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

shall provide powder coated paint only for front doors and end covers, which shall be made of CRCA sheet. However, painting procedure and thickness shall be as per our standard procedure.

20 Cl 5.01.00 (b)/Page 269 of 1481

Type tests Please note that we shall submit only relevant type test reports conducted within last ten years from date of bid opening and no conduction of type test is envisaged by us.

Bidder to follow the technical specifications

21 Cl 5.03 (b)/Page 270 of 1481

Testing to observe compliance………………………………IP5X- It shall not be possible to insert……………

As per specification IP 5X for VT/Relay compartment to be verified by IP-5X: It shall not be possible to insert a thin sheet of paper under gaskets and through enclosure joints Same way compliance to IP 5X will be demonstarted during FAT

Point withdrawn by bidder

LV SWITCHGEAR, LT Busduct& NGR - Technical Specification Vol II Part-B, Spec No PE-TS-401-506-E001

Page 9: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

22 Cl 4.02.00 Page 379 of 1481

All switchboard frames and load bearing members shall be fabricated………………………………………………………………….or hot / cold-rolled sheet steel and 4.0 mm for non-magnetic material

Please note that the Doors &Covers ( Both internal & external surface ) material & painting as per NTPC technical specification. However , all the internal parts like Structure Frame, Modules, Base plate etc. shall be hot dip galvanised sheet steel of grade GSM 275 without any painting. This GSM 275 grade galvanised sheet steel has many advantages over conventional CR sheet steel. Kindly give us your acceptance for same.

Point withdrawn by bidder.

23 Cl 4.05.00 Page 380 of 1481

All switchboards shall be of dust-proof and vermin-proof construction and shall be provided with a degree of protection of IP: 5X as per IS/IEC 60947……………………………………..shall be provided with EPDM / Neoprene gaskets

Please note that the Degree of protection of complete switchboard shall be as per NTPC specification & in line with IEC 60529 as under. a) IP-54 upto 1600 Amps switchboard rating. b) IP-42 above 1600A switchboard rating. Separate IP rating for busbar chamber for switchboard is not envisaged / applicable. Further, we would like to clarify that during withdrawable of ACB modules, necessary IP 5X shall be ensured with Acrylic cover on the ACB door. However,

Point withdrawn

Page 10: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

in case of Non-ACB starter modules, doors are integral part of modules & hence, IP-5X shall be ensured with additional blanking plate which shall be supplied loose with adequate quantities for each size of the modules.

24 Cl 4.09.00 Page 380 of 1481

Switchboards shall be supplied with base frames made of structural steel sections, along with all necessary mounting hardware………………………. not obstruct the movement of doors, covers, with draw able modules etc.

As per our standard, switchboard consist of 50mm integral base frame which can be mounted directly on the finished floor suitable for welded/bolted arrangement. However it is recommended to mount on the additional 50mm base frame incase of false floor which shall be mutually discussed & agreed upon in the event of order.

Point withdrawn by bidder

Page 11: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

25 Cl 4.10.00 (a) Page 380 of 1481

Busbar Compartment- A completely enclosed bus bar compartment shall be provided for the horizontal and vertical busbars. Bolted covers shall be provided............................................. Auxiliary and power busbars shall be in separate compartments.

Please note that a completely enclosed busbar compartment shall be provided for Main busbar and vertical busbar . However for drawout design , Vertical busbar ( With air clearance of 20 mm between the phases ) shall be completely encapsulated using halogen free Arc Resistant plastic material with opening only for engaging the plugin contacts(IP2X) to achive fault free zone between Main Busbar and the individual outgoing feeder Main switching device . Arc fault free Zone reduces the chances of any fault in the non protected area of switchboard thereby results into highest safety of the operator and higher life to the switchboard. This is one of additional safety feature ia available in the drawout type MCC to ensure internal arc as per IEC 61641 for vertical busbars.

Point withdrawn by bidder

Page 12: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

26 Cl 4.10.00 (c) Page 381 of 1481

CABLE COMPARTMENT OR CABLE ALLEY A full-height vertical cable alley of minimum 250mm width shall be provided for power and control cables...............................furnish suitable plugs to cover the cable openings in the partition between feeder compartment and cablealley. Cable alley door shall be hinged.

Please note that a full height cable alley of 200mm or 400mm width shall be provided in MCC cubicle for power & control cable terminaltion as required based on the cable size. Cable termination located in cable alley shall be designed to meet the Form 4b constructions as per IEC 60439 standards. Please note that Form 4b-Type 7 is not as per the IEC standard & hence same is not applicable for IEC complaint switchgear (Refer Annexure-D of IEC60439 for information on Form of segregation).

Point withdrawn by bidder

27 Cl 6.03.00 Page 384 of 1481

All busbars shall be adequately supported by non-hygroscopic, non-combustible, track-resistant and high strength sheet …………………………...The busbar insulators shall be supported on the main structure.

As per our standard design the Busbar supports are common for phases and Neutral. Both Horizontal & vertical busbar system is tested for Short circuit withstand with same supports. Antitracking barriers are not envisaged as we have adequate clearance between phases & Neutral.

Point withdrawn by bidder

Page 13: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

28 Cl 6.04.00 Page 385 of 1481

All busbar joints shall be provided with high tensile steel bolts, belleville / spring washers and nuts, so as to ensure good contacts at the joints.

Please note that all busbar joints shall be provided with high tensile steel bolts coated with WSH-ESLOK- Thread locking compound ( SPOT - COATING ) with possibility of dismantled and retightened up to 10 times and still offering sufficient thread locking effect . “Dry-type” (polyamide) used for ESLOK (MNS standard) is an abrasion-resistant coating ofpolyamide on an exactly defined area (spot coating) of the thread. This guarantees an efficient and practically approved clamping protection against loosening. This arrangement in turn avoid any possibility of overheating of Busbar joints during operation of switchboard.

Point withdrawn by bidder

Page 14: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

29 Cl 7.00.00 Page 385 of 1481

AUXILIARY BUSBARS AND CONTROL TRANSFORMERS

Please note that Auxiliary bus is wire bus which are inter connected through terminals. We use maximum size of wire 6 sq mm copper from the safety angle, this is acceptable to all major customers/consultants . As the load meant for Auxiliary supply is lower range, 6 sq mm copper wire bus can withstand the auxiliary load. This concept is being used in all application and the same is accepted worldwide. Please confirm.

Point withdrawn by bidder

30 Cl 24.09.00 Page 401 of 1481

All connections from vertical busbars for individual modules above…………………………...colour coded wire insulation / tapes shall be provided.

All connection from the vertical busbar to switch/fuses in the modules with rating upto 400A shall be made with Double insulated halogen free cable as per MNS design. This shall minimize phase to phase and phase to earth fault and so as to avoid fault free zone.

Point withdrawn by bidder

31 Sec-D, Cl 1.15(b), Sheet 17 of 23 OR Page 474 of 1481

Enclosure inside : RAL 5012 (Powder coated)

Please note that Enclosure of NSPBD shall be matt black as per manufacturer standard for better heat absorbtion.

Point withdrawn by bidder

32 Sec-D, Cl 2.1, Sheet 17 of 23, OR Page 474 of 1481

Material of insulator : Porcelain / Cast resin.

Insulator material shall be porcelain / cast resin / FRP/ SMC type. Please confirm.

Point withdrawn by bidder

Page 15: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

CABLING, EARTHING & LIGHTING PROTECTION SYSTEMS (INSTALLATION), Doc No. PE–TS–401–507–E006, Vol II Part-B

33 Cl 8.2 of CABLING, EARTHING & LIGHTNING PROTECTION SYSTEMS (SUPPLY), PE-TS-401-507-E006

Only 70% of the Ordered Quantity shall be considered as confirmed quantity as indicated in Lot-I quantitites of BOQ and shall be released for manufacture along with LOI/PO.

Please note that quantity given in BOQ is considered as firm quantity for quoting and final ordering after the award of contract. Any addition/deletion beyond the quantity specified in BOQ shall be mutually discussed and agreed upon during detailed engineering/execution.

Point withdrawn by bidder

Battery & Battery Charger, Doc No. PE-TS-401-508-E001, Vol II

34 DC battery Clause 6.01 Page 926 of 1481

Bidder to furnish sizing calculations in support of the battery Capacity chosen by Bidder.

Please provide DC load list for battery sizing in addition to the load cycle provided in the specification. This supercedes the battery rating mentioned in the page 950 of 1481 clause no.1.00.00

Bidder to follow Specifications

35 DC battery Clause 7.1 Page 928 of 1481

The batteries shall meet the ‘Load Duty Cycle’ requirements under all site-operating conditions as specified. For the purpose of design an ambient temperature of 50 degree centigrade and relative humidity of 85% shall

Please note that Battery shall be sized on 10deg C higher temp. from the minimum electrolyte temp.

Bidder to follow Specifications

Page 16: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

be considered.

36 Annexure-II, Page 939 of 1481

Ageing Factor-1.25 (for Lead Acid Plante)

Please note that ageing factor for Lead Acid Plante is 1 as per IS. Please accept the same.

Bidder to follow Specifications

37 Battery Charger Cl.2.02.00 (j) Page 954 of 1481

Suitable filter circuits shall be provided in all the Chargers to limit the ripple content (peak to peak) in the output voltage to 1% irrespective of the DC load, even when they are not connected to a battery.

Please note that Suitable filter capacitor will be provided at the input side of the charger only.

Point withdrawn by bidder

DRY TYPE TRANSFORMER, Doc No. PE-TS-401-999-E001, Vol II Part-B 38 Sec-D, Cl 25 (a),

Page 1128 of 1481 HV side terminal details of dry type service transformer.

Please note that same shall be done by means of cable only.

Point withdrawn by bidder

39 Sec-D, Cl 34 (a), Page 1129 of 1481

Maximum current density (A/mm2)

Please note that maximum current density shall be limited upto 3A /mm2 for dry type service transformer.

Point withdrawn by bidder

OIL TYPE TRANSFORMER, Doc No. PE-TS-401-302-E001, Vol II Part-B 40 Data Sheet-A,

11/3.3 KV, Cl 19.0(b)/ Page 1152 of 1474

Flange throat for TPN nonsegregated Al Busduct / Cable box as applicable

Please note that same shall be SPBD/Cable box as applicable.

Point withdrawn by bidder

Page 17: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

41 Data Sheet-A, 11/0.433, Cl 20.0/Page 1159 of 1481

LV side system fault level : 45kA (rms)

Please note that the system fault level for LV side shall be of 50kA for 1 sec as per Cl No 3.3.2 of Spec Doc No PE-TS-401-506-E001 Vol II Part-BSec-D, Page 3 of 23 OR Page 453 of 1474. All the 0.433kV LV system including transformer and switchgears will be designed with the fault level of 50kA for 1 sec only. Please confirm.

Bidder to follow Specifications

QUALITY

42 General Type Test for All Equipment Please note that we have not considered conduction of type test for any equipment. This is applicable for all equipments.

Follow Technical Specifications and quote as per Price Schedule

43 Annexure-3-appendix-E (MOM-QA)

Remarks-SQPno.0000-999-QOE-S-002 , SQPno.0000-999-QOE-S-38, SQPno.0000-999-QOE-S-005 , SQPno.0000-999-QOE-S-19, SQPno.0000-999-QOE-S-18,SFQPno.-000-999-QOE-I-002, SFQPno.-000-999-QOE-I-003, SFQPno.-000-999-QOE-I-006

Request to please arrange for the copies of the referred documents.

Refer clause 2.3.22 of Scope of Enquiry (Part of Tech Specs – Vol 1)

Page 18: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

44 Cl.No.22.04.00 Bidder shall also furnish copies of the reference documents/plant standards/acceptance norms/test and inspection procedures etc

Please note that all reference documents cannot be shared, further reference documents (if submitted ,any) will be provided for reference only.

Point withdrawn by bidder

45 Cl.no.22.23.00 Procedure been followed for eliminating infant mortile components

Please inform the standards to be referred and equipment’s for which the same are applicable.

Point withdrawn by bidder

46 Cl.no.22.23.00 Elevated temperature test cycle Ambient cannot be maintained at 50 degc. Please inform sampling plan and equipment’s on which the referred test is proposed.

Point withdrawn by bidder

47 Cl.no.22.23.00 Burn in test cycle Please note that it will not be possible to offer the test on all the panels. Sampling may please be suggested.

Point withdrawn by bidder

48 Cl.no.25.03.00 15 days written notice Please note that Notice of 10 days may be considered.

Point withdrawn by bidder

49 Cl.no.25.05.00 When factory tests have been completed at contractors or subcontractors works,the project manager/inspector shall issue a certificate to this effect

Please note that Certificate issuance should be with two days of inspection.

Point withdrawn by bidder

Page 19: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

fifteen days after completion of test

50 Cl.no.4.02.01 Medium voltage busduct-type test

We do not envisage any type test conduction. Only reports will be submitted

Point withdrawn by bidder

51 Cl.no.4.03.00 Medium voltage busduct -Routine tests-Radiography test

Not applicable and not required for this range of busduct

Point withdrawn by bidder

52 Cl 5.00.00 MV busduct-test mentioned under b,c,e and f

For b,c,e reports can be submitted. F –not required for this rating of BD.

Point withdrawn by bidder

53 Cl.no.10.1,volume II—Lightning protection system

The following stage of manufacture and installation shall be stage inspected by purchaser or his authorized representative………

It is requested that only final finished product be inspected, stage inspection for this commodity is not desired.

Point withdrawn by bidder

Page 20: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

54 Cl.no.5.13.00-Dry type transformer

Type tests-sc ,noise level, zps, harmonic, temp rise ,LI with chopping. Routine test-PD, cap and tan delta

Type test-short circuit test, noise level ,harmonics measurement and LI with chopped wave are special tests as per IS 2026 .Similarly cap and tan delta is also special test

Point withdrawn by bidder

II. Price Schedule Vol II Part C Doc No. - PE-TS-401-999- E001; Rev 0 55 (2) MV Switchgear

Annexure-2, Sr No 7, BOQ CUM PRICE SCHEDULE OF MV SWGR (Supply)

Site modification charges:As per annexure- 2C

Please clarify the requirement and define the scope of work in detail.

Bidder to quote as Price Schedule

III. NIT 56 Cl 6.0 Due Date of

Offer Submission Date: 29.09.2014, 14:00 hrs We request to please grant us extension

for 4 weeks i.e. till 29.10.2014 for bid submission.

Not possible

57 Price Schedule, Data Sheet & Formats

General We request to please provide soft copies of: 1. Price Schedule (Vol II Part-C) 2. Data Sheet (As listed in Technical Specifications) 3. Annexures/Formats (Vol IIIE) This is required for necessary filling up of relevant information to be provided as part of techno-commercial bid ubmission.

Not possible

Page 21: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

Sr. No.

Volume/ Chapter

Clause No.

Page No. Bid Specification Clarifications Client's reply

58 Volume-III, General Technical Requirement, Section C, Part C

4.01.00 1 of 75 Bidders may note that this is a turnkey contract. Each of the plant shall be engineered and designed in accordance with the specification requirement.

We presume that customer has already engineered and designed the plant. Hence, we are proceeding as per the BOQ furnished by the customer. We do not envisage design and engineering of the same. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

59 Volume-III, General Technical Requirement, Section C, Part C

8.03.01 A)

6, 7 of 75

Basic Engineering Documentation

We presume that the Sl. No. i) to x) in the said clause is not applicable for the present tender and not in our scope. We envisage that our scope is as per the furnished BOQ only. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 22: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

60 Volume-III, General Technical Requirement, Section C, Part C

8.03.01 B)

7, 8, 9 of 75

Detailed Engineering Documentation

We presume that the Sl. No. iii) to v); vii) to xiv); xvii) to xxix) in the said clause is not applicable for the present tender and not in our scope. We envisage that our scope is as per the furnished BOQ only. We understand that the basic documents related to General layout and layouts for equipment and facilities will be furnished by the customer and vendor has to develop the same. However, type test reports will be furnished for the equipment in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

61 Volume-III, General Technical Requirement, Section C, Part C

8.03.03.01

11 of 75 Plant Handbook We do not envisage Process and Instrumentation diagrams in our scope. We presume that the items listed in Sl. No. i) and iii) to viii) are pertained to our scope only.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 23: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

62 Volume-III, General Technical Requirement, Section C, Part C

8.03.04 i)

14 of 75 Drawings shall include all installations and detailed piping layout drawings.

Layout drawings for all piping of 65 mm and larger diameter shall be submitted for review/ approval of Employer prior to erection.

We do not envisage the said clause in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 24: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

63 Volume-III, General Technical Requirement, Section C, Part C

19.01.00

19 of 75 All equipment/ piping/ pipe services are to be painted by the Contractor in

accordance with Employer's standard colour coding scheme, which will be furnished

to the Contractor during detailed engineering stage

We do not envisage the said clause in our scope. However, painting will be done only for the equipment pertaining to our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

64 Volume-III, General Technical Requirement, Section C, Part C

20.05.00

20 of 75 All piping shall be cleaned after shop assembly by shot blasting or other means approved by the Employer. Lube oil piping or carbon steel shall be pickled.

We do not envisage the same in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 25: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

65 General Kindly note that we do not envisage piping and its associated works in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical SpecS (Volume-I)

66 Volume-III, General Technical Requirement, Section C, Part C

26.01.00 f) 34 of 75

The Contractor during initial operation and performance testing shall conduct

vibration testing to determine the ‘base line’ of performance of all plant rotating equipment. These tests shall be conducted when the equipment is running at the base load, peak load as well as lowest sustained operating

condition as far as practicable.

We do not envisage the same as rotating equipment of the plant is not in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 26: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

67 Volume-III, General Technical Requirement, Section C, Part C

28.01.00 36 of 75

Training of Employer’s Personnel.

We do not envisage training of Sl. No. a) and c) to g) as the same are not in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

68 Volume-III, General Technical Requirement, Section C, Part C

28.03.00 36 0f 75

This shall cover all disciplines viz, Mechanical, Electrical, C&I , QA etc

We presume that the training from our end will be confined to Electrical discipline. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

69 Volume-III, General Technical Requirement, Section C, Part C

30.00.00 37 of 75

Noise level We do not envisage the said clause in our scope of work. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 27: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

70 Volume-III, General Technical Requirement, Section C, Part C

34.00.00 39 of 75

Instrumentation and Control

We presume that the same is not applicable for our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

71 Volume-III, General Technical Requirement, Section C, Part C

35.00.00 40 of 75

Electrical Noise Control

The electrical noise control for electrical equipment will be as per OEM’s practice. Please confirm.

Follow Technical Specifications

72 Volume-III, General Technical Requirement, Section C, Part C

36.00.00 40 of 75

Surge protection for Solid state Equipment

We presume that the same is not applicable for our scope. Please confirm.

Follow Technical Specifications

Page 28: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

73 Volume-III, General Technical Requirement, Section C, Part C

37.00.00 40 of 75

Instrument Air compressor

We presume that the same is not applicable for our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

74 Volume-III, General Technical Requirement, Section C, Part C

38.00.00 40 of 75

Tapping Points for Measurements

We presume that the said clause is not applicable for our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

75 Volume-III, General Technical Requirement, Section C, Part C

39.00.00 41 of 75

System Documentation

We presume that the same is not applicable for our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 29: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

76 Volume-III, General Technical Requirement, Section C, Part C

39.01.00 41 of 75

Bill of material (instrument list) for all C&I equipment/ devices shall be furnished by the bidder in standard formats as approved by the Employer.

We presume that the said clause is not applicable for our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

77 Volume-III, General Technical Requirement, Section C, Part D

33.02.00 16 of 51

Commissioning Documentation

We presume that the said clause is only confined to the equipments in our scope. Please confirm.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

78 Volume-III, General Technical Requirement, Section C, Part D

46.00.00, 47.00.00, 48.00.00, 49.00.00, 50.00.00, 51.00.00

125 of 1474

The said clauses are strikethrough

With reference to the page no. 125 of 1474, we understand that the said clauses are not in our scope even though when some of the clauses are not marked strikethrough in the respective pages. Please confirm.

Follow Technical Specifications

Page 30: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

79 Scope of supply and services

2.04.02 and 6.01.00

196 of 1474 and 197 of 1474

The quantities of Medium Voltage Busducts of different ratings, 90 deg.

Bends, T-connection, phase cross over and termination at Switchgear and transformer end are given in BOQ at clause 4.02.00. The bid price shall be based on the unit rate for busduct length measured from matching flanges following the centre line of the busduct. The length shall be measured from matching flange of Generator, Generator

Transformer and other terminal equipments

As per the clause 2.04.02, we understand that the bidder shall follow the quantity of MV busduct of different rating along with its associated accessories.

As per the clause 6.01.00 and also as per the furnished layout of SPBD (page no. 200 of 1474), we understand that the length of SPBD shall be measured.

In view of the contradiction between the said clauses, we are proceeding with the BOQ furnished by the customer for both SPDB and support structures. Please confirm.

Follow Price Schedule & Technical Specification

Page 31: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

80 a. Electrical SLD for Auxiliary Power distribution drg no. PE-DG-401-565-E001

b. SLD for 11kV Switchgear metering and protection drg no. PE-DG-401-505-E001

1. Rating of Unit transformer 6A, 6B;

2. Rating of standby transformer OBAT01

1. The rating of unit transformer is mentioned as 40/50MVA as per point no. a and same is indicated as 40/45MVA as per the point no. b

2. The rating of standby transformer as per a. is 40/50MVA and same as per b. is 40/45MVA.

Kindly clarify the above.

Same shall be finalized during detailed Engineering. Presently consider 40/50MVA

81 a. Electrical SLD for Auxiliary Power distribution drg no. PE-DG-401-565-E001

b. SLD for 11kV Switchgear metering and protection drg no. PE-DG-401-505-E001

Voltage rating of standby transformer OBAT01

The voltage rating of Standby transformer as per a. is 400/11.5kV and same is mentioned as 21/11.5kV as per b.

Please clarify.

Same shall be finalized during detailed Engineering. Presently consider 400/11.50KV

Page 32: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

82 Section C, part B. PE-TS-401-506-E001;

Section VI, part B, subsection B-08

a. 14.10

b. 4.05.00

359 OF 1474and 10 of 58

Degree of Protection for LV Switchboard

As per the point no. a, the degree of protection for compartments and bus bar chambers up to 1600A shall be IP 52 and above 1600A shall be IP 4X and whereas point no. be calls for degree of protection to be IP 5X upto 1600A. Kindly clarify.

Clause no.4.05.00 shall prevail.

83 Section C, part B. PE-TS-401-506-E001;

Section VI, part B, subsection B-08

a. 13.2

b. 11.01.00

352 of 1474 and 20 of 58

a. The switchgear shall be draw out type.

b. MCCB shall be fixed type or part of withdrawable feeder module.

Kindly clarify the contradiction between the said clauses.

Follow Technical Specifications

Page 33: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

84 Section D, part B. PE-TS-401-506-E001;

Section VI, part B, subsection B-08

a. 3.01.01 4)

b. 3.3.2

4 of 58 and 453 of 1474

Fault Level of LV switchgear

The fault level of LV switchgear is mentioned as 45kA as per the point no. a whereas the same is given as 50kA as per the point no. b

Please clarify.

Fault Level of LV switchgear : 45 kA (rms) to be considered.

85 Spec. no. PE-TS-401-508-E001, Part B

Annexure-II 932 of 1474

Factors to be considered for battery sizing. Aging factor1.25 for Lead acid Plante and 1.25 for Ni-Cd. Bidder has to take ageing factor (margin) in their sizing and selection of both lead acid and Ni-Cd battery.

Please note that the ageing factor is not applicable for Lead acid Plante battery as perIEEE-485.

Hence, we do not envisage ageing factor. However, we will envisage design margin for both Lead acid Plante and Ni-Cd battery.

Follow Technical Specifications

Page 34: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

86 Vol-II, Part-B, Section C, Spec. no. PE-TS-401-510-E001

6.01, 6.03 and 6.06

987, 988 of 1474, 987 of 1474

The contractor shall carry out the type tests as listed in this specification on the equipment to be supplied under this contract.

In case the contractor has already conducted such specified type test(s), he may submit during detailed engineering the type test reports to the owner for waival of conductance of such type test(s).

In line with the mentioned clause (6.03), we will submit the type test certificates for GCB.

Follow Technical Specifications

Page 35: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

87 Vol-II, Part-B, Section C, Spec. no. PE-TS-401-510-E001

7.00 vii) 988 of 1474

Low frequency withstand voltage tests on GCB

Please note that the conduction of mentioned test is based on manufacturer’s concurrence.

Follow Technical Specifications

88 Vol-II, Part-B, Section C, Spec. no. PE-TS-401-510-E001

6.01 995 of 1474

Validity period of type test reports is 10 years

Request you to kindly note that the equipment which is having the type test certificate beyond 10 years is also said to be valid and acceptable, so long as there is no change in design.

Follow Technical Specifications

89 Vol-II, Part-B, Section C, PE-TS-401-302-E001;

SLD drg. No. PE-DG-401-565-E001

Sl. No. 1 a) to e);

Table 3 of SLD

1131 of 1434

Scope of supply and services of oil type transformers

As per the BOQ of Oil type transformers, we understand that Generator Transformer, Unit Auxiliary Transformers, CHP Aux and AHP Aux transformers are not in our scope. However, the same are indicated in the tender SLD. Please clarify.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I)

Page 36: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

90 Vol-II, Part-B, Section C, PE-TS-401-302-E001;

SLD drg. No. PE-DG-401-565-E001

Sl. No. 1 b) and c)

Table 3 of SLD

1131 of1474

Scope of supply and services of oil type transformers

As per the BOQ of Oil type transformers, the quantity of 1.6MVA & 2MVA transformers are mentioned as 2 and13 nos. respectively whereas the quantity of same seems to be 1.6MVA-10 nos. and 2MVA-9 nos. as per the SLD. Kindly clarify the contradiction.

As per Price Schedule

91 VoI I 2.4 18 of 1474

EXCLUSIONS: All building structure, all civil works other than grouting and fixing to the equipment structure.

NBPPL to confirm the scope of foundation bolts required for fixing the equipment.

Follow Scope of Enquiry Part of Technical Specifications (Volume-I); foundation bolts in the scope of bidder.

Page 37: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

92 VoI I 2.5 19 of 1474

VARIATION OF QUANTITIES MAY BE TO THE EXTENT OF +/-30% OF TOTAL CONTRACT VALUE. REFER GENERAL CONDITIONS OF CONTRACT FOR FURTHER DETAILS.

NBPPL to consider limiting quantity variation to +/- 15 %

Follow Technical Specifications

Page 38: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

93 VOLUME II PART-B

18 232 of 1474

All miscellaneous items such as disconnecting links, flexibles, shorting bars, hardwares, conduit for wiring, marshalling box, CTs and PTs wiring through conduit, earthing materials, bus bar fish plates etc. are part of bus duct installation. Hence separate breakup quantity is not given in BOQ.

NBPPL tp provide plant SLD to understand and incorporate the required / necessary components like CT, PT, JB's etc.

Provided in Technical Specifications

94

Technical specification – General technical requirement

8.03.01 5 of 57

A) Basic Engineering Documentation and

B) Detailed Engineering Documentation

Document submission list under this clause are not relevant to the electrical package scope of the tender. NBPPL to clarify.

Follow Scope of enquiry as part of Technical Specifications

Page 39: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

95 Vol – II, Section C

1.00.00 943 of 1474

A. CHARGER SHALL BE SUITABLE FOR NI-CD BATTERY OF 920AH CAPACITY.

OR

B.CHARGER SHALL BE SUITABLE FOR LEAD ACID PLANTE BATTERY OF

2035AH CAPACITY.

Design of Battery charger will be considered as given. NBPPL to confirm as no load list is provided.

Charger rating shall be as per Price Schedule and datasheet A

Page 40: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

96

Vol – II, Section C : Generator Circuit Breaker

14.00 991 of 1474

TRAINING OF ENGINEERS

Bidder shall provide training for a maximum of six (6) engineers from NBPPL/ultimate customer at works, training centre etc. The training shall also include application, layout, design, construction, operating principle, operating mechanism, local control panel, operation, maintenance, site inspection, erection, site testing, spares etc. of GCB.

GCB is imported item and manufactured at works in Europe. NBPPL to clarify on the training need aboard.

Follow Technical Specs

Page 41: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

97 Vol – II, Section B : EPABX

7.1.2 1259 of 1474

Analog subscriber lines: 512 no(location will be decided by site/owner)

NBPPL to specify about the areas/buildings where the telephone equipment will be installed. As cables and conduits will be estimated accordingly.

Will be Provided during detailed Engineering. Presently follow Price Schedule & Optional Price Schedule

98 Vol – II, Section B : EPABX

7.1.3 1259 of 1474

Desktop/wall mounted telephones-250 no’s

NBPPL to specify separately about the total no of Desktop and wall mounted telephones required.

Will be Provided during detailed Engineering. Presently follow Price Schedule & Optional Price Schedule

99 Vol – II, Section B : EPABX

NBPPL to specify if any specific no of weatherproof /flame proof type of telephone required.

Follow Technical Specifications

100

Vol – II, Section B : EPABX

NBPPL to specify about approved vendor list for EPABX SYSTEM.

Provided at Vendor List(A5) of Technical Specifications Volume-I

Page 42: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

101

Vol – II, Section B : EPABX

NBPPL to provide an Air-conditioned, dust free space for the exchange and its main accessories

Follow Technical Specifications

102

Vol – II, Section C : PA SYSTEM

NBPPL to specify about the areas/buildings AS cables and conduits will be estimated accordingly.

Shall be provided during detailed engineering. Bidder to quote as per Price Schedule

103 GCB Clause No. 2.11

Page 14 of 59

Natural Cooling

Please clarify and confirm as we do not have natural cooling in this range. We have supplied Forced cooling GCB to BHEL & NTPC in the past, hence we request to please accept Forced Cooling breakers.

Natural Cooling is applicable for Generator Bus-duct. Bidder to comply with Technical Specifications.

Page 43: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

104 GCB Clause No. 6.00

Page 15 of 59

Type Tests

We wish to inform you that 10 year clause is not applicable to GCB as the design of the GCB has not been changed since the conduction of the Type test. And moreover there is no change in the type test requirement in the standard also. Hence all our Type tests are still valid for the similar rating. Further it is not feasible for conducting any type test for 1 breaker. Hence we do not envisage any conduction of type test as all our type tests are valid and in line with the standard.

Follow Technical Specifications

Page 44: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

105 GCB Annexure B Page 21 of 59

Quality Plan

We wish to inform you that our QAP is fully complied to IEEE standards. Therefore we are unable to follow any other QAP. Further we wish to inform you that for GCB stage inspection is not applicable. We can conduct only Final acceptance Test in line with the standards. No stage inspection will be done. Further we also wish to inform you that chemical composition of any of the equipment will not be shared as this is confidential for us. Please see our QAP for your further actions.

Follow the Technical Specifications

106

Vol – II B, Section D : PA SYSTEM

1.6 of section 'D'

1068 of 1474

The clause says that BOQ has been given in section 'C'. But we do not find any BOQ in section C. NTPC to clarify the same.

Follow Price Schedule

Page 45: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

107

Vol – II B, Section C & D : PA SYSTEM

Clause 7.0 of section 'C' & clause 3.6.3 of section 'D'

1042 of 1474 & 1070 of 1474

Clause 7.0 of section 'C' says that enclosure with transparent glass door which can be open through number pad locked only. Also clause 3.6.3 of section 'D' says above the access code of the person does it means that the stations with access control system. NTPC to clarify that. Also Clause no. 3.6.3 - ask for access code of the person, the PA system operation will be restricted to the person who know the access code & the person who don't know the access code cannot use the system.

Clause No:7.0 of Section C will prevail

Page 46: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

Sl. No.

Volume Clause No.

