ANNEXURE II
TECHNICAL CLARIFICATIONS TO BIDDERS’ QUERIES
JOB Electrical Systems FGUTPP Stage-IV (1X500 MW) TENDERNO NBPPL/MM/FGUTPP/E-41034/14
Sr. No.
Reference clause of tender document
Existing provision Bidder’s query NBPPL’s clarification
I. Volume I - General/ Spec. No. - PE-TS-401-999-E001 1 Clause 2.5,
Quantity Variation Clause/ Page 19 of 1481
VARIATION OF QUANTITIES MAY BE TO THE EXTENT OF +/-30% OF TOTAL CONTRACT VALUE.
Please note that the price shall remain firm for the rating and BOQ specified in tender documents. For any increase or decrease beyond the quantity specified in tender documents, the same shall be subject to price implication as per unit rates specified in Price Schedule.
Please refer GCC Clause No: 6.1
2 Annexure-1 Vendor List/ Page 24 of 1481
2. Medium Voltage Busduct We request to please approve "(i). C&S (ii). Entraco (iii). Powergear (iv). Busbar System (v). Entraco" in the makelist of Medium Voltage Busduct.
Please refer Clause No: 2.3.22 of Scope of Enquiry of Technical specifications Volume-I
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
3 Annexure-1 Vendor List/ Page 24 of 1481
6. LT Outdoor Transformer We request to please approve "ABB Make" in the makelist of LT Outdoor Transformers.
Please refer Clause No: 2.3.22 of Scope of Enquiry of Technical specifications Volume-I
4 Annexure-1 Vendor List/ Page 24 of 1481
7. LT Switchgear We request to please approve "ABB Make" in the makelist of LT Switchgear.
Please refer Clause No: 2.3.22 of Scope of Enquiry of Technical specifications Volume-I
5 General Please note that the equipment quoted as a part of complete electrical system are not for Part Ordering and shall be treated under one electrical package as per the BOQ/Quantity estimated by NBPPL. Bidder shall not be responsible for estimation from the given layouts. Quantity provided in BOQ is treated final for ordering during execution.
Follow Technical Specifications
II. Vol II Part-B - TECHNICAL SPECIFICATIONS OF ELECTRICAL SYSTEMS, DOC. NO.: NBPPL-004-201-00-P4E-A 6 General Technical
TECHNICAL SPECIFICATION SECTION - VI PART-C, Cl 5.01.00 & Cl 5.02.00 /Page 2 of 75 OR Page
In addition to the codes and standards specifically mentioned in the relevant technical specifications for the equipment ……………………………...India as well as
Please note that we shall follow equipment specific relevant Indian Standards i.e. IS or IEC/IEEE standards only inline with applicable Statutory regulations if any.
Follow specifications – respective package standards as mentioned in specs shall be followed
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
50 of 1481 of the locality where..................
7 General Technical TECHNICAL SPECIFICATION SECTION - VI PART-C, Cl 5.06.00/Page 4 of 75 OR Page 52 of 1481
Two (2) English language copies of all national and international codes and/or standards used in the design of the plant……………….from the date of the Notification of Award.
Please note that Codes and standards cannot be duplicated. However we shall provide the list of the codes / standards related to the equipment supplied by us during detailed engineering. The same can be directly purchased by Client from the relevant governing authorities.
Follow GTR provided by NTPC
MV Busduct - Technical Specification Vol II Part-B, Doc No. - PE-TS-401-505-E002 8 Cl 3.05.02 /Page
220 of 1481 The design of the support structure shall conform to IS:800. the support structure shall also be designed to take care of Employer's cable tray load of 100 kg/ metre.
Please note that It is not recommended to load cable tray on the same support structure of SPBD and cables shall be routed separately.
Bidder to follow the technical specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
9 Cl 3.06.01/Page 220 of 1481
A continuous 65 x 8 mm galvanised mild steel earth bar shall be provided along the entire run of each busduct. Each section of the busduct enclosure shall be bonded to this earth bar at least at both ends of the enclosure.
Earthing busbar size shall be capable of system fault current & duration. Continuous earth busbar shall be provided only on one side of enclosure. Other side provision of earth busbar shall be given.
Bidder to follow the technical specifications
10 Cl 3.09.02/Page 221 of 1481
The paints shall consist of one coat of primer followed by one anti-corrosive coat for steel structures. Finally two coast of finishing paint shall be given. The final colour shade shall be BLUE RAL: 5012.
Please note that all the steel structures shall be hot dip galvanized only. Painting is not applicable for the structures. Painting procedure shall be manufacturer specific only. Color coding mentioned will be followed as per specification.
Bidder to follow the technical specifications
11 Cl 4.02.00 Page 223 of 1481
Type test to be conducted on Medium Voltage Busduct (Each rating)…………….
Please note that we shall submit only relevant type test reports conducted within last ten years from date of bid opening and no conduction of type test is envisaged by us.
Bidder to follow the technical specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
12 Cl 4.03.00 Page 215 of 1474/Cl 5.00.00 (f) Page 223 of 1481
Radiography Test (RT) shall be conducted as follow: 1. 2% on Enclosure (Circumferential and Longitudinal Butt weld joints) 2. 10% on Flexible conductor 10% radiography and 100% DP test on all site welded joints of busbar and enclosure.
Please note that Radiography Test is not applicable for MV Busduct. Hence the same shall not be conducted.
Bidder to follow the technical specifications
13 Annexure-A Sl. No.18 (e)/Page 225 of 1481
Material of insulator : Porcelain / Cast resin.
Please note that Insulator material shall be porcelain / cast resin / FRP type.
Bidder to follow the technical specifications
MV SWITCHGEAR - Technical Specification Vol II Part-B, Section - VI Part-B, Subsection-B-07(A) 33kV/11kV/6.kV6/3.3kV (HT Switchgear) 14 Cl 3.00.00(b)(2)
Page 253 of 1481 Temperature rise allowed for busbars shall be 40 deg.C for plain joints and 55 deg.C for silver plated joints.
Please note that Aluminium busbar with tempraure rise above ambient as per IEC 62271-200 i..e end temp of 115 deg C for Silver plated joint shalle be considered as per type tested OEM design.
Bidder to follow the technical specifications
15 Cl 4.01.00 (e)/Page 256 of 1481
The VT/relay compartments shall have degree of protection not less than IP 5X in
Please note that entire enclosure including relay / VT compartment will be IP 4X protection.
Bidder to follow the technical specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
accordance with…………………………
16 Cl 4.01.00 (f)/Page 257 of 1481
The Switchgear shall have an Internal Arc Classification………………….
Please note that inline with this clause we have already carried out Internal arc test. Test report for same shall be submitted during Detail engineering, we do not envisage any repetiiton of type tests
Bidder to follow the technical specifications
17 Cl 4.01.00 (o) /Page 258 of 1481
Suitable base frames made out of steel channels shall be supplied
Please note that Foundation frames shall be as per manufacturer standard shall be supplied.
Bidder to follow the technical specifications
18 Cl 4.06.00 (d)/Page 262 of 1481
Busbars and Insulators - All busbars shall be color coded
Please note that Busbars are HT sleeved and hence can not be color coded however stickers will be provided on rear cover for phase identification
Bidder to follow the technical specifications; colored HT sleeves shall be provided by the bidder.
19 Cl 4.08.00 (d)/Page 263of 1481
Painting Painting : We have offered panels made up of special material called "Alu Zinc". Alu Zinc is light in weight, has more strength, and extremely corrosion resistant compared to normal CRCA sheets and this does not require any surface treatment like powder coating. Panels shall be made up of Alu Zinc material except front doors & end covers which shall be painted sheet steel. We
Bidder to follow the technical specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
shall provide powder coated paint only for front doors and end covers, which shall be made of CRCA sheet. However, painting procedure and thickness shall be as per our standard procedure.
20 Cl 5.01.00 (b)/Page 269 of 1481
Type tests Please note that we shall submit only relevant type test reports conducted within last ten years from date of bid opening and no conduction of type test is envisaged by us.
Bidder to follow the technical specifications
21 Cl 5.03 (b)/Page 270 of 1481
Testing to observe compliance………………………………IP5X- It shall not be possible to insert……………
As per specification IP 5X for VT/Relay compartment to be verified by IP-5X: It shall not be possible to insert a thin sheet of paper under gaskets and through enclosure joints Same way compliance to IP 5X will be demonstarted during FAT
Point withdrawn by bidder
LV SWITCHGEAR, LT Busduct& NGR - Technical Specification Vol II Part-B, Spec No PE-TS-401-506-E001
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
22 Cl 4.02.00 Page 379 of 1481
All switchboard frames and load bearing members shall be fabricated………………………………………………………………….or hot / cold-rolled sheet steel and 4.0 mm for non-magnetic material
Please note that the Doors &Covers ( Both internal & external surface ) material & painting as per NTPC technical specification. However , all the internal parts like Structure Frame, Modules, Base plate etc. shall be hot dip galvanised sheet steel of grade GSM 275 without any painting. This GSM 275 grade galvanised sheet steel has many advantages over conventional CR sheet steel. Kindly give us your acceptance for same.
Point withdrawn by bidder.
23 Cl 4.05.00 Page 380 of 1481
All switchboards shall be of dust-proof and vermin-proof construction and shall be provided with a degree of protection of IP: 5X as per IS/IEC 60947……………………………………..shall be provided with EPDM / Neoprene gaskets
Please note that the Degree of protection of complete switchboard shall be as per NTPC specification & in line with IEC 60529 as under. a) IP-54 upto 1600 Amps switchboard rating. b) IP-42 above 1600A switchboard rating. Separate IP rating for busbar chamber for switchboard is not envisaged / applicable. Further, we would like to clarify that during withdrawable of ACB modules, necessary IP 5X shall be ensured with Acrylic cover on the ACB door. However,
Point withdrawn
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
in case of Non-ACB starter modules, doors are integral part of modules & hence, IP-5X shall be ensured with additional blanking plate which shall be supplied loose with adequate quantities for each size of the modules.
24 Cl 4.09.00 Page 380 of 1481
Switchboards shall be supplied with base frames made of structural steel sections, along with all necessary mounting hardware………………………. not obstruct the movement of doors, covers, with draw able modules etc.
As per our standard, switchboard consist of 50mm integral base frame which can be mounted directly on the finished floor suitable for welded/bolted arrangement. However it is recommended to mount on the additional 50mm base frame incase of false floor which shall be mutually discussed & agreed upon in the event of order.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
25 Cl 4.10.00 (a) Page 380 of 1481
Busbar Compartment- A completely enclosed bus bar compartment shall be provided for the horizontal and vertical busbars. Bolted covers shall be provided............................................. Auxiliary and power busbars shall be in separate compartments.
Please note that a completely enclosed busbar compartment shall be provided for Main busbar and vertical busbar . However for drawout design , Vertical busbar ( With air clearance of 20 mm between the phases ) shall be completely encapsulated using halogen free Arc Resistant plastic material with opening only for engaging the plugin contacts(IP2X) to achive fault free zone between Main Busbar and the individual outgoing feeder Main switching device . Arc fault free Zone reduces the chances of any fault in the non protected area of switchboard thereby results into highest safety of the operator and higher life to the switchboard. This is one of additional safety feature ia available in the drawout type MCC to ensure internal arc as per IEC 61641 for vertical busbars.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
26 Cl 4.10.00 (c) Page 381 of 1481
CABLE COMPARTMENT OR CABLE ALLEY A full-height vertical cable alley of minimum 250mm width shall be provided for power and control cables...............................furnish suitable plugs to cover the cable openings in the partition between feeder compartment and cablealley. Cable alley door shall be hinged.
Please note that a full height cable alley of 200mm or 400mm width shall be provided in MCC cubicle for power & control cable terminaltion as required based on the cable size. Cable termination located in cable alley shall be designed to meet the Form 4b constructions as per IEC 60439 standards. Please note that Form 4b-Type 7 is not as per the IEC standard & hence same is not applicable for IEC complaint switchgear (Refer Annexure-D of IEC60439 for information on Form of segregation).
Point withdrawn by bidder
27 Cl 6.03.00 Page 384 of 1481
All busbars shall be adequately supported by non-hygroscopic, non-combustible, track-resistant and high strength sheet …………………………...The busbar insulators shall be supported on the main structure.
As per our standard design the Busbar supports are common for phases and Neutral. Both Horizontal & vertical busbar system is tested for Short circuit withstand with same supports. Antitracking barriers are not envisaged as we have adequate clearance between phases & Neutral.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
28 Cl 6.04.00 Page 385 of 1481
All busbar joints shall be provided with high tensile steel bolts, belleville / spring washers and nuts, so as to ensure good contacts at the joints.
Please note that all busbar joints shall be provided with high tensile steel bolts coated with WSH-ESLOK- Thread locking compound ( SPOT - COATING ) with possibility of dismantled and retightened up to 10 times and still offering sufficient thread locking effect . “Dry-type” (polyamide) used for ESLOK (MNS standard) is an abrasion-resistant coating ofpolyamide on an exactly defined area (spot coating) of the thread. This guarantees an efficient and practically approved clamping protection against loosening. This arrangement in turn avoid any possibility of overheating of Busbar joints during operation of switchboard.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
29 Cl 7.00.00 Page 385 of 1481
AUXILIARY BUSBARS AND CONTROL TRANSFORMERS
Please note that Auxiliary bus is wire bus which are inter connected through terminals. We use maximum size of wire 6 sq mm copper from the safety angle, this is acceptable to all major customers/consultants . As the load meant for Auxiliary supply is lower range, 6 sq mm copper wire bus can withstand the auxiliary load. This concept is being used in all application and the same is accepted worldwide. Please confirm.
Point withdrawn by bidder
30 Cl 24.09.00 Page 401 of 1481
All connections from vertical busbars for individual modules above…………………………...colour coded wire insulation / tapes shall be provided.
All connection from the vertical busbar to switch/fuses in the modules with rating upto 400A shall be made with Double insulated halogen free cable as per MNS design. This shall minimize phase to phase and phase to earth fault and so as to avoid fault free zone.
Point withdrawn by bidder
31 Sec-D, Cl 1.15(b), Sheet 17 of 23 OR Page 474 of 1481
Enclosure inside : RAL 5012 (Powder coated)
Please note that Enclosure of NSPBD shall be matt black as per manufacturer standard for better heat absorbtion.
Point withdrawn by bidder
32 Sec-D, Cl 2.1, Sheet 17 of 23, OR Page 474 of 1481
Material of insulator : Porcelain / Cast resin.
Insulator material shall be porcelain / cast resin / FRP/ SMC type. Please confirm.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
CABLING, EARTHING & LIGHTING PROTECTION SYSTEMS (INSTALLATION), Doc No. PE–TS–401–507–E006, Vol II Part-B
33 Cl 8.2 of CABLING, EARTHING & LIGHTNING PROTECTION SYSTEMS (SUPPLY), PE-TS-401-507-E006
Only 70% of the Ordered Quantity shall be considered as confirmed quantity as indicated in Lot-I quantitites of BOQ and shall be released for manufacture along with LOI/PO.
Please note that quantity given in BOQ is considered as firm quantity for quoting and final ordering after the award of contract. Any addition/deletion beyond the quantity specified in BOQ shall be mutually discussed and agreed upon during detailed engineering/execution.
Point withdrawn by bidder
Battery & Battery Charger, Doc No. PE-TS-401-508-E001, Vol II
34 DC battery Clause 6.01 Page 926 of 1481
Bidder to furnish sizing calculations in support of the battery Capacity chosen by Bidder.
Please provide DC load list for battery sizing in addition to the load cycle provided in the specification. This supercedes the battery rating mentioned in the page 950 of 1481 clause no.1.00.00
Bidder to follow Specifications
35 DC battery Clause 7.1 Page 928 of 1481
The batteries shall meet the ‘Load Duty Cycle’ requirements under all site-operating conditions as specified. For the purpose of design an ambient temperature of 50 degree centigrade and relative humidity of 85% shall
Please note that Battery shall be sized on 10deg C higher temp. from the minimum electrolyte temp.
Bidder to follow Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
be considered.
36 Annexure-II, Page 939 of 1481
Ageing Factor-1.25 (for Lead Acid Plante)
Please note that ageing factor for Lead Acid Plante is 1 as per IS. Please accept the same.
Bidder to follow Specifications
37 Battery Charger Cl.2.02.00 (j) Page 954 of 1481
Suitable filter circuits shall be provided in all the Chargers to limit the ripple content (peak to peak) in the output voltage to 1% irrespective of the DC load, even when they are not connected to a battery.
Please note that Suitable filter capacitor will be provided at the input side of the charger only.
Point withdrawn by bidder
DRY TYPE TRANSFORMER, Doc No. PE-TS-401-999-E001, Vol II Part-B 38 Sec-D, Cl 25 (a),
Page 1128 of 1481 HV side terminal details of dry type service transformer.
Please note that same shall be done by means of cable only.
Point withdrawn by bidder
39 Sec-D, Cl 34 (a), Page 1129 of 1481
Maximum current density (A/mm2)
Please note that maximum current density shall be limited upto 3A /mm2 for dry type service transformer.
Point withdrawn by bidder
OIL TYPE TRANSFORMER, Doc No. PE-TS-401-302-E001, Vol II Part-B 40 Data Sheet-A,
11/3.3 KV, Cl 19.0(b)/ Page 1152 of 1474
Flange throat for TPN nonsegregated Al Busduct / Cable box as applicable
Please note that same shall be SPBD/Cable box as applicable.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
41 Data Sheet-A, 11/0.433, Cl 20.0/Page 1159 of 1481
LV side system fault level : 45kA (rms)
Please note that the system fault level for LV side shall be of 50kA for 1 sec as per Cl No 3.3.2 of Spec Doc No PE-TS-401-506-E001 Vol II Part-BSec-D, Page 3 of 23 OR Page 453 of 1474. All the 0.433kV LV system including transformer and switchgears will be designed with the fault level of 50kA for 1 sec only. Please confirm.
Bidder to follow Specifications
QUALITY
42 General Type Test for All Equipment Please note that we have not considered conduction of type test for any equipment. This is applicable for all equipments.
Follow Technical Specifications and quote as per Price Schedule
43 Annexure-3-appendix-E (MOM-QA)
Remarks-SQPno.0000-999-QOE-S-002 , SQPno.0000-999-QOE-S-38, SQPno.0000-999-QOE-S-005 , SQPno.0000-999-QOE-S-19, SQPno.0000-999-QOE-S-18,SFQPno.-000-999-QOE-I-002, SFQPno.-000-999-QOE-I-003, SFQPno.-000-999-QOE-I-006
Request to please arrange for the copies of the referred documents.
Refer clause 2.3.22 of Scope of Enquiry (Part of Tech Specs – Vol 1)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
44 Cl.No.22.04.00 Bidder shall also furnish copies of the reference documents/plant standards/acceptance norms/test and inspection procedures etc
Please note that all reference documents cannot be shared, further reference documents (if submitted ,any) will be provided for reference only.
Point withdrawn by bidder
45 Cl.no.22.23.00 Procedure been followed for eliminating infant mortile components
Please inform the standards to be referred and equipment’s for which the same are applicable.
Point withdrawn by bidder
46 Cl.no.22.23.00 Elevated temperature test cycle Ambient cannot be maintained at 50 degc. Please inform sampling plan and equipment’s on which the referred test is proposed.
Point withdrawn by bidder
47 Cl.no.22.23.00 Burn in test cycle Please note that it will not be possible to offer the test on all the panels. Sampling may please be suggested.
Point withdrawn by bidder
48 Cl.no.25.03.00 15 days written notice Please note that Notice of 10 days may be considered.
Point withdrawn by bidder
49 Cl.no.25.05.00 When factory tests have been completed at contractors or subcontractors works,the project manager/inspector shall issue a certificate to this effect
Please note that Certificate issuance should be with two days of inspection.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
fifteen days after completion of test
50 Cl.no.4.02.01 Medium voltage busduct-type test
We do not envisage any type test conduction. Only reports will be submitted
Point withdrawn by bidder
51 Cl.no.4.03.00 Medium voltage busduct -Routine tests-Radiography test
Not applicable and not required for this range of busduct
Point withdrawn by bidder
52 Cl 5.00.00 MV busduct-test mentioned under b,c,e and f
For b,c,e reports can be submitted. F –not required for this rating of BD.
Point withdrawn by bidder
53 Cl.no.10.1,volume II—Lightning protection system
The following stage of manufacture and installation shall be stage inspected by purchaser or his authorized representative………
It is requested that only final finished product be inspected, stage inspection for this commodity is not desired.
Point withdrawn by bidder
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
54 Cl.no.5.13.00-Dry type transformer
Type tests-sc ,noise level, zps, harmonic, temp rise ,LI with chopping. Routine test-PD, cap and tan delta
Type test-short circuit test, noise level ,harmonics measurement and LI with chopped wave are special tests as per IS 2026 .Similarly cap and tan delta is also special test
Point withdrawn by bidder
II. Price Schedule Vol II Part C Doc No. - PE-TS-401-999- E001; Rev 0 55 (2) MV Switchgear
Annexure-2, Sr No 7, BOQ CUM PRICE SCHEDULE OF MV SWGR (Supply)
Site modification charges:As per annexure- 2C
Please clarify the requirement and define the scope of work in detail.
Bidder to quote as Price Schedule
III. NIT 56 Cl 6.0 Due Date of
Offer Submission Date: 29.09.2014, 14:00 hrs We request to please grant us extension
for 4 weeks i.e. till 29.10.2014 for bid submission.
Not possible
57 Price Schedule, Data Sheet & Formats
General We request to please provide soft copies of: 1. Price Schedule (Vol II Part-C) 2. Data Sheet (As listed in Technical Specifications) 3. Annexures/Formats (Vol IIIE) This is required for necessary filling up of relevant information to be provided as part of techno-commercial bid ubmission.
Not possible
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
Sr. No.
Volume/ Chapter
Clause No.
Page No. Bid Specification Clarifications Client's reply
58 Volume-III, General Technical Requirement, Section C, Part C
4.01.00 1 of 75 Bidders may note that this is a turnkey contract. Each of the plant shall be engineered and designed in accordance with the specification requirement.
We presume that customer has already engineered and designed the plant. Hence, we are proceeding as per the BOQ furnished by the customer. We do not envisage design and engineering of the same. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
59 Volume-III, General Technical Requirement, Section C, Part C
8.03.01 A)
6, 7 of 75
Basic Engineering Documentation
We presume that the Sl. No. i) to x) in the said clause is not applicable for the present tender and not in our scope. We envisage that our scope is as per the furnished BOQ only. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
60 Volume-III, General Technical Requirement, Section C, Part C
8.03.01 B)
7, 8, 9 of 75
Detailed Engineering Documentation
We presume that the Sl. No. iii) to v); vii) to xiv); xvii) to xxix) in the said clause is not applicable for the present tender and not in our scope. We envisage that our scope is as per the furnished BOQ only. We understand that the basic documents related to General layout and layouts for equipment and facilities will be furnished by the customer and vendor has to develop the same. However, type test reports will be furnished for the equipment in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
61 Volume-III, General Technical Requirement, Section C, Part C
8.03.03.01
11 of 75 Plant Handbook We do not envisage Process and Instrumentation diagrams in our scope. We presume that the items listed in Sl. No. i) and iii) to viii) are pertained to our scope only.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
62 Volume-III, General Technical Requirement, Section C, Part C
8.03.04 i)
14 of 75 Drawings shall include all installations and detailed piping layout drawings.
Layout drawings for all piping of 65 mm and larger diameter shall be submitted for review/ approval of Employer prior to erection.
We do not envisage the said clause in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
63 Volume-III, General Technical Requirement, Section C, Part C
19.01.00
19 of 75 All equipment/ piping/ pipe services are to be painted by the Contractor in
accordance with Employer's standard colour coding scheme, which will be furnished
to the Contractor during detailed engineering stage
We do not envisage the said clause in our scope. However, painting will be done only for the equipment pertaining to our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
64 Volume-III, General Technical Requirement, Section C, Part C
20.05.00
20 of 75 All piping shall be cleaned after shop assembly by shot blasting or other means approved by the Employer. Lube oil piping or carbon steel shall be pickled.
We do not envisage the same in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
65 General Kindly note that we do not envisage piping and its associated works in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical SpecS (Volume-I)
66 Volume-III, General Technical Requirement, Section C, Part C
26.01.00 f) 34 of 75
The Contractor during initial operation and performance testing shall conduct
vibration testing to determine the ‘base line’ of performance of all plant rotating equipment. These tests shall be conducted when the equipment is running at the base load, peak load as well as lowest sustained operating
condition as far as practicable.
We do not envisage the same as rotating equipment of the plant is not in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
67 Volume-III, General Technical Requirement, Section C, Part C
28.01.00 36 of 75
Training of Employer’s Personnel.
We do not envisage training of Sl. No. a) and c) to g) as the same are not in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
68 Volume-III, General Technical Requirement, Section C, Part C
28.03.00 36 0f 75
This shall cover all disciplines viz, Mechanical, Electrical, C&I , QA etc
We presume that the training from our end will be confined to Electrical discipline. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
69 Volume-III, General Technical Requirement, Section C, Part C
30.00.00 37 of 75
Noise level We do not envisage the said clause in our scope of work. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
70 Volume-III, General Technical Requirement, Section C, Part C
34.00.00 39 of 75
Instrumentation and Control
We presume that the same is not applicable for our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
71 Volume-III, General Technical Requirement, Section C, Part C
35.00.00 40 of 75
Electrical Noise Control
The electrical noise control for electrical equipment will be as per OEM’s practice. Please confirm.
Follow Technical Specifications
72 Volume-III, General Technical Requirement, Section C, Part C
36.00.00 40 of 75
Surge protection for Solid state Equipment
We presume that the same is not applicable for our scope. Please confirm.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
73 Volume-III, General Technical Requirement, Section C, Part C
37.00.00 40 of 75
Instrument Air compressor
We presume that the same is not applicable for our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
74 Volume-III, General Technical Requirement, Section C, Part C
38.00.00 40 of 75
Tapping Points for Measurements
We presume that the said clause is not applicable for our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
75 Volume-III, General Technical Requirement, Section C, Part C
39.00.00 41 of 75
System Documentation
We presume that the same is not applicable for our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
76 Volume-III, General Technical Requirement, Section C, Part C
39.01.00 41 of 75
Bill of material (instrument list) for all C&I equipment/ devices shall be furnished by the bidder in standard formats as approved by the Employer.
We presume that the said clause is not applicable for our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
77 Volume-III, General Technical Requirement, Section C, Part D
33.02.00 16 of 51
Commissioning Documentation
We presume that the said clause is only confined to the equipments in our scope. Please confirm.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
78 Volume-III, General Technical Requirement, Section C, Part D
46.00.00, 47.00.00, 48.00.00, 49.00.00, 50.00.00, 51.00.00
125 of 1474
The said clauses are strikethrough
With reference to the page no. 125 of 1474, we understand that the said clauses are not in our scope even though when some of the clauses are not marked strikethrough in the respective pages. Please confirm.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
79 Scope of supply and services
2.04.02 and 6.01.00
196 of 1474 and 197 of 1474
The quantities of Medium Voltage Busducts of different ratings, 90 deg.
Bends, T-connection, phase cross over and termination at Switchgear and transformer end are given in BOQ at clause 4.02.00. The bid price shall be based on the unit rate for busduct length measured from matching flanges following the centre line of the busduct. The length shall be measured from matching flange of Generator, Generator
Transformer and other terminal equipments
As per the clause 2.04.02, we understand that the bidder shall follow the quantity of MV busduct of different rating along with its associated accessories.
As per the clause 6.01.00 and also as per the furnished layout of SPBD (page no. 200 of 1474), we understand that the length of SPBD shall be measured.
In view of the contradiction between the said clauses, we are proceeding with the BOQ furnished by the customer for both SPDB and support structures. Please confirm.
Follow Price Schedule & Technical Specification
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
80 a. Electrical SLD for Auxiliary Power distribution drg no. PE-DG-401-565-E001
b. SLD for 11kV Switchgear metering and protection drg no. PE-DG-401-505-E001
1. Rating of Unit transformer 6A, 6B;
2. Rating of standby transformer OBAT01
1. The rating of unit transformer is mentioned as 40/50MVA as per point no. a and same is indicated as 40/45MVA as per the point no. b
2. The rating of standby transformer as per a. is 40/50MVA and same as per b. is 40/45MVA.
Kindly clarify the above.
Same shall be finalized during detailed Engineering. Presently consider 40/50MVA
81 a. Electrical SLD for Auxiliary Power distribution drg no. PE-DG-401-565-E001
b. SLD for 11kV Switchgear metering and protection drg no. PE-DG-401-505-E001
Voltage rating of standby transformer OBAT01
The voltage rating of Standby transformer as per a. is 400/11.5kV and same is mentioned as 21/11.5kV as per b.
Please clarify.
Same shall be finalized during detailed Engineering. Presently consider 400/11.50KV
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
82 Section C, part B. PE-TS-401-506-E001;
Section VI, part B, subsection B-08
a. 14.10
b. 4.05.00
359 OF 1474and 10 of 58
Degree of Protection for LV Switchboard
As per the point no. a, the degree of protection for compartments and bus bar chambers up to 1600A shall be IP 52 and above 1600A shall be IP 4X and whereas point no. be calls for degree of protection to be IP 5X upto 1600A. Kindly clarify.
Clause no.4.05.00 shall prevail.
83 Section C, part B. PE-TS-401-506-E001;
Section VI, part B, subsection B-08
a. 13.2
b. 11.01.00
352 of 1474 and 20 of 58
a. The switchgear shall be draw out type.
b. MCCB shall be fixed type or part of withdrawable feeder module.
Kindly clarify the contradiction between the said clauses.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
84 Section D, part B. PE-TS-401-506-E001;
Section VI, part B, subsection B-08
a. 3.01.01 4)
b. 3.3.2
4 of 58 and 453 of 1474
Fault Level of LV switchgear
The fault level of LV switchgear is mentioned as 45kA as per the point no. a whereas the same is given as 50kA as per the point no. b
Please clarify.
Fault Level of LV switchgear : 45 kA (rms) to be considered.
85 Spec. no. PE-TS-401-508-E001, Part B
Annexure-II 932 of 1474
Factors to be considered for battery sizing. Aging factor1.25 for Lead acid Plante and 1.25 for Ni-Cd. Bidder has to take ageing factor (margin) in their sizing and selection of both lead acid and Ni-Cd battery.
Please note that the ageing factor is not applicable for Lead acid Plante battery as perIEEE-485.
Hence, we do not envisage ageing factor. However, we will envisage design margin for both Lead acid Plante and Ni-Cd battery.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
86 Vol-II, Part-B, Section C, Spec. no. PE-TS-401-510-E001
6.01, 6.03 and 6.06
987, 988 of 1474, 987 of 1474
The contractor shall carry out the type tests as listed in this specification on the equipment to be supplied under this contract.
In case the contractor has already conducted such specified type test(s), he may submit during detailed engineering the type test reports to the owner for waival of conductance of such type test(s).
In line with the mentioned clause (6.03), we will submit the type test certificates for GCB.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
87 Vol-II, Part-B, Section C, Spec. no. PE-TS-401-510-E001
7.00 vii) 988 of 1474
Low frequency withstand voltage tests on GCB
Please note that the conduction of mentioned test is based on manufacturer’s concurrence.
Follow Technical Specifications
88 Vol-II, Part-B, Section C, Spec. no. PE-TS-401-510-E001
6.01 995 of 1474
Validity period of type test reports is 10 years
Request you to kindly note that the equipment which is having the type test certificate beyond 10 years is also said to be valid and acceptable, so long as there is no change in design.
Follow Technical Specifications
89 Vol-II, Part-B, Section C, PE-TS-401-302-E001;
SLD drg. No. PE-DG-401-565-E001
Sl. No. 1 a) to e);
Table 3 of SLD
1131 of 1434
Scope of supply and services of oil type transformers
As per the BOQ of Oil type transformers, we understand that Generator Transformer, Unit Auxiliary Transformers, CHP Aux and AHP Aux transformers are not in our scope. However, the same are indicated in the tender SLD. Please clarify.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
90 Vol-II, Part-B, Section C, PE-TS-401-302-E001;
SLD drg. No. PE-DG-401-565-E001
Sl. No. 1 b) and c)
Table 3 of SLD
1131 of1474
Scope of supply and services of oil type transformers
As per the BOQ of Oil type transformers, the quantity of 1.6MVA & 2MVA transformers are mentioned as 2 and13 nos. respectively whereas the quantity of same seems to be 1.6MVA-10 nos. and 2MVA-9 nos. as per the SLD. Kindly clarify the contradiction.
As per Price Schedule
91 VoI I 2.4 18 of 1474
EXCLUSIONS: All building structure, all civil works other than grouting and fixing to the equipment structure.