Clause Ref. NBPPL's DESCRIPTION AS SPECIFIED

Bidder's CLARIFICATION NBPPL's REPLIES

108 General Technical Requirements

4.00.00 Pg 1 of 75

COMPLETENESS OF FACILITIES

Bidders may note that this is a turnkey contract. Each of the plant shall be engineered and designed in accordance with the specification requirement. All engineering and associated services are required to ensure a completely engineered plant shall be provided. All equipments furnished by the Contractor shall be complete in every respect, with all mountings, fittings, fixtures and standard accessories normally provided with such

We understand that this contract is a Bill Of Quantity based contract which comprises of Supplies & Services identified in the Tender Documents as well as in Price Schedule format provided by NBPPL.And any necessary inputs required for other departments like Mechanical, Civil, C & I will be provided for our supplied equipments only. Any Additional items not covered under the Bill of Quantity and required for completion of Power Plant shall be reimbursed by NBPPL.

Bidder to follow the Scope of Enquiry (part of Tech Specs- Vol 1)

Page 47: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

equipment and/or those needed for erection, completion and safe operation of the equipment and for the safety of the operating persnnel, as required by applicable codes, though they may not have been specifically detailed in the respective specifications, unless included in the list of exclusions.

109 General Technical Requirements

5.06.00 CODES & STANDARDS

Two (2) English language copies of all national and international codes and/or standards used in the design of the plant and equipment shall be provided by the Contractor to the Employer within two

Codes and standards can not be duplicated. However we shall provide the list of the codes / standards related to the equipment supplied by us.

Bidder to follow the tech specs

Page 48: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

calendar months from the date of the Notification of Award.

110 General Technical Requirements

7.02.00 MAINTENANCE AND AVILABILITY CONSIDERATIONS

Lifting devices i.e. hoists and chain pulley jacks ,etc. shall be provided by the contractor for handling of any equipment or any of its part having weight in excess of 500 Kgs during erection and maintenance activities.

Any necessary lifting device like chain pulley, jacks etc shall be considered during erection/execution and the same shall be taken back once the job is completed.

Lifting device like chain pulley, electric hoists etc shown in the layout drawing shall be used for the maintence purpose of the equipmen & shall be erected & commissioned to customer.However any other device used for sole erection purpose of the equipment can be taken back once the job is completed.

111 General Technical Requirements

8.00.00 8.01.00 to 8.05.03

DOCUMENTS, DATA AND DRAWINGS TO BE FURNISHED BY CONTRACTOR

Basic engineering documentation Detailed engineering documents Instruction manuals Operation & maintenance manuals Plant handbook and project completion

This clause shall be applicable only for those equipments supplied by us under this package.

As per Scope of Enquiry part of Technical Specifications (Volume-I)

Page 49: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

report Drawings Engineering information submission schedule

112 General Technical Requirements

9.02.00 TECHNICAL CO-ORDINATION MEETING

The Contractor should note that Time is the essence of the contract. In order to expedite the early completion of engineering activities, the Contractor shall submit all drawings as per the agreed Engineering Information Submission Schedule.The drawings submitted by the Contractor will be reviewed by the Employer as far as

We request NBPPL to delete the wording "Time is the essence of the contract"

Follow Technical Specifications

Page 50: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

practicable within three (3) weeks from the date of receipt of the drawing .The comments of the Employer shall then be discussed across the table during the above Technical Co-ordination Meeting (s) wherein best efforts shall be made by both sides to ensure the approval of the drawing

113 General Technical Requirements

13.00.00 LUBRICANTS, SERVO FLUIDS AND CHEMICALS

As far as possible lubricants marketed by the Indian Oil Corporation shall be used. The variety of lubricants shall be kept to a minimum possible

We presume this is not related to eBoP scope of work.

Follow Technical Specifications

Page 51: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

114 General Technical Requirements

28.07.00 TRAINING OF EMPLOYER'S PERSONNEL

In all the above cases, wherever the training of Owner's personnel is arranged at the works of the manufacturer's, it shall be noted that the lodging and boarding of the Owner's personnel shall be at the cost of Bidder. The Bidder shall make all necessary arrangements towards the same.

The Cost for lodging and boarding of the Owner's personnel shall be borne by NBPPL only.

Follow Technical Specifications

115 General Technical Requirements

TECHNICAL SPECIFICATION SECTION - VI PART-C

General Technical Requirments

We understand that this General Technical Requirement is for reference purpose only and all related clauses pertaining to electrical equipments shall only be applicable.

Follow Scope of enquiry as part of Technical Specifications

Page 52: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

116 MV SWITCHGEAR

TECHNICAL SPECIFICATION SECTION - VI PART-B

General Query Please furnish the type of cable entry for MV panels (either Top Entry or Bottom)

Bottom Entry for Cables

117 II (Part B) Section C

Clause No. 6.04 Pg no.6 of 12

GCB TYPE TEST

Further the Contractor shall only submit the reports of the type tests as listed in "LIST OF TESTS FOR WHICH REPORTS HAVE TO BE SUBMITTED" and carried out within last ten years from the date of bid opening. These reports should be for the test conducted on the equipment similar to those proposed to be supplied under this contract and the test(s)should have been either conducted at an independent laboratory or should

We wish to inform you that 10 year clause is not applicable to GCB as the design of the GCB has not been changed & moreover there is no change in the type test requirement in the respective standard also. Further it is not feasible for conducting any type test for 1 breaker. Hence we do not envisage any conduction of type test as all our type tests are valid and in line with the standard.

Follow Technical Specifications

Page 53: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

have been witnessed by a client. However if the contractor is not able to submit report of the type test(s) conducted within last ten years from the date of bid opening, or in the case of type test report(s) are not found to be meeting the specification requirements, the contractor shall conduct all such tests under this contract at no additional cost to the owner either at third party lab or in presence of client/owners representative and submit the reports for approval.

Page 54: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

118 II (Part B) Section C

Clause No. 9 Pg no.9 of 12

GCB QUALITY PLAN

QUALITY PLAN We wish to inform you that our QAP is fully complied to IEEE standards. Therefore we are unable to follow any other QAP. Further we wish to inform you that for GCB stage inspection is not applicable. We can conduct only Final acceptance Test in line with the standards. No stage inspection will be done. Further we also wish to inform you that chemical composition of any of the equipment will not be shared as this is confidential for us. We shall furnish manufacturer's standard QAP with our bid.

Follow Technical Specifications

Page 55: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

119 GENERAL GENERAL GENERAL GENERAL We request NBPPL to provide the bidders with editable version of Price Schedule & Technical Datasheet in MS excel Format/ MS word inorder to enable us to provide the same as per NBPPL requirements at the earliest.

Not possible

Page 56: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

Sr. No.

Doc. No. / Volume

Clause No.

Page no.

Bid Specification Stipulation

Statement of clarification sought

NBPPL's Remark

120 PE-TS-401-999-E001 / I

2.3.7 16 of 1481

During the course of erection, testing and commissioning Electrical/ C&I work certain rework / modification / rectification / repairs / fabrication etc. may be necessary on account of feedback from other power stations or units already commissioned and/ or units under erection and commissioning and also on account of design changes and manufacturing incompatibilities and site operation / maintenance

Please note that, we have considered our scope of work for Electrical packages as per tender BOQ / Price schedule and Detailed drawings to be furnised by NBPPL. Also note that, any rework /modification / rectification / fabrication / repairs etc, shall be deemed as extra works to be compensated to the L&T, based on the rates to be discussed and mutually agreed.

Follow Scope of Enquiry as part of Technical Specifications

Page 57: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

requirements. BIDDER shall carryout such rework /modification / rectification / fabrication / repairs etc, promptly and expeditiously and the same shall be deemed to be part of the scope of work.

121 PE-TS-401-999-E001 / I

2.4 19 of 1481

EXCLUSIONS: All building structure, all civil works other than grouting and fixing to the equipment structure.

Please note that, we have considered civil / Excavation works as mentioned in the tender BOQ / Price schedule. Apart from

Follow Technical Specifications

Page 58: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

ECC / Part-D

43.10.00 159 of 1481

Excavation The contractor shall take all necessary measures during excavation to prevent the hazards of falling or sliding material or article from any bank or side of such excavation which is more than one and a half meter above his footing by providing adequate piling, shoring, bracing etc. against such bank or sides.

that we have not considered any civil works in our scope.

Follow Technical Specifications

Page 59: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

122 PE-TS-401-999-E001 / I

2.5 19 of 1481

QUANTITY VARIATION CLAUSE ADDITION/ DELETION OF QUANTITIES SHALL BE APPLICALBE AT THE QUOTED PRICES. THE UNIT RATE OF SUPPLY AND E&C OF ALL EQUIPMENTS AND SERVICES QUOTED BY THE BIDDERS SHALL BE FIRM FOR A VARIATION OF QUANTITIES TILL COMPLETION OF 1X500 MW FGUTPP (STAGE-IV) PROJECT. VARIATION OF QUANTITIES MAY BE TO THE EXTENT OF +/-30% OF TOTAL CONTRACT VALUE. REFER GENERAL CONDITIONS OF CONTRACT FOR FURTHER DETAILS.

We request you to considered the quantity variation within +/- 10% of total value.

Please refer GCC Clause No: 6.1

Page 60: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

123 GTR / Part-C 8.03.01 54 of 1481

A) BASIC ENGINEERING DOCUMENTATION B) DETAILED ENGINEERING DOCUMENTS

Please note that, these clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

124 GTR / Part-C 8.00.00 53 of 1481

All engineering and technical services required to ensure a completely engineered plant shall be provided in respect of mechanical, electricaland power systems, control & instrumentation, civil & structural works.

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

Page 61: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

125 GTR / Part-C 13.01.00 65 of 1481

LUBRICANTS, SERVO FLUIDS AND CHEMICALS 13.01.00 The Bidder’s scope includes all the first fill and one year's topping, requirements of consumables such as oils, lubricants, servo fluids, gases essential chemicals etc. Consumption of all these consumables during the initial operation and final filling after the initial operation shall also be included in the scope of the Bidder. Bidder shall also supply a quantity not less than 10% of the full charge of each variety of lubricants, servo fluids,

Please note that, the lube oil shall be applicable only for Emergency DG set and not for fuel oil.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

Page 62: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

gases, chemicals etc. used which is expected to be utilised during the first year of operation. This additional quantity shall be supplied in separate Containers.

126 GTR / Part-C 25.11.00 79 of 1481

This shall include but not be limited to the following. a) System accuracy tests of DDCMIS for the various type of inputs identified in Part-B. b) Loop reaction time for sample loops/ logics. c) SOE functionality

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

Page 63: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

tests. d) Server changeover.

127 GTR / Part-C 25.12.01 80 of 1481

Based on NTPC inputs, the Contractor shall prepare and submit typical implemented scheme in their system ( Control system & HMI) on sample basis.

Please note that, these clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

128 GTR / Part-C 33.00.00 86 of 1481

JUNCTION BOXES The junction boxes shall be made of minimum 2 mm thick sheet steel. Gland plates shall be removable type and made of 3 mm thick sheet steel. The boxes shall be provided with

As per tender specification PE-TS-401-507-E006 / C, cl.no. 4.5 and page no. 539 of 1481, the junction boxes are mentioned as FRP. Kindly confirm, whether we have to consider FRP or Sheet

Clause No: 33 of GTR will be applicable

Page 64: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

detachable cover or hinged door with captive screws. Top of the box shall be arranged to slope towards the rear of the box. The box shall be hot dip galvanised and shall be provided with suitable neoprene gaskets to achieve requisite degree of protection.

steel.

129 GTR / Part-C 39.00.00 89 of 1481

SYSTEM DOCUMENTATION The Bidder shall provide drawings, system overview & description, hardware/software details, technical literature, functional & hardware schemes, bill of material, parts list, interconnection

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

Page 65: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

diagrams, data sheets, erection/ installation/ commissioning procedures, instruction/ operating manuals, etc. for each of the C& I system / sub-systems/ equipment supplied under this package.

130 GTR / Part-C 39.01.00 89 of 1481

Bill of material (instrument list) for all C&I equipment/ devices shall be furnished by the bidder in standard formats as approved by the Employer.

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

131 ECC / Part-D

26.03.00 145 of 1481

Water. Contractor shall make all arrangements himself for the supply of construction water as well as potable water for labour and other personnel at the

We assume that, NBPPL will provide the water at free of cost.

Follow Technical Specifications

Page 66: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

worksite/colony.

132 ECC / Part-D

45.00.00 165 of 1481

FOUNDATION DRESSING & GROUTING FOR EQUIPMENT/ EQUIPMENT BASES

Please note that, we have considered civil works as mentioned in the tender BOQ / Price schedule. Apart from that we have not considered any civil works in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

133 ECC / Part-D

51.04.00 173 of 1481

Equipment Installation j.Installation of Field Mounted Instruments and Devices

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

134 ECC / Part-D

51.04.00 173 of 1481

(2.) The removal of control and instrument equipment in order to allow bench calibration, if required, and the re-

Please note that, this clauses are not applicable to the package under consideration and hence not included in

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

Page 67: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

installation of the said equipment after calibration shall also be included as a part of the work under these specifications.

our scope.

135 GTR / Part-C

25.00.00 187 of 1481

Associated document for Quality Assurance programme 25.10.04 Manufacturing Quality Plan Format No. : QS-01-QAI-P-09/F1-R1 enclosed at Annexure-VI. 25.10.05 Field Quality Plan Format No.: QS-01-QAI-P-09/F2-R1 enclosed at Annexure-VII.

Please note tha mentioned drawings are not enclosed in the tender document, kindly provide the same for our review.

Follow QAP

Page 68: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

136 GTR / Part-C

25.11.00 187 of 1481

This shall include but not be limited to the following. a) System accuracy tests of DDCMIS for the various type of inputs identified in Part-B.

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

137 GTR / Part-C

25.12.00 188 of 1481

Based on NTPC inputs, the Contractor shall prepare and submit typical implemented scheme in their system ( Control system & HMI) on sample basis. The typical cases to be covered shall include but not be limited to the following.

Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.

Follow Scope of Enquiry as part of Technical Specifications(Volume-I)

138 PE-TS-401-505-E002 / C

4.02.01 205 of 1481

Busdut Support structure considers owners Load 400kg /Meter

Since there is the controversy between these clauses. Kindly confirm, whether we

Follow Technical Specifications

Page 69: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

PE-TS-401-505-E002 / C

3.05.02 220 of 1481

Busduct support structure designed to take care of Employers cable tray loadof 100 kg / Meter

have to consider 100kg/mtr or 400kg/mtr.

Follow Technical Specifications

139 PE-TS-401-505-E002 / C

Annex-C 209 of 1481

Busduct Elevation 3.5 Mtr in outdoor Transformer Yard

Since there is the controversy between these clauses. Kindly confirm, whether we have to consider 3.5mtr elevation or 6mtr elevation.

Elevation shall be decided during detailed engineering. Bidder to quote as per Price Schedule.

PE-TS-401-505-E002 / C

6.04.00 206 of 1481

MV Busduct shall run in outdoor transformer yard above 6 Mtr Elevation

Elevation shall be decided during detailed engineering. Bidder to quote as per Price Schedule.

140 PE-DG-401-505-E001 / -

-- 302 of 1481

Unit Transformer = 6A capacity 40/45 MVA

Since there is the controversy between these clauses. Kindly confirm, whether we have to consider 45MVA or 50MVA for considering the incomer in MV switchboards.

Bidder to quote as per Price Schedule and Optional Price Schedule

PE-TS-401-505-E001 / A

4.01.00 245 of 1481

Unit Transformer 50 MVA

PE-DG-401-505-E001 / -

303 of 1481

Standby Transformer 40/45 MVA,21/11.5kv

PE-TS-401-505-E001 / A

4.01.00 245 of 1481

Standby Transformer 50 MVA, 400/11.5/11.5 kv

Page 70: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

141 PE-TS-401-506-E001 / C

13.5 359 of 1481

All motors 30kW and above & less than 110KW shall be provided with CT and Multifunction meters with RS485/4-20mA outputs for remote metering in DCS.

Please note that, we have considered the feeder as per tender BOQ / Price schedule. Also note that, the RS485/4-20mA provision is available in MFM, however the required interconnection cables between the MFM and Purchaser DCS is not in our scope.

Cable is in Bidder's Scope

142 PE-TS-401-506-E001 / C

13.2 362 of 1481

a. Ethernet switches and cables for connection of LT relays in LT Swgear.

As per tender BOQ/Price schedule, the quantity of ethernet switch is not mentioned, kindly clarify whether we have to supply or not. If we have to supply provide the quantity.

Follow Technical Specifications and Price Schedule

143 PE-TS-401-506-E001 / C

13.2 362 of 1481

b. FO cable inbetween HT panel & LT panel

Please provide distance and the specification of FO cable.

Bidder to quote as per Price Schedule and Optional Price Schedule

Page 71: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

Technical specification / B

457 of 1481

FO link between LV board & Data Concentrator

144 PE-TS-401-506-E001 / C

13.2 362 of 1481

c. Programming Ethernet switches shall be part of vendor.

As per tender BOQ/Price schedule, the quantity of ethernet switch is not mentioned, kindly clarify whether we have to supply or not. If we have to supply provide the quantity.

Follow Technical Specifications and Price Schedule

Technical specification / B

18.00 & 19.00

397 of 1481

Fibre Optic Cables & Ethernet switches

145 Technical specification / B

6.01.00 384 of 1481

All Busbar and jumber connection shall be of high conductivity Al alloy/ CU of adequate size.

We have considered aluminium conductor for the same.

Follow Technical Specifications

Page 72: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

146 PE-TS-401-507-E006 / C

13.6 661 of 1481

IMPORTANT: – For all items supplied and installed as per Supply and Installation part of this specification as part of this contract, any minor left out items / non–quantifiable accessories, site consumables ,related services at site for preparing the materials for installation, etc, whether specially mentioned in the specification or not, shall be deemed to be included as part of bidder’s scope of installation.

Please note that, we have considered our scope of work for Electrical packages as per tender BOQ / Price schedule and Detailed drawings to be furnised by NBPPL. Appart from that we have not considered any other installation works in our scope

Follow Scope of Enquiry as part of Technical Specifications

Page 73: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

147 PES-507-11 / D

1.2 721 of 1481

The installation work shall generally be carried out as per purchaser’s drawings and documents. As part of cable installation, the scope shall also include exact detailing / adaptation of the system to specific site needs, to Engineers approval.

We presume that, the purchaser's detailed cable tray routing drawings cover all the following details: 1. Route identification with sectional views of the tray supports for plant overall cable tray routing as also all process buildings, sub-stations, Electrical rooms. 2. Cable schedule clearly indicating the route details for each cable (Power, Control and C&I cables). 3. The drawings shall not only cover main tray routes but also covers branch tray routes. 4. The tray supports shall cover sizes of

Follow Technical specifications

Page 74: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

structural steel members. 5. Areawise BOQ of trays and tray supports shall be clearly indicated on each of the drawings.

148 PES-507-11 / D

1.2 721 of 1481

The installation work shall generally be carried out as per purchaser’s drawings anddocuments. As part of cable installation, the scope shall also include exact detailing /adaptation of the system to specific site needs, to Engineers approval.

We presume that, the purchaser's detailed earthing and lightning protection drawings cover all the following details:1. Detailed constructional drawing of the earthing pits and their location on the detailed plot plan.2. Clear indication of route and size of the main earthing conductors.3.Areawise

Follow Technical Specifications and Price Schedule

Page 75: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

BOQ of earthing & lightning conductors and its accessories shall be clearly indicated on each of the drawings.4. Clear indictaion of interconnections between earth grid of different areas/buildings and the routes.5.Clear indication of location of equipment to be earthed, size of its earthing conductor, their routes and location of earthing JB's ( as applicable).

149 PES-507-11 / D

1.1 721 of 1481

h) Minor civil works. Please note that, we have considered civil / Excavation works as mentioned in the tender BOQ / Price schedule. Apart from that we have not

Follow Technical Specifications and Price Schedule

Page 76: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

considered any civil works in our scope.

150 PES-507-11 / D

3.2.9 726 of 1481

Cable trays shall be supported on ISA 50x50x6mm MS/GI brackets. Brackets shall be welded to steel plate inserts in the trenches/tunnels or supporting channel angle/inserts in other areas.

We presume that, all the tray supports are welded in insert plates, kindly confirm.

Follow Technical Specifications

151 PES-507-11 / D

3.7.24 731 of 1481

Wherever specific cable routes are not shown in cable schedules cables shall be laid as directed by Engineer.

Please note that, we have considered our scope of work for Electrical packages as per tender BOQ / Price schedule and Detailed drawings to be furnised by NBPPL. Also note that, any rework /modification / rectification / fabrication / repairs

Follow Scope of enquiry along with Technical Specifications

Page 77: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

etc, shall be deemed as extra works to be compensated to the L&T, based on the rates to be discussed and mutually agreed.

152 PES-507-11 / D

5.7 737 of 1481

c) Unit rate of supply and filling of sand shall be applicable for the quantity of sand in cubic metres.

As per the environment law, itis not permissible to fill the river sand, hence we are not consider in our scope.

Follow Technical Specifications

153 PES-507-11 / D

7.16 741 of 1481

Equipment layout drawings.

We presume that, the equipment layout drawings will be provided with individual equipment tag numbers ( inline with cable schedule) for easy identification.

Follow Technical Specifications

154 PE-TS-401-510-E001 / C

3.0 991 of 1481

The Generator Circuit Breaker (GCB) is installed indoor and connected to generator busduct (isolated phase) on

We have not considered IPBD in our scope.

Noted

Page 78: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

both sides. Suitable provisions shall be made for connection with isolated Phase Busducts (IPB) through flexible connection.

155 PE-TS-401-557- E001

1.2 1075 of 1481

Engineering: The “Engineering” shall broadly cover the detailed design of PA System as per the requirements of this specification, selection of equipment, materials, estimation of quantities etc. and preparation of all drawings necessary for the erection of the system. Complete engineering shall be as per the guidelines of purchaser and shall be subject to the approval.

We presume that the following informations /Drawings/Details shall be furnished by Purchaser to enable us take up the engineering. 1.Location of Hooters and Handsets (as required). 2. GA drawings of the buildings/ Structures, where the above mentioned equipment is proposed to be installed. It is presumed, that PA system cables can be

Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule

Page 79: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

installed in C&I cable trays, which please confirm.

156 PE-TS-401-999-E001

2.0 1252 of 1481

Following equipment and accessories will be supplied and installed. – Two Hundred and fifty (250) nos. of Telephone handsets. – Necessary quantity of Distribution Boxes. – Necessary quantity of Jelly filled cables. – Necessary quantity of wires, splicing / termination / connection accessories. – Sockets, matching plugs for Connection of

We presume that the following informations /Drawings/Details shall be furnished by Purchaser to enable us take up the engineering.1.Location of Telephone Handsets (as required).2. GA drawings of the buildings/ Structures, where the above mentioned equipment is proposed to be installed.It is presumed, that EPABX system cables can be

Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule

Page 80: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

Telephone Sets. – Necessary Grounding materials and connections. – All fittings, supports, brackets, clamps and connections.

installed in C&I cable trays, which please confirm.

157 PE-TS-401-557-E001 / C

12.0 1052 of 1481

INTERFACE WITH EXISTING EXCHANGE: Bidder to provide suitable built in interface for connection with employer's main telephone exchange in the Central Exchange and/or Master Control Units through which it shall

Kindly provide the distance details and location of existing exchange to considered the interconnection cables in our scope.

Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule

Page 81: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

be possible to communicate with any station in any zone from any telephone set through Central Exchange and/or Master Control Unit. All cables and interface hardware are in contractor’s scope of supply for connecting employer’s EPABX with central exchange.

PE-TS-401-557-E001 / C

6.1 1085 of 1481

INTERFACE WITH EXISTING EXCHANGE: PA system central exchange for the unit will be interfaced with existing/new EPABX/ PA system.

Page 82: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

158 PE-TS-401-302-E001 / B

30.0 1160 of 1481

2 independent sets of 4-20mA signals to be made available at marshalling box for display of winding temperature & oil temperature for remote display on DDCMIS.

Please note the provision will be made available in the marshalling box, however the required interconnecting cables are not in our scope.

Cable is in Bidder's Scope

159 PE-RC-999-302-E001 / D

3.02 1168 of 1481

Transformers ( Rating & quantity of transformer shall be as per specific project requirement)

We have considered the quantity and rating of transformer as per tender BOQ/Price schedule only.

Follow Technical Specifications and Price Schedule

160 PE-TS-401-561-E001/ -

-- 1211 of 1481

D.G. AUX DISTRIBUTION BOARD- Distribution Board shall be as follows. This shall supply auxiliary power to various auxiliary equipment’s for operation of Generator sets. The panel shall have 415 V

Since the same is covered in the LV switchgear BOQ, we are not considered separate switchgear for the same. Kindly confirm.

Follow Technical Specifications and Price Schedule

Page 83: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

AC, 3 Phase 3 Wire 50 HZ power as input. Auxiliary Power Supply requirement for this DG AUX MCC shall be generated in the MCC. There shall be one incomer with 125Amps rated MCCB. The MCCB’s shall be kept normally ON. The incoming supplies will be fed from each Unit Emergency MCC. No. of feeders are given in Section IV

161 PE-TS-401-561-E001/ -

-- 1249 of 1481

Minor civil works like drilling, chipping and punching holes and opening in concretefloors, slabs, brick-walls, and cleaning of all debris, Grouting, supply of

Please note that, we have considered civil / Excavation works as mentioned in the tender BOQ / Price schedule. Apart from that we have not considered any civil

Follow Technical Specifications and Price Schedule

Page 84: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

cement, sand,concrete etc.

works in our scope.

162 Vol-I / SECTION C1 (mech) Sub-Section-I

1.00 1270 of 1481

MINIMUM LIFTING REQUIREMENT Note; 1. Area, type, capacity mentioned are minimum requirement and shall be finalised during detail engineering without any commercial implication 2. Travel and Lift are layout dependent and shall be finalised during detail engineering without any commercial implication 3. Additional

We request you to provide the details for the same, to consider the same.

Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule

Page 85: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

electric/manual hoist required during detail engineering shall be provided as per design criteria given above without any commercial implication.

163 Vol-I / SECTION C1 (mech) Sub-Section-I

1.00 1277 of 1481

12.0 DRAWING/DOCUMENT SUBMISSION The successful bidder shall submit the following drawings / documents during detail engineering for customer’s approval /information: A) ELECTRIC HOIST C) MANUAL HOIST (CHAIN PULLEY BLOCK):

Kindly provide the basic drawing details for estimation purpose.

Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule

Page 86: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

164 General - - Electrical hoist Kindly provide the following information :- ELECTRIC HOIST (EACH HOIST) 1. Height of Lift in mtrs. 2. Length of Travel in mtrs. 3. Please inform Beam Size on which Hoist will be operating. 4. Inform Area Classification Safe Area / Hazardous Area. If Hazardous Area give detail vig. Gas Group, Zone & Temp Class etc. along with name of gas present. CHAIN PULLEY BLOCK

Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule

Page 87: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

1. Height of Lift. 2. Location of the Chain Pulley Block, whether Indoor or Outdoor. 3. Beam Size. 4. Any other relevant information necessary for designing to suit your requirement.

Page 88: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

S.N Page No Clause No

Description Clarification Points to be Clarify NBPPL Clarification

165 Annexure-

I 1.1 Pre-Qualification

Requirement Bider should have executed cable laid 400KM in a single Order

Can be related with P.O Value if cable qty is not matching as per criteria

Not Possible

1.2 Bider should have executed 100VCBs in a single Order

Can be related with P.O Value if panel qty is not matching as per criteria

Not Possible

166 Annexure-2B

Board wise BOM & Schedule

Dummy Panel & Adaptor Panel, both are required.

Despite of Bottom Cable Entry, please clarify the requirement for both.

Bidder to quote for Both Dummy & Adapter Panels

167 255 of 1481

3. h) Surge Arrester Class are not defined Surge Arrester is available CL-1, 2 or 3. Please Clarify.

To be provided during detailed Engg Stage

168 359 of 1481

13.1 Specific Technical requirements

Feeder should have 20% spare feeder

These 20% spare items shall be inclusive of depicted BOM or apart from BOM.

Inclusive of depicted BOM

169 360 of 1481

13.10 Ethernet Switches are required with Each Switchboard

Ethernet Switch has to considere as per Prices Schedule or as per Specification.

Ethernet switches to be supplied as per Price Schedule

No of Channel requirement for Ethernetr Switch.

Page 89: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

VOLUME-IIIE-ANNEXURES, FORMATS ETC

NTPC BHEL POWER PROJECTS PVT LTD

170 425 of 1481

Tender Drawing for BUS PT

Any type of Metering & Relay is not showing

To quote as per BOQ or Tender (Module Drawing)

Tender dwg is indicative only Bidder to follow Price Schedule

Page 90: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

PRICE SCHEDULE

Page 91: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL. No.DESCRIPTIONS OF WORKS OR EQUIPMENT

Total Quoted Price

1 2 31.0

TECHNICAL SPECIFICATION NO: PE-TS-401-999-E001, Rev. 0

TITLE: PRICE SCHEDULE Volume-II, Part-C

PACKAGE: - ELECTRICAL SYSTEM

Total firm price on “FOR” site basis for DESIGN, MANUFACTURE, INSPECTION AND TESTING AT MANUFACTURER'S WORKS, PROPER PACKING AND DELIVERY TO SITE, STORAGE AT SITE, HANDLING, TRANSPORTATION OF MATERIALS FROM PROJECT STORAGE YARD / STORES TO ERECTION SITE / PLACE OF ERECTION , STORAGE AT ERECTION SITE, PRESERVATION, WATCH AND WARD, DRESSING, CHIPPING AND LEVELLING OF FOUNDATIONS, CLEANING , CHECKING, TESTING, PRE-ASSEMBLY, ERECTION, CALIBRATION, ALIGNMENT, WELDING, WHEREVER REQUIRED, PRESERVATIVE/ TOUCH-UP PAINTING INCLUDING SUPPLY OF PAINTS ETC, EARTHING OF EQUIPMENT, INCLUDING OTHER ACTIVITIES REQUIRED FOR ERECTION, TESTING, COMMISSIONING, POST COMMISSIONING, TRIAL OPERATIONS & HANDING OVER OF ALL ELECTRICAL EQUIPMENTS AND ITEMS AS PER BOQ INCLUDING SUPPLY OF MANDATORY SPARES, RECOMMENDED SPARES, SPECIAL TOOLS & TACKLES FOR MAINTENANCE ,START-UP ,PRE COMMISSIONING & COMMISSIONING SPARES AS SPECIFIED & AS NECESSARY FOR COMPLETENESS IN ALL RESPECTS AND FOR EFFICIENT & TROUBLE FREE OPERATION OF ELECTRICAL SYSTEMS PACKAGE FOR FEROZE GANDHI UNCHAHAR THERMAL POWER PROJECT – STAGE IV (1 X 500 MW) AS PER

PROJECT : - 1 X 500 MW FGUTPP, UP (Stage - IV)

NOTES

4.Transit Insurance shall be in NBPPL Scope .

FEROZE GANDHI UNCHAHAR THERMAL POWER PROJECT – STAGE IV, (1 X 500 MW) AS PER TECHNICAL SPECIFICATION NO:PE-TS-401-999-E001, Rev. 0 namely - 11kV & 3.3kV segregated phase busduct- MV switchgear- Low voltage switchgear,LT bus duct & neutral grounding resistor (NGR)- Cabling, earthing & lightning protection systems- Fire sealing system- HT XLPE Cables- 1.1kV XLPE Power, PVC PowerCables- 1.1kV PVC Control Cables- Screened Control Cables- 220V DC Battery- 220V DC Battery Charger- Generator Circuit Breaker- Public Address System- Dry Type Transformers- Oil Filled Service Transformer - Emergency D.G. Set- EPABX system- Electrical Equipment Handling Arrangement

5. Any other items, if required to be included is in bidder's scope apart from the above, same shall be included in the respective items itself & no separate price shall be quoted.

6. The above items shall be quoted as per tender specification. Responsibility of ensuring correctness & completeness of scope of supply as per specification requirement solely lies with bidder. 7.Bidder shall furnish the Breakup Prices in Annexures attached with this Price Schedule only

1. L1 bidder shall be evaluated based on the Total Price under column 3 S.No. 1.0 and hence bidder prices should be complete in all respects for the full scope defined considering all terms and conditions agreed . 2. Bidder to furnish list of items as recommended spares for 3 years with its price breakup. Prices of Recommended Spares will be optional and not be considered for evaluation.

3.Bidder to fill all Optional Price Schedule Annexures attached with this Price Schedule

1 of 1

Page 92: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

1. 11 kV AND 3.3 kV SEGREGATED PHASE

BUSDUCT

Page 93: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

DESCRIPTION UNIT QTY Unit Ex-works

price/Unit Price

Total Ex-Works Price

duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

Total Supply and E&C in

INR

11kV, 3000A

LENGTH METER 180

90 deg Bend NOS. 30

TRANSFORMER TERMINATIONS NOS. 3

SWITCHGEAR TERMINATIONS NOS. 6

TEE CONNECTION NOS. 1

WALL FRAME ASSEMBLY NOS. 3

TOTAL PRICE

3.3kV, 3000A

LENGTH METER 90

90 deg Bend NOS. 12

TRANSFORMER TERMINATIONS NOS. 2

SWITCHGEAR TERMINATIONS NOS. 4

WALL FRAME ASSEMBLY NOS. 2

TOTAL PRICE

3.3kV, 2500A

LENGTH METER 40

90 deg Bend NOS. 4

TRANSFORMER TERMINATIONS NOS. 2

SWITCHGEAR TERMINATIONS NOS. 2

WALL FRAME ASSEMBLY NOS. 2

TOTAL PRICE

Supporting structure (hot dip galvanized MS), foundation channels, hardware etc. Suitable for bus ductelevation and length involved.

As required forcomplete scope

BOQ CUM UNPRICED SCHEDULE OF 11KV & 3.3KV SEGRAGATED PHASE BUSDUCT

ANNEXURE-1

Page 94: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

DESCRIPTION UNIT QTY Unit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in

INR on self manufactu

red only

Freight including Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissi

oning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply

and E&C in INR

11kV, 3000A   

LENGTH  METER  180

90 deg Bend  NOS.  30

TRANSFORMER TERMINATIONS  NOS.  3

SWITCHGEAR TERMINATIONS  NOS.  6

TEE CONNECTION  NOS.  1

WALL FRAME ASSEMBLY  NOS.  3

TOTAL PRICE   

3.3kV, 3000A   

LENGTH  METER  90

90 deg Bend  NOS.  12

TRANSFORMER TERMINATIONS  NOS.  2

SWITCHGEAR TERMINATIONS  NOS.  4

WALL FRAME ASSEMBLY  NOS.  2

TOTAL PRICE   

3.3kV, 2500A   

LENGTH  METER  40

90 deg Bend  NOS.  4

TRANSFORMER TERMINATIONS  NOS.  2

SWITCHGEAR TERMINATIONS  NOS.  2

WALL FRAME ASSEMBLY  NOS.  2

TOTAL PRICE   

ANNEXURE-1

BOQ for Erection & Commissioning of 11KV & 3.3KV SEGRAGATED PHASE BUSDUCT

 Supporting structure (hot dip galvanized MS), foundation channels, hardware etc. Suitable for bus duct

elevation and length involved.

As required for

complete scope

Page 95: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

S.no. Item Description Quantity

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess on E &

C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C in

INR

A 11 kV Busduct

1 Support insulators 25 Nos.

2 Three phase set of flexible terminal connectors for switchgear end of each type & rating 1 Set

3 Three phase set of flexible terminal connector for transformer end of each type & rating 1 Set

4 Seal off bushings of each type & rating 3 Nos.

B 3.3 kV Busduct

1 Support insulators 25 Nos.

2 Three phase set of flexible terminal connectors for switchgear end of each type & rating 1 Set

3 Three phase set of flexible terminal connector for transformer end of each type & rating 1 Set

4 Seal off bushings of each type & rating 3 Nos.

MANDATORY SPARES FOR MV BusductANNEXURE-1

Page 96: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

2. MV SWITCHGEAR

Page 97: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

S.no Description UOM Quantity Rating (A)

Unit Ex‐works 

price/Unit 

Price

Total Ex‐Works 

Price duly packed 

in INR/Total Price. 

Excise Duty 

@ on self 

manufactur

ed only

VAT/CST @ 

… in INR on 

self 

manufactur

ed only

Freight 

including 

Service tax 

@

Total FOR 

Site Price 

(Supply)  in 

INR 

Total 

Erection & 

Commission

ing Charges  

INR

Service tax 

@ including 

cess  on E & 

C  in INR

Total E & C 

prices 

including 

Service Tax  

in INR

Total 

Supply and  

E&C  in INR

1 11 kV Unit Switchboard#6BA Nos. 1 3000A

2 11 kV Unit Switchboard#6BB Nos. 1 3000A

3 11 kV Standby Switchboard#0BA Nos. 1 3000A

4 11 kV Colony Switchboard Nos. 1 630A

5 3.3 kV Unit Aux. Switchboard#6CA Nos. 1 3000A

6 3.3 kV Misc. Aux. Switchboard#0CA Nos. 1 2500A

7 Site modification charges:As per annexure‐2C Nos. 1

8 Mandatory Spares:As per annexure‐2D SET 1

9 Data Concetrator system:As per annexure‐2ENos. 1

10Networking and Harware for Numerical relay:As 

per annexure‐2F Nos. 1

11  Training Requirement Annexure‐2G SET 1

12Erection & commissioning charges:As per 

anenexure‐2H Nos.1

Notes.

1

3

4

5

6

7

8

9

10

11

12

13

a)

b)

c)

14

15

16

Minimum clearances required on all sides for each type of panel

Mandatory Spares:As per annexure‐2D

Addition/deletion of quantities shall be aplicable at the quoted prices.The Unit rate of supply of all 

equipments and services quoted by the bidders shall be frim.Requirement of feeders for various 11kV & 

3.3kV switchboards is enclosed in Annexure ‐B. Adopter panels for cable/bus duct connections as 

necessary shall be included by Bidder.

The 3.3 kV boards 6CA and 0CA shall be split into two section due to layout requirements. The cost of tie 

breaker to achieve this shall be included in switchboard price. Please refer MV SWGR layout.

List of MV Boards

For detailed panel wise and board wise BOM and Schedule of Unit Prices, refer Annexure‐2B

Site modification charges:As per annexure‐2C

1X500 MW FGUTPP

BOQ CUM PRICE SCHEDULE OF MV SWGR (Supply) Annexure‐2

Data Concetrator system:As per annexure‐2E

Networking and Harware for Numerical relay:As per annexure‐2F

 Training Requirement Annexure‐2G

List of make (Sub vendor items) is subject to customer approval  during contract stage without any price 

implication

Commissioning charges of numerical relays & data concentrator shall be included in the price quoted for 

SWGR & no extra chrges will be given for the same

All motors and dry type transformer feeders shall be provided with surge suppressors

Tinned brass, double compression type complete with necessary armour clamp cable glands and lugs for 

power & control cables for all external connections to MV switchboards.

Multifunction numerical relays with communication facility on protocol IEC‐61850 shall be selected to 

provide an integrated protection, control, monitoring and metering functions.Features such as self 

diagnosis and external testing, disturbance recording, sequence of event recording and time stampings 

shall be available with relay. Relays shall be of proven design & reputed make subject to customer 

approval during contract stage without any price implication.Bidder to specifically ensure inclusion of 

required hardware/software.

Unit rates quoted in Annexure‐2B,2C,2D,2E,2F and 2G shall be used for any addition/deletion during 

detailed engineering.

Following information other than those asked in the different parts of specification shall be furnished 

along with bid 

Complete dimensions of all the boards including number of panels

Dimension of each type of panel

Page 98: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Board  11kV unit Switchboard#6BA

Rating 3000A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 Incomer from UT#6A 3000A DC 1

2 Line PT ‐‐‐‐‐‐ 2

3 Bus PT ‐‐‐‐‐‐ G 1

4 Tie from Standby Switchboard#0BA 3000A DE 1

5 UAT#6CAT01 16MVA DBF 1

6 Misc Aux. Trf#0CAT01 12.5MVA DBF 1

7 CHP Trf. #0CBT01 5MVA DBF 1

8 AHP Trf. #0CCT01 5MVA DBF 1

9 Spare Trf. feeder 16 MVA DBF 1

10 MD BFP#6 10000 KW DAF 1

11 CWP#6A 2300KW DAF 1

12 PA FAN#6A 3250KW DAF 1

13 FD FAN#6A 1350KW DA 1

14 CEP#6A 900KW DA 1

15 VFD ID FAN#6A(CH1) 3900KW DBF 1

16 VFD ID FAN#6A(CH2) 3900KW DBF 1

17 Spare Motor feeder 10000 KW DAF 1

18 Dummy panel 1

19 Adopter Panel  1

Board  11kV unit Switchboard#6BB

Rating 3000A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 Incomer from UT#6B 3000A DC 1

2 Line PT ‐‐‐‐‐‐ 2

3 Bus PT ‐‐‐‐‐‐ G 1

4 Tie from Standby Switchboard#0BA 3000A DE 1

5 UAT#6CAT02 16MVA DBF 1

6 Misc Aux. Trf#0CAT02 12.5MVA DBF 1

7 CHP Trf. #0CBT02 5MVA DBF 1

8 AHP Trf. #0CCT02 5MVA DBF 1

9 Spare Trf. feeder 5 MVA DBF 1

10 CWP#6B 2300KW DAF 1

11 CWP#6C 2300KW DAF 1

12 PA FAN#6B 3250KW DAF 1

13 FD FAN#6B 1350KW DA 1

14 CEP#6B 900KW DA 1

15 CEP#6C 900KW DA 1

16 VFD ID FAN#6B(CH1) 3900KW DBF 1

17 VFD ID FAN#6B(CH2) 3900KW DBF 1

18 Spare Motor feeder 3250 KW DAF 1

19 Dummy panel 1

20 Adopter Panel  1

1X500 MW FGUTPP

Annexure ‐2B ( Board Wise BOM & Schedule of Unit Prices for various 11kV & 3.3kV switchboards )

Page 99: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Board  11kV Standby Switchboard#0BA

Rating 3000A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 Incomer from ST#0BAT01 3000A DC 1

2 Line PT ‐‐‐‐‐‐ 2

3 Bus PT ‐‐‐‐‐‐ G 1

4 Tie to Unit Switchboard#6BA/6BB 3000A DE 1

5 Adopter Panel  1

Board  11kV Colony Switchboard#0BA

Rating

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 Incomer from ST#0BAT01 630A DC 1

2 Line PT‐A ‐‐‐‐‐‐ 1

3 Bus PT‐A ‐‐‐‐‐‐ G 1

4 TRF. feeder‐1 2MVA DB 1

5 TRF. feeder‐2 2MVA DB 1

6 TRF. feeder‐3 2MVA DB 1

7 B/C 630A 1

8 Line PT‐B ‐‐‐‐‐‐ 1

9 Bus PT‐B ‐‐‐‐‐‐ G 1

10 TRF. feeder‐2 2MVA DB 1

11 TRF. feeder‐3 2MVA DB 1

12 TRF. feeder‐4 2MVA DB 1

13 Dummy panel 1

14 Adopter Panel  1

Page 100: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Board  3.3kV Unit Switchboard#6CA

Rating 3000A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 Incomer from UAT#6CAT01 3000A DC 1

2 Line PT‐A ‐‐‐‐‐‐ 1

3 Bus PT‐A ‐‐‐‐‐‐ G 1

4 Unit Service Trf.#6DAT01 2000KVA DB 1

5 Station Service Trf.#0DAT01 2000KVA DB 1

6 Fuel Oil Trf.#0DBT01 2000KVA DB 1

7 Service Building  Trf.#0DCT01 1600KVA DB 1

8 SWYD TRF.‐1 630KVA DB 1

9 Spare Trf. feeder 2000KVA DB 1

10 SA Compressor#6A 350KW DA 1

11 MILL MOTOR#6A 525KW DA 1

12 MILL MOTOR#6C 525KW DA 1

13 MILL MOTOR#6E 525KW DA 1

14 MILL MOTOR#6G 525KW DA 1

15 MILL MOTOR#6I 525KW DA 1

16 BCW PUMP#6A 350KW DA 1

17 ACW PUMP#6A 200KW DA 1

18 ACW PUMP#6C 200KW DA 1

19 ECW PUMP(TG)#6A 180KW DA 1

20 ECW PUMP(SG)#6A 180KW DA 1

21 Spare Motor feeder 525KW DA 1

22 B/C 3000A DD 1

23 Incomer from UAT#6CAT02 3000A DC 1

24 Line PT‐B ‐‐‐‐‐‐ 1

25 Bus PT‐B ‐‐‐‐‐‐ G 1

26 Unit Service Trf.#6DAT02 2000KVA DB 1

27 Station Service Trf.#0DAT02 2000KVA DB 1

28 Fuel Oil Trf.#0DBT02 2000KVA DB 1

29 Service Building  Trf.#0DCT02 1600KVA DB 1

30 SWYD TRF.‐1 630KVA DB 1

31 Spare Trf. feeder 1600KVA DB 1

32 MILL MOTOR#6B 525KW DA 1

33 MILL MOTOR#6D 525KW DA 1

34 MILL MOTOR#6F 525KW DA 1

35 MILL MOTOR#6H 525KW DA 1

36 MILL MOTOR#6J 525KW DA 1

37 BCW PUMP #6B 350KW DA 1

38 BCW PUMP #6C 350KW DA 1

39 IA Compressor#6A 350KW DA 1

40 ACW PUMP#6B 200KW DA 1

41 ECW PUMP(TG)#6B 180KW DA 1

42 ECW PUMP(TG)#6C 180KW DA 1

43 ECW PUMP(SG)#6B 180KW DA 1

44 Spare Motor feeder 350KW DA 1

45 Dummy panel 1

46 Adopter Panel  1

Page 101: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Board  3.3kV Misc. Aux. Switchboard#0CA

Rating 2500A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 Incomer from Misc. Aux. Trf.#0CAT01 2500A DC 1

2 Line PT‐A ‐‐‐‐‐‐ 1

3 Bus PT‐A ‐‐‐‐‐‐ G 1

4 ESP Service Trf.#6DCT01 1600KVA DB 1

5 ESP Service Trf.#6DDT01 1600KVA DB 1

6 ESP Service Trf.#6DET01 1600KVA DB 1

7 ESP Service Trf.#6DFT01 1600KVA DB 1

8 Make Up Water Trf.#0DET01 630KVA DB 1

9 Fire water/WTP Trf.#0DDT01 2000KVA DB 1

10 Cooling Tower Trf.#6DBT01 2000KVA DB 1

11 Spare Trf. feeder 2000KVA DB 1

12 CW M/U PUMP#A 180KW DA 1

13 Hydrant Main Pump#A 200KW DA 1

14 Spray Pump#A 200KW DA 1

15 Raw Water M/U Motor#A 450KW DA 1

16 APH wash M/U Pump#A 225KW DA 1

17 Spare Motor feeder 450KW DA 1

18 B/C 2500A DD 1

19 Incomer from Misc. Aux. Trf.#0CAT02 2500A DC 1

20 Line PT‐B ‐‐‐‐‐‐ 1

21 Bus PT‐B ‐‐‐‐‐‐ G 1

22 ESP Service Trf.#6DCT02 1600KVA DB 1

23 ESP Service Trf.#6DDT02 1600KVA DB 1

24 ESP Service Trf.#6DET02 1600KVA DB 1

25 ESP Service Trf.#6DFT02 1600KVA DB 1

26 Make Up Water Trf.#0DET02 630KVA DB 1

27 Fire water/WTP Trf.#0DDT02 2000KVA DB 1

28 Cooling Tower Trf.#6DBT02 2000KVA DB 1

29 Spare Trf. feeder 1600KVA DB 1

30 CW M/U PUMP#B 180KW DA 1

31 Hydrant Main Pump#B 200KW DA 1

32 Hydrant Main Pump#C 200KW DA 1

33 Raw Water M/U Motor#B 450KW DA 1

34 APH wash M/U Pump#B 225KW DA 1

35 Spare Motor feeder 350KW DA 1

36 Dummy panel 2nos. 1

37 Adopter Panel  1

S.no Description UOM Rating (A)Unit Ex‐works price/Unit 

Price

Total Ex‐Works Price duly 

packed in INR/Total Price. 

Excise Duty including cess  

@ ……Rs 

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total Erection & 

Commissioning 

Charges  INR

Service tax @ 

including cess  on 

E & C  in INR

Total E & C prices 

including Service 

Tax  in INR

Total Supply and  

E&C  in INR

1 11 kV Unit Switchboard#6BA 1Set 3000A

2 11 kV Unit Switchboard#6BB 1Set 3000A

3 11 kV Standby Switchboard#0BA 1Set 3000A

4 11 kV Colony Switchboard 1Set 630A

5 3.3 kV Unit Aux. Switchboard#6CA 1Set 3000A

6 3.3 kV Misc. Aux. Switchboard#0CA 1Set 2500A

Note: One set means one earthing truck suitable for all types of panels in that switchboard suitable for busbar side and cable side in that board / boards OR mulitple earthing trucks, one for each type of panel suitable for cable side earthing and independent truck for busbar side earthing in that board / boards.

BOQ for Earthing Trucks (If applicable)

The bidder shall bring out clearly in his bid the requirements of earthing trucks for the panels covered in this package

Page 102: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO. DETAILS QUANTITY Unit Charges in INR

Total Ex‐Works 

Price duly packed 

in INR/Total 

Price. 

Excise Duty @ on self 

manufactured only

VAT/CST @ … in INR 

on self manufactured 

only

Freight including 

Service tax @

Total FOR Site Price 

(Supply)  in INR 

(6+7+8+9)

Total Charges in  INR

Service tax @ 

including cess  on Total 

Charges  in INR

Total Charges 

including Service Tax  

in INR

1 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR 

SKILLED TECHNICIAN (EXCEPT DAILY CHARGES)

3 VISITS

2 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SKILLED 

TECHNICIAN 

20 DAYS

3 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR 

SERVICE ENGINEER (EXCEPT DAILY CHARGES)

3 VISITS

4 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SERVICE 

ENGINEER 

15 DAYS

NOTES:  

1) 

2)  AMOUNT PAYABLE FOR SERVICE ENGINEER PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 3 ABOVE  + 

(DAILY CHARGES AS PER SL. NO. 4 ABOVE  X  NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)

AMOUNT PAYABLE FOR SKILLED TECHNICIAN PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 1 ABOVE  + 

(DAILY CHARGES AS PER SL. NO. 2 ABOVE  X  NO. OF DAYS AT SITE) (TO BE CERTIFIED BY  SITE)

1X500 MW FGUTPP

SITE MODIFICATION CHARGES (Annexure‐2C)

Page 103: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

S.no. Item Description Quantity Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

11 KV/3.3KV SWITCHGEARS 1 Breaker of each rating 1 No. 2 Numerical relays 2 Nos. of each type

3Aux. Relays/ Lock out relays/ Timers(if applicable) 2 Nos. of each type

4 Bus bar support insulators 12 Nos. 5 Energy meter of each type & range 1 No. of each type 6 Spring charging motor complete 2 Nos. of each type.

7 Current transformer of each type & ratio 3 Nos. of each type

8 Potential transformer of each type & ratio 3 Nos. of each type 9 Shunt trip coil 5 Nos. of each type & rating

10 Closing coils 5 Nos. of each type & rating

11

Moving contact assembly of each rating (One set means complete replacement for one breaker) 2 Sets

12

Stationary (fixed contact of each rating.(One set means complete replacement for one breaker) 2 Sets

13 Bus seal off bushings 3 Nos. of each type & size 14 Limit switches 10 Nos. 15 Control switches 2 Nos. of each type 16 Selector switches 2 Nos. of each type 17 Isolation switch for the control supply 2 Nos.

18 Circuit breaker auxiliary contact assembly 6 Nos. of each type & rating 19 Indicating lamps with holders 20 Sets 20 (a) Fuse base and holder 12 Nos.

(b) Fuse link 12 Nos.

21

Isolating contact ( fixed & moving)( one set means male & female contacts of one complete breaker) 4 Sets of each rating

22 Terminal blocks 6 Nos.

23SF6 cylinder with SF6 gas filled alongwith nozzle for filling the gas(if applicable) 3 Nos.

24Multiple pin plug contact assy. with cables (male & female) 6 Nos.

25 Interphase barrier 2 Nos. of each type 26 Pressure gauge ( for SF6 breakers) 2 Nos. 27 Vacuum Contactors with HRC fuses 2 Sets (One set for three phases) 28 Surge arresters 3 Nos.

29Modules for Data Concentrator & system LAN 1 No. module of each type

1X500 MW FGUTPPAnnexure-2D LIST OF MANDATORY SPARES FOR 11KV/3.3KV SWITCHGEARS

Page 104: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sl. No. ITEM DESCRIPTION QUANTITYUnit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

Total Supply and E&C in

INR

1DATA CONCENTRATOR ALONGWITH ALL ACCESSORIES FOR COMPLETENESS OF SYSTEM

2 SETS

3 LASER PRINTER (A4 SIZE) 1 NOS.

Notes

a

b

1X500 MW FGUTPPData Concetrator system: Annexure-2E

2 HMI 2 SETS

For other details bidder to refer architecture for Networking of Numerical relays (drawung no 0000-205-POE-A-001) and specification.

All above items shall be supplied along with accessories (including special tools for installation) required for completeness of system.

Page 105: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sl. No. ITEM DESCRIPTION QUANTITYUnit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

a Ethernet Switch on IEC61850 with 8 Copper ports and 4 Gigabit FO ports 15

b Ethernet Switch on IEC61850 with 16 Copper ports and 4 Gigabit FO ports 20

2FIBER OPTICAL CABLE FOR COMMUNICATION (INCLUSIVE OFSUPPLY, LAYING AND TERMINATION ALONGWITH ANYHARDWARE REQUIRE AT EQUIPMENT SUPPLIED UNDER THISPACKAGE) 8 Km

3 LAPTOP PC WITH LICENCED VERSION SOFTWARE, HARDWARE ALONGWITH CONNECTING CABLES FOR RELAY PARAMETERISATION 1 No

4 Cat5E Ethernet cable for connection of Relays to Ethernet Switches 2 Km

5 Additional Numerical relays for Owner's requirement (for Module type DC) 2 Nos

6 Additional Numerical relays for Owner's requirement (for Module type DAF) 2 Nos

7 Additional Numerical relays for Owner's requirement (for Module type DBF) 2 Nos

8

COMMISSIONING CHARGES FOR CABLE LAYING FROM RELAY TO ETHERNET SWITCH AND ETHERNET SWITCH TO DATA CONCENTRATOR /ETHERNET SWITCH TO MV SYSTEM. AND FOR CABLE LAYING FROM ETHERNET SWITCH TO DATA CONCENTRATOR TO LV SYSTEM.

LOT

Notes

a

b

1

STAR COUPLER/EATHERNET SWITCH/ EQUIVALENT DEVICEWITH IEC-61850 PROTOCOL AND 100% REDUNDANT I/OTERMINALS FOR COMUNICATION BETWEEN RELAYS AND DATACONCENTRATOR/ GATEWAY CONCENTRATOR AS PER SYSTEMREQUIREMENT

For other details bidder to refer architecture for Networking of Numerical relays (drawung no 0000-205-POE-A-001) and specification.

All above items shall be supplied along with accessories (including special tools for installation) required for completeness of system.

1X500 MW FGUTPP

Annexure-2F (Networking and Harware for Numerical relay)

Page 106: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Item No. DESCRIPTION  UOM Unit Charges  in INR

Total Ex‐Works 

Price duly packed 

in INR/Total Price. 

Excise Duty @ on 

self manufactured 

only

VAT/CST @ … in 

INR on self 

manufactured 

only

Freight including 

Service tax @

Total FOR Site 

Price (Supply)  in 

INR 

Total  Charges  in 

INR

Service tax @ 

including cess  on 

Total Charges  in 

INR

Total 

Chargesincluding 

Service Tax  in INR

Training of Engineers:

a) Basic cost [irrespective of no. 

of engineers]

b) Additional variable cost per 

engineer

1 1 Set

1X500 MW FGUTPP

Annexure‐2G Training Requirement

Page 107: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

S.no Description UOM Quantity Rating (A)

Unit Erection 

Commissioni

ng Charges  

in INR

Total Ex‐Works 

Price duly 

packed in 

INR/Total Price. 

Excise Duty @ 

on self 

manufactured 

only

VAT/CST @ … 

in INR on self 

manufactured 

only

Freight 

including 

Service tax @

Total FOR Site 

Price (Supply)  

in INR 

Total Erection 

Commissioning 

Charges  INR

Service tax @ 

including cess  

on E & C  in INR

Total E & C 

prices including 

Service Tax in 

INR

Total Supply 

and  E&C  in 

INR

1 11 kV Unit Switchboard#6BANos.

13000A

2 11 kV Unit Switchboard#6BBNos.

13000A

3 11 kV Standby Switchboard#0BANos.

13000A

4 11 kV Colony SwitchboardNos.

1630A

5 3.3 kV Unit Aux. Switchboard#6CANos.

13000A

6 3.3 kV Misc. Aux. Switchboard#0CANos.

12500A

BOQ CUM PRICE SCHEDULE FOR ERECTION & COMMISSIONING OF MV SWGR ANNEXURE‐2H

1X500 MW FGUTPP

Page 108: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

3. LV SWITCHGEAR, LT

BUSDUCT, NGR

Page 109: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UCHAHAR FGTPS (UNIT-6) SUPPLY BOM FOR LV SWITCHGEAR,LT BUS DUCT AND NGR ANNEXURE-3A

RATING(A) BOARD NO.

1 UNIT SERVICE SWBD. NOS. 1 3200 A 6DA2 BOILER MCC NOS. 1 1000 A 6HA3 TURBINE MCC NOS. 1 1000 A 6KA4 BOILER V&D MCC NOS. 1 250 A 6HB5 TURBINE VALVE MCC NOS. 1 250 A 6KB6 UNIT SERVICE ACDB. NOS. 1 630 A 6QA7 BOILER ACDB. NOS. 1 630 A 6HC8 UNIT EMERGENCY SWBD NOS. 1 2500 A 6DG9 ESP-1 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DC

10 ESP-2 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DD11 ESP-3 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DE12 ESP-4 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DF13 ESP A/C & VENT MCC NOS. 1 400 A 6TB14 ESP AREA MCC NOS. 1 250 A 6HD15 COOLING TOWER SWBD NOS. 1 3200 A 6DB16 STATION SERVICE SWBD. NOS. 1 3200 A 0DA17 MISC. SERVICE MCC NOS. 1 630 A 0QA18 VENTILATION MCC NOS. 1 1000 A 6TA19 AIR CONDITIONING MCC NOS. 1 1000 A 0TA20 FIRE WATER/WTP SWBD. NOS. 1 3200 A 0DD21 CHLORINATION PLANT MCC NOS. 1 400 A 0SA22 HYDROGEN & PT PLANT MCC NOS. 1 630 A 0SB23 RO DM PLANT MCC NOS. 1 400 A 0SC24 FUEL OIL SWBD NOS. 1 1600 A 0DB25 MAKE UP WATER SWGR NOS. 1 1000 A 0DE26 SERVICE BUILDING SWGR NOS. 1 2500 A 0DC27 CPU/COMPRESSOR MCC NOS. 1 630 A 0SD28 220V MAIN DCDB NOS. 1 1000A 6FA29 240V AC FUSE DBS NOS. 12 63A 12WAY 1P O/G (16 amp)30 220V FUSE DCDB NOS. 4 50A 12 WAY O/G (10 amp)

31 LT BUSDUCT-3200A SET 4

LT BUSDUCT 3200A, FROM LV TERMINALS OF DRY TYPE TRANSFORMERS TO PCC / PMCC. EACH SET OF 15 M

32 LT BUSDUCT-3200A SET 13

LT BUSDUCT 3200A, FROM LV TERMINALS OF OIL FILLED TRANSFORMERS TO PCC / PMCC. EACH SET OF 4 M

33 LT BUSDUCT-2500A SET 2

LT BUSDUCT 2500A, FROM LV TERMINALS OF OIL FILLED TRANSFORMERS TO PMCC. EACH SET OF 15 M

34 LT BUSDUCT-1600A SET 2

LT BUSDUCT 1600A, FROM LV TERMINALS OF OIL FILLED TYPE TRANSFORMERS TO PMCC. EACH SET OF 15 M

35

EACH SET COMPRISING OF:

FOR DRY TYPE TRANSFORMERS 1) 90 DEG BEND – 2NOS 2) FLEXIBLE (CU) AT TRANSFORMER END – 1SET 3) ADAPTER – 1NO. 4) PHASE CROSSOVER – 1 NO. 5) SET OF HARDWARE AT TRANSFORMER & SWITCHGEAR END 6) EXPANSION JOINT – 1NO.7) WALL FRAME ASSEMBLY – N/A8) SUPPORT STRUCTURE – N/A

FOR OIL FILLED TYPE TRANSFORMERS 1) 90 DEG BEND – 4 NOS 2) FLEXIBLE (CU) AT TRANSFORMER END – 1SET 3) ADAPTER – 1NO. 4) PHASE CROSSOVER – 1NO. 5) SET OF HARDWARE AT TRANSFORMER & SWITCHGEAR END 6) EXPANSION JOINT – 1NO.7) WALL FRAME ASSEMBLY – 1 No.8) SUPPORT STRUCTURE – 200KG

36LOCAL PUSH BUTTON STATIONS TYPE - A NOS. 700

EMERGENCY STOP PUSH BUTTON STATION. 1NO. PRESS TO LOCK & TURN TO RELEASE TYPE EMERGENCY STOP PB WITH 2NO + 2NC CONTACTS WITH SUPPORTING STRUCTURE

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

Sr.No. ITEM NAME UOM TOTAL QTY.