NBPPL to confirm the scope of foundation bolts required for fixing the equipment.
Follow Scope of Enquiry Part of Technical Specifications (Volume-I); foundation bolts in the scope of bidder.
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
92 VoI I 2.5 19 of 1474
VARIATION OF QUANTITIES MAY BE TO THE EXTENT OF +/-30% OF TOTAL CONTRACT VALUE. REFER GENERAL CONDITIONS OF CONTRACT FOR FURTHER DETAILS.
NBPPL to consider limiting quantity variation to +/- 15 %
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
93 VOLUME II PART-B
18 232 of 1474
All miscellaneous items such as disconnecting links, flexibles, shorting bars, hardwares, conduit for wiring, marshalling box, CTs and PTs wiring through conduit, earthing materials, bus bar fish plates etc. are part of bus duct installation. Hence separate breakup quantity is not given in BOQ.
NBPPL tp provide plant SLD to understand and incorporate the required / necessary components like CT, PT, JB's etc.
Provided in Technical Specifications
94
Technical specification – General technical requirement
8.03.01 5 of 57
A) Basic Engineering Documentation and
B) Detailed Engineering Documentation
Document submission list under this clause are not relevant to the electrical package scope of the tender. NBPPL to clarify.
Follow Scope of enquiry as part of Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
95 Vol – II, Section C
1.00.00 943 of 1474
A. CHARGER SHALL BE SUITABLE FOR NI-CD BATTERY OF 920AH CAPACITY.
OR
B.CHARGER SHALL BE SUITABLE FOR LEAD ACID PLANTE BATTERY OF
2035AH CAPACITY.
Design of Battery charger will be considered as given. NBPPL to confirm as no load list is provided.
Charger rating shall be as per Price Schedule and datasheet A
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
96
Vol – II, Section C : Generator Circuit Breaker
14.00 991 of 1474
TRAINING OF ENGINEERS
Bidder shall provide training for a maximum of six (6) engineers from NBPPL/ultimate customer at works, training centre etc. The training shall also include application, layout, design, construction, operating principle, operating mechanism, local control panel, operation, maintenance, site inspection, erection, site testing, spares etc. of GCB.
GCB is imported item and manufactured at works in Europe. NBPPL to clarify on the training need aboard.
Follow Technical Specs
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
97 Vol – II, Section B : EPABX
7.1.2 1259 of 1474
Analog subscriber lines: 512 no(location will be decided by site/owner)
NBPPL to specify about the areas/buildings where the telephone equipment will be installed. As cables and conduits will be estimated accordingly.
Will be Provided during detailed Engineering. Presently follow Price Schedule & Optional Price Schedule
98 Vol – II, Section B : EPABX
7.1.3 1259 of 1474
Desktop/wall mounted telephones-250 no’s
NBPPL to specify separately about the total no of Desktop and wall mounted telephones required.
Will be Provided during detailed Engineering. Presently follow Price Schedule & Optional Price Schedule
99 Vol – II, Section B : EPABX
NBPPL to specify if any specific no of weatherproof /flame proof type of telephone required.
Follow Technical Specifications
100
Vol – II, Section B : EPABX
NBPPL to specify about approved vendor list for EPABX SYSTEM.
Provided at Vendor List(A5) of Technical Specifications Volume-I
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
101
Vol – II, Section B : EPABX
NBPPL to provide an Air-conditioned, dust free space for the exchange and its main accessories
Follow Technical Specifications
102
Vol – II, Section C : PA SYSTEM
NBPPL to specify about the areas/buildings AS cables and conduits will be estimated accordingly.
Shall be provided during detailed engineering. Bidder to quote as per Price Schedule
103 GCB Clause No. 2.11
Page 14 of 59
Natural Cooling
Please clarify and confirm as we do not have natural cooling in this range. We have supplied Forced cooling GCB to BHEL & NTPC in the past, hence we request to please accept Forced Cooling breakers.
Natural Cooling is applicable for Generator Bus-duct. Bidder to comply with Technical Specifications.
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
104 GCB Clause No. 6.00
Page 15 of 59
Type Tests
We wish to inform you that 10 year clause is not applicable to GCB as the design of the GCB has not been changed since the conduction of the Type test. And moreover there is no change in the type test requirement in the standard also. Hence all our Type tests are still valid for the similar rating. Further it is not feasible for conducting any type test for 1 breaker. Hence we do not envisage any conduction of type test as all our type tests are valid and in line with the standard.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
105 GCB Annexure B Page 21 of 59
Quality Plan
We wish to inform you that our QAP is fully complied to IEEE standards. Therefore we are unable to follow any other QAP. Further we wish to inform you that for GCB stage inspection is not applicable. We can conduct only Final acceptance Test in line with the standards. No stage inspection will be done. Further we also wish to inform you that chemical composition of any of the equipment will not be shared as this is confidential for us. Please see our QAP for your further actions.
Follow the Technical Specifications
106
Vol – II B, Section D : PA SYSTEM
1.6 of section 'D'
1068 of 1474
The clause says that BOQ has been given in section 'C'. But we do not find any BOQ in section C. NTPC to clarify the same.
Follow Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
107
Vol – II B, Section C & D : PA SYSTEM
Clause 7.0 of section 'C' & clause 3.6.3 of section 'D'
1042 of 1474 & 1070 of 1474
Clause 7.0 of section 'C' says that enclosure with transparent glass door which can be open through number pad locked only. Also clause 3.6.3 of section 'D' says above the access code of the person does it means that the stations with access control system. NTPC to clarify that. Also Clause no. 3.6.3 - ask for access code of the person, the PA system operation will be restricted to the person who know the access code & the person who don't know the access code cannot use the system.
Clause No:7.0 of Section C will prevail
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
Sl. No.
Volume Clause No.
Clause Ref. NBPPL's DESCRIPTION AS SPECIFIED
Bidder's CLARIFICATION NBPPL's REPLIES
108 General Technical Requirements
4.00.00 Pg 1 of 75
COMPLETENESS OF FACILITIES
Bidders may note that this is a turnkey contract. Each of the plant shall be engineered and designed in accordance with the specification requirement. All engineering and associated services are required to ensure a completely engineered plant shall be provided. All equipments furnished by the Contractor shall be complete in every respect, with all mountings, fittings, fixtures and standard accessories normally provided with such
We understand that this contract is a Bill Of Quantity based contract which comprises of Supplies & Services identified in the Tender Documents as well as in Price Schedule format provided by NBPPL.And any necessary inputs required for other departments like Mechanical, Civil, C & I will be provided for our supplied equipments only. Any Additional items not covered under the Bill of Quantity and required for completion of Power Plant shall be reimbursed by NBPPL.
Bidder to follow the Scope of Enquiry (part of Tech Specs- Vol 1)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
equipment and/or those needed for erection, completion and safe operation of the equipment and for the safety of the operating persnnel, as required by applicable codes, though they may not have been specifically detailed in the respective specifications, unless included in the list of exclusions.
109 General Technical Requirements
5.06.00 CODES & STANDARDS
Two (2) English language copies of all national and international codes and/or standards used in the design of the plant and equipment shall be provided by the Contractor to the Employer within two
Codes and standards can not be duplicated. However we shall provide the list of the codes / standards related to the equipment supplied by us.
Bidder to follow the tech specs
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
calendar months from the date of the Notification of Award.
110 General Technical Requirements
7.02.00 MAINTENANCE AND AVILABILITY CONSIDERATIONS
Lifting devices i.e. hoists and chain pulley jacks ,etc. shall be provided by the contractor for handling of any equipment or any of its part having weight in excess of 500 Kgs during erection and maintenance activities.
Any necessary lifting device like chain pulley, jacks etc shall be considered during erection/execution and the same shall be taken back once the job is completed.
Lifting device like chain pulley, electric hoists etc shown in the layout drawing shall be used for the maintence purpose of the equipmen & shall be erected & commissioned to customer.However any other device used for sole erection purpose of the equipment can be taken back once the job is completed.
111 General Technical Requirements
8.00.00 8.01.00 to 8.05.03
DOCUMENTS, DATA AND DRAWINGS TO BE FURNISHED BY CONTRACTOR
Basic engineering documentation Detailed engineering documents Instruction manuals Operation & maintenance manuals Plant handbook and project completion
This clause shall be applicable only for those equipments supplied by us under this package.
As per Scope of Enquiry part of Technical Specifications (Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
report Drawings Engineering information submission schedule
112 General Technical Requirements
9.02.00 TECHNICAL CO-ORDINATION MEETING
The Contractor should note that Time is the essence of the contract. In order to expedite the early completion of engineering activities, the Contractor shall submit all drawings as per the agreed Engineering Information Submission Schedule.The drawings submitted by the Contractor will be reviewed by the Employer as far as
We request NBPPL to delete the wording "Time is the essence of the contract"
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
practicable within three (3) weeks from the date of receipt of the drawing .The comments of the Employer shall then be discussed across the table during the above Technical Co-ordination Meeting (s) wherein best efforts shall be made by both sides to ensure the approval of the drawing
113 General Technical Requirements
13.00.00 LUBRICANTS, SERVO FLUIDS AND CHEMICALS
As far as possible lubricants marketed by the Indian Oil Corporation shall be used. The variety of lubricants shall be kept to a minimum possible
We presume this is not related to eBoP scope of work.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
114 General Technical Requirements
28.07.00 TRAINING OF EMPLOYER'S PERSONNEL
In all the above cases, wherever the training of Owner's personnel is arranged at the works of the manufacturer's, it shall be noted that the lodging and boarding of the Owner's personnel shall be at the cost of Bidder. The Bidder shall make all necessary arrangements towards the same.
The Cost for lodging and boarding of the Owner's personnel shall be borne by NBPPL only.
Follow Technical Specifications
115 General Technical Requirements
TECHNICAL SPECIFICATION SECTION - VI PART-C
General Technical Requirments
We understand that this General Technical Requirement is for reference purpose only and all related clauses pertaining to electrical equipments shall only be applicable.
Follow Scope of enquiry as part of Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
116 MV SWITCHGEAR
TECHNICAL SPECIFICATION SECTION - VI PART-B
General Query Please furnish the type of cable entry for MV panels (either Top Entry or Bottom)
Bottom Entry for Cables
117 II (Part B) Section C
Clause No. 6.04 Pg no.6 of 12
GCB TYPE TEST
Further the Contractor shall only submit the reports of the type tests as listed in "LIST OF TESTS FOR WHICH REPORTS HAVE TO BE SUBMITTED" and carried out within last ten years from the date of bid opening. These reports should be for the test conducted on the equipment similar to those proposed to be supplied under this contract and the test(s)should have been either conducted at an independent laboratory or should
We wish to inform you that 10 year clause is not applicable to GCB as the design of the GCB has not been changed & moreover there is no change in the type test requirement in the respective standard also. Further it is not feasible for conducting any type test for 1 breaker. Hence we do not envisage any conduction of type test as all our type tests are valid and in line with the standard.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
have been witnessed by a client. However if the contractor is not able to submit report of the type test(s) conducted within last ten years from the date of bid opening, or in the case of type test report(s) are not found to be meeting the specification requirements, the contractor shall conduct all such tests under this contract at no additional cost to the owner either at third party lab or in presence of client/owners representative and submit the reports for approval.
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
118 II (Part B) Section C
Clause No. 9 Pg no.9 of 12
GCB QUALITY PLAN
QUALITY PLAN We wish to inform you that our QAP is fully complied to IEEE standards. Therefore we are unable to follow any other QAP. Further we wish to inform you that for GCB stage inspection is not applicable. We can conduct only Final acceptance Test in line with the standards. No stage inspection will be done. Further we also wish to inform you that chemical composition of any of the equipment will not be shared as this is confidential for us. We shall furnish manufacturer's standard QAP with our bid.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
119 GENERAL GENERAL GENERAL GENERAL We request NBPPL to provide the bidders with editable version of Price Schedule & Technical Datasheet in MS excel Format/ MS word inorder to enable us to provide the same as per NBPPL requirements at the earliest.
Not possible
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
Sr. No.
Doc. No. / Volume
Clause No.
Page no.
Bid Specification Stipulation
Statement of clarification sought
NBPPL's Remark
120 PE-TS-401-999-E001 / I
2.3.7 16 of 1481
During the course of erection, testing and commissioning Electrical/ C&I work certain rework / modification / rectification / repairs / fabrication etc. may be necessary on account of feedback from other power stations or units already commissioned and/ or units under erection and commissioning and also on account of design changes and manufacturing incompatibilities and site operation / maintenance
Please note that, we have considered our scope of work for Electrical packages as per tender BOQ / Price schedule and Detailed drawings to be furnised by NBPPL. Also note that, any rework /modification / rectification / fabrication / repairs etc, shall be deemed as extra works to be compensated to the L&T, based on the rates to be discussed and mutually agreed.
Follow Scope of Enquiry as part of Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
requirements. BIDDER shall carryout such rework /modification / rectification / fabrication / repairs etc, promptly and expeditiously and the same shall be deemed to be part of the scope of work.
121 PE-TS-401-999-E001 / I
2.4 19 of 1481
EXCLUSIONS: All building structure, all civil works other than grouting and fixing to the equipment structure.
Please note that, we have considered civil / Excavation works as mentioned in the tender BOQ / Price schedule. Apart from
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
ECC / Part-D
43.10.00 159 of 1481
Excavation The contractor shall take all necessary measures during excavation to prevent the hazards of falling or sliding material or article from any bank or side of such excavation which is more than one and a half meter above his footing by providing adequate piling, shoring, bracing etc. against such bank or sides.
that we have not considered any civil works in our scope.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
122 PE-TS-401-999-E001 / I
2.5 19 of 1481
QUANTITY VARIATION CLAUSE ADDITION/ DELETION OF QUANTITIES SHALL BE APPLICALBE AT THE QUOTED PRICES. THE UNIT RATE OF SUPPLY AND E&C OF ALL EQUIPMENTS AND SERVICES QUOTED BY THE BIDDERS SHALL BE FIRM FOR A VARIATION OF QUANTITIES TILL COMPLETION OF 1X500 MW FGUTPP (STAGE-IV) PROJECT. VARIATION OF QUANTITIES MAY BE TO THE EXTENT OF +/-30% OF TOTAL CONTRACT VALUE. REFER GENERAL CONDITIONS OF CONTRACT FOR FURTHER DETAILS.
We request you to considered the quantity variation within +/- 10% of total value.
Please refer GCC Clause No: 6.1
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
123 GTR / Part-C 8.03.01 54 of 1481
A) BASIC ENGINEERING DOCUMENTATION B) DETAILED ENGINEERING DOCUMENTS
Please note that, these clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
124 GTR / Part-C 8.00.00 53 of 1481
All engineering and technical services required to ensure a completely engineered plant shall be provided in respect of mechanical, electricaland power systems, control & instrumentation, civil & structural works.
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
125 GTR / Part-C 13.01.00 65 of 1481
LUBRICANTS, SERVO FLUIDS AND CHEMICALS 13.01.00 The Bidder’s scope includes all the first fill and one year's topping, requirements of consumables such as oils, lubricants, servo fluids, gases essential chemicals etc. Consumption of all these consumables during the initial operation and final filling after the initial operation shall also be included in the scope of the Bidder. Bidder shall also supply a quantity not less than 10% of the full charge of each variety of lubricants, servo fluids,
Please note that, the lube oil shall be applicable only for Emergency DG set and not for fuel oil.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
gases, chemicals etc. used which is expected to be utilised during the first year of operation. This additional quantity shall be supplied in separate Containers.
126 GTR / Part-C 25.11.00 79 of 1481
This shall include but not be limited to the following. a) System accuracy tests of DDCMIS for the various type of inputs identified in Part-B. b) Loop reaction time for sample loops/ logics. c) SOE functionality
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
tests. d) Server changeover.
127 GTR / Part-C 25.12.01 80 of 1481
Based on NTPC inputs, the Contractor shall prepare and submit typical implemented scheme in their system ( Control system & HMI) on sample basis.
Please note that, these clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
128 GTR / Part-C 33.00.00 86 of 1481
JUNCTION BOXES The junction boxes shall be made of minimum 2 mm thick sheet steel. Gland plates shall be removable type and made of 3 mm thick sheet steel. The boxes shall be provided with
As per tender specification PE-TS-401-507-E006 / C, cl.no. 4.5 and page no. 539 of 1481, the junction boxes are mentioned as FRP. Kindly confirm, whether we have to consider FRP or Sheet
Clause No: 33 of GTR will be applicable
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
detachable cover or hinged door with captive screws. Top of the box shall be arranged to slope towards the rear of the box. The box shall be hot dip galvanised and shall be provided with suitable neoprene gaskets to achieve requisite degree of protection.
steel.
129 GTR / Part-C 39.00.00 89 of 1481
SYSTEM DOCUMENTATION The Bidder shall provide drawings, system overview & description, hardware/software details, technical literature, functional & hardware schemes, bill of material, parts list, interconnection
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
diagrams, data sheets, erection/ installation/ commissioning procedures, instruction/ operating manuals, etc. for each of the C& I system / sub-systems/ equipment supplied under this package.
130 GTR / Part-C 39.01.00 89 of 1481
Bill of material (instrument list) for all C&I equipment/ devices shall be furnished by the bidder in standard formats as approved by the Employer.
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
131 ECC / Part-D
26.03.00 145 of 1481
Water. Contractor shall make all arrangements himself for the supply of construction water as well as potable water for labour and other personnel at the
We assume that, NBPPL will provide the water at free of cost.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
worksite/colony.
132 ECC / Part-D
45.00.00 165 of 1481
FOUNDATION DRESSING & GROUTING FOR EQUIPMENT/ EQUIPMENT BASES
Please note that, we have considered civil works as mentioned in the tender BOQ / Price schedule. Apart from that we have not considered any civil works in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
133 ECC / Part-D
51.04.00 173 of 1481
Equipment Installation j.Installation of Field Mounted Instruments and Devices
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
134 ECC / Part-D
51.04.00 173 of 1481
(2.) The removal of control and instrument equipment in order to allow bench calibration, if required, and the re-
Please note that, this clauses are not applicable to the package under consideration and hence not included in
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
installation of the said equipment after calibration shall also be included as a part of the work under these specifications.
our scope.
135 GTR / Part-C
25.00.00 187 of 1481
Associated document for Quality Assurance programme 25.10.04 Manufacturing Quality Plan Format No. : QS-01-QAI-P-09/F1-R1 enclosed at Annexure-VI. 25.10.05 Field Quality Plan Format No.: QS-01-QAI-P-09/F2-R1 enclosed at Annexure-VII.
Please note tha mentioned drawings are not enclosed in the tender document, kindly provide the same for our review.
Follow QAP
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
136 GTR / Part-C
25.11.00 187 of 1481
This shall include but not be limited to the following. a) System accuracy tests of DDCMIS for the various type of inputs identified in Part-B.
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
137 GTR / Part-C
25.12.00 188 of 1481
Based on NTPC inputs, the Contractor shall prepare and submit typical implemented scheme in their system ( Control system & HMI) on sample basis. The typical cases to be covered shall include but not be limited to the following.
Please note that, this clauses are not applicable to the package under consideration and hence not included in our scope.
Follow Scope of Enquiry as part of Technical Specifications(Volume-I)
138 PE-TS-401-505-E002 / C
4.02.01 205 of 1481
Busdut Support structure considers owners Load 400kg /Meter
Since there is the controversy between these clauses. Kindly confirm, whether we
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
PE-TS-401-505-E002 / C
3.05.02 220 of 1481
Busduct support structure designed to take care of Employers cable tray loadof 100 kg / Meter
have to consider 100kg/mtr or 400kg/mtr.
Follow Technical Specifications
139 PE-TS-401-505-E002 / C
Annex-C 209 of 1481
Busduct Elevation 3.5 Mtr in outdoor Transformer Yard
Since there is the controversy between these clauses. Kindly confirm, whether we have to consider 3.5mtr elevation or 6mtr elevation.
Elevation shall be decided during detailed engineering. Bidder to quote as per Price Schedule.
PE-TS-401-505-E002 / C
6.04.00 206 of 1481
MV Busduct shall run in outdoor transformer yard above 6 Mtr Elevation
Elevation shall be decided during detailed engineering. Bidder to quote as per Price Schedule.
140 PE-DG-401-505-E001 / -
-- 302 of 1481
Unit Transformer = 6A capacity 40/45 MVA
Since there is the controversy between these clauses. Kindly confirm, whether we have to consider 45MVA or 50MVA for considering the incomer in MV switchboards.
Bidder to quote as per Price Schedule and Optional Price Schedule
PE-TS-401-505-E001 / A
4.01.00 245 of 1481
Unit Transformer 50 MVA
PE-DG-401-505-E001 / -
303 of 1481
Standby Transformer 40/45 MVA,21/11.5kv
PE-TS-401-505-E001 / A
4.01.00 245 of 1481
Standby Transformer 50 MVA, 400/11.5/11.5 kv
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
141 PE-TS-401-506-E001 / C
13.5 359 of 1481
All motors 30kW and above & less than 110KW shall be provided with CT and Multifunction meters with RS485/4-20mA outputs for remote metering in DCS.
Please note that, we have considered the feeder as per tender BOQ / Price schedule. Also note that, the RS485/4-20mA provision is available in MFM, however the required interconnection cables between the MFM and Purchaser DCS is not in our scope.
Cable is in Bidder's Scope
142 PE-TS-401-506-E001 / C
13.2 362 of 1481
a. Ethernet switches and cables for connection of LT relays in LT Swgear.
As per tender BOQ/Price schedule, the quantity of ethernet switch is not mentioned, kindly clarify whether we have to supply or not. If we have to supply provide the quantity.
Follow Technical Specifications and Price Schedule
143 PE-TS-401-506-E001 / C
13.2 362 of 1481
b. FO cable inbetween HT panel & LT panel
Please provide distance and the specification of FO cable.
Bidder to quote as per Price Schedule and Optional Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
Technical specification / B
457 of 1481
FO link between LV board & Data Concentrator
144 PE-TS-401-506-E001 / C
13.2 362 of 1481
c. Programming Ethernet switches shall be part of vendor.
As per tender BOQ/Price schedule, the quantity of ethernet switch is not mentioned, kindly clarify whether we have to supply or not. If we have to supply provide the quantity.
Follow Technical Specifications and Price Schedule
Technical specification / B
18.00 & 19.00
397 of 1481
Fibre Optic Cables & Ethernet switches
145 Technical specification / B
6.01.00 384 of 1481
All Busbar and jumber connection shall be of high conductivity Al alloy/ CU of adequate size.
We have considered aluminium conductor for the same.
Follow Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
146 PE-TS-401-507-E006 / C
13.6 661 of 1481
IMPORTANT: – For all items supplied and installed as per Supply and Installation part of this specification as part of this contract, any minor left out items / non–quantifiable accessories, site consumables ,related services at site for preparing the materials for installation, etc, whether specially mentioned in the specification or not, shall be deemed to be included as part of bidder’s scope of installation.
Please note that, we have considered our scope of work for Electrical packages as per tender BOQ / Price schedule and Detailed drawings to be furnised by NBPPL. Appart from that we have not considered any other installation works in our scope
Follow Scope of Enquiry as part of Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
147 PES-507-11 / D
1.2 721 of 1481
The installation work shall generally be carried out as per purchaser’s drawings and documents. As part of cable installation, the scope shall also include exact detailing / adaptation of the system to specific site needs, to Engineers approval.
We presume that, the purchaser's detailed cable tray routing drawings cover all the following details: 1. Route identification with sectional views of the tray supports for plant overall cable tray routing as also all process buildings, sub-stations, Electrical rooms. 2. Cable schedule clearly indicating the route details for each cable (Power, Control and C&I cables). 3. The drawings shall not only cover main tray routes but also covers branch tray routes. 4. The tray supports shall cover sizes of
Follow Technical specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
structural steel members. 5. Areawise BOQ of trays and tray supports shall be clearly indicated on each of the drawings.
148 PES-507-11 / D
1.2 721 of 1481
The installation work shall generally be carried out as per purchaser’s drawings anddocuments. As part of cable installation, the scope shall also include exact detailing /adaptation of the system to specific site needs, to Engineers approval.
We presume that, the purchaser's detailed earthing and lightning protection drawings cover all the following details:1. Detailed constructional drawing of the earthing pits and their location on the detailed plot plan.2. Clear indication of route and size of the main earthing conductors.3.Areawise
Follow Technical Specifications and Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
BOQ of earthing & lightning conductors and its accessories shall be clearly indicated on each of the drawings.4. Clear indictaion of interconnections between earth grid of different areas/buildings and the routes.5.Clear indication of location of equipment to be earthed, size of its earthing conductor, their routes and location of earthing JB's ( as applicable).
149 PES-507-11 / D
1.1 721 of 1481
h) Minor civil works. Please note that, we have considered civil / Excavation works as mentioned in the tender BOQ / Price schedule. Apart from that we have not
Follow Technical Specifications and Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
considered any civil works in our scope.
150 PES-507-11 / D
3.2.9 726 of 1481
Cable trays shall be supported on ISA 50x50x6mm MS/GI brackets. Brackets shall be welded to steel plate inserts in the trenches/tunnels or supporting channel angle/inserts in other areas.
We presume that, all the tray supports are welded in insert plates, kindly confirm.
Follow Technical Specifications
151 PES-507-11 / D
3.7.24 731 of 1481
Wherever specific cable routes are not shown in cable schedules cables shall be laid as directed by Engineer.
Please note that, we have considered our scope of work for Electrical packages as per tender BOQ / Price schedule and Detailed drawings to be furnised by NBPPL. Also note that, any rework /modification / rectification / fabrication / repairs
Follow Scope of enquiry along with Technical Specifications
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
etc, shall be deemed as extra works to be compensated to the L&T, based on the rates to be discussed and mutually agreed.
152 PES-507-11 / D
5.7 737 of 1481
c) Unit rate of supply and filling of sand shall be applicable for the quantity of sand in cubic metres.
As per the environment law, itis not permissible to fill the river sand, hence we are not consider in our scope.
Follow Technical Specifications
153 PES-507-11 / D
7.16 741 of 1481
Equipment layout drawings.
We presume that, the equipment layout drawings will be provided with individual equipment tag numbers ( inline with cable schedule) for easy identification.
Follow Technical Specifications
154 PE-TS-401-510-E001 / C
3.0 991 of 1481
The Generator Circuit Breaker (GCB) is installed indoor and connected to generator busduct (isolated phase) on
We have not considered IPBD in our scope.
Noted
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
both sides. Suitable provisions shall be made for connection with isolated Phase Busducts (IPB) through flexible connection.
155 PE-TS-401-557- E001
1.2 1075 of 1481
Engineering: The “Engineering” shall broadly cover the detailed design of PA System as per the requirements of this specification, selection of equipment, materials, estimation of quantities etc. and preparation of all drawings necessary for the erection of the system. Complete engineering shall be as per the guidelines of purchaser and shall be subject to the approval.
We presume that the following informations /Drawings/Details shall be furnished by Purchaser to enable us take up the engineering. 1.Location of Hooters and Handsets (as required). 2. GA drawings of the buildings/ Structures, where the above mentioned equipment is proposed to be installed. It is presumed, that PA system cables can be
Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
installed in C&I cable trays, which please confirm.
156 PE-TS-401-999-E001
2.0 1252 of 1481
Following equipment and accessories will be supplied and installed. – Two Hundred and fifty (250) nos. of Telephone handsets. – Necessary quantity of Distribution Boxes. – Necessary quantity of Jelly filled cables. – Necessary quantity of wires, splicing / termination / connection accessories. – Sockets, matching plugs for Connection of
We presume that the following informations /Drawings/Details shall be furnished by Purchaser to enable us take up the engineering.1.Location of Telephone Handsets (as required).2. GA drawings of the buildings/ Structures, where the above mentioned equipment is proposed to be installed.It is presumed, that EPABX system cables can be
Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
Telephone Sets. – Necessary Grounding materials and connections. – All fittings, supports, brackets, clamps and connections.
installed in C&I cable trays, which please confirm.
157 PE-TS-401-557-E001 / C
12.0 1052 of 1481
INTERFACE WITH EXISTING EXCHANGE: Bidder to provide suitable built in interface for connection with employer's main telephone exchange in the Central Exchange and/or Master Control Units through which it shall
Kindly provide the distance details and location of existing exchange to considered the interconnection cables in our scope.
Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
be possible to communicate with any station in any zone from any telephone set through Central Exchange and/or Master Control Unit. All cables and interface hardware are in contractor’s scope of supply for connecting employer’s EPABX with central exchange.
PE-TS-401-557-E001 / C
6.1 1085 of 1481
INTERFACE WITH EXISTING EXCHANGE: PA system central exchange for the unit will be interfaced with existing/new EPABX/ PA system.
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
158 PE-TS-401-302-E001 / B
30.0 1160 of 1481
2 independent sets of 4-20mA signals to be made available at marshalling box for display of winding temperature & oil temperature for remote display on DDCMIS.
Please note the provision will be made available in the marshalling box, however the required interconnecting cables are not in our scope.
Cable is in Bidder's Scope
159 PE-RC-999-302-E001 / D
3.02 1168 of 1481
Transformers ( Rating & quantity of transformer shall be as per specific project requirement)
We have considered the quantity and rating of transformer as per tender BOQ/Price schedule only.
Follow Technical Specifications and Price Schedule
160 PE-TS-401-561-E001/ -
-- 1211 of 1481
D.G. AUX DISTRIBUTION BOARD- Distribution Board shall be as follows. This shall supply auxiliary power to various auxiliary equipment’s for operation of Generator sets. The panel shall have 415 V
Since the same is covered in the LV switchgear BOQ, we are not considered separate switchgear for the same. Kindly confirm.
Follow Technical Specifications and Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
AC, 3 Phase 3 Wire 50 HZ power as input. Auxiliary Power Supply requirement for this DG AUX MCC shall be generated in the MCC. There shall be one incomer with 125Amps rated MCCB. The MCCB’s shall be kept normally ON. The incoming supplies will be fed from each Unit Emergency MCC. No. of feeders are given in Section IV
161 PE-TS-401-561-E001/ -
-- 1249 of 1481
Minor civil works like drilling, chipping and punching holes and opening in concretefloors, slabs, brick-walls, and cleaning of all debris, Grouting, supply of
Please note that, we have considered civil / Excavation works as mentioned in the tender BOQ / Price schedule. Apart from that we have not considered any civil
Follow Technical Specifications and Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
cement, sand,concrete etc.
works in our scope.
162 Vol-I / SECTION C1 (mech) Sub-Section-I
1.00 1270 of 1481
MINIMUM LIFTING REQUIREMENT Note; 1. Area, type, capacity mentioned are minimum requirement and shall be finalised during detail engineering without any commercial implication 2. Travel and Lift are layout dependent and shall be finalised during detail engineering without any commercial implication 3. Additional
We request you to provide the details for the same, to consider the same.
Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
electric/manual hoist required during detail engineering shall be provided as per design criteria given above without any commercial implication.
163 Vol-I / SECTION C1 (mech) Sub-Section-I
1.00 1277 of 1481
12.0 DRAWING/DOCUMENT SUBMISSION The successful bidder shall submit the following drawings / documents during detail engineering for customer’s approval /information: A) ELECTRIC HOIST C) MANUAL HOIST (CHAIN PULLEY BLOCK):
Kindly provide the basic drawing details for estimation purpose.
Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
164 General - - Electrical hoist Kindly provide the following information :- ELECTRIC HOIST (EACH HOIST) 1. Height of Lift in mtrs. 2. Length of Travel in mtrs. 3. Please inform Beam Size on which Hoist will be operating. 4. Inform Area Classification Safe Area / Hazardous Area. If Hazardous Area give detail vig. Gas Group, Zone & Temp Class etc. along with name of gas present. CHAIN PULLEY BLOCK
Details shall be furnished during detailed Engineering. Bidder to comply with Technical Specifications and quote as per Price Schedule
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
1. Height of Lift. 2. Location of the Chain Pulley Block, whether Indoor or Outdoor. 3. Beam Size. 4. Any other relevant information necessary for designing to suit your requirement.
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
S.N Page No Clause No
Description Clarification Points to be Clarify NBPPL Clarification
165 Annexure-
I 1.1 Pre-Qualification
Requirement Bider should have executed cable laid 400KM in a single Order
Can be related with P.O Value if cable qty is not matching as per criteria
Not Possible
1.2 Bider should have executed 100VCBs in a single Order
Can be related with P.O Value if panel qty is not matching as per criteria
Not Possible
166 Annexure-2B
Board wise BOM & Schedule
Dummy Panel & Adaptor Panel, both are required.
Despite of Bottom Cable Entry, please clarify the requirement for both.
Bidder to quote for Both Dummy & Adapter Panels
167 255 of 1481
3. h) Surge Arrester Class are not defined Surge Arrester is available CL-1, 2 or 3. Please Clarify.
To be provided during detailed Engg Stage
168 359 of 1481
13.1 Specific Technical requirements
Feeder should have 20% spare feeder
These 20% spare items shall be inclusive of depicted BOM or apart from BOM.
Inclusive of depicted BOM
169 360 of 1481
13.10 Ethernet Switches are required with Each Switchboard
Ethernet Switch has to considere as per Prices Schedule or as per Specification.
Ethernet switches to be supplied as per Price Schedule
No of Channel requirement for Ethernetr Switch.
VOLUME-IIIE-ANNEXURES, FORMATS ETC
NTPC BHEL POWER PROJECTS PVT LTD
170 425 of 1481
Tender Drawing for BUS PT
Any type of Metering & Relay is not showing
To quote as per BOQ or Tender (Module Drawing)
Tender dwg is indicative only Bidder to follow Price Schedule
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
PRICE SCHEDULE
SL. No.DESCRIPTIONS OF WORKS OR EQUIPMENT
Total Quoted Price
1 2 31.0
TECHNICAL SPECIFICATION NO: PE-TS-401-999-E001, Rev. 0
TITLE: PRICE SCHEDULE Volume-II, Part-C
PACKAGE: - ELECTRICAL SYSTEM
Total firm price on “FOR” site basis for DESIGN, MANUFACTURE, INSPECTION AND TESTING AT MANUFACTURER'S WORKS, PROPER PACKING AND DELIVERY TO SITE, STORAGE AT SITE, HANDLING, TRANSPORTATION OF MATERIALS FROM PROJECT STORAGE YARD / STORES TO ERECTION SITE / PLACE OF ERECTION , STORAGE AT ERECTION SITE, PRESERVATION, WATCH AND WARD, DRESSING, CHIPPING AND LEVELLING OF FOUNDATIONS, CLEANING , CHECKING, TESTING, PRE-ASSEMBLY, ERECTION, CALIBRATION, ALIGNMENT, WELDING, WHEREVER REQUIRED, PRESERVATIVE/ TOUCH-UP PAINTING INCLUDING SUPPLY OF PAINTS ETC, EARTHING OF EQUIPMENT, INCLUDING OTHER ACTIVITIES REQUIRED FOR ERECTION, TESTING, COMMISSIONING, POST COMMISSIONING, TRIAL OPERATIONS & HANDING OVER OF ALL ELECTRICAL EQUIPMENTS AND ITEMS AS PER BOQ INCLUDING SUPPLY OF MANDATORY SPARES, RECOMMENDED SPARES, SPECIAL TOOLS & TACKLES FOR MAINTENANCE ,START-UP ,PRE COMMISSIONING & COMMISSIONING SPARES AS SPECIFIED & AS NECESSARY FOR COMPLETENESS IN ALL RESPECTS AND FOR EFFICIENT & TROUBLE FREE OPERATION OF ELECTRICAL SYSTEMS PACKAGE FOR FEROZE GANDHI UNCHAHAR THERMAL POWER PROJECT – STAGE IV (1 X 500 MW) AS PER
PROJECT : - 1 X 500 MW FGUTPP, UP (Stage - IV)
NOTES
4.Transit Insurance shall be in NBPPL Scope .
FEROZE GANDHI UNCHAHAR THERMAL POWER PROJECT – STAGE IV, (1 X 500 MW) AS PER TECHNICAL SPECIFICATION NO:PE-TS-401-999-E001, Rev. 0 namely - 11kV & 3.3kV segregated phase busduct- MV switchgear- Low voltage switchgear,LT bus duct & neutral grounding resistor (NGR)- Cabling, earthing & lightning protection systems- Fire sealing system- HT XLPE Cables- 1.1kV XLPE Power, PVC PowerCables- 1.1kV PVC Control Cables- Screened Control Cables- 220V DC Battery- 220V DC Battery Charger- Generator Circuit Breaker- Public Address System- Dry Type Transformers- Oil Filled Service Transformer - Emergency D.G. Set- EPABX system- Electrical Equipment Handling Arrangement
5. Any other items, if required to be included is in bidder's scope apart from the above, same shall be included in the respective items itself & no separate price shall be quoted.
6. The above items shall be quoted as per tender specification. Responsibility of ensuring correctness & completeness of scope of supply as per specification requirement solely lies with bidder. 7.Bidder shall furnish the Breakup Prices in Annexures attached with this Price Schedule only
1. L1 bidder shall be evaluated based on the Total Price under column 3 S.No. 1.0 and hence bidder prices should be complete in all respects for the full scope defined considering all terms and conditions agreed . 2. Bidder to furnish list of items as recommended spares for 3 years with its price breakup. Prices of Recommended Spares will be optional and not be considered for evaluation.
3.Bidder to fill all Optional Price Schedule Annexures attached with this Price Schedule
1 of 1
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
1. 11 kV AND 3.3 kV SEGREGATED PHASE
BUSDUCT
DESCRIPTION UNIT QTY Unit Ex-works
price/Unit Price
Total Ex-Works Price
duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
Total Supply and E&C in
INR
11kV, 3000A
LENGTH METER 180
90 deg Bend NOS. 30
TRANSFORMER TERMINATIONS NOS. 3
SWITCHGEAR TERMINATIONS NOS. 6
TEE CONNECTION NOS. 1
WALL FRAME ASSEMBLY NOS. 3
TOTAL PRICE
3.3kV, 3000A
LENGTH METER 90
90 deg Bend NOS. 12
TRANSFORMER TERMINATIONS NOS. 2
SWITCHGEAR TERMINATIONS NOS. 4
WALL FRAME ASSEMBLY NOS. 2
TOTAL PRICE
3.3kV, 2500A
LENGTH METER 40
90 deg Bend NOS. 4
TRANSFORMER TERMINATIONS NOS. 2
SWITCHGEAR TERMINATIONS NOS. 2
WALL FRAME ASSEMBLY NOS. 2
TOTAL PRICE
Supporting structure (hot dip galvanized MS), foundation channels, hardware etc. Suitable for bus ductelevation and length involved.
As required forcomplete scope
BOQ CUM UNPRICED SCHEDULE OF 11KV & 3.3KV SEGRAGATED PHASE BUSDUCT
ANNEXURE-1
DESCRIPTION UNIT QTY Unit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in
INR on self manufactu
red only
Freight including Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissi
oning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply
and E&C in INR
11kV, 3000A
LENGTH METER 180
90 deg Bend NOS. 30
TRANSFORMER TERMINATIONS NOS. 3
SWITCHGEAR TERMINATIONS NOS. 6
TEE CONNECTION NOS. 1
WALL FRAME ASSEMBLY NOS. 3
TOTAL PRICE
3.3kV, 3000A
LENGTH METER 90
90 deg Bend NOS. 12
TRANSFORMER TERMINATIONS NOS. 2
SWITCHGEAR TERMINATIONS NOS. 4
WALL FRAME ASSEMBLY NOS. 2
TOTAL PRICE
3.3kV, 2500A
LENGTH METER 40
90 deg Bend NOS. 4
TRANSFORMER TERMINATIONS NOS. 2
SWITCHGEAR TERMINATIONS NOS. 2
WALL FRAME ASSEMBLY NOS. 2
TOTAL PRICE
ANNEXURE-1
BOQ for Erection & Commissioning of 11KV & 3.3KV SEGRAGATED PHASE BUSDUCT
Supporting structure (hot dip galvanized MS), foundation channels, hardware etc. Suitable for bus duct
elevation and length involved.
As required for
complete scope
S.no. Item Description Quantity
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess on E &
C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C in
INR
A 11 kV Busduct
1 Support insulators 25 Nos.
2 Three phase set of flexible terminal connectors for switchgear end of each type & rating 1 Set
3 Three phase set of flexible terminal connector for transformer end of each type & rating 1 Set
4 Seal off bushings of each type & rating 3 Nos.
B 3.3 kV Busduct
1 Support insulators 25 Nos.
2 Three phase set of flexible terminal connectors for switchgear end of each type & rating 1 Set
3 Three phase set of flexible terminal connector for transformer end of each type & rating 1 Set
4 Seal off bushings of each type & rating 3 Nos.
MANDATORY SPARES FOR MV BusductANNEXURE-1
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
2. MV SWITCHGEAR
S.no Description UOM Quantity Rating (A)
Unit Ex‐works
price/Unit
Price
Total Ex‐Works
Price duly packed
in INR/Total Price.
Excise Duty
@ on self
manufactur
ed only
VAT/CST @
… in INR on
self
manufactur
ed only
Freight
including
Service tax
@
Total FOR
Site Price
(Supply) in
INR
Total
Erection &
Commission
ing Charges
INR
Service tax
@ including
cess on E &
C in INR
Total E & C
prices
including
Service Tax
in INR
Total
Supply and
E&C in INR
1 11 kV Unit Switchboard#6BA Nos. 1 3000A
2 11 kV Unit Switchboard#6BB Nos. 1 3000A
3 11 kV Standby Switchboard#0BA Nos. 1 3000A
4 11 kV Colony Switchboard Nos. 1 630A
5 3.3 kV Unit Aux. Switchboard#6CA Nos. 1 3000A
6 3.3 kV Misc. Aux. Switchboard#0CA Nos. 1 2500A
7 Site modification charges:As per annexure‐2C Nos. 1
8 Mandatory Spares:As per annexure‐2D SET 1
9 Data Concetrator system:As per annexure‐2ENos. 1
10Networking and Harware for Numerical relay:As
per annexure‐2F Nos. 1
11 Training Requirement Annexure‐2G SET 1
12Erection & commissioning charges:As per
anenexure‐2H Nos.1
Notes.
1
3
4
5
6
7
8
9
10
11
12
13
a)
b)
c)
14
15
16
Minimum clearances required on all sides for each type of panel
Mandatory Spares:As per annexure‐2D
Addition/deletion of quantities shall be aplicable at the quoted prices.The Unit rate of supply of all
equipments and services quoted by the bidders shall be frim.Requirement of feeders for various 11kV &
3.3kV switchboards is enclosed in Annexure ‐B. Adopter panels for cable/bus duct connections as
necessary shall be included by Bidder.
The 3.3 kV boards 6CA and 0CA shall be split into two section due to layout requirements. The cost of tie
breaker to achieve this shall be included in switchboard price. Please refer MV SWGR layout.
List of MV Boards
For detailed panel wise and board wise BOM and Schedule of Unit Prices, refer Annexure‐2B
Site modification charges:As per annexure‐2C
1X500 MW FGUTPP
BOQ CUM PRICE SCHEDULE OF MV SWGR (Supply) Annexure‐2
Data Concetrator system:As per annexure‐2E
Networking and Harware for Numerical relay:As per annexure‐2F
Training Requirement Annexure‐2G
List of make (Sub vendor items) is subject to customer approval during contract stage without any price
implication
Commissioning charges of numerical relays & data concentrator shall be included in the price quoted for
SWGR & no extra chrges will be given for the same
All motors and dry type transformer feeders shall be provided with surge suppressors
Tinned brass, double compression type complete with necessary armour clamp cable glands and lugs for
power & control cables for all external connections to MV switchboards.
Multifunction numerical relays with communication facility on protocol IEC‐61850 shall be selected to
provide an integrated protection, control, monitoring and metering functions.Features such as self
diagnosis and external testing, disturbance recording, sequence of event recording and time stampings
shall be available with relay. Relays shall be of proven design & reputed make subject to customer
approval during contract stage without any price implication.Bidder to specifically ensure inclusion of
required hardware/software.
Unit rates quoted in Annexure‐2B,2C,2D,2E,2F and 2G shall be used for any addition/deletion during
detailed engineering.
Following information other than those asked in the different parts of specification shall be furnished
along with bid
Complete dimensions of all the boards including number of panels
Dimension of each type of panel
Board 11kV unit Switchboard#6BA
Rating 3000A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 Incomer from UT#6A 3000A DC 1
2 Line PT ‐‐‐‐‐‐ 2
3 Bus PT ‐‐‐‐‐‐ G 1
4 Tie from Standby Switchboard#0BA 3000A DE 1
5 UAT#6CAT01 16MVA DBF 1
6 Misc Aux. Trf#0CAT01 12.5MVA DBF 1
7 CHP Trf. #0CBT01 5MVA DBF 1
8 AHP Trf. #0CCT01 5MVA DBF 1
9 Spare Trf. feeder 16 MVA DBF 1
10 MD BFP#6 10000 KW DAF 1
11 CWP#6A 2300KW DAF 1
12 PA FAN#6A 3250KW DAF 1
13 FD FAN#6A 1350KW DA 1
14 CEP#6A 900KW DA 1
15 VFD ID FAN#6A(CH1) 3900KW DBF 1
16 VFD ID FAN#6A(CH2) 3900KW DBF 1
17 Spare Motor feeder 10000 KW DAF 1
18 Dummy panel 1
19 Adopter Panel 1
Board 11kV unit Switchboard#6BB
Rating 3000A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 Incomer from UT#6B 3000A DC 1
2 Line PT ‐‐‐‐‐‐ 2
3 Bus PT ‐‐‐‐‐‐ G 1
4 Tie from Standby Switchboard#0BA 3000A DE 1
5 UAT#6CAT02 16MVA DBF 1
6 Misc Aux. Trf#0CAT02 12.5MVA DBF 1
7 CHP Trf. #0CBT02 5MVA DBF 1
8 AHP Trf. #0CCT02 5MVA DBF 1
9 Spare Trf. feeder 5 MVA DBF 1
10 CWP#6B 2300KW DAF 1
11 CWP#6C 2300KW DAF 1
12 PA FAN#6B 3250KW DAF 1
13 FD FAN#6B 1350KW DA 1
14 CEP#6B 900KW DA 1
15 CEP#6C 900KW DA 1
16 VFD ID FAN#6B(CH1) 3900KW DBF 1
17 VFD ID FAN#6B(CH2) 3900KW DBF 1
18 Spare Motor feeder 3250 KW DAF 1
19 Dummy panel 1
20 Adopter Panel 1
1X500 MW FGUTPP
Annexure ‐2B ( Board Wise BOM & Schedule of Unit Prices for various 11kV & 3.3kV switchboards )
Board 11kV Standby Switchboard#0BA
Rating 3000A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 Incomer from ST#0BAT01 3000A DC 1
2 Line PT ‐‐‐‐‐‐ 2
3 Bus PT ‐‐‐‐‐‐ G 1
4 Tie to Unit Switchboard#6BA/6BB 3000A DE 1
5 Adopter Panel 1
Board 11kV Colony Switchboard#0BA
Rating
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 Incomer from ST#0BAT01 630A DC 1
2 Line PT‐A ‐‐‐‐‐‐ 1
3 Bus PT‐A ‐‐‐‐‐‐ G 1
4 TRF. feeder‐1 2MVA DB 1
5 TRF. feeder‐2 2MVA DB 1
6 TRF. feeder‐3 2MVA DB 1
7 B/C 630A 1
8 Line PT‐B ‐‐‐‐‐‐ 1
9 Bus PT‐B ‐‐‐‐‐‐ G 1
10 TRF. feeder‐2 2MVA DB 1
11 TRF. feeder‐3 2MVA DB 1
12 TRF. feeder‐4 2MVA DB 1
13 Dummy panel 1
14 Adopter Panel 1
Board 3.3kV Unit Switchboard#6CA
Rating 3000A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 Incomer from UAT#6CAT01 3000A DC 1
2 Line PT‐A ‐‐‐‐‐‐ 1
3 Bus PT‐A ‐‐‐‐‐‐ G 1
4 Unit Service Trf.#6DAT01 2000KVA DB 1
5 Station Service Trf.#0DAT01 2000KVA DB 1
6 Fuel Oil Trf.#0DBT01 2000KVA DB 1
7 Service Building Trf.#0DCT01 1600KVA DB 1
8 SWYD TRF.‐1 630KVA DB 1
9 Spare Trf. feeder 2000KVA DB 1
10 SA Compressor#6A 350KW DA 1
11 MILL MOTOR#6A 525KW DA 1
12 MILL MOTOR#6C 525KW DA 1
13 MILL MOTOR#6E 525KW DA 1
14 MILL MOTOR#6G 525KW DA 1
15 MILL MOTOR#6I 525KW DA 1
16 BCW PUMP#6A 350KW DA 1
17 ACW PUMP#6A 200KW DA 1
18 ACW PUMP#6C 200KW DA 1
19 ECW PUMP(TG)#6A 180KW DA 1
20 ECW PUMP(SG)#6A 180KW DA 1
21 Spare Motor feeder 525KW DA 1
22 B/C 3000A DD 1
23 Incomer from UAT#6CAT02 3000A DC 1
24 Line PT‐B ‐‐‐‐‐‐ 1
25 Bus PT‐B ‐‐‐‐‐‐ G 1
26 Unit Service Trf.#6DAT02 2000KVA DB 1
27 Station Service Trf.#0DAT02 2000KVA DB 1
28 Fuel Oil Trf.#0DBT02 2000KVA DB 1
29 Service Building Trf.#0DCT02 1600KVA DB 1
30 SWYD TRF.‐1 630KVA DB 1
31 Spare Trf. feeder 1600KVA DB 1
32 MILL MOTOR#6B 525KW DA 1
33 MILL MOTOR#6D 525KW DA 1
34 MILL MOTOR#6F 525KW DA 1
35 MILL MOTOR#6H 525KW DA 1
36 MILL MOTOR#6J 525KW DA 1
37 BCW PUMP #6B 350KW DA 1
38 BCW PUMP #6C 350KW DA 1
39 IA Compressor#6A 350KW DA 1
40 ACW PUMP#6B 200KW DA 1
41 ECW PUMP(TG)#6B 180KW DA 1
42 ECW PUMP(TG)#6C 180KW DA 1
43 ECW PUMP(SG)#6B 180KW DA 1
44 Spare Motor feeder 350KW DA 1
45 Dummy panel 1
46 Adopter Panel 1
Board 3.3kV Misc. Aux. Switchboard#0CA
Rating 2500A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Ex‐works price/Unit PriceTotal Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 Incomer from Misc. Aux. Trf.#0CAT01 2500A DC 1
2 Line PT‐A ‐‐‐‐‐‐ 1
3 Bus PT‐A ‐‐‐‐‐‐ G 1
4 ESP Service Trf.#6DCT01 1600KVA DB 1
5 ESP Service Trf.#6DDT01 1600KVA DB 1
6 ESP Service Trf.#6DET01 1600KVA DB 1
7 ESP Service Trf.#6DFT01 1600KVA DB 1
8 Make Up Water Trf.#0DET01 630KVA DB 1
9 Fire water/WTP Trf.#0DDT01 2000KVA DB 1
10 Cooling Tower Trf.#6DBT01 2000KVA DB 1
11 Spare Trf. feeder 2000KVA DB 1
12 CW M/U PUMP#A 180KW DA 1
13 Hydrant Main Pump#A 200KW DA 1
14 Spray Pump#A 200KW DA 1
15 Raw Water M/U Motor#A 450KW DA 1
16 APH wash M/U Pump#A 225KW DA 1
17 Spare Motor feeder 450KW DA 1
18 B/C 2500A DD 1
19 Incomer from Misc. Aux. Trf.#0CAT02 2500A DC 1
20 Line PT‐B ‐‐‐‐‐‐ 1
21 Bus PT‐B ‐‐‐‐‐‐ G 1
22 ESP Service Trf.#6DCT02 1600KVA DB 1
23 ESP Service Trf.#6DDT02 1600KVA DB 1
24 ESP Service Trf.#6DET02 1600KVA DB 1
25 ESP Service Trf.#6DFT02 1600KVA DB 1
26 Make Up Water Trf.#0DET02 630KVA DB 1
27 Fire water/WTP Trf.#0DDT02 2000KVA DB 1
28 Cooling Tower Trf.#6DBT02 2000KVA DB 1
29 Spare Trf. feeder 1600KVA DB 1
30 CW M/U PUMP#B 180KW DA 1
31 Hydrant Main Pump#B 200KW DA 1
32 Hydrant Main Pump#C 200KW DA 1
33 Raw Water M/U Motor#B 450KW DA 1
34 APH wash M/U Pump#B 225KW DA 1
35 Spare Motor feeder 350KW DA 1
36 Dummy panel 2nos. 1
37 Adopter Panel 1
S.no Description UOM Rating (A)Unit Ex‐works price/Unit
Price
Total Ex‐Works Price duly
packed in INR/Total Price.
Excise Duty including cess
@ ……Rs
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Erection &
Commissioning
Charges INR
Service tax @
including cess on
E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
1 11 kV Unit Switchboard#6BA 1Set 3000A
2 11 kV Unit Switchboard#6BB 1Set 3000A
3 11 kV Standby Switchboard#0BA 1Set 3000A
4 11 kV Colony Switchboard 1Set 630A
5 3.3 kV Unit Aux. Switchboard#6CA 1Set 3000A
6 3.3 kV Misc. Aux. Switchboard#0CA 1Set 2500A
Note: One set means one earthing truck suitable for all types of panels in that switchboard suitable for busbar side and cable side in that board / boards OR mulitple earthing trucks, one for each type of panel suitable for cable side earthing and independent truck for busbar side earthing in that board / boards.
BOQ for Earthing Trucks (If applicable)
The bidder shall bring out clearly in his bid the requirements of earthing trucks for the panels covered in this package
SL.NO. DETAILS QUANTITY Unit Charges in INR
Total Ex‐Works
Price duly packed
in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR
on self manufactured
only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
(6+7+8+9)
Total Charges in INR
Service tax @
including cess on Total
Charges in INR
Total Charges
including Service Tax
in INR
1 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR
SKILLED TECHNICIAN (EXCEPT DAILY CHARGES)
3 VISITS
2 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SKILLED
TECHNICIAN
20 DAYS
3 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR
SERVICE ENGINEER (EXCEPT DAILY CHARGES)
3 VISITS
4 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SERVICE
ENGINEER
15 DAYS
NOTES:
1)
2) AMOUNT PAYABLE FOR SERVICE ENGINEER PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 3 ABOVE +
(DAILY CHARGES AS PER SL. NO. 4 ABOVE X NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)
AMOUNT PAYABLE FOR SKILLED TECHNICIAN PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 1 ABOVE +
(DAILY CHARGES AS PER SL. NO. 2 ABOVE X NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)
1X500 MW FGUTPP
SITE MODIFICATION CHARGES (Annexure‐2C)
S.no. Item Description Quantity Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
11 KV/3.3KV SWITCHGEARS 1 Breaker of each rating 1 No. 2 Numerical relays 2 Nos. of each type
3Aux. Relays/ Lock out relays/ Timers(if applicable) 2 Nos. of each type
4 Bus bar support insulators 12 Nos. 5 Energy meter of each type & range 1 No. of each type 6 Spring charging motor complete 2 Nos. of each type.
7 Current transformer of each type & ratio 3 Nos. of each type
8 Potential transformer of each type & ratio 3 Nos. of each type 9 Shunt trip coil 5 Nos. of each type & rating
10 Closing coils 5 Nos. of each type & rating
11
Moving contact assembly of each rating (One set means complete replacement for one breaker) 2 Sets
12
Stationary (fixed contact of each rating.(One set means complete replacement for one breaker) 2 Sets
13 Bus seal off bushings 3 Nos. of each type & size 14 Limit switches 10 Nos. 15 Control switches 2 Nos. of each type 16 Selector switches 2 Nos. of each type 17 Isolation switch for the control supply 2 Nos.
18 Circuit breaker auxiliary contact assembly 6 Nos. of each type & rating 19 Indicating lamps with holders 20 Sets 20 (a) Fuse base and holder 12 Nos.
(b) Fuse link 12 Nos.
21
Isolating contact ( fixed & moving)( one set means male & female contacts of one complete breaker) 4 Sets of each rating
22 Terminal blocks 6 Nos.
23SF6 cylinder with SF6 gas filled alongwith nozzle for filling the gas(if applicable) 3 Nos.
24Multiple pin plug contact assy. with cables (male & female) 6 Nos.
25 Interphase barrier 2 Nos. of each type 26 Pressure gauge ( for SF6 breakers) 2 Nos. 27 Vacuum Contactors with HRC fuses 2 Sets (One set for three phases) 28 Surge arresters 3 Nos.
29Modules for Data Concentrator & system LAN 1 No. module of each type
1X500 MW FGUTPPAnnexure-2D LIST OF MANDATORY SPARES FOR 11KV/3.3KV SWITCHGEARS
Sl. No. ITEM DESCRIPTION QUANTITYUnit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
Total Supply and E&C in
INR
1DATA CONCENTRATOR ALONGWITH ALL ACCESSORIES FOR COMPLETENESS OF SYSTEM
2 SETS
3 LASER PRINTER (A4 SIZE) 1 NOS.
Notes
a
b
1X500 MW FGUTPPData Concetrator system: Annexure-2E
2 HMI 2 SETS
For other details bidder to refer architecture for Networking of Numerical relays (drawung no 0000-205-POE-A-001) and specification.
All above items shall be supplied along with accessories (including special tools for installation) required for completeness of system.
Sl. No. ITEM DESCRIPTION QUANTITYUnit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
a Ethernet Switch on IEC61850 with 8 Copper ports and 4 Gigabit FO ports 15
b Ethernet Switch on IEC61850 with 16 Copper ports and 4 Gigabit FO ports 20
2FIBER OPTICAL CABLE FOR COMMUNICATION (INCLUSIVE OFSUPPLY, LAYING AND TERMINATION ALONGWITH ANYHARDWARE REQUIRE AT EQUIPMENT SUPPLIED UNDER THISPACKAGE) 8 Km
3 LAPTOP PC WITH LICENCED VERSION SOFTWARE, HARDWARE ALONGWITH CONNECTING CABLES FOR RELAY PARAMETERISATION 1 No
4 Cat5E Ethernet cable for connection of Relays to Ethernet Switches 2 Km
5 Additional Numerical relays for Owner's requirement (for Module type DC) 2 Nos
6 Additional Numerical relays for Owner's requirement (for Module type DAF) 2 Nos
7 Additional Numerical relays for Owner's requirement (for Module type DBF) 2 Nos
8
COMMISSIONING CHARGES FOR CABLE LAYING FROM RELAY TO ETHERNET SWITCH AND ETHERNET SWITCH TO DATA CONCENTRATOR /ETHERNET SWITCH TO MV SYSTEM. AND FOR CABLE LAYING FROM ETHERNET SWITCH TO DATA CONCENTRATOR TO LV SYSTEM.
LOT
Notes
a
b
1
STAR COUPLER/EATHERNET SWITCH/ EQUIVALENT DEVICEWITH IEC-61850 PROTOCOL AND 100% REDUNDANT I/OTERMINALS FOR COMUNICATION BETWEEN RELAYS AND DATACONCENTRATOR/ GATEWAY CONCENTRATOR AS PER SYSTEMREQUIREMENT
For other details bidder to refer architecture for Networking of Numerical relays (drawung no 0000-205-POE-A-001) and specification.
All above items shall be supplied along with accessories (including special tools for installation) required for completeness of system.
1X500 MW FGUTPP
Annexure-2F (Networking and Harware for Numerical relay)
Item No. DESCRIPTION UOM Unit Charges in INR
Total Ex‐Works
Price duly packed
in INR/Total Price.
Excise Duty @ on
self manufactured
only
VAT/CST @ … in
INR on self
manufactured
only
Freight including
Service tax @
Total FOR Site
Price (Supply) in
INR
Total Charges in
INR
Service tax @
including cess on
Total Charges in
INR
Total
Chargesincluding
Service Tax in INR
Training of Engineers:
a) Basic cost [irrespective of no.
of engineers]
b) Additional variable cost per
engineer
1 1 Set
1X500 MW FGUTPP
Annexure‐2G Training Requirement
S.no Description UOM Quantity Rating (A)
Unit Erection
&
Commissioni
ng Charges
in INR
Total Ex‐Works
Price duly
packed in
INR/Total Price.
Excise Duty @
on self
manufactured
only
VAT/CST @ …
in INR on self
manufactured
only
Freight
including
Service tax @
Total FOR Site
Price (Supply)
in INR
Total Erection
&
Commissioning
Charges INR
Service tax @
including cess
on E & C in INR
Total E & C
prices including
Service Tax in
INR
Total Supply
and E&C in
INR
1 11 kV Unit Switchboard#6BANos.
13000A
2 11 kV Unit Switchboard#6BBNos.
13000A
3 11 kV Standby Switchboard#0BANos.
13000A
4 11 kV Colony SwitchboardNos.
1630A
5 3.3 kV Unit Aux. Switchboard#6CANos.
13000A
6 3.3 kV Misc. Aux. Switchboard#0CANos.
12500A
BOQ CUM PRICE SCHEDULE FOR ERECTION & COMMISSIONING OF MV SWGR ANNEXURE‐2H
1X500 MW FGUTPP
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
3. LV SWITCHGEAR, LT
BUSDUCT, NGR
1X500 MW UCHAHAR FGTPS (UNIT-6) SUPPLY BOM FOR LV SWITCHGEAR,LT BUS DUCT AND NGR ANNEXURE-3A
RATING(A) BOARD NO.
1 UNIT SERVICE SWBD. NOS. 1 3200 A 6DA2 BOILER MCC NOS. 1 1000 A 6HA3 TURBINE MCC NOS. 1 1000 A 6KA4 BOILER V&D MCC NOS. 1 250 A 6HB5 TURBINE VALVE MCC NOS. 1 250 A 6KB6 UNIT SERVICE ACDB. NOS. 1 630 A 6QA7 BOILER ACDB. NOS. 1 630 A 6HC8 UNIT EMERGENCY SWBD NOS. 1 2500 A 6DG9 ESP-1 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DC
10 ESP-2 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DD11 ESP-3 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DE12 ESP-4 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DF13 ESP A/C & VENT MCC NOS. 1 400 A 6TB14 ESP AREA MCC NOS. 1 250 A 6HD15 COOLING TOWER SWBD NOS. 1 3200 A 6DB16 STATION SERVICE SWBD. NOS. 1 3200 A 0DA17 MISC. SERVICE MCC NOS. 1 630 A 0QA18 VENTILATION MCC NOS. 1 1000 A 6TA19 AIR CONDITIONING MCC NOS. 1 1000 A 0TA20 FIRE WATER/WTP SWBD. NOS. 1 3200 A 0DD21 CHLORINATION PLANT MCC NOS. 1 400 A 0SA22 HYDROGEN & PT PLANT MCC NOS. 1 630 A 0SB23 RO DM PLANT MCC NOS. 1 400 A 0SC24 FUEL OIL SWBD NOS. 1 1600 A 0DB25 MAKE UP WATER SWGR NOS. 1 1000 A 0DE26 SERVICE BUILDING SWGR NOS. 1 2500 A 0DC27 CPU/COMPRESSOR MCC NOS. 1 630 A 0SD28 220V MAIN DCDB NOS. 1 1000A 6FA29 240V AC FUSE DBS NOS. 12 63A 12WAY 1P O/G (16 amp)30 220V FUSE DCDB NOS. 4 50A 12 WAY O/G (10 amp)
31 LT BUSDUCT-3200A SET 4
LT BUSDUCT 3200A, FROM LV TERMINALS OF DRY TYPE TRANSFORMERS TO PCC / PMCC. EACH SET OF 15 M
32 LT BUSDUCT-3200A SET 13
LT BUSDUCT 3200A, FROM LV TERMINALS OF OIL FILLED TRANSFORMERS TO PCC / PMCC. EACH SET OF 4 M
33 LT BUSDUCT-2500A SET 2
LT BUSDUCT 2500A, FROM LV TERMINALS OF OIL FILLED TRANSFORMERS TO PMCC. EACH SET OF 15 M
34 LT BUSDUCT-1600A SET 2
LT BUSDUCT 1600A, FROM LV TERMINALS OF OIL FILLED TYPE TRANSFORMERS TO PMCC. EACH SET OF 15 M
35
EACH SET COMPRISING OF:
FOR DRY TYPE TRANSFORMERS 1) 90 DEG BEND – 2NOS 2) FLEXIBLE (CU) AT TRANSFORMER END – 1SET 3) ADAPTER – 1NO. 4) PHASE CROSSOVER – 1 NO. 5) SET OF HARDWARE AT TRANSFORMER & SWITCHGEAR END 6) EXPANSION JOINT – 1NO.7) WALL FRAME ASSEMBLY – N/A8) SUPPORT STRUCTURE – N/A
FOR OIL FILLED TYPE TRANSFORMERS 1) 90 DEG BEND – 4 NOS 2) FLEXIBLE (CU) AT TRANSFORMER END – 1SET 3) ADAPTER – 1NO. 4) PHASE CROSSOVER – 1NO. 5) SET OF HARDWARE AT TRANSFORMER & SWITCHGEAR END 6) EXPANSION JOINT – 1NO.7) WALL FRAME ASSEMBLY – 1 No.8) SUPPORT STRUCTURE – 200KG
36LOCAL PUSH BUTTON STATIONS TYPE - A NOS. 700
EMERGENCY STOP PUSH BUTTON STATION. 1NO. PRESS TO LOCK & TURN TO RELEASE TYPE EMERGENCY STOP PB WITH 2NO + 2NC CONTACTS WITH SUPPORTING STRUCTURE
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
Sr.No. ITEM NAME UOM TOTAL QTY.