REMARKS

PAGE 1 OF 4

123
Text Box
Page 110: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UCHAHAR FGTPS (UNIT-6) SUPPLY BOM FOR LV SWITCHGEAR,LT BUS DUCT AND NGR ANNEXURE-3A

37LOCAL PUSH BUTTON STATIONS TYPE - B NOS. 25

START & EMERGENCY STOP PUSH BUTTON STATION .1 NO. START PB & 1NO MUSHROOM HEAD STAYPUT WITH EMERGENCY STOP PB WITH 2NO + 2NC CONTACTS WITH SUPPORTING STRUCTURE

38 LOCAL PUSH BUTTON STATIONS TYPE - C

NOS. 25

FLAME PROOF EMERGENCY STOP PUSH BUTTON STATION. 1NO. PRESS TO LOCK TURN TO RELEASE TYPE EMERGENCY STOP PB WITH 2NO + 2NC

39 LOCAL MOTOR STARTERS 0.37 KW NOS. 5

40 LOCAL MOTOR STARTERS 0.55 KW NOS. 10

41 LOCAL MOTOR STARTERS 0.75 KW NOS. 10

42 LOCAL MOTOR STARTERS 1.10 KW NOS. 25

43 LOCAL MOTOR STARTERS 1.50 KW NOS. 25

44 LOCAL MOTOR STARTERS 2.20 KW NOS. 10

45 LOCAL MOTOR STARTERS 3.70 KW NOS. 5

46 LOCAL MOTOR STARTERS 5.5 KW NOS. 5

47 Numerical Relay LOT 1 of each type

48 NGR 11KV (300A, 10 SEC, 22.163 OHMS)

NOS. 3

49 NGR 3.3KV (300A, 10 SEC, 6.74 OHMS)

NOS. 8

50 TOOLS & TACKLE SET 151 SITE VISIT CHARGES NOS. 152 E & C SPARES SET 1

53 MANDATORY SPARES LOT 1

54 NETWORKING HARDWARE FOR NUMERICAL RELAYS

NOS. 1

55 SITE MODIFICATION MATERIAL LOT 1

NOTES:

AS PER ANNEXURE-DAS PER ANNEXURE- GAS PER ANNEXURE-E1

AS PER ANNEXURE-M

REQUIRED FOR SITE MODIFICATION @ 1% TOTAL EX-WORKS PRICE

AS PER ANNEXURE-E2

ALL NECESSARY SUPPORTING STRUCTURES ARE PART OF NGR

1. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF TOOLS & TACKLES AS PER LIST IN ANNEXURE –3D SHALL BE FURNISHED.2. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF E & C SPARES AS PER LIST IN ANNEXURE – 3E1 SHALL BE FURNISHED.3. ALL LT PCC/ MCC/ DBs SHALL BE SUPPLIED ALONGWITH THE INTEGRAL BASE FRAMES, FOUNDATION BOLTS, CABLE GLANDS & LUGS AND TOOLS & TACKLES AS MENTIONED IN DIFFERENT SECTIONS. ALSO SEPARATE BASE FRAMES OF ISMC-75 FOR SWITCHGEAR ERECTION (IN ADDITION TO INTEGRAL BASE FRAMES) SHALL BE SUPPLIED LOOSE BY THE BIDDER. ALL FIXING NUTS & BOLTS TOGETHER WITH FOUNDATION BOLTS SHALL ALSO BE SUPPLIED. PRICES FOR THE BASE FRAME SHALL BE BUILT IN THE SWITCHBOARD PRICE.4. SITE MODIFICATION CHARGES AS PER LIST IN ANNEXURE – 3G SHALL BE FURNISHED.5. ITEM WISE PRICES FOR TYPE TESTS CHARGES AS PER LIST IN ANNEXURE -3F SHALL BE FURNISHED.6. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF O&M AS PER LIST IN ANNEXURE - E2 SHALL BE FURNISHED. LIST OF RECOMMENDED O&M SPARES FOR 3 YEARS (OPTIONAL) WITH ITEM WISE PRICE & QUANTITY OF EACH ITEM AS RECOMMENDED BY MANUFACTURER SHALL BE FURNISHED IN SCHEDULE OF PRICES ALONGWITH.7. ITEM WISE PRICES WITH DESCRIPTION AND RATING OF EACH ITEM COMPLYING TO LIST FURNISHED IN THE SCHEDULE OF UNIT PRICES IN ANNEXURE - 3H SHALL BE FURNISHED IN SCHEDULE OF UNIT PRICE.

8. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF NETWORKING HARDWARE FOR NUMERICAL RELAY (AS PER THE EQUIPMENT DETAILS MENTIONED IN THE REMARKS COLUMN) SHALL BE FURNISHED.9. FOR DETAILED BOARD WISE BOM, REFER ANNEXURE-3B.10. FOR DETAILED MODULE WISE BOM, REFER ANNEXURE-3C.11.ADDITION/DELETION OF QUANTITIES SHALL BE APPLICABLE AT THE QUOTED PRICE.12. FOLLOWING INFORMATION SHALL ALSO BE FURNISHED ALONG WITH BID:a. COMPLETE DIMENSIONS OF ALL THE BOARDS INCLUDING NO OF ACB, MCC AND DUMMY PANELS.b. DIMENSIONS OF EACH TYPE OF PANEL.c. MODULE SIZE OF EACH TYPE OF FEEDER.d. MINIMUM CLEARANCES REQUIRED ON ALL SIDES FOR EACH TYPE OF PANEL.13. DOUBLE COMPRESSION, NICKLE PLATED BRASS CABLE GLANDS & HEAVY DUTY LUGS OF BHEL APPROVED MAKE FOR EXTERNAL POWER, CONTROL & EARTHING CONNECTIONS AT SUPPLIED EQUIPMENT END AND FOUNDATION BOLT ARE IN THE SCOPE OF BIDDER. BIDDER TO QUOTE ALL EQUIPMENT WITH CABLE GLANDS, LUGS ABD FOUNDATION BOLTS.

14. COMMISSIONING AND TRAINING CHARGES OF NUMERICAL RELAYS SHALL BE INCLUDED IN THE PRICE QUOTED FOR SWGR & NO EXTRA CHARGESWILL BE GIVEN FOR THE SAME.

PAGE 2 OF 4

123
Text Box
123
Text Box
Page 111: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW UNCHAHAR FG TPP UNPRICED PRICE SCHEDULE OF BOARDWISE BILL OF MATERIAL FOR LV SWGR ANNEXURE-3B

TYPE OF FEEDER 6DA 6KA 6KB 6QA 6HA 6HB 6HC 6HD 6DB 0DA 0QA 0TA 6TA 6TB 0SB 0DC 0DD 0DE 6DG 6FA 0SA 0DB 0SC 6DC 6DD 6DD 6DD 0SD TOTAL QTY

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

Total Supply and E&C in INR

DAET(I/C)(3200A) 2 3 2 2 2 2 2 2 17DAE(B/C)(3200A) 1 2 1 1 1 1 1 1 9DAET(I/C)(2500A) 2 2DAE(TIE)(2500A) 2 2 4DAE(B/C)(2500A) 1 1 2DAE(I/C)(2500A)DAEG(I/C)(2500A) 2 2DAET(I/C)(1600A) 2 2DAE(B/C)(1600A) 1 1DAET(I/C)(1000A) 2 2DAE(B/C)(1000A) 1 1DAE(I/C)(1000A) 2 2 2 2 8DAE(B/C)(1000A) 1 1 1 1 4DAE(O/G)(1000A) 4 5 4 13DAE(O/G)(1600A)DAE(O/G)(2500A) 3 3EM3(I/C)(630A) 2 2 2 2 2 10EM3(B/C)(630A) 1 1 1 1 1 5EM3(I/C)(630A) (fixed type) 2 2EM3(B/C)(630A) (fixed type) 1 1EM3(I/C)(400A) 2 2 4EM3(B/C)(400A) 1 1 2EMC3(I/C)(250A)EMC3(I/C)(250A) (fixed type) 2 2 4EMC3(B/C)(250A)EM3(I/C)(250A) 2 2EM3(B/C)(250A)CH(400A) (fixed type) 2 2DC(1000A) (fixed type) 2 2HD(1000A) (fixed type) 1 1DB(1000A) (fixed type) 2 2EM3(O/G) (630A) 7 2 2 4 2 2 2 2EM3(O/G) (400A) 3 3 10 3 2 5 22 24 22 22 116EM3(O/G) (250A) 3 4 4 4 2 17EM3(O/G) (250A) (fixed type) 8 8E3(O/G)(6A) 6 5 4 6 9 9 9 39 87E3(O/G)(10A) 8 12 4 4 4 4 36E3(O/G)(16A) 4 7 5 8 3 9 6 8 6 6 23 20 105E3(O/G)(20A) 4 8 3 3 4 6 4 6 5 43E3(O/G)(25A) 3 1 7 11E3 (O/G)(32A) 25 4 20 28 4 4 5 13 22 14 4 2 4 7 156E3 (O/G)(50A) 3 4 12 3 22E3 (O/G)(63A) 16 8 8 4 4 8 5 6 9 3 2 3 2 2 2 2 3 87E3 (O/G)(80A) 4 5 9E3 (O/G)(100A) 3 3 3 3 2 2 2 2 20E3 (O/G)(125A) 12 13 5 4 3 3 3 6 2 5 2 58E3 (O/G)(160A) 3 3 3 5 3 10 27E3 (O/G)(200A) 4 3 6 4 5 2 2 26E3(O/G)(6A) (fixed type) 194 23 217E3(O/G)(10A) (fixed type) 26 8 34E3(O/G)(16A) (fixed type) 26 4 4 34E3(O/G)(20A) (fixed type) 14 25 39E3(O/G)(25A) (fixed type) 42 42E3 (O/G)(32A) (fixed type) 55 44 5 104E3 (O/G)(50A) (fixed type) 10 10E3 (O/G)(63A) (fixed type) 7 32 39E3 (O/G)(80A) (fixed type) 11 11E3 (O/G)(100A) (fixed type) 3 3E3 (O/G)(125A) (fixed type) 30 4 34E1(6A) 22 3 6 17 8 16 72E1(10A) 10 4 3 3 20E1(16A) 6 5 7 6 2 2 13 41E1(20A) 3 10 3 12 28E1(25A)E1(32A) 9 22 5 9 45E1(63A)E1(100A)E1(6A) (fixed type) 13 13E1(10A) (fixed type) 15 15E1(25A) (fixed type) 12 12E1(63A) (fixed type) 4 4EA1(.5KW)EA1(2KW)EA1(3KW)EA1(5.5KW) 4 4EA3(.06KW)EA3(.09KW)EA3(.55KW)EA3(1.1KW)EA3(1.2KW)EA3(1.5KW)EA3(2KW)EA3(2.2KW)EA3(3KW)EA3(3.7KW)EA3(4KW)EA3(4.5KW)EA3(5KW) 4 4EA3(5.5KW)EA3(7KW)EA3(7.5KW)EA3(8KW)EA3(9KW) 4 4EA3(10KW)EA3(15KW)

Page 112: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW UNCHAHAR FG TPP UNPRICED PRICE SCHEDULE OF BOARDWISE BILL OF MATERIAL FOR LV SWGR ANNEXURE-3B

TYPE OF FEEDER 6DA 6KA 6KB 6QA 6HA 6HB 6HC 6HD 6DB 0DA 0QA 0TA 6TA 6TB 0SB 0DC 0DD 0DE 6DG 6FA 0SA 0DB 0SC 6DC 6DD 6DD 6DD 0SD TOTAL QTY

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

Total Supply and E&C in INR

EA3(16KW)EA3(18KW)EA3(22KW) 5 5EA3(27KW)EA3(30KW)EA3(40KW)DN1 (0-5.5KW) 3 3 6DK2 (0.0-5.5KW) 34 13 28 19 11 5 10 10 37 29 29 29 46 2 53 33 388DK2 (5.6-7.0KW) 18 18DK2 (7.1-13.0KW) 3 14 3 2 3 10 7 7 10 7 66DK2 (13.1-24.0KW) 2 2 2 4 4 5 5 10 15 3 4 56DK2 (24.1-29.9KW) 2 2DK21 (30.0-44.9KW) 2 3 11 3 2 3 3 27DK21 (45.0-55.0KW) 8 5 1 14DK21 (55.1-75.0KW) 2 3 3 2 10DK21 (75.1.1-89.9.0KW) 3 5 3 11DK21 (90-109.9.0KW) 2 5 7DK2E(0.0-5.5KW)DK2E(5.6-7.0KW)DK2E(7.1-13.0KW) 2 2DK2E(13.1-24.0KW)DK2E(24.1-29.9KW)DK21E (30.0-37.0KW)DK21E (37.1-55.0KW)DK21E (55.1-75.0KW)DK21E (75.1-89.9.0KW)DK21E (90-109.9.0KW) 4 4K2/K3 (0.0- 5.5KW) 10 14 3 3 15 4 10 59K2/K3 (5.6-7.0KW)K2/K3 (7.1-13.0KW) 5 6 5 5 21K2/K3 (13.1-24.0KW) 3 3 6K2/K3 (24.1-29.9KW)K21/K31(30.0-37.0KW) 8 8K21/K31(37.1-55.0KW)K21/K31(55.1-75.0KW)K21/K31(75.1-89.9KW)K21/K31(90-109.9KW)DM(110.0-200.0KW) 5 18 3 5 4 3 38CS 2 2 2 2 2 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 49VM 2 1 2 2 1 2 1 2 2 2 2 2 2 2 2 2 29G1 2 2 2 2 2 2 2 2 2 2 20G2 2 2SH 1 1 1 1 1 1 1 1 2 2 2 2 1 17X 6A 11 11X 10A 83 83X 16A 7 7X 25A 19 19X 32AX 50A 10 10X 63A 5 5X 80AX 100AX 125A 4 4X 160A 4 4X 200 AX 400 A 3 3DW UP TO 10AS 2 2TOTAL PRICE

Page 113: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL. NO.

ITEM DESCRIPTION QUANTITY

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service Tax

in INR

Total Supply and E&C in

INR

1BREAKER LIFTING AND HANDLING TROLLEY (TELESCOPIC TROLLEY)

15

2 MODULE RACKING HANDLE FOR BREAKERS 12

3MODULE RACKING HANDLE FOR MCC MODULES

20

4

TEST PLUG WITH COUPLING CABLES FOR TESTING BREAKER IN WITHDRAWN POSITION

4

Annexure-3DTools & Tackles and Accessories

Page 114: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 FACTORY BUILT ASSEMBLIES (PCC/MCC/DB)

1.1 Busbar supports (Horizontal) 1 set of 3 1SET1.2 Primary isolating contacts (Bus side)

of each rating

1 set of 3 1SET

1.3 Primary isolating contacts (Load side) of each rating

1 set of 3 1SET

1.4 Secondary isolating contacts of each rating

1 set of 3 1SET

1.5 Gaskets (each size) Meter 101.6 Fixed Terminal (1way) Nos. 201.7

Shrouds (for outgoing modules)

Nos. one for each physical size of

module

1.8 Wire (for secondary wiring)a. 2.5 mm2 Metres 100

b. 1.5mm2 Metres 100

1.9 Lugs (for secondary wiring) Nos. 100

2Air Circuit Breaker(for each rating)

2.1Shunt trip coil

Nos. 1

2.2spring charging motor

Nos. 1 motor of each rating

2.3closing coil

Nos. 1

2.4Auxiliary switch

Nos. 1

3ISOLATING SWITCH

3.1Main contact kit for each rating

1 set of 3 poles

1

4POWER CONTACTORS

4.1Contactor coil of each rating

Nos. 1

4.2Contacts kit (main) for each rating

1 set of 3 poles

1

5AUXILIARY CONTACTORS

5.1Complete unit with 2NO + 2NC contacts

Nos. 1 no. of each rating/type

5.2Contactor coils

a.AC for each rating

Set 1

b.DC for each rating

Set 1

6MCCB

ANNEXURE 3E1

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E &

C in INR

Total E & C prices including Service Tax

in INR

Total Supply and E&C in INR

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR S.No. ITEM / COMPONENT UNIT QUANTITY

Total Ex-Works Price duly packed in INR/Total Price.

Unit Ex-works price/Unit Price

Page 115: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

6.1MCCB (EACH RATING)

Nos. 1

7PUSH BUTTONS

6.1Actuator contacts

Nos. 5

6.2Element

Nos. 5

8INDICATING LAMPS

8.1Complete unit

Nos. 10

8.2Lens (assorted)

Nos. 10

9OTHERS

9.1Selector & control switch (each type)

Nos. 1

9.2AC Voltmeter (0-500V)

Nos. 1

9.3DC Voltmeter (0-300 or 0-150 V)

Nos. 1

10LT BUSDUCT

10.1Busduct support insulators

TPN set for each rating of busduct.

1

10.2Gaskets for each rating of busduct

set (consisting of 10 meters or 2 nos.each of

1

11 NGR11.1 Porcelein post/support

insulator (for mounting on structure)

Nos. 1

11.2 Resistor bank support insulator (mounted inside enclosure)

Nos. 1

11.3Porcelein terminal bushing

Nos. 1

Note:

Bidder to ensure correctness & completeness of type and quantity of every item considered by them in above list. Bidder to note that there will not be any commercial implication to NBPPL as per final requirement after award of contract / during detailed engineering based on BOQ of various equipments given in the specification.

Page 116: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ITEM DESCRIPTION QTYUnit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

1. Complete pole of breaker 1 No. of each type & rating. 2. Spring charging motors 1 No. of each type & rating 3.Aux. Contact set 5 Nos. of each rating. 4. Limit switches 5 Nos. of each rating 5. Arc chutes 3 Nos. of each rating 6. Fixed contact set 5 Sets. 7. Moving contact set 5 Sets. 8. Arcing contact 6 Sets. 9. Charging spring 2 Nos. of each type 10. Current transformer (metering) 3 Nos. 11. Current transformer (protection) 3 Nos. 12. Closing coil 5 Nos. 13. Trip coil 5 Nos. 14. CT for Bimetal O/L relays 3 Nos. of each rating 15. Voltage transformer 3 Nos. 16. Control supply transformer 1 No. 17. Ammeter 1 No. of each range 18. Voltmeter 1 No. of each range 19. Relays 1 No. of each type & rating 20. Power contactor 1 No. of each rating. 21. Coil of above contactor 1 No. of each rating. 22. Air break switches 1 No. of each rating. 23. DP air break switches (DC) 1 No. 24. Control & selector switches. 3 Nos. of each rating. 25. Control fuses & neutral links 1 No. of each rating. 26. Indicating lamps 2 Nos. of each type 27. Bus bar support insulators 1 No. of each size. 28. Bus duct flexibles connectors 1 No. of each type. 29. Primary disconnect in MCC (Male / female contact) 5 Nos. 30. Push buttons 2 Nos. of each type & colour. 31. Power fuses 5 Nos. for each rating. 32. Thermal bimetal relays 2 Nos. of each rating 33. Indication lamp holders complete. 2 Nos. of each rating 34. Maintenance tools accessories formaintenance 1 Set 35. Terminal blocks 1Set for each type/rating 36. Busbar aluminium flat pieces 3 Meter of each size 37. Busbar angles/formed pieces for breaker 1 No. of each type & size

MANDATORY SPARE FOR AC, VENTILATION, COMPRESS AIR SYSTEM ANNEXURE-3F

Page 117: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO. DETAILS QUANTITY Unit Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on

self manufactu

red only

VAT/CST @ … in

INR on self manufactu

red only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Charges INR

Service tax @ including cess on Total Charges in

INR

Total Charges including Service

Tax in INR

1 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR SKILLED TECHNICIAN (EXCEPT DAILY CHARGES)

5 VISITS

2 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SKILLED TECHNICIAN

30 DAYS

3 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR SERVICE ENGINEER (EXCEPT DAILY CHARGES)

5 VISITS

4 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SERVICE ENGINEER

15 DAYS

NOTES:

1) AMOUNT PAYABLE FOR SKILLED TECHNICIAN PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 1 ABOVE + (DAILY CHARGES AS PER SL. NO. 2 ABOVE X NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)

2) AMOUNT PAYABLE FOR SERVICE ENGINEER PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 3 ABOVE + (DAILY CHARGES AS PER SL. NO. 4 ABOVE X NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)

ANNEXURE 3GSite Visit Charges

Page 118: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

 1X500 MW UCHAHAR FGTPS (UNIT‐6) ERECTION AND  COMMISIONING  BOM  FOR LV SWITCHGEAR   ANNEXURE‐3A

RATING(A) BOARD NO.

1 UNIT SERVICE SWBD. NOS. 1 3200 A 6DA

2 BOILER MCC NOS. 1 1000 A 6HA

3 TURBINE MCC NOS. 1 1000 A 6KA

4 BOILER V&D MCC NOS. 1 250 A 6HB

5 TURBINE VALVE MCC NOS. 1 250 A 6KB

6 UNIT SERVICE ACDB. NOS. 1 630 A 6QA

7 BOILER ACDB. NOS. 1 630 A 6HC

8 UNIT EMERGENCY SWBD NOS. 1 2500 A 6DG

9 ESP‐1 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DC

10 ESP‐2 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DD

11 ESP‐3 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DE

12 ESP‐4 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DF

13 ESP A/C & VENT MCC NOS. 1 400 A 6TB

14 ESP AREA MCC NOS. 1 250 A 6HD

15 COOLING TOWER SWBD NOS. 1 3200 A 6DB

16 STATION SERVICE SWBD. NOS. 1 3200 A 0DA

17 MISC. SERVICE MCC NOS. 1 630 A 0QA

18 VENTILATION MCC NOS. 1 1000 A 6TA

19 AIR CONDITIONING MCC NOS. 1 1000 A 0TA

20 FIRE WATER/WTP SWBD. NOS. 1 3200 A 0DD

21 CHLORINATION PLANT MCC NOS. 1 400 A 0SA

22 HYDROGEN & PT PLANT MCC NOS. 1 630 A 0SB

23 RO DM PLANT  MCC NOS. 1 400 A 0SC

24 FUEL OIL SWBD NOS. 1 1600 A 0DB

25 MAKE UP WATER SWGR NOS. 1 1000 A 0DE

26 SERVICE BUILDING SWGR NOS. 1 2500 A 0DC

27 CPU/COMPRESSOR MCC NOS. 1 630 A 0SD

28 220V MAIN DCDB NOS. 1 1000A 6FA

29 240V AC FUSE DBS NOS. 12 63A 12WAY 1P O/G (16 amp)

30 220V FUSE DCDB NOS. 4 50A  12 WAY O/G (10 amp)

31 LT BUSDUCT‐3200A SET    4

LT BUSDUCT 3200A, FROM LV 

TERMINALS OF DRY TYPE 

TRANSFORMERS TO PCC / PMCC. 

EACH SET OF 15 M

32 LT BUSDUCT‐3200A SET    13

LT BUSDUCT 3200A, FROM LV 

TERMINALS OF OIL FILLED  

TRANSFORMERS TO PCC / PMCC. 

EACH SET OF 4 M 

33 LT BUSDUCT‐2500A SET    2

LT BUSDUCT 2500A, FROM LV 

TERMINALS OF OIL FILLED  

TRANSFORMERS TO PMCC. EACH 

SET OF 15 M

34 LT BUSDUCT‐1600A SET    2

LT BUSDUCT 1600A, FROM LV 

TERMINALS OF OIL FILLED TYPE 

TRANSFORMERS TO PMCC. EACH 

SET OF 15 M

Sr.No. ITEM NAME

Total Supply

and E&C in INR

Excise Duty @ on

self manufactu

red only

VAT/CST @ … in

INR on self manufactu

red only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR UOM TOTAL QTY.

Total Erection & Commissi

oning Charges in INR

Service tax @

including cess on E & C in INR

Total E & C prices including Service

Tax in INR

REMARKSUnit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

PAGE 1 OF 4

123
Text Box
123
Text Box
Page 119: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

 1X500 MW UCHAHAR FGTPS (UNIT‐6) ERECTION AND  COMMISIONING  BOM  FOR LV SWITCHGEAR   ANNEXURE‐3A

35

EACH SET COMPRISING OF:

FOR DRY TYPE TRANSFORMERS 1)   90 DEG BEND – 2NOS              

2)   FLEXIBLE (CU) AT 

TRANSFORMER END – 1SET         

3)   ADAPTER – 1NO.                      

4)   PHASE CROSSOVER – 1 NO.   

5)   SET OF HARDWARE AT 

TRANSFORMER & SWITCHGEAR 

END     

6)    EXPANSION JOINT – 1NO.

7)    WALL FRAME ASSEMBLY – 

N/A

8)   SUPPORT STRUCTURE – N/A

FOR OIL FILLED TYPE TRANSFORMERS                 1)   90 DEG BEND – 4 NOS 

2)   FLEXIBLE (CU) AT 

TRANSFORMER END – 

1SET             

3)   ADAPTER – 1NO.           

4)   PHASE CROSSOVER – 

1NO.                                      

5)   SET OF HARDWARE 

AT TRANSFORMER & 

SWITCHGEAR END     

6)    EXPANSION JOINT – 

1NO.

7)    WALL FRAME 

ASSEMBLY – 1 No.

8)   SUPPORT STRUCTURE 

– 200KG

36LOCAL PUSH BUTTON 

STATIONS TYPE ‐ ANOS. 700

EMERGENCY STOP PUSH 

BUTTON STATION.  1NO. PRESS 

TO LOCK & TURN TO RELEASE 

TYPE EMERGENCY STOP PB WITH 

2NO + 2NC CONTACTS WITH 

SUPPORTING STRUCTURE

37LOCAL PUSH BUTTON 

STATIONS TYPE ‐ BNOS. 25

START & EMERGENCY STOP 

PUSH BUTTON STATION .1 NO. 

START PB & 1NO MUSHROOM 

HEAD STAYPUT WITH  

EMERGENCY STOP PB WITH 2NO 

+ 2NC CONTACTS WITH 

SUPPORTING STRUCTURE

38LOCAL PUSH BUTTON 

STATIONS TYPE ‐ CNOS. 25

 FLAME PROOF EMERGENCY 

STOP PUSH BUTTON STATION.  

1NO. PRESS TO LOCK TURN TO 

RELEASE TYPE EMERGENCY STOP 

PB WITH 2NO + 2NC CONTACTS 

WITH SUPPORTING STRUCTURE

39 LOCAL MOTOR STARTERS 0.37  NOS. 5

40 LOCAL MOTOR STARTERS 0.55  NOS. 10

41 LOCAL MOTOR STARTERS 0.75  NOS. 10

42 LOCAL MOTOR STARTERS 1.10  NOS. 25

43 LOCAL MOTOR STARTERS 1.50  NOS. 25

44 LOCAL MOTOR STARTERS 2.20  NOS. 10

45 LOCAL MOTOR STARTERS 3.70  NOS. 5

46 LOCAL MOTOR STARTERS 5.5  NOS. 5

47NGR 11KV (300A, 10 SEC, 

22.163 OHMS)NOS. 3

ALL NECESSARY SUPPORTING 

STRUCTURES ARE PART OF NGR

48NGR 3.3KV (300A, 10 SEC, 6.74 

OHMS)NOS. 8

PAGE 2 OF 4

123
Text Box
123
Text Box
Page 120: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

GROUP-A None

GROUP-B 1 Complete breaker 3 Nos. of each type & rating 2 Ammeter 2 Nos. of each type, size &

range 3 Voltmeter 2 Nos. of each type, size &

range 4 Relays 2 Nos. of each type 5 Bus bar support insulators(Porcelain) 10 Nos.

GROUP-C 1 Spring charging motors 3 Nos. of each type & rating 2 Aux. Contact set 6 Sets of each type & rating 3 Limit switches 10 Nos. 4 Arc chutes 4 Nos. of each type & rating 5 Fixed contact set 6 Sets of each type & rating 6 Moving contact set 6 Sets of each type & rating 7 Arcing contact 6 Sets of each type 8 Charging spring 4 Nos. of each type & rating 9 Current transformer 3 Nos. of each type & ratio

10 Closing coil 12 Nos. of each type & rating 11 Trip coil 12 Nos. of each type & rating 12 CT for Bimetal O/L relays 3 Nos. of each type & rating 13 Voltage transformer 3 Nos. of each type & ratio 14 Control supply transformer 3 Nos.of each type and rating 15 (a) Power contactor 2 Nos. of each type & rating

(b) Coil of above contactor 2 Nos. of each type & rating 16 Air break switches 3 Nos. of each type & rating 17 DP air break switches(DC) 3 Nos. of each type & rating 18 Control & selector switches 5 Nos. of each type & rating

19 Control fuses & neutral links Total 50 Nos.( Fuses) & 10 Nos. (Neutral links), to cover all the ratings.

20 Indicating lamps Total 50 Nos. to cover all the types & ratings

Total E & C prices including Service Tax

in INR

Total Supply and E&C in INR

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured

onlySl No. Item Description Quantity

LIST OF MANDATORY SPARES FOR 500MW UNITS LT SWITCHGEAR AND LT BUSDUCTANNEXURE-3E2

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E &

C in INR

21 Vertical bus bar dropper support insulators(FRP) 25 Nos. 22 Bus duct flexible connectors 1 Set for thee phases of each type & size

23(a) Primary disconnect in MCC( Bus bar end)(Male/female contact) Total 15 Nos. proportionately divide for all ratings

(b) Secondary disconnect in MCC(Cable end) Total 15 Nos. proportionately divide for all ratings 24 Push buttons 15 Nos.

25 Power fuses Total 100 Nos. proportionately divide for all ratings

26 Thermal Bimetal relays Total 30 Nos. proportionately divide for all ratings 27 Current transducers 12 Nos. proportionately divide for all ratings 28 Voltage transducers 12 Nos. proportionately divide for all ratings. 29 Indication lamp holders complete 10% of each type & rating 30 Busbar aluminium flat pieces 12 meters of each type & rating 31 Busbar angles/formed pieces for breaker 2 Nos. of each type 32 Terminal blocks 12 Nos. of each type & rating

Page 121: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

CHARGES OF NETWORKING HARDWAREFOR NUMERICAL RELAYS MULTIFUNCTION METERS

ANNEXURE-3M

1.0 NETWORKING OF NUMERICAL RELAYS:-

Sl. No. ITEM DESCRIPTION QUANTITY

Unit Ex-works price/Unit

Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufacture

d only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess on E &

C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C in INR

1ETHERNET SWITCHES ON IEC61850 (16 CHANNELS) 20 Nos.

3 DATA CABLE (CAT-5) FOR CONNECTION OF NUMERICAL RELAYS TO ETHERNET SWITCH

3 km

4

LAPTOP PC WITH LICENCED VERSION SOFTWARE, HARDWARE ALONGWITH CONNECTING CABLES FOR RELAY PARAMETERISATION

1 NO

NOTE

1)

2)

2ETHERNET SWITCHES ON IEC61850 (8 CHANNELS) 10 Nos.

All above items shall be supplied along with acessories (including special tools for installation) required for the completeness of system.

Looping of all the LT SWGR realys shall be in bidders scope.Bidder to configure each LT protection relay to provide protection & control facility up to data concentrator as per attched typical architecture for networking of numerical relays.(ANNEXURE-3P)

Page 122: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

4. CABLING, EARTHING AND LIGHTNING PROTECTION

Page 123: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500MW FGUTPP STAGE IV

PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

Total Supply and E&C in INR

1.0 HOT DIP GALVANISED LADDER TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.

i) CABLE TRAY 2 MM THICK- LADDER TYPE 150W MTR 4800 3400

ii) CABLE TRAY 2 MM THICK- LADDER TYPE 300W MTR 13000 9000

iii) CABLE TRAY 2 MM THICK- LADDER TYPE 600W MTR 26000 18200

2.0

HOT DIP GALVANISED PERFORATED TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.

i) CABLE TRAY 2 MM THICK- PERFORATED TYPE 150W MTR 2000 1400

ii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 300W MTR 5200 3700

iii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 600W MTR 7700 5400

3.0 HOT DIP GALVANISED CABLE TRAY ACCESSORIES

3.1 LADDER TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS

i) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 20 15

ii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 20 15

iii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 250 175

3.2LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)

i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7

ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7

iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35

3.3LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)

i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7

ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7

iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35

3.4 LADDER TYPE TEES-600mm RADIUS

i) LAD TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7

ii) LAD TEES 600MM RADIUS 2 MM THICK 300W NOS 140 100

iii) LAD TEES 600MM RADIUS 2 MM THICK 600W NOS 320 230

3.5 LADDER TYPE CROSS-600mm RADIUS

i) LAD CROSS 600 RAD 2 MM THICK 300W NOS 10 7

ii) LAD CROSS 600 RAD 2 MM THICK 600W NOS 25 20

3.6 LADDER TYPE REDUCERS

i) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8

ii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8

iii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8

3.7 PERFORATED TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS

i) PER HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 10 7

ii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 10 7

iii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 100 70

3.8PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)

i) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7

ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7

iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35

3.9PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)

i) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7

ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7

iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35

3.10 PERFORATED TYPE TEES-600mm RADIUS

i) PER TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7

ii) PER TEES 600MM RADIUS 2 MM THICK 300W NOS 10 7

iii) PER TEES 600MM RADIUS 2 MM THICK 600W NOS 10 7

3.11 PERFORATED TYPE CROSS-600mm RADIUS

i) PER CROSS 600 RAD 2 MM THICK 300W NOS 10 7

ii) PER CROSS 600 RAD 2 MM THICK 600W NOS 20 10

3.12 PERFORATED TYPE REDUCERS

i) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8

ii) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8

iii) PER REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8

ANNEXURE-4A: MAIN ITEMS

Item.No Item UnitOrder

QuantityLot-I

Quantity

PRICES

Page 124: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500MW FGUTPP STAGE IV

PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)

3.13 TROUGHS

i) 50 MM WIDE MTR 1000 700

ii) 75 MM WIDE MTR 1000 700

3.14

HOT DIP GALVANISED CABLE TRAY COVER COMPLETE WITH FORMED CHANNEL, PIPE, GI FLAT, BOLTS WITH NUTS & WASHERS & FIXING HARDWARES ETC. (1.6mm)THICK GALVANISED MS SHEET)

i) COVER 1.6MM THK- NON PERFORATED GALV MS 150W MTR 100 5

ii) COVER 1.6MM THK- NON PERFORATED GALV MS 300W MTR 100 5

iii) COVER 1.6MM THK- NON PERFORATED GALV MS 600W MTR 100 5

4.1SINGLE CHANNEL SC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 10000 7000

4.2DOUBLE CHANNEL DC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 16000 11200

4.3

CANTILEVER ARM EACH COMPLETE WITH 2 NOS. - M12 HEX. BOLT & WASHER 2 NOS. - M12 SPRING NUTS 2 NOS. - M6 PAN HEAD SCREWS & WASHER 2 NOS. - M6 SPRING NUTS

i) Cantilever arm of 750 mm for600mm wide cable trays Nos. 1000 700

ii) Cantilever arm of 620 mm for 600mm wide cable trays Nos. 19000 13300

iii) Cantilever arm of 320 mm for 300mm wide cable trays Nos. 9500 6650

iv) Cantilever arm of 170 mm for 150mm wide cable trays Nos. 3500 2450

4.4CLAMPS AND FITTINGS COMPLETE WITH REQUIRED HARDWARES (Spring nuts/ washers etc. as required for complete installation)

i) 90˚ ANGLE FITTING HL1 Nos. 6000 4200

ii) CLAMP FOR SINGLE CHANNEL CC1 Nos. 14500 10150

iii) CLAMP FOR DOUBLE CHANNEL CC2 Nos. 7200 5040

(iv) BASE PLATE FOR SINGLE CHANNEL BP1 Nos. 300 210

(v) BASE PLATE FOR DOUBLE CHANNEL BP2 Nos. 1800 1260

(vi) BEAM CLAMP BC1 Nos. 400 280

(vii) TRAY FIXING CLAMP TC1 Nos. 2700 1890

(viii) FLAT PLATE STRAIGHT FITTING PF2 Nos. 200 140

(ix) FLAT PLATE TEE FITTING PF1 Nos. 200 140

(x) 90˚ ANGLE FITTING LA1 Nos. 9100 6370

(xi) TRESTLE BRACKET Nos. 200 140

5.0 DOUBLE COMPRESSION HEAVY DUTY BRASS CABLE GLANDS

ABOVE (MM) UP TO (MM)

(i) -- 15 Nos. 600 420

(ii) 15 18 Nos. 160 110

(iii) 18 21 Nos. 100 70

(iv) 21 24 Nos. 110 80

(v) 24 27 Nos. 20 15

(vi) 27 30 Nos. 100 70

(vii) 30 33 Nos. 30 20

(viii) 33 36 Nos. 70 50

(ix) 36 39 Nos. 20 15

(x) 39 42 Nos. 50 35

(xi) 42 46 Nos. 15 10

(xii) 46 50 Nos. 30 20

(xiii) 50 54 Nos. 30 20

(xiv) 54 58 Nos. 30 20

(xv) 58 62 Nos. 20 14

(xvi) 62 67 Nos. 10 5

(xvii) 67 74 Nos. 10 5

6.0 TINNED COPPER LUGS

(SOLDERLESS CRIMPING TYPE) (i) 2.5 SQ MM Nos. 1100 770

(ii) 6 SQ MM Nos. 85 60

(iii) 10 SQ MM Nos. 260 180

(iv) 16 SQ MM Nos. 40 30

(v) 25 SQ MM Nos. 340 240

(vi) 35 SQ MM Nos. 10 7

(vii) 50 SQ MM Nos. 300 210

(viii) 95 SQ MM Nos. 130 90

(ix) 120 sq mm Nos. 20 15

(x) 150 SQ MM Nos. 30 20

(xi) 240 SQ MM Nos. 95 70

(xii) 400 SQ MM Nos. 50 35

(xiii) 630 SQ MM Nos. 40 30

7.0 TINNED COPPER LUGS

(WITH INSULATING SLEEVE)

(i) 1.5 SQ MM Nos. 950 650

(ii) 2.5 SQ MM Nos. 290 200

8.0 ALUMINIUM LUGS

(i) 10 SQ MM Nos. 50 35

(ii) 16 SQ MM Nos. 50 35

(iii) 25 SQ MM Nos. 50 35

(iv) 35 SQ MM Nos. 50 35

(v) 50 SQ MM Nos. 50 35

(vi) 95 SQ MM Nos. 50 35

(vii) 120 sq mm Nos. 50 35

(viii) 150 SQ MM Nos. 50 35

(ix) 240 SQ MM Nos. 50 35

(x) 400 SQ MM Nos. 50 35

(xi) 630 SQ MM Nos. 50 35

Page 125: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500MW FGUTPP STAGE IV

PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)

9.0 TREFOIL CLAMPS ( FOR SIZES AS UNDER)

(i) TREFOIL CLAMP CABLE OD- 25.1 - 30MM NOS. 500 450

(ii) TREFOIL CLAMP CABLE OD- 30.1 - 35MM NOS. 3600 3240

(iii) TREFOIL CLAMP CABLE OD- 35.1 - 40MM NOS. 4950 4460

(iv) TREFOIL CLAMP CABLE OD-45.1 - 50MM NOS. 850 770

(v) TREFOIL CLAMP CABLE OD-50.1 - 55MM NOS. 500 450

10.0 HT TERMINATION KITS FOR

10.1 11 KV UNARMOURED HT. XLPE POWER CABLE

(i) 1C-630 sq mm Nos. 25 18

(ii) 1C-300 sq mm Nos. 75 54

(iii) 3C-150 sq mm Nos. 40 28

10.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE

(i) 1C-630 sq mm Nos. 190 136

(ii) 1C-185 sq mm Nos. 65 46

(iii) 3C-150 sq mm Nos. 200 144

10.3 3.3 KV ARMOURED HT.XLPE POWER CABLE

(i) 3C-150 sq mm Nos. 6 4

11.0 HT/LT JOINT KITS FOR

11.1 11 KV UNARMOURED HT. XLPE POWER CABLE

(i) 1C-300 sq mm Nos. 34 24

11.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE

(i) 3C-150 sq mm Nos. 50 34

11.3 1.1 KV UNARMOURED LT.XLPE POWER CABLE

(i) 3C-240 sq mm Nos. 2 1

(ii) 3C-150 sq mm Nos. 3 2

12.0 RIGID GALVANISED MS CONDUITS / PIPES

(i) 100 mm diameter Metres 1000 700

(ii) 75 mm diameter Metres 1000 700

(iii) 50 mm diameter Metres 2000 1400

(iv) 25 mm diameter Metres 1000 700

(v) 20 mm diameter Metres 1000 700

13.0FLEXIBLE CONDUITS MADE OF COLD ROLLED ANNEALED

ELECTRO GALVANISED MS STRIP (i) 25 mm diameter Metres 2000 1400

(ii) 18 mm diameter Metres 1000 700

14.0 PVC Conduits (i) 250 mm diameter Metres 100 70(ii) 200 mm diameter Metres 100 70(iii) 100 mm diameter Metres 100 70(iv) 50 mm diameter Metres 100 70

15.0LIGHTNING PROTECTION AND ABOVE GROUND

EARTHING MATERIAL

15.1 Hot Dip Galvanised Steel Flats (to be supplied in length of minimum 6 meters)

(i) 65X8 mm MT 84 60

(ii) 50X6 mm MT 2 1

(iii) 25X6 mm MT 14 10

15.2 20 mm dia., 1-meter long Hot Dip Galvanized GS rod for vertical air termination as per enclosed drawing no.PE-DG-999-509-E003 .sheet

03 of 04 Nos.100 70

15.3 Test link with 150x25x6 thick Hot Dip Galvanised GS Flat wih box as per enclosed drawing no. PE-DG-999-509-E003 sheet 01 of 04

Nos.185 130

15.4 8 SWG Hot Dip Galvanized GI Stranded WireMeters

5000 3500

15.5

Flexible braided Copper Conductor of 600 mm length (Cross section equivalent to 300 sq. mm) with tinned copper clamp connected by U-bolt for fence gate earthing as per enclosed drawing no. PE-DG-999-

509-E003 sheet 03 of 04 Nos.25 20

15.6 50NB Galvanized MS pipe 2 meter long Perforated along the length as per enclosed drawing no. PE-DG-999-509-E003 sheet 03 of 04

Nos.145 100

16.0 JUNCTION BOX (i) 6 WAY Nos. 10 7(ii) 12 WAY Nos. 25 17(iii) 24 WAY Nos. 20 14(iv) 36 WAY Nos. 10 7(v) 48 WAY Nos. 10 7

Page 126: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500 MW FGUTPP STAGE IV

BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)

Unit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on

self manufactu

red only

VAT/CST @ … in

INR on self manufactu

red only

Freight including

Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissi

oning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices including Service

Tax in INR

1.0 HOT DIP GALVANISED LADDER TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.

i) CABLE TRAY 2 MM THICK- LADDER TYPE 150W MTR 4800 3400

ii) CABLE TRAY 2 MM THICK- LADDER TYPE 300W MTR 13000 9000

iii) CABLE TRAY 2 MM THICK- LADDER TYPE 600W MTR 26000 18200

2.0

HOT DIP GALVANISED PERFORATED TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.

i) CABLE TRAY 2 MM THICK- PERFORATED TYPE 150W MTR 2000 1400

ii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 300W MTR 5200 3700

iii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 600W MTR 7700 5400

3.0HOT DIP GALVANISED CABLE TRAY ACCESSORIES

3.1 LADDER TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS

i) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 20 15

ii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 20 15

iii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 250 175

3.2LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)

i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7

ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7

iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35

3.3LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)

i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7

ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7

iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35

3.4 LADDER TYPE TEES-600mm RADIUS

i) LAD TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7

ii) LAD TEES 600MM RADIUS 2 MM THICK 300W NOS 140 100

iii) LAD TEES 600MM RADIUS 2 MM THICK 600W NOS 320 230

3.5 LADDER TYPE CROSS-600mm RADIUS

i) LAD CROSS 600 RAD 2 MM THICK 300W NOS 10 7

ii) LAD CROSS 600 RAD 2 MM THICK 600W NOS 25 20

3.6 LADDER TYPE REDUCERS

i) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8

ii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8

iii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8

3.7PERFORATED TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS

i) PER HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 10 7

ii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 10 7

iii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 100 70

3.8PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)

i) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7

ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7

iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35

3.9PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)

i) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7

ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7

iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35

3.10 PERFORATED TYPE TEES-600mm RADIUS

i) PER TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7

ii) PER TEES 600MM RADIUS 2 MM THICK 300W NOS 10 7

iii) PER TEES 600MM RADIUS 2 MM THICK 600W NOS 10 7

3.11 PERFORATED TYPE CROSS-600mm RADIUS

i) PER CROSS 600 RAD 2 MM THICK 300W NOS 10 7

ii) PER CROSS 600 RAD 2 MM THICK 600W NOS 20 10

3.12 PERFORATED TYPE REDUCERS

i) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8

ii) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8

ANNEXURE 4A: MAIN ITEMS

PRICES

Item.No Item Unit Order Quantity Lot-I Quantity

Page 127: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500 MW FGUTPP STAGE IV

BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)

iii) PER REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8

3.13 TROUGHS

i) 50 MM WIDE MTR 1000 700

ii) 75 MM WIDE MTR 1000 700

3.14

HOT DIP GALVANISED CABLE TRAY COVER COMPLETE WITH FORMED CHANNEL, PIPE, GI FLAT, BOLTS WITH NUTS & WASHERS & FIXING HARDWARES ETC. (1.6mm)THICK GALVANISED MS SHEET)

i) COVER 1.6MM THK- NON PERFORATED GALV MS 150W MTR 100 5

ii) COVER 1.6MM THK- NON PERFORATED GALV MS 300W MTR 100 5

iii) COVER 1.6MM THK- NON PERFORATED GALV MS 600W MTR 100 5

4.1SINGLE CHANNEL SC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 10000 7000

4.2DOUBLE CHANNEL DC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 16000 11200

5.0 CABLE LAYING

5.1 11/11 Kv UNARMOURED CABLES

i) 3C – 150 Sq. mm MTR 4500 3500

ii) 1C – 300 Sq. mm MTR 13000 10000

iii) 1C – 630 Sq. mm MTR 3000 2000

5.2 3.3/3.3 kV UNARMOURED CABLES

i) 3C –150 Sq. mm MTR 33000 23000

ii) 1C –185 Sq. mm MTR 3000 2500

iii) 1C –630 Sq. mm MTR 5000 4000

5.3 3.3/3.3 kV ARMOURED CABLES

i) 3C –150 Sq. mm MTR 500 500

5.4 1.1 KV UNARMOURED ALUMINIUM PVC FRLS POWER CABLES

i) 2C‐10 Sq. mm MTR 7000 5000

ii) 2C‐25 Sq. mm MTR 10000 7000

iii) 2C‐95 Sq. mm MTR 8000 6000

(iv) 3C‐10 Sq. mm MTR 19000 14000

(v) 3C‐25 Sq. mm MTR 18000 13000

(vi) 3C‐50 Sq. mm MTR 14000 10000

(vii) 3C‐95 Sq. mm MTR 8000 6000

(viii) 3.5C‐25 Sq. mm MTR 7000 5000

(ix) 3.5C‐50 Sq. mm MTR 29000 20500

(x) 3.5C‐95 Sq. mm MTR 4000 3000

(xi) 4C‐10 Sq. mm MTR 2000 1000

(xii) 1C‐35 Sq. mm MTR 3000 2000

(xiii) 1C‐120 Sq. mm MTR 8000 6000

5.5 1.1 KV UNARMOURED ALUMINIUM XPLE FRLS POWER CABLES

i) 01C X 400 Sq. mm MTR 21500 15000

ii) 01C X 630 Sq. mm MTR 16500 12000

iii) 03C X 150 Sq. mm MTR 4500 3500

(iv) 03C X 240 Sq. mm MTR 15000 11000

(v) 3.5C X 185 Sq. mm MTR 4000 3000

5.6 1.1 KV ARMOURED ALUMINIUM PVC FRLS POWER CABLES

i) 3.5C‐25 Sq. mm MTR 4000 3000

ii) 3.5C‐50 Sq. mm MTR 2500 2000

5.7 1.1 KV ARMOURED COPPER PVC FRLS POWER CABLES

i) 3C‐2.5 Sq. mm MTR 20000 14000

5.8 1.1 KV UNARMOURED COPPER PVC FRLS POWER CABLES

i) 2C‐2.5 Sq. mm MTR 16000 11000

ii) 3C‐2.5 Sq. mm MTR 137000 96000

iii) 2C‐6 Sq. mm MTR 19000 14000

5.9 1.1 KV UNARMOURED COPPER PVC FRLS CONTROL CABLES

i) 3C X 1.5 Sq. mm MTR 48000 34000

ii) 5C X 1.5 Sq. mm MTR 3000 2000

iii) 5C X 2.5 Sq. mm MTR 21000 15000

(iv) 7C X 1.5 Sq. mm MTR 25000 18000

(v) 12C X 1.5 Sq. mm MTR 3000 2000

(vi) 12C X 2.5 Sq. mm MTR 4000 3000

(vii) 19C X 1.5 Sq. mm MTR 1000 1000

5.10225 V INDIVIDUAL & OVERALL SCREENED UNARMOURED SCREENED CONTROL CABLE

i) 4P, 0.5 MTR 103000 72000

ii) 8P, 0.5 MTR 31000 22000

(iii) 12P,0.5 MTR 12500 9000

(iv) 24P, 0.5 MTR 10000 7000

5.11225 V OVERALL SCREENED UNARMOURED SCREENED CONTROL CABLE

i) 4P,0.5 MTR 206000 144000

ii) 8P, 0.5 MTR 30000 21000

(iii) 12P,0.5 MTR 31000 21000

Page 128: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500 MW FGUTPP STAGE IV

BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)

6.0 HT POWER CABLE TERMINATION FOR

6.1 11 KV UNARMOURED HT. XLPE POWER CABLE

i) 1C-630 sq mm Nos. 25 18

ii) 1C-300 sq mm Nos. 75 54

iii) 3C-150 sq mm Nos. 40 28

6.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE

i) 1C-630 sq mm Nos. 190 136

ii) 1C-185 sq mm Nos. 65 46

iii) 3C-150 sq mm Nos. 200 144

6.3 3.3 KV ARMOURED HT.XLPE POWER CABLE

i) 3C-150 sq mm Nos. 6 4

7.0 LT POWER CABLE TERMINATION FOR

7.1 1.1 KV UNARMOURED ALUMINIUM PVC FRLS POWER CABLES

i) 2C‐10 Sq. mm Nos 250 175

ii) 2C‐25 Sq. mm Nos 120 84

iii) 2C‐95 Sq. mm Nos 40 28

(iv) 3C‐10 Sq. mm Nos 800 560

(v) 3C‐25 Sq. mm Nos 600 420

(vi) 3C‐50 Sq. mm Nos 150 105

(vii) 3C‐95 Sq. mm Nos 140 98

(viii) 3.5C‐25 Sq. mm Nos 400 280

(ix) 3.5C‐50 Sq. mm Nos 70 49

(x) 3.5C‐95 Sq. mm Nos 90 63

(xi) 4C‐10 Sq. mm Nos 100 70

(xii) 1C‐35 Sq. mm Nos 100 70

(xiii) 1C‐120 Sq. mm Nos 100 70

7.2 1.1 KV UNARMOURED ALUMINIUM XPLE FRLS POWER CABLES

i) 01C X 400 Sq. mm Nos 800 560

ii) 01C X 630 Sq. mm Nos 1000 700

iii) 03C X 150 Sq. mm Nos 80 56

(iv) 03C X 240 Sq. mm Nos 25 18

(v) 3.5C X 185 Sq. mm Nos 60 42

7.3 1.1 KV ARMOURED ALUMINIUM PVC FRLS POWER CABLES

i) 3.5C‐25 Sq. mm Nos 80 56

ii) 3.5C‐50 Sq. mm Nos 50 35

7.4 1.1 KV ARMOURED COPPER PVC FRLS POWER CABLES

i) 3C‐2.5 Sq. mm Nos 200 140

7.5 1.1 KV UNARMOURED COPPER PVC FRLS POWER CABLES

i) 2C‐2.5 Sq. mm Nos 2000 1400

ii) 3C‐2.5 Sq. mm Nos 4500 3100

iii) 2C‐6 Sq. mm Nos 200 140

8.0 CONTROL CABLE TERMINATION FOR

8.1 1.1 KV UNARMOURED COPPER PVC FRLS CONTROL CABLES

i) 3C X 1.5 Sq. mm Nos 1000 700

ii) 5C X 1.5 Sq. mm Nos 100 70

iii) 5C X 2.5 Sq. mm Nos 500 350

(iv) 7C X 1.5 Sq. mm Nos 500 350

(v) 12C X 1.5 Sq. mm Nos 200 140

(vi) 12C X 2.5 Sq. mm Nos 300 210

(vii) 19C X 1.5 Sq. mm Nos 100 70

9.0 225V SCREENED CABLE TERMINATION (INCLUDING SUPPLY OF LUGS)

i) 4P, 0.5 Nos. 1800 1260

ii) 8P, 0.5 Nos. 350 245

iii) 12P,0.5 Nos. 220 150

iv) 24P, 0.5 Nos. 100 70

10.0 225V SCREENED CABLE TERMINATION (EXCLUDING SUPPLY OF LUGS)

i) 4P, 0.5 Nos. 7200 5040

ii) 8P, 0.5 Nos. 1400 980

iii) 12P,0.5 Nos. 880 620

iv) 24P, 0.5 Nos. 400 280

11.0 CABLE JOINTS

11.1 11 KV UNARMOURED HT. XLPE POWER CABLE

i) 1C-300 sq mm Nos. 34 24

11.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE

i) 3C-150 sq mm Nos. 50 34

11.3 1.1 KV UNARMOURED LT.XLPE POWER CABLE

i) 3C-240 sq mm Nos. 2 1

ii) 3C-150 sq mm Nos. 3 2

12.0 RIGID GALVANISED MS CONDUITS / PIPES

i) 100 mm diameter Metres 1000 700

ii) 75 mm diameter Metres 1000 700

iii) 50 mm diameter Metres 2000 1400

(iv) 25 mm diameter Metres 1000 700

(v) 20 mm diameter Metres 1000 700

13.0FLEXIBLE CONDUITS MADE OF COLD ROLLED ANNEALED ELECTRO

GALVANISED MS STRIP

i) 25 mm diameter Metres 2000 1400

(ii) 18 mm diameter Metres 1000 700

Page 129: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500 MW FGUTPP STAGE IV

BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)

14.0 PVC Conduitsi) 250 mm diameter Metres 100 70ii) 200 mm diameter Metres 100 70iii) 100 mm diameter Metres 100 70(iv) 50 mm diameter Metres 100 70

15.0ABOVE GROUND EARTHING AND LIGHTNING PROTECTION

MATERIAL

15.1INSTALLATION OF VERTICAL AIR TERMINATION (20 MM DIA GALVANISED MS

ROD 1000 MM LONG)Nos. 100 70

15.2 EARTH CONTINUITY CONNECTION CONDUCTOR

i) GALVANISED MS FLAT 65 X 8 Metres 8000 5600

ii) GALVANISED MS FLAT 50 X 6 Metres 600 420

iii) GALVANISED MS FLAT 25 X 6 Metres 2200 1540

(iv) G S WIRE 8 SWG Metres 5000 3500

15.3 RUNWAY CONDUCTOR

i) 65X8 GALVANISED MS FLAT Metres 13000 9100

15.4INSTALLATION OF HORIZONTAL AIR TERMINATION ON WEATHER PROOFED

SURFACES GALVANISED MS STRIP

i) 25 X 6 mm Metres 5000 3500

15.5INSTALLATION OF HORIZONTAL AIR TERMINATION ON OTHER SURFACES

GALVANISED MS STRIP

i) 25 X 6 mm Metres 500 350

15.6INSTALLATION OF DOWN CONDUCTOR

( 25 X 6 MM GALVANISED MS STRIP)

i) 25 X 6 mm Metres 3500 2450

16.0 JUNCTION BOX (i) 6 WAY Nos. 10 7(ii) 12 WAY Nos. 25 17(iii) 24 WAY Nos. 20 14(iv) 36 WAY Nos. 10 7(v) 48 WAY Nos. 10 7

Page 130: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Item.No Item Description Unit Order Quantity

Unit Erection & Commissio

ning Charges in

INR

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection & Commissio

ning Charges

INR

Service tax @ including cess on E & C in INR

Total E & C prices

including Service Tax

in INR

1 Earthwork in excavation & back filling CU. M 1

2 Supply & filling of sand CU. M 1

3 Supply and installation of protective concrete covering CU. M 1

4 Minor civil works

(i) Making opening in brick wall CU. M 1

(ii) Making opening in concrete floor / wall CU. M 1

(iii) Making opening in concrete through core drilling CU. M1

(iv)Making (Constricting into smaller openings already existing large openings) in brickwork CU. M 1

(v)Making (Constricting into smaller openings already existing large openings) in Concrete CU. M 1

(vi) Supply and spreading of bricks CU. M 1

5 Installation of earth electrode driven into earth Nos.1

6 Installation of test pit Nos. 17 Installation of risers Nos. 1

8 Iinstallation of submat in floor Metres 19 Steel fabrication Sq. m 1

1 X 500 MW FGUTPP STAGE IV

BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)

ANNEXURE 4B-SCHEDULE OF UNIT PRICES

Page 131: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

5. FIRE SEALING SYSTEM

Page 132: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO. DESCRIPTION UNIT ORDER QTY. LOT 1 QTY Unit Ex-works price/Unit

Price

Total Ex-Works Price

duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufacture

d only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including

cess on E & C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C in

INR

MAIN ITEMS (IN RUPEES) (IN RUPEES)1 FSS-TYPE A FLOOR OPENINGS

BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)

SQM

170 120

2 FSS-TYPE B FLOOR OPENINGS BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)

SQM

620 440

3 FSS-TYPE B FLOOR OPENINGS (FLOOR THICKNESS 190 MM APPROX)

SQM120 90

4 FSS-TYPE B WALL OPENINGS (WALL THICKNESS 250 MM APPROX) SQM

100 70

5 FSS TYPE-B PIPE SLEEVES (250 NB)NOS

350 245

6TOOLS AND ACCESSORIES REQUIRED FOR ADDITION OR REMOVAL OF CABLES AFTER THE SEAL IS MADE. THIS SHALL INCLUDE SPECIAL TOOLS, COMPOUND INJECTION GUNS, SPRAY GUNS, ETC. (As applicable)

SET

1 1

Notes:-

1)

2)

3)

4)

5)

FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)

ANNEXURE -5A

BILL OF QUANTITIES/ PRICE SCHEDULE FOR SUPPLY OF FIRE SEALING SYSTEM

Successful bidder is responsible for estimation of additional quantities based on site conditions and work progress. The estimates shall be used by NBPPL as inputs for clearing further quantities. These activities shall be completed within the overall contractual period.

Unit prices for supply shall be quoted in line with clause no. 8.3, Section D of Part B of specification.

LOT 1 Quantity shall be released along with LOI, which is approximately 70% of the ordered Quantity/Contract value.

The fire sealing area indicated under Column “Ordered Quantity” above shall be considered for ordering purposes. Bidder shall indicate the quantity of material required to be supplied per square metre, which shall be used for billing purposes of the supply portion after review and acceptance. However, the vendor shall supply the actual material necessary for meeting the specified area requirements as per type-tested arrangement without any commercial implication.

LOT 1 quantities shall be cleared for supply along with the LOI/ PO. However, supplies of quantities shall be made only after approval of drawings, datasheets, quality documentation and successful completion of type testing (if required).

Page 133: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

s. no. DESCRIPTION UNIT ORDER QTY. LOT 1 QTY Unit Erection &

Commissioning Charges

in INR

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufac

tured only

Freight including Service tax @

Total FOR Site

Price (Supply) in INR

Total Erection

& Commiss

ioning Charges

INR

Service tax @

including cess on E & C in

INR

Total E & C prices

including Service Tax in INR

MAIN ITEMS1 FSS-TYPE A FLOOR OPENINGS

BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)

SQM

170 120

2 FSS-TYPE B FLOOR OPENINGS BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)

SQM

620 440

3 FSS-TYPE B FLOOR OPENINGS (FLOOR THICKNESS 190 MM APPROX)

SQM120 90

4 FSS-TYPE B WALL OPENINGS (WALL THICKNESS 250 MM APPROX)

SQM100 70

5 FSS TYPE-B PIPE SLEEVES (250 NB) NOS

350 245

Notes‐

1

3

3

FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)

ANNEXURE- 5A

BILL OF QUANTITIES/ PRICE SCHEDULE FOR INSTALLATION OF FIRE SEALING SYSTEM

Unit prices for installation shall be quoted in line with clause no. 8.3, Section D of Part B of specification.

Successful bidder is responsible for estimation of additional quantities based on site conditions and work progress. 

The estimates shall be used by NBPPL as inputs for clearing further quantities.  These activities shall be completed 

within the overall contractual period. 

LOT 1 Quantity shall be released along with LOI, which is approximately 70% of the ordered Quantity/Contract 

value.

Page 134: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

6. HT XLPE CABLES

Page 135: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Unit Ex-works

price/Unit Price

Total Ex-Works

Price duly packed in INR/Total

Price.

Excise Duty @ on

self manufactu

red only

VAT/CST @ … in

INR on self manufactu

red only

Freight including Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissi

oning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply

and E&C in INR

1.1 3C – 150Sq. mm

4500 Meters

3500 Meters

500 Meters

1.2 1C – 300Sq. mm

13000 Meters

10000 Meters

500 Meters

1.3 1C – 630Sq. mm

3000 Meters

2000 Meters

500 Meters

Unit Ex-works

price/Unit Price

Total Ex-Works

Price duly packed in INR/Total

Price.

Excise Duty @ on

self manufactu

red only

VAT/CST @ … in

INR on self manufactu

red only

Freight including Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissi

oning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply

and E&C in INR

2.1 3C –150Sq. mm

33000 Meters

23000 Meters

500 Meters

2.2 1C –185Sq. mm

3000 Meters

2500 Meters

500 Meters

2.3 1C –630Sq. mm

5000 Meters

4000 Meters

500 Meters

Unit Ex-works

price/Unit Price

Total Ex-Works

Price duly packed in INR/Total

Price.

Excise Duty @ on

self manufactu

red only

VAT/CST @ … in

INR on self manufactu

red only

Freight including Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissi

oning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply

and E&C in INR

3.1 3C –150Sq. mm

500Meters

500 Meters

500 Meters

Notes:

11/11 kV unarmoured cables

3.3/3.3 kV unarmoured cables

3.3/3.3 kV armoured cables

Sl. No. Cable Sizes

Total Quantity

Sl. No. Cable Sizes

Total Quantity

LOT-1 Quantity

Drum Length

Supply

1. Total Quantities indicated above shall be known as Order Quantities.

2. The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.

LOT-1 Quantity

Drum Length

Supply

Sl. No. Cable Sizes

Total Quantity

LOT-1 Quantity

Drum Length

Supply

3. Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be

4. The standard drum length for power cables shall not be less than 500 meters. The length per drum shall be subjected to a maximum tolerance of +/- 5% of the standard drum length. Customer shall have the option of rejecting cable drum with shorter lengths.

5. Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0% Cables consumed for testing and inspection shall be to bidder’s account.

6. For each individual cable size, one short length of not less than 200m may be accepted only in the final drum length to complete the supply (except where the total ordered quantity is one single drum length of 500m). The overall tolerance limits stipulated above shall continue to apply (in case short lengths are accepted).

7. Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.

Bill of Quantities(Main Items) Annexure 6

Page 136: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

7A. 1.1 kV XLPE POWER AND PVC POWER CABLES

Page 137: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

DRUM LENGTH

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

500 METER500 METER

DRUM LENGTH

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

1000 METER

1100 V grade, power cables with stranded compacted plain Aluminium conductor (H2 grade, class 2) , XLPE insulated, PVC type ST2 extruded inner sheathed (no inner sheath for single core cables) and extruded PVC Type ST2 outer sheath with FRLS properties, generally conforming to IS:7098 (Part-1) and NBPPL specification.

1100 V grade power cables with stranded aluminium conductor, PVC Type-A insulation, core identification by colour coding, distinct extruded inner sheath of PVC Type ST2 material (for multi-core cables only) and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1).

1100 V grade power cables with tinned copper conductor, PVC Type-A insulation, core identification by colour coding, distinct extruded inner sheath of PVC Type ST2 material, aluminium wire armour for single core cables and GS round wire/ formed wire armour (Type-'b') for multicore cables, and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1). Colour of the outersheath shall be YELLOW.

(A): UNARMOURED ALUMINIUM PVC FRLS POWER CABLES

S. NO.

SIZE (IN SQ.MM.) QUANTITY (km.)

LOT-1 QTY (km.) DRUM LENGTH

1 2C-10 7 5 500 METER2 2C-25 10 7 500 METER3 2C-95 8 6 500 METER4 3C-10 19 14 500 METER5 3C-25 18 13 500 METER6 3C-50 14 10 500 METER7 3C-95 8 6 500 METER8 3.5C-25 7 5 500 METER9 3.5C-50 29 20.5 500 METER

10 3.5C-95 4 3 500 METER11 4C-10 2 1 500 METER12 1C-35 3 2 500 METER13 1C-120 8 6 500 METER

S. NO.

SIZE (IN SQ.MM.) QUANTITY (km.)