REMARKS
PAGE 1 OF 4
1X500 MW UCHAHAR FGTPS (UNIT-6) SUPPLY BOM FOR LV SWITCHGEAR,LT BUS DUCT AND NGR ANNEXURE-3A
37LOCAL PUSH BUTTON STATIONS TYPE - B NOS. 25
START & EMERGENCY STOP PUSH BUTTON STATION .1 NO. START PB & 1NO MUSHROOM HEAD STAYPUT WITH EMERGENCY STOP PB WITH 2NO + 2NC CONTACTS WITH SUPPORTING STRUCTURE
38 LOCAL PUSH BUTTON STATIONS TYPE - C
NOS. 25
FLAME PROOF EMERGENCY STOP PUSH BUTTON STATION. 1NO. PRESS TO LOCK TURN TO RELEASE TYPE EMERGENCY STOP PB WITH 2NO + 2NC
39 LOCAL MOTOR STARTERS 0.37 KW NOS. 5
40 LOCAL MOTOR STARTERS 0.55 KW NOS. 10
41 LOCAL MOTOR STARTERS 0.75 KW NOS. 10
42 LOCAL MOTOR STARTERS 1.10 KW NOS. 25
43 LOCAL MOTOR STARTERS 1.50 KW NOS. 25
44 LOCAL MOTOR STARTERS 2.20 KW NOS. 10
45 LOCAL MOTOR STARTERS 3.70 KW NOS. 5
46 LOCAL MOTOR STARTERS 5.5 KW NOS. 5
47 Numerical Relay LOT 1 of each type
48 NGR 11KV (300A, 10 SEC, 22.163 OHMS)
NOS. 3
49 NGR 3.3KV (300A, 10 SEC, 6.74 OHMS)
NOS. 8
50 TOOLS & TACKLE SET 151 SITE VISIT CHARGES NOS. 152 E & C SPARES SET 1
53 MANDATORY SPARES LOT 1
54 NETWORKING HARDWARE FOR NUMERICAL RELAYS
NOS. 1
55 SITE MODIFICATION MATERIAL LOT 1
NOTES:
AS PER ANNEXURE-DAS PER ANNEXURE- GAS PER ANNEXURE-E1
AS PER ANNEXURE-M
REQUIRED FOR SITE MODIFICATION @ 1% TOTAL EX-WORKS PRICE
AS PER ANNEXURE-E2
ALL NECESSARY SUPPORTING STRUCTURES ARE PART OF NGR
1. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF TOOLS & TACKLES AS PER LIST IN ANNEXURE –3D SHALL BE FURNISHED.2. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF E & C SPARES AS PER LIST IN ANNEXURE – 3E1 SHALL BE FURNISHED.3. ALL LT PCC/ MCC/ DBs SHALL BE SUPPLIED ALONGWITH THE INTEGRAL BASE FRAMES, FOUNDATION BOLTS, CABLE GLANDS & LUGS AND TOOLS & TACKLES AS MENTIONED IN DIFFERENT SECTIONS. ALSO SEPARATE BASE FRAMES OF ISMC-75 FOR SWITCHGEAR ERECTION (IN ADDITION TO INTEGRAL BASE FRAMES) SHALL BE SUPPLIED LOOSE BY THE BIDDER. ALL FIXING NUTS & BOLTS TOGETHER WITH FOUNDATION BOLTS SHALL ALSO BE SUPPLIED. PRICES FOR THE BASE FRAME SHALL BE BUILT IN THE SWITCHBOARD PRICE.4. SITE MODIFICATION CHARGES AS PER LIST IN ANNEXURE – 3G SHALL BE FURNISHED.5. ITEM WISE PRICES FOR TYPE TESTS CHARGES AS PER LIST IN ANNEXURE -3F SHALL BE FURNISHED.6. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF O&M AS PER LIST IN ANNEXURE - E2 SHALL BE FURNISHED. LIST OF RECOMMENDED O&M SPARES FOR 3 YEARS (OPTIONAL) WITH ITEM WISE PRICE & QUANTITY OF EACH ITEM AS RECOMMENDED BY MANUFACTURER SHALL BE FURNISHED IN SCHEDULE OF PRICES ALONGWITH.7. ITEM WISE PRICES WITH DESCRIPTION AND RATING OF EACH ITEM COMPLYING TO LIST FURNISHED IN THE SCHEDULE OF UNIT PRICES IN ANNEXURE - 3H SHALL BE FURNISHED IN SCHEDULE OF UNIT PRICE.
8. ITEM WISE PRICES WITH QUANTITY OF EACH ITEM OF NETWORKING HARDWARE FOR NUMERICAL RELAY (AS PER THE EQUIPMENT DETAILS MENTIONED IN THE REMARKS COLUMN) SHALL BE FURNISHED.9. FOR DETAILED BOARD WISE BOM, REFER ANNEXURE-3B.10. FOR DETAILED MODULE WISE BOM, REFER ANNEXURE-3C.11.ADDITION/DELETION OF QUANTITIES SHALL BE APPLICABLE AT THE QUOTED PRICE.12. FOLLOWING INFORMATION SHALL ALSO BE FURNISHED ALONG WITH BID:a. COMPLETE DIMENSIONS OF ALL THE BOARDS INCLUDING NO OF ACB, MCC AND DUMMY PANELS.b. DIMENSIONS OF EACH TYPE OF PANEL.c. MODULE SIZE OF EACH TYPE OF FEEDER.d. MINIMUM CLEARANCES REQUIRED ON ALL SIDES FOR EACH TYPE OF PANEL.13. DOUBLE COMPRESSION, NICKLE PLATED BRASS CABLE GLANDS & HEAVY DUTY LUGS OF BHEL APPROVED MAKE FOR EXTERNAL POWER, CONTROL & EARTHING CONNECTIONS AT SUPPLIED EQUIPMENT END AND FOUNDATION BOLT ARE IN THE SCOPE OF BIDDER. BIDDER TO QUOTE ALL EQUIPMENT WITH CABLE GLANDS, LUGS ABD FOUNDATION BOLTS.
14. COMMISSIONING AND TRAINING CHARGES OF NUMERICAL RELAYS SHALL BE INCLUDED IN THE PRICE QUOTED FOR SWGR & NO EXTRA CHARGESWILL BE GIVEN FOR THE SAME.
PAGE 2 OF 4
1 X 500 MW UNCHAHAR FG TPP UNPRICED PRICE SCHEDULE OF BOARDWISE BILL OF MATERIAL FOR LV SWGR ANNEXURE-3B
TYPE OF FEEDER 6DA 6KA 6KB 6QA 6HA 6HB 6HC 6HD 6DB 0DA 0QA 0TA 6TA 6TB 0SB 0DC 0DD 0DE 6DG 6FA 0SA 0DB 0SC 6DC 6DD 6DD 6DD 0SD TOTAL QTY
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
Total Supply and E&C in INR
DAET(I/C)(3200A) 2 3 2 2 2 2 2 2 17DAE(B/C)(3200A) 1 2 1 1 1 1 1 1 9DAET(I/C)(2500A) 2 2DAE(TIE)(2500A) 2 2 4DAE(B/C)(2500A) 1 1 2DAE(I/C)(2500A)DAEG(I/C)(2500A) 2 2DAET(I/C)(1600A) 2 2DAE(B/C)(1600A) 1 1DAET(I/C)(1000A) 2 2DAE(B/C)(1000A) 1 1DAE(I/C)(1000A) 2 2 2 2 8DAE(B/C)(1000A) 1 1 1 1 4DAE(O/G)(1000A) 4 5 4 13DAE(O/G)(1600A)DAE(O/G)(2500A) 3 3EM3(I/C)(630A) 2 2 2 2 2 10EM3(B/C)(630A) 1 1 1 1 1 5EM3(I/C)(630A) (fixed type) 2 2EM3(B/C)(630A) (fixed type) 1 1EM3(I/C)(400A) 2 2 4EM3(B/C)(400A) 1 1 2EMC3(I/C)(250A)EMC3(I/C)(250A) (fixed type) 2 2 4EMC3(B/C)(250A)EM3(I/C)(250A) 2 2EM3(B/C)(250A)CH(400A) (fixed type) 2 2DC(1000A) (fixed type) 2 2HD(1000A) (fixed type) 1 1DB(1000A) (fixed type) 2 2EM3(O/G) (630A) 7 2 2 4 2 2 2 2EM3(O/G) (400A) 3 3 10 3 2 5 22 24 22 22 116EM3(O/G) (250A) 3 4 4 4 2 17EM3(O/G) (250A) (fixed type) 8 8E3(O/G)(6A) 6 5 4 6 9 9 9 39 87E3(O/G)(10A) 8 12 4 4 4 4 36E3(O/G)(16A) 4 7 5 8 3 9 6 8 6 6 23 20 105E3(O/G)(20A) 4 8 3 3 4 6 4 6 5 43E3(O/G)(25A) 3 1 7 11E3 (O/G)(32A) 25 4 20 28 4 4 5 13 22 14 4 2 4 7 156E3 (O/G)(50A) 3 4 12 3 22E3 (O/G)(63A) 16 8 8 4 4 8 5 6 9 3 2 3 2 2 2 2 3 87E3 (O/G)(80A) 4 5 9E3 (O/G)(100A) 3 3 3 3 2 2 2 2 20E3 (O/G)(125A) 12 13 5 4 3 3 3 6 2 5 2 58E3 (O/G)(160A) 3 3 3 5 3 10 27E3 (O/G)(200A) 4 3 6 4 5 2 2 26E3(O/G)(6A) (fixed type) 194 23 217E3(O/G)(10A) (fixed type) 26 8 34E3(O/G)(16A) (fixed type) 26 4 4 34E3(O/G)(20A) (fixed type) 14 25 39E3(O/G)(25A) (fixed type) 42 42E3 (O/G)(32A) (fixed type) 55 44 5 104E3 (O/G)(50A) (fixed type) 10 10E3 (O/G)(63A) (fixed type) 7 32 39E3 (O/G)(80A) (fixed type) 11 11E3 (O/G)(100A) (fixed type) 3 3E3 (O/G)(125A) (fixed type) 30 4 34E1(6A) 22 3 6 17 8 16 72E1(10A) 10 4 3 3 20E1(16A) 6 5 7 6 2 2 13 41E1(20A) 3 10 3 12 28E1(25A)E1(32A) 9 22 5 9 45E1(63A)E1(100A)E1(6A) (fixed type) 13 13E1(10A) (fixed type) 15 15E1(25A) (fixed type) 12 12E1(63A) (fixed type) 4 4EA1(.5KW)EA1(2KW)EA1(3KW)EA1(5.5KW) 4 4EA3(.06KW)EA3(.09KW)EA3(.55KW)EA3(1.1KW)EA3(1.2KW)EA3(1.5KW)EA3(2KW)EA3(2.2KW)EA3(3KW)EA3(3.7KW)EA3(4KW)EA3(4.5KW)EA3(5KW) 4 4EA3(5.5KW)EA3(7KW)EA3(7.5KW)EA3(8KW)EA3(9KW) 4 4EA3(10KW)EA3(15KW)
1 X 500 MW UNCHAHAR FG TPP UNPRICED PRICE SCHEDULE OF BOARDWISE BILL OF MATERIAL FOR LV SWGR ANNEXURE-3B
TYPE OF FEEDER 6DA 6KA 6KB 6QA 6HA 6HB 6HC 6HD 6DB 0DA 0QA 0TA 6TA 6TB 0SB 0DC 0DD 0DE 6DG 6FA 0SA 0DB 0SC 6DC 6DD 6DD 6DD 0SD TOTAL QTY
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
Total Supply and E&C in INR
EA3(16KW)EA3(18KW)EA3(22KW) 5 5EA3(27KW)EA3(30KW)EA3(40KW)DN1 (0-5.5KW) 3 3 6DK2 (0.0-5.5KW) 34 13 28 19 11 5 10 10 37 29 29 29 46 2 53 33 388DK2 (5.6-7.0KW) 18 18DK2 (7.1-13.0KW) 3 14 3 2 3 10 7 7 10 7 66DK2 (13.1-24.0KW) 2 2 2 4 4 5 5 10 15 3 4 56DK2 (24.1-29.9KW) 2 2DK21 (30.0-44.9KW) 2 3 11 3 2 3 3 27DK21 (45.0-55.0KW) 8 5 1 14DK21 (55.1-75.0KW) 2 3 3 2 10DK21 (75.1.1-89.9.0KW) 3 5 3 11DK21 (90-109.9.0KW) 2 5 7DK2E(0.0-5.5KW)DK2E(5.6-7.0KW)DK2E(7.1-13.0KW) 2 2DK2E(13.1-24.0KW)DK2E(24.1-29.9KW)DK21E (30.0-37.0KW)DK21E (37.1-55.0KW)DK21E (55.1-75.0KW)DK21E (75.1-89.9.0KW)DK21E (90-109.9.0KW) 4 4K2/K3 (0.0- 5.5KW) 10 14 3 3 15 4 10 59K2/K3 (5.6-7.0KW)K2/K3 (7.1-13.0KW) 5 6 5 5 21K2/K3 (13.1-24.0KW) 3 3 6K2/K3 (24.1-29.9KW)K21/K31(30.0-37.0KW) 8 8K21/K31(37.1-55.0KW)K21/K31(55.1-75.0KW)K21/K31(75.1-89.9KW)K21/K31(90-109.9KW)DM(110.0-200.0KW) 5 18 3 5 4 3 38CS 2 2 2 2 2 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 49VM 2 1 2 2 1 2 1 2 2 2 2 2 2 2 2 2 29G1 2 2 2 2 2 2 2 2 2 2 20G2 2 2SH 1 1 1 1 1 1 1 1 2 2 2 2 1 17X 6A 11 11X 10A 83 83X 16A 7 7X 25A 19 19X 32AX 50A 10 10X 63A 5 5X 80AX 100AX 125A 4 4X 160A 4 4X 200 AX 400 A 3 3DW UP TO 10AS 2 2TOTAL PRICE
SL. NO.
ITEM DESCRIPTION QUANTITY
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service Tax
in INR
Total Supply and E&C in
INR
1BREAKER LIFTING AND HANDLING TROLLEY (TELESCOPIC TROLLEY)
15
2 MODULE RACKING HANDLE FOR BREAKERS 12
3MODULE RACKING HANDLE FOR MCC MODULES
20
4
TEST PLUG WITH COUPLING CABLES FOR TESTING BREAKER IN WITHDRAWN POSITION
4
Annexure-3DTools & Tackles and Accessories
1 FACTORY BUILT ASSEMBLIES (PCC/MCC/DB)
1.1 Busbar supports (Horizontal) 1 set of 3 1SET1.2 Primary isolating contacts (Bus side)
of each rating
1 set of 3 1SET
1.3 Primary isolating contacts (Load side) of each rating
1 set of 3 1SET
1.4 Secondary isolating contacts of each rating
1 set of 3 1SET
1.5 Gaskets (each size) Meter 101.6 Fixed Terminal (1way) Nos. 201.7
Shrouds (for outgoing modules)
Nos. one for each physical size of
module
1.8 Wire (for secondary wiring)a. 2.5 mm2 Metres 100
b. 1.5mm2 Metres 100
1.9 Lugs (for secondary wiring) Nos. 100
2Air Circuit Breaker(for each rating)
2.1Shunt trip coil
Nos. 1
2.2spring charging motor
Nos. 1 motor of each rating
2.3closing coil
Nos. 1
2.4Auxiliary switch
Nos. 1
3ISOLATING SWITCH
3.1Main contact kit for each rating
1 set of 3 poles
1
4POWER CONTACTORS
4.1Contactor coil of each rating
Nos. 1
4.2Contacts kit (main) for each rating
1 set of 3 poles
1
5AUXILIARY CONTACTORS
5.1Complete unit with 2NO + 2NC contacts
Nos. 1 no. of each rating/type
5.2Contactor coils
a.AC for each rating
Set 1
b.DC for each rating
Set 1
6MCCB
ANNEXURE 3E1
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E &
C in INR
Total E & C prices including Service Tax
in INR
Total Supply and E&C in INR
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR S.No. ITEM / COMPONENT UNIT QUANTITY
Total Ex-Works Price duly packed in INR/Total Price.
Unit Ex-works price/Unit Price
6.1MCCB (EACH RATING)
Nos. 1
7PUSH BUTTONS
6.1Actuator contacts
Nos. 5
6.2Element
Nos. 5
8INDICATING LAMPS
8.1Complete unit
Nos. 10
8.2Lens (assorted)
Nos. 10
9OTHERS
9.1Selector & control switch (each type)
Nos. 1
9.2AC Voltmeter (0-500V)
Nos. 1
9.3DC Voltmeter (0-300 or 0-150 V)
Nos. 1
10LT BUSDUCT
10.1Busduct support insulators
TPN set for each rating of busduct.
1
10.2Gaskets for each rating of busduct
set (consisting of 10 meters or 2 nos.each of
1
11 NGR11.1 Porcelein post/support
insulator (for mounting on structure)
Nos. 1
11.2 Resistor bank support insulator (mounted inside enclosure)
Nos. 1
11.3Porcelein terminal bushing
Nos. 1
Note:
Bidder to ensure correctness & completeness of type and quantity of every item considered by them in above list. Bidder to note that there will not be any commercial implication to NBPPL as per final requirement after award of contract / during detailed engineering based on BOQ of various equipments given in the specification.
ITEM DESCRIPTION QTYUnit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
1. Complete pole of breaker 1 No. of each type & rating. 2. Spring charging motors 1 No. of each type & rating 3.Aux. Contact set 5 Nos. of each rating. 4. Limit switches 5 Nos. of each rating 5. Arc chutes 3 Nos. of each rating 6. Fixed contact set 5 Sets. 7. Moving contact set 5 Sets. 8. Arcing contact 6 Sets. 9. Charging spring 2 Nos. of each type 10. Current transformer (metering) 3 Nos. 11. Current transformer (protection) 3 Nos. 12. Closing coil 5 Nos. 13. Trip coil 5 Nos. 14. CT for Bimetal O/L relays 3 Nos. of each rating 15. Voltage transformer 3 Nos. 16. Control supply transformer 1 No. 17. Ammeter 1 No. of each range 18. Voltmeter 1 No. of each range 19. Relays 1 No. of each type & rating 20. Power contactor 1 No. of each rating. 21. Coil of above contactor 1 No. of each rating. 22. Air break switches 1 No. of each rating. 23. DP air break switches (DC) 1 No. 24. Control & selector switches. 3 Nos. of each rating. 25. Control fuses & neutral links 1 No. of each rating. 26. Indicating lamps 2 Nos. of each type 27. Bus bar support insulators 1 No. of each size. 28. Bus duct flexibles connectors 1 No. of each type. 29. Primary disconnect in MCC (Male / female contact) 5 Nos. 30. Push buttons 2 Nos. of each type & colour. 31. Power fuses 5 Nos. for each rating. 32. Thermal bimetal relays 2 Nos. of each rating 33. Indication lamp holders complete. 2 Nos. of each rating 34. Maintenance tools accessories formaintenance 1 Set 35. Terminal blocks 1Set for each type/rating 36. Busbar aluminium flat pieces 3 Meter of each size 37. Busbar angles/formed pieces for breaker 1 No. of each type & size
MANDATORY SPARE FOR AC, VENTILATION, COMPRESS AIR SYSTEM ANNEXURE-3F
SL.NO. DETAILS QUANTITY Unit Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on
self manufactu
red only
VAT/CST @ … in
INR on self manufactu
red only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Charges INR
Service tax @ including cess on Total Charges in
INR
Total Charges including Service
Tax in INR
1 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR SKILLED TECHNICIAN (EXCEPT DAILY CHARGES)
5 VISITS
2 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SKILLED TECHNICIAN
30 DAYS
3 LUMP SUM ALL INCLUSIVE CHARGES PER VISIT FOR SERVICE ENGINEER (EXCEPT DAILY CHARGES)
5 VISITS
4 LUMP SUM ALL INCLUSIVE DAILY CHARGES FOR SERVICE ENGINEER
15 DAYS
NOTES:
1) AMOUNT PAYABLE FOR SKILLED TECHNICIAN PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 1 ABOVE + (DAILY CHARGES AS PER SL. NO. 2 ABOVE X NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)
2) AMOUNT PAYABLE FOR SERVICE ENGINEER PER VISIT TO SITE = VISIT CHARGES AS PER SL. NO. 3 ABOVE + (DAILY CHARGES AS PER SL. NO. 4 ABOVE X NO. OF DAYS AT SITE) (TO BE CERTIFIED BY SITE)
ANNEXURE 3GSite Visit Charges
1X500 MW UCHAHAR FGTPS (UNIT‐6) ERECTION AND COMMISIONING BOM FOR LV SWITCHGEAR ANNEXURE‐3A
RATING(A) BOARD NO.
1 UNIT SERVICE SWBD. NOS. 1 3200 A 6DA
2 BOILER MCC NOS. 1 1000 A 6HA
3 TURBINE MCC NOS. 1 1000 A 6KA
4 BOILER V&D MCC NOS. 1 250 A 6HB
5 TURBINE VALVE MCC NOS. 1 250 A 6KB
6 UNIT SERVICE ACDB. NOS. 1 630 A 6QA
7 BOILER ACDB. NOS. 1 630 A 6HC
8 UNIT EMERGENCY SWBD NOS. 1 2500 A 6DG
9 ESP‐1 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DC
10 ESP‐2 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DD
11 ESP‐3 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DE
12 ESP‐4 LT MAIN SWITCH BOARD NOS. 1 3200 A 6DF
13 ESP A/C & VENT MCC NOS. 1 400 A 6TB
14 ESP AREA MCC NOS. 1 250 A 6HD
15 COOLING TOWER SWBD NOS. 1 3200 A 6DB
16 STATION SERVICE SWBD. NOS. 1 3200 A 0DA
17 MISC. SERVICE MCC NOS. 1 630 A 0QA
18 VENTILATION MCC NOS. 1 1000 A 6TA
19 AIR CONDITIONING MCC NOS. 1 1000 A 0TA
20 FIRE WATER/WTP SWBD. NOS. 1 3200 A 0DD
21 CHLORINATION PLANT MCC NOS. 1 400 A 0SA
22 HYDROGEN & PT PLANT MCC NOS. 1 630 A 0SB
23 RO DM PLANT MCC NOS. 1 400 A 0SC
24 FUEL OIL SWBD NOS. 1 1600 A 0DB
25 MAKE UP WATER SWGR NOS. 1 1000 A 0DE
26 SERVICE BUILDING SWGR NOS. 1 2500 A 0DC
27 CPU/COMPRESSOR MCC NOS. 1 630 A 0SD
28 220V MAIN DCDB NOS. 1 1000A 6FA
29 240V AC FUSE DBS NOS. 12 63A 12WAY 1P O/G (16 amp)
30 220V FUSE DCDB NOS. 4 50A 12 WAY O/G (10 amp)
31 LT BUSDUCT‐3200A SET 4
LT BUSDUCT 3200A, FROM LV
TERMINALS OF DRY TYPE
TRANSFORMERS TO PCC / PMCC.
EACH SET OF 15 M
32 LT BUSDUCT‐3200A SET 13
LT BUSDUCT 3200A, FROM LV
TERMINALS OF OIL FILLED
TRANSFORMERS TO PCC / PMCC.
EACH SET OF 4 M
33 LT BUSDUCT‐2500A SET 2
LT BUSDUCT 2500A, FROM LV
TERMINALS OF OIL FILLED
TRANSFORMERS TO PMCC. EACH
SET OF 15 M
34 LT BUSDUCT‐1600A SET 2
LT BUSDUCT 1600A, FROM LV
TERMINALS OF OIL FILLED TYPE
TRANSFORMERS TO PMCC. EACH
SET OF 15 M
Sr.No. ITEM NAME
Total Supply
and E&C in INR
Excise Duty @ on
self manufactu
red only
VAT/CST @ … in
INR on self manufactu
red only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR UOM TOTAL QTY.
Total Erection & Commissi
oning Charges in INR
Service tax @
including cess on E & C in INR
Total E & C prices including Service
Tax in INR
REMARKSUnit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
PAGE 1 OF 4
1X500 MW UCHAHAR FGTPS (UNIT‐6) ERECTION AND COMMISIONING BOM FOR LV SWITCHGEAR ANNEXURE‐3A
35
EACH SET COMPRISING OF:
FOR DRY TYPE TRANSFORMERS 1) 90 DEG BEND – 2NOS
2) FLEXIBLE (CU) AT
TRANSFORMER END – 1SET
3) ADAPTER – 1NO.
4) PHASE CROSSOVER – 1 NO.
5) SET OF HARDWARE AT
TRANSFORMER & SWITCHGEAR
END
6) EXPANSION JOINT – 1NO.
7) WALL FRAME ASSEMBLY –
N/A
8) SUPPORT STRUCTURE – N/A
FOR OIL FILLED TYPE TRANSFORMERS 1) 90 DEG BEND – 4 NOS
2) FLEXIBLE (CU) AT
TRANSFORMER END –
1SET
3) ADAPTER – 1NO.
4) PHASE CROSSOVER –
1NO.
5) SET OF HARDWARE
AT TRANSFORMER &
SWITCHGEAR END
6) EXPANSION JOINT –
1NO.
7) WALL FRAME
ASSEMBLY – 1 No.
8) SUPPORT STRUCTURE
– 200KG
36LOCAL PUSH BUTTON
STATIONS TYPE ‐ ANOS. 700
EMERGENCY STOP PUSH
BUTTON STATION. 1NO. PRESS
TO LOCK & TURN TO RELEASE
TYPE EMERGENCY STOP PB WITH
2NO + 2NC CONTACTS WITH
SUPPORTING STRUCTURE
37LOCAL PUSH BUTTON
STATIONS TYPE ‐ BNOS. 25
START & EMERGENCY STOP
PUSH BUTTON STATION .1 NO.
START PB & 1NO MUSHROOM
HEAD STAYPUT WITH
EMERGENCY STOP PB WITH 2NO
+ 2NC CONTACTS WITH
SUPPORTING STRUCTURE
38LOCAL PUSH BUTTON
STATIONS TYPE ‐ CNOS. 25
FLAME PROOF EMERGENCY
STOP PUSH BUTTON STATION.
1NO. PRESS TO LOCK TURN TO
RELEASE TYPE EMERGENCY STOP
PB WITH 2NO + 2NC CONTACTS
WITH SUPPORTING STRUCTURE
39 LOCAL MOTOR STARTERS 0.37 NOS. 5
40 LOCAL MOTOR STARTERS 0.55 NOS. 10
41 LOCAL MOTOR STARTERS 0.75 NOS. 10
42 LOCAL MOTOR STARTERS 1.10 NOS. 25
43 LOCAL MOTOR STARTERS 1.50 NOS. 25
44 LOCAL MOTOR STARTERS 2.20 NOS. 10
45 LOCAL MOTOR STARTERS 3.70 NOS. 5
46 LOCAL MOTOR STARTERS 5.5 NOS. 5
47NGR 11KV (300A, 10 SEC,
22.163 OHMS)NOS. 3
ALL NECESSARY SUPPORTING
STRUCTURES ARE PART OF NGR
48NGR 3.3KV (300A, 10 SEC, 6.74
OHMS)NOS. 8
PAGE 2 OF 4
GROUP-A None
GROUP-B 1 Complete breaker 3 Nos. of each type & rating 2 Ammeter 2 Nos. of each type, size &
range 3 Voltmeter 2 Nos. of each type, size &
range 4 Relays 2 Nos. of each type 5 Bus bar support insulators(Porcelain) 10 Nos.
GROUP-C 1 Spring charging motors 3 Nos. of each type & rating 2 Aux. Contact set 6 Sets of each type & rating 3 Limit switches 10 Nos. 4 Arc chutes 4 Nos. of each type & rating 5 Fixed contact set 6 Sets of each type & rating 6 Moving contact set 6 Sets of each type & rating 7 Arcing contact 6 Sets of each type 8 Charging spring 4 Nos. of each type & rating 9 Current transformer 3 Nos. of each type & ratio
10 Closing coil 12 Nos. of each type & rating 11 Trip coil 12 Nos. of each type & rating 12 CT for Bimetal O/L relays 3 Nos. of each type & rating 13 Voltage transformer 3 Nos. of each type & ratio 14 Control supply transformer 3 Nos.of each type and rating 15 (a) Power contactor 2 Nos. of each type & rating
(b) Coil of above contactor 2 Nos. of each type & rating 16 Air break switches 3 Nos. of each type & rating 17 DP air break switches(DC) 3 Nos. of each type & rating 18 Control & selector switches 5 Nos. of each type & rating
19 Control fuses & neutral links Total 50 Nos.( Fuses) & 10 Nos. (Neutral links), to cover all the ratings.
20 Indicating lamps Total 50 Nos. to cover all the types & ratings
Total E & C prices including Service Tax
in INR
Total Supply and E&C in INR
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured
onlySl No. Item Description Quantity
LIST OF MANDATORY SPARES FOR 500MW UNITS LT SWITCHGEAR AND LT BUSDUCTANNEXURE-3E2
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E &
C in INR
21 Vertical bus bar dropper support insulators(FRP) 25 Nos. 22 Bus duct flexible connectors 1 Set for thee phases of each type & size
23(a) Primary disconnect in MCC( Bus bar end)(Male/female contact) Total 15 Nos. proportionately divide for all ratings
(b) Secondary disconnect in MCC(Cable end) Total 15 Nos. proportionately divide for all ratings 24 Push buttons 15 Nos.
25 Power fuses Total 100 Nos. proportionately divide for all ratings
26 Thermal Bimetal relays Total 30 Nos. proportionately divide for all ratings 27 Current transducers 12 Nos. proportionately divide for all ratings 28 Voltage transducers 12 Nos. proportionately divide for all ratings. 29 Indication lamp holders complete 10% of each type & rating 30 Busbar aluminium flat pieces 12 meters of each type & rating 31 Busbar angles/formed pieces for breaker 2 Nos. of each type 32 Terminal blocks 12 Nos. of each type & rating
CHARGES OF NETWORKING HARDWAREFOR NUMERICAL RELAYS MULTIFUNCTION METERS
ANNEXURE-3M
1.0 NETWORKING OF NUMERICAL RELAYS:-
Sl. No. ITEM DESCRIPTION QUANTITY
Unit Ex-works price/Unit
Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufacture
d only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess on E &
C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C in INR
1ETHERNET SWITCHES ON IEC61850 (16 CHANNELS) 20 Nos.
3 DATA CABLE (CAT-5) FOR CONNECTION OF NUMERICAL RELAYS TO ETHERNET SWITCH
3 km
4
LAPTOP PC WITH LICENCED VERSION SOFTWARE, HARDWARE ALONGWITH CONNECTING CABLES FOR RELAY PARAMETERISATION
1 NO
NOTE
1)
2)
2ETHERNET SWITCHES ON IEC61850 (8 CHANNELS) 10 Nos.
All above items shall be supplied along with acessories (including special tools for installation) required for the completeness of system.