(B): UNARMOURED ALUMINIUM XPLE FRLS POWER CABLES

LOT-1 QTY (km.) DRUM LENGTH

1 01C X 400 21.5 15 500 METER2 01C X 630 16.5 12 500 METER

5 3.5C X 185 4 3 500 METER(C): ARMOURED ALUMINIUM PVC FRLS POWER CABLES

3 03C X 150 4.5 3.5 500 METER4 03C X 240 15 11 500 METER

SIZE (IN SQ.MM.) QUANTITY (km.) LOT-1 QTY (km.)1 3.5C-25 4 3

S. NO.

1100 V grade power cables with stranded aluminium conductor, PVC Type-A insulation, core identification by colour coding, distinct extruded inner sheath of PVC Type ST2 material, aluminium wire armour for single core cables and GS round wire/ formed wire armour (Type-'b') for multicore cables, and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1).

(D): ARMOURED COPPER PVC FRLS POWER CABLES

S. NO. SIZE (IN SQ.MM.) QUANTITY (km.) LOT-1 QTY (km.)

2 3.5C-50 2.5 2

1 3C-2.5 20 14

ANNEXURE 7AA

Page 138: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

5.            For each individual cable size, one short length of not less than 200m may be accepted only in the final drum length to complete the supply (except where the total ordered quantity is one single drum length of 500m). The overall tolerance limits stipulated above shall continue to apply (in case short lengths are accepted).

6.            Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.

7.            The standard drum length shall be 500 meters for Aluminium Cables and 1000m for Copper Cables. Tolerance on individual drum length shall be ±5%.

1.            Quantities indicated above shall be known as Order Quantities.

2.            The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Unit Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.

3.            Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be given for completion of supply for each subsequent lot from the date of clearance of the quantities.

4.            Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0%. Cables consumed for testing and inspection shall be to bidder’s account.

1100 V grade power cables with stranded tinned copper conductor, PVC Type-A insulation, core identification by colour coding , distinct extruded inner sheath of PVC Type ST2 material (for multicore cables only) and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1).

(E): UNARMOURED COPPER PVC FRLS POWER CABLES

S. NO.

SIZE (IN SQ.MM.) QUANTITY (km.)

LOT-1 QTY (km.) DRUM LENGTH

1000 METER

NOTES :

1 2C-2.5 16 11 1000 METER2 3C-2.5 137 96 1000 METER3 2C-6 19 14

Page 139: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

7B. 1.1 kV PVC CONTROL CABLES

Page 140: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

S. NO. QUANTITY (km.)

LOT-1 QTY (km.) DRUM LENGTH Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

Total Supply and E&C in INR

1 48 34 1000 METER2 3 2 1000 METER3 21 15 1000 METER4 25 18 1000 METER5 3 2 1000 METER6 4 3 1000 METER7 1 1 1000 METER

(A): UNARMOURED COPPER PVC FRLS CONTROL CABLES

'Control cables are of 1100 V earthed grade with stranded plain annealed copper conductor, PVC Type-A insulation, core identification by colour coding (upto five cores)/ number marking (more than five cores), distinct extruded inner sheath of PVC Type ST1 material, GS formed wire armour as per IS: 3975 (armour provided for directly buried cables only) and extruded PVC type ST1 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1). Maximum conductor temperature for normal operation is 70 deg. C and for short circuit conditions, 160 deg. C. The minimum conductor cross section is 1.5 sq. mm.

12C X 2.519C X 1.5

SIZE (IN SQ.MM.)

3C X 1.55C X 1.5

7C X 1.512C X 1.5

5C X 2.5

ANNEXURE 7AB

1. Quantities indicated above shall be known as Order Quantities. 2. The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Unit Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.

3. Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be given for completion of supply for each subsequent lot from the date of clearance of the quantities.

4. Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0%. Cables consumed for testing and inspection shall be to bidder’s account.

5. For each individual cable size, one short length of not less than 200m may be accepted only in the final drum length to complete the supply (except where the total ordered quantity is one single drum length of 500m). The overall tolerance limits stipulated above shall continue to apply (in case short lengths are accepted). 6. Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.7. The standard drum length shall be 1000m for Copper Cables. Tolerance on individual drum length shall be ±5%.

NOTES :

Page 141: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

8. SCREENED CONTROLCABLES

Page 142: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

(A):

S.No. SIZE IN SQ. MM Order Quantity (Km) LOT 1 Quantity (Km)Drum Length (Meters)

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on

self manufactur

ed only

VAT/CST @ … in

INR on self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection & Commissio

ning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices

including Service

Tax in INR

Total Supply and E&C in

INR

1 4P, 0.5 103 722 8P,0.5 31 223 12P, 0.5 12.5 94 24P,0.5 10 7

(B):

Total Ex- Excise VAT/CST Total Service tax Total E & C

SCREENED CONTROL CABLE ANNEXURE-8A: BOQ/ PRICE SCHEDULE

500

TYPE 'G', 0.5 SQ. MM. CABLES: Multi pair (twisted) overall shielded instrumentation cables.

225 volt peak, multi-pair (twisted) instrumentation cables, 0.5 sq. mm. high conductivity, electrolytic, Annealed bare, multi stranded copper conductor as per VDE 0815, extruded PVC (compound YI3) insulation as per VDE 0207 Part-4, core & pair identification by suitable colour coding & band marking as per VDE 0815, stranded tin coated copper conductor drain wire, overall shielded with aluminium mylar tape, extruded PVC (compound YM1) outer sheath (sky blue) as per VDE 0207 Part-5 and VDE 0816 with FRLS properties.

225 volt peak, multi-pair (twisted) instrumentation cables, 0.5 sq. mm. high conductivity, electrolytic, Annealed bare, multi stranded copper conductor as per VDE 0815, extruded PVC (compound YI3) insulation as per VDE 0207 Part-4, core & pair identification by suitable colour coding & band marking as per VDE 0815, individual pair and overall shielded with aluminium mylar tape, stranded tin coated copper conductor drain wire provided separately for both individual pair & overall shielding, extruded PVC (compound YM1) outer sheath (sky blue) as per VDE 0207 Part-5 and VDE 0816 with FRLS properties.

100010001000

TYPE 'F' , 0.5 SQ. MM.CABLES: Multi pair (twisted) individual & overall shielded instrumentation cables.

S.No. SIZE IN SQ. MM Order Quantity (Km) LOT 1 Quantity (Km)

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on

self manufactur

ed only

VAT/CST @ … in

INR on self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection & Commissio

ning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices

including Service

Tax in INR

Total Supply and

E&C Rs

1 4P, 0.5 206 144. 2 8P, 0.5 30 21

3 12P, 0.5 31 21

NOTES:

1

2

3

4

5

6

7

100010001000

Drum Length (Meters)

Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0%. Cables consumed for testing and inspection shall be to bidder ’s account

The tolerance of drum length shall be + 5%. Short lengths of individual cable size not less than 300m may be accepted only in the final drum length to complete the supply within the overall variation limits stipulated above.

Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be given for completion of supply for each subsequent lot from the date of clearance of the quantities.

Quantities indicated above shall be known as Order Quantities.

The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Unit Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.

In case the quantities of any one lot cleared by NBPPL for manufacturing are manufactured and offered for inspection by successful bidder in more than one batch, NBPPL reserves the right to witness type testing on all batches.

Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.

Page 143: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

9. 220 V DC BATTERY

Page 144: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on

self manufactur

ed only

VAT/CST @ … in INR

on self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection & Commissio

ning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices

including Service

Tax in INR

Total Supply and

E&C in INR

(A) MAIN ITEMS

1.0

NI-CD POCKET PLATE 220V BATTERY (169 CELLS,220V Ni-Cd, HIGH discharge battery 1.14 ECVsuitable as per Load Duty Cycle( Annexure-III) with all accessories & MS racks with 3 coats of anti acidpaints.(For each battery))

Sets 2

Break up detail

220V , Ni-Cd battery suitable as per Load Duty Cycle(Annexure-III) ( 1 set comprises 170 nos. cell) Sets 2

MS racks with 3 coats of anti acid paints for 220V DCBattery Sets 2

Intercell connectors Sets 2

Electrolyte (sulphuric acid for first filling plus10%extra ) Sets 2

1.1LIST OF ACCESSORIES (for each set of battery)

a Hydrometer Nos 2

bSet of hydrometer syringes (suitable for the ventholes in different cells) Nos 2

cThermometer with specific gravity correction scale(for measuring electrolyte temperature) Nos 5

d Specific gravity correction chart Nos 2

e Wall mounting type holder made of teak wood for hydrometer and thermometer

Nos 2

f Cell testing digital voltmeter (3-0-3V) with testing leads

Nos 2

g Acid/alkali mixing jar Nos 2

h Rubber apron Nos 2

i Pair of rubber hand gloves Nos 2

j Set of spanners Nos 2

k `No smoking’ notice Nos 2

l Goggles (industrial) Nos 2

m Instruction card Nos 10

n Minimum and maximum temperature indicator forBattery Room

Nos 1

o Interconnector bolt wrenches Nos 1

p Stand insulators lot 1

q Battery log book Nos 1

r Funnel Nos 2

s Multimeter Nos 2

t Cell interconnectors with 5% extra and end take-off with one no. extra

lot 1

u Lead coated connection hardware plus 5% extra lot 1

v Teakwood Cable clamps with hardware lot 1

2.0 E & C SPARES

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-1)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (NI-CD Battery)

Page 1 of 2

123
Text Box
Page 145: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-1)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (NI-CD Battery)

a INTER CELL CONNECTOR NOS 2

b GLOVES SET 2

c VENT PLUGS NOS 2

3.0 MANDATORY SPARES

COMPLETELY ASSEMBLED CELL (DRY)NOS.

2% or 2 Nos. whichever is more

Intercell connectors with hardwareNOS./%

10% or 5 nos. whichever ismore of total population of2 sets of battery

Vent plugNOS./%

10% or 5 nos. whichever ismore of total population of2 sets of battery

Acid level indicating float (for opaque containers only)NOS./%

10% or 5 nos. whichever ismore of total population of2 sets of battery

Stand insulatorNOS./%

10% or 5 nos. whichever ismore of total population of2 sets of battery

Cell insulatorNOS./%

10% or 5 nos. whichever ismore of total population of2 sets of battery

Note: A)Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering. B) Bidder can quote for either Option-1 or Option-2

Page 2 of 2

123
Text Box
Page 146: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR (6+7+8+9)

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax (11+12) in INR

Total Supply and E&C in INR

(A) MAIN ITEMS

1.0

LEAD -ACID BATTERY PLANTE, 220V BATTERY (107CELLS, 220V LEAD ACID, 1.85 ECV suitable as perLoad Duty Cycle(Annexure-III ) with all accessories& Teakwood racks with 3 coats of anti acidpaints.(For each battery set)

Sets 2

Break up detail 2

220V , Lead acid plante battery suitable as perAnnexure-III (Load duty cycle) (1 set comprises 107nos cell)

Sets 2

Teakwood racks with 3 coats of anti acid paints for220V DC Battery Sets 2

Intercell connectors Sets 2

Electrolyte (sulphuric acid for first filling plus10%extra ) Sets 2

1.1LIST OF ACCESSORIES (for each set ofbattery)

a Hydrometer Nos 2

bSet of hydrometer syringes (suitable for the ventholes in different cells) Nos 2

cThermometer with specific gravity correction scale(for measuring electrolyte temperature) Nos 5

d Specific gravity correction chart Nos 2

e Wall mounting type holder made of teak wood for hydrometer and thermometer

Nos 2

f Cell testing digital voltmeter (3-0-3V) with testing leads

Nos 2

g Acid/alkali mixing jar Nos 2

h Rubber apron Nos 2

i Pair of rubber hand gloves Nos 2

j Set of spanners Nos 2

k `No smoking’ notice Nos 2

l Goggles (industrial) Nos 2

m Instruction card Nos 10

n Minimum and maximum temperature indicator forBattery Room

Nos 1

o Interconnector bolt wrenches Nos 1

p Stand insulators lot 1

q Battery log book Nos 1

r Funnel Nos 2

s Multimeter Nos 2

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-2)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (LEAD -ACID PLANTE)

Page 1 of 2

123
Text Box
Page 147: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-2)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (LEAD -ACID PLANTE)

t Cell interconnectors with 5% extra and end take-off with one no. extra

lot 1

u Lead coated connection hardware plus 5% extra lot 1

v Teakwood Cable clamps with hardware lot 1

2.0 E & C SPARES

a INTER CELL CONNECTOR NOS 2

b GLOVES SET 2

c VENT PLUGS NOS 2

3.0 MANDATORY SPARES

COMPLETELY ASSEMBLED CELL (DRY)NOS.

2% or 2 Nos. whichever is

Intercell connectors with hardwareNOS./%

10% or 5 nos.whichever is

f lVent plugNOS./%

10% or 5 nos.whichever ismore of total

Acid level indicating float (for opaque containers only) NOS./%

10% or 5 nos.whichever ismore of total

Stand insulatorNOS./%

10% or 5 nos.whichever ismore of total

Cell insulatorNOS./%

10% or 5 nos.whichever ismore of total

Note: A)Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering. B) Bidder can quote for either Option-1 or Option-2

Page 2 of 2

123
Text Box
Page 148: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sr. No. Item Description Unit QuantityUnit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service Tax

in INR

Total Supply and E&C in INR

1

LEAD -ACID BATTERYPLANTE, 220V BATTERY(107 CELLS, 220V LEADACID, 1.81 ECV suitable asper Load Duty Cycle(pl referPART-B of technicalspecification ) with allaccessories & Teakwoodracks with 3 coats of anti acidpaints.(For each battery set)

Sets 2

Break up detail 2220V , Lead acid plantebattery suitable as per Loadduty cycle. (1 set comprises107 nos cell)

Sets 2

Teakwood racks with 3 coatsof anti acid paints for 220VDC Battery

Sets 2

Intercell connectors Sets 2Electrolyte (sulphuric acid forfirst filling plus10% extra ) Sets 2

                                                       Annexure‐9AUNPRICED PRICE SCHEDULE E & C FOR 220V DC BATTERY (Lead-Acid Plante Battery) (OPTION-2)

Note: Bidder can quote for either Option-1 or Option-2

Page 149: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sr. No. Item Description Unit QuantityUnit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service Tax

in INR

Total Supply and E&C in INR

1

NI-CD POCKET PLATE 220VBATTERY (169 CELLS, 220VNi-Cd, HIGH discharge battery1.14 ECV suitable as per LoadDuty Cycle(pl refer PART-B oftechnical specification) with allaccessories & MS racks with3 coats of anti acid paints.(Foreach battery))

Sets 2Break up detail220V , Ni-Cd battery suitableas per Load Duty Cycle ( 1 setcomprises 170 nos. cell)

Sets 2MS racks with 3 coats of antiacid paints for 220V DCBattery Sets 2Intercell connectors Sets 2Electrolyte (sulphuric acid forfirst filling plus10% extra )

Sets 2

UNPRICED PRICE SCHEDULE E & C FOR 220V DC BATTERY (Ni-Cd Battery) (OPTION-1)

Note: Bidder can quote for either Option-1 or Option-2

                                                        Annexure‐9A

Page 150: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

10. 220 V DC BATTERY CHARGER

Page 151: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE 9C

Sr. No. Item Description Unit QuantityRemarks

Unit Ex-works price/Unit PriceTotal Ex-Works Price

duly packed in INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

Total Supply and E&C in

INR

1 FLOAT-CUM-BOOST CHARGER1 NOS 2 400A, 220V DC Float-cumboost

2 BATTERY FUSE BOX NOS 2Battery fuse suitable as per Load Duty Cycle (Annexure-VI)

3 DISCHARGE RESISTOR NOS 1 Variable mettalic resistor and shunt for 220V DC, 920AH Ni-Cd battery for 5 hr. discharge rate/ 1500AH Lead acid plante battery for 10 hr. discharge rate

4 E & C SPARES LOT 14.1 FUSE LINK WITHOUT HOLDERa AC I/P HRC FUSE LINK NOS 2b GLASS FUSE NOS 2c CONTROL HRC FUSE LINK NOS 2d RECTIFIER FUSE LINK NOS 2e FILTER CAPACITOR FUSE LINK NOS 2f DC O/P FUSE LINK NOS 2

4.2 INDICATING LAMPAC I/P LAMP RED COLOR NOS 2AC I/P LAMP YELLOW COLOR NOS 2AC I/P LAMP BLUE COLOR NOS 2DC O/P LAMP NOS 2

5 MANDATORY SPARES LOT 1

5.1ELECTRONIC CARDS (ALLCOMPONENTS MOUNTED)

5.1.1

Set of Cards and modules (Each type and rating: CPC Card, HV PFPSR card, Rectifier FFD card, DC under/over voltage relay card, ACOR card, DC output fuse FFD card, Earth leakage card,etc.)

SET 1

5.1.2

Set of Auxiliary relays (Each type and rating: Auxiliary relays, 6 amp/ 110 V DC coil and 6 amp/240 V AC coil)

SET 1

5.1.3

Set of fuse links and glass fuses(Each type and rating:AC input fuse links, 315 Amp,Rectifier fuse link, GS1000/400 Amp,Filter condenser fuse link, 160 Amp,DC output HRC fuse link, 500 Amp,Control HRC fuses links, 2 &

SETS 3

5.1.4Set of SCR and Diode (One of each type and rating)

SETS 3

5.1.5 Rectifier transformerNos. 1 No. of each type

& rating

5.1.6 Control transformersNos. 1 No. of each type

& rating

BOQ CUM UNPRICED PRICE SCHEDULE FOR SUPPLY OF 220V DC BATTERY CHARGER

Page 152: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

                                               FEROZ GANDHI UNCHAHAR TPP STAGE‐IV( 1 X 500MW)                                     ANNEXURE 9C

Sr. No.

Item Description Unit  Quantity

Unit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning Charges in INR

Service tax @ including cess on

E & C in INR

Total E & C prices including Service

Tax in INR

1400A, 220V DC Float-cum boost  NOS  2

2

Battery fuse suitable as per Load Duty Cycle (for load duty cycle , pl refer PART-B of technical specification)

 NOS  2

3

Variable metallic resistor and shunt for 220V DC, Ni-Cd battery for 5 hr. discharge rate/ Lead acid plante battery for 10 hr. discharge rate

 NOS  1

UNPRICED PRICE SCHEDULE E & C FOR 220V DC BATTERY CHARGER

Page 153: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

11. GENERATOR CIRCUIT BREAKER

Page 154: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO. ITEM QTY.

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service Tax

in INR

Total Supply and E&C in INR

1 Generator Circuit Breaker including all associated series isolators, earth-switches, surge capacitors

1 No

2 Start-up and Commissioning Spares(Bidder to furnish the list)

1 No

3 Special Tools and Tackles(Bidder to furnish the list)

1 Set

4 Mandatory Spares(as per Annexure-II)

1 Lot

Notes:

1.    Wherever set is indicated above, it means the total parts/ accessories required to replace the particular item for given equipment.2.    For item no. 4 (Mandatory spares), bidders to also indicate prices for individual type test/items as per Annexure-II.

ANNEXURE 10Supply BOM for GCB

Page 155: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL. NO. DESCRIPTION QUANTITY

Unit Ex-works

price/Unit Price

Total Ex-Works Price

duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

Total Supply and E&C in

INR

1Complete pole assembly (along with internally mountedequipment) 1 Set

2 Closing coils 3 Nos.3 Tripping coil 3 Nos.4 Closing springs (if applicable) 1 No.5 Tripping springs (if applicable) 1 No.6 Gaskets 1 Set for a breaker7 Limit Switches 1 Set for a breaker8 Bus seal off bushings 1 Set for a breaker

9Upper and lower terminals with finger contact device

1 Set upper & 1 set lower

10 Arc extinction coil 2 Nos.11 SF6 cylinders 3 Nos.12 Auxiliary switches 2 Sets13 Drive assembly complete for GCB 1 Set

14In case of SF6 GCB following shall be provided: 1 Set

a Gas density switch 1 No.b Gas pressure gauge 1 No.c Gas density indicator 1 No.d Absorbent 3 Nos.

eTeflon hoses for one replacement in all the six poles of breakers 1 Set

NOTE: (1) Wherever quantity is mentioned as set bidder to quote for each type & rating.

(2) Bidder to indicate prices for individual items.

PRICE SCHEDULE FOR MANDATORY SPARESANNEXURE –II

Page 156: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO.

ITEM QTY. Unit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges in INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

1

Generator Circuit Breaker including all associated series isolators, earth-switches, surge capacitors

1 No

PRICE SCHEDULE(E&C )

Annexure-10

Page 157: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO. ITEM QTY.

Unit Supervision of E&C price

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty including cess

@ ……Rs

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR (6+7+8+9)

Total Erection & Commissioning

Charges INR

Service tax @ including cess on supervision of E & C in INR

Total E & C prices including

Service Tax (11+12) in INR

Total Supply and E&C Rs(10+13)

4 Supervision of Erection, Testing and Commissioning(Refer Note 1 & 2)

1 Set

Notes:

1.     Supervision of Erection, Testing and Commissioning shall be performed by original equipment manufacturer.2.    For Supervision of Erection, Testing and Commissioning, price for 4 man-days & 1 visit shall be quoted for each GCB. The price shall be all inclusive of charges for airfare, boarding/ lodging, visa, medical, insurance etc.

Price Schedule for Supervision of E&C of GCB

Page 158: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL. NO. DESCRIPTION QUANTITY Unit Price in INR Total Price in INR

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning Charges INR

Service tax @ including cess

on Total Price in INR

Total Price including Service

Tax in INR

1Rated dielectric strength tests

1LOT

(i)Rated low frequency withstand voltage dry test

(ii)Rated full wave impulse withstand voltage test.

2

Short circuit rating and transient recovery voltage tests

1LOT

(i)

Test for rated symmetrical short circuit current interrupting capability, duty cycle and rated transient recovery voltage parameters

(ii)

Test for rated closing, latching and short time current carrying capability

(iii)

Test for rated Generator source asymmetrical short circuit interrupting capability.

3Load current switching test.

1LOT

4

Out of phase switching current tests.

1LOT

5

Rated excitation current switching tests.

1LOT

6

Type tests and oscillographic test records for closing and tripping timings for generator circuit breaker of the rating offered.

1LOT

NOTE: (1) Bidder to indicate type test charges separately for each test.

ANNEXURE –IPRICE SCHEDULE FOR TYPE TEST - GCB

(2) In case Bidder  has already conducted such specified type test(s), he may submit during detailed engineering the type test reports to the owner for waival of conductance of such type test(s). 

These reports should be for the tests conducted on the equipment similar to those proposed to be supplied under this contract and test(s) should have been either conducted at an independent 

laboratory or should have been witnessed by a client. The owner reserves the right to waive conducting of any or all the specified type test(s) under this contract. In case type tests are waived, 

the type test charges shall not be payable to the contractor.

(3) Further theBidder shall only submit the reports of the type tests as listed in Price Schedule and carried out within last ten years from the date of bid opening. These reports should be for the 

test conducted on the equipment similar to those proposed to be supplied under this contract and the test(s) should have been either conducted at an independent laboratory or should have 

been witnessed by a client. However if the contractor is not able to submit report of the type test(s) conducted within last ten years from the date of bid opening, or in the case of type test 

report(s) are not found to be meeting the specification requirements, the contractor shall conduct all such tests under this contract at no additional cost to the owner either at third party lab or 

in presence of client/owners representative and submit the reports for approval.

Page 159: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

12. PA SYSTEM

Page 160: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11

Item No.

DESCRIPTION Unit

(A) MAIN EQUIPMENT MAKE MODEL NO.

Unit Ex-works

price/Unit Price

Total Ex-Works Price

duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess on E & C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C

in INR

1 Central exchange for unit & common area with integrated MDF 1 No.Microprocessor controlled, digital, programmable central control unit(CCU) with PCM/TDM technology suitable for 110 stations and abilityto interconnect 10 more zones for future expansion

2 Central exchange for CHP area with integrated MDF 1 No.Microprocessor controlled, digital, programmable central control unit(CCU) with PCM/TDM technology suitable for 90 stations and ability tointerconnect 10 more zones for future expansion

3 Master Control Station (MCS) 4 Nos.Built-in mic & speaker, LCD display, handset, 4 LED indicators & 18nos. key board switches

4 Flush Mounted Station (FMS) 4 Nos.Built-in mic & speaker, LCD display, handset, 4 LED indicators & 18nos. key board switches

5 Desktop Station with Cone type speaker 20 Nos.

SUPPLY (Rs)QUANTITY

1 X 500 MW FGUTPP STAGE-IV - Bill of Quantity for Main Items for Public Address System

5 Desktop Station with Cone type speaker 20 Nos.Built-in mic & speaker, LCD display, handset, 4 LED indicators & 18nos. key board switches

6 Extension amplifier for MCS, FMS and desktop station 28 Nos.7 Wall/column mounted, weatherproof field call station with handset and

built-in power amplifier,Horn type loudspeaker with 15W (RMS) , for outdoor area (Main & Common plant) conforming to IP-55

60 Nos.

8 Wall/column mounted, weatherproof field call station with handset and built-in power amplifier,Horn type loudspeaker with 15W (RMS) , for outdoor area (CHP area) conforming to IP-65

50 Nos.

9 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (Main & Common plant) conforming to IP-52

45 Nos.

10 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (CHP area) conforming to IP-65

25 Nos.

11 Sub-distribution frame (SDF) 24 pairs 35 Nos.12 Portable handset station with multi-pin plug and 25 meter wire 4 Nos.13 Socket box for Portable handset station 10 Nos.14 Wall/ column mounted 4W Cone type loudspeaker 20 Nos.15 Wall/ column mounted 15W Horn type loudspeaker (Main & common

plant area) conforming to IP-55 for outdoor area60 Nos.

Page 161: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11

Item No.

DESCRIPTION Unit

(A) MAIN EQUIPMENT MAKE MODEL NO.

Unit Ex-works

price/Unit Price

Total Ex-Works Price

duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess on E & C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C

in INR

SUPPLY (Rs)QUANTITY

1 X 500 MW FGUTPP STAGE-IV - Bill of Quantity for Main Items for Public Address System

16 Wall/ column mounted 15W Horn type loudspeaker (Main & commonplant area) conforming to IP-52 for indoor area

45 Nos.

17 Wall/ column mounted 15W Horn type loudspeaker (CHP plant area)conforming to IP-65

75 Nos.

18 Power junction box 200 Nos.19 Signal junction box 30 Nos.20 Sound protecting floor mounted Acoustic hood 10 Nos.21 Weather protecting canopy for field call station 110 Nos.22 Power distribution box 2 Nos.23 Special tools & tackles, if any24 Additional item, required for the completeness of system

NOTES:1. Bidder must indicate the make & model number of each item else the offer can not be evaluated.2. The unit rates of supply for all equipment are to be quoted by the bidder.3. Design and engineering charges shall form part of main equipment.4. Charges for special tools & tackles required for the PA system shall form part of main equipment.5. Main equipment Items, which are not applicable for their system, bidder to mention in "Remarks" column and same shall appear in the unpriced5. Main equipment Items, which are not applicable for their system, bidder to mention in "Remarks" column and same shall appear in the unpriced

copy of the bid also.6. Any additional item/equipment required (as per system quoted by the bidder), bidder shall quote it separately with their unit rate.

Page 162: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11

Item No.

DESCRIPTION

1 Central exchange for unit & common area with integrated MDF 1 No.

Microprocessor controlled, digital, programmable centralcontrol unit (CCU) with PCM/TDM technology suitable for 110stations and ability to interconnect 10 more zones for futureexpansion

2 Central exchange for CHP area with integrated MDF 1 No.

Microprocessor controlled, digital, programmable centralcontrol unit (CCU) with PCM/TDM technology suitable for 90stations and ability to interconnect 10 more zones for futureexpansion

3 Master Control Station (MCS) 4 Nos.

Built-in mic & speaker, LCD display, handset, 4 LED indicators& 18 nos. key board switches

4 Flush Mounted Station (FMS) 4 Nos.

Built-in mic & speaker, LCD display, handset, 4 LED indicators& 18 nos. key board switches

5 Desktop Station with Cone type speaker 20 Nos.

Built-in mic & speaker, LCD display, handset, 4 LED indicators& 18 nos. key board switches

6 Extension amplifier for MCS, FMS and desktop station 28 Nos.

7 Wall/column mounted, weatherproof field call station with handset and built-in power amplifier,Horn type loudspeaker with 15W (RMS) for outdoor area (Main & Common plant) conforming to IP-55

60 Nos.

8 Wall/column mounted, weatherproof field call station with handset and built-in power amplifier,Horn type loudspeaker with 15W (RMS) for outdoor area (CHP area) conforming to IP-65

50 Nos.

9 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (Main & Common plant) conforming to IP-52

45 Nos.

Total Ex-Works Price duly packed in INR/Total

Price.

Total Erection &

Commissioning Charges

in INR

ERECTION & COMMISSIONING

Unit Excise Duty @ on self

manufactured only

E & C (Rs)

QUANTITY

1 X 500 MW FGUTPP STAGE-IV - Price Schedule E & C for Public Address System

VAT/CST @ … in INR on

self manufacture

d only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Service tax @ including

cess on E & C in INR

Total E & C prices

including Service Tax

in INR

(B)

Unit Erection & Commissioning Charges in INR

Page 163: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11

10 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (CHP area) conforming to IP-65

25 Nos.

11 Sub-distribution frame (SDF) 24 pairs 35 Nos.

12 Portable handset station with multi-pin plug and 25 meter wire 4 Nos.

13 Socket box for Portable handset station 10 Nos.

14 Wall/ column mounted 4W Cone type loudspeaker 20 Nos.

15 Wall/ column mounted 15W Horn type loudspeaker (Main &common plant area) conforming to IP-55 for outdoor area

60 Nos.

16 Wall/ column mounted 15W Horn type loudspeaker (Main &common plant area) conforming to IP-52 for indoor area

45 Nos.

17 Wall/ column mounted 15W Horn type loudspeaker (CHPplant area) conforming to IP-65

75 Nos.

18 Power junction box 200 Nos.19 Signal junction box 30 Nos.20 Sound protecting floor mounted Acoustic hood 10 Nos.21 Weather protecting canopy for field call station 110 Nos.22 Power distribution box 2 Nos.

NOTES:12

345 Cables laying is not in the scope of the bidder (except the local cable from JB to station). However, termination of cables on

bidder's equipment is in bidder's scope.

The unit rates of E&C for all equipment are to be quoted by the bidder.Fabrication & painting of support structure for various equipment shall be in bidders scope. However, structural steel will be free issue from NBPPL.E & C spares required shall form part of erection & commissioning charges.Instruments required for testing & commissioning shall be arranged by the bidder.