Looping of all the LT SWGR realys shall be in bidders scope.Bidder to configure each LT protection relay to provide protection & control facility up to data concentrator as per attched typical architecture for networking of numerical relays.(ANNEXURE-3P)
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
4. CABLING, EARTHING AND LIGHTNING PROTECTION
1x 500MW FGUTPP STAGE IV
PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
Total Supply and E&C in INR
1.0 HOT DIP GALVANISED LADDER TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.
i) CABLE TRAY 2 MM THICK- LADDER TYPE 150W MTR 4800 3400
ii) CABLE TRAY 2 MM THICK- LADDER TYPE 300W MTR 13000 9000
iii) CABLE TRAY 2 MM THICK- LADDER TYPE 600W MTR 26000 18200
2.0
HOT DIP GALVANISED PERFORATED TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.
i) CABLE TRAY 2 MM THICK- PERFORATED TYPE 150W MTR 2000 1400
ii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 300W MTR 5200 3700
iii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 600W MTR 7700 5400
3.0 HOT DIP GALVANISED CABLE TRAY ACCESSORIES
3.1 LADDER TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS
i) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 20 15
ii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 20 15
iii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 250 175
3.2LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)
i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7
ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7
iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35
3.3LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)
i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7
ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7
iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35
3.4 LADDER TYPE TEES-600mm RADIUS
i) LAD TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7
ii) LAD TEES 600MM RADIUS 2 MM THICK 300W NOS 140 100
iii) LAD TEES 600MM RADIUS 2 MM THICK 600W NOS 320 230
3.5 LADDER TYPE CROSS-600mm RADIUS
i) LAD CROSS 600 RAD 2 MM THICK 300W NOS 10 7
ii) LAD CROSS 600 RAD 2 MM THICK 600W NOS 25 20
3.6 LADDER TYPE REDUCERS
i) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8
ii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8
iii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8
3.7 PERFORATED TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS
i) PER HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 10 7
ii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 10 7
iii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 100 70
3.8PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)
i) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7
ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7
iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35
3.9PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)
i) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7
ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7
iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35
3.10 PERFORATED TYPE TEES-600mm RADIUS
i) PER TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7
ii) PER TEES 600MM RADIUS 2 MM THICK 300W NOS 10 7
iii) PER TEES 600MM RADIUS 2 MM THICK 600W NOS 10 7
3.11 PERFORATED TYPE CROSS-600mm RADIUS
i) PER CROSS 600 RAD 2 MM THICK 300W NOS 10 7
ii) PER CROSS 600 RAD 2 MM THICK 600W NOS 20 10
3.12 PERFORATED TYPE REDUCERS
i) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8
ii) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8
iii) PER REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8
ANNEXURE-4A: MAIN ITEMS
Item.No Item UnitOrder
QuantityLot-I
Quantity
PRICES
1x 500MW FGUTPP STAGE IV
PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)
3.13 TROUGHS
i) 50 MM WIDE MTR 1000 700
ii) 75 MM WIDE MTR 1000 700
3.14
HOT DIP GALVANISED CABLE TRAY COVER COMPLETE WITH FORMED CHANNEL, PIPE, GI FLAT, BOLTS WITH NUTS & WASHERS & FIXING HARDWARES ETC. (1.6mm)THICK GALVANISED MS SHEET)
i) COVER 1.6MM THK- NON PERFORATED GALV MS 150W MTR 100 5
ii) COVER 1.6MM THK- NON PERFORATED GALV MS 300W MTR 100 5
iii) COVER 1.6MM THK- NON PERFORATED GALV MS 600W MTR 100 5
4.1SINGLE CHANNEL SC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 10000 7000
4.2DOUBLE CHANNEL DC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 16000 11200
4.3
CANTILEVER ARM EACH COMPLETE WITH 2 NOS. - M12 HEX. BOLT & WASHER 2 NOS. - M12 SPRING NUTS 2 NOS. - M6 PAN HEAD SCREWS & WASHER 2 NOS. - M6 SPRING NUTS
i) Cantilever arm of 750 mm for600mm wide cable trays Nos. 1000 700
ii) Cantilever arm of 620 mm for 600mm wide cable trays Nos. 19000 13300
iii) Cantilever arm of 320 mm for 300mm wide cable trays Nos. 9500 6650
iv) Cantilever arm of 170 mm for 150mm wide cable trays Nos. 3500 2450
4.4CLAMPS AND FITTINGS COMPLETE WITH REQUIRED HARDWARES (Spring nuts/ washers etc. as required for complete installation)
i) 90˚ ANGLE FITTING HL1 Nos. 6000 4200
ii) CLAMP FOR SINGLE CHANNEL CC1 Nos. 14500 10150
iii) CLAMP FOR DOUBLE CHANNEL CC2 Nos. 7200 5040
(iv) BASE PLATE FOR SINGLE CHANNEL BP1 Nos. 300 210
(v) BASE PLATE FOR DOUBLE CHANNEL BP2 Nos. 1800 1260
(vi) BEAM CLAMP BC1 Nos. 400 280
(vii) TRAY FIXING CLAMP TC1 Nos. 2700 1890
(viii) FLAT PLATE STRAIGHT FITTING PF2 Nos. 200 140
(ix) FLAT PLATE TEE FITTING PF1 Nos. 200 140
(x) 90˚ ANGLE FITTING LA1 Nos. 9100 6370
(xi) TRESTLE BRACKET Nos. 200 140
5.0 DOUBLE COMPRESSION HEAVY DUTY BRASS CABLE GLANDS
ABOVE (MM) UP TO (MM)
(i) -- 15 Nos. 600 420
(ii) 15 18 Nos. 160 110
(iii) 18 21 Nos. 100 70
(iv) 21 24 Nos. 110 80
(v) 24 27 Nos. 20 15
(vi) 27 30 Nos. 100 70
(vii) 30 33 Nos. 30 20
(viii) 33 36 Nos. 70 50
(ix) 36 39 Nos. 20 15
(x) 39 42 Nos. 50 35
(xi) 42 46 Nos. 15 10
(xii) 46 50 Nos. 30 20
(xiii) 50 54 Nos. 30 20
(xiv) 54 58 Nos. 30 20
(xv) 58 62 Nos. 20 14
(xvi) 62 67 Nos. 10 5
(xvii) 67 74 Nos. 10 5
6.0 TINNED COPPER LUGS
(SOLDERLESS CRIMPING TYPE) (i) 2.5 SQ MM Nos. 1100 770
(ii) 6 SQ MM Nos. 85 60
(iii) 10 SQ MM Nos. 260 180
(iv) 16 SQ MM Nos. 40 30
(v) 25 SQ MM Nos. 340 240
(vi) 35 SQ MM Nos. 10 7
(vii) 50 SQ MM Nos. 300 210
(viii) 95 SQ MM Nos. 130 90
(ix) 120 sq mm Nos. 20 15
(x) 150 SQ MM Nos. 30 20
(xi) 240 SQ MM Nos. 95 70
(xii) 400 SQ MM Nos. 50 35
(xiii) 630 SQ MM Nos. 40 30
7.0 TINNED COPPER LUGS
(WITH INSULATING SLEEVE)
(i) 1.5 SQ MM Nos. 950 650
(ii) 2.5 SQ MM Nos. 290 200
8.0 ALUMINIUM LUGS
(i) 10 SQ MM Nos. 50 35
(ii) 16 SQ MM Nos. 50 35
(iii) 25 SQ MM Nos. 50 35
(iv) 35 SQ MM Nos. 50 35
(v) 50 SQ MM Nos. 50 35
(vi) 95 SQ MM Nos. 50 35
(vii) 120 sq mm Nos. 50 35
(viii) 150 SQ MM Nos. 50 35
(ix) 240 SQ MM Nos. 50 35
(x) 400 SQ MM Nos. 50 35
(xi) 630 SQ MM Nos. 50 35
1x 500MW FGUTPP STAGE IV
PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)
9.0 TREFOIL CLAMPS ( FOR SIZES AS UNDER)
(i) TREFOIL CLAMP CABLE OD- 25.1 - 30MM NOS. 500 450
(ii) TREFOIL CLAMP CABLE OD- 30.1 - 35MM NOS. 3600 3240
(iii) TREFOIL CLAMP CABLE OD- 35.1 - 40MM NOS. 4950 4460
(iv) TREFOIL CLAMP CABLE OD-45.1 - 50MM NOS. 850 770
(v) TREFOIL CLAMP CABLE OD-50.1 - 55MM NOS. 500 450
10.0 HT TERMINATION KITS FOR
10.1 11 KV UNARMOURED HT. XLPE POWER CABLE
(i) 1C-630 sq mm Nos. 25 18
(ii) 1C-300 sq mm Nos. 75 54
(iii) 3C-150 sq mm Nos. 40 28
10.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE
(i) 1C-630 sq mm Nos. 190 136
(ii) 1C-185 sq mm Nos. 65 46
(iii) 3C-150 sq mm Nos. 200 144
10.3 3.3 KV ARMOURED HT.XLPE POWER CABLE
(i) 3C-150 sq mm Nos. 6 4
11.0 HT/LT JOINT KITS FOR
11.1 11 KV UNARMOURED HT. XLPE POWER CABLE
(i) 1C-300 sq mm Nos. 34 24
11.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE
(i) 3C-150 sq mm Nos. 50 34
11.3 1.1 KV UNARMOURED LT.XLPE POWER CABLE
(i) 3C-240 sq mm Nos. 2 1
(ii) 3C-150 sq mm Nos. 3 2
12.0 RIGID GALVANISED MS CONDUITS / PIPES
(i) 100 mm diameter Metres 1000 700
(ii) 75 mm diameter Metres 1000 700
(iii) 50 mm diameter Metres 2000 1400
(iv) 25 mm diameter Metres 1000 700
(v) 20 mm diameter Metres 1000 700
13.0FLEXIBLE CONDUITS MADE OF COLD ROLLED ANNEALED
ELECTRO GALVANISED MS STRIP (i) 25 mm diameter Metres 2000 1400
(ii) 18 mm diameter Metres 1000 700
14.0 PVC Conduits (i) 250 mm diameter Metres 100 70(ii) 200 mm diameter Metres 100 70(iii) 100 mm diameter Metres 100 70(iv) 50 mm diameter Metres 100 70
15.0LIGHTNING PROTECTION AND ABOVE GROUND
EARTHING MATERIAL
15.1 Hot Dip Galvanised Steel Flats (to be supplied in length of minimum 6 meters)
(i) 65X8 mm MT 84 60
(ii) 50X6 mm MT 2 1
(iii) 25X6 mm MT 14 10
15.2 20 mm dia., 1-meter long Hot Dip Galvanized GS rod for vertical air termination as per enclosed drawing no.PE-DG-999-509-E003 .sheet
03 of 04 Nos.100 70
15.3 Test link with 150x25x6 thick Hot Dip Galvanised GS Flat wih box as per enclosed drawing no. PE-DG-999-509-E003 sheet 01 of 04
Nos.185 130
15.4 8 SWG Hot Dip Galvanized GI Stranded WireMeters
5000 3500
15.5
Flexible braided Copper Conductor of 600 mm length (Cross section equivalent to 300 sq. mm) with tinned copper clamp connected by U-bolt for fence gate earthing as per enclosed drawing no. PE-DG-999-
509-E003 sheet 03 of 04 Nos.25 20
15.6 50NB Galvanized MS pipe 2 meter long Perforated along the length as per enclosed drawing no. PE-DG-999-509-E003 sheet 03 of 04
Nos.145 100
16.0 JUNCTION BOX (i) 6 WAY Nos. 10 7(ii) 12 WAY Nos. 25 17(iii) 24 WAY Nos. 20 14(iv) 36 WAY Nos. 10 7(v) 48 WAY Nos. 10 7
1x 500 MW FGUTPP STAGE IV
BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)
Unit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on
self manufactu
red only
VAT/CST @ … in
INR on self manufactu
red only
Freight including
Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissi
oning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices including Service
Tax in INR
1.0 HOT DIP GALVANISED LADDER TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.
i) CABLE TRAY 2 MM THICK- LADDER TYPE 150W MTR 4800 3400
ii) CABLE TRAY 2 MM THICK- LADDER TYPE 300W MTR 13000 9000
iii) CABLE TRAY 2 MM THICK- LADDER TYPE 600W MTR 26000 18200
2.0
HOT DIP GALVANISED PERFORATED TYPE CABLE TRAY COMPLETE WITH COUPLER PLATES, FASTENERS, CLAMPS AND FIXING HARDWARES ETC.
i) CABLE TRAY 2 MM THICK- PERFORATED TYPE 150W MTR 2000 1400
ii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 300W MTR 5200 3700
iii) CABLE TRAY 2 MM THICK- PERFORATED TYPE 600W MTR 7700 5400
3.0HOT DIP GALVANISED CABLE TRAY ACCESSORIES
3.1 LADDER TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS
i) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 20 15
ii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 20 15
iii) LAD HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 250 175
3.2LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)
i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7
ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7
iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35
3.3LADDER TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)
i) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7
ii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7
iii) LAD VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35
3.4 LADDER TYPE TEES-600mm RADIUS
i) LAD TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7
ii) LAD TEES 600MM RADIUS 2 MM THICK 300W NOS 140 100
iii) LAD TEES 600MM RADIUS 2 MM THICK 600W NOS 320 230
3.5 LADDER TYPE CROSS-600mm RADIUS
i) LAD CROSS 600 RAD 2 MM THICK 300W NOS 10 7
ii) LAD CROSS 600 RAD 2 MM THICK 600W NOS 25 20
3.6 LADDER TYPE REDUCERS
i) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8
ii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8
iii) LAD REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8
3.7PERFORATED TYPE HORIZONTAL 90 DEG. BEND-600mm RADIUS
i) PER HOR 90DEG BEND 2 MM THICK 600 RAD 150W NOS 10 7
ii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 300W NOS 10 7
iii) PER HOR 90DEG BEND 2 MM THICK 600 RAD 600W NOS 100 70
3.8PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (INSIDE)
i) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 150W NOS 10 7
ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 300W NOS 10 7
iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-INSIDE 600W NOS 50 35
3.9PERFORATED TYPE VERTICAL 90 DEG. BEND-600mm RADIUS (OUTSIDE)
i) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 150W NOS 10 7
ii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 300W NOS 10 7
iii) PER VER 90DEG BEND 2 MM THICK 600 RAD-OUTSIDE 600W NOS 50 35
3.10 PERFORATED TYPE TEES-600mm RADIUS
i) PER TEES 600MM RADIUS 2 MM THICK 150W NOS 10 7
ii) PER TEES 600MM RADIUS 2 MM THICK 300W NOS 10 7
iii) PER TEES 600MM RADIUS 2 MM THICK 600W NOS 10 7
3.11 PERFORATED TYPE CROSS-600mm RADIUS
i) PER CROSS 600 RAD 2 MM THICK 300W NOS 10 7
ii) PER CROSS 600 RAD 2 MM THICK 600W NOS 20 10
3.12 PERFORATED TYPE REDUCERS
i) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-300W NOS 10 8
ii) PER REDUCER (50% LHS/RHS) 2 MM THICK 600-150W NOS 10 8
ANNEXURE 4A: MAIN ITEMS
PRICES
Item.No Item Unit Order Quantity Lot-I Quantity
1x 500 MW FGUTPP STAGE IV
BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)
iii) PER REDUCER (50% LHS/RHS) 2 MM THICK 300-150W NOS 10 8
3.13 TROUGHS
i) 50 MM WIDE MTR 1000 700
ii) 75 MM WIDE MTR 1000 700
3.14
HOT DIP GALVANISED CABLE TRAY COVER COMPLETE WITH FORMED CHANNEL, PIPE, GI FLAT, BOLTS WITH NUTS & WASHERS & FIXING HARDWARES ETC. (1.6mm)THICK GALVANISED MS SHEET)
i) COVER 1.6MM THK- NON PERFORATED GALV MS 150W MTR 100 5
ii) COVER 1.6MM THK- NON PERFORATED GALV MS 300W MTR 100 5
iii) COVER 1.6MM THK- NON PERFORATED GALV MS 600W MTR 100 5
4.1SINGLE CHANNEL SC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 10000 7000
4.2DOUBLE CHANNEL DC1 (IN STANDARD LENGTH OF 6M PER PIECE) MTR 16000 11200
5.0 CABLE LAYING
5.1 11/11 Kv UNARMOURED CABLES
i) 3C – 150 Sq. mm MTR 4500 3500
ii) 1C – 300 Sq. mm MTR 13000 10000
iii) 1C – 630 Sq. mm MTR 3000 2000
5.2 3.3/3.3 kV UNARMOURED CABLES
i) 3C –150 Sq. mm MTR 33000 23000
ii) 1C –185 Sq. mm MTR 3000 2500
iii) 1C –630 Sq. mm MTR 5000 4000
5.3 3.3/3.3 kV ARMOURED CABLES
i) 3C –150 Sq. mm MTR 500 500
5.4 1.1 KV UNARMOURED ALUMINIUM PVC FRLS POWER CABLES
i) 2C‐10 Sq. mm MTR 7000 5000
ii) 2C‐25 Sq. mm MTR 10000 7000
iii) 2C‐95 Sq. mm MTR 8000 6000
(iv) 3C‐10 Sq. mm MTR 19000 14000
(v) 3C‐25 Sq. mm MTR 18000 13000
(vi) 3C‐50 Sq. mm MTR 14000 10000
(vii) 3C‐95 Sq. mm MTR 8000 6000
(viii) 3.5C‐25 Sq. mm MTR 7000 5000
(ix) 3.5C‐50 Sq. mm MTR 29000 20500
(x) 3.5C‐95 Sq. mm MTR 4000 3000
(xi) 4C‐10 Sq. mm MTR 2000 1000
(xii) 1C‐35 Sq. mm MTR 3000 2000
(xiii) 1C‐120 Sq. mm MTR 8000 6000
5.5 1.1 KV UNARMOURED ALUMINIUM XPLE FRLS POWER CABLES
i) 01C X 400 Sq. mm MTR 21500 15000
ii) 01C X 630 Sq. mm MTR 16500 12000
iii) 03C X 150 Sq. mm MTR 4500 3500
(iv) 03C X 240 Sq. mm MTR 15000 11000
(v) 3.5C X 185 Sq. mm MTR 4000 3000
5.6 1.1 KV ARMOURED ALUMINIUM PVC FRLS POWER CABLES
i) 3.5C‐25 Sq. mm MTR 4000 3000
ii) 3.5C‐50 Sq. mm MTR 2500 2000
5.7 1.1 KV ARMOURED COPPER PVC FRLS POWER CABLES
i) 3C‐2.5 Sq. mm MTR 20000 14000
5.8 1.1 KV UNARMOURED COPPER PVC FRLS POWER CABLES
i) 2C‐2.5 Sq. mm MTR 16000 11000
ii) 3C‐2.5 Sq. mm MTR 137000 96000
iii) 2C‐6 Sq. mm MTR 19000 14000
5.9 1.1 KV UNARMOURED COPPER PVC FRLS CONTROL CABLES
i) 3C X 1.5 Sq. mm MTR 48000 34000
ii) 5C X 1.5 Sq. mm MTR 3000 2000
iii) 5C X 2.5 Sq. mm MTR 21000 15000
(iv) 7C X 1.5 Sq. mm MTR 25000 18000
(v) 12C X 1.5 Sq. mm MTR 3000 2000
(vi) 12C X 2.5 Sq. mm MTR 4000 3000
(vii) 19C X 1.5 Sq. mm MTR 1000 1000
5.10225 V INDIVIDUAL & OVERALL SCREENED UNARMOURED SCREENED CONTROL CABLE
i) 4P, 0.5 MTR 103000 72000
ii) 8P, 0.5 MTR 31000 22000
(iii) 12P,0.5 MTR 12500 9000
(iv) 24P, 0.5 MTR 10000 7000
5.11225 V OVERALL SCREENED UNARMOURED SCREENED CONTROL CABLE
i) 4P,0.5 MTR 206000 144000
ii) 8P, 0.5 MTR 30000 21000
(iii) 12P,0.5 MTR 31000 21000
1x 500 MW FGUTPP STAGE IV
BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)
6.0 HT POWER CABLE TERMINATION FOR
6.1 11 KV UNARMOURED HT. XLPE POWER CABLE
i) 1C-630 sq mm Nos. 25 18
ii) 1C-300 sq mm Nos. 75 54
iii) 3C-150 sq mm Nos. 40 28
6.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE
i) 1C-630 sq mm Nos. 190 136
ii) 1C-185 sq mm Nos. 65 46
iii) 3C-150 sq mm Nos. 200 144
6.3 3.3 KV ARMOURED HT.XLPE POWER CABLE
i) 3C-150 sq mm Nos. 6 4
7.0 LT POWER CABLE TERMINATION FOR
7.1 1.1 KV UNARMOURED ALUMINIUM PVC FRLS POWER CABLES
i) 2C‐10 Sq. mm Nos 250 175
ii) 2C‐25 Sq. mm Nos 120 84
iii) 2C‐95 Sq. mm Nos 40 28
(iv) 3C‐10 Sq. mm Nos 800 560
(v) 3C‐25 Sq. mm Nos 600 420
(vi) 3C‐50 Sq. mm Nos 150 105
(vii) 3C‐95 Sq. mm Nos 140 98
(viii) 3.5C‐25 Sq. mm Nos 400 280
(ix) 3.5C‐50 Sq. mm Nos 70 49
(x) 3.5C‐95 Sq. mm Nos 90 63
(xi) 4C‐10 Sq. mm Nos 100 70
(xii) 1C‐35 Sq. mm Nos 100 70
(xiii) 1C‐120 Sq. mm Nos 100 70
7.2 1.1 KV UNARMOURED ALUMINIUM XPLE FRLS POWER CABLES
i) 01C X 400 Sq. mm Nos 800 560
ii) 01C X 630 Sq. mm Nos 1000 700
iii) 03C X 150 Sq. mm Nos 80 56
(iv) 03C X 240 Sq. mm Nos 25 18
(v) 3.5C X 185 Sq. mm Nos 60 42
7.3 1.1 KV ARMOURED ALUMINIUM PVC FRLS POWER CABLES
i) 3.5C‐25 Sq. mm Nos 80 56
ii) 3.5C‐50 Sq. mm Nos 50 35
7.4 1.1 KV ARMOURED COPPER PVC FRLS POWER CABLES
i) 3C‐2.5 Sq. mm Nos 200 140
7.5 1.1 KV UNARMOURED COPPER PVC FRLS POWER CABLES
i) 2C‐2.5 Sq. mm Nos 2000 1400
ii) 3C‐2.5 Sq. mm Nos 4500 3100
iii) 2C‐6 Sq. mm Nos 200 140
8.0 CONTROL CABLE TERMINATION FOR
8.1 1.1 KV UNARMOURED COPPER PVC FRLS CONTROL CABLES
i) 3C X 1.5 Sq. mm Nos 1000 700
ii) 5C X 1.5 Sq. mm Nos 100 70
iii) 5C X 2.5 Sq. mm Nos 500 350
(iv) 7C X 1.5 Sq. mm Nos 500 350
(v) 12C X 1.5 Sq. mm Nos 200 140
(vi) 12C X 2.5 Sq. mm Nos 300 210
(vii) 19C X 1.5 Sq. mm Nos 100 70
9.0 225V SCREENED CABLE TERMINATION (INCLUDING SUPPLY OF LUGS)
i) 4P, 0.5 Nos. 1800 1260
ii) 8P, 0.5 Nos. 350 245
iii) 12P,0.5 Nos. 220 150
iv) 24P, 0.5 Nos. 100 70
10.0 225V SCREENED CABLE TERMINATION (EXCLUDING SUPPLY OF LUGS)
i) 4P, 0.5 Nos. 7200 5040
ii) 8P, 0.5 Nos. 1400 980
iii) 12P,0.5 Nos. 880 620
iv) 24P, 0.5 Nos. 400 280
11.0 CABLE JOINTS
11.1 11 KV UNARMOURED HT. XLPE POWER CABLE
i) 1C-300 sq mm Nos. 34 24
11.2 3.3 KV UNARMOURED HT.XLPE POWER CABLE
i) 3C-150 sq mm Nos. 50 34
11.3 1.1 KV UNARMOURED LT.XLPE POWER CABLE
i) 3C-240 sq mm Nos. 2 1
ii) 3C-150 sq mm Nos. 3 2
12.0 RIGID GALVANISED MS CONDUITS / PIPES
i) 100 mm diameter Metres 1000 700
ii) 75 mm diameter Metres 1000 700
iii) 50 mm diameter Metres 2000 1400
(iv) 25 mm diameter Metres 1000 700
(v) 20 mm diameter Metres 1000 700
13.0FLEXIBLE CONDUITS MADE OF COLD ROLLED ANNEALED ELECTRO
GALVANISED MS STRIP
i) 25 mm diameter Metres 2000 1400
(ii) 18 mm diameter Metres 1000 700
1x 500 MW FGUTPP STAGE IV
BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)
14.0 PVC Conduitsi) 250 mm diameter Metres 100 70ii) 200 mm diameter Metres 100 70iii) 100 mm diameter Metres 100 70(iv) 50 mm diameter Metres 100 70
15.0ABOVE GROUND EARTHING AND LIGHTNING PROTECTION
MATERIAL
15.1INSTALLATION OF VERTICAL AIR TERMINATION (20 MM DIA GALVANISED MS
ROD 1000 MM LONG)Nos. 100 70
15.2 EARTH CONTINUITY CONNECTION CONDUCTOR
i) GALVANISED MS FLAT 65 X 8 Metres 8000 5600
ii) GALVANISED MS FLAT 50 X 6 Metres 600 420
iii) GALVANISED MS FLAT 25 X 6 Metres 2200 1540
(iv) G S WIRE 8 SWG Metres 5000 3500
15.3 RUNWAY CONDUCTOR
i) 65X8 GALVANISED MS FLAT Metres 13000 9100
15.4INSTALLATION OF HORIZONTAL AIR TERMINATION ON WEATHER PROOFED
SURFACES GALVANISED MS STRIP
i) 25 X 6 mm Metres 5000 3500
15.5INSTALLATION OF HORIZONTAL AIR TERMINATION ON OTHER SURFACES
GALVANISED MS STRIP
i) 25 X 6 mm Metres 500 350
15.6INSTALLATION OF DOWN CONDUCTOR
( 25 X 6 MM GALVANISED MS STRIP)
i) 25 X 6 mm Metres 3500 2450
16.0 JUNCTION BOX (i) 6 WAY Nos. 10 7(ii) 12 WAY Nos. 25 17(iii) 24 WAY Nos. 20 14(iv) 36 WAY Nos. 10 7(v) 48 WAY Nos. 10 7
Item.No Item Description Unit Order Quantity
Unit Erection & Commissio
ning Charges in
INR
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection & Commissio
ning Charges
INR
Service tax @ including cess on E & C in INR
Total E & C prices
including Service Tax
in INR
1 Earthwork in excavation & back filling CU. M 1
2 Supply & filling of sand CU. M 1
3 Supply and installation of protective concrete covering CU. M 1
4 Minor civil works
(i) Making opening in brick wall CU. M 1
(ii) Making opening in concrete floor / wall CU. M 1
(iii) Making opening in concrete through core drilling CU. M1
(iv)Making (Constricting into smaller openings already existing large openings) in brickwork CU. M 1
(v)Making (Constricting into smaller openings already existing large openings) in Concrete CU. M 1
(vi) Supply and spreading of bricks CU. M 1
5 Installation of earth electrode driven into earth Nos.1
6 Installation of test pit Nos. 17 Installation of risers Nos. 1
8 Iinstallation of submat in floor Metres 19 Steel fabrication Sq. m 1
1 X 500 MW FGUTPP STAGE IV
BILL OF MATERIAL FOR CABLING, EARTHING AND LIGHTNING PROTECTION SYSTEMS (INSTALLATION)
ANNEXURE 4B-SCHEDULE OF UNIT PRICES
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
5. FIRE SEALING SYSTEM
SL.NO. DESCRIPTION UNIT ORDER QTY. LOT 1 QTY Unit Ex-works price/Unit
Price
Total Ex-Works Price
duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufacture
d only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including
cess on E & C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C in
INR
MAIN ITEMS (IN RUPEES) (IN RUPEES)1 FSS-TYPE A FLOOR OPENINGS
BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)
SQM
170 120
2 FSS-TYPE B FLOOR OPENINGS BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)
SQM
620 440
3 FSS-TYPE B FLOOR OPENINGS (FLOOR THICKNESS 190 MM APPROX)
SQM120 90
4 FSS-TYPE B WALL OPENINGS (WALL THICKNESS 250 MM APPROX) SQM
100 70
5 FSS TYPE-B PIPE SLEEVES (250 NB)NOS
350 245
6TOOLS AND ACCESSORIES REQUIRED FOR ADDITION OR REMOVAL OF CABLES AFTER THE SEAL IS MADE. THIS SHALL INCLUDE SPECIAL TOOLS, COMPOUND INJECTION GUNS, SPRAY GUNS, ETC. (As applicable)
SET
1 1
Notes:-
1)
2)
3)
4)
5)
FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)
ANNEXURE -5A
BILL OF QUANTITIES/ PRICE SCHEDULE FOR SUPPLY OF FIRE SEALING SYSTEM
Successful bidder is responsible for estimation of additional quantities based on site conditions and work progress. The estimates shall be used by NBPPL as inputs for clearing further quantities. These activities shall be completed within the overall contractual period.
Unit prices for supply shall be quoted in line with clause no. 8.3, Section D of Part B of specification.
LOT 1 Quantity shall be released along with LOI, which is approximately 70% of the ordered Quantity/Contract value.
The fire sealing area indicated under Column “Ordered Quantity” above shall be considered for ordering purposes. Bidder shall indicate the quantity of material required to be supplied per square metre, which shall be used for billing purposes of the supply portion after review and acceptance. However, the vendor shall supply the actual material necessary for meeting the specified area requirements as per type-tested arrangement without any commercial implication.
LOT 1 quantities shall be cleared for supply along with the LOI/ PO. However, supplies of quantities shall be made only after approval of drawings, datasheets, quality documentation and successful completion of type testing (if required).
s. no. DESCRIPTION UNIT ORDER QTY. LOT 1 QTY Unit Erection &
Commissioning Charges
in INR
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufac
tured only
Freight including Service tax @
Total FOR Site
Price (Supply) in INR
Total Erection
& Commiss
ioning Charges
INR
Service tax @
including cess on E & C in
INR
Total E & C prices
including Service Tax in INR
MAIN ITEMS1 FSS-TYPE A FLOOR OPENINGS
BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)
SQM
170 120
2 FSS-TYPE B FLOOR OPENINGS BELOW PANELS (FLOOR THICKNESS 190 MM APPROX)
SQM
620 440
3 FSS-TYPE B FLOOR OPENINGS (FLOOR THICKNESS 190 MM APPROX)
SQM120 90
4 FSS-TYPE B WALL OPENINGS (WALL THICKNESS 250 MM APPROX)
SQM100 70
5 FSS TYPE-B PIPE SLEEVES (250 NB) NOS
350 245
Notes‐
1
3
3
FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)
ANNEXURE- 5A
BILL OF QUANTITIES/ PRICE SCHEDULE FOR INSTALLATION OF FIRE SEALING SYSTEM
Unit prices for installation shall be quoted in line with clause no. 8.3, Section D of Part B of specification.
Successful bidder is responsible for estimation of additional quantities based on site conditions and work progress.
The estimates shall be used by NBPPL as inputs for clearing further quantities. These activities shall be completed
within the overall contractual period.
LOT 1 Quantity shall be released along with LOI, which is approximately 70% of the ordered Quantity/Contract
value.
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
6. HT XLPE CABLES
Unit Ex-works
price/Unit Price
Total Ex-Works
Price duly packed in INR/Total
Price.
Excise Duty @ on
self manufactu
red only
VAT/CST @ … in
INR on self manufactu
red only
Freight including Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissi
oning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply
and E&C in INR
1.1 3C – 150Sq. mm
4500 Meters
3500 Meters
500 Meters
1.2 1C – 300Sq. mm
13000 Meters
10000 Meters
500 Meters
1.3 1C – 630Sq. mm
3000 Meters
2000 Meters
500 Meters
Unit Ex-works
price/Unit Price
Total Ex-Works
Price duly packed in INR/Total
Price.
Excise Duty @ on
self manufactu
red only
VAT/CST @ … in
INR on self manufactu
red only
Freight including Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissi
oning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply
and E&C in INR
2.1 3C –150Sq. mm
33000 Meters
23000 Meters
500 Meters
2.2 1C –185Sq. mm
3000 Meters
2500 Meters
500 Meters
2.3 1C –630Sq. mm
5000 Meters
4000 Meters
500 Meters
Unit Ex-works
price/Unit Price
Total Ex-Works
Price duly packed in INR/Total
Price.
Excise Duty @ on
self manufactu
red only
VAT/CST @ … in
INR on self manufactu
red only
Freight including Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissi
oning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply
and E&C in INR
3.1 3C –150Sq. mm
500Meters
500 Meters
500 Meters
Notes:
11/11 kV unarmoured cables
3.3/3.3 kV unarmoured cables
3.3/3.3 kV armoured cables
Sl. No. Cable Sizes
Total Quantity
Sl. No. Cable Sizes
Total Quantity
LOT-1 Quantity
Drum Length
Supply
1. Total Quantities indicated above shall be known as Order Quantities.
2. The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.
LOT-1 Quantity
Drum Length
Supply
Sl. No. Cable Sizes
Total Quantity
LOT-1 Quantity
Drum Length
Supply
3. Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be
4. The standard drum length for power cables shall not be less than 500 meters. The length per drum shall be subjected to a maximum tolerance of +/- 5% of the standard drum length. Customer shall have the option of rejecting cable drum with shorter lengths.
5. Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0% Cables consumed for testing and inspection shall be to bidder’s account.
6. For each individual cable size, one short length of not less than 200m may be accepted only in the final drum length to complete the supply (except where the total ordered quantity is one single drum length of 500m). The overall tolerance limits stipulated above shall continue to apply (in case short lengths are accepted).
7. Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.
Bill of Quantities(Main Items) Annexure 6
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
7A. 1.1 kV XLPE POWER AND PVC POWER CABLES
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
DRUM LENGTH
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
500 METER500 METER
DRUM LENGTH
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
1000 METER
1100 V grade, power cables with stranded compacted plain Aluminium conductor (H2 grade, class 2) , XLPE insulated, PVC type ST2 extruded inner sheathed (no inner sheath for single core cables) and extruded PVC Type ST2 outer sheath with FRLS properties, generally conforming to IS:7098 (Part-1) and NBPPL specification.
1100 V grade power cables with stranded aluminium conductor, PVC Type-A insulation, core identification by colour coding, distinct extruded inner sheath of PVC Type ST2 material (for multi-core cables only) and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1).
1100 V grade power cables with tinned copper conductor, PVC Type-A insulation, core identification by colour coding, distinct extruded inner sheath of PVC Type ST2 material, aluminium wire armour for single core cables and GS round wire/ formed wire armour (Type-'b') for multicore cables, and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1). Colour of the outersheath shall be YELLOW.
(A): UNARMOURED ALUMINIUM PVC FRLS POWER CABLES
S. NO.
SIZE (IN SQ.MM.) QUANTITY (km.)
LOT-1 QTY (km.) DRUM LENGTH
1 2C-10 7 5 500 METER2 2C-25 10 7 500 METER3 2C-95 8 6 500 METER4 3C-10 19 14 500 METER5 3C-25 18 13 500 METER6 3C-50 14 10 500 METER7 3C-95 8 6 500 METER8 3.5C-25 7 5 500 METER9 3.5C-50 29 20.5 500 METER
10 3.5C-95 4 3 500 METER11 4C-10 2 1 500 METER12 1C-35 3 2 500 METER13 1C-120 8 6 500 METER
S. NO.
SIZE (IN SQ.MM.) QUANTITY (km.)
(B): UNARMOURED ALUMINIUM XPLE FRLS POWER CABLES
LOT-1 QTY (km.) DRUM LENGTH
1 01C X 400 21.5 15 500 METER2 01C X 630 16.5 12 500 METER
5 3.5C X 185 4 3 500 METER(C): ARMOURED ALUMINIUM PVC FRLS POWER CABLES
3 03C X 150 4.5 3.5 500 METER4 03C X 240 15 11 500 METER
SIZE (IN SQ.MM.) QUANTITY (km.) LOT-1 QTY (km.)1 3.5C-25 4 3
S. NO.
1100 V grade power cables with stranded aluminium conductor, PVC Type-A insulation, core identification by colour coding, distinct extruded inner sheath of PVC Type ST2 material, aluminium wire armour for single core cables and GS round wire/ formed wire armour (Type-'b') for multicore cables, and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1).
(D): ARMOURED COPPER PVC FRLS POWER CABLES
S. NO. SIZE (IN SQ.MM.) QUANTITY (km.) LOT-1 QTY (km.)
2 3.5C-50 2.5 2
1 3C-2.5 20 14
ANNEXURE 7AA
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
5. For each individual cable size, one short length of not less than 200m may be accepted only in the final drum length to complete the supply (except where the total ordered quantity is one single drum length of 500m). The overall tolerance limits stipulated above shall continue to apply (in case short lengths are accepted).
6. Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.
7. The standard drum length shall be 500 meters for Aluminium Cables and 1000m for Copper Cables. Tolerance on individual drum length shall be ±5%.
1. Quantities indicated above shall be known as Order Quantities.
2. The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Unit Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.
3. Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be given for completion of supply for each subsequent lot from the date of clearance of the quantities.
4. Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0%. Cables consumed for testing and inspection shall be to bidder’s account.
1100 V grade power cables with stranded tinned copper conductor, PVC Type-A insulation, core identification by colour coding , distinct extruded inner sheath of PVC Type ST2 material (for multicore cables only) and extruded PVC type ST2 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1).
(E): UNARMOURED COPPER PVC FRLS POWER CABLES
S. NO.
SIZE (IN SQ.MM.) QUANTITY (km.)
LOT-1 QTY (km.) DRUM LENGTH
1000 METER
NOTES :
1 2C-2.5 16 11 1000 METER2 3C-2.5 137 96 1000 METER3 2C-6 19 14
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
7B. 1.1 kV PVC CONTROL CABLES
S. NO. QUANTITY (km.)
LOT-1 QTY (km.) DRUM LENGTH Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
Total Supply and E&C in INR
1 48 34 1000 METER2 3 2 1000 METER3 21 15 1000 METER4 25 18 1000 METER5 3 2 1000 METER6 4 3 1000 METER7 1 1 1000 METER
(A): UNARMOURED COPPER PVC FRLS CONTROL CABLES
'Control cables are of 1100 V earthed grade with stranded plain annealed copper conductor, PVC Type-A insulation, core identification by colour coding (upto five cores)/ number marking (more than five cores), distinct extruded inner sheath of PVC Type ST1 material, GS formed wire armour as per IS: 3975 (armour provided for directly buried cables only) and extruded PVC type ST1 outer sheath with FRLS properties, generally conforming to IS:1554 (Part-1). Maximum conductor temperature for normal operation is 70 deg. C and for short circuit conditions, 160 deg. C. The minimum conductor cross section is 1.5 sq. mm.
12C X 2.519C X 1.5
SIZE (IN SQ.MM.)
3C X 1.55C X 1.5
7C X 1.512C X 1.5
5C X 2.5
ANNEXURE 7AB
1. Quantities indicated above shall be known as Order Quantities. 2. The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Unit Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.
3. Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be given for completion of supply for each subsequent lot from the date of clearance of the quantities.
4. Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0%. Cables consumed for testing and inspection shall be to bidder’s account.
5. For each individual cable size, one short length of not less than 200m may be accepted only in the final drum length to complete the supply (except where the total ordered quantity is one single drum length of 500m). The overall tolerance limits stipulated above shall continue to apply (in case short lengths are accepted). 6. Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.7. The standard drum length shall be 1000m for Copper Cables. Tolerance on individual drum length shall be ±5%.
NOTES :
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
8. SCREENED CONTROLCABLES
(A):
S.No. SIZE IN SQ. MM Order Quantity (Km) LOT 1 Quantity (Km)Drum Length (Meters)
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on
self manufactur
ed only
VAT/CST @ … in
INR on self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection & Commissio
ning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and E&C in
INR
1 4P, 0.5 103 722 8P,0.5 31 223 12P, 0.5 12.5 94 24P,0.5 10 7
(B):
Total Ex- Excise VAT/CST Total Service tax Total E & C
SCREENED CONTROL CABLE ANNEXURE-8A: BOQ/ PRICE SCHEDULE
500
TYPE 'G', 0.5 SQ. MM. CABLES: Multi pair (twisted) overall shielded instrumentation cables.
225 volt peak, multi-pair (twisted) instrumentation cables, 0.5 sq. mm. high conductivity, electrolytic, Annealed bare, multi stranded copper conductor as per VDE 0815, extruded PVC (compound YI3) insulation as per VDE 0207 Part-4, core & pair identification by suitable colour coding & band marking as per VDE 0815, stranded tin coated copper conductor drain wire, overall shielded with aluminium mylar tape, extruded PVC (compound YM1) outer sheath (sky blue) as per VDE 0207 Part-5 and VDE 0816 with FRLS properties.
225 volt peak, multi-pair (twisted) instrumentation cables, 0.5 sq. mm. high conductivity, electrolytic, Annealed bare, multi stranded copper conductor as per VDE 0815, extruded PVC (compound YI3) insulation as per VDE 0207 Part-4, core & pair identification by suitable colour coding & band marking as per VDE 0815, individual pair and overall shielded with aluminium mylar tape, stranded tin coated copper conductor drain wire provided separately for both individual pair & overall shielding, extruded PVC (compound YM1) outer sheath (sky blue) as per VDE 0207 Part-5 and VDE 0816 with FRLS properties.
100010001000
TYPE 'F' , 0.5 SQ. MM.CABLES: Multi pair (twisted) individual & overall shielded instrumentation cables.
S.No. SIZE IN SQ. MM Order Quantity (Km) LOT 1 Quantity (Km)
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on
self manufactur
ed only
VAT/CST @ … in
INR on self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection & Commissio
ning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C Rs
1 4P, 0.5 206 144. 2 8P, 0.5 30 21
3 12P, 0.5 31 21
NOTES:
1
2
3
4
5
6
7
100010001000
Drum Length (Meters)
Overall tolerance on total dispatched quantity of each size shall be (-) 2% and (+) 0%. Cables consumed for testing and inspection shall be to bidder ’s account
The tolerance of drum length shall be + 5%. Short lengths of individual cable size not less than 300m may be accepted only in the final drum length to complete the supply within the overall variation limits stipulated above.
Lot-I quantities indicated above (in case the cable quantities are to be released for manufacture in more than one lot), or Order Quantity (in case the quantities are cleared for manufacture in one lot only) shall be cleared for manufacturing along with LOI. However, manufacturing of the cables shall be taken up by the successful bidder only after approval of technical and quality documentation and shall be completed within four months from the date of approval of documentation. Subsequent lots shall be cleared for manufacture based on progress of engineering and site requirements. A lead-time of three months shall be given for completion of supply for each subsequent lot from the date of clearance of the quantities.
Quantities indicated above shall be known as Order Quantities.
The bidder shall indicate the unit price of each type and size of cables listed as per the BOQ in the Unit Price Schedule enclosed with this specification. The unit prices shall apply for adjustment of variation in quantity as stipulated above.
In case the quantities of any one lot cleared by NBPPL for manufacturing are manufactured and offered for inspection by successful bidder in more than one batch, NBPPL reserves the right to witness type testing on all batches.
Bidder shall indicate unit price of cables inclusive of type test charges. No separate charges shall be payable for type tests.
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
9. 220 V DC BATTERY
Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on
self manufactur
ed only
VAT/CST @ … in INR
on self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection & Commissio
ning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply and
E&C in INR
(A) MAIN ITEMS
1.0
NI-CD POCKET PLATE 220V BATTERY (169 CELLS,220V Ni-Cd, HIGH discharge battery 1.14 ECVsuitable as per Load Duty Cycle( Annexure-III) with all accessories & MS racks with 3 coats of anti acidpaints.(For each battery))
Sets 2
Break up detail
220V , Ni-Cd battery suitable as per Load Duty Cycle(Annexure-III) ( 1 set comprises 170 nos. cell) Sets 2
MS racks with 3 coats of anti acid paints for 220V DCBattery Sets 2
Intercell connectors Sets 2
Electrolyte (sulphuric acid for first filling plus10%extra ) Sets 2
1.1LIST OF ACCESSORIES (for each set of battery)
a Hydrometer Nos 2
bSet of hydrometer syringes (suitable for the ventholes in different cells) Nos 2
cThermometer with specific gravity correction scale(for measuring electrolyte temperature) Nos 5
d Specific gravity correction chart Nos 2
e Wall mounting type holder made of teak wood for hydrometer and thermometer
Nos 2
f Cell testing digital voltmeter (3-0-3V) with testing leads
Nos 2
g Acid/alkali mixing jar Nos 2
h Rubber apron Nos 2
i Pair of rubber hand gloves Nos 2
j Set of spanners Nos 2
k `No smoking’ notice Nos 2
l Goggles (industrial) Nos 2
m Instruction card Nos 10
n Minimum and maximum temperature indicator forBattery Room
Nos 1
o Interconnector bolt wrenches Nos 1
p Stand insulators lot 1
q Battery log book Nos 1
r Funnel Nos 2
s Multimeter Nos 2
t Cell interconnectors with 5% extra and end take-off with one no. extra
lot 1
u Lead coated connection hardware plus 5% extra lot 1
v Teakwood Cable clamps with hardware lot 1
2.0 E & C SPARES
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-1)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (NI-CD Battery)
Page 1 of 2
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-1)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (NI-CD Battery)
a INTER CELL CONNECTOR NOS 2
b GLOVES SET 2
c VENT PLUGS NOS 2
3.0 MANDATORY SPARES
COMPLETELY ASSEMBLED CELL (DRY)NOS.
2% or 2 Nos. whichever is more
Intercell connectors with hardwareNOS./%
10% or 5 nos. whichever ismore of total population of2 sets of battery
Vent plugNOS./%
10% or 5 nos. whichever ismore of total population of2 sets of battery
Acid level indicating float (for opaque containers only)NOS./%
10% or 5 nos. whichever ismore of total population of2 sets of battery
Stand insulatorNOS./%
10% or 5 nos. whichever ismore of total population of2 sets of battery
Cell insulatorNOS./%
10% or 5 nos. whichever ismore of total population of2 sets of battery
Note: A)Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering. B) Bidder can quote for either Option-1 or Option-2
Page 2 of 2
Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR (6+7+8+9)
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax (11+12) in INR
Total Supply and E&C in INR
(A) MAIN ITEMS
1.0
LEAD -ACID BATTERY PLANTE, 220V BATTERY (107CELLS, 220V LEAD ACID, 1.85 ECV suitable as perLoad Duty Cycle(Annexure-III ) with all accessories& Teakwood racks with 3 coats of anti acidpaints.(For each battery set)
Sets 2
Break up detail 2
220V , Lead acid plante battery suitable as perAnnexure-III (Load duty cycle) (1 set comprises 107nos cell)
Sets 2
Teakwood racks with 3 coats of anti acid paints for220V DC Battery Sets 2
Intercell connectors Sets 2
Electrolyte (sulphuric acid for first filling plus10%extra ) Sets 2
1.1LIST OF ACCESSORIES (for each set ofbattery)
a Hydrometer Nos 2
bSet of hydrometer syringes (suitable for the ventholes in different cells) Nos 2
cThermometer with specific gravity correction scale(for measuring electrolyte temperature) Nos 5
d Specific gravity correction chart Nos 2
e Wall mounting type holder made of teak wood for hydrometer and thermometer
Nos 2
f Cell testing digital voltmeter (3-0-3V) with testing leads
Nos 2
g Acid/alkali mixing jar Nos 2
h Rubber apron Nos 2
i Pair of rubber hand gloves Nos 2
j Set of spanners Nos 2
k `No smoking’ notice Nos 2
l Goggles (industrial) Nos 2
m Instruction card Nos 10
n Minimum and maximum temperature indicator forBattery Room
Nos 1
o Interconnector bolt wrenches Nos 1
p Stand insulators lot 1
q Battery log book Nos 1
r Funnel Nos 2
s Multimeter Nos 2
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-2)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (LEAD -ACID PLANTE)
Page 1 of 2
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9B (OPTION-2)BOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (LEAD -ACID PLANTE)
t Cell interconnectors with 5% extra and end take-off with one no. extra
lot 1
u Lead coated connection hardware plus 5% extra lot 1
v Teakwood Cable clamps with hardware lot 1
2.0 E & C SPARES
a INTER CELL CONNECTOR NOS 2
b GLOVES SET 2
c VENT PLUGS NOS 2
3.0 MANDATORY SPARES
COMPLETELY ASSEMBLED CELL (DRY)NOS.
2% or 2 Nos. whichever is
Intercell connectors with hardwareNOS./%
10% or 5 nos.whichever is
f lVent plugNOS./%
10% or 5 nos.whichever ismore of total
Acid level indicating float (for opaque containers only) NOS./%
10% or 5 nos.whichever ismore of total
Stand insulatorNOS./%
10% or 5 nos.whichever ismore of total
Cell insulatorNOS./%
10% or 5 nos.whichever ismore of total
Note: A)Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering. B) Bidder can quote for either Option-1 or Option-2
Page 2 of 2
Sr. No. Item Description Unit QuantityUnit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service Tax
in INR
Total Supply and E&C in INR
1
LEAD -ACID BATTERYPLANTE, 220V BATTERY(107 CELLS, 220V LEADACID, 1.81 ECV suitable asper Load Duty Cycle(pl referPART-B of technicalspecification ) with allaccessories & Teakwoodracks with 3 coats of anti acidpaints.(For each battery set)
Sets 2
Break up detail 2220V , Lead acid plantebattery suitable as per Loadduty cycle. (1 set comprises107 nos cell)
Sets 2
Teakwood racks with 3 coatsof anti acid paints for 220VDC Battery
Sets 2
Intercell connectors Sets 2Electrolyte (sulphuric acid forfirst filling plus10% extra ) Sets 2
Annexure‐9AUNPRICED PRICE SCHEDULE E & C FOR 220V DC BATTERY (Lead-Acid Plante Battery) (OPTION-2)
Note: Bidder can quote for either Option-1 or Option-2
Sr. No. Item Description Unit QuantityUnit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service Tax
in INR
Total Supply and E&C in INR
1
NI-CD POCKET PLATE 220VBATTERY (169 CELLS, 220VNi-Cd, HIGH discharge battery1.14 ECV suitable as per LoadDuty Cycle(pl refer PART-B oftechnical specification) with allaccessories & MS racks with3 coats of anti acid paints.(Foreach battery))
Sets 2Break up detail220V , Ni-Cd battery suitableas per Load Duty Cycle ( 1 setcomprises 170 nos. cell)
Sets 2MS racks with 3 coats of antiacid paints for 220V DCBattery Sets 2Intercell connectors Sets 2Electrolyte (sulphuric acid forfirst filling plus10% extra )
Sets 2
UNPRICED PRICE SCHEDULE E & C FOR 220V DC BATTERY (Ni-Cd Battery) (OPTION-1)
Note: Bidder can quote for either Option-1 or Option-2
Annexure‐9A
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
10. 220 V DC BATTERY CHARGER
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE 9C
Sr. No. Item Description Unit QuantityRemarks
Unit Ex-works price/Unit PriceTotal Ex-Works Price
duly packed in INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
Total Supply and E&C in
INR
1 FLOAT-CUM-BOOST CHARGER1 NOS 2 400A, 220V DC Float-cumboost
2 BATTERY FUSE BOX NOS 2Battery fuse suitable as per Load Duty Cycle (Annexure-VI)
3 DISCHARGE RESISTOR NOS 1 Variable mettalic resistor and shunt for 220V DC, 920AH Ni-Cd battery for 5 hr. discharge rate/ 1500AH Lead acid plante battery for 10 hr. discharge rate
4 E & C SPARES LOT 14.1 FUSE LINK WITHOUT HOLDERa AC I/P HRC FUSE LINK NOS 2b GLASS FUSE NOS 2c CONTROL HRC FUSE LINK NOS 2d RECTIFIER FUSE LINK NOS 2e FILTER CAPACITOR FUSE LINK NOS 2f DC O/P FUSE LINK NOS 2
4.2 INDICATING LAMPAC I/P LAMP RED COLOR NOS 2AC I/P LAMP YELLOW COLOR NOS 2AC I/P LAMP BLUE COLOR NOS 2DC O/P LAMP NOS 2
5 MANDATORY SPARES LOT 1
5.1ELECTRONIC CARDS (ALLCOMPONENTS MOUNTED)
5.1.1
Set of Cards and modules (Each type and rating: CPC Card, HV PFPSR card, Rectifier FFD card, DC under/over voltage relay card, ACOR card, DC output fuse FFD card, Earth leakage card,etc.)
SET 1
5.1.2
Set of Auxiliary relays (Each type and rating: Auxiliary relays, 6 amp/ 110 V DC coil and 6 amp/240 V AC coil)
SET 1
5.1.3
Set of fuse links and glass fuses(Each type and rating:AC input fuse links, 315 Amp,Rectifier fuse link, GS1000/400 Amp,Filter condenser fuse link, 160 Amp,DC output HRC fuse link, 500 Amp,Control HRC fuses links, 2 &
SETS 3
5.1.4Set of SCR and Diode (One of each type and rating)
SETS 3
5.1.5 Rectifier transformerNos. 1 No. of each type
& rating
5.1.6 Control transformersNos. 1 No. of each type
& rating
BOQ CUM UNPRICED PRICE SCHEDULE FOR SUPPLY OF 220V DC BATTERY CHARGER
FEROZ GANDHI UNCHAHAR TPP STAGE‐IV( 1 X 500MW) ANNEXURE 9C
Sr. No.
Item Description Unit Quantity
Unit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning Charges in INR
Service tax @ including cess on
E & C in INR
Total E & C prices including Service
Tax in INR
1400A, 220V DC Float-cum boost NOS 2
2
Battery fuse suitable as per Load Duty Cycle (for load duty cycle , pl refer PART-B of technical specification)
NOS 2
3
Variable metallic resistor and shunt for 220V DC, Ni-Cd battery for 5 hr. discharge rate/ Lead acid plante battery for 10 hr. discharge rate
NOS 1
UNPRICED PRICE SCHEDULE E & C FOR 220V DC BATTERY CHARGER
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
11. GENERATOR CIRCUIT BREAKER
SL.NO. ITEM QTY.
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service Tax
in INR
Total Supply and E&C in INR
1 Generator Circuit Breaker including all associated series isolators, earth-switches, surge capacitors
1 No
2 Start-up and Commissioning Spares(Bidder to furnish the list)
1 No
3 Special Tools and Tackles(Bidder to furnish the list)
1 Set
4 Mandatory Spares(as per Annexure-II)
1 Lot
Notes:
1. Wherever set is indicated above, it means the total parts/ accessories required to replace the particular item for given equipment.2. For item no. 4 (Mandatory spares), bidders to also indicate prices for individual type test/items as per Annexure-II.
ANNEXURE 10Supply BOM for GCB
SL. NO. DESCRIPTION QUANTITY
Unit Ex-works
price/Unit Price
Total Ex-Works Price
duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
Total Supply and E&C in
INR
1Complete pole assembly (along with internally mountedequipment) 1 Set
2 Closing coils 3 Nos.3 Tripping coil 3 Nos.4 Closing springs (if applicable) 1 No.5 Tripping springs (if applicable) 1 No.6 Gaskets 1 Set for a breaker7 Limit Switches 1 Set for a breaker8 Bus seal off bushings 1 Set for a breaker
9Upper and lower terminals with finger contact device
1 Set upper & 1 set lower
10 Arc extinction coil 2 Nos.11 SF6 cylinders 3 Nos.12 Auxiliary switches 2 Sets13 Drive assembly complete for GCB 1 Set
14In case of SF6 GCB following shall be provided: 1 Set
a Gas density switch 1 No.b Gas pressure gauge 1 No.c Gas density indicator 1 No.d Absorbent 3 Nos.
eTeflon hoses for one replacement in all the six poles of breakers 1 Set
NOTE: (1) Wherever quantity is mentioned as set bidder to quote for each type & rating.
(2) Bidder to indicate prices for individual items.
PRICE SCHEDULE FOR MANDATORY SPARESANNEXURE –II
SL.NO.
ITEM QTY. Unit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges in INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
1
Generator Circuit Breaker including all associated series isolators, earth-switches, surge capacitors
1 No
PRICE SCHEDULE(E&C )
Annexure-10
SL.NO. ITEM QTY.
Unit Supervision of E&C price
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty including cess
@ ……Rs
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR (6+7+8+9)
Total Erection & Commissioning
Charges INR
Service tax @ including cess on supervision of E & C in INR
Total E & C prices including
Service Tax (11+12) in INR
Total Supply and E&C Rs(10+13)
4 Supervision of Erection, Testing and Commissioning(Refer Note 1 & 2)
1 Set
Notes:
1. Supervision of Erection, Testing and Commissioning shall be performed by original equipment manufacturer.2. For Supervision of Erection, Testing and Commissioning, price for 4 man-days & 1 visit shall be quoted for each GCB. The price shall be all inclusive of charges for airfare, boarding/ lodging, visa, medical, insurance etc.
Price Schedule for Supervision of E&C of GCB
SL. NO. DESCRIPTION QUANTITY Unit Price in INR Total Price in INR
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning Charges INR
Service tax @ including cess
on Total Price in INR
Total Price including Service
Tax in INR
1Rated dielectric strength tests
1LOT
(i)Rated low frequency withstand voltage dry test
(ii)Rated full wave impulse withstand voltage test.
2
Short circuit rating and transient recovery voltage tests
1LOT
(i)
Test for rated symmetrical short circuit current interrupting capability, duty cycle and rated transient recovery voltage parameters
(ii)
Test for rated closing, latching and short time current carrying capability
(iii)
Test for rated Generator source asymmetrical short circuit interrupting capability.
3Load current switching test.
1LOT
4
Out of phase switching current tests.
1LOT
5
Rated excitation current switching tests.
1LOT
6
Type tests and oscillographic test records for closing and tripping timings for generator circuit breaker of the rating offered.
1LOT
NOTE: (1) Bidder to indicate type test charges separately for each test.
ANNEXURE –IPRICE SCHEDULE FOR TYPE TEST - GCB
(2) In case Bidder has already conducted such specified type test(s), he may submit during detailed engineering the type test reports to the owner for waival of conductance of such type test(s).
These reports should be for the tests conducted on the equipment similar to those proposed to be supplied under this contract and test(s) should have been either conducted at an independent
laboratory or should have been witnessed by a client. The owner reserves the right to waive conducting of any or all the specified type test(s) under this contract. In case type tests are waived,
the type test charges shall not be payable to the contractor.
(3) Further theBidder shall only submit the reports of the type tests as listed in Price Schedule and carried out within last ten years from the date of bid opening. These reports should be for the
test conducted on the equipment similar to those proposed to be supplied under this contract and the test(s) should have been either conducted at an independent laboratory or should have
been witnessed by a client. However if the contractor is not able to submit report of the type test(s) conducted within last ten years from the date of bid opening, or in the case of type test
report(s) are not found to be meeting the specification requirements, the contractor shall conduct all such tests under this contract at no additional cost to the owner either at third party lab or
in presence of client/owners representative and submit the reports for approval.
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
12. PA SYSTEM
ANNEXURE-11
Item No.
DESCRIPTION Unit
(A) MAIN EQUIPMENT MAKE MODEL NO.
Unit Ex-works
price/Unit Price
Total Ex-Works Price
duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess on E & C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C
in INR
1 Central exchange for unit & common area with integrated MDF 1 No.Microprocessor controlled, digital, programmable central control unit(CCU) with PCM/TDM technology suitable for 110 stations and abilityto interconnect 10 more zones for future expansion
2 Central exchange for CHP area with integrated MDF 1 No.Microprocessor controlled, digital, programmable central control unit(CCU) with PCM/TDM technology suitable for 90 stations and ability tointerconnect 10 more zones for future expansion
3 Master Control Station (MCS) 4 Nos.Built-in mic & speaker, LCD display, handset, 4 LED indicators & 18nos. key board switches
4 Flush Mounted Station (FMS) 4 Nos.Built-in mic & speaker, LCD display, handset, 4 LED indicators & 18nos. key board switches
5 Desktop Station with Cone type speaker 20 Nos.
SUPPLY (Rs)QUANTITY
1 X 500 MW FGUTPP STAGE-IV - Bill of Quantity for Main Items for Public Address System
5 Desktop Station with Cone type speaker 20 Nos.Built-in mic & speaker, LCD display, handset, 4 LED indicators & 18nos. key board switches
6 Extension amplifier for MCS, FMS and desktop station 28 Nos.7 Wall/column mounted, weatherproof field call station with handset and
built-in power amplifier,Horn type loudspeaker with 15W (RMS) , for outdoor area (Main & Common plant) conforming to IP-55
60 Nos.
8 Wall/column mounted, weatherproof field call station with handset and built-in power amplifier,Horn type loudspeaker with 15W (RMS) , for outdoor area (CHP area) conforming to IP-65
50 Nos.
9 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (Main & Common plant) conforming to IP-52
45 Nos.
10 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (CHP area) conforming to IP-65
25 Nos.
11 Sub-distribution frame (SDF) 24 pairs 35 Nos.12 Portable handset station with multi-pin plug and 25 meter wire 4 Nos.13 Socket box for Portable handset station 10 Nos.14 Wall/ column mounted 4W Cone type loudspeaker 20 Nos.15 Wall/ column mounted 15W Horn type loudspeaker (Main & common
plant area) conforming to IP-55 for outdoor area60 Nos.
ANNEXURE-11
Item No.
DESCRIPTION Unit
(A) MAIN EQUIPMENT MAKE MODEL NO.
Unit Ex-works
price/Unit Price
Total Ex-Works Price
duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess on E & C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C
in INR
SUPPLY (Rs)QUANTITY
1 X 500 MW FGUTPP STAGE-IV - Bill of Quantity for Main Items for Public Address System
16 Wall/ column mounted 15W Horn type loudspeaker (Main & commonplant area) conforming to IP-52 for indoor area
45 Nos.
17 Wall/ column mounted 15W Horn type loudspeaker (CHP plant area)conforming to IP-65
75 Nos.
18 Power junction box 200 Nos.19 Signal junction box 30 Nos.20 Sound protecting floor mounted Acoustic hood 10 Nos.21 Weather protecting canopy for field call station 110 Nos.22 Power distribution box 2 Nos.23 Special tools & tackles, if any24 Additional item, required for the completeness of system
NOTES:1. Bidder must indicate the make & model number of each item else the offer can not be evaluated.2. The unit rates of supply for all equipment are to be quoted by the bidder.3. Design and engineering charges shall form part of main equipment.4. Charges for special tools & tackles required for the PA system shall form part of main equipment.5. Main equipment Items, which are not applicable for their system, bidder to mention in "Remarks" column and same shall appear in the unpriced5. Main equipment Items, which are not applicable for their system, bidder to mention in "Remarks" column and same shall appear in the unpriced
copy of the bid also.6. Any additional item/equipment required (as per system quoted by the bidder), bidder shall quote it separately with their unit rate.
ANNEXURE-11
Item No.
DESCRIPTION
1 Central exchange for unit & common area with integrated MDF 1 No.
Microprocessor controlled, digital, programmable centralcontrol unit (CCU) with PCM/TDM technology suitable for 110stations and ability to interconnect 10 more zones for futureexpansion
2 Central exchange for CHP area with integrated MDF 1 No.
Microprocessor controlled, digital, programmable centralcontrol unit (CCU) with PCM/TDM technology suitable for 90stations and ability to interconnect 10 more zones for futureexpansion
3 Master Control Station (MCS) 4 Nos.
Built-in mic & speaker, LCD display, handset, 4 LED indicators& 18 nos. key board switches
4 Flush Mounted Station (FMS) 4 Nos.
Built-in mic & speaker, LCD display, handset, 4 LED indicators& 18 nos. key board switches
5 Desktop Station with Cone type speaker 20 Nos.
Built-in mic & speaker, LCD display, handset, 4 LED indicators& 18 nos. key board switches
6 Extension amplifier for MCS, FMS and desktop station 28 Nos.
7 Wall/column mounted, weatherproof field call station with handset and built-in power amplifier,Horn type loudspeaker with 15W (RMS) for outdoor area (Main & Common plant) conforming to IP-55
60 Nos.
8 Wall/column mounted, weatherproof field call station with handset and built-in power amplifier,Horn type loudspeaker with 15W (RMS) for outdoor area (CHP area) conforming to IP-65
50 Nos.
9 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (Main & Common plant) conforming to IP-52
45 Nos.
Total Ex-Works Price duly packed in INR/Total
Price.
Total Erection &
Commissioning Charges
in INR
ERECTION & COMMISSIONING
Unit Excise Duty @ on self
manufactured only
E & C (Rs)
QUANTITY
1 X 500 MW FGUTPP STAGE-IV - Price Schedule E & C for Public Address System
VAT/CST @ … in INR on
self manufacture
d only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Service tax @ including
cess on E & C in INR
Total E & C prices
including Service Tax
in INR
(B)
Unit Erection & Commissioning Charges in INR
ANNEXURE-11
10 Wall/column mounted, with handset, built-in power amplifier with horn type speaker 15W (RMS) for indoor area (CHP area) conforming to IP-65
25 Nos.
11 Sub-distribution frame (SDF) 24 pairs 35 Nos.
12 Portable handset station with multi-pin plug and 25 meter wire 4 Nos.
13 Socket box for Portable handset station 10 Nos.
14 Wall/ column mounted 4W Cone type loudspeaker 20 Nos.
15 Wall/ column mounted 15W Horn type loudspeaker (Main &common plant area) conforming to IP-55 for outdoor area
60 Nos.
16 Wall/ column mounted 15W Horn type loudspeaker (Main &common plant area) conforming to IP-52 for indoor area
45 Nos.
17 Wall/ column mounted 15W Horn type loudspeaker (CHPplant area) conforming to IP-65
75 Nos.
18 Power junction box 200 Nos.19 Signal junction box 30 Nos.20 Sound protecting floor mounted Acoustic hood 10 Nos.21 Weather protecting canopy for field call station 110 Nos.22 Power distribution box 2 Nos.
NOTES:12
345 Cables laying is not in the scope of the bidder (except the local cable from JB to station). However, termination of cables on
bidder's equipment is in bidder's scope.
The unit rates of E&C for all equipment are to be quoted by the bidder.Fabrication & painting of support structure for various equipment shall be in bidders scope. However, structural steel will be free issue from NBPPL.E & C spares required shall form part of erection & commissioning charges.Instruments required for testing & commissioning shall be arranged by the bidder.