Page 164: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11A

Item No. DESCRIPTION QUANTITY

Handsets(i) Handset with cord for outdoor station 15 nos(ii) Handset with cord for indoor station (desk for mounted) 4 nos(iii) Handset with cord indoor flush mounted 1 nos(iv) Portable Handset 1 nos

Loudspeakers(i) Outdoor horn type loudspeaker 15 nos(ii) indoor cone type loudspeaker 4 nos(iii) Cradle switch 2 nos of each type(iv) Push buttons of all types and model 2 nos. of each type

(v)Amplifier PCB with all components mounted for wall mounted Handset station 10%

(vi) Extension Amplifier PCB with all components mounted for wall type mounted Handset station (in case different from ix above) 2 nos. of each type

(vii) JB's of Handset. 2 nos(viii) JB's of Loudspeaker 2 nosix) Electronic modules of all types. 10% 10%

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service Tax in

INR

Total Supply and E&C in INR

1 X 500 MW FGUTPP STAGE-IV - Price Schedule Mandatory Spares for Public Address System PUBLIC ADDRESS SYSTEM MANDATORY SPARES

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Page 165: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

13. DRY TYPE TRANSFORMERS

Page 166: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

A. MAIN ITEM

S.No Description Unit Qty Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax

in INR

Total Supply and E&C in INR

I3.3/0.433KV Indoor Transformer

(Dry Type)

12.0 MVA,3.3/0.433KV Indoor

Transformers (Dry Type)Nos 4

II Mandatory Spares

1For above 3.3/0.433KV 2.0 MVA

Transformer

1.1 HV Bushing Nos 1

1.2 LV Bushing Nos 1

1.3 LV Neutral Nos 1

1.4Complete Winding Limb (HV and

LV)Nos 1

1.5 WTI Nos 1

1.6Set of Thermistor / RTD with

associated leads complete for one transformer

Nos 1

Annexure-12 (Price Schedule/BOM ofDry Type Transformer)

Page 167: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Bill of quantity of Erection and commissioning of Dry Type Transformers A. MAIN ITEM

S.No Description Unit QtyUnit Erection &

Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty including cess @ ……Rs

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges in

INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

12.0 MVA,3.3/0.433 kV Indoor 

Transformers (Dry Type)Nos 4

Annexure 12

Page 168: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

14. OIL FILLED TRANSFORMERS

Page 169: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

TOTAL

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

(Nos) Rs. Rs.1 12500kVA, 11kV/3.5kV, 3 phase, 2

winding, outdoor, ONAN, Z= 11.7%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

2 2000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 10.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

13

3 1600KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 8.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

4 1000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

5 630KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

NOTES

S. NO. DESCRIPTION QTY. OF TRANSFORMERS

COST OF 10% EXTRA OIL PER TRANSFORMER

TOTAL COST OF 10% EXTRA OIL Total Ex-Works Price

duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service

Tax in INR

Total Supply and

E&C Rs

10 % EXTRA TRANSFORMER OIL IN SEALED NON RETURNABLE STANDARD DRUMS FOR :

2

Annexure-13AAUXILIARY SERVICE TRANSFORMERS (OIL FILLED)

SCHEDULE OF PRICES – TRANSFORMERS

1. ALL ROUTINE AND ACCEPTANCE TESTS AS PER CLAUSE NO. 10.04 AND 10.05 OF TECHNICAL SPECIFICATION NO. PE-RC-999-302-E001 SHALL BE CARRIED OUT ON ALL TRANSFORMERS WITHOUT ANY ADDITIONAL COST. CHARGES FOR ALL ROUTINE AND ACCEPTANCE TESTS SHALL BE DEEMED TO BE INCLUDED IN BID PRICE. BIDDERS SHALL QUOTE ACCORDINGLY.

Annexure-13B

S. No. DESCRIPTION

AUXILIARY SERVICE TRANSFORMERS (OIL FILLED) SCHEDULE OF PRICES – EXTRA OIL

1

Page 170: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

(A)       12500kVA, 11kV/3.5kV, 3 phase, 2 winding, outdoor, ONAN, Z= 11.7%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination))

13

(B)       2000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 10.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination) )

2

(C)      1600KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 8.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

(D)      1000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

(E)       630KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

Note:Bidder shall supply 10% extra oil as per the quoted price. Quantity of extra oil shall be subject to approval during detail engineering.

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

Rs. Rs.HV bushing with metal parts & gaskets

a)   11.0/3.5kV,125000KVA 1 no.b)   3.3/0.433kV, 2000KVA 1 no.c)   3.3/0.433kV, 1600KVA 1 no.d)   3.3/0.433kV, 1000KVA 1 noe)   3.3/0.433kV, 630KVA 1 no.

LV bushing with metal parts & gasketsa)       11.0/3.5kV,125000KVA 1 no.b)       3.3/0.433kV, 2000KVA 1 no.c)       3.3/0.433kV, 1600KVA 1 no.d)       3.3/0.433kV, 1000KVA 1 no.e)       3.3/0.433kV, 630KVA 1 no.

Neutral bushing with metal parts & gaskets

a) 11.0/3.5kV,125000KVA 1 no.c) 3.3/0.433kV, 2000KVA 1 no.d) 3.3/0.433kV, 1600KVA 1 no.e) 3.3/0.433kV, 1000KVA 1 no.f) 3.3/0.433kV, 630KVA 1 no.

4 WTI with contacts 1 no.5 OTI with contacts 1 no.

2

3

Annexure-13DAUXILIARY SERVICE TRANSFORMERS (OIL FILLED)

1

S. NO. DESCRIPTION QTY.SCHEDULE OF PRICES – MANDATORY SPARES

Page 171: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

6 Pressure relief device 1 no.7 Magnetic oil gauge 1 no.8 Buchholz relay complete 1 no.9 Set of gaskets 1 set

10 Set of valves 1 set11 Air cell for conservator (if applicable) 1 no.

NOTES

SET CONSISTS OF QUANTITIES REQUIRED FOR 1 COMPLETE TRANSFORMER. WHEREVER ‘SET’ IS INDICATED ABOVE, IT MEANS THE TOTAL PARTS / ACCESSORIES REQUIRED TO REPLACE THE PARTICULAR ITEM FOR A GIVEN EQUIPMENT.

Page 172: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

TOTALUnit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges in INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service Tax

in INR

(Nos) Rs. Rs.

3 1600KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 8.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

4 1000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

5 630KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

Annexure‐13AUXILIARY SERVICE TRANSFORMERS (OIL FILLED)

BILL OF QUANTITY ERECTION & COMMISSIONING OF OIL FILLED SERVICE TRANSFORMERSS. No. DESCRIPTION

1 12500kVA, 11kV/3.5kV, 3 phase, 2 winding, outdoor, ONAN, Z= 11.7%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

2

2 2000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 10.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)

13

Page 173: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

15. EMERGENCY DG SET

Page 174: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-14

S.NO. ITEM DESCRIPTION UNIT Nos.

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges

INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in

INR

Total Supply and E&C in INR

1

1500 KVA, 3 phase, 415 V diesel generator set (The complete DG set shall be supplied along with equipments/accessories/panels/tools & tackales mentioned in various sections of the technical specification.)

Set 2

UNPRICED PRICE SCHEDULE OF SUPPLY FOR EMERGENCY DG SET

Page 175: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

S.NO. ITEM DESCRIPTION UNIT Nos.

Unit Erection &

Commissioning Charges

in INR

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufacture

d only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

in INR

Service tax @ including

cess on E & C in INR

Total E & C prices

including Service Tax

in INR

1

1500 KVA, 3 phase, 415 V diesel generator set (Erection/commisioning of the complete DG set along with equipments/accessories/panels/tools & tackales mentioned in various sections of the technical specification.)

Set 2

UNPRICED PRICE SCHEDULE OF E & C FOR EMERGENCY DG SETANNEXURE‐14

Page 176: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

LIST OF MANDATORY SPARES FOR DG SET

GROUP-A

S.no. Item Description Quantity Unit Ex-works

price/Unit Price

Total Ex-Works Price

duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

Total Supply and E&C in

INR

None GROUP-B

S.no. Item Description Quantity

1 Ammeter 96x96mm, (0-200 amp) Accuracy class:1.0 1 No.

2 A.C. Voltmeter 96x96 mm, (0-15 kV) Accuracy class:1.0 1 No.

GROUP-C S.no. Item Description Quantity 1. Gaskets & packing 1 Set 2. Valve springs 1 Set 3. Fuel pump complete 1 Set 4. Fuel nozzles and needles 1 Set 5. Piston, complete with rings and rod 1 Set 6. Piston rings( for each engine) 1 Set

7. Flow and temperature relay of each type used 1 Set

8. Main and end bearing shells for the diesel engine 1 Set

9. Generator bearing sheets 1 No. 10. Rotor pole coil 1 No. 11 Battery charging rectifier diodes 4 Nos.

12 Complete rotating rectifier assembly for alternator 1 Set

13 Fuses for the excitation diodes 3 Sets 14 Automatic voltage regulator 1 Set

15 Solenoid coil for each solenoid operated valve or relay used 2 Each

16 Instrument and indicator of each type used 1 Each

17 Alarm and signal lamps of each type used 10% of total population

18 Cabinet lighting lamps( if applicable) 2 Each 19 Bearing check kit 1 Set 20 Shut down coil 1 No. 21 Lub oil pressure relay 1 No. 22 Filter screen 1 No. 23 ‘O’ ring injector 1 Set 24 ‘ O’ ring breather 1 Set 25 Magnetic pick up 1 No. 26 Actuator 1 Set 27 Air cleaner 1 Set 28 Belts( Fan belt) 1 Set 29 Hose bypass 1 No. 30 Hose turbo oil supply 2 Nos. 31 Hose turbo oil drain 2 Nos. 32 Turbo repair kit 1 No.

Page 177: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

33 Over speed stop 1 No. 34 Resistor for diesel generator 48 Nos.

35 Element lube oil filter for Diesel Engine 48 Nos.

36 Element lube oil by-pass filter for Diesel Engine 24 Nos.

37 Element fuel filter for Diesel Engine 24 Nos.

38 Plate corr. Resistor for Diesel Engine 96 Nos.

39 Element air cleaner for Diesel engine 4 Nos. 40 Diodes forward for alternator 3 Nos. 41 Diodes reverse for alternator 3 Nos. 42 HRC fuses links of various rating 3 Nos. of each type 43 Ammeter selector switches 1 No. 44 Local/Remote selector switches 1 No. 45 Voltmeter selector switches 1 No.

46 Push button for trip circuit healthy test 1 No.

47 White indication lamps for spring charged position 1 No.

48 Alarm bell 1 No.

49 Space heater along with control switch 1 No. 50 Trip circuit supervision relay 1 No.

51 Lube oil pump assembly/rotating assembly/impeller/shaft 1 Set

52 Starting air motor 1 No. 53 Governing mechanism of DG set 1 No.

Page 178: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

16. EPABX SYSTEM

Page 179: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

EPBAX SYSTEM Price Schedule

Main item

S NO DESCRIPTION UNIT

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service Tax in

INR

Total Supply and E&C in INR

1Complete EPBAX system as per scope of supply mentioned in the Technical specification including installation & commisioning

1 LOT

Page 180: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

17. ELECTRICAL EQUIPMENT HANDLING ARRANGEMENT

Page 181: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Proj

ect:

1X

500

MW

FG

UT

PPR

01

Pack

age:

EL

EC

TR

IC H

OIS

T a

nd C

HA

IN P

UL

LE

Y B

LO

CK

-

SU

PPL

YPr

ice

Form

atS.

N.

Des

crip

tion

of e

quip

men

t / it

emTo

tal Q

ty

requ

irdU

nit E

x-w

orks

pric

e/U

nit

Pric

e

Tota

l Ex-

Wor

ks

Pric

e du

ly

pack

ed in

IN

R/T

otal

Pric

e.

Exci

seD

uty

@ o

n se

lfm

anuf

actu

red

only

VAT/

CST

@ …

in

INR

on

self

man

ufac

ture

d on

ly

Frei

ght

incl

udin

gSe

rvic

eta

x @

Tota

l FO

R

Site

Pric

e (S

uppl

y)in

INR

12

34

51.

0To

tal l

umps

um fi

rm p

rice

for d

esig

n, e

ngin

eerin

g, m

anuf

actu

ring,

in

spec

tion

and

test

ing,

pain

ting,

supp

ly/d

eliv

ery

duly

pac

ked

at p

roje

ct

site

incl

udin

g fr

eigh

t in

line

with

dra

win

gs/ d

ocum

ents

/ tes

t pro

cedu

res

appr

oved

by

NB

PPL/

NTP

C fo

r the

tota

l sco

pe o

f ele

ctric

hoi

sts a

nd

chai

n pu

lley

bloc

k de

fined

as p

er te

chni

cal s

peci

ficat

ion

PE-

TS-4

04-x

xx-

xxx

taki

ng in

to a

ccou

nt a

ll cl

arifi

catio

ns, c

onfir

mat

ions

and

agr

eem

ents

til

l dat

e.

LOT

BR

EA

K U

P FO

R P

RIC

E A

T 1

.0

1.1

Tota

l lum

psum

pric

e of

1 N

o. E

lect

ric H

oist

of

5T c

ap fo

r ESP

con

trol

room

with

all

acce

ssor

ies i

nclu

ding

isol

atin

g sw

itch

& D

SL1

no.

1.2

Tota

l lum

psum

pric

e of

1 N

o. E

lect

ric H

oist

of

3T c

ap fo

r Boi

ler M

CC

ro

om w

ith a

ll ac

cess

orie

s inc

ludi

ng is

olat

ing

switc

h &

DSL

1 no

.

1.3

Tota

l lum

psum

pric

e of

1 N

o. M

anua

l Hoi

st (C

hain

pul

ley

bloc

k) o

f 2T

ca

p fo

r MV

switc

hgea

r with

all

acce

ssor

ies

1 no

.

1.4

Tota

l lum

psum

pric

e fo

r E&

C sp

ares

as p

er a

nnex

ure

A1

set

1.5

Tota

l lum

psum

pric

e fo

r mai

nten

ance

tool

s and

tack

les a

s per

ann

exur

e B

1 se

t

1 2 3 4

NO

TE Bid

der t

o no

te th

at to

tal p

rice

indi

cate

d ab

ove

at 1

.0 s

hall

be c

onsi

dere

d fo

r eva

luat

ion

and

henc

e sh

ould

be

com

plet

e in

all

resp

ect f

or th

e fu

ll sc

ope

defin

ed a

nd

cons

ider

ing

all t

erm

s and

con

ditio

ns a

gree

d.

Any

item

not

incl

uded

in th

e pr

ice

quot

ed a

bove

and

show

n se

para

tely

will

not

be

take

n co

gniz

ance

of a

nd th

e of

fer s

hall

be li

able

for r

ejec

tion.

Bid

der t

o no

te th

at in

un-

pric

e bi

d, b

idde

r mus

t ind

icat

e as

"Q

UO

TED

" ag

ains

t uni

t pric

e &

tota

l pric

e co

lum

n. P

rice

shou

ld b

e in

dica

ted

in P

rice

Bid

onl

y.

Pric

es q

uote

d ab

ove

at S

.No.

1.1,

1.2

& 1

.3 o

f pric

e sc

hedu

le sh

all b

e co

nsid

ered

for a

ny a

dditi

onal

scop

e re

quire

men

t of E

lect

ric h

oist

s & c

hain

pul

ley

bloc

ks d

urin

g de

tail

engi

neer

ing.

R1

22

5N

opr

ice

impl

icat

ion

shal

lbe

prov

ided

fort

rave

l&lif

tvar

iatio

n.

Page 182: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Proj

ect:

1X

500

MW

FG

UT

PPR

01SY

STE

M-

AN

NEX

UR

E-A

Pack

age:

EL

EC

TR

IC H

OIS

TS

Pric

e Fo

rmat

Sl.n

oD

escr

iptio

nTo

tal

quan

tity

requ

ired

Uni

tU

nit E

x-w

orks

pric

e/U

nit

Pric

e

Tota

l Ex-

Wor

ks

Pric

e du

ly p

acke

d in

INR

/Tot

al

Pric

e.

Exci

se D

uty

@

on s

elf

man

ufac

ture

don

ly

VAT/

CST

@ …

in

INR

on

self

man

ufac

ture

don

ly

Frei

ght

incl

udin

gSe

rvic

e ta

x @

Tota

l FO

R

Site

Pric

e (S

uppl

y)in

INR

12

34

56

Afo

r 3T

capa

city

ele

ctric

hoi

st.

1se

tI)

Ove

rload

Rel

ay

ii)Li

mit

Sw

itch

iii)

Fuse

Lin

k

Bfo

r 5T

capa

city

ele

ctric

hoi

st.

1S

etI)

Ove

rload

Rel

ay

ii)Li

mit

Sw

itch

iii)

Fuse

Lin

k

Tota

l for

site

pric

e fo

r Com

m. S

pare

s

List

of C

omm

isio

ning

spa

res

Page 183: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Proj

ect:

1X

500

MW

FG

UT

PPR

01SY

STE

M-

AN

NEX

UR

E-B

Pack

age:

EL

EC

TR

IC H

OIS

TS

& C

PBPr

ice

Form

at

Sl.n o

Des

crip

tion

Tota

l qu

antit

yre

quire

d

Uni

tU

nit E

x-w

orks

pric

e/U

nit

Pric

e

Tota

l Ex-

Wor

ks P

rice

duly

pac

ked

in IN

R/T

otal

Pr

ice.

Exci

se D

uty

@ o

n se

lf m

anuf

actu

red

only

VAT/

CST

@

… in

INR

on

self

man

ufac

tur

ed o

nly

Frei

ght

incl

udin

gSe

rvic

e ta

x @

Tota

l FO

R S

ite P

rice

(Sup

ply)

in

INR

1C

ompl

ete

set

of6

nos.

ring

span

ners

(Ind

icat

e si

zes)

1Se

ts

2C

ompl

ete

set o

f scr

ewdr

iver

s (M

in 6

nos

, in

dica

te si

ze)

1Se

ts

3A

djus

tabl

e Sp

anne

r 12"

1no

.4

Line

test

er1

no.

5In

sula

ted

plie

r1

no.

6G

reas

e gu

n1

no.

7O

il gu

n1

no.

8To

ol b

ox1

no.

Tot

al P

rice

List

of M

aint

enan

ce T

ools

& T

ackl

es

Not

e: 1

LO

T of

all

item

s in

dica

ted

abov

e ar

e to

be

prov

ided

for e

lect

ric h

oist

and

cha

in p

ulle

y bl

ock

i.e. 1

LO

T fo

r ele

ctric

hoi

st a

nd 1

LO

T fo

r cha

in p

ulle

y bl

ock.

2:B

idde

rto

cons

ider

tool

s&

tack

les

insu

cha

way

that

can

cate

rreq

uire

men

tofe

ach

capa

city

&ty

peof

elec

tric

hois

ts&

chai

npu

lley

bloc

ks

Page 184: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Proj

ect:

1X

500

MW

FG

UT

PPSY

STE

M-

Pack

a ge:

EL

EC

TR

IC H

OIS

TS

& C

hain

Pul

ley

Blo

cks

Pric

e Fo

rmat

R01

S.N

.D

escr

iptio

n of

equ

ipm

ent /

item

Tota

l Qty

re

quird

E&C

cha

rges

in

INR

Serv

ice

tax

@in

clud

ing

cess

on

E& C

in

INR

Tota

l E &

C p

rices

incl

udin

g Se

rvic

eTa

x in

INR

12

34

56

1.0

Tota

l lum

psum

firm

pric

e fo

r rec

eipt

, unl

oadi

ng, s

tora

ge &

ha

ndlin

g at

site

, ere

ctio

n an

d co

mm

issi

onin

g, lo

ad te

stin

g,

trial

run,

han

dlin

g ov

er to

cus

tom

er fo

r the

tota

l sco

pe o

f el

ectri

c ho

ists

and

cha

in p

ulle

y bl

ock

defin

ed a

s per

tech

nica

l sp

ecifi

catio

n P

E-TS

-404

-xxx

-xxx

taki

ng in

to a

ccou

nt a

ll cl

arifi

catio

ns, c

onfir

mat

ions

and

agr

eem

ents

till

date

.

LOT

BR

EA

K U

P FO

R P

RIC

E A

T 1

.01.

1To

tal E

&C

pric

eof

1 N

o. E

lect

ric H

oist

of

5T c

ap fo

r ESP

co

ntro

l roo

m w

ith a

ll ac

cess

orie

s inc

ludi

ng is

olat

ing

switc

h,

DSL

,mai

nten

ance

tool

s and

tack

les,

E&C

spar

es e

tc.

1 no

.

1.2

Tota

l E&

C p

rice

of 1

No.

Elec

tric

Hoi

st o

f 3T

cap

for B

oile

r M

CC

room

with

all

acce

ssor

ies i

nclu

ding

isol

atin

g sw

itch

DSL

,mai

nten

ance

tool

s and

tack

les,

E&C

spar

es e

tc.

1 no

.

1.3

Tota

l E&

C p

rice

of 1

No.

Man

ual H

oist

(Cha

in p

ulle

y bl

ock)

of

2T c

ap fo

r MV

switc

hgea

r with

all

acce

ssor

ies &

m

aint

enan

ce to

ols a

nd ta

ckle

s etc

.

1 no

.

NO

TE

1 2 3 4

Bid

der t

o no

te th

at to

tal p

rice

indi

cate

d ab

ove

at 1

.0 s

hall

be c

onsi

dere

d fo

r eva

luat

ion

and

henc

e sh

ould

be

com

plet

e in

all

resp

ect f

or th

e fu

ll sc

ope

defin

ed

and

cons

ider

ing

all t

erm

s and

con

ditio

ns a

gree

d.

Any

item

not

incl

uded

in th

e pr

ice

quot

ed a

bove

and

show

n se

para

tely

will

not

be

take

n co

gniz

ance

of a

nd th

e of

fer s

hall

be li

able

for r

ejec

tion.

Bid

der t

o no

te th

at in

un-

pric

e bi

d, b

idde

r mus

t ind

icat

e as

"Q

UO

TED

" ag

ains

t uni

t pric

e &

tota

l pric

e co

lum

n. P

rice

shou

ld b

e in

dica

ted

in P

rice

Bid

onl

y.

Pric

es q

uote

d ab

ove

at S

.No.

1.1,

1.2

& 1

.3 o

f pric

e sc

hedu

le sh

all b

e co

nsid

ered

for a

ny a

dditi

onal

scop

e re

quire

men

t of E

lect

ric h

oist

s & c

hain

pul

ley

bloc

ks

durin

g de

tail

engi

neer

ing.

-E&

C

Page 185: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C

Tech Spec No.- PE-TS-401-999-E001; Rev.1

OPTIONAL ITEMS

Page 186: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Board 11kV SwitchboardRating 3150A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Price (Rs.)1 Incomer 3150A DC 12 Tie from Other Switchboard 2750A DE 1

Board 11kV SwitchboardRating 2750A

S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Price (Rs.)1 Incomer 2750A DC 12 Tie from Other Switchboard 2750A DE 1

1X500 MW FGUTPPAnnexure -2J ( Board Wise BOM & Schedule of Unit Prices for 11kV switchboard )

(OPTIONAL ITEM)

Unit rates quoted in Annexure-2J shall be used for any addition /deletion during detail engineering.

Page 187: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

 1X500 MW UCHAHAR FGTPS (UNIT‐6) RECOMMENNDED O SPARES FOR LV SWITCHGEAR,LT BUS DUCT   AND  NGR (OPTIONAL)   ANNEXURE‐3A

RATING(A) BOARD NO.

56RECOMMENDED O & M 

SPARES for LV switchgearNOS. 1 BIDDER TO FURNISH

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufactured

only

Total Supply and E&C in

INRSr.No. ITEM NAME UOM TOTAL QTY.REMARKS

Freight including Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges INR

Service tax @ including cess on E &

C in INR

Total E & C prices

including Service Tax

in INR

PAGE 1 OF 4

123
Text Box
Page 188: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

1 INCOMING FEEDER UNITa) Incoming ACB to PCC/PMCC from Trafo. - Module Type DAET (I/C)

1000A1250A1600A2500A3200A

b) Incoming ACB to MCC - Module Type DAE (I/C)630A800A1000A1250A1600A

c) Incoming ACB to Emergency MCC - Module Type DAE(EMG-I/C)800A1000A1250A

d) MCCB Incomer for MCC / ACDB – Module Type E3 (I/C) (Upto 200A SFU controlled)

Upto 63A – Fixed Type125A – Fixed Type200A – Fixed Type250A – Fixed Type400A – Fixed Type630A – Fixed TypeUpto 63A – Drawout Type (Upto 200A SFU controlled)125A – Drawout Type200A – Drawout Type250A – Drawout Type400A – Drawout Type630A – Drawout Type

e) TPN SFU Incomer for AC Fuse DBs – Module Type H3 (I/C)63A 125A

f) 220V DCDB Incomer from charger - Module type CH 200A – CH Fixed Type400A – CH Fixed Type630A – CH Fixed Type800A – CH Fixed Type200A – CH Drawout Type400A – CH Drawout Type630A – CH Drawout Type800A – CH Drawout Type

g) 220V DCDB Incomer from battery - Module type DB200A – DB Fixed Type400A – DB Fixed Type630A – DB Fixed Type800A – DB Fixed Type200A – DB Drawout Type400A – DB Drawout Type630A – DB Drawout Type800A – DB Drawout Type

h) 220V DC Fuse DB Incomer from DCDB - Module type HD32A 50A 63A

2 BUSCOUPLER UNITa) ACB buscoupler for PCC/PMCC- Module Type DAE (TIE)

1000A1250A1600A2500A3200A

b) ACB buscoupler for PCC/PMCC- Module Type DAE (B/C)630A800A1000A1250A1600A

c) MCCB buscoupler – Module type E3 (B/C) (Upto 200A SFU controlled)UPTO 63A - Fixed Type125A - Fixed Type

PAGE 1 OF 13

Page 189: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

200A - Fixed Type250A - Fixed Type400A - Fixed Type630A - Fixed TypeUPTO 63A - Drawout Type125A - Drawout Type200A - Drawout Type250A - Drawout Type400A - Drawout Type630A - Drawout Type

3 Outgoing ACB supply feeder - Module Type DAE (O/G)630A800A1000A1250A1600A2000A

4 Outgoing ACB MLDB feeder - Module Type DAE (LDB)630A800A

5 Outgoing ACB motor feeder - Module Type DM/PM (controlled from DDCMIS/PLC)

100.1 - 200KW6 DOL Motor Starter - Unidirectional Drive - Drawout Typea) Module Type K2 (Controlled from Local Control Panel)

Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 - 29.9KW

b) Module Type K21 (Controlled from Local Control Panel)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW

c) Module Type K3 (Controlled from Local Push Button Station)Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 - 29.9KW

d) Module Type K31 (Controlled from Local Push Button Station)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW

e) Module Type DK2/AK2/PK2 (Controlled from DDCMIS/ATRS/PLC)Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW

f) Module Type DK21/AK21/PK21 (Controlled from DDCMIS/ATRS/PLC)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW

g) Module Type DKE2/AKE2/PKE2 (Controlled from DDCMIS/ATRS/PLC)Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW

PAGE 2 OF 13

Page 190: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

h) Module Type DKE21/AKE21/PKE21 (Controlled from DDCMIS/ATRS/PLC)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW

7 RDOL Motor Starter – Bidirectional Drive Drawout Typea) Module Type DN1/AN1/PN1 (Controlled from DDCMIS/ATRS/PLC)

Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW

b) Module Type N1 (Controlled from Local Control Panel)Upto 5.5KW5.6-7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW

8 Outgoing MCCB controlled feedersa) Outgoing MCCB controlled supply feeder - Module Type E3 (O/G) up to 200A SFU

controlled.upto 10A - Fixed type16A - Fixed type25A - Fixed type32A - Fixed type63A - Fixed type80A - Fixed type100A - Fixed type125A - Fixed type160A - Fixed type200A - Fixed type250A - Fixed type400A - Fixed type630A - Fixed typeupto 10A - Drawout type (up to 200A SFU controlled)16A - Drawout type25A - Drawout type32A - Drawout type63A - Drawout type80A - Drawout type100A - Drawout type125A - Drawout type160A - Drawout type200A - Drawout type250A - Drawout type400A - Drawout type630A - Drawout type

b) Double pole MCCB controlled 1-ph feeder - E1 (O/G) - Fixed Type (up to 200A SFU controlled)16A25A32A63A125A

c) Double pole MCCB controlled 1-ph feeder - E1 (O/G) - Drawout Type (up to 200A SFU controlled)16A25A32A63A125A

d) 3-Ph MCCB controlled Outgoing contactor feeder (EA3) – Fixed Type (up to 200A SFU controlled)16A25A32A63A

e) 3-Ph MCCB controlled Outgoing contactor feeder (EA3) – Drawout Type (up to 200A SFU controlled)

PAGE 3 OF 13

Page 191: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

16A25A32A63A125A185A200A

f) 1-Ph MCCB controlled Outgoing contactor feeder (EA1) – Fixed Type (up to 200A SFU controlled)16A25A32A63A125A

g) 1-Ph MCCB controlled Outgoing contactor feeder (EA1) – Drawout Type (up to 200A SFU controlled)16A25A32A63A125A

9 Outgoing Switch-fuse feedersa) Outgoing TPN Switch-fuse feeder - Module Type H3 (O/G)

16A25A32A

b) Single phase switch-fuse feeder - H1 (O/G) 16A25A32A

c) 220V DC Outgoing switch fuse feeder (X) 6A10A16A25A32A50A63A100A125A160A200A400A630A

10 Common Auxiliary Modulea) PT module

i Bus PT module for PCC/PMCC-G1ii Bus PT module for Emergency MCC-G2iii Bus PT module for MCC-VMiv Bus PT module for DCDB-Sb) Panel space heating modulec) 110V AC control supply module – Type CS (consisting of 415/110V control Trafo.)