ANNEXURE-11A
Item No. DESCRIPTION QUANTITY
Handsets(i) Handset with cord for outdoor station 15 nos(ii) Handset with cord for indoor station (desk for mounted) 4 nos(iii) Handset with cord indoor flush mounted 1 nos(iv) Portable Handset 1 nos
Loudspeakers(i) Outdoor horn type loudspeaker 15 nos(ii) indoor cone type loudspeaker 4 nos(iii) Cradle switch 2 nos of each type(iv) Push buttons of all types and model 2 nos. of each type
(v)Amplifier PCB with all components mounted for wall mounted Handset station 10%
(vi) Extension Amplifier PCB with all components mounted for wall type mounted Handset station (in case different from ix above) 2 nos. of each type
(vii) JB's of Handset. 2 nos(viii) JB's of Loudspeaker 2 nosix) Electronic modules of all types. 10% 10%
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service Tax in
INR
Total Supply and E&C in INR
1 X 500 MW FGUTPP STAGE-IV - Price Schedule Mandatory Spares for Public Address System PUBLIC ADDRESS SYSTEM MANDATORY SPARES
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
13. DRY TYPE TRANSFORMERS
A. MAIN ITEM
S.No Description Unit Qty Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax
in INR
Total Supply and E&C in INR
I3.3/0.433KV Indoor Transformer
(Dry Type)
12.0 MVA,3.3/0.433KV Indoor
Transformers (Dry Type)Nos 4
II Mandatory Spares
1For above 3.3/0.433KV 2.0 MVA
Transformer
1.1 HV Bushing Nos 1
1.2 LV Bushing Nos 1
1.3 LV Neutral Nos 1
1.4Complete Winding Limb (HV and
LV)Nos 1
1.5 WTI Nos 1
1.6Set of Thermistor / RTD with
associated leads complete for one transformer
Nos 1
Annexure-12 (Price Schedule/BOM ofDry Type Transformer)
Bill of quantity of Erection and commissioning of Dry Type Transformers A. MAIN ITEM
S.No Description Unit QtyUnit Erection &
Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty including cess @ ……Rs
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges in
INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
12.0 MVA,3.3/0.433 kV Indoor
Transformers (Dry Type)Nos 4
Annexure 12
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
14. OIL FILLED TRANSFORMERS
TOTAL
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
(Nos) Rs. Rs.1 12500kVA, 11kV/3.5kV, 3 phase, 2
winding, outdoor, ONAN, Z= 11.7%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
2 2000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 10.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
13
3 1600KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 8.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
4 1000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
5 630KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
NOTES
S. NO. DESCRIPTION QTY. OF TRANSFORMERS
COST OF 10% EXTRA OIL PER TRANSFORMER
TOTAL COST OF 10% EXTRA OIL Total Ex-Works Price
duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service
Tax in INR
Total Supply and
E&C Rs
10 % EXTRA TRANSFORMER OIL IN SEALED NON RETURNABLE STANDARD DRUMS FOR :
2
Annexure-13AAUXILIARY SERVICE TRANSFORMERS (OIL FILLED)
SCHEDULE OF PRICES – TRANSFORMERS
1. ALL ROUTINE AND ACCEPTANCE TESTS AS PER CLAUSE NO. 10.04 AND 10.05 OF TECHNICAL SPECIFICATION NO. PE-RC-999-302-E001 SHALL BE CARRIED OUT ON ALL TRANSFORMERS WITHOUT ANY ADDITIONAL COST. CHARGES FOR ALL ROUTINE AND ACCEPTANCE TESTS SHALL BE DEEMED TO BE INCLUDED IN BID PRICE. BIDDERS SHALL QUOTE ACCORDINGLY.
Annexure-13B
S. No. DESCRIPTION
AUXILIARY SERVICE TRANSFORMERS (OIL FILLED) SCHEDULE OF PRICES – EXTRA OIL
1
(A) 12500kVA, 11kV/3.5kV, 3 phase, 2 winding, outdoor, ONAN, Z= 11.7%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination))
13
(B) 2000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 10.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination) )
2
(C) 1600KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 8.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
(D) 1000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
(E) 630KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps ±5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
Note:Bidder shall supply 10% extra oil as per the quoted price. Quantity of extra oil shall be subject to approval during detail engineering.
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
Rs. Rs.HV bushing with metal parts & gaskets
a) 11.0/3.5kV,125000KVA 1 no.b) 3.3/0.433kV, 2000KVA 1 no.c) 3.3/0.433kV, 1600KVA 1 no.d) 3.3/0.433kV, 1000KVA 1 noe) 3.3/0.433kV, 630KVA 1 no.
LV bushing with metal parts & gasketsa) 11.0/3.5kV,125000KVA 1 no.b) 3.3/0.433kV, 2000KVA 1 no.c) 3.3/0.433kV, 1600KVA 1 no.d) 3.3/0.433kV, 1000KVA 1 no.e) 3.3/0.433kV, 630KVA 1 no.
Neutral bushing with metal parts & gaskets
a) 11.0/3.5kV,125000KVA 1 no.c) 3.3/0.433kV, 2000KVA 1 no.d) 3.3/0.433kV, 1600KVA 1 no.e) 3.3/0.433kV, 1000KVA 1 no.f) 3.3/0.433kV, 630KVA 1 no.
4 WTI with contacts 1 no.5 OTI with contacts 1 no.
2
3
Annexure-13DAUXILIARY SERVICE TRANSFORMERS (OIL FILLED)
1
S. NO. DESCRIPTION QTY.SCHEDULE OF PRICES – MANDATORY SPARES
6 Pressure relief device 1 no.7 Magnetic oil gauge 1 no.8 Buchholz relay complete 1 no.9 Set of gaskets 1 set
10 Set of valves 1 set11 Air cell for conservator (if applicable) 1 no.
NOTES
SET CONSISTS OF QUANTITIES REQUIRED FOR 1 COMPLETE TRANSFORMER. WHEREVER ‘SET’ IS INDICATED ABOVE, IT MEANS THE TOTAL PARTS / ACCESSORIES REQUIRED TO REPLACE THE PARTICULAR ITEM FOR A GIVEN EQUIPMENT.
TOTALUnit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges in INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service Tax
in INR
(Nos) Rs. Rs.
3 1600KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 8.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
4 1000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
5 630KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 6.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
Annexure‐13AUXILIARY SERVICE TRANSFORMERS (OIL FILLED)
BILL OF QUANTITY ERECTION & COMMISSIONING OF OIL FILLED SERVICE TRANSFORMERSS. No. DESCRIPTION
1 12500kVA, 11kV/3.5kV, 3 phase, 2 winding, outdoor, ONAN, Z= 11.7%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
2
2 2000KVA, 3.3kV/433V, 3 phase, 2 winding, outdoor, ONAN, Z= 10.0%, Dyn11, OFF Circuit taps 5% in steps of 2.5% (with cable box type HV and with bus-duct type LV termination)
13
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
15. EMERGENCY DG SET
ANNEXURE-14
S.NO. ITEM DESCRIPTION UNIT Nos.
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges
INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in
INR
Total Supply and E&C in INR
1
1500 KVA, 3 phase, 415 V diesel generator set (The complete DG set shall be supplied along with equipments/accessories/panels/tools & tackales mentioned in various sections of the technical specification.)
Set 2
UNPRICED PRICE SCHEDULE OF SUPPLY FOR EMERGENCY DG SET
S.NO. ITEM DESCRIPTION UNIT Nos.
Unit Erection &
Commissioning Charges
in INR
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufacture
d only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
in INR
Service tax @ including
cess on E & C in INR
Total E & C prices
including Service Tax
in INR
1
1500 KVA, 3 phase, 415 V diesel generator set (Erection/commisioning of the complete DG set along with equipments/accessories/panels/tools & tackales mentioned in various sections of the technical specification.)
Set 2
UNPRICED PRICE SCHEDULE OF E & C FOR EMERGENCY DG SETANNEXURE‐14
LIST OF MANDATORY SPARES FOR DG SET
GROUP-A
S.no. Item Description Quantity Unit Ex-works
price/Unit Price
Total Ex-Works Price
duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
Total Supply and E&C in
INR
None GROUP-B
S.no. Item Description Quantity
1 Ammeter 96x96mm, (0-200 amp) Accuracy class:1.0 1 No.
2 A.C. Voltmeter 96x96 mm, (0-15 kV) Accuracy class:1.0 1 No.
GROUP-C S.no. Item Description Quantity 1. Gaskets & packing 1 Set 2. Valve springs 1 Set 3. Fuel pump complete 1 Set 4. Fuel nozzles and needles 1 Set 5. Piston, complete with rings and rod 1 Set 6. Piston rings( for each engine) 1 Set
7. Flow and temperature relay of each type used 1 Set
8. Main and end bearing shells for the diesel engine 1 Set
9. Generator bearing sheets 1 No. 10. Rotor pole coil 1 No. 11 Battery charging rectifier diodes 4 Nos.
12 Complete rotating rectifier assembly for alternator 1 Set
13 Fuses for the excitation diodes 3 Sets 14 Automatic voltage regulator 1 Set
15 Solenoid coil for each solenoid operated valve or relay used 2 Each
16 Instrument and indicator of each type used 1 Each
17 Alarm and signal lamps of each type used 10% of total population
18 Cabinet lighting lamps( if applicable) 2 Each 19 Bearing check kit 1 Set 20 Shut down coil 1 No. 21 Lub oil pressure relay 1 No. 22 Filter screen 1 No. 23 ‘O’ ring injector 1 Set 24 ‘ O’ ring breather 1 Set 25 Magnetic pick up 1 No. 26 Actuator 1 Set 27 Air cleaner 1 Set 28 Belts( Fan belt) 1 Set 29 Hose bypass 1 No. 30 Hose turbo oil supply 2 Nos. 31 Hose turbo oil drain 2 Nos. 32 Turbo repair kit 1 No.
33 Over speed stop 1 No. 34 Resistor for diesel generator 48 Nos.
35 Element lube oil filter for Diesel Engine 48 Nos.
36 Element lube oil by-pass filter for Diesel Engine 24 Nos.
37 Element fuel filter for Diesel Engine 24 Nos.
38 Plate corr. Resistor for Diesel Engine 96 Nos.
39 Element air cleaner for Diesel engine 4 Nos. 40 Diodes forward for alternator 3 Nos. 41 Diodes reverse for alternator 3 Nos. 42 HRC fuses links of various rating 3 Nos. of each type 43 Ammeter selector switches 1 No. 44 Local/Remote selector switches 1 No. 45 Voltmeter selector switches 1 No.
46 Push button for trip circuit healthy test 1 No.
47 White indication lamps for spring charged position 1 No.
48 Alarm bell 1 No.
49 Space heater along with control switch 1 No. 50 Trip circuit supervision relay 1 No.
51 Lube oil pump assembly/rotating assembly/impeller/shaft 1 Set
52 Starting air motor 1 No. 53 Governing mechanism of DG set 1 No.
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
16. EPABX SYSTEM
EPBAX SYSTEM Price Schedule
Main item
S NO DESCRIPTION UNIT
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service Tax in
INR
Total Supply and E&C in INR
1Complete EPBAX system as per scope of supply mentioned in the Technical specification including installation & commisioning
1 LOT
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
17. ELECTRICAL EQUIPMENT HANDLING ARRANGEMENT
Proj
ect:
1X
500
MW
FG
UT
PPR
01
Pack
age:
EL
EC
TR
IC H
OIS
T a
nd C
HA
IN P
UL
LE
Y B
LO
CK
-
SU
PPL
YPr
ice
Form
atS.
N.
Des
crip
tion
of e
quip
men
t / it
emTo
tal Q
ty
requ
irdU
nit E
x-w
orks
pric
e/U
nit
Pric
e
Tota
l Ex-
Wor
ks
Pric
e du
ly
pack
ed in
IN
R/T
otal
Pric
e.
Exci
seD
uty
@ o
n se
lfm
anuf
actu
red
only
VAT/
CST
@ …
in
INR
on
self
man
ufac
ture
d on
ly
Frei
ght
incl
udin
gSe
rvic
eta
x @
Tota
l FO
R
Site
Pric
e (S
uppl
y)in
INR
12
34
51.
0To
tal l
umps
um fi
rm p
rice
for d
esig
n, e
ngin
eerin
g, m
anuf
actu
ring,
in
spec
tion
and
test
ing,
pain
ting,
supp
ly/d
eliv
ery
duly
pac
ked
at p
roje
ct
site
incl
udin
g fr
eigh
t in
line
with
dra
win
gs/ d
ocum
ents
/ tes
t pro
cedu
res
appr
oved
by
NB
PPL/
NTP
C fo
r the
tota
l sco
pe o
f ele
ctric
hoi
sts a
nd
chai
n pu
lley
bloc
k de
fined
as p
er te
chni
cal s
peci
ficat
ion
PE-
TS-4
04-x
xx-
xxx
taki
ng in
to a
ccou
nt a
ll cl
arifi
catio
ns, c
onfir
mat
ions
and
agr
eem
ents
til
l dat
e.
LOT
BR
EA
K U
P FO
R P
RIC
E A
T 1
.0
1.1
Tota
l lum
psum
pric
e of
1 N
o. E
lect
ric H
oist
of
5T c
ap fo
r ESP
con
trol
room
with
all
acce
ssor
ies i
nclu
ding
isol
atin
g sw
itch
& D
SL1
no.
1.2
Tota
l lum
psum
pric
e of
1 N
o. E
lect
ric H
oist
of
3T c
ap fo
r Boi
ler M
CC
ro
om w
ith a
ll ac
cess
orie
s inc
ludi
ng is
olat
ing
switc
h &
DSL
1 no
.
1.3
Tota
l lum
psum
pric
e of
1 N
o. M
anua
l Hoi
st (C
hain
pul
ley
bloc
k) o
f 2T
ca
p fo
r MV
switc
hgea
r with
all
acce
ssor
ies
1 no
.
1.4
Tota
l lum
psum
pric
e fo
r E&
C sp
ares
as p
er a
nnex
ure
A1
set
1.5
Tota
l lum
psum
pric
e fo
r mai
nten
ance
tool
s and
tack
les a
s per
ann
exur
e B
1 se
t
1 2 3 4
NO
TE Bid
der t
o no
te th
at to
tal p
rice
indi
cate
d ab
ove
at 1
.0 s
hall
be c
onsi
dere
d fo
r eva
luat
ion
and
henc
e sh
ould
be
com
plet
e in
all
resp
ect f
or th
e fu
ll sc
ope
defin
ed a
nd
cons
ider
ing
all t
erm
s and
con
ditio
ns a
gree
d.
Any
item
not
incl
uded
in th
e pr
ice
quot
ed a
bove
and
show
n se
para
tely
will
not
be
take
n co
gniz
ance
of a
nd th
e of
fer s
hall
be li
able
for r
ejec
tion.
Bid
der t
o no
te th
at in
un-
pric
e bi
d, b
idde
r mus
t ind
icat
e as
"Q
UO
TED
" ag
ains
t uni
t pric
e &
tota
l pric
e co
lum
n. P
rice
shou
ld b
e in
dica
ted
in P
rice
Bid
onl
y.
Pric
es q
uote
d ab
ove
at S
.No.
1.1,
1.2
& 1
.3 o
f pric
e sc
hedu
le sh
all b
e co
nsid
ered
for a
ny a
dditi
onal
scop
e re
quire
men
t of E
lect
ric h
oist
s & c
hain
pul
ley
bloc
ks d
urin
g de
tail
engi
neer
ing.
R1
22
5N
opr
ice
impl
icat
ion
shal
lbe
prov
ided
fort
rave
l&lif
tvar
iatio
n.
Proj
ect:
1X
500
MW
FG
UT
PPR
01SY
STE
M-
AN
NEX
UR
E-A
Pack
age:
EL
EC
TR
IC H
OIS
TS
Pric
e Fo
rmat
Sl.n
oD
escr
iptio
nTo
tal
quan
tity
requ
ired
Uni
tU
nit E
x-w
orks
pric
e/U
nit
Pric
e
Tota
l Ex-
Wor
ks
Pric
e du
ly p
acke
d in
INR
/Tot
al
Pric
e.
Exci
se D
uty
@
on s
elf
man
ufac
ture
don
ly
VAT/
CST
@ …
in
INR
on
self
man
ufac
ture
don
ly
Frei
ght
incl
udin
gSe
rvic
e ta
x @
Tota
l FO
R
Site
Pric
e (S
uppl
y)in
INR
12
34
56
Afo
r 3T
capa
city
ele
ctric
hoi
st.
1se
tI)
Ove
rload
Rel
ay
ii)Li
mit
Sw
itch
iii)
Fuse
Lin
k
Bfo
r 5T
capa
city
ele
ctric
hoi
st.
1S
etI)
Ove
rload
Rel
ay
ii)Li
mit
Sw
itch
iii)
Fuse
Lin
k
Tota
l for
site
pric
e fo
r Com
m. S
pare
s
List
of C
omm
isio
ning
spa
res
Proj
ect:
1X
500
MW
FG
UT
PPR
01SY
STE
M-
AN
NEX
UR
E-B
Pack
age:
EL
EC
TR
IC H
OIS
TS
& C
PBPr
ice
Form
at
Sl.n o
Des
crip
tion
Tota
l qu
antit
yre
quire
d
Uni
tU
nit E
x-w
orks
pric
e/U
nit
Pric
e
Tota
l Ex-
Wor
ks P
rice
duly
pac
ked
in IN
R/T
otal
Pr
ice.
Exci
se D
uty
@ o
n se
lf m
anuf
actu
red
only
VAT/
CST
@
… in
INR
on
self
man
ufac
tur
ed o
nly
Frei
ght
incl
udin
gSe
rvic
e ta
x @
Tota
l FO
R S
ite P
rice
(Sup
ply)
in
INR
1C
ompl
ete
set
of6
nos.
ring
span
ners
(Ind
icat
e si
zes)
1Se
ts
2C
ompl
ete
set o
f scr
ewdr
iver
s (M
in 6
nos
, in
dica
te si
ze)
1Se
ts
3A
djus
tabl
e Sp
anne
r 12"
1no
.4
Line
test
er1
no.
5In
sula
ted
plie
r1
no.
6G
reas
e gu
n1
no.
7O
il gu
n1
no.
8To
ol b
ox1
no.
Tot
al P
rice
List
of M
aint
enan
ce T
ools
& T
ackl
es
Not
e: 1
LO
T of
all
item
s in
dica
ted
abov
e ar
e to
be
prov
ided
for e
lect
ric h
oist
and
cha
in p
ulle
y bl
ock
i.e. 1
LO
T fo
r ele
ctric
hoi
st a
nd 1
LO
T fo
r cha
in p
ulle
y bl
ock.
2:B
idde
rto
cons
ider
tool
s&
tack
les
insu
cha
way
that
can
cate
rreq
uire
men
tofe
ach
capa
city
&ty
peof
elec
tric
hois
ts&
chai
npu
lley
bloc
ks
Proj
ect:
1X
500
MW
FG
UT
PPSY
STE
M-
Pack
a ge:
EL
EC
TR
IC H
OIS
TS
& C
hain
Pul
ley
Blo
cks
Pric
e Fo
rmat
R01
S.N
.D
escr
iptio
n of
equ
ipm
ent /
item
Tota
l Qty
re
quird
E&C
cha
rges
in
INR
Serv
ice
tax
@in
clud
ing
cess
on
E& C
in
INR
Tota
l E &
C p
rices
incl
udin
g Se
rvic
eTa
x in
INR
12
34
56
1.0
Tota
l lum
psum
firm
pric
e fo
r rec
eipt
, unl
oadi
ng, s
tora
ge &
ha
ndlin
g at
site
, ere
ctio
n an
d co
mm
issi
onin
g, lo
ad te
stin
g,
trial
run,
han
dlin
g ov
er to
cus
tom
er fo
r the
tota
l sco
pe o
f el
ectri
c ho
ists
and
cha
in p
ulle
y bl
ock
defin
ed a
s per
tech
nica
l sp
ecifi
catio
n P
E-TS
-404
-xxx
-xxx
taki
ng in
to a
ccou
nt a
ll cl
arifi
catio
ns, c
onfir
mat
ions
and
agr
eem
ents
till
date
.
LOT
BR
EA
K U
P FO
R P
RIC
E A
T 1
.01.
1To
tal E
&C
pric
eof
1 N
o. E
lect
ric H
oist
of
5T c
ap fo
r ESP
co
ntro
l roo
m w
ith a
ll ac
cess
orie
s inc
ludi
ng is
olat
ing
switc
h,
DSL
,mai
nten
ance
tool
s and
tack
les,
E&C
spar
es e
tc.
1 no
.
1.2
Tota
l E&
C p
rice
of 1
No.
Elec
tric
Hoi
st o
f 3T
cap
for B
oile
r M
CC
room
with
all
acce
ssor
ies i
nclu
ding
isol
atin
g sw
itch
DSL
,mai
nten
ance
tool
s and
tack
les,
E&C
spar
es e
tc.
1 no
.
1.3
Tota
l E&
C p
rice
of 1
No.
Man
ual H
oist
(Cha
in p
ulle
y bl
ock)
of
2T c
ap fo
r MV
switc
hgea
r with
all
acce
ssor
ies &
m
aint
enan
ce to
ols a
nd ta
ckle
s etc
.
1 no
.
NO
TE
1 2 3 4
Bid
der t
o no
te th
at to
tal p
rice
indi
cate
d ab
ove
at 1
.0 s
hall
be c
onsi
dere
d fo
r eva
luat
ion
and
henc
e sh
ould
be
com
plet
e in
all
resp
ect f
or th
e fu
ll sc
ope
defin
ed
and
cons
ider
ing
all t
erm
s and
con
ditio
ns a
gree
d.
Any
item
not
incl
uded
in th
e pr
ice
quot
ed a
bove
and
show
n se
para
tely
will
not
be
take
n co
gniz
ance
of a
nd th
e of
fer s
hall
be li
able
for r
ejec
tion.
Bid
der t
o no
te th
at in
un-
pric
e bi
d, b
idde
r mus
t ind
icat
e as
"Q
UO
TED
" ag
ains
t uni
t pric
e &
tota
l pric
e co
lum
n. P
rice
shou
ld b
e in
dica
ted
in P
rice
Bid
onl
y.
Pric
es q
uote
d ab
ove
at S
.No.
1.1,
1.2
& 1
.3 o
f pric
e sc
hedu
le sh
all b
e co
nsid
ered
for a
ny a
dditi
onal
scop
e re
quire
men
t of E
lect
ric h
oist
s & c
hain
pul
ley
bloc
ks
durin
g de
tail
engi
neer
ing.
-E&
C
1X500 MW UNCHAHAR TPP, RAE BARELI Price Schedule – Volume II, Part C
Tech Spec No.- PE-TS-401-999-E001; Rev.1
OPTIONAL ITEMS
Board 11kV SwitchboardRating 3150A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Price (Rs.)1 Incomer 3150A DC 12 Tie from Other Switchboard 2750A DE 1
Board 11kV SwitchboardRating 2750A
S.no Feeder Description Rating Module Type Quantity (Nos.) Unit Price (Rs.)1 Incomer 2750A DC 12 Tie from Other Switchboard 2750A DE 1
1X500 MW FGUTPPAnnexure -2J ( Board Wise BOM & Schedule of Unit Prices for 11kV switchboard )
(OPTIONAL ITEM)
Unit rates quoted in Annexure-2J shall be used for any addition /deletion during detail engineering.
1X500 MW UCHAHAR FGTPS (UNIT‐6) RECOMMENNDED O SPARES FOR LV SWITCHGEAR,LT BUS DUCT AND NGR (OPTIONAL) ANNEXURE‐3A
RATING(A) BOARD NO.
56RECOMMENDED O & M
SPARES for LV switchgearNOS. 1 BIDDER TO FURNISH
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufactured
only
Total Supply and E&C in
INRSr.No. ITEM NAME UOM TOTAL QTY.REMARKS
Freight including Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges INR
Service tax @ including cess on E &
C in INR
Total E & C prices
including Service Tax
in INR
PAGE 1 OF 4
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
1 INCOMING FEEDER UNITa) Incoming ACB to PCC/PMCC from Trafo. - Module Type DAET (I/C)
1000A1250A1600A2500A3200A
b) Incoming ACB to MCC - Module Type DAE (I/C)630A800A1000A1250A1600A
c) Incoming ACB to Emergency MCC - Module Type DAE(EMG-I/C)800A1000A1250A
d) MCCB Incomer for MCC / ACDB – Module Type E3 (I/C) (Upto 200A SFU controlled)
Upto 63A – Fixed Type125A – Fixed Type200A – Fixed Type250A – Fixed Type400A – Fixed Type630A – Fixed TypeUpto 63A – Drawout Type (Upto 200A SFU controlled)125A – Drawout Type200A – Drawout Type250A – Drawout Type400A – Drawout Type630A – Drawout Type
e) TPN SFU Incomer for AC Fuse DBs – Module Type H3 (I/C)63A 125A
f) 220V DCDB Incomer from charger - Module type CH 200A – CH Fixed Type400A – CH Fixed Type630A – CH Fixed Type800A – CH Fixed Type200A – CH Drawout Type400A – CH Drawout Type630A – CH Drawout Type800A – CH Drawout Type
g) 220V DCDB Incomer from battery - Module type DB200A – DB Fixed Type400A – DB Fixed Type630A – DB Fixed Type800A – DB Fixed Type200A – DB Drawout Type400A – DB Drawout Type630A – DB Drawout Type800A – DB Drawout Type
h) 220V DC Fuse DB Incomer from DCDB - Module type HD32A 50A 63A
2 BUSCOUPLER UNITa) ACB buscoupler for PCC/PMCC- Module Type DAE (TIE)
1000A1250A1600A2500A3200A
b) ACB buscoupler for PCC/PMCC- Module Type DAE (B/C)630A800A1000A1250A1600A
c) MCCB buscoupler – Module type E3 (B/C) (Upto 200A SFU controlled)UPTO 63A - Fixed Type125A - Fixed Type
PAGE 1 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
200A - Fixed Type250A - Fixed Type400A - Fixed Type630A - Fixed TypeUPTO 63A - Drawout Type125A - Drawout Type200A - Drawout Type250A - Drawout Type400A - Drawout Type630A - Drawout Type
3 Outgoing ACB supply feeder - Module Type DAE (O/G)630A800A1000A1250A1600A2000A
4 Outgoing ACB MLDB feeder - Module Type DAE (LDB)630A800A
5 Outgoing ACB motor feeder - Module Type DM/PM (controlled from DDCMIS/PLC)
100.1 - 200KW6 DOL Motor Starter - Unidirectional Drive - Drawout Typea) Module Type K2 (Controlled from Local Control Panel)
Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 - 29.9KW
b) Module Type K21 (Controlled from Local Control Panel)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW
c) Module Type K3 (Controlled from Local Push Button Station)Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 - 29.9KW
d) Module Type K31 (Controlled from Local Push Button Station)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW
e) Module Type DK2/AK2/PK2 (Controlled from DDCMIS/ATRS/PLC)Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW
f) Module Type DK21/AK21/PK21 (Controlled from DDCMIS/ATRS/PLC)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW
g) Module Type DKE2/AKE2/PKE2 (Controlled from DDCMIS/ATRS/PLC)Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW
PAGE 2 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
h) Module Type DKE21/AKE21/PKE21 (Controlled from DDCMIS/ATRS/PLC)30.0 - 37.0KW37.1 - 40.0KW40.1 - 49.9KW50.0 - 55.0KW55.1 - 80KW80.1 - 90KW90.1 - 100KW
7 RDOL Motor Starter – Bidirectional Drive Drawout Typea) Module Type DN1/AN1/PN1 (Controlled from DDCMIS/ATRS/PLC)
Upto 5.5KW5.6 - 7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW
b) Module Type N1 (Controlled from Local Control Panel)Upto 5.5KW5.6-7.0KW7.1 - 13KW13.1 - 24KW24.1 – 29.9KW
8 Outgoing MCCB controlled feedersa) Outgoing MCCB controlled supply feeder - Module Type E3 (O/G) up to 200A SFU
controlled.upto 10A - Fixed type16A - Fixed type25A - Fixed type32A - Fixed type63A - Fixed type80A - Fixed type100A - Fixed type125A - Fixed type160A - Fixed type200A - Fixed type250A - Fixed type400A - Fixed type630A - Fixed typeupto 10A - Drawout type (up to 200A SFU controlled)16A - Drawout type25A - Drawout type32A - Drawout type63A - Drawout type80A - Drawout type100A - Drawout type125A - Drawout type160A - Drawout type200A - Drawout type250A - Drawout type400A - Drawout type630A - Drawout type
b) Double pole MCCB controlled 1-ph feeder - E1 (O/G) - Fixed Type (up to 200A SFU controlled)16A25A32A63A125A
c) Double pole MCCB controlled 1-ph feeder - E1 (O/G) - Drawout Type (up to 200A SFU controlled)16A25A32A63A125A
d) 3-Ph MCCB controlled Outgoing contactor feeder (EA3) – Fixed Type (up to 200A SFU controlled)16A25A32A63A
e) 3-Ph MCCB controlled Outgoing contactor feeder (EA3) – Drawout Type (up to 200A SFU controlled)
PAGE 3 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
16A25A32A63A125A185A200A
f) 1-Ph MCCB controlled Outgoing contactor feeder (EA1) – Fixed Type (up to 200A SFU controlled)16A25A32A63A125A
g) 1-Ph MCCB controlled Outgoing contactor feeder (EA1) – Drawout Type (up to 200A SFU controlled)16A25A32A63A125A
9 Outgoing Switch-fuse feedersa) Outgoing TPN Switch-fuse feeder - Module Type H3 (O/G)
16A25A32A
b) Single phase switch-fuse feeder - H1 (O/G) 16A25A32A
c) 220V DC Outgoing switch fuse feeder (X) 6A10A16A25A32A50A63A100A125A160A200A400A630A
10 Common Auxiliary Modulea) PT module
i Bus PT module for PCC/PMCC-G1ii Bus PT module for Emergency MCC-G2iii Bus PT module for MCC-VMiv Bus PT module for DCDB-Sb) Panel space heating modulec) 110V AC control supply module – Type CS (consisting of 415/110V control Trafo.)
1KVA2KVA2.5KVA3KVA5KVA7.5KVA10KVA
d) 240 V AC control supply module – type CS (consisting of 415/240V control Trafo.)1KVA2KVA2.5KVA3KVA5KVA7.5KVA10KVA
e) 240V AC motor space heater module220V DC supply module(for receiving 220V DC supply)
g) 24 V winding heating moduleh) Alarm module
f)
PAGE 4 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
i) Test supply module11 Empty Panel with Horizontal & Vertical Busbar, Support & Auxiliary Busbara) MCC Panel (Double Front Drawout Type)
250 / 250A400 / 400A630 / 630A800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A
b) MCC Panel (Double Front Fixed Type)250 / 250A400 / 400A630 / 630A800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A
c) 220V DCDB Panel (Double Front Fixed type) UPTO 800A (with 630A VBB)1000A (with 630A VBB)
d) 220V DCDB Panel (Double Front Drawout type) UPTO 800A (with 630A VBB)1000A (with 630A VBB)
12 Empty Panel With Horizontal & Vertical Busbar, Support & Auxiliary Busbara) PCC Panel (Single Front Drawout Type)
1600 / 1600A2500 / 2500A3200 / 3200A
b) MCC Panel (Single Front Drawout Type)250 / 250A400 / 400A630 / 630A800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A
c) MCC Panel (Single Front Fixed Type )250 / 250A400 / 400A630 / 630A
PAGE 5 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
800 / 630A800 / 800A1000 / 630A1000 / 800A1000 / 1000A1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A
d) DCDB Panel (Single Front Fixed Type Each Rating)UPTO 800A (with 630A VBB)1000A (with 630A VBB)
e) DCDB Panel (Single Front Drawout Type Each Rating)UPTO 800A 1000A
13 ACB Panel with Horizontal & Vertical Busbar, Support & Auxiliary Busbar800 / 630A 800 / 800A 1000 / 630A 1000 / 800A 1000 / 1000A 1250 / 630A1250 / 800A1250 / 1000A1250 / 1250A1600 / 630A1600 / 800A1600 / 1000A1600 / 1250A1600 / 1600A2500 / 630A2500 / 800A2500 / 1000A2500 / 1250A2500 / 1600A2500 / 2500A3200 / 630A3200 / 800A3200 / 1000A3200 / 1250A3200 / 1600A3200 / 2500A3200 / 3200A4000 / 630A4000 / 800A4000 / 1000A4000 / 1250A4000 / 1600A4000 / 2500A4000 / 3200A4000 / 4000A
14 Dummy Panel UPTO 630A800A1000A1250A1600A2500A3200A4000A
15 Unit Prices For Circuit Componentsa) Air Circuit Breaker without releases
630A (M)800A (M)1000A (M)1250A (M)
PAGE 6 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
630A800A1000A1250A1600A2500A3200A4000A
b) Air circuit breaker (with built-in O/L & S/C releases)630A (M)800A (M)1000A (M)1250A (M)630A800A1000A1250A1600A2500A3200A4000A
c) MCCB (Utilization category-'A')16A25A32A63A80A115A150A185A265A315A400A630A
d) MCCB (Utilization category-'B')16A25A32A63A80A115A150A185A265A315A400A630A
d (i) SFU16A25A32A63A80A115A150A185A265A315A400A630A
e) Switches (AC)-TPNUpto 16A25A32A63A125A250A400A630A
f) Switches (DC)Upto 16A
PAGE 7 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
25A40A60A100A200A300A400A630A
g) HRC Fuse Links (Offset tag Type)Upto 10A16A25A32A50A63A
h) DIN Type (Blade Contact)Upto 10A16A20A32A36A50A63A80A100A125A160A200A250A315A400AControl Fuse Link
i) Power contactor (AC)16A25A32A63A80A115A185A265A315A400A630A
j) Power contactor (DC)16A25A32A63A80A115A150A185A265A400A
k) Fuse Base UPTO 20A32A50/63A100A250A400A630A
l) Auxiliary contactor AC/DCi) AC Aux. contactor
2NO + 2NC3NO + 3NC4NO + 4NC6NO + 6NC
ii) DC Aux. contactor2NO + 2NC
PAGE 8 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
3NO + 3NC4NO + 4NC6NO + 6NC
m) Protection RelayVAGM 23CTU 12CTU 32VTT 11VAG 11VAA 11VAJHM 13VAJHM 23CDGM-12CAG 12CAG 34CCUM 21CDG11CDG 31CDG61VDG 14CDV 62CAG 14VAX 31CAG 37CAEM-21VAG-21VAJC-11CTMM-501MOTPROVAA21VTT12VTIGVTU21NUMERICAL RELAY FOR FOLLOWING FUNCTIONS:• SHORT CIRCUIT PROTECTION (51)• EARTH FAULT PROTECTION (51N)• UNDER VOLTAGE PROTECTION (27)• TRIP CIRCUIT SUPERVISION (95)NUMERICAL RELAY FOR FOLLOWING FUNCTIONS:• SHORT CIRCUIT PROTECTION (51)• EARTH FAULT PROTECTION (51N)• TRIP CIRCUIT SUPERVISION (95)Numerical relay for E/F protection for DCDBNumerical Check synchronising RealyNUMERICAL COMPOSITE RELAY for STANDBY E/F,SHORT CIRCUITPROTECTION, E/F PROTECTION, OVER LOAD PROTECTION,RESTRICTED E/F PROTECTION TC SUPERVISION,CB FAILURE PROTECTION,SYNCHRONISING CHECK FEATURE,MASTER TRIP FEATURE,CB MONITERING, UNDER VOLTAGE PROTECTIONWITH METERING OF CURRENT(3 PHASE), VOLTAGE (ALL3 PHASE & PHASE TO NEUTRAL) kW, ACTIVE POWER ,REACTIVE POWER,ENERGY, NEUTRAL CURRENT/RESIDUAL VOLTAGE, (WITH COMMUNICATION USING 61850 PROTOCOL)Check synchronising Realy Type-SKE
n) O/L Relaysi) Thermal O/L relay with SPP
Upto 5.5KW5.6 to 11KW11.1 to 22KW22.1 to 45KW45.1 to 75MW75.1 to 100KW
ii) Heavy Duty Thermal O/L relay with SPPUpto 5.5KW5.6 to 11KW11.1 to 22KW22.1 to 45KW45.1 to 75MW75.1 to 100KW
o) Timer (each type)p) Meter of each type & range
AC ammeter (Digital)AC ammeter (Analog)DC ammeter (Digital)
PAGE 9 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
DC ammeter (Analog)AC voltmeter (Digital)DC voltmeter (Analog)Wattmeter (3 Phase)Wattmeter (1 Phase)3-PH Electronic KWH Meter with RS485 Port1-PH Electronic KWH Meter with RS485 PortFrequency meter
q) Single Phase Preventor Relayr) MCB (each applicable type & rating)s) Control & Selector Switch And Push Button Stationi) Breaker control switchii) Test/normal/trial selector switchiii) Auto/manual switchiv) Limit switchv) Ammeter selector switchvi) Voltmeter selector switchvii) Synchronisation selector switchviii) Push Button
2NO + 2NC Shrouded1NO + 1NC Shrouded2NO + 2NC Mushroom head stayput2NO + 2NC Lockable type
t) Indicating Lamp Assembly (LED Type)u) CTi) Metering CT
Upto 75/1A100/1A125/1A150/1A200/1A250/1A300/1A400/1A500/1A630/1A800/1A1000/1A1250/1A1600/1A2000/1A2500/1A3200/1A4000/1A
ii) Protection CT (5P20)Upto 75/1A100/1A125/1A150/1A200/1A250/1A300/1A400/1A500/1A630/1A800/1A1000/1A1250/1A1600/1A2000/1A2500/1A3200/1A4000/1A630/5A800/5A1000/5A1250/5A1600/5A2000/5A2500/5A3200/5A
PAGE 10 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
iii) PS Class CT1600/1A2500/1A3200/1A4000/1A2500/5A3200/5A4000/5A
v) Voltage Transformeri) 415/√3 : 110/√3V, 1ph, 50VAii) 415/√3 : 110/√3V, 1ph, 100VAiii) 415/√3 : 240/√3V, 1ph, 50VAiv) 415/√3 : 240/√3V, 1ph, 100VAw) Toggle switch
16A toggle switchx) Secondary Isolating Contact Blocky) Control Terminal (Fixed)z) Thermostat
aa) 4-20mA Dual Output Current transducerab) 4-20mA Dual Output Voltage transducerac) 4-20mA Dual Output Watt transducerad) 4-20mA Dual Output Frequency transducerae) Interposing relay RE 302 or Eqvt with freewheeling diode & LEDaf) 4-16-20mA Dual Output Current transducerag) 4-16-20mA Dual Output Voltage transducerah) 4-16-20mA Dual Output Watt transducerai) 4-16-20mA Dual Output Frequency transducer16 Foundation Framea) MCC panel
upto 1600A (SF)2500A (SF)3200A (SF)4000A (SF)upto 1600A (DF)2500A (DF)3200A (DF)4000A (DF)
b) 220V DCDB panelSFDF
c) PCC / PMCC panelupto 1600A2500A3200A4000A
17 ACDB i) 12 way with 1-Ph O/G feedersii) 12 way with TPN O/G feedersiii) 20 way with TPN O/G feeders18 LT Busduct & Accessoriesa) Straight run per meter, TPN
1600A2500A3200A
b) 90 Deg. Bend (extra over & above straight run)1600A2500A3200A
c) Termination flexible -TPN set (extra over & above straight run)Copper1600A2500A3200AAluminium1600A2500A3200A
d) Adapter, TPN for equipment terminal connection1600A2500A3200A
PAGE 11 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
e) Phase cross over chamber 1600A2500A3200A
f) Busduct Supporting Structure per Tong) Expansion joint, TPN in the run of Busduct (extra over & above straight run)
1600A2500A3200A
19 Connection from PMCC/MCC panel to PMCC/MCC panel250A400A630A800A1000A1250A1600A2500A3200A
20 Cable Glands & Lugs: a) Single Compression Cable Glands for cable sizes:
2C X 2.5 Sq. mm. 3C X 2.5 Sq. mm. 5C X 2.5 Sq. mm. 7C X 2.5 Sq. mm. 12C X 2.5 Sq. mm. 16C X 2.5 Sq. mm. 2C X 10 Sq. mm. 2C X 16 Sq. mm. 2C X 25 Sq. mm. 2C X 35 Sq. mm. 3C X 2.5 Sq. mm. 3C X 10 Sq. mm. 3C X 16 Sq. mm. 3C X 25 Sq. mm. 3C X 35 Sq. mm. 3C X 50 Sq. mm. 3C X 70 Sq. mm. 3C X 95 Sq. mm. 3C X 150 Sq. mm. 3C X 185 Sq. mm. 3C X 240 Sq. mm. 3.5C X 300 Sq. mm. 3.5C X 240 Sq. mm. 3.5C X 185 Sq. mm. 3.5C X 95 Sq. mm. 4C X 16 Sq. mm. 4C X 35 Sq. mm. 1C X 35 Sq. mm.1C X 500 Sq. mm. 1C X 630 Sq. mm.
b) Double Compression Cable Glands for cable sizes:2C X 2.5 Sq. mm. 3C X 2.5 Sq. mm. 5C X 2.5 Sq. mm. 7C X 2.5 Sq. mm. 12C X 2.5 Sq. mm. 16C X 2.5 Sq. mm. 2C X 10 Sq. mm. 2C X 16 Sq. mm. 2C X 25 Sq. mm. 2C X 35 Sq. mm. 3C X 2.5 Sq. mm. 3C X 10 Sq. mm. 3C X 16 Sq. mm. 3C X 25 Sq. mm. 3C X 35 Sq. mm. 3C X 50 Sq. mm. 3C X 70 Sq. mm. 3C X 95 Sq. mm. 3C X 150 Sq. mm.
PAGE 12 OF 13
1 X 500 MW FG TPS (STAGE-IV)
LV SWITCHGEAR LT BUSDUCT NGR(PE-TS-401-506-E001, REV.0)
SCHEDULE OF UNIT PRICES FOR ADDITION / DELETION (OPTIONAL)
ANNEXURE-3H
SL.NO.
ITEM DESCRIPTION Unit Ex-works price
3C X 185 Sq. mm. 3C X 240 Sq. mm. 3.5C X 300 Sq. mm. 3.5C X 240 Sq. mm. 3.5C X 185 Sq. mm. 3.5C X 95 Sq. mm. 4C X 16 Sq. mm. 4C X 35 Sq. mm. 1C X 35 Sq. mm.1C X 500 Sq. mm. 1C X 630 Sq. mm.
c) Cable Lugs for sizes:2.5 Sq. mm. 10 Sq. mm. 16 Sq. mm. 25 Sq. mm. 35 Sq. mm. 50 Sq. mm. 70 Sq. mm. 95 Sq. mm. 150 Sq. mm. 185 Sq. mm. 240 Sq. mm. 300 Sq. mm. 500 Sq. mm. 630 Sq. mm.
d) FIBER OPTICAL CABLE (PER METER)21 Daily 8 hour rate deployed at site:
Engineer : (per day)22 Module Name plate23 Wires for Secondary wiring:a) 1.5 Sq. mm. per meterb) 2.5 Sq. mm. per meterc) 4.0 Sq. mm. per meter
24 Control Terminal for Secondary wiring suitable for cable size:a) 0.5 Sq. mm. b) 1.5 Sq. mm. c) 2.5 Sq. mm.
25 Unit price for following tests:a) Local Push Button Station - Degree of protection testb) Local motor Starter - Degree of protection testc) Type tests on NGRi) Heat run test on prototypeii) DOP test for IP 33iii) DOP test for IP 55c) Any other test as per IS / BHEL specification
26 LPBS TYPE-ALPBS TYPE-BLPBS TYPE-C
27 LOCAL MOTOR STARTERLOCAL MOTOR STARTERS 0.37 KWLOCAL MOTOR STARTERS 0.55 KWLOCAL MOTOR STARTERS 0.75 KWLOCAL MOTOR STARTERS 1.10 KWLOCAL MOTOR STARTERS 1.50 KWLOCAL MOTOR STARTERS 2.20 KWLOCAL MOTOR STARTERS 3.70 KWLOCAL MOTOR STARTERS 5.5 KW
28 ANY OTHER ITEM WHICH MAY BE REQUIRED FOR ADDITION / DELETION DURING DETAILED ENGINEERING
Note:Unit Rates as quoted in the Main supply schedule
PAGE 13 OF 13
1x 500MW FGUTPP STAGE IV
PRICE SCHEDULE FOR CABLING, EARTHING LIGHTNING PROTECTION SYSTEMS (SUPPLY)
Item.No Item Type TestTest Charges
(in Rs.)
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in INR
Total Supply and E&C in INR
1 TREFOIL CLAMPS Short Circuit Test (for fault levels and durations specified in the specification)
2 HT TERMINATION KITS Type Tests as per IS:13573 for 11 KV kitsType Tests as per IS:13573 for 3.3 KV kitsType Tests as per VDE 0278 for 3.3 KV kits
3 STRAIGHT THROUGH JOINTING KITS Type Tests as per IS:13573 for 11 KV kitsType Tests as per IS:13573 for 3.3 KV kitsType Tests as per VDE 0278 for 3.3 KV kits
4 JUNCTION BOXImpact resistance for impact energy of 2 Joules (IK07)as per BS EN50102Thermal ageing at 70deg C for 96 hours as per IEC60068-2-2Bb.Class of protection ( IP 55)HV test.
ANNEXURE-4B: TYPE TEST CHARGES (OPTIONAL)
A TYPE TEST FOR TYPE-A FIRE SEALING SYSTEM(OPTIONAL)TYPE TEST UNIT Unit Price in INR Total Price in INR Excise Duty @ on self
manufactured onlyVAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on Total Price in INR
Total Price including Service Tax
in INR
1Accelerated Ageing Test
LOT
2Water Absorption Test
LOT
3 Fire Rating Test LOT4 Hose Stream Test LOT5
Vibration Test Followed by Fire rating TestLOT
B TYPE TEST FOR TYPE-B FIRE SEALING SYSTEM(OPTIONAL)TYPE TEST UNIT Unit Price in INR Total Price in INR Excise Duty @ on self
manufactured onlyVAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on Total Price in INR
Total Price including Service Tax in INR
1 Accelerated Ageing Test LOT
2 Water Absorption Test LOT
3 Fire Rating Test LOT
4 Hose Stream Test LOT
5Vibration Test Followed by Fire rating Test
LOT
Notes:‐
1 For Type Tests refer clause no. 6.0 of Section‐C of Part ‐B of specification
FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)
ANNEXURE- 5B
PRICE SCHEDULE FOR TYPE TEST OF FIRE SEALING SYSTEM (OPTIONAL)
s.no. CIVIL WORKS(OPTIONAL)
DESCRIPTION UNIT Unit Price in INR Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
Service tax @ including cess on Unit Price in INR
Unit Price including Service
Tax in INR
a ENLARGEMENT OF PENETRATION AREA IN
SQM
a1 BRICK WALL SQMa2 CONCRETE WALL SQMa3 FLOORS SQMb REDUCTION OF PENETRATION
AREA INb1 BRICK WALL SQMb2 CONCRETE WALL SQMb3 FLOORS SQM
Notes-
1Unit rates for civil works shall be as per clause no. 8.3 (e) of Section-D of Part-B of specification.
FEROZ GANDHI UNCHAHAR TPPSTAGE-IV( 1 X 500MW)
ANNEXURE- 5B
PRICE SCHEDULE FOR CIVIL WORKS OF FIRE SEALING SYSTEM (OPTIONAL)
Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on
self manufactur
ed only
VAT/CST @ … in INR on
self manufactur
ed only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection & Commissio
ning Charges
INR
Service tax @ including cess on E & C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C in INR
(B) OPTIONAL ITEMS1.0
O & M SPARES FOR 220V BATTERY(BIDDER TOFURNISH THE LIST)
LOT 1
2.0
INCREMENTAL INCREASE/DECREASE IN BATTERY RATING*
*Unit rate of additional price applicable for battery charger capacity increase/decrease by 10AH
NOS 1
3.0SUPERVISION CHARGES OF COMMISSIONING OF220V DC BATTERY)
LOT 1
4.0SUPERVISION CHARGES OF ERECTION &COMMISSIONING OF 220V DC BATTERY) SET 1
5.0 SUPV. OF E & C- MANDAY RATE SET 1
6.0 SUPV. OF E & C- TRAVEL CHARGE SET 1
7.0 TYPE TEST
a DISCHARGE PERFORMANCE AT LOW TEMPERETURE LOT 1
b LIFE CYCLE TEST LOT 1
c AIR PRESSURE TEST LOT 1
d VARIFICATION OF CONSTRUCTIONAL REQUIREMENT LOT 1
e ENVIRONMENTAL TEST LOT 1
f INSUALATION RESISTANCE TEST LOT 1
Note: Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering.
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9BBOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (NI-CD Battery)
Page 1 of 1
Sr. No. Item code Item Description Unit Quantity Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR (6+7+8+9)
Total Erection & Commissioning Charges INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax (11+12) in INR
Total Supply and E&C in INR
(B) OPTIONAL ITEMS1.0
O & M SPARES FOR 220V BATTERY(BIDDER TOFURNISH THE LIST) LOT 1
2.0
INCREMENTAL INCREASE/DECREASE IN BATTERY RATING*
*Unit rate of additional price applicable for battery charger capacity increase/decrease by 10AH
NOS 1
3.0 SUPERVISION CHARGES OF COMMISSIONING OF220V DC BATTERY)
LOT 1
4.0SUPERVISION CHARGES OF ERECTION &COMMISSIONING OF 220V DC BATTERY) SET 1
5.0 SUPV. OF E & C- MANDAY RATE SET 1
6.0 SUPV. OF E & C- TRAVEL CHARGE SET 1
7.0 TYPE TEST
aTEST FOR CAPACITY- TEST FOR VOLTAGE DURING DISCHJARGE
LOT 1
d TEST FOR CHARGE RETENTION/ LOSS OF CAPACITY LOT 1
c AMPERE HOUR AND WATT-HOUR EFFICIENCY TEST LOT 1
d ENDURANCE TEST. LOT 1
Note: Cable Lugs at Battery terminals shall be in bidders Scope & Same shall be informed during detailed engineering.
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE-9BBOQ-cum-PRICE SCHEDULE FOR 220V DC BATTERY (LEAD -ACID PLANTE)
Page 1 of 1
FEROZ GANDHI UNCHAHAR TPP STAGE-IV( 1 X 500MW) ANNEXURE 9C
Sr. No. Item Description Unit QuantityRemarks
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed
in INR/Total Price.
Excise Duty @ on
self manufactur
ed only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service
Tax in INR
Total Supply and E&C in INR
OPTIONAL ITEMS
1INCREMENTAL INCREASE/DECREASE IN CHARGER RATING*
NOS 1*Unit rate of additional price applicable for battery charger capacity increase/decrease by 20A
2INCREMENTAL INCREASE/ DECREASE IN DISCH RESISTOR RATING*
NOS 1*Unit rate of additional price applicable for discharge resistor capacity increase/decrease by 20A
3SUPERVISION OF COMMISSIONING SET 1
Supervision of commissioning activities of 220V DC & Float cum-Boost charger
4 SUPV.OF E&C SET 1 Supervision of E & C activities of 220V DC Float-cum-Boost charger
BOQ CUM UNPRICED PRICE SCHEDULE FOR SUPPLY OF 220V DC BATTERY CHARGER
CABLE GLANDS AND LUGS AT CHARGER AND FUSE BOX END SHALL BE IN BIDDERS SCOPE. TENTATIVE CABLE SIZE ARE MENTIONED IN DATASHEET-A. NOTE:
SL.NO. ITEM QTY. Unit Price in INR Total Price in INR Excise Duty @ on self
manufactured onlyVAT/CST @ … in INR on self
manufactured onlyFreight including
Service tax @Total FOR Site Price (Supply) in
INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on Total Price in INR
Total Price including Service Tax in INR
Training of Engineers:
(Optional)
a) Basic cost [irrespective of no. of engineers]
b) Additional variable cost per engineer
ANNEXURE 10Training for GCB
7 1 Set
ANNEXURE-11A
Item DESCRIPTION QTY. UnitUNIT RATE ITEMS
1 Main distribution frame (MDF) 200 pairs 1 No.
2 Sub-distribution frame (SDF) 30 pairs 1 No.
3 Signal line booster unit [housed in FRP enclosure] 1 No.
4 Loud Speaker junction box 1 No.
5 Junction box (Die cast Al material) 1 No.
6 Master control station junction box 1 No.
7 Looping junction 1 No.
8 Flameproof field call station with handset 4 W cone type speaker. 1 No.
9 Flameproof field call station with handset 15 W horn type speaker. 1 No.
10 Power supply unit [48V DC] 1 No.
11 Wall/column mounted, weatherproof field call station with hand freemicrophone & speaker and built-in power amplifier
1 No.
12 Sound protecting booth 1 No.
Service tax @ including cess
on E & C in INR
Total E & C prices including Service Tax in
INR
SUPPLY (Rs)
Total Ex-Works Price duly packed in
INR/Total Price.
Unit Ex-works price/Unit Price
Excise Duty @ on self
manufactured only
1 X 500 MW FGUTPP STAGE-IV - Price Schedule Optional Items for Public Address System
Total Supply and E&C in
INR
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges INR
ANNEXURE-11A
Item No. DESCRIPTION QTY. Unit
TYPE TESTS
1.0 All type tests as per relevant standard shall be conducted on one piece of the following items:
1.1 Amplifier, as per IS-9302 Part-II 1 No.1.2 Microphone, as per IS-9302 Part-III 1 No.
1.3 Loudspeaker, as per IS-9302 Part-IV 1 No.
2.0 All type tests as per relevant standard shall be conducted on one piece of all solid state equipment/systems:
2.1Surge protections test
1 No.
2.2 Dry heat test as per IEC-68-2-2 1 No.
2.3 Damp heat test as per IEC-68-3 1 No.2.4 Vibration test as per IEC-68-2-6 1 No.2 5 1 N
1 X 500 MW FGUTPP STAGE-IV - Price Schedule Type Test for Public Address System[OPTIONAL]
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufactured
only
Freight including
Service tax @
TYPE TEST CHARGES
in INR
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including
cess in INR
Total Charges including
Service Tax in INR
Unit Ex-works price/Unit
Price
Total Ex-Works Price duly packed in INR/Total
Price.
2.5 Electrostatic discharge test as per IEC-801-2 or equivalent 1 No.2.6 Radio frequency immunity test as per IEC-801-6 or equivalent 1 No.2.7 Electromagnetic immunity test as per IEC-801-3 or equivalent 1 No.
NOTE:1. Bidder to indicate lump sum charges for conducting all type tests as per relevant standard on one piece.
ANNEXURE-11A
Sl No. DESCRIPTION QTY. Unit RemarksRECOMMENDED SPARES
1 Recommended spares for 3 years * ** Nos.
* Bidder to furnish the list** Bidder to furnish the quantity
Total Supply and E&C in
INR
Total Ex-Works Price duly packed in INR/Total Price.
Unit Ex-works price/Unit Price
Excise Duty including cess @ ……Rs
VAT/CST @ … in INR on self manufactured
only
1 X 500 MW FGUTPP STAGE-IV- Price Schedule Recommended Spares for Public Address System [OPTIONAL]
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
ANNEXURE-11A
Sl No. DESCRIPTION SUPERVISION CHARGES
1 Charges for erection supervision, testing & commissioning for complete PA system. [Instruments required for testing & commissioning shall be arranged by the bidder].
Unit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Freight including
Service tax @
1 X 500 MW FGUTPP STAGE-IV - Price Schedule supervision charges for Public Address System[OPTIONAL]
Total FOR Site Price
(Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service Tax in
INR
NOTE:1. Lump sum charges quoted by the bidder shall be firm irrespective of variation in the supply BOQ of main equipment during the contract.
ANNEXURE-11A
Item No. DESCRIPTION UOM Lump sum charges (Rs)
Training of Engineers:
(Optional)
a) Basic cost [irrespective of no. of engineers]
b) Additional variable cost per engineer
1 Set
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
1 X 500 MW FGUTPP STAGE-IV - Price Schedule Training requirement for Public Address System (Optional)
Service tax @ including cess in
INR
Total Charges including Service Tax
in INR
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges INR
1
B. OPTIONAL ITEM
S.No Description Unit Qty
Unit Ex-works
price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on
self manufacture
d only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess on E &
C in INR
Total E & C prices
including Service Tax
in INR
Total Supply and E&C in
INR
I 3.3/0.433KV Indoor Transformer
(Dry Type)
1 2.5 MVA,3.3/0.433KV Indoor
Transformers (Dry Type)
Nos 2
II Mandatory Spares
1 For above 3.3/0.433KV 2.5 MVA
Transformer
1.1 HV Bushing Nos 1
1.2 LV Bushing Nos 1
1.3 LV Neutral Nos 1
1.4 Complete Winding Limb (HV and LV) Nos 1
1.5 WTI Nos 1
1.6 Set of Thermistor / RTD with
associated leads complete for one
transformer
Nos 1
SL. NO.
DESCRIPTION
Unit Price
Total Ex-Works
Price duly packed in INR/Total
Price.
Excise Duty @ on self
manufactured only
Freight including
Service tax @
Total FOR Site Price
(Supply) in INR
Total Erection &
Commissioning Charges
INR
Service tax @ including cess in INR
Total Price including
Service Tax in INR
1 SHORT CIRCUIT TEST
2 NOISE LEVEL MEASUREMENT
3MEASUREMENT OF ZERO PHASE
SEQUENCE IMPEDANCE
4 MEASUREMENT OF THE
HARMINICS OF NO LOAD
CURRENT
5 TEMPERATURE RISE
6LIGHTING IMPULSE VOLTAGE
TEST ON ALL THE THREE LIMBS
AS PER CL. 14.1 OF IEC 60076‐3
7 DEGREE OF PROTECTION TEST
ON MARSHALLING BOX, CABLE
BOX AND ENCLOSURE.
i). SUPPLY ITEMS
ii). TYPE TEST FOR 2.0/2.5 MVA,3.3/0.433KV Indoor Transformers (Dry Type).
Note: Transformer shall be short circuited tested after conducting the routine tests. Rest of the type tests shall be conducted after successful short circuit testing.
Annexure‐12 (Price Schedule/BOM ofDry Type Transformer)
Bill of quantity of Erection and commissioning of Dry Type Transformers B. OPTIONAL ITEM
S.No Description Unit Qty
Unit Erection & Commissioning Charges in INR
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty including cess
@ ……Rs
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self manufactured
only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissioning Charges in INR
Service tax @ including cess
on E & C in INR
Total E & C prices including Service Tax in
INR
1 2.5 MVA,3.3/0.433 kV
Indoor Transformers
(Dry Type)
Nos 2
i). SUPPLY ITEMS
1X500 MW UNCHAHAR FGTPS (UNIT‐6) RECOMMENNDED O SPARES FOR AUXILARY SERVICE TRANSFORMER(OIL FILLED) (OPTIONAL) ANNEXURE‐13E
RATING(A) BOARD NO.
56RECOMMENDED O & M SPARES for
3years OperationNOS. 1 BIDDER TO FURNISH
Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in
INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in INR on self
manufactured only
Total Supply and E&C in
INRSr.No. ITEM NAME UOM TOTAL QTY.
REMARKS Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection &
Commissioning Charges INR
Service tax @ including cess
on E & C in INR
Total E & C prices
including Service Tax in
INR
PAGE 1 OF 4
Sl.no. DESCRIPTION UNIT Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total
Price.
Excise Duty @ on self manufactured only
VAT/CST @ … in INR on self manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning Charges
INR
Service tax @ including cess on E & C in INR
Total E & C prices including Service Tax in
INR
Total Supply and E&C in INR
1Desktop/Wall mounted Push button operated decadic type Telephone Set
Nos
2 PVC & Jelly filled Cables Meter
Optional prices for EPABX system
DESCRIPTION UNIT QTY Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self
manufactured only
VAT/CST @ … in
INR on self manufactu
red only
Freight including
Service tax @
Total FOR Site Price (Supply)
in INR
Total Erection & Commissi
oning Charges
INR
Service tax @
including cess on E & C in INR
Total E & C prices
including Service
Tax in INR
Total Supply
and E&C in INR
11kV, 3150A LENGTH METER 5090 deg Bend NOS. 8
TRANSFORMER TERMINATIONS NOS. 1
SWITCHGEAR TERMINATIONS NOS. 1
TEE CONNECTION NOS. 0
WALL FRAME ASSEMBLY NOS. 1TOTAL PRICE 11kV, 2750A LENGTH METER 13090 deg Bend NOS. 22
TRANSFORMER TERMINATIONS NOS. 2
SWITCHGEAR TERMINATIONS NOS. 5
TEE CONNECTION NOS. 1
WALL FRAME ASSEMBLY NOS. 2TOTAL PRICE 3.3kV, 3000A LENGTH METER 9090 deg Bend NOS. 12TRANSFORMER TERMINATIONS NOS. 2SWITCHGEAR TERMINATIONS NOS. 4WALL FRAME ASSEMBLY NOS. 2TOTAL PRICE 3.3kV, 2500A LENGTH METER 4090 deg Bend NOS. 4TRANSFORMER TERMINATIONS NOS. 2SWITCHGEAR TERMINATIONS NOS. 2WALL FRAME ASSEMBLY NOS. 2TOTAL PRICE Supporting structure (hot dip galvanized MS), foundation channels, hardware etc. Suitable for bus ductelevation and length involved.
As required forcomplete scope
BOQ CUM UNPRICED SCHEDULE OF 11KV & 3.3KV SEGRAGATED PHASE BUSDUCT (OPTIONAL)
ANNEXURE-1
Unit rates quoted here shall be used for any addition /deletion during detail engineering.
SL NO ITEM DESCRIPTION UNIT QTY Unit Ex-works price/Unit Price
Total Ex-Works Price duly packed in INR/Total Price.
Excise Duty @ on self manufactured
only
VAT/CST @ … in INR on self
manufactured only
Freight including Service tax @
Total FOR Site Price (Supply) in INR
Total Erection & Commissioning
Charges INR
Service tax @ including cess on E
& C in INR
Total E & C prices including Service
Tax in INR
SEGREGATED PHASE BUS DUCT
Transportation from stores / storage yardto erection site, assembly, erection,welding, testing & commissioning ofSegregated Phase Bus Duct forinterconnection of Unit/StationTransformers to 11kV Switch Boards
2750ASPBD from Unit Transformers to 11 kV UnitSwitch BoardSPBD for interconnection of 11kV Unit Switchboard to 11 kV Station Switch Board (Approx. total length 150 Mtr)
3150ASPBD from Station Transformer to 11 kVStation Switch Board (Approx. total length 60 Mtr)
3000ASPBD from Unit Aux. Transformer to 3.3 kVSwitch Board Approx. Total length 100 Mtr
2500ASPBD from Misc Transformer to 3.3 kV SwitchBoard Approx. Total length 50 Mtr
Unit rates quoted here shall be used for any addition /deletion during detail engineering.
3 SET 3
1
Annexure-1Bill of quantity of Erection and commissioning (OPTIONAL)
1 SET 5
2 SET
4 SET 2
TITLE: 1 X 500 MW UNCHAHAR TPP STAGE-IV
TECHNICAL SPECIFICATION FOR
ELECTRIC HOIST AND MANUAL HOIST
SPECIFICATION NO. PE-TS-404-xxx-xxx
VOLUME - I
SECTION - C1(Mech) SUB SECTION - II
REV.NO. 0 DATE :
SHEET
ANNEXURE IV
1.1.0 ELECTRIC HOIST AND MANUAL HOIST (CHAIN PULLEY BLOCK)
Required number of electric hoist / manual hoist of adequate capacity, to meet the erection and maintenance requirements are to be provided for the various areas. Manual hoists (hand operated) shall be designed to duty class 2 as per IS 3832 and electric wire rope hoist shall be designed as per lS: 3938 (latest). The stipulations of all statutory codes like Indian Electricity Act, Indian Electricity Rules, Factory Acts, Local Municipality act etc. shall however prevail over the specification requirements, in case any conflict arises between this specification and the statutory codes. Maintenance tools and tackles shall be as per data sheet attached. DESIGN CRITERIA For the hoists with more than 2.0 tonne lifting capacity or more than 10.0 M lift, Electrical hoist shall be provided. Other hoist blocks shall be of hand operated type for both travel and lift. However, all monorails coming out of the building shall be provided with electric hoist block, irrespective of load and lift. Capacity of electric and manual (Chain pulley block) hoists shall be decided keeping 25% margin over equipment to be handled. For hand operated hoists, the hoists shall be suitable for operation from floor level. Hand chain shall be provided for long travel of trolley and the Hoisting mechanism. The operator shall be able to control the movement of the electrical/ manual hoist with the help of floor operated pendant
MINIMUM LIFTING REQUIREMENT
S.N. AREA DESCRIPTION QTY(nos) CAPACITY(T) TYPE 1 ESP control room ( below
16.7 m)
1 5T
Electric hoist
2 Boiler MCC Room 1 3T Electric hoist 3 MV Switchgear Room 1 2T Manual Hoist
Note; 1. Area, type, capacity mentioned are minimum requirement and any additional requirement shall be
finalised during detail engineering without any commercial implication 2. Travel and Lift are layout dependent and shall be finalised during detail engineering without any
commercial implication 3. Additional electric/manual hoist required during detail engineering shall be provided as per design