1KVA2KVA2.5KVA3KVA5KVA7.5KVA10KVA

d) 240 V AC control supply module – type CS (consisting of 415/240V control Trafo.)1KVA2KVA2.5KVA3KVA5KVA7.5KVA10KVA

e) 240V AC motor space heater module220V DC supply module(for receiving 220V DC supply)

g) 24 V winding heating moduleh) Alarm module

f)

PAGE 4 OF 13

Page 192: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

i) Test supply module11 Empty Panel with Horizontal & Vertical Busbar, Support & Auxiliary Busbara) MCC Panel (Double Front Drawout Type)

250 / 250A400 / 400A630 / 630A800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A

b) MCC Panel (Double Front Fixed Type)250 / 250A400 / 400A630 / 630A800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A

c) 220V DCDB Panel (Double Front Fixed type) UPTO 800A (with 630A VBB)1000A (with 630A VBB)

d) 220V DCDB Panel (Double Front Drawout type) UPTO 800A (with 630A VBB)1000A (with 630A VBB)

12 Empty Panel With Horizontal & Vertical Busbar, Support & Auxiliary Busbara) PCC Panel (Single Front Drawout Type)

1600 / 1600A2500 / 2500A3200 / 3200A

b) MCC Panel (Single Front Drawout Type)250 / 250A400 / 400A630 / 630A800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A

c) MCC Panel (Single Front Fixed Type )250 / 250A400 / 400A630 / 630A

PAGE 5 OF 13

Page 193: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A

d)  DCDB Panel (Single Front Fixed Type Each Rating)UPTO 800A (with 630A VBB)1000A (with 630A VBB)

e)  DCDB Panel (Single Front Drawout Type Each Rating)UPTO 800A 1000A

13 ACB Panel with Horizontal & Vertical Busbar, Support & Auxiliary Busbar800 / 630A 800 / 800A 1000 / 630A 1000 / 800A 1000 / 1000A 1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A2500 / 630A2500 / 800A2500 / 1000A2500 / 1250A2500 / 1600A2500 / 2500A3200 / 630A3200 / 800A3200 / 1000A3200 / 1250A3200 / 1600A3200 / 2500A3200 / 3200A4000 / 630A4000 / 800A4000 / 1000A4000 / 1250A4000 / 1600A4000 / 2500A4000 / 3200A4000 / 4000A

14 Dummy Panel UPTO 630A800A1000A1250A1600A2500A3200A4000A

15 Unit Prices For Circuit Componentsa) Air Circuit Breaker without releases

630A (M)800A (M)1000A (M)1250A (M)

PAGE 6 OF 13

Page 194: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

630A800A1000A1250A1600A2500A3200A4000A

b) Air circuit breaker (with built-in O/L & S/C releases)630A (M)800A (M)1000A (M)1250A (M)630A800A1000A1250A1600A2500A3200A4000A

c) MCCB (Utilization category-'A')16A25A32A63A80A115A150A185A265A315A400A630A

d) MCCB (Utilization category-'B')16A25A32A63A80A115A150A185A265A315A400A630A

d (i) SFU16A25A32A63A80A115A150A185A265A315A400A630A

e) Switches (AC)-TPNUpto 16A25A32A63A125A250A400A630A

f) Switches (DC)Upto 16A

PAGE 7 OF 13

Page 195: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

25A40A60A100A200A300A400A630A

g) HRC Fuse Links (Offset tag Type)Upto 10A16A25A32A50A63A

h) DIN Type (Blade Contact)Upto 10A16A20A32A36A50A63A80A100A125A160A200A250A315A400AControl Fuse Link

i) Power contactor (AC)16A25A32A63A80A115A185A265A315A400A630A

j) Power contactor (DC)16A25A32A63A80A115A150A185A265A400A

k) Fuse Base UPTO 20A32A50/63A100A250A400A630A

l) Auxiliary contactor AC/DCi) AC Aux. contactor

2NO + 2NC3NO + 3NC4NO + 4NC6NO + 6NC

ii) DC Aux. contactor2NO + 2NC

PAGE 8 OF 13

Page 196: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

3NO + 3NC4NO + 4NC6NO + 6NC

m) Protection RelayVAGM 23CTU 12CTU 32VTT 11VAG 11VAA 11VAJHM 13VAJHM 23CDGM-12CAG 12CAG 34CCUM 21CDG11CDG 31CDG61VDG 14CDV 62CAG 14VAX 31CAG 37CAEM-21VAG-21VAJC-11CTMM-501MOTPROVAA21VTT12VTIGVTU21NUMERICAL RELAY FOR FOLLOWING FUNCTIONS:• SHORT CIRCUIT PROTECTION (51)• EARTH FAULT PROTECTION (51N)• UNDER VOLTAGE PROTECTION (27)• TRIP CIRCUIT SUPERVISION (95)NUMERICAL RELAY FOR FOLLOWING FUNCTIONS:• SHORT CIRCUIT PROTECTION (51)• EARTH FAULT PROTECTION (51N)• TRIP CIRCUIT SUPERVISION (95)Numerical relay for E/F protection for DCDBNumerical Check synchronising RealyNUMERICAL COMPOSITE RELAY for STANDBY E/F,SHORT CIRCUITPROTECTION, E/F PROTECTION, OVER LOAD PROTECTION,RESTRICTED E/F PROTECTION TC SUPERVISION,CB FAILURE PROTECTION,SYNCHRONISING CHECK FEATURE,MASTER TRIP FEATURE,CB MONITERING, UNDER VOLTAGE PROTECTIONWITH METERING OF CURRENT(3 PHASE), VOLTAGE (ALL3 PHASE & PHASE TO NEUTRAL) kW, ACTIVE POWER ,REACTIVE POWER,ENERGY, NEUTRAL CURRENT/RESIDUAL VOLTAGE, (WITH COMMUNICATION USING 61850 PROTOCOL)Check synchronising Realy Type-SKE

n) O/L Relaysi) Thermal O/L relay with SPP

Upto 5.5KW5.6 to 11KW11.1 to 22KW22.1 to 45KW45.1 to 75MW75.1 to 100KW

ii) Heavy Duty Thermal O/L relay with SPPUpto 5.5KW5.6 to 11KW11.1 to 22KW22.1 to 45KW45.1 to 75MW75.1 to 100KW

o) Timer (each type)p) Meter of each type & range

AC ammeter (Digital)AC ammeter (Analog)DC ammeter (Digital)

PAGE 9 OF 13

Page 197: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

DC ammeter (Analog)AC voltmeter (Digital)DC voltmeter (Analog)Wattmeter (3 Phase)Wattmeter (1 Phase)3-PH Electronic KWH Meter with RS485 Port1-PH Electronic KWH Meter with RS485 PortFrequency meter

q) Single Phase Preventor Relayr) MCB (each applicable type & rating)s) Control & Selector Switch And Push Button Stationi) Breaker control switchii) Test/normal/trial selector switchiii) Auto/manual switchiv) Limit switchv) Ammeter selector switchvi) Voltmeter selector switchvii) Synchronisation selector switchviii) Push Button

2NO + 2NC Shrouded1NO + 1NC Shrouded2NO + 2NC Mushroom head stayput2NO + 2NC Lockable type

t) Indicating Lamp Assembly (LED Type)u) CTi) Metering CT

Upto 75/1A100/1A125/1A150/1A200/1A250/1A300/1A400/1A500/1A630/1A800/1A1000/1A1250/1A1600/1A2000/1A2500/1A3200/1A4000/1A

ii) Protection CT (5P20)Upto 75/1A100/1A125/1A150/1A200/1A250/1A300/1A400/1A500/1A630/1A800/1A1000/1A1250/1A1600/1A2000/1A2500/1A3200/1A4000/1A630/5A800/5A1000/5A1250/5A1600/5A2000/5A2500/5A3200/5A

PAGE 10 OF 13

Page 198: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

iii) PS Class CT1600/1A2500/1A3200/1A4000/1A2500/5A3200/5A4000/5A

v) Voltage Transformeri) 415/√3 : 110/√3V, 1ph, 50VAii) 415/√3 : 110/√3V, 1ph, 100VAiii) 415/√3 : 240/√3V, 1ph, 50VAiv) 415/√3 : 240/√3V, 1ph, 100VAw) Toggle switch

16A toggle switchx) Secondary Isolating Contact Blocky) Control Terminal (Fixed)z) Thermostat

aa) 4-20mA Dual Output Current transducerab) 4-20mA Dual Output Voltage transducerac) 4-20mA Dual Output Watt transducerad) 4-20mA Dual Output Frequency transducerae) Interposing relay RE 302 or Eqvt with freewheeling diode & LEDaf) 4-16-20mA Dual Output Current transducerag) 4-16-20mA Dual Output Voltage transducerah) 4-16-20mA Dual Output Watt transducerai) 4-16-20mA Dual Output Frequency transducer16 Foundation Framea) MCC panel

upto 1600A (SF)2500A (SF)3200A (SF)4000A (SF)upto 1600A (DF)2500A (DF)3200A (DF)4000A (DF)

b) 220V DCDB panelSFDF

c) PCC / PMCC panelupto 1600A2500A3200A4000A

17 ACDB i) 12 way with 1-Ph O/G feedersii) 12 way with TPN O/G feedersiii) 20 way with TPN O/G feeders18 LT Busduct & Accessoriesa) Straight run per meter, TPN

1600A2500A3200A

b) 90 Deg. Bend (extra over & above straight run)1600A2500A3200A

c) Termination flexible -TPN set (extra over & above straight run)Copper1600A2500A3200AAluminium1600A2500A3200A

d) Adapter, TPN for equipment terminal connection1600A2500A3200A

PAGE 11 OF 13

Page 199: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

e) Phase cross over chamber 1600A2500A3200A

f) Busduct Supporting Structure per Tong) Expansion joint, TPN in the run of Busduct (extra over & above straight run)

1600A2500A3200A

19 Connection from PMCC/MCC panel to PMCC/MCC panel250A400A630A800A1000A1250A1600A2500A3200A

20 Cable Glands & Lugs: a) Single Compression Cable Glands for cable sizes:

2C X 2.5 Sq. mm. 3C X 2.5 Sq. mm. 5C X 2.5 Sq. mm. 7C X 2.5 Sq. mm. 12C X 2.5 Sq. mm. 16C X 2.5 Sq. mm. 2C X 10 Sq. mm. 2C X 16 Sq. mm. 2C X 25 Sq. mm. 2C X 35 Sq. mm. 3C X 2.5 Sq. mm. 3C X 10 Sq. mm. 3C X 16 Sq. mm. 3C X 25 Sq. mm. 3C X 35 Sq. mm. 3C X 50 Sq. mm. 3C X 70 Sq. mm. 3C X 95 Sq. mm. 3C X 150 Sq. mm. 3C X 185 Sq. mm. 3C X 240 Sq. mm. 3.5C X 300 Sq. mm. 3.5C X 240 Sq. mm. 3.5C X 185 Sq. mm. 3.5C X 95 Sq. mm. 4C X 16 Sq. mm. 4C X 35 Sq. mm. 1C X 35 Sq. mm.1C X 500 Sq. mm. 1C X 630 Sq. mm.

b) Double Compression Cable Glands for cable sizes:2C X 2.5 Sq. mm. 3C X 2.5 Sq. mm. 5C X 2.5 Sq. mm. 7C X 2.5 Sq. mm. 12C X 2.5 Sq. mm. 16C X 2.5 Sq. mm. 2C X 10 Sq. mm. 2C X 16 Sq. mm. 2C X 25 Sq. mm. 2C X 35 Sq. mm. 3C X 2.5 Sq. mm. 3C X 10 Sq. mm. 3C X 16 Sq. mm. 3C X 25 Sq. mm. 3C X 35 Sq. mm. 3C X 50 Sq. mm. 3C X 70 Sq. mm. 3C X 95 Sq. mm. 3C X 150 Sq. mm.

PAGE 12 OF 13

Page 200: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1 X 500 MW FG TPS (STAGE-IV)

LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)

SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)

ANNEXURE-3H

SL.NO.

ITEM DESCRIPTION Unit Ex-works price

3C X 185 Sq. mm. 3C X 240 Sq. mm. 3.5C X 300 Sq. mm. 3.5C X 240 Sq. mm. 3.5C X 185 Sq. mm. 3.5C X 95 Sq. mm. 4C X 16 Sq. mm. 4C X 35 Sq. mm. 1C X 35 Sq. mm.1C X 500 Sq. mm. 1C X 630 Sq. mm.

c) Cable Lugs for sizes:2.5 Sq. mm. 10 Sq. mm. 16 Sq. mm. 25 Sq. mm. 35 Sq. mm. 50 Sq. mm. 70 Sq. mm. 95 Sq. mm. 150 Sq. mm. 185 Sq. mm. 240 Sq. mm. 300 Sq. mm. 500 Sq. mm. 630 Sq. mm.

d) FIBER OPTICAL CABLE (PER METER)21 Daily 8 hour rate deployed at site:

Engineer : (per day)22 Module Name plate23 Wires for Secondary wiring:a) 1.5 Sq. mm. per meterb) 2.5 Sq. mm. per meterc) 4.0 Sq. mm. per meter

24 Control Terminal for Secondary wiring suitable for cable size:a) 0.5 Sq. mm. b) 1.5 Sq. mm. c) 2.5 Sq. mm.

25 Unit price for following tests:a) Local Push Button Station - Degree of protection testb) Local motor Starter - Degree of protection testc) Type tests on NGRi) Heat run test on prototypeii) DOP test for IP 33iii) DOP test for IP 55c) Any other test as per IS / BHEL specification

26 LPBS TYPE-ALPBS TYPE-BLPBS TYPE-C

27 LOCAL MOTOR STARTERLOCAL MOTOR STARTERS 0.37 KWLOCAL MOTOR STARTERS 0.55 KWLOCAL MOTOR STARTERS 0.75 KWLOCAL MOTOR STARTERS 1.10 KWLOCAL MOTOR STARTERS 1.50 KWLOCAL MOTOR STARTERS 2.20 KWLOCAL MOTOR STARTERS 3.70 KWLOCAL MOTOR STARTERS 5.5 KW

28 ANY OTHER ITEM WHICH MAY BE REQUIRED FOR ADDITION / DELETION DURING DETAILED ENGINEERING

Note:Unit Rates as quoted in the Main supply schedule

PAGE 13 OF 13

Page 201: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

1x 500MW FGUTPP STAGE IV

PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)

Item.No Item Type TestTest Charges

(in Rs.)

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in INR

Total Supply and E&C in INR

1 TREFOIL CLAMPS Short Circuit Test (for fault levels and durations specified in the specification)

2 HT TERMINATION KITS Type Tests as per IS:13573 for 11 KV kitsType Tests as per IS:13573 for 3.3 KV kitsType Tests as per VDE 0278 for 3.3 KV kits

3 STRAIGHT THROUGH JOINTING KITS Type Tests as per IS:13573 for 11 KV kitsType Tests as per IS:13573 for 3.3 KV kitsType Tests as per VDE 0278 for 3.3 KV kits

4 JUNCTION BOXImpact resistance for impact energy of 2 Joules (IK07)as per BS EN50102Thermal ageing at 70deg C for 96 hours as per IEC60068-2-2Bb.Class of protection ( IP 55)HV test.

ANNEXURE-4B: TYPE TEST CHARGES (OPTIONAL)

Page 202: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

A TYPE TEST FOR TYPE-A FIRE SEALING SYSTEM(OPTIONAL)TYPE TEST UNIT Unit Price in INR Total Price in INR Excise Duty @ on self

manufactured onlyVAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on Total Price in INR

Total Price including Service Tax

in INR

1Accelerated Ageing Test

LOT

2Water Absorption Test

LOT

3 Fire Rating Test LOT4 Hose Stream Test LOT5

Vibration Test Followed by Fire rating TestLOT

B TYPE TEST FOR TYPE-B FIRE SEALING SYSTEM(OPTIONAL)TYPE TEST UNIT Unit Price in INR Total Price in INR Excise Duty @ on self

manufactured onlyVAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on Total Price in INR

Total Price including Service Tax in INR

1 Accelerated Ageing Test LOT

2 Water Absorption Test LOT

3 Fire Rating Test LOT

4 Hose Stream Test LOT

5Vibration Test Followed by Fire rating Test

LOT

Notes:‐

1 For Type Tests refer clause no. 6.0 of Section‐C of Part ‐B of specification

FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)

ANNEXURE- 5B

PRICE SCHEDULE FOR TYPE TEST OF FIRE SEALING SYSTEM (OPTIONAL)

Page 203: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

s.no. CIVIL WORKS(OPTIONAL)

DESCRIPTION UNIT Unit Price in INR Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

Service tax @ including cess on Unit Price in INR

Unit Price including Service

Tax in INR

a ENLARGEMENT OF PENETRATION AREA IN

SQM

a1 BRICK WALL SQMa2 CONCRETE WALL SQMa3 FLOORS SQMb REDUCTION OF PENETRATION

AREA INb1 BRICK WALL SQMb2 CONCRETE WALL SQMb3 FLOORS SQM

Notes-

1Unit rates for civil works shall be as per clause no. 8.3 (e) of Section-D of Part-B of specification.

FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)

ANNEXURE- 5B

PRICE SCHEDULE FOR CIVIL WORKS OF FIRE SEALING SYSTEM (OPTIONAL)

Page 204: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on

self manufactur

ed only

VAT/CST @ … in INR on

self manufactur

ed only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection & Commissio

ning Charges

INR

Service tax @ including cess on E & C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C in INR

(B) OPTIONAL ITEMS1.0

O & M SPARES FOR 220V BATTERY(BIDDER TOFURNISH THE LIST)

LOT 1

2.0

INCREMENTAL INCREASE/DECREASE IN BATTERY RATING*

*Unit rate of additional price applicable for battery charger capacity increase/decrease by 10AH

NOS 1

3.0SUPERVISION CHARGES OF COMMISSIONING OF220V DC BATTERY)

LOT 1

4.0SUPERVISION CHARGES OF ERECTION &COMMISSIONING OF 220V DC BATTERY) SET 1

5.0 SUPV. OF E & C- MANDAY RATE SET 1

6.0 SUPV. OF E & C- TRAVEL CHARGE SET 1

7.0 TYPE TEST

a DISCHARGE PERFORMANCE AT LOW TEMPERETURE LOT 1

b LIFE CYCLE TEST LOT 1

c AIR PRESSURE TEST LOT 1

d VARIFICATION OF CONSTRUCTIONAL REQUIREMENT LOT 1

e ENVIRONMENTAL TEST LOT 1

f INSUALATION RESISTANCE TEST LOT 1

Note: Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering.

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9BBOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (NI-CD Battery)

Page 1 of 1

Page 205: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR (6+7+8+9)

Total Erection & Commissioning Charges INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax (11+12) in INR

Total Supply and E&C in INR

(B) OPTIONAL ITEMS1.0

O & M SPARES FOR 220V BATTERY(BIDDER TOFURNISH THE LIST) LOT 1

2.0

INCREMENTAL INCREASE/DECREASE IN BATTERY RATING*

*Unit rate of additional price applicable for battery charger capacity increase/decrease by 10AH

NOS 1

3.0 SUPERVISION CHARGES OF COMMISSIONING OF220V DC BATTERY)

LOT 1

4.0SUPERVISION CHARGES OF ERECTION &COMMISSIONING OF 220V DC BATTERY) SET 1

5.0 SUPV. OF E & C- MANDAY RATE SET 1

6.0 SUPV. OF E & C- TRAVEL CHARGE SET 1

7.0 TYPE TEST

aTEST FOR CAPACITY- TEST FOR VOLTAGE DURING DISCHJARGE

LOT 1

d TEST FOR CHARGE RETENTION/ LOSS OF CAPACITY LOT 1

c AMPERE HOUR AND WATT-HOUR EFFICIENCY TEST LOT 1

d ENDURANCE TEST. LOT 1

Note: Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering.

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9BBOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (LEAD -ACID PLANTE)

Page 1 of 1

Page 206: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE 9C

Sr. No. Item Description Unit QuantityRemarks

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed

in INR/Total Price.

Excise Duty @ on

self manufactur

ed only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service

Tax in INR

Total Supply and E&C in INR

OPTIONAL ITEMS

1INCREMENTAL INCREASE/DECREASE IN CHARGER RATING*

NOS 1*Unit rate of additional price applicable for battery charger capacity increase/decrease by 20A

2INCREMENTAL INCREASE/ DECREASE IN DISCH RESISTOR RATING*

NOS 1*Unit rate of additional price applicable for discharge resistor capacity increase/decrease by 20A

3SUPERVISION OF COMMISSIONING SET 1

Supervision of commissioning activities of 220V DC & Float cum-Boost charger

4 SUPV.OF E&C SET 1 Supervision of E & C activities of 220V DC Float-cum-Boost charger

BOQ CUM UNPRICED PRICE SCHEDULE FOR SUPPLY OF 220V DC BATTERY CHARGER

CABLE GLANDS AND LUGS AT CHARGER AND FUSE BOX END SHALL BE IN BIDDERS SCOPE. TENTATIVE CABLE SIZE ARE MENTIONED IN DATASHEET-A. NOTE:

Page 207: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL.NO. ITEM QTY. Unit Price in INR Total Price in INR Excise Duty @ on self

manufactured onlyVAT/CST @ … in INR on self

manufactured onlyFreight including

Service tax @Total FOR Site Price (Supply) in

INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on Total Price in INR

Total Price including Service Tax in INR

Training of Engineers:

(Optional)

a) Basic cost [irrespective of no. of engineers]

b) Additional variable cost per engineer

ANNEXURE 10Training for GCB

7 1 Set

Page 208: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11A

Item DESCRIPTION QTY. UnitUNIT RATE ITEMS

1 Main distribution frame (MDF) 200 pairs 1 No.

2 Sub-distribution frame (SDF) 30 pairs 1 No.

3 Signal line booster unit [housed in FRP enclosure] 1 No.

4 Loud Speaker junction box 1 No.

5 Junction box (Die cast Al material) 1 No.

6 Master control station junction box 1 No.

7 Looping junction 1 No.

8 Flameproof field call station with handset 4 W cone type speaker. 1 No.

9 Flameproof field call station with handset 15 W horn type speaker. 1 No.

10 Power supply unit [48V DC] 1 No.

11 Wall/column mounted, weatherproof field call station with hand freemicrophone & speaker and built-in power amplifier

1 No.

12 Sound protecting booth 1 No.

Service tax @ including cess

on E & C in INR

Total E & C prices including Service Tax in

INR

SUPPLY (Rs)

Total Ex-Works Price duly packed in

INR/Total Price.

Unit Ex-works price/Unit Price

Excise Duty @ on self

manufactured only

1 X 500 MW FGUTPP STAGE-IV - Price Schedule Optional Items for Public Address System

Total Supply and E&C in

INR

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges INR

Page 209: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11A

Item No. DESCRIPTION QTY. Unit

TYPE TESTS

1.0 All type tests as per relevant standard shall be conducted on one piece of the following items:

1.1 Amplifier, as per IS-9302 Part-II 1 No.1.2 Microphone, as per IS-9302 Part-III 1 No.

1.3 Loudspeaker, as per IS-9302 Part-IV 1 No.

2.0 All type tests as per relevant standard shall be conducted on one piece of all solid state equipment/systems:

2.1Surge protections test

1 No.

2.2 Dry heat test as per IEC-68-2-2 1 No.

2.3 Damp heat test as per IEC-68-3 1 No.2.4 Vibration test as per IEC-68-2-6 1 No.2 5 1 N

1 X 500 MW FGUTPP STAGE-IV - Price Schedule Type Test for Public Address System[OPTIONAL]

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufactured

only

Freight including

Service tax @

TYPE TEST CHARGES

in INR

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including

cess in INR

Total Charges including

Service Tax in INR

Unit Ex-works price/Unit

Price

Total Ex-Works Price duly packed in INR/Total

Price.

2.5 Electrostatic discharge test as per IEC-801-2 or equivalent 1 No.2.6 Radio frequency immunity test as per IEC-801-6 or equivalent 1 No.2.7 Electromagnetic immunity test as per IEC-801-3 or equivalent 1 No.

NOTE:1. Bidder to indicate lump sum charges for conducting all type tests as per relevant standard on one piece.

Page 210: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11A

Sl No. DESCRIPTION QTY. Unit RemarksRECOMMENDED SPARES

1 Recommended spares for 3 years * ** Nos.

* Bidder to furnish the list** Bidder to furnish the quantity

Total Supply and E&C in

INR

Total Ex-Works Price duly packed in INR/Total Price.

Unit Ex-works price/Unit Price

Excise Duty including cess @ ……Rs

VAT/CST @ … in INR on self manufactured

only

1 X 500 MW FGUTPP STAGE-IV- Price Schedule Recommended Spares for Public Address System [OPTIONAL]

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

Page 211: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11A

Sl No. DESCRIPTION SUPERVISION CHARGES

1 Charges for erection supervision, testing & commissioning for complete PA system. [Instruments required for testing & commissioning shall be arranged by the bidder].

Unit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Freight including

Service tax @

1 X 500 MW FGUTPP STAGE-IV - Price Schedule supervision charges for Public Address System[OPTIONAL]

Total FOR Site Price

(Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service Tax in

INR

NOTE:1. Lump sum charges quoted by the bidder shall be firm irrespective of variation in the supply BOQ of main equipment during the contract.

Page 212: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

ANNEXURE-11A

Item No. DESCRIPTION UOM Lump sum charges (Rs)

Training of Engineers:

(Optional)

a) Basic cost [irrespective of no. of engineers]

b) Additional variable cost per engineer

1 Set

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

1 X 500 MW FGUTPP STAGE-IV - Price Schedule Training requirement for Public Address System (Optional)

Service tax @ including cess in

INR

Total Charges including Service Tax

in INR

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges INR

1

Page 213: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

B. OPTIONAL ITEM

S.No Description Unit Qty

Unit Ex-works

price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on

self manufacture

d only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess on E &

C in INR

Total E & C prices

including Service Tax

in INR

Total Supply and E&C in

INR

I 3.3/0.433KV Indoor Transformer 

(Dry Type)

1 2.5 MVA,3.3/0.433KV Indoor 

Transformers (Dry Type)

Nos 2

II Mandatory Spares

1 For above 3.3/0.433KV 2.5 MVA 

Transformer

1.1 HV Bushing Nos 1

1.2 LV Bushing Nos 1

1.3 LV Neutral  Nos 1

1.4 Complete Winding Limb (HV and LV) Nos 1

1.5 WTI Nos 1

1.6 Set of Thermistor / RTD with 

associated leads complete for one 

transformer

Nos 1

SL. NO.

DESCRIPTION

Unit Price

Total Ex-Works

Price duly packed in INR/Total

Price.

Excise Duty @ on self

manufactured only

Freight including

Service tax @

Total FOR Site Price

(Supply) in INR

Total Erection &

Commissioning Charges

INR

Service tax @ including cess in INR

Total Price including

Service Tax in INR

1 SHORT CIRCUIT TEST

2 NOISE LEVEL MEASUREMENT

3MEASUREMENT OF  ZERO PHASE 

SEQUENCE IMPEDANCE

4 MEASUREMENT OF THE 

HARMINICS OF NO LOAD 

CURRENT

5 TEMPERATURE RISE

6LIGHTING IMPULSE VOLTAGE 

TEST ON ALL THE THREE LIMBS 

AS PER CL. 14.1 OF IEC 60076‐3

7 DEGREE OF PROTECTION TEST 

ON MARSHALLING BOX, CABLE 

BOX AND ENCLOSURE.

i). SUPPLY ITEMS

ii). TYPE TEST FOR 2.0/2.5 MVA,3.3/0.433KV Indoor Transformers (Dry Type).

Note: Transformer shall be short circuited tested after conducting the routine tests. Rest of the type tests shall be conducted after successful short circuit testing.

Annexure‐12 (Price Schedule/BOM ofDry Type Transformer)

Page 214: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Bill of quantity of Erection and commissioning of Dry Type Transformers B. OPTIONAL ITEM

S.No Description Unit Qty

Unit Erection & Commissioning Charges in INR

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty including cess

@ ……Rs

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self manufactured

only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissioning Charges in INR

Service tax @ including cess

on E & C in INR

Total E & C prices including Service Tax in

INR

1 2.5 MVA,3.3/0.433 kV 

Indoor Transformers 

(Dry Type)

Nos 2

i). SUPPLY ITEMS

Page 215: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

 1X500 MW UNCHAHAR FGTPS (UNIT‐6) RECOMMENNDED O SPARES FOR AUXILARY SERVICE TRANSFORMER(OIL FILLED)   (OPTIONAL)   ANNEXURE‐13E

RATING(A) BOARD NO.

56RECOMMENDED O & M SPARES for 

3years OperationNOS. 1 BIDDER TO FURNISH

Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in

INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in INR on self

manufactured only

Total Supply and E&C in

INRSr.No. ITEM NAME UOM TOTAL QTY.

REMARKS Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection &

Commissioning Charges INR

Service tax @ including cess

on E & C in INR

Total E & C prices

including Service Tax in

INR

PAGE 1 OF 4

123
Text Box
Page 216: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

Sl.no. DESCRIPTION UNIT Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total

Price.

Excise Duty @ on self manufactured only

VAT/CST @ … in INR on self manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning Charges

INR

Service tax @ including cess on E & C in INR

Total E & C prices including Service Tax in

INR

Total Supply and E&C in INR

1Desktop/Wall mounted Push button operated decadic type Telephone Set

Nos

2 PVC & Jelly filled Cables Meter

Optional prices for EPABX system

Page 217: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

DESCRIPTION UNIT QTY Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self

manufactured only

VAT/CST @ … in

INR on self manufactu

red only

Freight including

Service tax @

Total FOR Site Price (Supply)

in INR

Total Erection & Commissi

oning Charges

INR

Service tax @

including cess on E & C in INR

Total E & C prices

including Service

Tax in INR

Total Supply

and E&C in INR

11kV, 3150A LENGTH METER 5090 deg Bend NOS. 8

TRANSFORMER TERMINATIONS NOS. 1

SWITCHGEAR TERMINATIONS NOS. 1

TEE CONNECTION NOS. 0

WALL FRAME ASSEMBLY NOS. 1TOTAL PRICE 11kV, 2750A LENGTH METER 13090 deg Bend NOS. 22

TRANSFORMER TERMINATIONS NOS. 2

SWITCHGEAR TERMINATIONS NOS. 5

TEE CONNECTION NOS. 1

WALL FRAME ASSEMBLY NOS. 2TOTAL PRICE 3.3kV, 3000A LENGTH METER 9090 deg Bend NOS. 12TRANSFORMER TERMINATIONS NOS. 2SWITCHGEAR TERMINATIONS NOS. 4WALL FRAME ASSEMBLY NOS. 2TOTAL PRICE 3.3kV, 2500A LENGTH METER 4090 deg Bend NOS. 4TRANSFORMER TERMINATIONS NOS. 2SWITCHGEAR TERMINATIONS NOS. 2WALL FRAME ASSEMBLY NOS. 2TOTAL PRICE Supporting structure (hot dip galvanized MS), foundation channels, hardware etc. Suitable for bus ductelevation and length involved.

As required forcomplete scope

BOQ CUM UNPRICED SCHEDULE OF 11KV & 3.3KV SEGRAGATED PHASE BUSDUCT (OPTIONAL)

ANNEXURE-1

Unit rates quoted here shall be used for any addition /deletion during detail engineering.

Page 218: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

SL NO ITEM DESCRIPTION UNIT QTY Unit Ex-works price/Unit Price

Total Ex-Works Price duly packed in INR/Total Price.

Excise Duty @ on self manufactured

only

VAT/CST @ … in INR on self

manufactured only

Freight including Service tax @

Total FOR Site Price (Supply) in INR

Total Erection & Commissioning

Charges INR

Service tax @ including cess on E

& C in INR

Total E & C prices including Service

Tax in INR

SEGREGATED PHASE BUS DUCT

Transportation from stores / storage yardto erection site, assembly, erection,welding, testing & commissioning ofSegregated Phase Bus Duct forinterconnection of Unit/StationTransformers to 11kV Switch Boards

2750ASPBD from Unit Transformers to 11 kV UnitSwitch BoardSPBD for interconnection of 11kV Unit Switchboard to 11 kV Station Switch Board (Approx. total length 150 Mtr)

3150ASPBD from Station Transformer to 11 kVStation Switch Board (Approx. total length 60 Mtr)

3000ASPBD from Unit Aux. Transformer to 3.3 kVSwitch Board Approx. Total length 100 Mtr

2500ASPBD from Misc Transformer to 3.3 kV SwitchBoard Approx. Total length 50 Mtr

Unit rates quoted here shall be used for any addition /deletion during detail engineering.

3 SET 3

1

Annexure-1Bill of quantity of Erection and commissioning (OPTIONAL)

1 SET 5

2 SET

4 SET 2

Page 219: VOLUME-IIIE-ANNEXURES, FORMATS ETC - NBPPLnbppl.in/uploads/corr_file_pdf/Corrigendum-2_E-41034_Pre_bid... · VOLUME-IIIE-ANNEXURES, FORMATS ETC NTPC BHEL POWER PROJECTS PVT LTD 3

TITLE: 1 X 500 MW UNCHAHAR TPP STAGE-IV

TECHNICAL SPECIFICATION FOR

ELECTRIC HOIST AND MANUAL HOIST

SPECIFICATION NO. PE-TS-404-xxx-xxx

VOLUME - I

SECTION - C1(Mech) SUB SECTION - II

REV.NO. 0 DATE :

SHEET

ANNEXURE IV

1.1.0 ELECTRIC HOIST AND MANUAL HOIST (CHAIN PULLEY BLOCK)

Required number of electric hoist / manual hoist of adequate capacity, to meet the erection and maintenance requirements are to be provided for the various areas. Manual hoists (hand operated) shall be designed to duty class 2 as per IS 3832 and electric wire rope hoist shall be designed as per lS: 3938 (latest). The stipulations of all statutory codes like Indian Electricity Act, Indian Electricity Rules, Factory Acts, Local Municipality act etc. shall however prevail over the specification requirements, in case any conflict arises between this specification and the statutory codes. Maintenance tools and tackles shall be as per data sheet attached. DESIGN CRITERIA For the hoists with more than 2.0 tonne lifting capacity or more than 10.0 M lift, Electrical hoist shall be provided. Other hoist blocks shall be of hand operated type for both travel and lift. However, all monorails coming out of the building shall be provided with electric hoist block, irrespective of load and lift. Capacity of electric and manual (Chain pulley block) hoists shall be decided keeping 25% margin over equipment to be handled. For hand operated hoists, the hoists shall be suitable for operation from floor level. Hand chain shall be provided for long travel of trolley and the Hoisting mechanism. The operator shall be able to control the movement of the electrical/ manual hoist with the help of floor operated pendant

MINIMUM LIFTING REQUIREMENT

S.N. AREA DESCRIPTION QTY(nos) CAPACITY(T) TYPE 1 ESP control room ( below

16.7 m)

1 5T

Electric hoist

2 Boiler MCC Room 1 3T Electric hoist 3 MV Switchgear Room 1 2T Manual Hoist

Note; 1. Area, type, capacity mentioned are minimum requirement and any additional requirement shall be

finalised during detail engineering without any commercial implication 2. Travel and Lift are layout dependent and shall be finalised during detail engineering without any

commercial implication 3. Additional electric/manual hoist required during detail engineering shall be provided as per design

criteria given above without any commercial implication.